1 St. Monica Food Pantry ELECTRICAL WORK DIVISION 26 SECTION INTERIOR LIGHTING FIXTURES PART 1. GENERAL 1.1 WORK INCLUDES A. Extent, location, and details of interior lighting fixture work are indicated on drawings, in schedules and as specified hereinafter. B. Types of interior lighting fixtures in this section include the following: 1) Removal, cleaning, testing, relaying, re-lamping and re-installation of existing fluorescent fixtures; 2) The installation of owner furnished lighting fixtures; 3) New Contractor furnished and installed lighting fixtures: (a) LED 1.2 SUBMITTALS A. General: 1) Submittals shall be made on all items in this section and shall be in accordance with Division 01, Section and Division 26, Section Electrical Submittals. B. Product Data: Submit manufacturer's technical product data, independent testing lab photometric data, including fixture specifications and installation instructions, for each type of lighting fixture required. Include data substantiating that materials comply with requirements. C. Maintenance Data: Submit maintenance data and parts lists for each type of lighting fixture installed, including furnished specialties and accessories. Include this data, product data, and shop drawings in maintenance manual; in accordance with requirements of the General Conditions of this Specification. 1.3 PREREQUISITE CONDITIONS A. The General Conditions, Supplemental General Conditions and Special Conditions are part of this contract and requirements set forth in those sections apply to all work in this division of the specifications. 1.4 QUALITY ASSURANCE A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of interior lighting fixtures of sizes, types and ratings required, whose products have been in satisfactory use in similar service for not less than five (5) years. B. Installer's Qualifications: Firms with at least three (3) years of successful installation experience on projects with interior lighting fixture work similar to that required for this project. C. Electrical Code Compliance: Comply with applicable local code requirements of the authority having jurisdiction and NEC Articles 220, 410, and 510 as applicable to installation, and construction of interior building lighting fixtures. D. NEMA Compliance: Comply with applicable requirements of NEMA Stds Pub/No.'s LE 1 and LE 2 pertaining to lighting equipment. E. IES Compliance: Comply with IES RP-1 pertaining to general lighting practices and RP-15, regarding selection of illuminance values for interior office lighting. sys-tek, P.A. Project No. Insert Number Section INTERIOR LIGHTING FIXTURES: Page 1

2 St. Monica Food Pantry F. UL Compliance: Comply with UL standards, including UL 486A and B, pertaining to interior lighting fixtures. Provide interior lighting fixtures and components which are UL-listed and labeled. G. Work in this division shall include all lighting fixtures as specified and as called for on plans and shall also include lamps as required installed in fixtures. Lighting fixtures shall be complete including hickeys, suspension nipples, connectors and all other material and equipment as required for re-hanging fixtures in accordance with the National Electrical Code. Fixtures and lamps shall be wiped clean before and after installation. PART 2. PRODUCTS 2.1 LIGHTING FIXTURES A. All recessed incandescent lighting fixtures shall be furnished to comply with requirements of NEC (c) and shall be U.L. approved and labeled in accordance with UL Fixtures recessed in all ceilings, other than suspended T-bar lay-in panel ceilings, shall be U.L. type "I.C." without thermal protection or U.L. "Non-I.C." with thermal cutout protection, and both types shall bear the appropriate U.L. label. Fixtures for use in suspended T-bar panel ceilings shall be U.L. Labeled "For Use in Suspended Ceilings Only". The above requirements do not apply to fixtures recessed in concrete construction, but fixtures so mounted shall be approved for recessing in concrete. B. Any flat acrylic lens specified in fluorescent fixtures shall be a minimum of.125" thick, KSH type K12, or approved equal, unless otherwise shown in schedule on fixtures. C. Fixtures shall be wired with color coded fixture wire approved for temperature involved. Circuitry wiring run in fluorescent fixture channels shall be 'THHN" or "XHHW" and not less than #12 AWG. D. Unless shown or specified otherwise, fixtures are specified by type identified by letter shown on drawings adjacent to outlet. All fixtures shall be Underwriter's label. Finish on all metal parts, unless specified, shall be applied after fixture fabrication, and shall be as directed by the Architect. E. Where lighting fixtures are installed in suspended ceilings, the lighting fixture shall be securely attached to the building structure with a minimum of two (2) 12 gauge safety wires located at opposite ends of the lighting fixture and the ceiling support system shall be adequately supported at each corner of the lighting fixture. F. Where lighting fixtures are specified or called out on drawings to have a fire rated enclosure, the Contractor shall furnish and install an approved fire rated enclosure to completely enclose the lighting fixture above the ceiling. The enclosure shall be constructed of an approved fire rated material to maintain the fire rating of the ceiling and shall be held together with a fire, and heat resistant adhesive and steel pins or nails. The top of the enclosure shall have a 4" square opening located above each ballast for ventilation. Submit shop drawings for approval. G. Manufacturers: Subject to compliance with requirements, provide products of one of the following (for each type of interior lighting fixture): LED 1) CREE 2) Williams 3) Hubbell 4) Lithonia 5) Prescolite sys-tek, P.A. Project No. Insert Number Section INTERIOR LIGHTING FIXTURES: Page 2

