SECTION CONTROLS AND INSTRUMENTATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS

Size: px
Start display at page:

Download "SECTION CONTROLS AND INSTRUMENTATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS"

Transcription

1 SECTION CONTROLS AND INSTRUMENTATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification Sections, Mechanical General Requirements Section 15050, and Electrical General Provisions apply to work of this Section WORK INCLUDED A. Provide a Building Control System (BCS) incorporating Direct Digital Control (DDC), energy management, and equipment monitoring and control, consisting of the following elements: 1. Microcomputer based Plant Control Processors (PCPs) interfacing directly with sensors, actuators and environmental delivery systems (i.e., HVAC units, chillers, lighting systems, etc.). 2. Electric controls, and mechanical devices for all items indicated on drawings and described hereinafter, including valves, HVAC units, lighting, etc. 3. Microcomputer based Terminal Equipment Controllers (TECs) interfacing with sensors, actuators, and terminal equipment control devices. 4. Digital input to dry contact to fire alarm control panel. 5. Control low voltage wiring. B. Submittals, data entry, electrical installation, programming, start up, test and validation, instruction of Owner's representative on maintenance and operation, as-built documentation, and system warranty WORK BY OTHERS A. Access doors and setting in place of valves, flow meters, water pressure and differential taps, flow switches, thermal wells, air flow stations,current transformers, dampers, combination fire/smoke dampers and smoke detectors.

2

3 1.04 QUALITY ASSURANCE A. The Contractor shall have a local office within 100-miles of the job-site, staffed with trained engineers capable of providing instruction and maintenance service on system components. A 5-year experience record in the design and installation of building systems similar in performance to this Project or as required by the Owner. Be prepared to provide evidence of this history as condition of acceptance and approval prior to bidding. B. Bids by Wholesalers, Contractors, Franchised Dealers, or any firm whose principal business is not that of manufacturing and installing automatic temperature control systems will not be acceptable. C. The system shall be installed by competent mechanics, regularly employed by the BCS manufacturer, with full responsibility for proper operation of the BCS, including debugging and calibration of each component in the system. D. All system components are to be designed and built to be fault tolerant SUBMITTALS 1. Provide satisfactory operation without damage at 110% above, and 85% below rated voltage, and at +3 hertz variation in line frequency. 2. Provide static, transient, and short circuit protection on all inputs and outputs. Communication lines shall be protected against incorrect wiring, static transients, and induced magnetic interference. Bus connected devices shall be a.c. coupled or equivalent, so that any single device failure will not disrupt or halt bus communication. A. Submit in accordance with Division 1 and the following instructions: B. Mark each submittal to clearly indicate the intended use for each product, material, or procedure. Mark each item submitted for identification with the applicable page and paragraph number of the Specification and/or the detail and sheet number of the Contract Drawings. C. Provide data sheets and shop drawings, each in bound form with index and descriptions. Provide data sheets with dividers and tabs referenced to the index/and submittal control log number.

4 D. Provide a 2-part submittal consisting of: 1. First Part: a. Manufacturer's data sheets describing control valves, thermostats temperature sensors, mechanical installation materials, and electrical installation materials submittal within 30-days following award of Contract. Indicate on each page of each data sheet which piece of equipment or material is intended for use on this Project. Highlight, in yellow, xerographic reproduction; red marks or arrow stamps are unacceptable. 2. Second Part: a. System drawings in ISA format indicating airflow for air handling systems and flow diagrams for wet systems. Show instrument locations, mechanical and electrical equipment. b. Control panel layouts drawn to scale clearly indicating device locations, terminal blocks, plastic wire ducts, plastic tubing ducts, usable spare space, name tags, and their legends. Provide a Bill of Material with complete model numbers and descriptions. c. Elementary electrical schematic wiring drawings for motor control of chillers, cooling towers, pumps, fan coil and air handling units, hot water circulators, outdoor lighting, other fan and devices as indicated on the drawings. d. Point-to-point wiring diagram in block format showing actual device terminations. e. Detailed sequence of operation for each control system. f. Drawing minimum character height is 1/8" prior to halfsize reduction. g. Complete data sheets on each control component. Include terminations, power requirements, installation instructions, dimensions, and operating descriptions. Tag these sheets to match tag items in drawing Bill of Material.

5 h. Clearly indicate on each page of each data sheet which piece of equipment or material is to be provided under this Contract. Supplier markings shall be highlighted in yellow; red marks or arrow stamps are unacceptable. i. Contractor/supplier letters will not be considered or acted on in lieu of manufacturer's printed information and/or instructions. E. Where control circuits are involved with packages mechanical or electrical equipment, indicate actual terminal connections at the control panel for each piece of equipment on control shop drawings. Reproduce packaged equipment supplier furnished schematic diagrams on control shop drawings to integrate system controls with equipment controls. Verify data included is for the exact model furnished on this Project. (Some examples of package equipment are chillers, rooftop HVAC units, and evaporative coolers.) F. List analog values of all control devices. Show engineering units. G. Indicate the following on each shop drawing: 1. Original drawing date. 2. Show any change made after the original date within a "cloud" or "balloon" with a delta symbol. The delta symbol shall also appear in the revision block adjacent to the revision date, and contain the same number corresponding to its revision. H. Provide submittals meeting project criteria within 90 working days following award of Contract. Do not provide any personnel at the job-site prior to all submittals being reviewed by the architect. I. Provide color coordinated temperature sensor cover for each space. Submit physical sample or color chart for each different colored cover for review by the Architect. Submit a list of spaces where used. J. Call deviations of the Drawings or submittal data, from the express intent of this Document, to the attention of the Owner in writing. Explain reasons for such deviations in full, and address, coordinate, and assume any additional costs for such deviations without additional cost to Owner.

