LIFT APPLICATION GUIDELINES COURTROOM WHEELCHAIR LIFTS ACCESSOR I MODEL VMW-09 ACCESSOR II MODEL VMX-07

Size: px
Start display at page:

Download "LIFT APPLICATION GUIDELINES COURTROOM WHEELCHAIR LIFTS ACCESSOR I MODEL VMW-09 ACCESSOR II MODEL VMX-07"

Transcription

1 LIFT APPLICATION GUIDELINES COURTROOM WHEELCHAIR LIFTS ACCESSOR I MODEL VMW-09 ACCESSOR II MODEL VMX-07

2 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES TALE OF CONTENTS GENERAL INFORMATION...3 PURPOSE...3 PRODUCT OVERVIEW...3 SUITALE LIFT APPLICATIONS...3 APPLICATION GUIDELINES...4 LIFT MODEL SELECTION...4 SIZE AND DOOR OPENING LIMITATIONS...4 ACCESSOR SPECIFICATIONS...5 COMPONENTS SUPPLIED Y...5 REGULATORY REQUIREMENTS...7 RESPONSIILITY OF OTHERS...8 SCOPE OF WORK Y OTHERS...8 INTERFACE REQUIREMENTS...8 REGULATORY COMPLIANCE Y OTHERS...9 COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 2 REV J 4/16

3 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES GENERAL INFORMATION PURPOSE has prepared this document for the purpose of providing building owners and owner representatives such as architects, contractors, and installers with information specific to design planning, special provisions, installation considerations, and regulatory compliance responsibility relevant to the Accessor I Model VMW and Accessor II Model VMX Courtroom Wheelchair Lifts, hereinafter referred to as VMW and VMX respectively. The information presented in this document is fairly generic for VMW and VMX lift applications and not intended to address every detail or special conditions that may be encountered on a project. PRODUCT OVERVIEW y way of introduction, the VMW and VMX lift models are not conventional Vertical Platform Lifts comprised of a car with platform mounted sidewalls, but rather the VMW and VMX are comprised of a platform that raises and lowers within the confines of stationary millwork walls and the closed entrance/exit doors hingedly attached thereto. Subsequently, the lift layout is customized for each application. SUITALE LIFT APPLICATIONS The VMW and VMX Courtroom Wheelchair Lifts are specifically designed for use in courtrooms to facilitate mobility-impaired judges, witnesses, clerks, and jurors. COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 3 REV J 4/16

4 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES LIFT MODEL SELECTION APPLICATION GUIDELINES Accessor I Model VMW 1. The four (4) screw jack column design permits the lift to be installed directly on the lower landing floor without the need for a pit. 2. The lift screw columns, base frame, and drive train are encased in millwork walls surrounding the lift platform, thus requiring the coordination of other trades. 3. The drive motor and electronics are located under the upper landing. 4. Refer to exemplar Lift Configuration drawing which is included in this document. Accessor II Model VMX 1. The lever-screw design requires the lift to be installed in a pit or sub-floor at least 6 inches below the lower landing floor; recommends 7 inches. 2. The lift drive mechanism, motor, and electronics are oriented under the upper landing, thus minimizing the influence on millwork walls surrounding the lift platform. 3. Refer to exemplar Lift Configuration drawing which is included in this document. For graphic illustration of these design differences and the variables to consider when planning for a particular lift application, as well as s recommended interface design principles for the lift and optional equipment, refer to exemplar Lift Configuration drawings and along with the following drawings included near the back portion of this document: , VMW Lift / Millwork Interface , Roll-up arrier / Millwork Interface , Step Module / Millwork Interface , Door Set-up Alternatives , Strike Latch / Millwork Interface , Operable Step / Millwork Interface , Roll-Up arrier Overview , Retractable Step Overview , Operable Step Overview , Electromagnetic Door Holder / Millwork Interface , Door Operator Overview , Door Operator / Millwork Interface , Over 24 to 42 Upper Landing Roll-Up arrier / Millwork Interface , Door Operator / Millwork Interface , Door Operator / Millwork Interface , Door Operator / Millwork Interface To further facilitate the architectural design process, design files such as 2D CAD drawings and 3D images, contact at or at markramos@hoganmfg.com or donbirdsall@hoganmfg.com. COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 4 REV J 4/16