3 St. Monica Food Pantry EXIT LIGHTS A. Exit lights shall be dual voltage AC/DC rated for voltages shown. Illumination source shall be Light EMITTING Diodes (LED's). Provide automatic transfer circuit to transfer to 48 DC source on loss of AC source where shown. B. Exit lights furnished with 6" high stencil letters. Use red LED's. Verify color used with local codes, if a different color is required; indicate on the shop drawing submittal. Exit lights wired for separate AC and DC circuits as shown. C. Exit lights shall be interlocked with Fire Alarm system to flash where required by the local authorities having jurisdiction. Coordinate flashing circuit required with Fire Alarm System Vendor. 2.3 BALLASTS A. Ballasts for fluorescent fixtures, unless specified or indicated otherwise, shall be 430 MA. energy saving type, long life, high power factor, rapid-start, premium Class "P", non-drip, with automatic resetable thermal cutout protection, U.L., CBM, and ETL approved, sound rated "A". Input energy savings shall be no less than 11% of the normal conventional Class "P" ballast. Ballasts shall be General Electric, "Watt-Miser"; Advance "Mark III"; Universal "Watt Reducer", or approved equal. Specific data on ballasts shall be submitted with light fixture shop drawings. Ballasts that produce objectionable noise after installation of the fixtures, in the opinion of the Architect, shall be removed and replaced by the Contractor and at no extra cost. B. All ballast shall be for operating at 120 volts unless otherwise indicated on drawings, or schedule of lighting fixtures. Contractor shall verify exact voltage prior to submission of shop drawings. C. All ballasts for twin tube and double twin tube type fluorescent fixtures shall be high power factor type. D. Acceptable Electronic Fluorescent Ballast Manufacturers: 1) Advance 2) Magnetek 3) Motorola 4) Universal PART 3. EXECUTION 3.1 CEILING GRID SYSTEM A. The Contractor and fixture supplier shall verify the type of ceiling grid system being used and shall provide assurance that the lighting fixtures being supplied for this project shall have the proper type of trim for the type of grid and ceiling material being used and that the lighting fixture will fit the grid system and remain secure within the ceiling grid system. Clips shall be installed to prevent grid spread from the lighting fixtures. 3.2 INSTALLATION OF INTERIOR LIGHTING FIXTURES A. Install interior lighting fixtures at locations and heights as indicated on drawings. B. Support fixtures from structural members of building, independent of ceiling. Support grid type fixtures from ceiling. Arrange with ceiling contractor for extra ceiling support. Provide one support at each corner of 2'X4' and larger fixtures, and one at each end at opposite corners of 1'x4' and 2'x2' fixtures. C. Provide devices for securing fixture to ceiling grid to comply with NEC (B). D. Submit hanging details to Consultant before fixture installation. sys-tek, P.A. Project No. Insert Number Section INTERIOR LIGHTING FIXTURES: Page 3

4 St. Monica Food Pantry E. Wire grid fixtures with flexible conduit individually to junction boxes. Do not wire fixture to fixture. F. Anchor high intensity discharge fixtures mounted in ceiling or on wall to structure. Support recessed ceiling fixtures independent of ceiling construction; supports to consist of 1/4" diameter bolts or rods. G. Support recessed incandescent fixtures with 3/4" black iron ceiling channel, one piece on each side of fixture, anchored to ceiling system. Support large recessed incandescent fixtures over 20 pounds independent of furred ceiling system with rods, size as required, anchored to structure. H. Support surface and pendant incandescent fixtures from 3/8" fixture stud in outlet box. Large surface or pendant incandescent fixtures (in excess of 20 pounds) with 3/8" rod run through the outlet box to structure and anchored independent of ceiling and conduit systems. I. Support surface and pendant fluorescent fixtures independent of furred ceiling with 1/4" rods anchored to structure. Provide one support for each 4 feet of fixture length, minimum of two supports required. Support fixtures mounted on grid type ceiling independent of ceiling with rods to structure. J. Provide plaster frames for recessed fluorescent luminaries in plaster and concealed spline ceilings supported independent of ceiling construction with 1/4" rod anchored to structure. K. Individual flexible connections to fixtures shall be made with 2#14 and 1#14 (ground) THHN-2 in 3/8" flexible conduit. Bond ground wire at each end. L. Stems on fluorescent fixtures shall be installed as follows (except fixtures with slide grip hangers): First and last stem in row shall be installed in first knockout from end of fixtures; one stem shall be installed between each two fixtures connect intermediate stems to center joint where fixtures join and attach by use of "joining plates". Provide adequate number of stems to completely support fixtures and keep fixtures aligned straight and plumb. M. Connect fixtures in continuous rows other than recessed grid type connected by nipples with locknuts and bushings. N. Furnish complete manufacturers shop drawing for continuous fixtures s O. Coordinate fixture installation with the other trades on the project prior to installation of ductwork, ceilings, etc. to eliminate any conflictions prior to construction of space. 3.3 GUARANTEE A. All lighting fixtures, components, accessories etc., except lamps, shall be guaranteed against defects in materials and workmanship for one (1) year from date of inservice acceptance by Owner. Replacement shall include parts and labor at the site of the work for the term of the warranty. B. Lamps shall be guaranteed as specified above. 3.4 FIELD QUALITY CONTROL A. Replace defective and burned out lamps for a period of one year following the Date of Substantial Completion. B. At Date of Substantial Completion, replace lamps in interior lighting fixtures which are observed to be noticeably dimmed after Contractor's use and testing, as determined by the Architect. C. Clean interior lighting fixtures of dirt and construction debris upon completion of installation. Clean fingerprints and smudges from lenses and lamps. D. Protect installed fixtures from weather and damage during remainder of construction period. E. Provide equipment grounding connections for interior lighting fixtures as indicated. sys-tek, P.A. Project No. Insert Number Section INTERIOR LIGHTING FIXTURES: Page 4

