PRACTICAL GUIDE. Low-voltage power systems Protection against overvoltages

Size: px
Start display at page:

Download "PRACTICAL GUIDE. Low-voltage power systems Protection against overvoltages"

Transcription

1 PRACTICAL GUIDE Low-voltage power systems Protection against overvoltages

2 Introduction Overvoltage Since the 1960s, the purely technical term EMC (electromagnetic compatibility) has become a term comprising not only safety for appliances and components, but in particular, for their users. Apart from others, it refers to the resistance of devices and equipment to all forms of electromagnetic disturbance, including impulse overvoltage and high frequency disturbance. It is thus the suppliers who must increase the resistance of systems today. A correctly designed and installed system of surge protective devices and SALTEK filters can satisfy even the most demanding requirements for the safety of equipment in terms of electromagnetic compatibility. The current standard of technology offers good protection for electronic and electrical equipment against the effects of dangerous impulse overvoltage, i.e., surge arresters. Equipment can be protected not only against the effects of a destructive impulse that features great energy, but also against the effects of high frequency disturbances. Unprotected electrical wiring, computer and data networks always pose a huge risk for their users. Installing overvoltage protection devices therefore prevents possible damage. The price of surge arresters is oniy a tiny part of the cost expended on protected equipment and a negligible amount compa to the potential damage resulting from a failure or destruction of the technological equipment followed by financial losses. SALTEK surge arresters are complied Czech and inter- national standards. Overvoltage types Basically, overvoltage can be classed according to its duration. Transient overvoltage short-term changes in voltage: overvoltage that lasts a short time not exceeding several thousandths of a second, oscillating or non-oscillating, usually highly damped, in hunds of microseconds (see Fig. 1a) such overvoltage can be successfully eliminated using an SPD. Temporary overvoltage long-term changes in voltage: overvoltage with industrial frequency of oscillation and a relatively long duration in milliseconds or less (see Fig. 1b) such overvoltage cannot be eliminated by means of an SPD. Fig. 1a Overvoltage caused by lightning Transient overvoltage Switching overvoltage 230 V, 50 Hz Fig. 1b Temporary overvoltage Electronic components damaged by overvoltage Overvoltage 230 V, 50 Hz 2

3 Practical Guide - Low-voltage power systems Short-term changes in voltage, i.e. transient overvoltage can be classed in several groups according to the origin: differential mode of overvoltage: overvoltage between live conductors (L1-L2, L-N with LV supply, a-b with telecommunications ), such overvoltage occurs as a result of technological events e.g. switching of non-linear loads (motors, refrigerators,...). These are particularly dangerous for electronic equipment, sensitive hardware-like control systems, computers and their software utilities, etc. (see Fig. 2) common mode of overvoltage: overvoltage between the neutral conductor and earthing conductor (L-PE, N-PE in LV, a/b-pe in telecommunications ) that results from atmospheric events a lightning strike. Such overvoltages are particularly dangerous for technology, the frame of which is earthed (insulation breakdown). (see Fig. 3) An SPD in the supply network will be selected according to the type of respective overvoltage. L N Fig. 2 Fig. 3 L N Differential mode (switching) of overvoltage Common mode (lightning) of overvoltagee Overvoltage wave parameters Fig. 4 Impulse front time Impulse tail time 50 10/350 μs i (ka) t (μs) Test impulse 10/350 µs simulates a lightning strike and SPD type 1 and SPD type 1+2 are tested according to it 3

4 Fig /20 μs Protection of technology against overvoltage i (ka) 25 The principle of surge protective devices is based on the equipotential bonding. This is conditioned by the effective equalising potential in the whole building. It is only possible if the whole building is thoroughly provided with equipotential bonding and it should be connected to the earthing electrode t (μs) If a building features external lightning protection (LPS), both the down conductor as well as the protective conductor of the supply network should be connected to the earthing conductor. This is shown in the following chapter. Test impulse 8/20 µs simulates technological overvoltage and SPD type 2 and SPD type 3 are tested according to it. Fig. 6 Zkušební proudové vlny 10/350 μs a 8/20 μs I sn (ka) 8/20 µs Lightning arresters SPD type 1 10/350 µs Surge arresters SPD type 2 Surge arresters SPD type 2 Comparison of the energy of testing impulses 10/350 µs and 8/20 µs Supply networks SPD connection principles on how to connect SPDs An SPD in power supply networks should be connected in two connection modes mode x+0 and mode x+1. The x+0 connection mode is designated 3+0 (TN-C) or 4+0 (TN-S) for three-phase power supply and 1+0 (TN-C) or 2+0 (TN-S) for single-phase power supply. Such mode is benefi cial in eliminating common mode of overvoltage. The x+1 connection mode is designated 3+1 for three-phase power supply and 1+1 for single-phase power supply. It cannot be used in the TN-C supply network. It is advantageous to use it to eliminate differential mode of overvoltage. 4

5 Practical Guide - Low-voltage power systems TN-S system An SPD type 1 or SPD type 1 and 2 should be located at the incoming supply to the building (mostly in the main distribution board). These SPDs are mainly intended to restrict lightning electromagnetic impulses (lightning strikes) and therefore are installed in the x+0 design, i.e., all live conductors (L1, L2, L3 and N) against ground (PE). An SPD type 2 should be located in a subsidiary distribution board. In such supply networks, an SPD type 2 can either be connected in the x + 0 mode (to eliminate longitudinal lightning electromagnetic impulse) or in the x + 1 mode (to restrict overvoltage in the equipment). An SPD type 3 is always mounted close to the equipment to be protected. TN-C-S system In a TN-C-S supply network, the SPD located before the point from which the PEN conductor separates to the N and PE conductors should always be connected in the x+0 mode. Behind the point of separation, an SPD type 2 can be connected in both x+1 mode or x+0, with the same principle to be followed as in a TN-S network, i.e., such type of connection should be chosen to better suit the respective situation. In a TN-S supply network, connection of a type 2 SPD must follow the type of overvoltage that will prevail in the supply network. Consequently, in industrial operations, where a great number of switching overvoltage occurs, it is more advantageous to connect an SPD type 2 in the x + 1 mode, while in administrative and residential buildings it is better to connect an SPD type 2 in the x + 0 mode. Fig. 7 L1 L2 L3 N PE LPZ 0 SPD type 1 or 1+2 LPZ 1 SPD type 2 LPZ 2 SPD type 2 LPZ 2 Main distribution board Subsidiary distribution board (1) Subsidiary distribution board (2) Origin of the installation F1 RCD SPD type 3 Fine protection 16 A 16 A 63 A *F2 *F3 *F4 External lightning protection Main earthing bonding bar Local earthing bonding bar Local earthing bonding bar * Additional protection of SPD see page 7 Equipment (technology) TN-S system Fig. 8 L1 L2 L3 L1 L2 PEN L3 PEN F1 LPZ 0 SPD type 1 or 1+2 LPZ 1 LPZ 2 SPD type 2 LPZ 2 Main distribution board Subsidiary distribution board (2) Origin of the installation F1 *F2 N PE N PE SPD type 2 Subsidiary distribution board (1) *F3 *F4 RCD RCD 16 A SPD type 3 16 A Fine protection 63 A A 63 A *F2 *F3 *F4 External lightning protection Main earthing bonding bar Local earthing bonding bar Local earthing bonding bar * Additional protection of SPD see page 7 Equipment (technology) TN-C-S system L1 L2 L3 F1 16 A 16 A 63 A 16 Jemná ochrana 5

6 RCD 16 A 63 A L1 F1 TN-C system L2 In a TN-C L3 supply network, an SPD can only be connected in the x+0 mode. In an SPD type 3, manufactu N in the x+1 connection PEN mode, the N conductor (blue) as well PE as the PE conductor (yellow-green) should always be connected to the *F2 PEN conductor. *F3 *F3 *F4 TT system 16 A For a TT supply network, in which only neutral conductors 63 A L1, L2, L3 are routed from the power source, all levels of SPD should always be connected in the x+1 mode. *F4 RCD 16 A obr. 9 L1 L2 L3 LPZ 0 SPD type 1 or 1+2 LPZ 1 LPZ 2 Main distribution board Origin of the installation F1 SPD type 2 Subsidiary distribution board SPD type 3 Fine protection 16 A 16 A 63 A PEN L1 L2 L3 External lightning protection PEN F1 *F2 *F2 Main earthing bonding bar *F3 *F3 Local earthing bonding bar 16 A 16 A 63 A * Additional protection of SPD see page 7 Equipment (technology) TN-C system obr. 10 L1 L2 L3 N překlad LPZ 0 SPD type 1 or 1+2 LPZ 1 SPD type 2 LPZ 2 Origin of the installation Main distribution board Subsidiary distribution board F1 *F2 PE RCD 16 A * 16 předjišťování A SPD viz str A SPD type 3 Fine protection External lightning protection *F2 Main earthing bonding bar *F3 Local earthing bonding bar * Additional protection of SPD see page 7 Equipment (technology) TT system 6