5 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES SIZE AND DOOR OPENING LIMITATIONS The advantage of using the VMW or VMX is that the platform size and layout can be customized for each application, as well as orientation and placement of the entrance/exit doors. e advised, there are certain limitations to be aware of with respect to minimum and maximum dimensions. The minimum platform size and minimum door opening are contingent upon door orientation, i.e., whether the lift provides straight through access or involves a 90 degree turn for the wheelchair-bound passenger. For illustration of available orientations and preferred minimum dimensions refer to template layout drawings thru for the VMW and thru for the VMX near the back portion of this document. Further, the maximum platform size per code is no greater than 25 sq. ft. However, certain applications may be cause for exception and must be evaluated on a case-by case basis. Exceeding 25 sq. ft. may require a variance from the authority having jurisdiction. The best method to prevent exceeding the 25 sq. ft. maximum platform size, particularly for courtroom lift applications where the witness stand or clerk bench footprint may be larger than 25 sq. ft., is to include the Roll-up arrier in the witness/clerk landing. Since space in the interior of the witness stand or clerk bench is typically too restrictive for a hinged self-closing door, the Roll-up arrier is a practical alternative. The Roll-up arrier is also practical for non-courtroom lift applications when door swing is an issue. The Roll-up arrier is illustrated in context on drawing , Roll-up arrier Overview. Additional details are shown on drawing , titled Roll-up arrier/millwork Interface. oth drawings are included near the back portion of this document. ACCESSOR SPECIFICATIONS 1. Platform dimensions vary for each application. 2. Lift capacity (maximum operating load): 750 lbs for platforms less than or equal to 18 ft lbs for platforms greater than 18 ft Speed is 10 ft./min. maximum. 4. Maximum vertical travel is limited to 24 inches. 5. Manual lowering device is included. 6. Factory finish for all steel framework is black powder-coat. 7. Power source requirements are 115 VAC, 15 amp, 3 wire, single-phase service. COMPONENTS SUPPLIED Y The lift package as delivered includes the following: 1. Lift Assembly. 2. Threshold Ramp (if applicable). 3. Electrical Control Panel with Lockable Disconnect. 4. Operator Control Stations (call buttons). 5. Electric Strike Latches. 6. Spring-loaded Latch olts. 7. Anchor olts. 8. Roll-up arrier Module (if applicable). 9. Retractable Step Module (if applicable). COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 5 REV J 4/16

6 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES 10. Hinged Riser VMW (if applicable). 11. Fixed Riser VMX (if applicable). 12. attery ack-up / UPS (if applicable). 13. Operable Step (if applicable). 14. Electromagnetic Door Holder (if applicable) 15. Door Operator (if applicable) COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 6 REV J 4/16

7 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES REGULATORY REQUIREMENTS Vertical Platform Lift design, construction, installation, operation, inspection, testing, maintenance, and repair is specified in Standards developed and published by The American Society of Mechanical Engineers (ASME), entitled ASME A18.1 Safety Standard For Platform Lifts And Stairway Chairlifts. The ASME Standard is intended to serve as the basis for state, municipal, and other jurisdictional authorities in drafting regulations governing Vertical Platform Lifts. With respect to A18.1 effectivity in each jurisdiction, the edition date in effect established by the local jurisdiction may vary; therefore, the local regulations from the authority having jurisdiction (AHJ) must be reviewed prior to each lift installation. For ASME A18.1 references sited in this document, the latest 2014 edition is used. Regarding ASME A18.1, Section 2 categories, refer to Section for courtroom lift applications. Due to architecturally desired features, certain VMW and VMX applications may not comply to the letter with all the requirements specified in the A18.1 Standard. In those cases, a variance must be requested for certain specification deviations from the authority having jurisdiction. Typically a variance application for the VMW and VMX will address items such as platform size, stationary millwork walls, millwork wall height and door height, and intermediate landing guard (if applicable). If a variance is necessary will, on behalf of the building owner, facilitate expediting the variance application. The basis for a variance request is expressly permitted by A18.1 para. 1.2, which states: The purpose of this Standard is to provide for the safety of life and limb, and to promote the public welfare. The provisions of this Standard are not intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety to those prescribed by this Standard provided that there is technical documentation to demonstrate the equivalency of the system, method, or device. The specific requirements of this Standard shall be permitted to be modified by the authority having jurisdiction based upon technical documentation or physical performance verification to allow alternative arrangements that will assure safety equivalent to that which would be provided by conformance to the corresponding requirements of this Standard. For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer to the section entitled, Regulatory Compliance by Others, on page 9 of this document. COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 7 REV J 4/16