5 St. Monica Food Pantry F. Upon completion of installation of interior lighting fixtures, and after building circuitry has been energized, apply electrical energy to demonstrate capability and compliance with requirements. Where possible, correct malfunctioning units at site, then retest to demonstrate compliance; otherwise, remove and replace with new units, and proceed with retesting. END OF SECTION sys-tek, P.A. Project No. Insert Number Section INTERIOR LIGHTING FIXTURES: Page 5

SECTION LIGHTING

SECTION LIGHTING SECTION 16500 - LIGHTING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION LIGHTING PART 1- GENERAL

SECTION LIGHTING PART 1- GENERAL SECTION 16500 LIGHTING PART 1- GENERAL 1.01 WORK INCLUDED A. The Contractor shall provide all lighting fixtures, panelboards, labor, material, etc., in accordance with the preceding specifications, the

More information

SECTION MANUFACTURED CASEWORK

SECTION MANUFACTURED CASEWORK 1 GENERAL 1.1 SECTION INCLUDES SECTION 12300 MANUFACTURED CASEWORK A. Work required to complete the manufactured casework indicated by the Contract Documents, and the items necessary for its proper installation.

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

A. Deviation from this standard must be approved by the Project Architect.

A. Deviation from this standard must be approved by the Project Architect. September 2012, rev. 00 26 5600 Exterior Lighting PART 1. GENERAL 1.01 Related Documents A. Deviation from this standard must be approved by the Project Architect. B. Drawings and general provisions of

More information

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

DIVISION 26 ELECTRICAL SECTION ELECTRICAL

DIVISION 26 ELECTRICAL SECTION ELECTRICAL DIVISION 26 ELECTRICAL SECTION 26 1000 ELECTRICAL PART 1 - GENERAL 1.1 WORK INCLUDED A. Furnish all labor, material and equipment necessary for the complete installation of the Electrical System as shown

More information

SECTION LIGHTING FIXTURES AND LAMPS

SECTION LIGHTING FIXTURES AND LAMPS SECTION 16511 LIGHTING FIXTURES AND LAMPS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09200 - Metal Studs, Lath, Suspension Ceiling, Plaster, and Stucco. 2. 09510 - Acoustical Ceilings. 3. 16112

More information

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations. General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 53 00.00 40 (November 2015) ----------------------------------- Preparing Activity: NASA Superseding UFGS-26 53 00.00 40 (November 2008) UFGS-26 53 00 (August 2008)

More information

Music Area Casework General 1.01 Summary Related Sections Definitions Qualifications and Quality Assurance

Music Area Casework General 1.01 Summary Related Sections Definitions Qualifications and Quality Assurance 1.00 General 1.01 Summary Music Area Casework A. This section includes the following Scope of Work as referred to in the plans: 1. Thermally Fused Laminate manufactured casework, for use in music areas,

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

SPECIAL SPECIFICATION Inch LED Traffic Signal Lamp Unit

SPECIAL SPECIFICATION Inch LED Traffic Signal Lamp Unit 1993 Specifications SPECIAL SPECIFICATION 1201 12 Inch LED Traffic Signal Lamp Unit 1. Description. This specification describes the minimum acceptable design and performance requirements for a twelve

More information

SCI-FAB Product Specifications. Casework Section 1. Part 1 General

SCI-FAB Product Specifications. Casework Section 1. Part 1 General SCI-FAB Product Specifications Casework Section 1 Part 1 General 1.1 SCOPE OF WORK Includes all factory fabricated stainless steel casework as required by the project drawings. 1.2 TYPICAL INCLUSIONS A.