7 Practical Guide - Low-voltage power systems Principle of overcurrent protection of SPD For overcurrent protection of SPD it is important to consider whether we should follow the protection priority principle, which is used in most installations, or the power supply priority principle. a) protection priority principle an SPD should be provided with additional protection in this case only if the value of the line protection (F1 fuse) is higher than the value of the respective SPD shown in the catalogue (F2 fuse) and the SPD protection always has the value shown in the manufacturer s catalogue (parameter maximum additional protection). An example of back-up fuse for SPD FLP-B+C MAXI V in different supply networks. The catalogue value of maximum back-up fuse for FLP-B+C MAXI V is 250 A, and 125 A for the V connection. 1 TN-C Parallel connection V (series) connection F1 125 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A F1 > 250 A F2 F1 250 A F2 F1 > 125 A F1 125 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A 2 TN-C-S F1 125 A N PE N PE FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A F1 > 250 A F2 F1 250 A F2 F1 > 125 A F1 125 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A 3 TN-S F1 125 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A F1 > 250 A F2 F1 250 A F2 F1 > 125 A F1 125 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A FLP-B+C MAXI V červená U c: 260 V~ I imp: 25 ka I n: 30 ka I max: 60 ka U p: < 1,5 kv 250 A 7

8 b) supply priority principle an SPD should always be provided with a back-up fuse in this case, i.e., there are always both F1 and F2 fuses. The value of the SPD back-up (F2 fuse) must be calculated in this case according to the principle of protection selectivity, whereas the value should never be higher than the value specified in the manufacturer s catalogue. Should the calculation show a higher value than that shown in the catalogue, then the value of the SPD back-up fuse is the same as that in the manufacturer s catalogue. Should the value of the SPD back-up be lower than that shown in the catalogue, the whole installation (i.e., the SPD back-up and the SPD itself) should be provided with at least another protection installation next to the original one, as indicated in the example below. An example of additional SPD protection - FLP-12,5 V- in different supply networks. The catalogue value of the maximum back-up for FLP-12,5 V is F2 = 160 A. F2 the value of the SPD back-up established by the calculation 1 TN-C F1 > 160 A F1 F2 = 160 A F2' F2' L3 L2 L1 L1 L2 L3 F2' 160 A F2 F2' < 160 A F2' L3 L2 L1 L1 L2 L3 L3 L2 L1 L1 L2 L3 PEN PEN PEN PEN PEN PEN 2 TN-C-S F1 > 160 A F1 N N PE PE F2 = 160 A F2' F2' L3 L2 L1 L1 L2 L3 F2' 160 A F2 F2' < 160 A F2' PEN TN-S F1 > 160 A F1 F2 = 160 A F2' F2' L1 L2 L3 N F2' 160 A F2 F2' < 160 A F2' PE PE PE N L3 L2 L1 N L3 L2 L1 L1 L2 L3 N L1 L2 L3 N PE PE PE N L3 L2 L1 PEN L3 L2 L1 L3 L2 L1 L1 L2 L3 L1 L2 L3 PEN PEN PEN PEN 3 8

9 Practical Guide - Low-voltage power systems SPD dimensioning Only the SPD type 1 should be dimensioned. Dimensioning of the SPD type 1 should be based on the calculation of the lightning protection level (LPL) for the lightning protection system (LPS). The table from CLC/TS below shows minimum values of the discharge lightning strike current to the pole considering the lightning protection (LPL) class of the building for the SPD type 1. If the LPL value is not known, the worse scenario is anticipated Low voltage networks Table 1 LPL 1 or unknown Maximum current corresponding to LPL 200 ka ka 3 or ka Number of conductors (n) TT TN-C TN-S IT without neutral conductor Connection mode Connection mode Connection mode IT with neutral conductor C C C C C C L-PE N-PE L-N N-PE L-PEN L-PE N-PE L-N N-PE L-PE L-N N-PE I imp (ka) 5 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 33,3 33,3 66,7 33,3 N/A N/A N/A N/A N/A N/A I imp (ka) 5 N/A N/A N/A N/A 15,0 15,0 60,0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 25,0 25,0 50,0 25,0 N/A N/A N/A N/A N/A N/A I imp (ka) 5 N/A N/A N/A N/A 10,0 10,0 40,0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Note: C SPD connected in the x+0 mode; C SPD connected in the x+1 mode C TN-C C TN-S C 9

10 Selection of SPD at the incoming supply to the building For selection of the SPD type 1 at the incoming supply to the building we use the table for SPD type 1 dimensioning (see table 1). At the same time, it is necessary to consider the specifi c situation. Even if the calculation made according to the previous table shows that the Impulse current of SPD type 1 may be, for example, 12.5 ka in a 10/350 µs wave and the building is fed by external cabling, then the probability of a lightning strike in the outdoor line is high and the SPD type 1 would be under-dimensioned. Variants of SPD applications are shown in the following examples: Situation Solution A house with LPS, earthed antenna, or metallic roof, etc. SPD type 1 SPD type 2 A house with an overhead line SPD type 1 SPD type 2 A house with earthed metallic parts or LPS nearby SPD type 1 SPD type 2 1 A family house in a built-up area or a detached structure with or without LPS and overhead line DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 TN-C FLP-12,5 V/3 TN-C-S FLP-12,5 V/3 TN-S FLP-12,5 V/4 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 10

11 Practical Guide - Low-voltage power systems 2 A detached family house with or without LPS, with a underground cable connection DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 TN-C FLP-12,5 V/3 TN-C-S FLP-12,5 V/3 TN-S FLP-12,5 V/4 3 A family house in a built-up area without LPS and with a underground cable connection DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 TN-C FLP-12,5 V/3 TN-C-S FLP-12,5 V/3 TN-S FLP-12,5 V/4 TN-C FLP-12,5 V/3 TN-C-S FLP-12,5 V/3 TN-S FLP-12,5 V/4 11

12 4 Terrace houses with a common LPS and overhead line DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 5 Terrace houses with a common LPS and a underground cable connection DA-275 A CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 TN-C FLP-12,5 V/3 TN-C-S FLP-12,5 V/3 TN-S FLP-12,5 V/4 12

13 Practical Guide - Low-voltage power systems 6 Blocks of flats with a underground cable connection without the possibility to install an SPD type 1 upstream of power meter TN-C FLP-12,5 V/1 TN-C-S FLP-12,5 V/1 TN-S FLP-12,5 V/2 TN-C FLP-12,5 V/3 TN-C-S FLP-12,5 V/3 TN-S FLP-12,5 V/4 CZ-275 A DA-275 A TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 7 Blocks of flats with a underground cable connection with the possibility to install an SPD type 1 upstream of power meter TN-C SLP-275 V/1 TN-C-S SLP-275 V/1 TN-S SLP-275 V/1+1 or SLP-275 V/2 TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 CZ-275 A DA-275 A TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 13

14 8 Administrative building DA-275 A or CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/3+1 or SLP-275 V/4 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 14

15 Practical Guide - Low-voltage power systems 9 A commercial building or or a TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 TN-C FLP-25--V(S)/3 TN-C-S FLP-25--V(S)/3 TN-S FLP-25--V(S)/4 TN-C 3 pce. FLP-SG50 V(S)/1 TN-C-S 3 pce. FLP-SG50 V(S)/1 TN-S 4 pce. FLP-SG50 V(S)/1 TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/4 10 A commercial building of special importance TN-C 3 pce. FLP-SG50 V(S)/1 TN-C-S 3 pce. FLP-SG50 V(S)/1 TN-S 4 pce. FLP-SG50 V(S)/1 15

16 11 Administrative and commercial premises DA-275 A or TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/4 TN-S DA-275 DF16 CZ-275 A TN-C SLP-275 V/3 TN-C-S SLP-275 V/3 TN-S SLP-275 V/4 TN-S DA-275 DF25 TN-S SLP-275 V/3+1 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 TN-S DA-275 V/3+1 16

17 Practical Guide - Low-voltage power systems TN-S SLP-275 V/3+1 TN-S DA-275 DF25 TN-S SLP-275 V/3+1 TN-S DA-275 DF16 TN-C 3 pce. FLP-SG50 V(S)/1 TN-C-S 3 pce. FLP-SG50 V(S)/1 TN-S 4 pce. FLP-SG50 V(S)/1 TN-S DA-275 V/3+1 TN-S FLP-12,5 V/3+1 17

18 12 A building with LPS and air conditioner or heating cables in gutters TN-C FLP-12,5 V/1 TN-C-S FLP-12,5 V/1 TN-S FLP-12,5 V/2 TN-C FLP-B+C MAXI V(S)/3 TN-C-S FLP-B+C MAXI V(S)/3 TN-S FLP-B+C MAXI V(S)/4 DA-275 A or CZ-275 A 13 A house with a single-phase power supply and LPS (LPL I) 1 Double- 2 -conductor supply Three- -conductor supply TN-C 1 pce. FLP-SG50 V(S)/1 TN-C-S 1 pce. FLP-SG50 V(S)/1 TN-S 2 pce. FLP-A35 18

19 Practical Guide - Low-voltage power systems Reducing overvoltage in LPZ zones The principle of ucing voltage using zones lies in progressive uction of the overvoltage level to a safe value that will not damage the specifi c equipment or technology. To obtain a safe overvoltage value, the whole structure is divided into individual zones and the SPD is installed at the boundary between the zones. LPZ 0 A LPZ 1 LPZ 0 A LPZ 2 LPZ 3 LPZ 3 LPZ 2 LPZ 3 LPZ 3 LPZ 3 LPZ 0 B LPZ 2 LPZ 0 B LPZ 3 LPZ 3 LPZ 1 L1 L2 L3 PEN LPZ 0 SPD type 1 or 1+2 LPZ 1 SPD type 2 LPZ 2 SPD type 2 LPZ 2 Main distribution board Subsidiary distribution board (1) Subsidiary distribution board (2) Origin of the installation F1 N PE RCD SPD type 3 Fine protection 16 A 16 A 63 A *F2 *F3 *F4 External lightning protection Main earthing bonding bar Local earthing bonding bar Local earthing bonding bar * Additional protection of SPD see page 7 Equipment (technology) 19