6 K. In checking Drawings and submittal date, the reviewer makes every effort to detect errors and omissions. Failure of the reviewer to detect errors or omissions during the review if Drawings and submittal data shall not relieve the vendor of his responsibility to comply with the Contract Documents FINAL PROJECT SUBMITTALS A. Upon completion of Project, prior to acceptance of the system by Owner, submit the following supplemental items: 1. Detailed report of check-out and calibration of the entire automatic control system. List control set points, tuning constants, and calibrating ranges on shop drawings. 2. Provide a shop drawing submittal prior to final acceptance, showing all revisions incorporated during the Project. Provide Final Recorded Documents in accordance with Division 1 with all delta symbols, clouds, and reference to same removed. 3. Provide two (2) sets of reduced (11" x 17") blackline shop and schematic drawings to the owner. In the event system changes occur during the warranty period, revise original record document drawings to reflect the changes and submit to owner. prices. 4. Provide a complete spare parts list with part numbers and current 5. Provide a 1-year service agreement quotation for consideration by Owner. Indicate rates for labor and materials. If accepted, the agreement becomes effective upon the expiration date of contract warranty. 6. Provide manufacturer's installation and calibration instructions for each piece of equipment. 7. Provide four (4) copies of operation and maintenance manuals. a. Operators Manual shall be provided with graphic explanations of keyboard use for all operator functions specified under Operation Training. b. Computerized printouts of all PCP data file construction, including all point processing assignments, terminal relationships, scales and offsets, command and alarm limits, program flow charts, etc.

7

8 1.07 SCOPE OF WORK 8. Prior to acceptance of the BCS System, provide the Owner with a "Letter of Certification" insuring that the total system is installed in a manner meeting all governing fire codes. A. Provide a complete operating system consisting of: 1. Control of the following equipment: a. Gas Furnace/DX Units The Contractor shall furnish and install all necessary hardware and all operating and applications software necessary to perform the control sequences of operation as called for in this specification. All software required shall be turned over to the Owner ready for use including all operating parameters, set points, and schedules. 2. Operator Instruction. 3. Control system wiring between control panels and equipment or devices to be controlled. 4. On site work station and software. 5. Electrical work installation practices and devices in accordance with Division SINGLE-SOURCE RESPONSIBILITY A. Provide a fully integrated system. B. Provide hardware, sensors and controls, wiring, piping, engineering, installation, supervision, labor, calibration, and commissioning for a complete and fully operational system TRAINING A. Provide competent instructors to instruct designated personnel in adjustment, operation, and maintenance, including safety requirements, of equipment and system specified.

9 B. All training shall be by the BCS Contractor and shall utilize specified manuals and as-built documentation. C. Operator training shall include two (2) eight-hour sessions encompassing: 1.10 WORK PROGRESS -- Sequence of Operation review -- Selection of all displays and reports -- Use of Portable Operators Terminals -- Troubleshooting of sensors (determining bad sensors). -- Password assignment and modification One training session shall be conducted at project completion, and the other shall be conducted forty-five days after project completion. A. Submit a monthly progress report to the Owner's representative. Relate progress reports to a Project manpower loading analysis, starting dates the work is planned for completion, and the number of calendar days actual job progress varies from the original plan. Coordinate format with Project schedule format ACCEPTANCE PROCEDURE A. Test and adjust all equipment to perform as specified and give satisfactory operation. Coordinate the testing of components installed under this Division with the testing requirements of Section WARRANTY A. Warranty components, parts, and assemblies against defects in material and workmanship for a period of 1-year after written acceptance by Owner. Warranty commences at time of acceptance. Partial acceptance of any system will not be provided. B. Provide for complete service of the control system. Make two (2) complete inspections of 8-hours duration. Submit written reports to the Owner. C. Do not reference warranty on Drawings or equipment manuals provided by BCS Contractor.

