Chicago Zoological Society
|
|
- Debra Pope
- 5 years ago
- Views:
Transcription
1 3300 Golf Road Brookfield, Illinois 6053 E0.0 E0. E0.2 E0.3 E0.4 E0.5 E0.6 DRAWING LIST GENERAL NOTES SYMBOL LIST AND SPECIFICATIONS WIRING DIAGRAM VOLTAGE DROP DIAGRAM PANEL SCHEDULES DETAILS SHEET DETAILS SHEET 2 EG_0 EG_0 EG_0 EG_0 EG_0 EG_0 EG_02 E.0 /6"='-0" SITE LIGHTING NORTH ENTRANCE NORTH OF 3ST ST. RUN EL_Site E. /6"='-0" SITE LIGHTING NORTH ENTRANCE SOUTH OF 3ST ST. RUN EL_Site E.2 E.3 E.4 E.5 E.6 /6"='-0" /6"='-0" /6"='-0" /6"='-0" /6"='-0" SITE LIGHTING PACHYDERM BLDG SOUTH RUN /3 SITE LIGHTING PACHYDERM BLDG SOUTH RUN 2/3 SITE LIGHTING PACHYDERM BLDG SOUTH RUN 3/3 SITE LIGHTING EAST NORTH AND SOUTH RUNS SITE LIGHTING RUNS EL_Site EL_Site EL_Site EL_Site EL_Site 4 4 Total Number of Drawings DRAWING LIST 3st B AUSTRALIAN GIRAFFE EHIBIT HARBOR SEAL EHIBIT EHIBIT PACHYDERM FIRST (st) I B E FORMAL REPTILE N S P E SLOTH S PONI ES GREEN, LUNCHROOM WARE POWER COVER SHEET DRAWING LIST GENERAL NOTES LOCATION MAP ARENA KEY PLAN E0.0
2 ABBREVIATIONS ONE-LINE ELECTRICAL DIAGRAM SYMBOL LIGHTING SWITCHES RECEPTACLES RACEWAYS AND WIREWAYS CONDUIT PART - ELECTRICAL WORK. GENERAL CONDITIONS A. THE WORD PROVIDE MEANS THE CONTRACTOR SHALL FURNISH AND INSTALL. B. PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR A COMPLETE AND FULLY OPERATIONAL ELECTRICAL SYSTEM AND INSTALLATION. C. MATERIALS AND INSTALLATION SHALL COMPLY WITH OWNER ARDS AND ALL CODES, LAWS, AND ORDINANCES OF FEDERAL, STATE, AND LOCAL GOVERNING BODIES HAVING JURISDICTION. D. ALL MATERIALS AND EQUIPMENT SHALL BE LISTED AND/OR LABELED BY UL, ETL, CSA, OR ANOTHER CITY CODE RECOGNIZED TESTING LABORATORY. E. SECURE AND PAY FOR ALL PERMITS, GOVERNMENTAL FEES TAES AND LICENSES NECESSARY FOR THE PROPER EECUTION AND COMPLETION OF ALL ELECTRICAL WORK. F. PREPARE AND SUBMIT TO OWNER, GOVERNMENTAL AGENCIES, AND LOCAL CODE OFFICIALS, SHOP DRAWINGS AND/OR INSTALLATION DETAILS WHICH ARE REQUIRED BY THESE AGENCIES FOR THEIR REVIEW AND APPROVAL. G. NOTIFY THE OWNER IN WRITING OF ANY MATERIALS, INSTALLATIONS OR APPARATUS BELIEVED TO BE INADEQUATE, UNSUITABLE, IN VIOLATION OF LAWS, ORDINANCES, RULES, OR REGULATIONS OF THE AUTHORITIES HAVING JURISDICTION PRIOR TO PURCHASE AND INSTALLATION. H. CAREFULLY EAMINE THE CONTRACT DOCUME AND MAKE A SCHEDULED ARRANGEMENT WITH THE OWNER TO VISIT THE SITE AND BECOME THOROUGHLY FAMILIAR WITH EISTING CONDITIONS RELATING TO THE WORK. FAILURE TO DO SO WILL NOT RELIEVE THE CONTRACTOR OF THE OBLIGATIONS OF THE CONTRACT AND REFERENCES NOTED ABOVE. I. NUMBERED CIRCUITS SHOWN ON PLAN ARE FOR THE CONVEYANCE OF DESIGN INTENT ONLY. ACTUAL FIELD CONDITIONS MAY AFFECT CIRCUITRY. INDICATE THE ACTUAL (AS-BUILT) CIRCUIT NUMBERS INSTALLED AND PANELBOARD ORIGINATION ON THE "AS-BUILT" DRAWINGS. J. WHERE CONDUIT RACEWAY SYSTEMS ARE SHOWN ON THE DRAWINGS, IT IS SHOWN DIAGRAMMATICALLY. THE EACT ROUTING OF THE EISTING CONDUIT RACEWAY SYSTEMS SHALL BE DETERMINED ON THE JOB SITE BY THE CONTRACTOR. K. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CONSTRUCTION DOCUME. IN THE EVENT THAT MORE STRINGENT REQUIREME THAN THOSE DESCRIBED HEREIN ARE SET FORTH UNDER EFFECTIVE UPDATED CODES, LAWS, AND ORDINANCES OF FEDERAL, STATE, AND LOCAL GOVERNING BODIES HAVING JURISDICTION, THE GREATER REQUIREME SHALL BE COMPLIED WITH. SUBMIT WRITTEN STATEMENT OF COMPLIANCE, ECLUSIONS AND EEMPTIONS IF ANY, TO ARCHITECT/ENGINEER AND OWNER PRIOR TO FINAL BID ACCEPTANCE. L. EISTING CONDITIONS OF ALL EISTING EQUIPMENT, DEVICES, FITURES, AND SYSTEMS THAT REQUIRE REWIRING, REUSE, RELOCATION, OR REFURBISHING AS PER DRAWINGS AND SPECIFICATIONS SHALL BE FIELD VERIFIED PRIOR TO COMMENCEMENT OF ANY WORK TO BE COMPLETELY OPERATIONAL. CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT AND ITEMIZED LISTING OF ALL EISTING UNSUITABLE CONDITIONS. M. SUBMIT THE WRITTEN STATEMENT TO THE OWNER PRIOR TO WORK. IN THE EVENT THAT THE CONTRACTOR COMMENCES WORK WITHOUT SUBMITTAL, ASSUME ALL RESPONSIBILITY AND COST TO MAINTAIN THE ABOVE IN GOOD WORKING ORDER AND CONDITION. N. WHERE THE INSTALLATION OF NEW CONSTRUCTION SURFACES OR MATERIALS RENDERS AN EISTING JUNCTION BO, PULL BO OR OTHER ELECTRICAL EQUIPMENT INACCESSIBLE, RELOCATE THESE ITEMS TO MAINTAIN THE REQUIRED ACCESSABILITY..2 ELECTRICAL INSTALLATION A. PROVIDE