20 SPD mounting principles Principle 1 length of connecting conductors If you want to protect equipment, there are several things to remember when installing an SPD, i.e., apart from its diverting ability, it is the maximum value of voltage protective level to be withheld by the equipment at its terminals considering the installation method. Protection level U p and the drop in voltage at the supply conductors U must not exceed the withstand voltage at the terminals of the equipment. Fig. 11 clearly shows that the aggregate protection level is given by adding partial uctions in voltage, while such a sum must not exceed the withstand voltage U w at the terminals of the equipment. U w > U p + U 1 + U 2 where U w withstand voltage U p voltage protection level U 1, U 2 uction in voltage at the supply conductor. The impedance of supply conductors for high frequency currents is approximately 1 µh per 1 m of conductor length. The voltage drop in this conductor is given by the formula: U = L di/dt So with a steepness of the pulse rise time of 1 ka/µs, there is a uction of 1,000 V per 1 m of length, which is added to the protection voltage level of the SPD itself. With the total length of supply conductors being 0.5 m, 500 V will be added to the protection voltage level Up. Consequently, the length of the supply conductors must be as short as possible and should not exceed an aggregate length of 0.5 m, as shown in the following fi gures (Fig. 12 and Fig. 13), depicting the connection options. Fig. 11 U 1 OCP a U W SPD U p U 2 b Fig. 12 Fig. 13 a b c a + b 0,5 m c 0,5 m 20

21 Practical Guide - Low-voltage power systems The two practical examples below show that it is possible to meet the stipulated conductor length 0.5 m in practice for connecting the SPD. Before the intervention: The SPD installation fails to meet the condition the length of supply conductors for the SPD After the intervention: By relocating the SPD, the condition will be satisfied the length of supply conductors for the SPD Before the intervention: The SPD installation fails to meet the condition the length of supply conductors After the intervention: By relocating the SPD, the condition will be satisfied 21

22 Principle 2 SPD location in the distribution board An SPD in the distribution board is located at the entry of the customer s structure, to eliminate surges coming in the supply line as soon as possible and to prevent the effects on appliances in the distribution board. This will make sure that the unprotected conductors (affected by overvoltage) are as short as possible. The overvoltage that could induce the protected conductors (conductors protected by the SPD), is minimized in this way. Basic options are shown in Fig.14. Fig. 14 a) b) c) d) EBB The next fi gure shows option c) directly in practice from Fig. 14. Before the intervention: The SPD installation fails to meet the condition the length of supply conductors for the SPD After the intervention: By adding a terminal block and connecting a PEN conductor, these conditions will be satisfi ed 22

23 Practical Guide - Low-voltage power systems +1 Before the intervention: The SPD installation fails to meet the condition the length of supply conductors for the SPD and also the SPD connection for the TN-S system After the intervention: By relocating the circuit breaker and the SPD, the conditions will be satisfi ed; and by adding one more SPD, the N conductor will also be protected. Principle 3 loops The surface of a loop consisting of conductors (L, N and PE) must be as small as possible to minimize the overvoltage induced in the loop and to considerably uce the effects of such overvoltage on other equipments (technology) connected in the distribution board. The principle of minimizing the loop is shown in Fig. 14 and the following examples. Before the intervention After the intervention: By turning the SPD, the connection in the distribution board will be better arranged and, at the same time, the condition from IEC /2008 (CLC/TS /2009) concerning loops will be satisfi ed 23

24 Before the intervention After the intervention: By relocating the SPD, the connection in the distribution board will be better arranged, the condition concerning loops specifi ed in IEC /2008 (CLC/TS /2009) will be satisfi ed and, at the same time, the condition stipulating the length of supply conductors for the SPD will be met as well Principle 4 conductor routing in the distribution board When routing the conductors in the distribution board it is always necessary to separate protected ( clean ) and unprotected ( dirty ) conductors. To minimise the bonding between the different types of conductors ( clean and dirty ), it is essential to keep the distance between them as great as possible (over 30 cm). If such a distance is impossible to observe, a protection partition should be placed between them, see Fig. 15. If you cannot avoid crossing of protected and unprotected conductors, the crossing should be made in the right angle to prevent induction of interference pulses in the protected conductors, as shown in Fig. 16. Fig. 15 > 30 cm Unprotected cable Protected cable < 30 cm < 30 cm Unprotected cable Protected cable Unprotected cable Divider Protected cable Fig. 16 Unprotected cable Unprotected cable 90 Protected cable Protected cable 24

25 Practical Guide - Low-voltage power systems Coordination of SALTEK principles To achieve correct operation of individual SPD levels, specifi c distances should be observed between them. A general solution is shown in Fig. 17 and Fig. 19. Fig. 18 shows incorrect coordination between individual SPDs. Should it be impossible to observe the coordination distances between the specifi c protection levels, the distance can be extended using coordination RTO impendences. These coordination impendences must be dimensioned to the current fl owing through the line. This can be established from the value of the circuit protection. Since it is rather diffi cult to apply RTO if the distances between the individual protection levels in higher continuous currents are not observed, we use a coordinated SPD type 1 with the relevant SPD type 2. Fig. 17 L 10 m L 5 m Type 1 Type 2 Type 3 Fig. 18 L < 10 m L < 5 m Type 1 Type 2 Type 3 Fig. 19 L < 10 m L < 5 m RTO RTO Type 1 Type 2 Type 3 25

26 If the lightning arrester FLP-SG50 V/1 is used as an SPD type 1 and SLP-275 V is used as an SPD type 2, it will not be necessary to keep the distance between them over 10 m, because they are mutually coordinated and can be mounted next to each other (see Fig. 20). If, for example, FLP-B++C MAXI V is installed as an SPD type 1, which is an SPD type 1+2 with Up < 1.5 kv and the distance between this SPD and the next one exceeds 10 m, an SPD type 2 should be located behind the SPD type 1+2, e.g., SLP-275 V (see Fig. 21). If the distance between this SPD and the next one is less than 10 m, you will not need to install an SPD type 2 behind the SPD type 1+2. The same applies oniy if an SPD type 2 is used instead of an SPD type 1+2 (see Fig. 22). Fig m < L < 10 m L 5 m Type 1 Type 2 Type 3 FLP-SG50 V /1 SLP-275 V* * according to type of connection Fig. 21 L 10 m L 5 m Type Type 2 Type 3 FLP-B+C MAXI V* SLP-275 V* * according to type of connection L 5 m Fig. 22 L 10 m L 5 m Type 2 Type 2 Type 3 SLP-275 V* SLP-275 V* * according to type of connection L 5 m 26

27 Practical Guide - Low-voltage power systems Since there are situations in practice where the technology is connected directly from the main distribution board and the technology distribution board is usually at a distance of tens of meters, it is advisable to install an SPD in the technology distribution board to cope with overvoltage as well as different earth potentials that might occur there, particularly if the earthing (equipotential bonding) is not completely all right. Consequently, an SPD type 1+2, featuring a diverting ability of In = 30 ka (8/20µs), should be installed in the position of the SPD type 2, whose diverting ability is In = 20 ka (8/20µs), to work In this case as a strong SPD type 2 (see Fig and Fig ). Protective distance To protect specifi c equipment, an SPD should be installed as close as possible to the protected equipment. If the SPD-SPD or SPD-technology distances are too great, the line features refl ections which can destroy the technology or the line insulation. These refl ections can even double the Up protection voltage level. The doubling effect occurs if the equipment is disconnected inside or its input impedance is high. If the distance between the SPD and the technology is L 10 m, refl ections need not be taken into consideration. If the distance is great (L>> 10 m), remember to install an additional SPD (see Fig and Fig ). Fig. 23 L > 50 m Fig. 24 L > 50 m Type 1 Type 2 Type 1 Type 1+2 FLP-SG50 V /1 FLP-SG50 V /1 SLP-275 V/1+1 FLP-12,5 V/1+1 Fig. 25 L > 100 m Fig. 26 L > 100 m Type 1 Type 2 Type 1 Type 1+2 FLP-SG50 V /1 FLP-SG50 V /1 SLP-275 V/1+1 FLP-B+C MAXI V/2 Fig. 27 L >> 10 m Fig. 28 L > 10 m Type 1+2 Type 2 Type 1+2 FLP-B+C MAXI V/2 FLP-B+C MAXI V/2 SLP-275 V/1+1 Fig. 29 L > 10 m Fig. 30 L > 5 m Type 2 Type 2 Type 3 SLP-275 V/1+1 SLP-275 V/1+1 DA-275 V/1+1 27