10 PARTS 2 AND 3 - PRODUCTS AND EXECUTION 2.01 ACCEPTABLE MANUFACTURERS A. Andover Controls by ATT Integrated Technologies. B. Control Engineering, Inc. C. Direct Digital Control D. Staefa 2.02 SYSTEM REQUIREMENTS A. Control Systems: Consist of temperature sensors, thermostats, relative humidity sensor, photocell, control valves, operators, indicating devices, interface equipment, and related apparatus to operate the mechanical systems. B. Basic Design: Provide basic control circuit design to allow safe system shutdown upon control device failure, interruption of electrical, or its reduction below safe operating levels. Energize control devices and circuits to operate systems, and de-energize control devices and circuits to stop system operation, unless otherwise indicated on the drawings. C. Components: Provide materials, coordination, and field work to connect and interface BCS components supplied by others as a part of an "equipment package." D. System Capability: Proportional and integral unless specified to the contrary. E. System Type: The interpretation of terminology used in Project Drawings and Specifications shall be in accordance with the latest edition of the ASHRAE Guide and ISA Standards. F. Powerline Protection Devices: Provide to insure protection against transients, electrical noise interference, voltage swings, and distorted sine wave power on all sensitive control devices provided under this Contract. G. Materials and Equipment: Provide standard products of a reputable manufacturer regularly engaged in the production of same. Where more than 1 unit of an item is required, all shall be provided by the same manufacturer. Permanently affix manufacturer's nameplate indicating model number, serial number, and performance data to equipment

11 furnished under this Contract. Use manufacturer's latest model. H. Protection: Deliver material and equipment to site in manufacturer's original, unopened, and labeled containers. Provide protective measures to allow on-site storage exposed to the weather, without damage to the equipment. I. Codes and Standards: 1. Materials, equipment design, supports and testing shall comply with local, county, state and national codes. 2. Comply with the applicable Standards/Codes of AMCA, ANSI, ARI, ASHRAE, ASME, ASTM, EIA, FCC, FM, NBS, NEMA, NFPA, OSHA, SAMA, UBC, UMC, UFC, AND UL, as adopted by the authority having jurisdiction. 3. The complete BCS installation shall be in strict accordance to the national and local electrical codes and the electrical section of these specifications. All devices designed for or used in line voltage applications shall be UL Listed. a. All microprocessor based devices shall be UL 916 listed. b. All electrical environmental control and monitoring devices shall be UL 429 and/or UL 873 Listed. 4. All electronic equipment shall conform to the requirements of FCC regulation Class B Part 15, Section 15 governing radio frequency electromagnetic interference and be so labeled. J. Diagrams: Predicated upon Project magnitude, Construction Documents may include flow diagrams and point lists as a part of the working Drawings. Flow diagrams and point lists are not for the purpose of giving physical dimension, locations or quantities, but rather to make clear the interconnections by systems, of the various units of the process. If an item is shown on either the flow diagrams, drawings, point list, or in the specification, but not on all, it will be assumed that the contractor has included such item in his estimate of the cost of the work, and that he shall provide same COORDINATION A. Provide coordination to assure that the BCS system, as installed, is totally compatible with devices provided by others. Provide additional devices, where required, to assure complete compatibility at no additional cost to the Owner.

12

13 2.04 OPERATION BY OWNER A. Owner may require operation of part of the system prior to final acceptance. Operation is not to be construed as acceptance of work SYSTEMS OPERATION A. Provide indications and alarms as shown on the Drawings. B. Power Outage, Power Restoration: Upon loss of normal power, restart equipment and devices in accordance with the emergency power restart schedule or normal power restart schedule as applies CONTROL DEVICES A. System Requirements: 1. Programmable thermostats. 2. Provide all wiring, materials and methods. 3. Provide items manufacturers listed. Do not substitute. 4. Review other Specification Sections to avoid duplication of instrumentation and work scope. B. Wiring Methods: 1. Install no more than two (2) wires under a single screw or pressure terminal. 2. Provide same physical conductor with the same tag identification throughout the circuit. wire. system. 3. Tag panel terminal strip with the same number as the attached 4. Provide shop drawings to reflect this method and numbering 5. Provide 5% spare wires in all conduit runs, but not less than one (1) spare wire.

14 6. All line voltage wiring, all wiring exposed, and all wiring in equipment rooms shall be installed in conduit in accordance to the electrical specifications. 7. All electronic wiring shall be #18 AWG minimum THHN and shielded if required. 8. All wiring in the central control room shall be concealed in an approved manner. 9. Where the space above the ceiling is a supply or return air plenum, the wiring shall be plenum rated. Teflon wiring can be run without conduit above suspended ceilings. C. Power Wiring 1. All BCS equipment power shall be the responsibility of the Division 16 Electrical Contractor. 2. It is the responsibility of the Contractor to coordinate with the Division 16 Electrical Contractor on the final locations to which BAS equipment power is wired. 3. The power shall be obtained from dedicated circuits on the nearest available 120V panel and clearly labeled. Power for any BAS equipment that is controlling equipment that operates under emergency power shall be obtained from emergency power panels. 4. All power wiring for the BCS equipment shall be done with a dedicated earth ground by means of wire media only, originating at the power service source earth ground. This applies to all Level 1 and Level 2 controllers along with workstations and the file server. D. Programmable Electric Thermostats 1. Electric thermostats shall be line voltage or low voltage type suitable for the application. Low voltage type heating thermostats shall have adjustable heat anticipation.