More information

Slate Shingle Specifications

Slate Shingle Specifications Slate Shingle Specifications California Slate is a proud member of the Slate Roofing Contractors Association of North America, Inc. (SRCA) which publishes Section 07310 Slate Shingles setting forth architectural

More information

SECTION ARCHITECTURAL WOOD CASEWORK

SECTION ARCHITECTURAL WOOD CASEWORK SECTION 06410 - ARCHITECTURAL WOOD CASEWORK PART 1 GENERAL 1.01 SECTION INCLUDES A. Wood cabinets for opaque finish. B. Flush wood paneling for transparent finish. C. Factory finishing. 1.02 RELATED REQUIREMENTS

More information

SECTION MEDICAL AND SURGICAL LIGHTING FIXTURES

SECTION MEDICAL AND SURGICAL LIGHTING FIXTURES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 55 71 MEDICAL AND SURGICAL LIGHTING FIXTURES SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph

More information

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410 DOCUMENT 009104 - ADDENDUM NO. 4 Issued to all Bidders: Date: October 14, 2015 Contract Name: Electrical Installation Contract Number: C8410 This addendum forms a part of the Bid described above. The original

More information

Inde-Pendants Family. 32L Surface Mount Cylinder Plaster Trim, Grid and Drywall Ceiling Types. Document No

Inde-Pendants Family. 32L Surface Mount Cylinder Plaster Trim, Grid and Drywall Ceiling Types. Document No Inde-Pendants Family 32L Surface Mount Cylinder Plaster Trim, Grid and Drywall Ceiling Types Installation instructions for 32L-C-S-D Document No. Supplied by Litecontrol 32L Inde-Pendants: Cylinder (Surface

More information

MOVEABLE GLASS WALL TECHNICAL DATA

MOVEABLE GLASS WALL TECHNICAL DATA Ideal for applications requiring space division, visibility, and security. Used in banks, office lobbies, conference areas, interior storefronts, and arena skyboxes. Clean look of secure, yet easily moveable

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

General Installation Instructions

General Installation Instructions General Installation Instructions WARNING To reduce the risk of death, injury or property damage from fire, electric shock, cuts, abrasions, falling parts and other hazards: Service of the equipment must

More information

B. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form.

B. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form. McKee and Associates Architecture and Interior Design Addendum No. THREE Date: 12.11.17 Project: A NEW BUILDING FOR THE GREATER LIMESTONE COUNTY CHAMBER OF COMMERCE ATHENS, ALABAMA A3.1 GENERAL PROJECT

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM 2004 Specifications CSJ 3622-01-001, ETC. SPECIAL SPECIFICATION 8398 LIGHTNING PROTECTION SYSTEM 1. Description. This Special Specification governs the design and installation of Lightning Protection System

More information

Regal Series Recessed Flatwalls

Regal Series Recessed Flatwalls Regal Series Recessed Flatwalls General Specifications The Amico Regal Series Recessed Flatwall shall be manufactured by Amico Corporation, in accordance with job specific shop drawings and documents.

More information

SeriesTWO RGB Fluorescent Fixtures. Installation and Instruction Manual

SeriesTWO RGB Fluorescent Fixtures. Installation and Instruction Manual SeriesTWO RGB Fluorescent Fixtures Installation and Instruction Manual Brightline LP 580 Mayer Street #7, Bridgeville PA 15017 Phone 1-412-206-0106 Fax 1-412-206-0146 www.brightlines.com The Brightline

More information

SECTION FINISH CARPENTRY PART 1 GENERAL. 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section.

SECTION FINISH CARPENTRY PART 1 GENERAL. 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section. SECTION 06200 - FINISH CARPENTRY PART 1 GENERAL 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section. 1.2 RELATED SECTIONS A. Section 06100 - Rough Carpentry:

More information

TOLL FREE:(888) FAX:(941) ASSEMBLY of ProTEC CONCRETE STRUCTURAL INSULATED PANEL

TOLL FREE:(888) FAX:(941) ASSEMBLY of ProTEC CONCRETE STRUCTURAL INSULATED PANEL ASSEMBLY of ProTEC CONCRETE STRUCTURAL INSULATED PANEL The ProTEC panels are manufactured with grooves on all four sides to accept the steel components. This grooving applies to the regular panel whose

More information

UFGS-16553N (Septermber 1999) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS-16553N (Septermber 1999) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 55 80.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-16553N (Septermber 1999) UNIFIED FACILITIES GUIDE

More information

REVISIONS Summary of Change. 6/1/12 All Replaced entire document with new revision

REVISIONS Summary of Change. 6/1/12 All Replaced entire document with new revision Revision Date Section REVISIONS Summary of Change 6/1/12 All Replaced entire document with new revision REV 6/12 1 of 5 UNIVERSITY CONTACT: INTERIOR LIGHTING Electrical Services, Maintenance & Operations

More information

Copyright 2017 AIA MasterSpec Premium 05/17 PRODUCT MASTERSPEC LICENSED BY ARCOM TO WEREVER PRODUCTS, INC.