28 The protective distance of the SPD is always uced as a result of the voltage induced by lightning current or switching of the technology connected to same circuit. This is why the distance between an SPD and the technology must not exceed 5 m. This is of particular importance in protecting highly sensitive equipment, such as electronic security systems, electronic fi re signalling systems, PLC and other processor-controlled technology that is also prone to induced switching overvoltage. Such overvoltage with a very short duration (in µs) and a small pulse amplitude (hunds of volts) would pass up to the equipment, which will not be destroyed, but it can affect processor freezing or damage or erase memory chips or impair the functionality of the equipment. Hence, an SPD type 3 with a VF fi lter, able to cope with this problem, should be installed in these cases. An example of the connection of an SPD type 3 with a VF fi lter is shown in Fig. 31 and Fig. 32. Socket circuits with SPD type 3 Consideration should be taken regarding socket circuits, which are usually very long and are used in different situations. The protective distance of an SPD type 3 in socket circuits is less than 5 m down the cable, as shown in Fig. 33. To ensure correct functioning of an SPD type 3, both protection levels SPD type 1 and SPD type 2 should be mounted before. Socket circuitry featuring all sockets either with integrated SPD type 3 protection or available with SPD type 3 protection for additional installation (see Fig. 34), is always used in heavily disturbed environments, or places with a number of electrical appliances. Laboratories are a typical example of such environment. Fig. 31 L > 5 m L < 5 m Type 1+2 FLP-B+C MAXI V/2 Type 3 DA-275 DF 16 Fig. 32 L > 5 m L < 5 m Type 2 SLP-275 V/1+1 Type 3 DA-275 DF 16 Fig. 33 < 5 m < 5 m Fig. 33a Application of SPD type 3 for additional mounting in different types of sockets CZ-275 A A socket with integrated SPD type 3 Earth Pin SCHUKO DA-275 A 28

29 Practical Guide - Low-voltage power systems Fig. 34 A socket with integrated SPD type 3 SPD type 3 for additional installation (DA or CZ according to type of sockets see Fig. 33a) DA-275 A DA-275 A DA-275 A DA-275 A DA-275 A CZ-275 A CZ-275 A CZ-275 A CZ-275 A CZ-275 A To uce the number of SPD type 3 in socket circuitry, protective distances of SPD type 3 protection, being below 5 m, are used as standard. In these cases, it is not necessary to equip all sockets with SPD type 3 protection. The basic principle to follow in this method of installing an SPD type 3 is that the SPD must always be installed at the fi rst socket in the socket circuit; the protective distance principle for SPD type 3, as shown in Fig. 35, can be applied only after that. Fig. 36 shows an example of incorrect application of the protective distance. The principle of protective distance cannot be applied to situations where one side of the wall features a socket circuit with, for example, a down conductor bar or an unprotected ascending LV line situated on the other side of the wall. All sockets in this place should be provided with an SPD type 3, as shown in Fig. 37 and Fig. 38. Fig. 35 < 5 m < 5 m < 5 m < 5 m DA-275 A DA-275 A DA-275 A Fig. 36 < 5 m < 5 m < 5 m < 5 m DA-275 A DA-275 A 29

30 If this principle is not observed, the problem located at the LV line bar will induce in the socket circuit and will damage the technology connected to the specifi c socket. Administrative buildings feature a great number of socket circuits with many sockets. To uce the number of SPDs in such cases, not only the protective distance for the SPD type 3 is used, but also so-called installations in groups, as shown in the following examples. If distances between individual groups exceed 5 m, as shown in Fig. 39, the passage socket group must be provided with an SPD type 3 at the fi rst and last socket. Fig. 37 < 5 m < 5 m < 5 m < 5 m DA-275 A DA-275 A DA-275 A DA-275 A for example, the down conductor bar Fig. 38 < 5 m < 5 m < 5 m < 5 m DA-275 A DA-275 A DA-275 A for example, the down conductor bar Fig. 39 > 5 m DA-275 A passage group DA-275 A last group 30

31 Practical Guide - Low-voltage power systems If the group is not a passage group, an SPD type 3 should always be installed at the fi rst socket. Should the distance between individual socket groups be less than 5 m, you can use the property of the SPD protective distance, i.e., you do not need to install an SPD type 3 at the last socket in the passage group, as shown in Fig. 40. The principle of protective distance cannot be applied in situations where the distance between two groups is less than 5 m, and, for example, a down conductor bar or an unprotected LV line is located on the other side of the wall. It is necessary in this case that the last socket of the passage group be provided with an SPD type 3. This option is shown in Fig. 41. SPD connection considering U p (protective voltage level) Connection of SPDs in sequence is shown in the following fi gures (Fig and Fig ). Fig. 40 < 5 m DA-275 A passage group DA-275 A last group Fig. 41 passage group < 5 m last group DA-275 A for example, the down conductor bar DA-275 A Fig. 42 Fig. 43 Type 1+2 U p (L-N) 1.5 kv Type 3 U p (L-N) 1.0 kv Type 2 U p (L-N) 1.2 kv Type 3 U p (L-N) 1.0 kv Fig Fig. 45 Type 1 U p (L-N) 2.5 kv Type 3 U p (L-N) 1.0 kv Type 1 U p (L-N) 2.5 kv Type 2 U p (L-N) 1.2 kv 31

32 SALTEK SPD applications in LV distribution systems Type of structure system main distribution board (in the structure) sub-distribution board (in the same structure) end consumer Family houses, administrative buildings, technologic units, industrial structures Blocks of flats with 12 or more apartments (SPD located in the apart. distr. boards) Demanding applications (structures operations classified at the risk of explosion, chemical plants, structures of a very high importance) 3-ph. TN-C FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 FLP-25--VS/3, FLP-25--V/3 FLP-25--VS/3, FLP-25--V/3 FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 FLP-25--VS/3 + SLP-275 V/3 S FLP-25--V/3 + SLP-275 V/3 (also with terminals to the equipment) 3-ph. TN-S FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4 FLP-25--VS/4, FLP-25--V/4 3-ph. TN-C-S 3-ph. TN-C 3-ph. TN-S 3-ph. TN-C-S 1-ph. TN-C 1-ph. TN-S 3-ph. TN-C 3-ph. TN-S 3-ph. TN-C-S FLP-25--VS/4, FLP-25--V/4 FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4 FLP-25--VS/4 + SLP-275 V/4 S FLP-25--V/4 + SLP-275 V/4 (also with terminals to the equipment) FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 FLP-25--VS/3, FLP-25--V/3 FLP-25--VS/3, FLP-25--V/3 FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 FLP-25--VS/3 + SLP-275 V/3 S FLP-25--V/3 + SLP-275 V/3 (also with terminals to the equipment) division in the apartment distr. board 3 FLP-SG50 V(S) with terminals to the equipment 3 FLP-SG50 V(S) + 1 SLP-275 V/3(S) 4 FLP-SG50 V(S) with terminals to the equipment 4 FLP-SG50 V(S) + 1 SLP-275 V/4(S) division in the main distribution board 3 FLP-SG50 V(S) with terminals to the equipment 3 FLP-SG50 V(S) + 1 SLP-275 V/4(S) distance > 10 m SLP-275 V/3(S) distance > 50 m FLP-12.5 V/3(S) distance > 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 distance < 10 m SLP-275 V/3(S) distance > 10 m SLP-275 V/3(S) distance > 50 m FLP-12.5 V/3(S) distance > 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 distance < 10 m SLP-275 V/4(S) distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 distance < 10 m SLP-275 V/4(S) distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 FLP-12.5 V/3(S) FLP-12.5 V/4(S) FLP-12.5 V/3(S) FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1 FLP-12.5 V/2(S) distance < 10 m 1 SLP-275 V/3(S) distance > 10 m SLP-275 V/3(S) distance > 50 m FLP-12.5 V/3(S) distance > 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 distance < 10 m 1 SLP-275 V/4(S) distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 distance < 10 m 1 SLP-275 V/4(S) distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 distance > 5 m overvoltage protection to DIN rail: DA-275 V/1(S)+1 (to 63 A) DA-275 V/3(S)+1 (to 63 A) DA-275 DJ (to 16 A) overvoltage protection to a DIN rail with a vf filter: DA-275 DFx (S) (x = 2, 6, 10, 16 A) DA-275 DF 25 for 25 A DA-275 DFIx (x = 1, 6, 10, 16 A) RACK-PROTECTOR multiple sockets to 19"stands CZ-275 A, DA-275 CZS DA-275 A, DA-275 S for additional assembly to the sockets and appliances sockets with overvoltage protection (ABB) XX-overdrive socket adapters distance < 5 m place before the overvoltage protection RTO-xx (xx rated current 16, 35 or 63 A) number acording to connection 1-phase TN-C 1x RTO-xx 1-phase TN-S 2x RTO-xx 3-phase TN-C 3x RTO-xx 3-phase TN-S 4x RTO-xx 32