8 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES RESPONSIILITY OF OTHERS SCOPE OF WORK Y OTHERS The design, materials, construction, and installation of the following items are the responsibility of others. 1. Lift support structure/foundation. 2. Site preparations, including main electrical power connection to lift power input. 3. Prior to installation, placement of lift must be defined. Chalk lines may be used to outline exact lift location. 4. uilding elements and millwork that encase the lift mechanism adjacent to and surrounding the lift platform, including but not limited to structural framing and veneered panel finishes. 5. Doors, including self-closing spring hinges. 6. Installation of lift control panels (supplied by ). 7. Installation of door strike latches (supplied by ). 8. Illumination of lift area. 9. Platform floor covering material. 10. Removable step (if applicable). INTERFACE REQUIREMENTS Space and structural provisions shall be provided in building elements and millwork to accommodate the lift assembly, motor, and electronics. As non-limiting examples, the following features shall be included: 1. Adequate clear space is required under the upper landing for the lift drive mechanism, motor, and electronics. 2. A service hatch is required in the upper landing floor approximate to the motor and electronics. The size of the service hatch shall be sufficient for access to the main power disconnect and to facilitate maintenance. 3. Cutout reliefs in the millwork are required for lift frame clearance and operational lift elements. 4. Interior millwork panels adjacent to the lift platform shall be smooth. 5. With respect to the VMW, the interior millwork panels are to be made removable to facilitate lift maintenance. 6. Running clearance between platform edges and adjacent millwork surfaces shall be no less than inch nor more than 0.75 inch. Refer to applicable Lift Configuration drawing for layout, orientation, and controlling dimensions for each project. COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 8 REV J 4/16

9 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES REGULATORY COMPLIANCE Y OTHERS The ASME A18.1 specifies requirements for the design, construction, installation, operation, inspection, testing, maintenance, and repair for Vertical Platform Lifts. With respect to the VMW and VMX installation, while is required to certify that the lift complies with the A18.1 Standard and any variance decisions granted by the AHJ, there are certain requirements associated with elements necessary for the installation of a complete lift system that are not provided by, and therefore require the cooperation of other trades contracted by the building owner. Subsequently, these other trades are responsible for compliance with the A18.1 requirements related to their respective work. These elements are itemized in the Scope of Work by Others noted on page 8 of this document. hereby advises the building owner, or owner s designated representative, of the owner s responsibility to communicate the applicable A18.1 requirements to the appropriate trades. To facilitate this effort, has summarized below the A18.1 requirements that other trades involved with the lift installation must comply with - refer to the A18.1 Standard for complete text. Applicable to Courtroom Lift Installations Upper Landing Entrance A door measuring at least 36 inches high shall guard the entrance. Door shall be unperforated. Door shall be self-closing. Door shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation. Clearance between the door and platform edge shall not be less than inch nor more than 0.75 inch Vertical Fascia A vertical fascia shall be provided from the upper landing sill and any intermediate landing sill to the lower landing and shall guard the full width of the platform. If openings are necessary in the fascia for operation, they shall reject a ball 0.5 inch in diameter. Fascia shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation. Clearance between the fascia and platform edge shall not be less than inch nor more than 0.75 inch Lower Landing Entrance A door measuring at least 36 inches high shall guard the entrance. Door shall be unperforated. Door shall be self-closing. Door shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation. COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 9 REV J 4/16

10 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES Clearance between the door and platform edge shall not be less than inch nor more than 0.75 inch Stationary Runway Guards [millwork sidewalls] Sides of the platform not used for entrance or exit shall be guarded by stationary millwork walls that extend to a height of at least 36 inches above the lower landing. Millwork walls shall be unperforated. Openings necessary for lift operation shall reject a ball 0.5 inch in diameter. Clearance between stationary millwork walls and the platform edge shall not be less than inch nor more than 0.75 inch Doors / Guards Doors shall be provided with a combination mechanical lock and electric contact. furnishes the electric strike latches and associated wiring to interface with the lift control system, which are incorporated by other trades. Applicable to oth Courtroom and Non-Courtroom Lift Installations Protrusions No hardware shall project beyond the vertical line of travel of the platform. For witness stands that may include a desk or counter top positioned within the vertical line of travel of the platform, recommends desk and counter tops either be mounted to the lift platform and thus move with the lift, or be hinge mounted to the millwork or removable to prevent a potential hazard to the passenger Platform Running Clearance The running clearance between the entrance and exit sides of the platform floor and the interior of the runway enclosure [millwork walls] shall not be less than inch nor more than 0.75 inch Pipes in Runway Vicinity No piping is permitted in the runway [lift footprint] Structural Support The structure on which the equipment is installed shall be capable of safely supporting the loads imposed. provides the building owner, or owner s representative, with the appropriate load data Headroom Clearance Headroom clearance throughout the range of travel shall be not less than 79 inches as measured vertically from the platform floor. Refer to the Lift Configuration drawing for lift operational envelope dimensions. COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 10 REV J 4/16