Copyright 2017 AIA MasterSpec Premium 05/17 PRODUCT MASTERSPEC LICENSED BY ARCOM TO WEREVER PRODUCTS, INC. This Product MasterSpec Section is licensed by ARCOM to Werever Products, Inc. ("Licensee"). This proprietary Product MasterSpec Section uses modified original MasterSpec text. Revisions made to the original

More information

A. This Section includes plumbing fixtures and related components.

A. This Section includes plumbing fixtures and related components. SECTION 224200 PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 00 00.00 20 (July 2006) ------------------------------- Preparing Activity: NAVFAC Superseding UFGS-26 00 00.00 20 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

CaseworkUSA. specifications. 1.1 General 1.2 Summary. 1.3 Related Sections. 1.4 Definitions. 1.5 Qualifications and Quality Assurance

CaseworkUSA. specifications. 1.1 General 1.2 Summary. 1.3 Related Sections. 1.4 Definitions. 1.5 Qualifications and Quality Assurance 1.1 General 1.2 Summary A. This section includes the following Scope of Work as referred to in the plans: 1. Plastic laminate manufactured casework 2. Plastic laminate countertops 1.3 Related Sections

More information

Solid Surface Countertops

Solid Surface Countertops USE THIS SECTION FOR COUNTERTOPS. USE SECTION 06 61 16 FOR OTHER SOLID SURFACING APPLICATIONS INCLUDING WALL CLADDING AND MISCELLANEOUS FABRICATIONS. GENERAL NOTES TO SPECIFIER: THIS SPECIFICATION SECTION

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

SECTION EQUIPMENT WIRING

SECTION EQUIPMENT WIRING PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 26 27 17 EQUIPMENT WIRING A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General Provisions,

More information

D. Product Certificates: Signed by manufacturers of casework certifying that products furnished comply with requirements.

D. Product Certificates: Signed by manufacturers of casework certifying that products furnished comply with requirements. SECTION 12356 - CASEWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION LAP SIDING. A. Fiber cement lap siding, panels, single, trim, fascia, moulding and accessories.

SECTION LAP SIDING. A. Fiber cement lap siding, panels, single, trim, fascia, moulding and accessories. SECTION 07460 LAP SIDING PART 1 GENERAL 1.1 SECTION INCLUDES A. Fiber cement lap siding, panels, single, trim, fascia, moulding and accessories. B. Factory-finished fiber cement lap siding, panels, single,

More information

J-BOX. 3-O or 4-0 MUD RING J-BOX BRACKET BAR CABLE GRIPPER/ CANOPY MOUNTING STUD 8-32 BRACKET BAR SCREWS CANOPY STRAIN RELIEF POWER CORD CANOPY

J-BOX. 3-O or 4-0 MUD RING J-BOX BRACKET BAR CABLE GRIPPER/ CANOPY MOUNTING STUD 8-32 BRACKET BAR SCREWS CANOPY STRAIN RELIEF POWER CORD CANOPY KELSEY - CSS Cable Suspended Rotational and Static CSS - Cable Suspended 3-O or 4-0 MUD RING BRACKET BAR 1/4-20 STUD 8-32 BRACKET BAR SCREWS STRAIN RELIEF POWER CORD MOUNTING GRIPPER AIRCRAFT CABLE CABLE

More information

Lightplane 3.5 Recessed

Lightplane 3.5 Recessed INSTALLATION INSTRUCTIONS Lightplane 3.5 Recessed LP3.5R Recessed Ceiling IMPORTANT SAFETY INSTRUCTIONS When installing or using this fixtures basic safety precautions must be followed. Read all instructions

More information

Product Guide Specification

Product Guide Specification Extrutech Plastics, Inc. September 2012 5902 West Custer Street Manitowoc, Wisconsin 54220 Toll Free 888-818-0118 Phone 920-684-9650 Fax 920-684-4344 Website www.epiplastics.com E-mail info@epiplastics.com

More information

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION PRE-MANUFACTURED CABINETS

SECTION PRE-MANUFACTURED CABINETS SECTION 12390 PRE-MANUFACTURED PART 1 GENERAL 1.1 DESCRIPTION OF WORK A. The work includes furnishing all labor, materials and equipment required to complete the Pre-Manufactured Cabinet work as shown

More information

SECTION FRAMELESS GLASS SLIDING BI-FOLD SHOWER DOOR HARDWARE

SECTION FRAMELESS GLASS SLIDING BI-FOLD SHOWER DOOR HARDWARE 1 SECTION 10 2880 FRAMELESS GLASS SLIDING BI-FOLD SHOWER DOOR HARDWARE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