33 Practical Guide - Low-voltage power systems SALTEK SPD applications in LV distribution systems Type of structure system main distribution board (in the structure) sub-distribution board (in the same structure) end consumer Structures equipped with ESE (active down conductor) Technology with 1-phase connection 3-ph. TN-C 3x FLP-A35 distance > 10 m SLP-275 V/3(S) distance > 50 m FLP-12.5 V/3(S) distance > 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 3x FLP-SG50 V(S) distance < 10 m SLP-275 V/3(S) also with terminals to the equipment 3x FLP-SG50 V(S) + SLP-275 V/3(S) distance > 10 m SLP-275 V/3(S) distance > 50 m FLP-12.5 V/3(S) distance > 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 3-ph. TN-S 4x FLP-A35 distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 4x FLP-SG50 V(S) distance < 10 m SLP-275 V/4(S) also with terminals to the equipment 4x FLP-SG50 V(S) + SLP-275 V/4(S) distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 3-ph. TN-C-S 3x FLP-A35 distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 3x FLP-SG50 V(S) distance < 10 m SLP-275 V/4(S) 1-ph. TN-C 1-ph. TN-S 1-ph. TN-C-S also with terminals to the equipment 3x FLP-SG50 V(S) + SLP-275 V/3(S) FLP-SG50 V(S)/1 with terminals to the equipment FLP-SG50 V(S)/1 + SLP-275 V/1(S) 2 FLP-SG50 V(S)/1 with terminals to the equipment 2 FLP-SG50 V(S)/1 + 1 SLP-275 V/2(S) Division in the main distribution board FLP-SG50 V(S)/1 with terminals to the equipment FLP-SG50 V(S)/1 + SLP-275 V/1(S) distance > 10 m SLP-275 V/4(S) distance > 50 m FLP-12.5 V/4(S) distance > 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 distance < 10 m SLP-275 V/1(S) distance > 10 m SLP-275 V/1(S) distance > 50 m FLP-12.5 V/1(S) distance > 100 m FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1 distance < 10 m 1 SLP-275 V/2(S) distance > 10 m 1 SLP-275 V/2(S) distance > 50 m 1 FLP-12.5 V/2(S) distance > 100 m FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2 distance < 10 m 1 SLP-275 V/2(S) distance > 10 m 1 SLP-275 V/2(S) distance > 50 m 1 FLP-12.5 V/2(S) distance > 100 m FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2 distance > 5 m overvoltage protection to DIN rail: DA-275 V/1(S)+1 (up to 63 A) DA-275 V/3(S)+1 (up to 63 A) DA-275 DJ (up to 16 A) Overvoltage protection to DIN rail with vf filter: DA-275 DFx (S) (x = 2, 6, 10, 16 A) DA-275 DF 25 for 25 A DA-275 DFIx (x = 1, 6, 10, 16 A) RACK-PROTECTOR multiple sockets for 19"stands CZ-275 A, DA-275 CZS DA-275 A, DA-275 S For additional mounting to sockets and appliances Sockets with overvoltage protection (ABB) XX-overdrive Socket adapters distance < 5 m SPD back-up RTO-xx (xx rated current 16, 35 or 63 A) number acording to connection 1-phase TN-C 1x RTO-xx 1-phase TN-S 2x RTO-xx 3-phase TN-C 3x RTO-xx 3-phase TN-S 4x RTO-xx 33

34 Lightning current arresters Spark gaps FLP-SG50 V/1 I imp = 50 ka (10/350 µs) I n = 50 ka (8/20 µs) SPD type 1 lightning current arrester A high-performance spark gap specifi ed for installations in LV cabling, at the boundary of the LPZ 0 and LPZ 1 zones, and for protection against overvoltage effects in direct as well as indirect lightning strikes in the most exacting applications both in heavy industry and chemicals industry, power plants, etc. FLP-SG50 V/1 is coordinated with the type 2 SPD SLP-275 V (S) also without surge separating inductors. FLP-SG50 VS/1 I imp = 50 ka (10/350 µs) I n = 50 ka (8/20 µs) SPD type 1 lightning current arrester A high-performance spark gap specifi ed for installations in LV cabling, at the boundary of the LPZ 0 a LPZ 1 zones, and for protection against overvoltage effects in direct as well as indirect lightning strikes in the most exacting applications both in heavy industry and chemicals industry, power plants, etc. FLP-SG50 VS/1 is coordinated with the type 2 SPD SLP-275 V(S) also without surge separating inductors. FLP-A35 I imp = 35 ka (10/350 µs) I n = 35 ka (8/20 µs) U p 4.0 kv SPD type 1 lightning current arrester A high-performance encapsulated spark gap specifi ed for installations in LV cabling, at the boundary of the LPZ 0 a LPZ 1 zones, and protection against overvoltage effects in direct as well as indirect lightning strikes. Coordination of FLP-A35 with SPD type 2 (SLP-275 V) is provided by installing a surge separating inductor or by correct distance. Spark gaps between N and PE FLP-A50N VS/NPE U c = 255 V AC I imp = 50 ka (10/350 µs) I n = 50 ka (8/20 µs) I max = 100 ka (8/20 µs) FLP-A100N VS/NPE U c = 255 V AC I imp = 100 ka (10/350 µs) I n = 100 ka (8/20 µs) I max = 100 ka (8/20 µs) SPD type 1 lightning current arrester A spark gap for N-PE with a replaceable module, specifi ed for installation in LV cabling, at the boundary of the LPZ 0 and LPZ 1 zones, and for protection against overvoltage effects in direct as well as indirect lightning strikes, for connecting SPD type 1 in the 1+1 mode. ATTENTION! Only specifi ed for connections between N and PE! SPD type 1 lightning current arrester A spark gap pro N-PE with a replaceable module, specifi ed for installation in LV cabling, at the boundary of the LPZ 0 a LPZ 1 zones, and for protection against overvoltage effects in direct as well as indirect lightning strikes for connecting SPD type 1 in the 3+1 mode. ATTENTION! Only specifi ed for connections between N and PE! 34

35 Practical Guide - Low-voltage power systems Lightning current arresters Combined lightning current arresters SPD type 1 FLP-25--V/3 I imp = 25 ka (10/350 µs) Zero leakage current No follow-on current FLP-25--VS/3 I imp = 25 ka (10/350 µs) Zero leakage current No follow-on current Status remote signalling FLP-25--V/4 I imp = 25 ka (10/350 µs) Zero leakage current No follow-on current FLP-25--VS/4 I imp = 25 ka (10/350 µs) Zero leakage current No follow-on current Status remote signalling FLP-25--V/3+1 I imp = 25 ka (10/350 µs) U p 2.2 kv (L-PE) Zero leakage current No follow-on current FLP-25--VS/3+1 I imp = 25 ka (10/350 µs) U p 2.2 kv (L-PE) Zero leakage current No follow-on current Status remote signalling SPD type 1 lightning current arrester A three-pole high-performance lightning current arrester for installation in LV cabling at the boundary of the LPZ 0A LPZ 1 zones and higher levels. It is used to protect against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-C networks. SPD type 1 lightning current arrester A three-pole high-performance lightning current arrester for installations in LV cabling at the boundary of the LPZ 0A LPZ 1 zones and higher levels. It is used to protect against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-C networks. SPD type 1 lightning current arrester A four-pole high-performance lightning current arrester for installations in LV cabling at the boundary of the LPZ 0A LPZ 1 zones and higher levels. It is used to protect against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-S networks. SPD type 1 lightning current arrester A four-pole high-performance lightning current arrester for installations in LV cabling at the boundary of the LPZ 0A LPZ 1 zones and higher levels. It is used to protect against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-S networks. SPD type 1 lightning current arrester A combination of a three-pole high-performance lightning arrester and encapsulated effi ciency spark gap, connected in the 3+1 mode for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TT networks. SPD type 1 lightning current arrester A combination of a three-pole high-performance lightning arrester and encapsulated effi ciency spark gap, connected in the 3+1 mode for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in subsidiary distribution boards of large premises. It is specifi ed for three-phase TT networks. 35

36 Lightning current arresters Combined lightning current arresters SPD type 1+2 FLP-B+C MAXI V/1 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where no remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for single-phase TN-C networks. FLP-B+C MAXI V/1+1 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where no remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in subsidiary distribution boards of large premises. It is specifi ed for single-phase TT networks. FLP-B+C MAXI V/2 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where no remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for single-phase TN-S networks. FLP-B+C MAXI V/3 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where no remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-C networks. FLP-B+C MAXI V/3+1 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) U p 1.5 kv Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where no remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TT networks. 36

37 Practical Guide - Low-voltage power systems Lightning current arresters Combined lightning current arresters SPD type 1+2 FLP-B+C MAXI V/4 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where no remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-S networks. FLP-B+C MAXI VS/1 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for single-phase TN-C networks. FLP-B+C MAXI VS/1+1 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for single-phase TT networks. FLP-B+C MAXI VS/2 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for single-phase TN-S networks. FLP-B+C MAXI VS/3 I imp = 25 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-C networks. 37

38 Lightning current arresters Combined lightning current arresters SPD type 1+2 FLP-B+C MAXI VS/3+1 I imp = 50 ka (10/350 µs) I n = 50 ka (8/20 µs) I max = 100 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TT networks. FLP-B+C MAXI VS/4 I imp = 50 ka (10/350 µs) I n = 50 ka (8/20 µs) I max = 100 ka (8/20 µs) Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A high-performance lightning current arrester for installations in LV cabling, at the boundary of the LPZ 0 LPZ 1 zones and higher levels, where remote signalling is requi, and for protection against overvoltage effects in direct as well as indirect lightning strikes. It can be used in a variety of installations, suitable for family houses, administrative and commercial buildings, or in sub-distribution boards of large premises. It is specifi ed for three-phase TN-S networks. Varistor lightning arresters SPD type 1+2 FLP-12,5 V/1(S) I imp = 12.5 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 1 and 2 lightning current arrester A varistor lightning current arrester specifi ed for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against the effects of partial lightning strike currents, induced overvoltage in lightning strikes and against switching overvoltage. It is suitable for III and IV risk class buildings, in sub-distribution boards of large premises or the protection of air conditioners or heating cables. It is specifi ed for single-phase TN-C networks. FLP-12,5 V/1(S)+1 I imp = 12.5 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 1 and 2 lightning current arrester A varistor lightning current arrester specifi ed for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against the effects of partial lightning strike currents, induced overvoltage in lightning strikes and against switching overvoltage. It is suitable for III and IV risk class buildings, in subsidiary distribution boards of large premises or the protection of air conditioners or heating cables. It is specifi ed for single-phase TT networks. FLP-12,5 V/2(S) I imp = 12.5 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 1 and 2 lightning current arrester A varistor lightning current arrester specifi ed for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against the effects of partial lightning strike currents, induced overvoltage in lightning strikes and against switching overvoltage. It is suitable for III and IV risk class buildings, in sub-distribution boards of large premises or the protection of air conditioners or heating cables. It is specifi ed for single-phase TN-S networks. 38