15 PART 3 - EXECUTION 3.01 GENERAL A. The Control System shall be designed, installed, and commissioned in a turnkey fully implemented, and operational manner; including all labor not noted in Work by Others paragraph of PART I of this section of these specifications, and not noted in other sections of these specifications DATA POINT REQUIREMENTS A. Provide fully implemented application and custom software and controls necessary to accomplish the control sequences as specified. B. Computer input and output points shall be provided where specified, shown, or required to accomplish the requirements of the Sequence of Operation. C. Unless otherwise specified or approved prior to bidding, the primary analog input and the analog output of each DDC loop shall be resident in a single panel containing the DDC algorithm, and shall function independent of any peer or communication links. Secondary (reset type) analog inputs may be received from the peer network, but approved default values and/or procedures shall be substituted in the DDC algorithm for this secondary input, if network communications fail, or if the secondary input becomes erroneous or invalid INSTALLATION A. All wiring shall be properly supported and run in a neat and workmanlike manner. B. The BCS Contractor shall be responsible for all electrical installation required for a fully functional control system. All wiring shall be in accordance to all local and national codes. C. The BCS Contractor shall enter all computer programs and data files into the related computers, including all control programs, initial approved parameters and settings, and English descriptors. D. The BCS Contractor shall maintain diskette copies of all data file and application software for reload use in the event of a system crash or memory failure. One (1) copy shall be delivered to the Owner during training session, and one (1) copy shall be archived in the BCS Contractor's local software vault.

16 3.04 VALIDATION A. The BCS Contractor shall completely check out, calibrate, and test all connected hardware and software to insure that the system performs in accordance with the approved specifications and sequences of operations submitted. B. Witnessed validation demonstration shall consist of: -- Display and demonstrate each type of data entry to show site specific customizing capability. Demonstrate parameter changes. -- Execute digital and analog commands. -- Demonstrate DDC loop precision and stability via trend logs of inputs and outputs. -- Demonstrate EMS performance via trend logs and command trace SEQUENCE OF OPERATIONS A. Start/Stop a. Operators Manual shall be provided with graphic explanations of keyboard use for all operator functions specified under Operator Training. b. Computerized printouts of all PCP data file construction including all point processing assignments, terminal relationships, scales and offsets, command and alarm limits, program flowcharts, etc. Provide software to start and stop equipment based upon the time of day and day of the week. Each equipment start/stop shall be coordinated to prevent multiple concurrent equipment start-ups either during routine scheduled control or upon BCS start-up subsequent to an electrical power outage.

17 Where space temperature sensors with override switches have been specified, the program shall respond to an occupant's "off-hour" use of the override by re-activating scheduled occupied temperature control of the associated HVAC system and required ancillary systems (i.e., chillers, pumps, etc.). The re-activation shall be sustained for a operator definable time period (initially 1 hour). Occupant use of the override during normally scheduled (or reactivated) time periods shall be ignored by the program. C. Temperature Override (Night Setback) Temperature override control shall be provided to enable or activate HVAC operation during non-scheduled hours of each system specified. The program shall permit an operator to define either or both a heating and cooling setpoint for each override control specified, a minimum on time limit for override operation, a minimum off time limit following an override operation and the ability to enable/disable space temperature information for override control from specific spaces of system with multiple space temperature points. D. Economizer System Operation Outdoor dry bulb temperature and relative humidity shall be monitored. When the operator selects economizer system operation, the chiller shall stop. Motorized valves shall position to direct CHW and CW flows through the respective load and source sides of the plate and frame heat exchanger (HX-1). The CW pump shall start and the cooling tower fans shall cycle to maintain 45 F condenser water temperature. The chilled water pump shall circulate CHW on the load side of the heat exchange. E. Hydronic Economizer Control The hydronic economizer shall be used whenever chilled water can be produced at the currently required chilled water supply temperature. The economizer control algorithm shall determine if the economizer can produce the current required chilled water temperature based on current drybulb and relative humidity conditions and economizer performance data. If the economizer cannot produce the required chilled water temperature, it shall remain off. Once the economizer is on, it shall remain on until such time that it cannot produce the chilled water temperature required.

18 To start the economizer, the program shall first shutdown any operating chiller(s) associated chilled and condenser water pumps and close the chiller's condenser water isolation valve(s). The cooling tower control program shall then be overridden. The cooling tower fans shall not be controlled to maintain a condenser temperature at an operator defined amount less the current CHWS setpoint (initial 10 F less) as determined by the chilled water supply during economizer operation shall be 40 F (initially). Then the condenser water isolation valves shall be positioned for economizer operation and the condenser pump(s) assigned to hydronic economizer operation shall be started. The program shall then start the assigned chilled water pump(s) and open the hydronic economizer's CHW isolation valve. To turn off the economizer, the program shall shutdown the chilled water pump, cooling tower and condenser pump. The condenser water isolation valves shall then be repositioned for non-economizer operation and the cooling tower control parameters shall be returned to their normal operating states. If chiller(s) are subsequently required, they can then be started as specified within the chiller system control program. F. Mechanical Room Exhaust Fan The time clock function shall activate this fan. The refrigerant detection system shall override the schedule and start the fan in the event a high refrigerant level is detected. Provide start/stop switch control of all exhaust fans. G. Furnace Coil Units/DX Units Units shall be started/stopped from BCS air handling system programmed schedule. When room temperature drops below heating night setback or cooling set up temperature, the units shall be cycled to maintain temperature. Setpoints shall be adjustable from workstations, but not locally. Space temperatures shall be monitored by a wall mounted temperature sensor provided by controls contractor. The exhaust fans unit shall be interlocked where indicated on drawings.