A. Extent of structural precast concrete work is shown on drawings and in schedules.

A. Extent of structural precast concrete work is shown on drawings and in schedules. SECTION 03 41 00 - STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification

More information

SECTION INTERIOR SIGNAGE

SECTION INTERIOR SIGNAGE SECTION 10 14 02 INTERIOR SIGNAGE PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by

More information

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available. SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

General Installation Instructions LED

General Installation Instructions LED General Installation Instructions LED To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions and other hazards, please read all warnings

More information

4. Metal roof jacks at penetrations and attachments

4. Metal roof jacks at penetrations and attachments - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SECTION 07 61 00 METAL SHINGLE ROOFING - - - - - - - - - - -

More information

SECTION SUBMITTALS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION SUBMITTALS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 013300 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section 02760-1 of 5 SECTION 02760 STEEL LIGHTING STANDARDS 02760.01 GENERAL A. Description Steel lighting standards shall include, but not necessarily be limited to, furnishing and installing steel lighting poles,

More information

CEILING SYSTEMS. Between us, ideas become reality. Installing. Suspended Ceilings. International Version

CEILING SYSTEMS. Between us, ideas become reality. Installing. Suspended Ceilings. International Version CEILING SYSTEMS Between us, ideas become reality Installing Suspended Ceilings International Version 1 Installing Armstrong Suspended Ceilings An Armstrong suspended mineral fiber ceiling is functional,

More information

Inde-Pendants Family. 32L Surface Mount Cylinder with Ring Plaster Trim, Grid and Drywall Ceiling Types. Document No

Inde-Pendants Family. 32L Surface Mount Cylinder with Ring Plaster Trim, Grid and Drywall Ceiling Types. Document No Inde-Pendants Family 32L Surface Mount Cylinder with Ring Plaster Trim, Grid and Drywall Ceiling Types Installation instructions for 32L-CRxx-S-D Document No. Supplied by Litecontrol 32L Inde-Pendants:

More information

A. Columns: Worthington Millwork; Cellular Polyvinyl Chloride (PVC) columns; decorative, weatherproof, insect-proof, and highly durable.

A. Columns: Worthington Millwork; Cellular Polyvinyl Chloride (PVC) columns; decorative, weatherproof, insect-proof, and highly durable. WorthingtonWrap PVC Columns Architectural Specifications 1.1 SECTION INCLUDES A. Columns: Worthington Millwork; Cellular Polyvinyl Chloride (PVC) columns; decorative, weatherproof, insect-proof, and highly

More information

SECTION CUSTOM CASEWORK

SECTION CUSTOM CASEWORK PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 06 41 00 CUSTOM CASEWORK A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification sections,

More information

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018 SECTION 055000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. PAGE 1 PART 1 GENERAL 1.1 REFERENCE.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. 1.2 RELATED WORK SPECIFIED ELSEWHERE.1 Installation

More information

Ductwork Controls and Instrumentation Outlets (HVAC) HVAC Control System.

Ductwork Controls and Instrumentation Outlets (HVAC) HVAC Control System. SECTION 15910 DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15890 - Ductwork. 2. 15900 - Controls and Instrumentation. 3. 15940 - Outlets (HVAC). 4. 15970 - HVAC Control System.

More information

INSTALLATION INSTRUCTION Solorail - Low Voltage Starter Kit

INSTALLATION INSTRUCTION Solorail - Low Voltage Starter Kit IMPORTANT SAFETY INSTRUCTIONS: Read all instructions. Turn off power at main switch before installing or modifying the system. Do not install the system: - Within six inches of any curtain or combustible

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-08 33 13 (May 2009) Change 2-11/12 --------------------------- Preparing Activity: USACE Nontechnical Title Revision (August 2015) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Panel Grille Suspended Ceiling Installation Guide

Panel Grille Suspended Ceiling Installation Guide Panel Grille Suspended Ceiling Installation Guide World Commerce Center 2000 Ring Way Road, St. Augustine, FL 32092 Phone: 800-227-8566 or 904-584-1400 www.rulonco.com Receipt and Storage: a. All material

More information

XL MAX. Suspension System Data Center Ceiling Solutions. Assembly and Installation Instructions

XL MAX. Suspension System Data Center Ceiling Solutions. Assembly and Installation Instructions PRELUDE Top Lock XL MAX (4) #8 x 1/" Long Main Beam Sharp Point Truss Head Screws Suspension System Data Center Ceiling Solutions Assembly and Installation Instructions SYSTEM OVERVIEW The Prelude XL Max

More information

B. Division-16 Basic Materials and Methods section apply to work specified in this section.

B. Division-16 Basic Materials and Methods section apply to work specified in this section. Section 16745 PREMISE CABLING SYSTEMS PART ONE GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

ENDUREED VIVA SERIES Specifications

ENDUREED VIVA SERIES Specifications ENDUREED VIVA SERIES Specifications SECTION 07312 HDPE THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Viva Series synthetic thatch shingles.