11 Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES rackets, Fastenings, and Supports The guide-rail brackets, their fastenings and supports, such as building beams and walls, shall be capable of resisting the horizontal forces imposed by rated load with a total deflection to the point of support not in excess of inch. [Related to millwork walls that encase the VMW screw columns] Design and Strength of rackets and Supports The building construction forming the supports for the guide rails, and the guide-rail brackets, shall be designed to safely withstand the application of the platform when stopping the platform and its rated load; and withstand the forces specified in para within the deflection limits specified. Where necessary, the building construction shall be reinforced to provide adequate support for the guide rails. [Related to millwork walls that encase the VMW screw columns] Guiding Member Enclosures The guiding members shall be guarded to prevent accidental contact. Any openings necessary in guards for operation, they shall reject a ball 0.75 inch in diameter. [Related to millwork walls that encase the VMW screw columns] Guarding All suspension means shall be guarded against accidental contact. Suspension means, which operate within a guide or track and travel at the same speed and in the same direction as the platform shall be considered suitably guarded. [Related to millwork walls that encase the VMW screw columns or VMX mechanism] Illumination At the threshold of the floor, with the landing door open, the minimum illumination shall be not less than 5 ftc (50 lx) During operation, the minimum illumination on the floor and controls shall be not less than 5 ftc (50 lx) An auxiliary illumination source to provide general illumination of not less then 0.2 ftc (2.2 lx) on the floor and controls shall be provided. The auxiliary system shall be automatically activated when normal illumination power fails and shall be capable of maintaining the above illumination intensity for a period of not less than 4 hr and shall use no fewer than two lamps of approximately equal wattage Operator Control Stations Controls shall be located between 48 inches maximum and 15 inches minimum above the platform floor or facility floor or ground level. COPYRIGHT 2016 DOC ALL RIGHTS RESERVED 11 REV J 4/16

12 WALL THRESHOLD RAMP.50 NOMINAL RUNNING CLEARANCE (.38 MIN /.75 MAX) R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED CAL 6/21/2006 REVISED STRIKE LATCH NOTE ON SHT 1 CAL 9/7/2007 C UPDATED MODEL PER CURRENT DESIGN R 9/21/2011 STRUCTURAL FRAMING C D LIFT WALL SEGMENT PLAN VIEW A A WALL HT TD Y DESIGNER ( HT +36"-42").50 CONTROL STATION HT 42" - 48" ELECTRIC STRIKE LATCH - REFER TO DRAWING FOR MORTISE DIMENSIONS AND MOUNTING DETAILS. TRAVEL +3" CUT RELIEF SLOT IN INTERIOR PANEL TO ALLOW VERTICAL TRAVEL OF CARRIAGE RACKET C LIFT SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) WALL SEGMENT ELEVATION VIEW C D NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED LIFT / INTERFACE. FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. THE VMW LIFT MECHANISM (i.e., SCREW COLUMNS, ASE FRAME, AND DRIVE TRAIN) IS ENCASED IN WALLS SURROUNDING A LIFT THAT TRAVELS UP AND DOWN. SINCE THE IS FURNISHED AND INSTALLED Y OTHERS THE INTERFACE OF THE TO THE LIFT IS CRITICAL TO A SUCCESSFUL INSTALL- ATION, WHEREIN THE WALL SYSTEM IS NOT ONLY STRUCTURALLY SOUND AND AESTHETCIALLY APPEALING, UT JUST AS IMPORTANT SPECIFIC PROVISIONS AND CLEARANCES TO ACCOMMODATE CERTAIN LIFT ELEMENTS ARE ALSO INCLUDED IN THE TO ENSURE PROPER LIFT OPERATION AND SERVICAILITY. ONLY A SMALL SEGMENT OF WALL AND ONE SCREW COLUMN IS SHOWN ON THIS DRAWING. THE SAME DESIGN PRINCIPLES CAN E APPLIED TO THE OTHER WALLS ORDERING THE LIFT. ENLARGED VIEW OF WALL SEGMENT WITH INTERIOR PANEL REMOVED (SEE SHEETS 2-4 FOR SECTIONS AND DETAILS) VMW LIFT / INTERFACE C 1 OF 4