TEMPORARY POWER AND WIRING FOR THE ENTIRE PERIOD OF DEMOLITION AND CONSTRUCTION AND REMOVE ALL TEMPORARY WIRING AT THE COMPLETION OF CONSTRUCTION. B. ALL MATERIALS AND EQUIPMENT SHALL BE ERECTED, INSTALLED, TOOLED, CONNECTED, CLEANED, ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS, INCLUDING UL REQUIREME. C. PERFORM ALL CUTTING, DRILLING, ECAVATION AND PATCHING OF EISTING PATHWAYS OR OTHER EQUIPMENT IN ORDER THAT WORK MAY BE PROPERLY INSTALLED. VERIFY LOCATION OF UNDERGROUND UTILITIES BEFORE ECAVATION. UNDER NO CONDITIONS MAY STRUCTURAL WORK BE MODIFIED OR CUT, ECEPT AT THE DIRECTION OF THE OWNER. D. ALL MATERIAL, EQUIPMENT, WIRING DEVICES, ETC. SHALL BE NEW AND OF COMMERCIAL GRADE, UNO. E. ALL WORK REQUIRED FOR THE ELECTRICAL INSTALLATION AS SHOWN ON CONSTRUCTION DOCUME SHALL INCLUDE ALL LABOR, INSTALLATION METHODS, EQUIPMENT, AND MATERIALS. F. PROVIDE A COMPLETE RACEWAY SYSTEM, FITTINGS AND ENCLOSURES FOR ALL ELECTRICAL WIRING SYSTEMS TO BE INSTALLED FOR THE PROJECT. G. CONDUITS ROUTED BELOW GRADE SHALL BE SCHEDULE 40 PVC. H. PROVIDE 3" ENCASEMENT FOR CONDUIT INSTALLED UNDER ROADWAYS..3 FIRE SEAL SYSTEMS A. PROVIDE 3M FIRESEAL SYSTEMS FOR ALL CORES AND RACEWAY PENETRATIONS IN FIRE RATED WALLS AND FLOORS. FIRESEAL ALL WALL AND FLOOR PENETRATIONS, ETC. UTILIZING UL LISTED 3M PRODUCTS INSTALLED AS PER MANUFACTURER'S INSTRUCTIONS TO MAINTAIN EISTING AND NEW FIRE RATINGS. VERIFY EACT FIRE RATING CONDITIONS AND LOCATIONS PRIOR TO FINAL BIDS. ALL OPEN CONDUIT SLEEVE PENETRATIONS SHALL BE FIRE SEALED INSIDE AND OUTSIDE AFTER ALL CABLING IS COMPLETELY INSTALLED. FIRE SEAL METHODS AT SLEEVES SHALL BE SUBJECT TO THE APPROVAL OF THE CABLING CONTRACTOR. PROVIDE CAPS FOR UNUSED CONDUIT SLEEVES AND FIRE SEAL TO MAINTAIN THE ORIGINAL FIRE RATING OF THE FLOOR SLAB INCLUDING EISTING CORES THAT ARE NOT TO RE REUSED. VERIFY EACT QUANTITIES OF PENETRATIONS IN THE FIELD. PART 2-2. SERVICE AND DISTRIBUTION BASIC MATERIALS AND METHODS A. ALL NEW ELECTRICAL WORK SHALL BE INSTALLED AS INDICATED ON THE ELECTRICAL DISTRIBUTION DIAGRAM. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF ALL EQUIPMENT TO BE INSTALLED INDICATING ELECTRICAL FLOOR PLAN LAYOUT, ELEVATIONS, AND ALL DIMENSIONS FOR APPROVAL OF OWNER PRIOR TO INSTALLATION. CODE REQUIRED CLEARANCES IN FRONT OF ALL ELECTRICAL EQUIPMENT SHALL BE MAINTAINED AT ALL TIMES FOR EISTING AND NEW EQUIPMENT. B. ALL CIRCUIT BREAKERS SHALL BE BOLT ON TYPE. AIC RATING OF NEW CIRCUIT BREAKER SHALL MATCH AIC RATING OF PANELBOARD IN WHICH IT IS INSTALLED. C. PROVIDE A TYPE WRITTEN PANEL DIRECTORY AT THE COMPLETION OF THE PROJECT FOR EACH PANEL. EACH CIRCUIT BREAKER SHALL BE LABELED TO IDENTIFY LOAD. PROVIDE COPIES OF ALL PANELBOARD DIRECTORIES TO THE OWNER UPON COMPLETION. PART 3 - EECUTION 3. SUBMITTALS/AS-BUILTS A. PROVIDE A WRITTEN GUARANTEE THAT THE ELECTRICAL INSTALLATION IS FREE FROM MECHANICAL AND ELECTRICAL DEFECTS. CONTRACTOR SHALL AT THEIR SOLE COST, REPLACE AND/OR REPAIR, TO THE SATISFACTION OF THE OWNER AND TO COMPLY WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, ANY PARTS OF THE INSTALLATION WHICH MAY FAIL WITHIN A PERIOD OF 2 MONTHS FROM CONSTRUCTION WRITTEN ACCEPTANCE, IN ACCORDANCE WITH THE CONTRACT DOCUME, PROVIDED THAT SUCH FAILURE IS DUE TO DEFECTS IN MATERIAL, WORKMANSHIP, OR FAILURE TO FOLLOW THE SPECIFICATIONS, MANUFACTURER'S INSTALLATION INSTRUCTIONS AND/OR DRAWINGS. PROVIDE WARRANTIES FOR ALL EQUIPMENT EPRESSED BY THE MANUFACTURER BEYOND 2 MONTHS. B. SHOP DRAWINGS SHALL INCLUDE MANUFACTURER'S NAMES, CATALOG NUMBERS, PRODUCT LITERATURE, DIAGRAMS, AND OTHER SUCH DESCRIPTIVE DATA AS MAY BE REQUIRED TO IDENTIFY AND REVIEW THE EQUIPMENT. SUBMITTALS SHALL BE IN LOGICAL GROUPS (FOR EAMPLE ALL LIGHTING FITURES). PARTIAL SUBMITTALS WILL NOT BE REVIEWED. SUBSTITUTION OF MATERIALS SUBMITTED IN SHOP DRAWINGS SHALL BE APPROVED BY OWNER AND ENGINEER/ARCHITECT IN WRITING PRIOR TO SUBMITTAL. DETERMINATION OF EQUALITY TO BE MADE BY ENGINEER PRIOR TO APPROVAL. C. SUBMIT TWO COPIES OF THE FOLLOWING SHOP DRAWINGS FOR REVIEW: DISTRIBUTION EQUIPMENT AND PANELBOARDS WIRING DEVICES OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY. SUBMITTALS SHALL BE IN DIGITAL AND WRITTEN FORM. SUBMITTALS SHALL INCLUDE: FAULT CURRENT STUDY REPORT PER IEEE 4 AND 242 COORDINATION STUDY INPUT DATA ARC FLASH STUDY REPORT PER NFPA-70E D. PROVIDE AS-BUILT CAD FILES AND TWO HARD COPY AS-BUILT DRAWING SETS AT THE COMPLETION OF THE PROJECT. SUBMIT AS-BUILTS TO THE OWNER. AS-BUILT DRAWINGS SHALL INDICATE EACT CIRCUIT NUMBERS, LOCATIONS OF ALL EQUIPMENT AND RACEWAY FOR POWER DISTRIBUTION SYSTEMS AS INSTALLED. DRAWING FORMAT FOR AS-BUILTS SHALL BE AUTOCAD DWG FORMAT VERSION 207 OR HIGHER OR DF. E. PROVIDE AS-BUILT SINGLE LINE DIAGRAMS. F. PROVIDE OPERATING AND MAINTENANCE MANUALS INCLUDING THE FOLLOWING:. EQUIPMENT RATINGS AND SELECTED OPTIONS. 