More information

Inde-Pendants Family. 32L Ring Plaster Trim, Grid and Drywall Ceiling Types. Document No Installation instructions for 32L-Rxx-P

Inde-Pendants Family. 32L Ring Plaster Trim, Grid and Drywall Ceiling Types. Document No Installation instructions for 32L-Rxx-P Inde-Pendants Family 32L Ring Plaster Trim, Grid and Drywall Ceiling Types Installation instructions for 32L-Rxx-P Document No. Supplied by Litecontrol 32L Inde-Pendants: Ring (Plaster Trim, Grid and Drywall

More information

5 ACCESS PANEL INSTALLATION SPACER *SLIDE TO LOCATION OF FASTENER DURING INSTALLATION OF EACH FASTENER

5 ACCESS PANEL INSTALLATION SPACER *SLIDE TO LOCATION OF FASTENER DURING INSTALLATION OF EACH FASTENER 1/2 K.O. (3/8 K.O. on 165 with factory supplied 3/8 flex conduit fitting) TR - Trim Flange Side Blocking Install Method Secure fixture to structure following instructions below: 1. Remove lens and internal

More information

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following:

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following: SECTION 01 31 00 PROJECT MANAGEMENT AND COORDINATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

WARNINGS & SAFETY INFORMATION: PLEASE READ CAREFULLY AND KEEP A COPY ON THE PROPERTY FOR FUTURE REFERENCE!

WARNINGS & SAFETY INFORMATION: PLEASE READ CAREFULLY AND KEEP A COPY ON THE PROPERTY FOR FUTURE REFERENCE! WARNINGS & SAFETY INFORMATION: PLEASE READ CAREFULLY AND KEEP A COPY ON THE PROPERTY FOR FUTURE REFERENCE! General Safety Information To reduce the risk of death, personal injury or property damage from

More information

SECTION WOOD DOORS

SECTION WOOD DOORS SECTION 08211 WOOD DOORS Notice to Vendors: CANV prefers to purchase products that contain tropical wood only if they are certified according to the guidelines of the Forest Stewardship Council (FSC).

More information

Bovard Studios Inc. Section April 6, 2004 Page 1

Bovard Studios Inc. Section April 6, 2004 Page 1 April 6, 2004 Page 1 This section includes solid flush and surface articulated wood doors, may have veneer facing, solid or glazed (stained glass) design, factory pre-fit, may be factory finished or site

More information

DETAILED STILE AND RAIL WOOD DOOR SPECIFICATION

DETAILED STILE AND RAIL WOOD DOOR SPECIFICATION DETAILED STILE AND RAIL WOOD DOOR SPECIFICATION UNIVERSITY CONTACT: Structural Services, Maintenance & Operations (302) 831-8456 PART 1 GENERAL DOORS 1.01 GENERAL PROVISIONS 1. The Drawings and General

More information

Line volt rail & fixtures. Low volt quick connect fixtures with transformers

Line volt rail & fixtures. Low volt quick connect fixtures with transformers INSTRUCTIONS: Line Volt Flexrail2 Safety Instructions: A qualified electrician must install system only. System is intended for installation in accordance with National Electric Code, local and Federal

More information

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 051200 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION (10670) - WIRE CLOSET AND UTILITY SHELVING

SECTION (10670) - WIRE CLOSET AND UTILITY SHELVING SECTION 10 57 23.13 (10670) - WIRE CLOSET AND UTILITY SHELVING PART 1 GENERAL 1.01 SUMMARY 1. Wire Closet Shelves B. Related Sections: 1.02 SUBMITTALS 1. Section 06 10 00 (06100) - Rough Carpentry A. Submit

More information

DOWNLIGHT LED SERIES INSTALLATION INSTRUCTIONS

DOWNLIGHT LED SERIES INSTALLATION INSTRUCTIONS WARNING: This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved. Make sure all

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

AMPCO PRODUCTS, INC. TECHNICAL SPECIFICATIONS SOLID PHENOLIC CORE TOILET COMPARTMENTS

AMPCO PRODUCTS, INC. TECHNICAL SPECIFICATIONS SOLID PHENOLIC CORE TOILET COMPARTMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS TECHNICAL SPECIFICATIONS SOLID PHENOLIC CORE TOILET COMPARTMENTS A. Drawings and General Provisions of Contract, including General and Supplementary Conditions and

More information

Section. DEVELOPMENT STANDARDS City of Ellensburg ILLUMINATION STANDARDS

Section. DEVELOPMENT STANDARDS City of Ellensburg ILLUMINATION STANDARDS Section 8 City of Ellensburg ILLUMINATION STANDARDS Table of Contents STREET ILLUMINATION...3-5 GENERAL NOTES...3 INSTALLATION AND CONNECTIONS...3 MARKING...3 STAKING...3-4 TRENCH REQUIREMENTS...4 ILLUMINATION