13 PROVIDE HOLES FOR ROUTING ELECTRICAL CALES PROVIDE HOLES FOR ROUTING ELECTRICAL CALES INTERIOR SURFACES WITHIN THE RANGE OF LIFT MOTION MUST E SMOOTH SHEET METAL ANGLES ON SCREW JACK COLUMNS FACILITATE THE ATTACHMENT OF FRAMING AND VENEERED PANELS FINISH TREATMENT SUCH AS TOP CAP AND EXTERIOR TRIM DETAILS TD Y DESIGNER G DOOR JAM IS SHOWN CUT INTO INTERIOR PANEL. JAM CONFIGURATION MAY VARY TO SUIT DOOR AND DESIGN. SECTION A-A PROVIDE OPENING IN STRINGER AT SCREW COLUMN TO ACCESS EARING FASTENERS C (TALL COLUMN) C (SHORT COLUMN) FRAME STRINGERS E EXTERIOR PANEL OR LOCKING MATERIAL MAY E FASTENED TO SCREW COLUMN ANGLES NAILER MAY E FASTENED TO ASE FRAME.50 LIFT F CALE RACEWAY CARRIAGE RACKET LIFT ASE FRAME MIN 7.00 LIFT SECTION C-C SECTION D-D INTERIOR PANEL TO E FASTENED TO SCREW COLUMN ANGLES SECTION - VMW LIFT / INTERFACE C 2 OF 4

14 7.00 OVERALL WALL THK SHOWN - THK SUJECT TO INTERIOR AND EXT PANEL THK - TD Y DESIGNER 5.75 SCREW COLUMN.75 INTERIOR PANEL THK SHOWN -.50 MIN /.88 MAX TO COMPLY WITH ALLOWALE RUNNING CLEARANCE 5.50 SCREW COLUMN.75 EXT PANEL THK SHOWN - THK TD Y DESIGNER FRAME STRINGER SCREW COLUMN ANGLES SCREW COLUMN ANGLES FRAME STRINGER 5.50 SCREW COLUMN SCREW COLUMN ANGLES CALE RACEWAY FRAME STRINGER NAILER DRIVE SHAFT LIFT SCREW COLUMN ANGLES DETAIL E DETAIL G 1.25 SCREW COLUMN TO EDGE LIFT ASE FRAME DETAIL F VMW LIFT / INTERFACE C 3 OF 4

15 ELECTRICAL CALES STRUCTURAL FRAMING THE INTERIOR PANELS SHOULD E MADE REMOVALE TO PROVIDE ACCESS TO LEVEL SWITCHES AND ENALE SERVICE OR REPLACEMENT OF SCREW JACKS, GEAROXES, AND DRIVE SHAFTS. PROVIDE OPENINGS FOR MOUNTING CONTROL STATIONS AND ROUTING CALES CONTROL STATION LEVEL 1 CONTROL STATION ELECTRIC STRIKE LATCH CUT RELIEF IN FRAMING ADJACENT TO THE STRIKE LATCH FOR WIRE CLEARANCE DRIVE SHAFT C LIFT SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) CARRIAGE RACKET LIFT PERSPECTIVE VIEW OF WALL SEGMENT VMW LIFT / INTERFACE C 4 OF 4

16 R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED CAL 7/7/2006 UPDATED PER CURRENT DESIGN WAC 10/14/2011 LIFT PW PW = PORTAL WIDTH VARIES C ROLL-UP ARRIER MODULE ROUTER x.12 DEEP 2 - PLACES ROUTER x.12 DEEP C A PW WITNESS DETAIL A FLOOR OPENING AND SUGGESTED PREP TO ACCOMMODATE ROLL-UP ARRIER MODULE JUDGE PLAN VIEW NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED ROLL-UP ARRIER / INTERFACE. THE ROLL-UP ARRIER PORTAL WIDTH, VERTICAL GUIDES, AND EXTENDED ARRIER HEIGHT WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT, LIFT ENVELOPE DIMENSIONS, AND ROLL-UP ARRIER MODULE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. ROLL-UP ARRIER / INTERFACE OF 3

17 PW PW = PORTAL WIDTH VERTICAL GUIDE 6.00 MIN. D VARIES E F VARIES PW FASCIA SHIM AT INSTALLATION SECTION SECTION C-C.12 ROUTER DEPTH (TYP) INSTALL FLUSH WITH FASCIA DETAIL D OR PROVIDE VERTICAL NOTCHES FOR CLIP NUT/OLT CLEARANCE 1.53 FLNG DETAIL E 4.50 DETAIL F ROLL-UP ARRIER / INTERFACE OF 3