2. REQUIRED ROUTINE MAINTENANCE PROCEDURES. 3. IDENTIFICATION OF QUALIFIED SERVICE AGENCY. 4. COMPLETE OPERATIONAL NARRATIVE. G. AS-BUILT DOCUME SHALL INCLUDE UPDATE TO SITE ELECTRICAL ONE LINE DIAGRAMS. CONTRACTOR SHALL CONTACT OWNER TO OBTAIN DRAWINGS OF ELECTRICAL DIAGRAMS. UPDATE APPLICABLE SECTIONS OF DIAGRAM AFFECTED BY THIS PROJECT AND INDICATE ON AS-BUILT SUBMITTALS. PANELBOARDS O. VERIFY CLEARANCES FOR ALL ELECTRICAL WORK BEFORE PROCEEDING WITH CONSTRUCTION. COORDINATE USAGE OF AVAILABLE SPACE WITH THE OWNER. IN THE EVENT OF CONFLICTS, NOTIFY THE OWNER BEFORE PROCEEDING WITH THE WORK. P. ALL CONDUITS SHALL RUN CONTINUOUS WITHOUT ANY UNDERGROUND SPLICES. SPLICING OF CONDUCTORS WILL BE PERMITTED ONLY IN THE BASE OF THE LIGHTING UNITS AND IN PULL BOES. Q. LANDSCAPING FLOODLIGHT LUMINAIRES SHALL BE ORIENTED WITH THE OPTICS PERPENDICULAR TO THE LANDSCAPING UNLESS OTHERWISE INDICATED OR DIRECTED BY THE OWNER. THE LUMINAIRES MAY REQUIRE NIGHT-TIME OPTICAL ADJUSTMENT UPON INSPECTION BY THE OWNER. SYMBOL LIST AND SPECIFICATIONS E0.
3 LIGHT POLE WIRING DIAGRAM WIRING DIAGRAM E0.2
4 7 PLANTERS RUN VOLTAGE DROP DIAGRAM 6 NORTH RUN VOLTAGE DROP DIAGRAM 5 EAST SOUTH RUN VOLTAGE DROP DIAGRAM 4 EAST NORTH RUN VOLTAGE DROP DIAGRAM 3 PACHYDERM BLDG SOUTH RUN VOLTAGE DROP DIAGRAM 2 NORTH ENTRANCE SOUTH OF 3ST ST. RUN VOLTAGE DROP DIAGRAM VOLTAGE DROP DIAGRAMS NORTH ENTRANCE NORTH OF 3ST ST. RUN VOLTAGE DROP DIAGRAM E0.3
5 Designation: NW PARKING MAIN TYPE: MB MOUNTING: SURFACE OCP TYPE: MOLDED CASE C/B Voltage: BUS AMPS: 225A ENCLOSURE: NEMA 4 FAULT DUTY: 0KAIC PH 3W GROUND BUS: YES NEUTRAL BUS: 00% RATED SPD: NO No. Description A B Size Size A B Description No. EISTING LOAD 20A 20A EISTING LOAD A 688 PATH LTG: NORTH ENTRY 4 20A* 5 EISTING LOAD 20A 688 NORTH OF 3ST ST 6 7 EISTING LOAD 20A 20A 8 9 EISTING LOAD 20A 20A 0 EISTING LOAD 20A 20A EISTING LOAD 2 3 EISTING LOAD 20A 20A EISTING LOAD 4 5 EISTING LOAD 20A 20A EISTING LOAD 6 7 EISTING LOAD 20A 20A EISTING LOAD 8 9 EISTING LOAD 20A 20A EISTING LOAD 20 2 EISTING LOAD 20A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD 28 5 EISTING LOAD 20A 20A EISTING LOAD 6 7 EISTING LOAD 20A 20A EISTING LOAD 8 9 EISTING LOAD 20A 20A EISTING LOAD 20 2 EISTING LOAD 20A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD 30 Total Total Total Phase A: 688 VA Total Connected Load:.38 kva Total Phase B: 688 VA 6.62 Amps Designation: MEMBERSHIP MAIN TYPE: MB MOUNTING: SURFACE OCP TYPE: MOLDED CASE C/B Voltage: BUS AMPS: 225A ENCLOSURE: NEMA 4 FAULT DUTY: 0KAIC PH 3W GROUND BUS: YES NEUTRAL BUS: 00% RATED SPD: NO No. Description A B Size Size A B Description No. 20A 20A A 20A EISTING LOAD 4 5 EISTING LOAD 20A 20A EISTING LOAD 6 7 EISTING LOAD 20A 20A EISTING LOAD 8 9 EISTING LOAD 20A 20A EISTING LOAD 0 EISTING LOAD 20A 20A EISTING LOAD 2 3 EISTING LOAD 20A 20A EISTING LOAD 4 5 EISTING LOAD 20A 20A EISTING LOAD 6 7 EISTING LOAD 20A 20A EISTING LOAD 8 9 EISTING LOAD 20A 688 PATH LTG: NORTH ENTRY 20 20A* 2 EISTING LOAD 20A 688 SOUTH 0F 3ST ST EISTING LOAD 20A 20A A 20A A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD 30 3 EISTING LOAD 20A 20A EISTING LOAD A 20A EISTING LOAD A 20A EISTING LOAD A 39 20A 60A EISTING LOAD A 42 Total Total Total Phase A: 688 VA Total Connected Load:.38 kva Total Phase B: 688 VA 5.73 Amps Designation: SL- MAIN TYPE: MB MOUNTING: SURFACE OCP TYPE: MOLDED CASE C/B Voltage: BUS AMPS: 225A ENCLOSURE: NEMA 4 FAULT DUTY: 0KAIC PH 3W GROUND BUS: YES NEUTRAL BUS: 00% RATED SPD: NO No. Description A B Size Size A B Description No. 2 EISTING EISTING 80A 80A 3 BLDG SL AUSTRALIAN BLDG SL 4 5 EISTING HABITAT 6 80A 80A EISTING LOAD 7 AFRICA SL 8 9 PATH LTG: PACHYDERM PATH LTG: PACHYDERM 0 20A* 20A* BLDG SOUTHWEST BLDG