More information

INSTALLATION: D1-NOTCH DRYWALL TRIM FLANGE

INSTALLATION: D1-NOTCH DRYWALL TRIM FLANGE T F W 604.549.979 604.549.9555 fluxwerx.com INSTALLATION: D1-NOTCH DRYWALL TRIM FLANGE fixture housing endcap kit optic kit join kit notch 2 cross section notch 4 cross section 4 4" 4-11/2" 4 /8 (111)

More information

E L E G A N C E A N D S O P H I S T I C AT I O N

E L E G A N C E A N D S O P H I S T I C AT I O N E L E G A N C E A N D S O P H I S T I C AT I O N CurVista: Slender, luminescent blades are placed along each side of an elegant curvature to create unparalleled aesthetics. Sophisticated in style and function,

More information

A. It is preferred that all submittals to be submitted electronically in PDF format.

A. It is preferred that all submittals to be submitted electronically in PDF format. June 20 2013, Rev 00 10 2800 Toilet, Bath, and Laundry Accessories PART 1. GENERAL 1.01 This Section includes: A. Toilet room accessories: 1.02 Submittals 1. Grab bars 2. Metal framed mirrors 3. Sanitary

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

Storefront Installation Guide

Storefront Installation Guide Storefront General Notes: 1. Check Contract Documents and Shop Drawings. Understand and clarify any Field Verify Notes and approvals of drawings and products to be familiar with the project. Installation

More information

SECTION WOOD SHINGLES

SECTION WOOD SHINGLES SECTION 07 31 29.13 WOOD SHINGLES SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. This guide specification does not include requirements

More information

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related

More information

A. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension.

A. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension. HIGGINSVILLE HABILITATION CENTER MISC. BUILDING RENOVATIONS STATE OF MISSOURI HIGGINSVILLE, MISSOURI SECTION 061000 - ROUGH CARPENTRY PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-27 05 28.36 40 (August 2011) ----------------------------------- Preparing Activity: NASA Superseding UFGS-27 05 28.36 40 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Fold-A-Way Patio Door ASSEMBLY & INSTALLATION GUIDE

Fold-A-Way Patio Door ASSEMBLY & INSTALLATION GUIDE Fold-A-Way Patio Door ASSEMBLY & INSTALLATION GUIDE This instruction guide provides the minimum recommended procedures to correctly prepare the rough opening, install a fold-a-way patio door unit and apply

More information

Design and Construction Standards SECTION ATHLETIC LOCKERS

Design and Construction Standards SECTION ATHLETIC LOCKERS SECTION 10505 ATHLETIC LOCKERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The provisions of the General Conditions, Supplementary Conditions, and the Sections included under Division 1, General Requirements,

More information

SUNSET & FRANCISQUITO SHOPPING CENTER S I G N P R O G R A M

SUNSET & FRANCISQUITO SHOPPING CENTER S I G N P R O G R A M SUNSET & FRANCISQUITO SHOPPING CENTER WEST COVINA, CALIFORNIA S I G N P R O G R A M PROJECT LOCATION: 1200-1314 West Francisquito Ave., West Covina, CA 91790 PREPARED BY: 6399 Wilshire Blvd., Ste. #604

More information

SECTION SIGNAGE

SECTION SIGNAGE SECTION 10 14 00 SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1 specification section, apply

More information

SAVE THESE INSTALLATION INSTRUCTIONS

SAVE THESE INSTALLATION INSTRUCTIONS Light Without Boundaries LUMATO RESERVES THE RIGHT TO CHANGE PRODUCT 7500003 8/4 Light Without Boundaries LUMATO RESERVES THE RIGHT TO CHANGE PRODUCT GENERAL INSTALLATION WARNING To Reduce Risk Of Death,

More information

Aluminum Clad Wood Window 1/2 Reinforced Field Mulling and Stacking Supplement

Aluminum Clad Wood Window 1/2 Reinforced Field Mulling and Stacking Supplement Aluminum Clad Wood Window 1/2 Reinforced Field Mulling and Stacking Supplement 1 Aluminum Clad Wood Window 1/2 Reinforced Field Mulling and Stacking Supplement The following instructions are a supplement

More information

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal City of Winnipeg Brady Road Landfill Site Section 01300 New Entrance and Scale Facility Page 1 of 4 SUBMITTALS 1. SHOP DRAWINGS 1.1 General.1 Arrange for the preparation of clearly identified Shop Drawings

More information

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia BULLETIN NO. 6 TO THE PLANS AND SPECIFICATIONS FOR JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia EwingCole Architects.Engineers.Interior Designers.Planners

More information