18 ARRIER VERTICAL GUIDES MAY E DRESSED OUT WITH TRIM (Y OTHERS) 2) REMOVE COVER TO INSTALL FASTENERS THAT MATE THE ROLL-UP ARRIER MODULE TO PAN. RE-ASSEMLE COVER. 3) SECURE VERTICAL GUIDES TO ADJACENT WALLS WITH FLAT HEAD WOOD SCREWS. SHIM GAP AS REQUIRED. FLOOR COVERING MATERIAL (Y OTHERS) ROLL-UP ARRIER MODULE 1) PAN INSTALLS FIRST. USE FLAT HEAD WOOD SCREW TO ATTACH PAN TO WITNESS FLOOR. ROLL-UP ARRIER PAN ROLL-UP ARRIER MODULE SUGGESTED INSTALLATION SEQUENCE LIFT ALL, INCLUDING STRUCTURAL FRAMING AND VENEERED PANEL FINISHES, ARE Y OTHERS. PERSPECTIVE VIEW FLOOR AND FRAMING TO E CONSTRUCTED TO SUPPORT AND ACCOMMODATE ROLL-UP ARRIER MODULE. ROLL-UP ARRIER / INTERFACE OF 3

19 C R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED CAL 8/28/2007 UPDATED PER CURRENT STEP DESIGN SA 9/20/2011 A A PROVIDE ACCESS HATCH TO ENALE SERVICE OR REPLACEMENT OF STEP MODULE C PERSPECTIVE VIEW PLAN VIEW NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED RETRACTALE STEP MODULE / INTERFACE. THE RETRACTALE STEP MODULE HEIGHT AND WIDTH WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT, LIFT ENVELOPE DIMENSIONS, AND STEP MODULE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AND FLOOR JOIST FRAMING USED TO FASTEN AND SUPPORT THE STEP MODULE ARE FURNISHED AND INSTALLED Y OTHERS. STEP MODULE / INTERFACE OF 4

20 RISER FASCIA SHOULD E MADE REMOVALE TO ENALE SERVICE OR REPLACEMENT OF STEP MODULE RISER FASCIA = SR -.50".50 NOMINAL CLEARANCE STEP MODULE HANGER PLATES RELIEF SLOTS IN INTERIOR PANEL TO ALLOW VERTICAL TRAVEL OF CARRIAGE RACKETS TOP OF LIFT FASCIA OPNG = SR +.63 SR = STEP RISE.13 RETRACTALE STEP SR VARIES 3 EQ RISERS MAX 7" EACH LIFT ASE CHANNEL DETAIL D FINISHED INTERIOR PANEL STEP MODULE ENCLOSURE STEP MODULE SUPPORT RACKET (IF APPLICALE) D SECTION A-A LIFT STEP MODULE / INTERFACE OF 4

21 MIN FASCIA OPNG = SW SW = STEP WIDTH.50 SCREW JACK COLUMN FINISHED INTERIOR PANEL LAG SCREW OR CARRIAGE OLT STEP MODULE HANGER PLATE TO FLOOR JOIST RISER FASCIA.50 NOMINAL CLEARANCE LIFT SECTION - STEP MODULE E CARRIAGE RACKET DETAIL E DETAIL F SW VARIES STEP MODULE SUPPORT RACKETS (IF APPLICALE) MAY E REMOVED AFTER THE HANGER PLATES ARE FASTENED TO FLOOR JOISTS SECTION C-C F STEP MODULE / INTERFACE OF 4

22 PREFERRED ATTACHMENT: LAG SCREW OR CARRIAGE OLT STEP MODULE HANGER PLATES TO FLOOR JOIST. FASTENERS ARE SUPPLIED AND INSTALLED Y OTHERS. FLOOR JOIST SPACING TO CORRESPOND WITH STEP MODULE HANGER PLATES DETAIL G G JOISTS AOVE STEP MODULE USED TO FRAME THE ACCESS HATCH OPENING SHOULD E REMOVALE TO ENALE SERVICE AND REPLACEMENT OF STEP MODULE PARTIAL PERSPECTIVE VIEW w/ CUT AWAY AND SU-FLOOR HIDDEN TO ILLUSTRATE FRAMING CONCEPT THE STEP MODULE IS SUSPENDED ELOW THE UPPER FLOOR Y FASTENING THE HANGER PLATES (INCLUDED WITH THE STEP MODULE) TO FLOOR JOISTS. ALTERNATIVELY, SUPPORT RACKETS (INCLUDED WITH MOST APPLICATIONS), WHICH ARE INTENDED TO FACILITATE INSTALLATION OF THE STEP MODULE EFORE THE IS COMPLETE, MAY E MADE PERMANENT Y ANCHORING TO THE FLOOR, UT MUST ALSO E SECURED LATERALLY FOR STAILITY; i.e., RACE TO ADJACENT STRUCTURE OR UTILIZE HANGER CONNECTION TO FLOOR JOISTS. FURNISHES THE ANCHOR OLTS TO EXERCISE THIS OPTION. STEP MODULE / INTERFACE OF 4