19 DX Cooling Coil Unit Control HVAC unit and DX fan coil/condensing units shall be started/stopped from BCS system programmed schedule. Wall mounted temperature sensors (provided by controls contractor) shall cause units to operate in cooling mode and heating mode (for AC-1 only) based on required space temperatures of 75 F and 70 F respectively. When space temperature drops below heating night setback (for AC-1 only) or cooling set up temperature, the unit heating system shall be cycled to maintain the space temperature. Setpoints shall be adjustable from workstations, but not locally. Units shall be interlocked with exhaust fans. H. General and Restroom Exhaust Fans These will not controlled by the BCS unless noted below. Provide all wiring and controls interfacing required for fully operational split system cooling components integrating with gas furnace controls. **END OF SECTION**

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER Honeywell RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER W7620 Zone Controller Water Source Heat Pump - -.> The W7620 Zone Controller provides customized control of HVAC zone equipment.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017 SECTION 23 0553 - MECHANICAL SYSTEMS IDENTIFICATION GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL SECTION 23 00 10 - MECHANICAL SCOPE OF WORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01

More information

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia BULLETIN NO. 6 TO THE PLANS AND SPECIFICATIONS FOR JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia EwingCole Architects.Engineers.Interior Designers.Planners

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION Buebtel/Perlcins Community Learning Center GPD - 2001271.15 SECTION 15075 MECHANICAL IDENTIFICATION PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION SUBMITTAL PROCEDURES

SECTION SUBMITTAL PROCEDURES SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification

More information

A. Action Submittals: Written and graphic information that requires Architect's responsive action.

A. Action Submittals: Written and graphic information that requires Architect's responsive action. SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification

More information

SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 01 33 00 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Record Documents. B. Operation and Maintenance Manuals. C. Warranties and bonds. 1.02 RELATED REQUIREMENTS SECTION 01 78 00 A. Section 01 30 00 - Administrative

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 SUBMITTALS A.

More information

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe Markers. 2. Valve Tags. 3. Equipment Nameplates. 4. Underground Marking Tape. 5. Duct

More information

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to

More information

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

MISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration

MISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration SECTION 01 340 - SHOP DRAWINGS, PRODUCT DATA AND SAMPLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other

More information

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION GUIDE SPECIFICATIONS 256920-UGS-A-0506 Simplicity Intelli-Comfort Optional Control in 3-25 Ton Packaged Units GENERAL DESCRIPTION CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP Equipment with Simplicity

More information

Facility Services Subgroup Preface for Divisions 21` through 28

Facility Services Subgroup Preface for Divisions 21` through 28 Facility Services Subgroup Preface for Divisions 21` through 28 1.1 EXECUTIVE SUMMARY A. This document provides standards for the Consultants and Contractors producing mechanical and electrical design

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 01 3300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

A. Action Submittals: Written and graphic information that requires Engineer's responsive action.

A. Action Submittals: Written and graphic information that requires Engineer's responsive action. SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification

More information

East Central College

East Central College SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 00 00.00 20 (July 2006) ------------------------------- Preparing Activity: NAVFAC Superseding UFGS-26 00 00.00 20 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.: WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO-00111 Job No.: 16-7003 To Respondent of Record: ADDENDUM 2 July 5, 2017 This addendum, applicable to work referenced

More information

Introduction to BAS Technology

Introduction to BAS Technology Introduction to BAS Technology Dave Kahn, P.E. Why Back to basics? Sometimes you get what you ask for resulting in: The perfect job OR Unhappy owners & occupants Unexpected network limitations Product

More information

Section Meetings Section Material and Equipment. None Required

Section Meetings Section Material and Equipment. None Required January 2000 Page 1 of 8 PART 1 GENERAL 1.01 OTHER CONTRACT DOCUMENTS 1.02 DESCRIPTION OF WORK 1.03 RELATED WORK PART 2 PRODUCTS The General Conditions of the Contract, General Requirements and Supplemental

More information

SECTION SUBMITTAL PROCEDURES

SECTION SUBMITTAL PROCEDURES SECTION 013300 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply

More information

SECTION SUBMITTAL PROCEDURES

SECTION SUBMITTAL PROCEDURES SECTION 01330 SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide submittals in accordance with the General Conditions as modified by the Supplementary Conditions,

More information

Heat Exchanger Construction Checklist

Heat Exchanger Construction Checklist Heat Exchanger Checklist Project: Pump tag: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified 8/23/17 Updated sections on System Design and Performance Requirements; Submittals; Equipment; Accessories or Special Features; Quality

More information

SECTION SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS

SECTION SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS SECTION 01300 SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and other Division-1 Specification Sections,

More information

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK PART 1.0 GENERAL 1.1 SCOPE A. This specification contains the minimum requirements for the design, manufacture and testing of a UL listed,