39 Practical Guide - Low-voltage power systems Lightning current arresters Varistor lightning current arresters SPD type 1+2 FLP-12,5 V/3(S) I imp = 12.5 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 1 and 2 lightning current arrester A varistor lightning current arrester specifi ed for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against the effects of partial lightning strike currents, induced overvoltage in lightning strikes and against switching overvoltage. It is suitable for III and IV risk class buildings, in subsidiary distribution boards of large premises or the protection of air conditioners or heating cables. It is specifi ed for three-phase TN-C networks. FLP-12,5 V/3(S)+1 I imp = 12.5 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) U p 1.2 kv Zero leakage current No follow-on current SPD type 1 and 2 lightning current arrester A varistor lightning current arrester specifi ed for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against the effects of partial lightning strike currents, induced overvoltage in lightning strikes and against switching overvoltage. It is suitable for III and IV risk class buildings, in sub-distribution boards of large premises or the protection of air conditioners or heating cables. It is specifi ed for three-phase TT networks. FLP-12,5 V/4(S) I imp = 12.5 ka (10/350 µs) I n = 30 ka (8/20 µs) I max = 60 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 1 and 2 lightning current arrester A varistor lightning current arrester specifi ed for installations in LV cabling at the boundary of the LPZ 0 LPZ 1 zones and higher levels. It is used to protect against the effects of partial lightning strike currents, induced overvoltage in lightning strikes and against switching overvoltage. It is suitable for III and IV risk class buildings, in sub-distribution boards of large premises or the protection of air conditioners or heating cables. It is specifi ed for three-phase TN-S networks. Coordination impedance RTO-xxx I L (xxx) = 16; 35; 63 A U n = 500 V AC L = 10 µh Surge separating inductors Coupling impedance to secure proper coordination of an SPD if the minimum distance between an SPD type 1 and SPD type 2, which exceeds 10 m, is not maintained, or an SPD type 2 and 3, which exceeds 5 m. RTO-16 RTO-35 RTO-63 39

40 Surge arresters SLP-275 V/1(S) I n = 20 ka (8/20 µs) I max = 40 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 2 surge arrester Varistor surge protection specifi ed for installations in LV cabling, particularly in sub-distribution boards. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is specifi ed for single-phase TN-C networks. SLP-275 V/1(S)+1 I n = 20 ka (8/20 µs) I max = 40 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 2 surge arrester Varistor surge protection specifi ed for installations in LV cabling, particularly in sub-distribution boards. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is specifi ed for single-phase TN-S and TT networks. SLP-275 V/2(S) I n = 20 ka (8/20 µs) I max = 40 ka (8/20 µs) U p 1.2 kv SPD type 2 surge arrester Varistor surge protection specifi ed for installations in LV cabling, particularly in sub-distribution boards. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is specifi ed for three-phase TN networks. Optional remote signalling (S) SLP-275 V/3(S) I n = 20 ka (8/20 µs) I max = 40 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 2 surge arrester Varistor surge protection specifi ed for installations in LV cabling, particularly in sub-distribution boards. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is specifi ed for three-phase TN-C networks. SLP-275 V/3(S)+1 I n = 20 ka (8/20 µs) I max = 40 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 2 surge arrester Varistor surge protection specifi ed for installations in LV cabling, particularly in sub-distribution boards. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is specifi ed for three-phase TT networks. 40

41 Practical Guide - Low-voltage power systems Surge arresters SLP-275 V/4(S) I n = 20 ka (8/20 µs) I max = 40 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) SPD type 2 surge arrester Varistor surge protection specifi ed for installations in LV cabling, particularly in sub-distribution boards. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is specifi ed for three-phase TN-S networks. SLP-xxx V/1(S) xxx - other voltages U n(xxx) = 75, 150, 385, 440, 600 V AC I n = ka (8/20 µs) I max = 40 ka (8/20 µs) SPD type 2 surge arrester Varistor surge protection specifi ed for installations in LV cabling, particularly in sub-distribution boards. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. The SLP-600 V version is specifi ed for the protection of wind turbines and inventor equipment. Optional remote signalling (S) SLP-275 VB/1(S) I n = 20 ka (8/20 µs) I max = 25 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) No leakage current SPD type 2 surge arrester It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes in areas with more frequent storms, and against switching overvoltage, or to protect measurement circuits as the fi rst level of protection. It is also suitable for installations in communications (M&C) circuits at the boundary of the LPZ 0 and LPZ 1 zones. SLP-275 VB/3(S)+1 I n = 20 ka (8/20 µs) I max = 25 ka (8/20 µs) U p 1.2 kv Optional remote signalling (S) No leakage current SPD type 2 surge arrester It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes in areas with more frequent storms, and against switching overvoltage, or to protect measurement circuits as the fi rst level of protection. It is also suitable for installations in communications (M&C) circuits at the boundary of the LPZ 0 and LPZ 1 zones. SLP-xxx VB/1(S) xxx - other voltages U n = (xxx) = 75, 130 V AC I n = ka (8/20 µs) I max = 40 ka (8/20 µs) Optional remote signalling (S) No leakage current SPD type 2 surge arrester It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes in areas with more frequent storms and against switching overvoltage or to protect measurement circuits as the fi rst level of protection. It is also suitable for installations in communications (M&C) circuits at the boundary of the LPZ 0 and LPZ 1 zones. 41

42 Surge arresters to DIN rail DA-275 V/1 (S)+1 U C 230 V AC I n = 5 ka (8/20 µs) U OC = 10 kv AC Optional remote signalling (S) SPD type 3 surge arrester A combination of varistor surge protection and an enapsulated spark gap connected in the 1+1 mode. Specifi ed for installations in LV cabling, at the boundary of the LPZ 2 and LPZ 3 zones. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is located as close as possible to the protected equipment. DA-275 V/3 (S)+1 U C 230 V AC I n = 5 ka (8/20 µs) U OC = 10 kv AC Optional remote signalling (S) SPD type 3 surge arrester A combination of three-pole varistor surge protection and an encapsulated spark gap connected in the 3+1 mode. It is specifi ed for installations in LV cabling, at the boundary of the LPZ 2 a LPZ 3 zones. It is used to protect cabling and equipment against the effects of induced overvoltage in lightning strikes and against switching overvoltage. It is located as close as possible to the protected equipment. DA-275 DJ U C 230 V AC I n = 5 ka (8/20 µs) U OC = 10 kv AC SPD type 3 surge arrester A surge arrester for universal use to protect all types of LV electrical and electronic equipment against surge overvoltage. It is specifi ed for mounting in all types of systems (TN-S, TT, TN-C, IT). Visual status signalling (S) DA-xxx DJ xxx - other voltages U C (xxx) = 75; 130 V AC I n = 4 5 ka (8/20 µs) U oc = 8 10 kv AC SPD type 3 surge arrester A surge arrester for universal use to protect all types of LV electrical and electronic equipment against surge overvoltage. Visual status signalling (S) Socket outlet DA socket outlet U c = 275 V AC Visual or acoustic status signalling SPD type 3 surge arrester A socket with surge protection should be mounted close to the protected equipment or at the boundary of the LPZ 2 and LPZ 3 zones. Supplied surge arresters: protected sockets in versions Classic, Tango, Time, Element, Profi l 45, Refl ex SI, Praktik socket adapters in combination with protection of telephone ISDN, data line or antenna conductor bar multiple sockets for 19" stands 42

43 Practical Guide - Low-voltage power systems Surge arresters with RFI filter DA-275 DF xxx (S) I L (xxx) = 2; 6; 10; 16; 25 A U OC = 10 kv SPD type 3 surge arrester A surge arrester with an integrated RFI fi lter to protect the supply of control systems such as M&C, ESS, EFS, etc., against surge overvoltage and RFI disturbance. Optional remote signalling (S) No remote signalling available for DA-275 DF 25 DA-275 DFI xxx I L (xxx) = 1; 6; 10; 16 A U OC = 3-10 kv SPD type 3 surge arrester A surge arrester with an integrated RFI fi lter to protect the supply of control systems such as M&C, ESS, EFS, etc., against surge overvoltage and RFI disturbance. DA-275 DF 25 I L = 20 A U OC = 10 kv SPD type 3 surge arrester A surge arrester with an integrated RFI fi lter to protect the supply of control systems such as M&C, ESS, EFS, etc., against surge overvoltage and RFI disturbance. DA-400 DF 16 (S) I L = 16 A U n = 400 V AC U OC = 10 kv U p 1.4 kv SPD type 3 surge arrester A surge arrester with an integrated RFI fi lter to protect the supply of control systems such as M&C, ESS, EFS, etc., against surge overvoltage and RFI disturbance for two-phase supply. Optional remote signalling (S) DA-275 BFG I L = 16 A U OC = 10 kv U p 15 kv SPD type 3 surge arrester A surge arrester with an integrated RFI fi lter to protect the supply of control systems such as M&C, ESS, EFS, etc., against surge overvoltage and RFI disturbance. 43