23 UPPER UPPER R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED CAL 9/5/ MIN MIN MIN JAM STYLE A OR UPPER DOOR MUST CLOSE FLUSH WITH INTERIOR EXTENDS INTO OPENING NEAR CLOSED DOOR TO COMPLY WITH GAP REQUIREMENTS JAM STYLE D LIFT UPPER DOOR MUST CLOSE FLUSH WITH INTERIOR JAM STYLE D LIFT UPPER DOOR MUST CLOSE FLUSH WITH INTERIOR MIN UPPER LIFT JAM STYLE A OR HINGE PLATE JAM STYLE D JAM STYLE A OR MIN MIN MIN LOWER DOOR CLOSES FLUSH WITH EXTERIOR - HINGES 180 LOWER DOOR CLOSES FLUSH WITH INTERIOR - HINGES 90 LOWER DOOR CLOSES FLUSH WITH EXTERIOR - HINGES 90 NOTES: EXTENDS INTO OPENING NEAR CLOSED DOOR TO COMPLY WITH GAP REQUIREMENTS LIFT LIFT THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED DOOR / INTERFACE ALTERNATIVES. FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT AND LIFT ENVELOPE DIMENSIONS. REFER TO DRAWING FOR THE RECOMMENDED JAM STYLES NOTED ON THIS DRAWING, AND FOR STRIKE LATCH / INTERFACE. THE LIFT REQUIRES 3/8" MINIMUM TO 3/4" MAXIMUM RUNNING CLEARANCE WITH ALL ADJACENT SURFACES; i.e., CLOSED DOORS AND FINISHED SURFACES MIN JAM STYLE C OR SIMILAR TO LOWER DOOR CLOSES FLUSH WITH EXTERIOR - HINGES MIN JAM STYLE D LOWER DOOR CLOSES FLUSH WITH INTERIOR - HINGES 90 ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. DOOR SET-UP ALTERNATIVES OF 1 A

24 SEE CONFIG DWG FOR DOOR THK, 2.00 PREFERRED SEE CONFIG DWG FOR DOOR THK, 2.00 PREFERRED R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED CAL 9/6/2007 ADDED STRIKE LATCH DIMENSIONS ON SHEET 2 SA 11/15/2011 C REVISED TO ADJUSTALE SPRING LATCH WAC 3/4/2013 DOOR JAM RECESSED JAM ELECTRIC STRIKE LATCH, SEE SHT 2 A DRILL FOR #12 WOOD SCREW HOLD JAM 3.00 AOVE UPPER JAM STYLE A JAM STYLE SEE CONFIG DWG FOR DOOR THK, 2.00 PREFERRED 1.25 SEE CONFIG DWG, 1.25 MIN DETAIL A NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED JAM STYLES AND STRIKE LATCH / INTERFACE. JAM STYLE C JAM STYLE D CLEARANCE AND/OR OPENINGS INSIDE THE WALLS MUST E PROVIDED FOR ROUTING OF ELECTRIC STRIKE LATCH WIRING. REFER TO DRAWING FOR ADDITIONAL RECOMMENDED WALL INTERFACE DESIGN PRINCIPLES. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. STRIKE LATCH / INTERFACE OF 2 C

25 STRIKE INSERT MAY E ADJUSTED FOR PROPER ALIGNMENT WITH SPRING LATCH ELECTRIC STRIKE LATCH MINIMUM ORE DEPTH C ADJUSTALE SPRING LATCH 1.96 MAX 1.68 MIN MIN SEE CONFIG DWG FOR DOOR THICKNESS, 2.00 PREFERRED C.38 RECOMMENDED LATCH ENGAGEMENT.13 RECOMMENDED DOOR GAP C WALL DOOR 1.23 PERSPECTIVE VIEW OF LOCKSET.63 2X, ELECTRIC STRIKE LATCH ADJUSTALE SPRING LATCH ADJUST JAM NUTS TO ACHIEVE PROPER LATCH ENGAGEMENT. TIGHTEN JAM NUTS TO LOCK IN POSITION..88 C ADJUST JAM NUTS TO ACHIEVE PROPER LATCH ENGAGEMENT. TIGHTEN JAM NUTS TO LOCK IN POSITION. 2X, DEPRESSED MAXIMUM 1.25 C ADJUSTALE SPRING LATCH DIMENSIONS ELEVATION VIEW OF LOCKSET INTERFACE 1.85 SECTION - STRIKE LATCH / INTERFACE OF 2 C