More information

B. Division-16 Basic Materials and Methods section apply to work specified in this section.

B. Division-16 Basic Materials and Methods section apply to work specified in this section. Section 16745 PREMISE CABLING SYSTEMS PART ONE GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following:

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following: SECTION 01 31 00 PROJECT MANAGEMENT AND COORDINATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

STANDARD SPECIFICATIONS SECTION SUBMITTAL PROCEDURES

STANDARD SPECIFICATIONS SECTION SUBMITTAL PROCEDURES STANDARD SPECIFICATIONS SECTION 01330 SUBMITTAL PROCEDURES PART 1 GENERAL 1.1 DESCRIPTION A. Section includes general requirements and procedures related to preparation and transmittal of Submittals to

More information

B. Samples: For color, letter style, and graphic representation required for each identification material and device.

B. Samples: For color, letter style, and graphic representation required for each identification material and device. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication

More information

SECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS

SECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS PART 1 GENERAL 1.01 SECTION INCLUDES A. Project Coordination. B. Preconstruction meeting. C. Progress meetings. D. Preinstallation conferences. E. Requests for information (RFI). F. Coordination drawings.

More information

SECTION EMERGENCY RESPONDER RADIO COVERAGE SYSTEMS

SECTION EMERGENCY RESPONDER RADIO COVERAGE SYSTEMS 510.1 Emergency responder radio coverage in new buildings. Approved radio coverage for emergency responders shall be provided within all buildings meeting any one of the following conditions: 1. There

More information

SECTION PROJECT MANAGEMENT AND COORDINATION

SECTION PROJECT MANAGEMENT AND COORDINATION SECTION 013100 - PROJECT MANAGEMENT AND COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other

More information

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY SECTION 16075 - SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Provide a short-circuit, component protection, flash

More information

UNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ

UNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 General

More information

A. This section specifies procedural requirements for Shop Drawings, product data, samples, and other miscellaneous Work-related submittals.

A. This section specifies procedural requirements for Shop Drawings, product data, samples, and other miscellaneous Work-related submittals. SECTION 01300 PART 1 GENERAL 1.1 SECTION INCLUDES A. Description of Requirements B. Submittal Procedures C. Specific Submittal Requirements D. Action on Submittals E. Repetitive Review 1.2 DESCRIPTION

More information

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal City of Winnipeg Brady Road Landfill Site Section 01300 New Entrance and Scale Facility Page 1 of 4 SUBMITTALS 1. SHOP DRAWINGS 1.1 General.1 Arrange for the preparation of clearly identified Shop Drawings

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION SECTION 15190 MECHANICAL IDENTIFICATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Identification of mechanical products installed under Division 15. B. Related Sections: 1.02 REFERENCES 1.

More information

CLARK COUNTY FIRE CODE AMENDMENTS

CLARK COUNTY FIRE CODE AMENDMENTS CLARK COUNTY FIRE CODE AMENDMENTS SECTION 510 EMERGENCY RESPONDER RADIO COVERAGE SYSTEM is amended to read as follows: SECTION 510 EMERGENCY RESPONDER RADIO COVERAGE SYSTEM 510.1 Emergency responder radio

More information

[Note to PSC: Include these sections in the Contract Documents, even though some are not included in the U of I Facilities Standards]

[Note to PSC: Include these sections in the Contract Documents, even though some are not included in the U of I Facilities Standards] SECTION 01 78 23 - OPERATION AND MAINTENANCE DATA PART I - GENERAL 1.1 SUMMARY A. Operation and Maintenance Data shall be submitted in appropriately-sized binders, with dividers, and organized by each

More information

SECTION INTEGRATED AUTOMATION

SECTION INTEGRATED AUTOMATION SECTION 25 00 00 INTEGRATED AUTOMATION Note: All building controls projects will be Tridium Niagara DDC based. Note: This section provides an overview of the entire Division 25. It includes background

More information

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing). SECTION 15047 - IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Identification including necessary accessories indicated on Construction Documents and specified in this section or as required

More information

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT SECTION 21 05 53 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2015-2015 ARCAT, Inc. - All rights reserved PART 1 GENERAL

More information

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor. Basis of Design This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor. Background Information A Short Circuit and Coordination

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

A/E REVIEW CHECKLIST HVAC

A/E REVIEW CHECKLIST HVAC A/E CHECKLIST HVAC Reviewers should - Use Checklists when reviewing any type of VA construction project for the following disciplines: Site and Landscape, Architectural, Structural, Plumbing, Fire Protection,

More information

DIVISION 1 GENERAL REQUIREMENTS SECTION SUBMITTAL PROCEDURES

DIVISION 1 GENERAL REQUIREMENTS SECTION SUBMITTAL PROCEDURES DIVISION 1 GENERAL REQUIREMENTS SECTION 01 33 00 PART 1 - GENERAL 1.1 SUMMARY A. This section includes administrative and procedural requirements for submittals required for performance of the work, including

More information

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES SECTION 01334 SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES PART 1 GENERAL 1.01 SUMMARY A. Submit to the ENGINEER for review, such working drawings, shop drawings, test reports and data on materials and equipment

More information

SECTION BASIC MATERIALS AND METHODS. A. The requirements of the General Conditions and Supplementary Conditions apply to all Work herein.