SOUTHEAST 2 3 SPACE SPACE 4 5 SPACE SPACE 6 7 SPACE SPACE 8 Total Total 38 Designation: SL- MAIN TYPE: MB MOUNTING: SURFACE OCP TYPE: MOLDED CASE C/B Voltage: BUS AMPS: 225A ENCLOSURE: NEMA 4 FAULT DUTY: 0KAIC PH 3W GROUND BUS: YES NEUTRAL BUS: 00% RATED SPD: NO No. Description A B Size Size A B Description No. EISTING LION EISTING FRAGILE 2 80A 80A 3 RD SL KINGDOM SL 4 5 EISTING DOLPHIN 6 80A 80A 7 BLDG SL 8 9 PATH LTG: NORTH PATH LTG: 0 20A* 20A* PLAYGROUND NORTHWEST 2 3 SPACE SPACE 4 5 SPACE SPACE 6 Total Total Total Phase A: 2063 VA Total Connected Load: 4.3 kva Total Phase B: 2063 VA 7.9 Amps Designation: S MAIN TYPE: MB MOUNTING: SURFACE OCP TYPE: MOLDED CASE C/B Voltage: BUS AMPS: 400A ENCLOSURE: NEMA 4 FAULT DUTY: 0KAIC PH 3W GROUND BUS: YES NEUTRAL BUS: 00% RATED SPD: NO No. Description A B Size Size A B Description No. PATH LTG: A* 3 SOUTHWEST A 4 5 PATH LTG: SOUTHEAST A* 9 60A 0 20A A EISTING LOAD 4 20A 5 20A EISTING LOAD A EISTING LOAD 8 20A 9 20A EISTING LOAD A EISTING LOAD 22 20A 23 20A EISTING LOAD A 20A EISTING LOAD EISTING LOAD 20A 20A EISTING LOAD A 20A EISTING LOAD A A 35 EISTING STING RAY 36 50A 37 MERCH FEEDERS 38 20A A 42 Total Total Total Phase A: 53 VA Total Connected Load: 3.03 kva Total Phase B: 53 VA 4.55 Amps Designation: NORTH BUGGY MAIN TYPE: MB MOUNTING: SURFACE OCP TYPE: MOLDED CASE C/B Voltage: BUS AMPS: 225A ENCLOSURE: NEMA 4 FAULT DUTY: 0KAIC PH 3W GROUND BUS: YES NEUTRAL BUS: 00% RATED SPD: NO No. Description A B Size Size A B Description No. EISTING LOAD 20A 20A EISTING LOAD 2 3 EISTING LOAD 20A 20A EISTING LOAD 4 5 EISTING LOAD 20A 20A EISTING LOAD 6 7 EISTING LOAD 20A 20A EISTING LOAD 8 9 EISTING LOAD 20A 20A EISTING LOAD 0 EISTING LOAD 20A 20A EISTING LOAD 2 3 PATH LTG: DISCOVERY 43 20A EISTING LOAD 4 20A* 5 CENTER NORTH 43 20A EISTING LOAD PATH LTG: DISCOVERY CENTER PLANTERS PATH REC: DISCOVERY CENTER PLANTERS 26 20A* 20A EISTING LOAD A* 20A A 20A A 20A A 20A A 20A A 20A 30 Total Total Total Phase A: 539 VA Total Connected Load:.3 kva Total Phase B: 773 VA 5.47 Amps PANEL SCHEDULES Total Phase A: 788 VA Total Connected Load: 3.58 kva Total Phase B: 788 VA 4.90 Amps PANEL SCHEDULES E0.4
6 H N G H H G TYPICAL SPLICE DETAIL 4 G LIGHT POLE ELECTRICAL WIRING DETAIL 2 SECO LIGHTING CONTROL CONNECTION DETAIL 3 TRENCH DETAILS DETAILS SHEET E0.5
7 PULL BO DETAIL 3 DETAILS SHEET 2 EISTING PANELBOARD FOUNDATION DETAIL 2 LIGHT POLE FOUNDATION DETAIL E0.6
8 W E T L A N D I N D I A N L A K E T H I R T Y - F I R S T 5 MOUSE COLONY ROUND ONE STORY BRICK #25 WOLF HABITAT ARICA! 2 4 ONE STORY METAL BLDG #4 PENGUIN COAST GIRAFFE/KOPJE FLIGHT CAGE ENTERPRISE 3 GIRAFFE EHIBIT AQUATIC BIRDS EHIBIT I B E AARDVARK CORRAL ANIMAL HOSPITAL 3 4 B FORMAL PERCHING BIRD 2 POWER REPTILE, LUNCHROOM AUSTRALIAN PACHYDERM PEN GREEN WARE THE SWAMP PACHY EAST MEMBERSHIP WEST WING S WO TEMPORARY SOUTH ENTRY EAST WING S SOUTH PARKING LOT ECO ADMIN. ANNE LION WEST 3st GUEST SERVICES FRAGILE KINGDOM LION SLOTH S SOUTH GATE TICKET BOOTHS DENS NORTHEAST PARKING LOT PONIES HARBOR SEAL EHIBIT NEW TOILETS PINNIPED S PINNIPED A R E N A O A K G R O V E P I C N I C CZ LIFE SUPPORT T/F = DOLPHIN PET COGEN. H E A V I L Y CONSERVATION KEEPER VIEWING GALLERY DESIGN P E N S FOUNTAIN F I R S T ( s t ) A V E N U E SITE LIGHTING NORTH ENTRANCE NORTH 0F 3ST ST. RUN KEYPLAN NORTH ENTRANCE NORTH OF 3ST ST. RUN E.0
9 W E T L A N D I N D I A N L A K E T H I R T Y - F I R S T 5 MOUSE COLONY ROUND ONE STORY BRICK #25 WOLF HABITAT ARICA! 2 4 ONE STORY METAL BLDG #4 PENGUIN COAST GIRAFFE/KOPJE FLIGHT CAGE ENTERPRISE 3 GIRAFFE EHIBIT AQUATIC BIRDS EHIBIT I B E AARDVARK CORRAL ANIMAL HOSPITAL 3 4 B FORMAL PERCHING BIRD 2 POWER REPTILE, LUNCHROOM AUSTRALIAN PACHYDERM PEN GREEN WARE THE SWAMP PACHY EAST MEMBERSHIP WEST WING S WO TEMPORARY SOUTH ENTRY EAST WING S SOUTH PARKING LOT ECO ADMIN. ANNE LION WEST 3st GUEST SERVICES FRAGILE KINGDOM LION SLOTH S SOUTH GATE TICKET BOOTHS DENS NORTHEAST PARKING LOT PONIES HARBOR SEAL EHIBIT NEW TOILETS PINNIPED S PINNIPED A R E N A O A K G R O V E P I C N I C CZ LIFE SUPPORT T/F = DOLPHIN PET COGEN. H E A V I L Y MEMB OFFIC CONSERVATION KEEPER VIEWING GALLERY DESIGN P E N S FOUNTAIN F I R S T ( s t ) A V E N U E SITE LIGHTING NORTH ENTRANCE SOUTH OF 3ST ST. RUN NORTH ENTRANCE SOUTH OF 3ST ST. RUN KEYPLAN E.