44 Surge arresters For additional mounting CZ-275 A I n = 3 ka (8/20 µs) U OC = 6 kv SPD type 3 surge arrester Surge arresters for additional mounting in appliances, devices, machines, equipment, etc., specifi ed to protect all types of LV electrical and electronic equipment against surge overvoltage. CZ-275 A - Acoustic status signalling DA-275 CZS I n = 3 ka (8/20 µs) U OC = 6 kv SPD type 3 surge arrester Surge arresters for additional mounting in appliances, devices, machines, equipment, etc., specifi ed to protect all types of LV electrical and electronic equipment against surge overvoltage. Remote signalling is potential-free break contact DA-275 A I n = 2 ka (8/20 µs) U OC = 4 kv AC Acoustic status signalling SPD type 3 surge arrester Surge arresters for additional mounting in appliances, devices, machines, equipment, etc., specifi ed to protect all types of LV electrical and electronic equipment against surge overvoltage. It is suitable for single-phase supply networks, without the need to comply with the connection of the L, N conductors in the installation. It can also be used for single-phase supply networks with a separating transformer. DA-275 S I n = 2 ka (8/20 µs) U OC = 4 kv AC Status remote signalling SPD type 3 surge arrester Surge arresters for additional mounting in appliances, devices, machines, equipment, etc., specifi ed to protect all types of LV electrical and electronic equipment against surge overvoltage. It is suitable for single-phase supply networks, without the need to comply with the connection of the L, N conductors in the installation. It can also be used for single-phase supply networks with a separating transformer. Others ISG-A100 I imp = 100 ka (10/350 µs) Isolation resistance >100 kω classification H class Isolating spark gap It is used for the indirect connection of an external lightning protection system to other close metallic parts, where a direct connection is not allowed due to operating conditions: earthing systems of heavy current installations, telecommunications systems, auxiliary and rail earthing bars of earth short-circuit breakers trigge by the voltage, AC and DC rail earthing bars, measurement earthing bars for laboratories, installations with cathodic protection and stray current systems, service entry poles for external LV cables, by-pass of isolated fl anges and isolated connections to pipes. 44

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

Use of application-optimised type 1 combined arresters in low-voltage installations

Use of application-optimised type 1 combined arresters in low-voltage installations Use of application-optimised type 1 combined arresters White Paper Contents Use of prewired and application-optimised DEHNshield combined arresters with spark gap technology Examples: Under-road radiators

More information

6. Internal lightning protection

6. Internal lightning protection 6. Internal lightning protection 6.1 Equipotential bonding for metal installations Equipotential bonding according to IEC 60364-4- 41 and IEC 60364-5-54 Equipotential bonding is required for all newly

More information

The Role of the Grounding System in Electronics Lightning Protection

The Role of the Grounding System in Electronics Lightning Protection ILPS 2016 - International Lightning Protection Symposium April 21-22, 2016 Porto Portugal The Role of the Grounding System in Electronics Lightning Protection Roberto Menna Barreto SEFTIM Brazil Rio de

More information

Surge Protection Device (SPD) 7P

Surge Protection Device (SPD) 7P Surge Protection Device (SPD) SЕRIS Panels for electrical distribution Control panels Surge protection Road / tunnel lighting levators and lifts FINDR reserves the right to alter characteristics at any

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392 2007 DEHN + SÖHNE / protected by ISO 16016 EXFS 100 11.12.07 / 5392 Ex Isolating Spark Gaps EXFS 100 (923 100) and EXFS 100 KU (923 101) 2007 DEHN + SÖHNE / protected by ISO 16016 Ex isolating spark gap

More information

ITU-T K.98. Overvoltage protection guide for telecommunication equipment installed in customer premises SERIES K: PROTECTION AGAINST INTERFERENCE

ITU-T K.98. Overvoltage protection guide for telecommunication equipment installed in customer premises SERIES K: PROTECTION AGAINST INTERFERENCE I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T K.98 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (08/2014) SERIES K: PROTECTION AGAINST INTERFERENCE Overvoltage guide for

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product overview Residual Current Operated C ircuit-breakers (RCCBs) Number of poles Rated fault current I n ma Rated current I n A MW Auxiliary switches can be mounted (Type A) (Type B) 5SM1and 5SM3 RCCBs

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems PPLICATION GUIDELINES OVERVOLTAGE PROTECTION Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems Foreword Up until 1998 no international standards

More information

ABSTRACTS of SESSION 6

ABSTRACTS of SESSION 6 ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested

More information

Protection against unacceptable voltages in railway systems

Protection against unacceptable voltages in railway systems Bernhard Richter*, Alexander Bernhard*, Nick Milutinovic** SUMMERY Based on the system voltages for AC and DC railway systems the required voltage ratings for modern gapless MO surge arresters are given.

More information

Introduction EMC. Filter parameters. Definition of EMC / EMI. X-Capacitor. Sources of EMI. Coupling mechanism. Y-Capacitor.

Introduction EMC. Filter parameters. Definition of EMC / EMI. X-Capacitor. Sources of EMI. Coupling mechanism. Y-Capacitor. Introduction to EMC Schurter has over 75 years experience in the electronics and electrical industries, developing and manufacturing components that ensure a clean and safe supply of power. Schurter provides

More information

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Power Quality. Case Study. Conrad Bottu Laborelec January 2008 Case Study Electromagnetic compatibility (EMC) study Breakdown of low voltage electronic equipment in a 25 kv substation Conrad Bottu Laborelec January 2008 Power Quality Power Quality 1 Introduction Description

More information

IMP/007/011 - Code of Practice for the Application of Lightning Protection

IMP/007/011 - Code of Practice for the Application of Lightning Protection Version 1.1 of Issue Aug 2006 Page 1 of 11 IMP/007/011 - Code of Practice for the Application of Lightning Protection 1.0 Purpose The purpose of this document is to ensure the company achieves its requirements

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge

More information

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent Technical Requirements for Resistibility of Telecommunications Equipment to Overvoltage and Overcurrent TR NO.189001 Edition 3 1st, April, 2018 Nippon Telegraph and Telephone Corporation Notice This document

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent Technical Requirements for Resistibility of Telecommunications Equipment to Overvoltage and Overcurrent TR NO.189001 Edition 2.1 1st, April, 2015 Nippon Telegraph and Telephone Corporation Notice This

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

SIOV metal oxide varistors

SIOV metal oxide varistors SIOV metal oxide varistors Application notes Date: January 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without

More information

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016. Title Grounding System Introduction Date October, 2016 Related Products Key words All industrial automation products Grounding, Earthing, TN, TT, IT, Introduction The automation industry of today has adopted

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Date: Given Names: Time: Assessment Time (includes 10 minutes reading time): At the end of this time you will be asked to stop. 4 hours Have you

More information

Coaxial Cable Protection

Coaxial Cable Protection Coaxial Cable Protection 1485-005 Technical Note Coaxial Cable Protection Coaxial Cable Protection Why is coaxial cable protection needed? Skin effect is a physical phenomenon that relates to the limited

More information

TN, TT & IT Earthing Arrangements

TN, TT & IT Earthing Arrangements TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering

More information

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems 701880MAC0010.1177/0020294017701880 research-article2017 Contributed Paper Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

More information

V1.3. TBLC08 50mH AC-LISN TBLC08

V1.3. TBLC08 50mH AC-LISN TBLC08 V1.3 TBLC08 The TBLC08 is a Line Impedance Stabilization Network for the measurement of line-conducted interference within the range of 9kHz to 30MHz, according to the CISPR16 standard. The device is designed

More information

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:

More information

Earthing for EMC in Installations

Earthing for EMC in Installations Earthing for EMC in Installations Ian McMichael n 1 PQSynergy 2010 Conference Earthing for EMC in Installations Introduction Electromagnetic Compatibility or EMC EMC and installations Standards and References

More information

The Problem of Interference

The Problem of Interference The Problem of Interference Unfortunately not everything is resolved just because we have succeeded in finding the right transmission methods and the right interface. The largest irritant to data communications

More information

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE INTERNATIONAL TELECOMMUNICATION UNION )454 + TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (10/96) SERIES K: PROTECTION AGAINST INTERFERENCE 2ISK ASSESSMENT OF DAMAGES TO TELECOMMUNICATION SITES DUE

More information

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.

More information

Table of Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient (EFT) 3 Electromagnetic Interference

Table of Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient (EFT) 3 Electromagnetic Interference Electromagnetic Compatibility and Electrical Safety GR-1089-CORE Table of Contents Table of Contents 1 Introduction 1.1 Purpose and Scope.................................. 1 1 1.2 Items Not Covered in

More information

Energy Division. Bowthorpe LV/MV Surge Arresters

Energy Division. Bowthorpe LV/MV Surge Arresters Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early

More information

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC DATA SHEET No. 1 December 2000 Issued by the French Lightning Protection Association Precautions to be considered for use of surge arresters tested according to Class 1 of IEC 61643-1 Foreword: The protection

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

Education & Training

Education & Training Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Insulation Test System

Insulation Test System Component Tests Insulation Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 3 Generator Specifications.................

More information

Coordination of surge arresters in DC 3 kv railway traction system field tests

Coordination of surge arresters in DC 3 kv railway traction system field tests Coordination of surge arresters in DC 3 kv railway traction system field tests Miroslaw Zielenkiewicz Tomasz Maksimowicz Center of Protection against Overvoltages and Electromagnetic Interferences RST

More information

Residual current circuit breakers (RCCBs)

Residual current circuit breakers (RCCBs) Residual current circuit breakers (RCCBs) Description Automatically trips in event of earth leakage fault Provides protection against direct & indirect contact with live parts Technical data IS 12640-1,

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Earth Fault Loop Impedance Tests 1 Revision Inspections are made to verify that the installed

More information

Combination Wave Test System

Combination Wave Test System Immunity Tests Combination Wave Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 4 Generator Specifications.................