SECTION BASIC MATERIALS AND METHODS. A. The requirements of the General Conditions and Supplementary Conditions apply to all Work herein. SECTION 230500 BASIC MATERIALS AND METHODS PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all Work herein. B. The Contract

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15.

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15. SECTION 15190 MECHANICAL IDENTIFICATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Identification of mechanical products installed under Division 15. B. Related Sections: 1. Section 09900 -

More information

Piping & Equipment Identification

Piping & Equipment Identification Piping & Equipment Identification Part 1 General 1.01 Description of Work A. Work in this section includes: Identification materials, including necessary accessories indicated on Contract Documents and

More information

Bid No. B14-02 Building 100 HVAC Improvements

Bid No. B14-02 Building 100 HVAC Improvements Bid No. B14-02 Building 100 HVAC Improvements Addendum No. 1 This Addendum No. 1 sets forth modifications to portions of the bid and contract documents for the above-referenced work described as: Building

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

***************************************************************************** DRAFT UFGS- 01 XX XX (FEB 2014)

***************************************************************************** DRAFT UFGS- 01 XX XX (FEB 2014) DRAFT UFGS- 01 XX XX (FEB 2014) ------------------------ Drafting Activity: USACE UNIFIED FACILITIES GUIDE SPECIFICATION SECTION TABLE OF CONTENTS DIVISION 01 GENERAL REQUIREMENTS SECTION 01 XX XX (FEB

More information

Feedback Systems in HVAC ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies

Feedback Systems in HVAC ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies Feedback Systems in HVAC ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies ASHRAE, Madison Chapter October, 2014 Agenda Definitions: feedback and closed-loop control Types of

More information

ADDENDUM #2 September 12, 2018

ADDENDUM #2 September 12, 2018 Physical Plant Services Project Management 1000 Rim Drive Phone: (970) 247-7523 Fax: (970) 247-7555 Project No. 2007-130P18 Whalen Gymnasium Expansion and Renovation for Exercise Science Request for Qualifications

More information

Taylor County July 2011 SECTION SHOP DRAWINGS, WORKING DRAWINGS AND SAMPLES

Taylor County July 2011 SECTION SHOP DRAWINGS, WORKING DRAWINGS AND SAMPLES SECTION 01340 SHOP DRAWINGS, WORKING DRAWINGS AND SAMPLES PART 1 - GENERAL 1.1 REQUIREMENTS INCLUDED A. Contractor shall submit to the Architect/Engineer for review and exception, if any, such working

More information

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES SECTION 01 33 23 SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES PART 1 GENERAL 1.1 DESCRIPTION A. This specification defines the general requirements and procedures for submittals. A submittal is information

More information

SECTION CONTRACTOR SUBMITTALS. A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER.

SECTION CONTRACTOR SUBMITTALS. A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER. SECTION 01300 - PART 1 - GENERAL 1.1 GENERAL A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER. B. Unless otherwise noted, within 14 days after the date of commencement as stated in

More information

YD (MOD A-C) WITH OPTIVIEW CONTROL CENTER FIELD CONTROL MODIFICATIONS

YD (MOD A-C) WITH OPTIVIEW CONTROL CENTER FIELD CONTROL MODIFICATIONS Supersedes: 160.69-PW2 (815) Form 160.69-PW2 (116) WIRING DIAGRAM CONTRACTOR ORDER NO. JCI CONTRACT NO. JCI ORDER NO. YD (MOD A-C) WITH OPTIVIEW CONTROL CENTER FIELD CONTROL MODIFICATIONS PURCHASER JOB

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives 3.0 50HP @ 200 to 240V AC 3.0 350HP @ 380 to 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum

More information

Answer: Qualification statement should be provided with the bid.

Answer: Qualification statement should be provided with the bid. Little Diversified Architectural Consulting, Inc. 5815 Westpark Drive Charlotte, North Carolina 28217 Phone: 704-525-6350 Fax: 704-561-8700 Lincoln County Probation Renovation 208 N. Government Street

More information

DIVISION 1 - GENERAL REQUIREMENTS SECTION SUBMITTALS

DIVISION 1 - GENERAL REQUIREMENTS SECTION SUBMITTALS DIVISION 1 - GENERAL REQUIREMENTS SECTION 01300 - SUBMITTALS PART 1 - GENERAL 1.1 STIPULATIONS A. The section "Special Requirements" forms a part of this section by this reference thereto and shall have

More information

ADDENDUM NO. 4 November 15, Page 1

ADDENDUM NO. 4 November 15, Page 1 ADDENDUM NO. 4 November 15, 201 8 Page 1 PROJECT MANUAL FOR CONSTRUCTION OF HVAC REPLACEMENT FOR NORTH OCONEE HIGH SCHOOL FOR OCONEE COUNTY SCHOOLS WATKINSVILLE, GEORGIA DATED: SEPTEMBER 14, 2018 CUNNINGHAM,