10 W E T L A N D I N D I A N L A K E T H I R T Y - F I R S T 5 MOUSE COLONY ROUND ONE STORY BRICK #25 WOLF HABITAT ARICA! 2 4 ONE STORY METAL BLDG #4 PENGUIN COAST GIRAFFE/KOPJE FLIGHT CAGE ENTERPRISE 3 GIRAFFE EHIBIT AQUATIC BIRDS EHIBIT I B E AARDVARK CORRAL ANIMAL HOSPITAL 3 4 B FORMAL PERCHING BIRD 2 POWER REPTILE, LUNCHROOM AUSTRALIAN PACHYDERM PEN GREEN WARE THE SWAMP PACHY EAST MEMBERSHIP WEST WING S WO TEMPORARY SOUTH ENTRY EAST WING S SOUTH PARKING LOT ECO ADMIN. ANNE LION WEST 3st GUEST SERVICES FRAGILE KINGDOM LION SLOTH S SOUTH GATE TICKET BOOTHS DENS NORTHEAST PARKING LOT PONIES HARBOR SEAL EHIBIT NEW TOILETS PINNIPED S PINNIPED A R E N A O A K G R O V E P I C N I C CZ LIFE SUPPORT T/F = DOLPHIN PET COGEN. H E A V I L Y P CONSERVATION KEEPER VIEWING GALLERY DESIGN P E N S FOUNTAIN F I R S T ( s t ) A V E N U E SITE LIGHTING PACHYDERM BLDG SOUTH RUN /3 PACHYDERM BLDG SOUTH RUN KEYPLAN E.2
11 W E T L A N D I N D I A N L A K E T H I R T Y - F I R S T 5 MOUSE COLONY ROUND ONE STORY BRICK #25 WOLF HABITAT ARICA! 2 4 ONE STORY METAL BLDG #4 PENGUIN COAST GIRAFFE/KOPJE FLIGHT CAGE ENTERPRISE 3 GIRAFFE EHIBIT AQUATIC BIRDS EHIBIT I B E AARDVARK CORRAL ANIMAL HOSPITAL 3 4 B FORMAL PERCHING BIRD 2 POWER REPTILE, LUNCHROOM AUSTRALIAN PACHYDERM PEN GREEN WARE THE SWAMP PACHY EAST MEMBERSHIP WEST WING S WO TEMPORARY SOUTH ENTRY EAST WING S SOUTH PARKING LOT ECO ADMIN. ANNE LION WEST 3st GUEST SERVICES FRAGILE KINGDOM LION SLOTH S SOUTH GATE TICKET BOOTHS DENS NORTHEAST PARKING LOT PONIES HARBOR SEAL EHIBIT NEW TOILETS PINNIPED S PINNIPED A R E N A O A K G R O V E P I C N I C CZ LIFE SUPPORT T/F = DOLPHIN PET COGEN. H E A V I L Y PACHYDERM CONCRET CONSERVATION KEEPER VIEWING GALLERY DESIGN P E N S FOUNTAIN F I R S T ( s t ) A V E N U E SITE LIGHTING PACHYDERM BLDG SOUTH RUN 2/3 PACHYDERM BLDG SOUTH RUN KEYPLAN E.3
12 W E T L A N D I N D I A N L A K E T H I R T Y - F I R S T 5 MOUSE COLONY ROUND ONE STORY BRICK #25 WOLF HABITAT ARICA! 2 4 ONE STORY METAL BLDG #4 PENGUIN COAST GIRAFFE/KOPJE FLIGHT CAGE ENTERPRISE 3 GIRAFFE EHIBIT AQUATIC BIRDS EHIBIT I B E AARDVARK CORRAL ANIMAL HOSPITAL 3 4 B FORMAL PERCHING BIRD 2 POWER REPTILE, LUNCHROOM AUSTRALIAN PACHYDERM PEN GREEN WARE THE SWAMP PACHY EAST MEMBERSHIP WEST WING S WO TEMPORARY SOUTH ENTRY EAST WING S SOUTH PARKING LOT ECO ADMIN. ANNE LION WEST 3st GUEST SERVICES FRAGILE KINGDOM LION SLOTH S SOUTH GATE TICKET BOOTHS DENS NORTHEAST PARKING LOT PONIES HARBOR SEAL EHIBIT NEW TOILETS PINNIPED S PINNIPED A R E N A O A K G R O V E P I C N I C CZ LIFE SUPPORT T/F = DOLPHIN PET COGEN. H E A V I L Y DING CONSERVATION KEEPER VIEWING GALLERY DESIGN P E N S FOUNTAIN F I R S T ( s t ) A V E N U E SITE LIGHTING PACHYDERM BLDG SOUTH RUN 3/3 KEYPLAN PACHYDERM BLDG SOUTH RUN E.4
13 T H I R T Y - F I R S T 3st WO TEMPORARY CONSERVATION O O D E D A R E A W ONE STORY METAL BLDG #4 3 4 B COGEN. MEMBERSHIP NORTHEAST PARKING LOT W O AUSTRALIAN O D E D A R E WETLAND A GIRAFFE EHIBIT GUEST SERVICES AARDVARK LIFE SUPPORT T/F = W O O CORRAL D E D FRAGILE KINGDOM PINNIPED A ONE STORY BRICK #25 R E A GIRAFFE/KOPJE HARBOR SEAL EHIBIT LION PINNIPED S HABITAT ARICA! 2 EHIBIT PACHYDERM LION WEST DOLPHIN PACHY EAST DS OM WOOHRO INDIAN WAS LAKE FOUNTAIN I B E W O O D E D RI OM ITU RO SH WA (st) DENS CZ ND STA FIRST ING VIEW ERY GALL NEW PEN KEEPER FLIGHT CAGE AQUATIC BIRDS FORMAL TOILETS REPTILE WOLF THE SWAMP N S P E MOUSE COLONY SLOTH S OFFIC E PONIES PERCHING BIRD DESIGN PENGUIN COAST ECO ARENA GREEN ENTERPRISE ADMIN. ANNE WEST WING S SOUTH ENTRY EAST WING S ANIMAL HOSPITAL, LUNCHROOM WARE POWER PET ROUND O A K P I C N I C G R O V E H E A V I L Y W O O D E D SOUTH PARKING LOT SOUTH GATE TICKET BOOTHS KEYPLAN SITE LIGHTING EAST NORTH AND SOUTH RUNS EAST NORTH AND SOUTH RUNS E.5
14 W E T L A N D I N D I A N L A K E T H I R T Y - F I R S T 5 MOUSE COLONY ROUND ONE STORY BRICK #25 WOLF HABITAT ARICA! 2 4 ONE STORY METAL BLDG #4 PENGUIN COAST GIRAFFE/KOPJE FLIGHT CAGE ENTERPRISE 3 GIRAFFE EHIBIT AQUATIC BIRDS EHIBIT I B E AARDVARK CORRAL ANIMAL HOSPITAL 3 4 B FORMAL PERCHING BIRD 2 POWER REPTILE, LUNCHROOM AUSTRALIAN PACHYDERM PEN GREEN WARE THE SWAMP PACHY EAST MEMBERSHIP WEST WING S WO TEMPORARY SOUTH ENTRY EAST WING S SOUTH PARKING LOT ECO ADMIN. ANNE LION WEST 3st GUEST SERVICES FRAGILE KINGDOM LION SLOTH S SOUTH GATE TICKET BOOTHS DENS NORTHEAST PARKING LOT PONIES HARBOR SEAL EHIBIT NEW TOILETS PINNIPED S PINNIPED A R E N A O A K G R O V E P I C N I C CZ LIFE SUPPORT T/F = DOLPHIN PET COGEN. H E A V I L Y CONSERVATION KEEPER VIEWING GALLERY DESIGN P E N S FOUNTAIN F I R S T ( s t ) A V E N U E SITE LIGHTING RUNS RUNS KEYPLAN E.6
SECTION PANELBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section
More informationFacility Services Subgroup Preface for Divisions 21` through 28
Facility Services Subgroup Preface for Divisions 21` through 28 1.1 EXECUTIVE SUMMARY A. This document provides standards for the Consultants and Contractors producing mechanical and electrical design
More informationB. Manufacturers: Square-D, G.E. or Westinghosue.
SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationPREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!
PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling
More informationThis section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.
Basis of Design This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor. Background Information A Short Circuit and Coordination
More informationNew Co-Brand Convenience Store McPherson, Kansas SECTION BASIC METHODS AND REQUIREMENTS PART 1 - GENERAL 1.1 GENERAL CONDITIONS:
SECTION 16050 - BASIC METHODS AND REQUIREMENTS PART 1 - GENERAL 1.1 GENERAL CONDITIONS: A. The General Conditions, Supplementary General Conditions, General Requirements, and Special Conditions shall be
More informationDESIGN CHECKLIST INTRODUCTION
INTRODUCTION 1 The checklist is intended to serve as a convenient guide in design development as well as the final checking of plans and specifications for construction projects. Its main usefulness for
More informationChapter 25. Lighting Plans
Chapter 25 Lighting Plans The following are changes, additions or deletions to the January 2014, Topic #625-000-008, Plans Preparation Manual (PPM), for use on Turnpike projects only. 25.1 General Replace
More information.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal
City of Winnipeg Brady Road Landfill Site Section 01300 New Entrance and Scale Facility Page 1 of 4 SUBMITTALS 1. SHOP DRAWINGS 1.1 General.1 Arrange for the preparation of clearly identified Shop Drawings
More informationNORTHWEST FLORIDA STATE COLLEGE MONUMENT SIGNS WITH LED DISPLAYS
PREPARED FOR: FOUNDATION PLAN & STRUCTURAL NOTES DESIGNED BY: NJB DRAWN BY: NJB REVIEWED BY: BLSE S1 PREPARED FOR: FRAMING PLANS DESIGNED BY: NJB DRAWN BY: NJB REVIEWED BY: BLSE S2 PREPARED FOR: SECTION
More informationSECTION CABLE TRAYS
SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationSection. DEVELOPMENT STANDARDS City of Ellensburg ILLUMINATION STANDARDS
Section 8 City of Ellensburg ILLUMINATION STANDARDS Table of Contents STREET ILLUMINATION...3-5 GENERAL NOTES...3 INSTALLATION AND CONNECTIONS...3 MARKING...3 STAKING...3-4 TRENCH REQUIREMENTS...4 ILLUMINATION
More informationSECTION DISTRIBUTION SWITCHBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection
More informationResidential Construction Checklist Single and Two Family Construction
DATE: _ Building Inspection Submittal Requirements Residential Construction Checklist Single and Two Family Construction Submit a City of Big Spring Permit Application, checklist, and 3 complete hard copy
More informationSECTION ELECTRICAL IDENTIFICATION
SECTION 16075 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationB. Division-16 Basic Materials and Methods section apply to work specified in this section.
Section 16745 PREMISE CABLING SYSTEMS PART ONE GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
More informationA. Product Data: For each electrical identification product indicated.
SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY
SECTION 16075 - SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Provide a short-circuit, component protection, flash
More informationB. The designated coverage areas shall include both indoor and outdoor coverage.
Page 1 of 8 This Wi-Fi Section shall be included in the Contract Specifications, unless directed by the University Project Manager. Contact the UW Project Manager to determine if the design for Wi-Fi outlet
More informationSPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM
2004 Specifications CSJ 3622-01-001, ETC. SPECIAL SPECIFICATION 8398 LIGHTNING PROTECTION SYSTEM 1. Description. This Special Specification governs the design and installation of Lightning Protection System
More informationSection Meetings Section Material and Equipment. None Required
January 2000 Page 1 of 8 PART 1 GENERAL 1.01 OTHER CONTRACT DOCUMENTS 1.02 DESCRIPTION OF WORK 1.03 RELATED WORK PART 2 PRODUCTS The General Conditions of the Contract, General Requirements and Supplemental
More informationTaylor County July 2011 SECTION SHOP DRAWINGS, WORKING DRAWINGS AND SAMPLES
SECTION 01340 SHOP DRAWINGS, WORKING DRAWINGS AND SAMPLES PART 1 - GENERAL 1.1 REQUIREMENTS INCLUDED A. Contractor shall submit to the Architect/Engineer for review and exception, if any, such working
More informationSECTION 2 GENERAL REQUIREMENTS
SECTION 2 GENERAL REQUIREMENTS 2-1 ENGINEER REQUIRED: All plans and specifications for Improvements which are to be accepted for maintenance by the County and private, on-site drainage and grading shall
More informationSECTION WIREWAYS FOR RADIOLOGY EQUIPMENT
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable
More informationWhat Are Submittals?
Introduction Overview of the Submittal Process Comparison of AIA with ConsensusDOCS Architect and Contractor Obligations FAR Requirements State Licensing Requirements 1 What Are Submittals? Submittals
More informationSECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Record Documents. B. Operation and Maintenance Manuals. C. Warranties and bonds. 1.02 RELATED REQUIREMENTS SECTION 01 78 00 A. Section 01 30 00 - Administrative
More informationPROJECT LOCATION BOZEMAN HIGH SCHOOL. ELECTRICAL ENGINEER: Van Dykken Engineering 37 Spanish Peak Drive Bozeman, MT Phone:
DRAWING INDEX GENERAL C. PROJECT COVER G-WING A/V IMPROVEMENTS.0 AREA PLAN ST FLOOR SOUTH. TYP. PROJECTOR MOUNTING & PROJECTOR NOTES.2 G-WING TECHNOLOGY CABINET ELEVATIONS.3 G-WING WIRING DIAGRAM.4 G-WING
More informationSECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION
SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from
More information1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.
PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02
More informationSECTION LIGHTING PART 1- GENERAL
SECTION 16500 LIGHTING PART 1- GENERAL 1.01 WORK INCLUDED A. The Contractor shall provide all lighting fixtures, panelboards, labor, material, etc., in accordance with the preceding specifications, the
More informationADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030
ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: December 17, 2018 The following changes, additions, revisions, and/or deletions
More informationSECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL
PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.
More informationSPECIAL PROVISION Description of Project, Scope of Contract and Sequence of Work
2004 Specifications CSJ 0110-04-166 SPECIAL PROVISION 000--363 Description of Project, Scope of Contract and Sequence of Work 1. General. The work to be performed on this project consists of furnishing,
More informationCMH Architects, Inc
SECTION 16010 - ELECTRICAL GENERAL This project will be administered under a Construction Management arrangement. The Contractor responsible for the Work of this Section is responsible to review all portions
More informationCity of Palm Coast. 160 Cypress Point Parkway, Suite B-106 Palm Coast, FL Tel (386)
ITB-C-CM-14-11 Holland Park Improvements ISSU AT: July 24, 2014 BI AT: SUBJCT: INTNT: August 11, 2014 @ 2:00 PM ANUM NO. 01 City of Palm Coast 160 Cypress Point Parkway, Suite B-106 Palm Coast, FL 32164
More informationGuidelines for the Preparation of Traffic Signal & Intelligent Transportation System Plans on Design-Build Projects August 2007
Guidelines for the Preparation of Traffic Signal & Intelligent Transportation System Plans on Design-Build Projects August 2007 INTRODUCTION Use the following Guidelines in conjunction with the Traffic
More information2. Electrical rooms shall be centrally located and stacked so that feeder conduits and bus duct are run as straight and short as possible.
PART 1: GENERAL 1.01 Electrical/Telecommunications Design A. This section of the design and construction standard outlines general requirements for electrical and telecommunications designs to be performed
More informationSECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also, delete any other item or
More informationVanderbilt University Standard Specification Revised 2/6/08
SECTION 01 78 23 OPERATION AND MAINTENANCE DATA PART 1 GENERAL 1.01 RELATED SECTIONS A. Section 01 77 00 Closeout Procedures B. Section 01 78 39 Project Record Documents 1.02 SUMMARY A. This section provides
More informationSIGN PERMIT APPLICATION
SIGN PERMIT APPLICATION City of Hawaiian Gardens Community Development Department 21815 Pioneer Boulevard, Hawaiian Gardens, CA 90716 Ph: (562) 420-2641 Fax: (562) 420-8521 www.hgcity.org Please complete
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
conduit? 9/8/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Can branch circuits of different services be installed in the same Yes, see 300.3(C)(1) for conductors of different systems
More informationDIVISION 26 ELECTRICAL SECTION ELECTRICAL
DIVISION 26 ELECTRICAL SECTION 26 1000 ELECTRICAL PART 1 - GENERAL 1.1 WORK INCLUDED A. Furnish all labor, material and equipment necessary for the complete installation of the Electrical System as shown
More informationSpec Section: , Complete Elec, Comm, and Fire Alarm , Complete Elec, Comm, and Fire Alarm Data Sheets RAN/GCAN
SUBMITTAL REVIEW Submittal: No. 019.00 Spec Section: 26 0000, 28 0000 Complete Elec, Comm, and Fire Alarm Reviewed By: Laura Landon, Comma-Q Architecture Date: June 29, 2012 Project: BPS Belgrade Elementary
More informationSECTION DISTRIBUTION SWITCHBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 13 DISTRIBUTION SWITCHBOARDS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationSPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections
SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation
More information03/7/12 Issuance UTD Section Page 1 of 5 Electrical General
SECTION 26 01 00 ELECTRICAL GENERAL PART 1: GENERAL 1.1 Electrical/Telecommunications Design 1.1.1 This section of the design and construction standard outlines general requirements for electrical and
More informationELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Electrical/Telecommunications Design
PART 1: GENERAL 1.01 Electrical/Telecommunications Design A. This section of the design and construction standard outlines general requirements for electrical and telecommunications designs to be performed
More informationPOWER SERVICE DETAILS
POWER SOURCE # POLE MOUNTED SERVICE TRANSFORMER BY POWER HANDHOLE 0/0V, -PHASE, SERVICE CONDUCTORS; -# AWG SERVICE CONDUCTOR AND -# AWG GROUNDED SERVICE CONDUCTOR (NEUTRAL) SERVICE XFMR SECONDARY. A 0V
More informationREVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty
HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to
More information2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis
1 Summary 1.1 Provide a complete Arc Flash Hazard Analysis for the project indicated in the accompanying RFP. The Analysis may be performed: independent of the construction project in concert with the
More informationCITY OF NEW ROCHELLE RENOVATIONS TO FIRE STATION NO WEBSTER AVENUE, NEW ROCHELLE, NEW YORK
AREVIATIONS AFF AOVE FINISHED FLOOR AHJ AUTHORITIES HAVING JURISDICTION APPROX APPROXIMATE LDG UILDING CLG CEILING CONST CONSTRUCTION CD CEILING DIFFUSER CO CARON DIOXIDE CXA COMMISSIONING AGENT DEG DEGREES
More informationSECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)
ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX
More informationSingle-Family Dwelling Submittal Requirements
Single-Family Dwelling Submittal Requirements The purpose of this guideline is to assist our customers in preparing for plan submittal. The items listed must be included before your plans can be accepted
More informationElectrical IP Red Seal Practice Exam
Electrical IP Red Seal Practice Exam PRACTICE EXAM-3 1. What size 2 pole breaker must you use on a 3HP, 115V single phase motor? A. 40A B. 50A C. 80A. D. 100A. 2. An electrical equipment approved for use
More informationMichigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE
PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION EMERGENCY RESPONDER RADIO COVERAGE SYSTEMS
510.1 Emergency responder radio coverage in new buildings. Approved radio coverage for emergency responders shall be provided within all buildings meeting any one of the following conditions: 1. There
More informationSPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS. 1 Definitions. 2 Scope of Work. 3 Extent of Work
SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation 7 Backfilling
More informationNOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING
1 1 1 1 1 NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING NORTH CAROLINA BUILDING CODE COUNCIL Notice of Rule-making Proceedings is hereby given by NC Building Code Council in accordance with G.S.
More informationJEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia
BULLETIN NO. 6 TO THE PLANS AND SPECIFICATIONS FOR JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia EwingCole Architects.Engineers.Interior Designers.Planners
More informationADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030
ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: January 8, 2019 The following changes, additions, revisions, and/or deletions
More informationPage Electric Utility Service Specifications
T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum - UG-1 Sheet 1 of 3 87 T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum
More informationEMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL
EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION 05720 METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL EMMEGI ARCHITECTURAL FENCING is a high quality steel fencing system comprised of a hybrid
More informationMISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration
SECTION 01 340 - SHOP DRAWINGS, PRODUCT DATA AND SAMPLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other
More informationA. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following:
SECTION 01 31 00 PROJECT MANAGEMENT AND COORDINATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division
More informationSECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES
SECTION 01334 SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES PART 1 GENERAL 1.01 SUMMARY A. Submit to the ENGINEER for review, such working drawings, shop drawings, test reports and data on materials and equipment
More informationELPT 1429 RESIDENTIAL WIRING
SYLLABUS ELPT 1429 RESIDENTIAL WIRING INDUSTRIAL AND COMMERCIAL ELECTRICITY BRAZOSPORT COLLEGE LAKE JACKSON TEXAS PREPARED BY: Larry Grable DATE: September 13, 2005 INSTRUCTOR RECOMMENDED BY: RECOMMENDED
More informationRegal Series Recessed Flatwalls
Regal Series Recessed Flatwalls General Specifications The Amico Regal Series Recessed Flatwall shall be manufactured by Amico Corporation, in accordance with job specific shop drawings and documents.
More informationFor crossing under a railroad, contact the specific railroad company's engineering department.
PAGE 330524-1 SECTION 330524 SPECIFIER: This section is for the underground installation of piping by directional drilling. When specifying this method of piping installation, care must be taken to ensure
More informationUCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL
SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationUniversity of Central Florida Main Campus. Electric. Service and Meter Installations Requirements. Issued January 26 th, 2017.
University of Central Florida Main Campus Electric Service and Meter Installations Requirements Issued January 26 th, 2017 1 P a g e Table of Contents 1. GENERAL INFORMATION... 3 2. DEFINITIONS... 3 3.
More informationA. Action Submittals: Written and graphic information that requires Architect's responsive action.
SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification
More informationSECTION SUBMITTAL PROCEDURES
SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification
More informationSECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES
SECTION 01 33 23 SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES PART 1 GENERAL 1.1 DESCRIPTION A. This specification defines the general requirements and procedures for submittals. A submittal is information
More informationSTANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST
STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST Item Comments 1. The electrical plan check is approved and ready to have the electrical permit issued, pending the building permit being issued.
More information.1 Applicability: These criteria shall be applied as follows:
DESIGN CRITERIA DIVISION 4800 STREET LIGHTING 4801 GENERAL: These criteria shall be adhered to for the design of all publiclyfinanced or privately-financed traffic signal systems to be installed in the
More informationMPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA
MPA Project No. M495-C1 Refrigerated Container Storage Improvements Project Location: Conley Terminal, Boston, MA RESPONSES TO QUESTIONS and/or RFI s Date: 11/29/2017 The attention of Contractors submitting
More informationBid No. B14-02 Building 100 HVAC Improvements
Bid No. B14-02 Building 100 HVAC Improvements Addendum No. 1 This Addendum No. 1 sets forth modifications to portions of the bid and contract documents for the above-referenced work described as: Building
More informationA. Deviation from this standard must be approved by the Project Architect.
September 2012, rev. 00 26 5600 Exterior Lighting PART 1. GENERAL 1.01 Related Documents A. Deviation from this standard must be approved by the Project Architect. B. Drawings and general provisions of
More informationDOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410
DOCUMENT 009104 - ADDENDUM NO. 4 Issued to all Bidders: Date: October 14, 2015 Contract Name: Electrical Installation Contract Number: C8410 This addendum forms a part of the Bid described above. The original
More informationADDENDUM #2 September 12, 2018
Physical Plant Services Project Management 1000 Rim Drive Phone: (970) 247-7523 Fax: (970) 247-7555 Project No. 2007-130P18 Whalen Gymnasium Expansion and Renovation for Exercise Science Request for Qualifications
More informationDesign Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost
Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Adam T. Powell, PE President Emerald Engineering, Inc. Jeffrey L. Small, Sr. Senior
More informationPALM SQUARE SHOPPING CENTER TENANT SIGN CRITERIA
PALM SQUARE SHOPPING CENTER TENANT SIGN CRITERIA Approved: PC Reso No. 430 (05) September 12, 2005 Amended: PC Reso No. 583 (08) March 12, 2008 Palm Square Shopping Center Page 1 PALM SQUARE SHOPPING CENTER
More informationUNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ
SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 General
More informationSECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Coordination. B. Preconstruction meeting. C. Progress meetings. D. Preinstallation conferences. E. Requests for information (RFI). F. Coordination drawings.
More informationSECTION 5 TRANSFORMERS
SECTION 5 TRANSFORMERS Necessary transformers will be installed and maintained by The City of Aspen. The City of Aspen will not furnish transformers unless they are of standard size and voltage as established
More informationGuidelines for the Preparation of ITS & Signal Plans by Private Engineering Firms
Guidelines for the Preparation of ITS & Signal Plans by Private Engineering Firms INTRODUCTION Use the following Guidelines in conjunction with the ITS & Signals Scope of work provided in the Project Scoping
More informationSite Plan Review Application. Interest in the Property (e.g. fee simple, land option, etc.)
1. Identification CITY OF FENTON 301 South Leroy Street Fenton, Michigan 48430-2196 (810) 629-2261 FAX (810) 629-2004 Site Plan Review Application Project Name Applicant Name Address City/State/Zip Phone
More informationQuadroMAX. Installation Manual. QM Series. LED Outdoor Lighting Fixtures REV: 3/22/16
QuadroMAX LED Outdoor Lighting Fixtures Installation Manual QM Series REV: 3/22/16 BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING Risk of fire or electric shock. Luminaire wiring
More information2014 NEC Changes Part 1
www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More information3 Basic Code Enforcement, Part 3
Study Session 3 Basic Code Enforcement, Part 3 Technical Aspects of Code Enforcement OBJECTIVE: To become familiar with the technical aspects of code enforcement: first, by learning to recognize the basic
More informationPROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA
PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA Generally inspection of electrical installations is carried out under Regulation-30 (Periodical inspection & testing) & Regulation-43 (Approval
More informationQuality Control Checklist - Design Drawings
Quality Control Checklist - Design Drawings Date Company Name Address Telephone Fax Email Job Number 1) Drawing Set a) Drawing one is site/location/incoming power i) Should contain location map if not
More informationCustomer Connection Guide Updates Effective May 2017
This document provides a list of the updates to the EPCOR Distribution and Transmission Inc. (EDTI) Customer Connection Guide. If you have any questions, please contact EDTI Customer Engineering Services
More information4. Special Systems Design: including Fire Alarm and Security. C. Electrical and Telecommunications Ductbanks: Refer to Section 16118
PART 1: GENERAL This section of the design standard outlines general requirements for electrical and telecommunications designs to be performed for the University of Texas at Austin. This standard is intended
More informationSECTION COMMUNICATIONS COPPER BACKBONE CABLING
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications shall include all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationINDIGO LAKES HOA ARCHITECTURAL REVIEW COMMITTEE REQUEST FOR MODIFICATION
INDIGO LAKES HOA ARCHITECTURAL REVIEW COMMITTEE REQUEST FOR MODIFICATION I/We hereby request approval by the Architectural Review Committee for the modification shown below of Lot #: Street Address: Phone
More informationTCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II
SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 01 3300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More information