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise S. Sekioka, K. Aiba, S. Okabe Abstract-- The lightning overvoltages incoming from an overhead line such as a power distribution

More information

SERIES K: PROTECTION AGAINST INTERFERENCE

SERIES K: PROTECTION AGAINST INTERFERENCE International Telecommunication Union ITU-T K.21 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (04/2008) SERIES K: PROTECTION AGAINST INTERFERENCE Resistibility of telecommunication equipment installed

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011 NATIONAL RULES FOR ELECTRICAL INSTALLATIONS Fourth Edition ET 101:2008 Extracts from Amendment No.1:2011 22 June 2011 Page vi: Insert after 1 st Paragraph: Section 710: Medical Locations was prepared by

More information

Outdoor Installation 2: Lightning Protection and Grounding

Outdoor Installation 2: Lightning Protection and Grounding Outdoor Installation 2: Lightning Protection and Grounding Training materials for wireless trainers This one hour talk covers lightning protection, grounding techniques and problems, and electrolytic incompatibility.

More information

Isolating Spark Gaps. Isolating spark gaps at an additional earth ring conductor. Isolating spark gaps for Ex zones

Isolating Spark Gaps. Isolating spark gaps at an additional earth ring conductor. Isolating spark gaps for Ex zones Isolating Spark Gaps Isolating spark gaps at an additional earth ring conductor Isolating spark gaps for Ex zones 187 Protective Spark Gaps For use at roof supports for overhead lines For indirect connection

More information

Insulation Test System

Insulation Test System Component Tests Insulation Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 3 Generator Specifications.................

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Surge Mitigation Component Overview

Surge Mitigation Component Overview Surge Mitigation Component Overview Presented by Mick Maytum m.j.maytum@ieee.org Protection or Mitigation? Protective: having the quality or character of protecting; tending to protect; defensive; preservative.

More information

Choosing the right Pico Technology active differential probe

Choosing the right Pico Technology active differential probe Pico Technology offers many active s covering a wide range of voltages, category (CAT) ratings and bandwidths. As the name suggests, these probes have two major features: Active: Active probes achieve

More information

Investigation on the Performance of Different Lightning Protection System Designs

Investigation on the Performance of Different Lightning Protection System Designs IX- Investigation on the Performance of Different Lightning Protection System Designs Nicholaos Kokkinos, ELEMKO SA, Ian Cotton, University of Manchester Abstract-- In this paper different lightning protection

More information

Time over/underfrequency relay with protection assemblies

Time over/underfrequency relay with protection assemblies Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features

More information

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding

More information

Source: EMP environnement MIL-STD-464

Source: EMP environnement MIL-STD-464 HUBER+SUHNER AG RF PM Components EMP and Lightning Protection DOC-0000825338 Gregor Kuehne / 4302 Product Manager Phone +41 71 353 4302 24 July 2018 www.hubersuhner.com Coupling of HEMP into RF-Antennas

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement.

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement. Application Note Pico Technology offers many s covering a wide range of voltages, category (CAT) ratings and bandwidths. As the name suggests, these probes have two major features: Active: Active probes

More information

SERIES K: PROTECTION AGAINST INTERFERENCE

SERIES K: PROTECTION AGAINST INTERFERENCE International Telecommunication Union ITU-T K.21 TELECOMMUNICTION STNDRDIZTION SECTOR OF ITU (11/2011) SERIES K: PROTECTION GINST INTERFERENCE Resistibility of telecommunication equipment installed in

More information

Immunity Testing for the CE Mark

Immunity Testing for the CE Mark Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half

More information

Prepared by Mick Maytum

Prepared by Mick Maytum IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not

More information

Tab 8 Surge Arresters

Tab 8 Surge Arresters s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information

ITU-T K.97. Lightning protection of distributed base stations SERIES K: PROTECTION AGAINST INTERFERENCE. Recommendation ITU-T K.

ITU-T K.97. Lightning protection of distributed base stations SERIES K: PROTECTION AGAINST INTERFERENCE. Recommendation ITU-T K. International Telecommunication Union ITU-T K.97 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (02/2014) SERIES K: PROTECTION AGAINST INTERFERENCE Lightning protection of distributed base stations Recommendation

More information

Why the IT system is often the best choice for power supply systems of all types

Why the IT system is often the best choice for power supply systems of all types Why the IT system is often the best choice for power supply systems of all types Let us start initially with a clear commitment: the IT system ("unearthed system") is a type of system infrequently used

More information

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING 1 PRACTICAL PROBLEMS WITH SUBSTATION EARTHING Dr Hendri Geldenhuys Craig Clark Eskom Distribution Technology This paper considers the issues around substation sites where the soil resistivity is of particularly

More information

SERIES K: PROTECTION AGAINST INTERFERENCE

SERIES K: PROTECTION AGAINST INTERFERENCE I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T K.21 TELECOMMUNICTION STNDRDIZTION SECTOR OF ITU (12/2016) SERIES K: PROTECTION GINST INTERFERENCE Resistibility of telecommunication

More information

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS ENGINEERING DESIGN STANDARD EDS 08-2109 LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS Network(s): Summary: EPN, LPN, SPN This standard provides guidance on the installation of

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

In order to minimise distribution (11 and 22 kv) feeder breaker

In order to minimise distribution (11 and 22 kv) feeder breaker Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus

More information

EMC filters. Mounting instructions. Date: January 2006

EMC filters. Mounting instructions. Date: January 2006 Date: January 2006 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS prior express consent is prohibited. EMC cannot be assured

More information

Utility System Lightning Protection

Utility System Lightning Protection Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

ITU-T K.40. Protection against lightning electromagnetic pulses in telecommunication centres SERIES K: PROTECTION AGAINST INTERFERENCE

ITU-T K.40. Protection against lightning electromagnetic pulses in telecommunication centres SERIES K: PROTECTION AGAINST INTERFERENCE I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T K.40 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (01/2018) SERIES K: PROTECTION AGAINST INTERFERENCE Protection against lightning

More information

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor Leong Bee Keoh 1, Mohd Wazir Mustafa 1, Sazali P. Abdul Karim 2, 1 University of Technology Malaysia, Power Department,

More information

SERIES K: PROTECTION AGAINST INTERFERENCE

SERIES K: PROTECTION AGAINST INTERFERENCE I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T K.21 TELECOMMUNICTION STNDRDIZTION SECTOR OF ITU (07/2017) SERIES K: PROTECTION GINST INTERFERENCE Resistibility of telecommunication

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

Three-phase monitoring relay

Three-phase monitoring relay 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Practical Lightning Mitigation

Practical Lightning Mitigation Practical Lightning Mitigation Jerry Hogan MBA, BSEE Director of Engineering, Solara Technical Sales Jerry Hogan, MBA, BSEE Director of Eng. Solara Technical Sales BSEE, University of Colorado MBA, University

More information

VBS TBS KTS BSS LFS UFS

VBS TBS KTS BSS LFS UFS VBS TBS KTS BSS LFS UFS TBS. Surge protection systems Order information and technical data Protection and isolating spark gaps Protection spark gap or isolating spark gap? Isolating spark gaps Protection

More information

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of: 1 PAPER 5 Sample Questions A- C&G 2382 17th Edition Paper A 1 o/c1 BS 7671 does not apply to a equipment of aircraft b photovoltaic systems c marinas d fairgrounds. 2 o/c1 Where protection for persons

More information

Module Title: Electrical Installation II Laboratory Sheet:

Module Title: Electrical Installation II Laboratory Sheet: Vocational Training Council Hong Kong Institute of Vocational Education Department of Engineering Module Title: Electrical Installation II Laboratory Sheet: Student name: Course / Year: Subject: Date:

More information

The Lightning Event. White Paper

The Lightning Event. White Paper The Lightning Event White Paper The Lightning Event Surge Protection Solutions for PTC 1 The Lightning Event There are volumes of information available on what we believe lightning is and how we think

More information

Choice of earth leakage protection devices

Choice of earth leakage protection devices Protection Choice of earth leakage protection devices DB123167 DB123168 DB123169 Choice of sensitivity The sensitivity of an earth leakage protection device depends mainly on the function it has to perform:

More information

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER Customer : REV. 0 Page 1/16 Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INRUMENTRANSFORMER CVS - 24 - G - Revision Prepared Description Checked by Rev. Date by 0 13/06/16 First issue E.

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

Distribution systems and protection against indirect contact and earth fault

Distribution systems and protection against indirect contact and earth fault 3 April 2008 1SDC007102G0202 Technical Application Papers Distribution systems and protection against indirect contact and earth fault Technical Application Papers Distribution systems and protection

More information

ITU-T K.120. Lightning protection and earthing of a miniature base station SERIES K: PROTECTION AGAINST INTERFERENCE. Recommendation ITU-T K.

ITU-T K.120. Lightning protection and earthing of a miniature base station SERIES K: PROTECTION AGAINST INTERFERENCE. Recommendation ITU-T K. I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T K.120 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (12/2016) SERIES K: PROTECTION AGAINST INTERFERENCE Lightning protection

More information

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg Coupling modes Véronique Beauvois, Ir. 2015-2016 General problem in EMC = a trilogy Parameters Amplitude Spectrum Source (disturbing) propagation Coupling modes Victim (disturbed) lightning electrostatic

More information