More information

Industrial Pipe Marking

Industrial Pipe Marking Industrial Pipe Marking Pipe and Valve Identification Specialists SPECIFICATIONS ASME (ANSI) Standard A13.1-2007 The ASME (ANSI) Standard for pipe identification is a widely used guideline in determining

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018 SECTION 01 7839 - PROJECT RECORD DOCUMENTS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General Section 16621A - AUTOMATIC TRANSFER SWITCH Part 1 General 1.01 One 600 Amp, 3 Phase, 480 Volt Automatic Transfer Switch (ATS) shall be provided with gasketed enclosure. The ATS shall consist of an inherently

More information

Residential Construction Checklist Single and Two Family Construction

Residential Construction Checklist Single and Two Family Construction DATE: _ Building Inspection Submittal Requirements Residential Construction Checklist Single and Two Family Construction Submit a City of Big Spring Permit Application, checklist, and 3 complete hard copy

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION 01 3100 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Assign unit identification numbers to operating units of equipment within a class or subclass during the design phase of new buildings, additions,

More information

A. Section includes administrative and procedural requirements for project record documents, including the following:

A. Section includes administrative and procedural requirements for project record documents, including the following: SECTION 017839 - PROJECT RECORD DOCUMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01

More information

INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS:

INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS: INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS: 013300 SUBMITTAL PROCEDURES 018116 CONSTRUCTION WASTE MANAGEMENT DIVISION 2 EXISTING CONDITIONS: 023000 EARTHWORK

More information

SECTION SUBMITTALS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION SUBMITTALS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 013300 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA SECTION 01 78 00 CLOSE-OUT SUBMITTALS PART 1 - GENERAL 1.1 GUARANTEES A. Compile and submit guarantees, bonds, and service and maintenance contracts specified in the individual B. Guarantees from Subcontractors

More information

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030 ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: December 17, 2018 The following changes, additions, revisions, and/or deletions

More information

SPECIAL PROVISION Description of Project, Scope of Contract and Sequence of Work

SPECIAL PROVISION Description of Project, Scope of Contract and Sequence of Work 2004 Specifications CSJ 0110-04-166 SPECIAL PROVISION 000--363 Description of Project, Scope of Contract and Sequence of Work 1. General. The work to be performed on this project consists of furnishing,

More information

SECTION BASIC MECHANICAL REQUIREMENTS GENERAL BASIC MECHANICAL REQUIREMENTS PART RELATED DOCUMENTS

SECTION BASIC MECHANICAL REQUIREMENTS GENERAL BASIC MECHANICAL REQUIREMENTS PART RELATED DOCUMENTS SECTION 15010 - BASIC MECHANICAL REQUIREMENTS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Requirements of the Contract Forms, Conditions of the Contract, Specifications, Drawings, and

More information

1. State that all workmanship must conform to all pertinent laws, ordinances and regulations of all bodies having jurisdiction.

1. State that all workmanship must conform to all pertinent laws, ordinances and regulations of all bodies having jurisdiction. SECTION 230800 GENERAL MECHANICAL REQUIREMENTS 1.0 In addition to the requirements previously presented herein, each specification shall contain the following general information: A. General 1. Incorporate,

More information

BAE Systems Combat Vehicles Supplier Quality Assurance AS9102 Requirement

BAE Systems Combat Vehicles Supplier Quality Assurance AS9102 Requirement 1 BAE Systems Combat Vehicles Supplier Quality Assurance AS9102 Requirement February 27, 2019 2 Scope The intent of this document is to provide an understanding, and clarification as to what BAE Systems

More information

St. Monica Food Pantry

St. Monica Food Pantry St. Monica Food Pantry 26 5113-1 ELECTRICAL WORK DIVISION 26 SECTION 265113 INTERIOR LIGHTING FIXTURES PART 1. GENERAL 1.1 WORK INCLUDES A. Extent, location, and details of interior lighting fixture work

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

VARIABLE FREQUENCY DRIVE SPECIFICATION

VARIABLE FREQUENCY DRIVE SPECIFICATION VARIABLE FREQUENCY DRIVE SPECIFICATION 1.0. SUMMARY The use of variable frequency drives (VFDs) in conjunction with wastewater lift stations has been identified as a means improve efficiency and to moderate

More information

SECTION PROJECT COORDINATION VIA BIM

SECTION PROJECT COORDINATION VIA BIM SECTION 01 31 13 PROJECT COORDINATION VIA BIM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations. General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings

More information

Emergency responder radio coverage in new buildings. California Fire Code Section is hereby amended to read:

Emergency responder radio coverage in new buildings. California Fire Code Section is hereby amended to read: Sunnyvale 2013 Fire Code Section 510 16.52.510. Emergency responder radio coverage. (a) Emergency responder radio coverage in new buildings. California Fire Code Section 510.1 is hereby amended to read:

More information

SUBMITTAL PROCEDURES

SUBMITTAL PROCEDURES SUBMITTAL PROCEDURES PART 1 GENERAL The ASPA Project Engineer (APE) may request submittals in addition to those specified when deemed necessary to adequately describe the work covered in the respective

More information