26 CENTER ETWEEN GEAROXES S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC UPPER RUNNING CLEARANCE UPPER 3.88 ASE FRAME 6.72 (TYP) MIN MIN COLUMN VMW LIFT Y OTHERS MIN 7.00 WALL ENCASING COLUMN COLUMN PERSPECTIVE VIEW 2.00 DOOR Y OTHERS LOWER MIN SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) MIN CLEAR DOOR OPENING (TALL COLUMN) (SHORT COLUMN) DRIVE MOTOR VMW SIMPLE TEMPLATE FOOTPRINT SHOWN 7.45 NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMW DETAILED LIFT TEMPLATE ASE FRAME 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW TEMPLATE, LAYOUT A OF 1

27 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC UPPER 3.88 ASE FRAME 6.72 (TYP) Y OTHERS WIDTH SEE TALE UPPER MIN CLEAR DOOR OPENING LENGTH SEE TALE MINUS 1" LENGTH SEE TALE COLUMN CENTER ETWEEN GEAROXES VMW LIFT.50 RUNNING CLEARANCE 7.00 WALL ENCASING COLUMN COLUMN PERSPECTIVE VIEW 2.00 DOOR Y OTHERS VMW 90 DEG EGRESS WIDTH LENGTH 42" 60" 43" 59" 44" 58" 45" 57" 46" 56" WIDTH SEE TALE MINUS 1" SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) LOWER TALE MIN CLEAR DOOR OPENING NOTES: 1. SPECIFIC TO THIS CONFIGURATION, THE MINIMUM WIDTH CORRESPONDS TO THE MINIMUM LENGTH - REFER TO TALE. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24". VMW SIMPLE TEMPLATE FOOTPRINT SHOWN 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION (TALL COLUMN) (SHORT COLUMN) VMW DETAILED LIFT TEMPLATE DRIVE MOTOR 7.45 ASE FRAME 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW TEMPLATE, LAYOUT OF 1

28 S 2.00 DOOR Y OTHERS UPPER CENTER ETWEEN GEAROXES REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC WALL ENCASING COLUMN UPPER MIN MIN.50 RUNNING CLEARANCE 8.78 COLUMN 3.88 ASE FRAME 5.47 COLUMN MIN MIN (TYP) VMW LIFT PERSPECTIVE VIEW Y OTHERS 7.00 SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) MIN CLEAR DOOR OPENING LOWER VMW SIMPLE TEMPLATE FOOTPRINT SHOWN NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMW DETAILED LIFT TEMPLATE (TALL COLUMN) (SHORT COLUMN) ASE FRAME DRIVE MOTOR FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW TEMPLATE, LAYOUT C OF 1

29 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE UPPER CENTER ETWEEN GEAROXES A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC UPPER MIN 7.00 WALL ENCASING COLUMN 8.78 COLUMN RUNNING CLEARANCE 3.88 ASE FRAME 5.47 COLUMN MIN VMW LIFT Y OTHERS MIN PERSPECTIVE VIEW MIN 6.72 (TYP) 2.00 DOOR Y OTHERS LOWER SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) MIN CLEAR DOOR OPENING VMW SIMPLE TEMPLATE FOOTPRINT SHOWN (TALL COLUMN) (SHORT COLUMN) DRIVE MOTOR 7.45 NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMW DETAILED LIFT TEMPLATE ASE FRAME 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW TEMPLATE, LAYOUT D OF 1

30 S UPPER CENTER ETWEEN GEAROXES REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC UPPER.50 RUNNING CLEARANCE 7.00 WALL ENCASING COLUMN ROLL-UP ARRIER INTERMEDIATE MIN MIN MIN MIN 8.78 COLUMN 6.72 (TYP) 3.88 ASE FRAME 5.47 COLUMN MIN MIN VMW LIFT Y OTHERS 2.00 DOOR Y OTHERS LOWER ROLL-UP ARRIER MODULE INSTALLS IN THE INTERMEDIATE. ASE FRAME AND DRIVE SHAFTS ROUTE AROUND THE ROLL-UP ARRIER MODULE WHEN THE INTERMEDIATE ELEV IS LESS THAN 10", UT THE MUST E AT LEAST 6" AOVE THE LOWER PERSPECTIVE VIEW SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) MIN CLEAR DOOR OPENING VMW SIMPLE TEMPLATE FOOTPRINT SHOWN (TALL COLUMN) (SHORT COLUMN) DRIVE MOTOR NOTES: 1. MINIMUM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM DIMENSIONS. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMW DETAILED LIFT TEMPLATE ASE FRAME FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW TEMPLATE, LAYOUT E OF 1

31 2.00 DOOR Y OTHERS UPPER CENTER ETWEEN GEAROXES S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC UPPER ROLL-UP ARRIER.50 RUNNING CLEARANCE 7.00 WALL ENCASING COLUMN INTERMEDIATE MIN MIN MIN MIN 8.78 COLUMN 3.88 ASE FRAME 5.47 COLUMN MIN MIN (TYP) VMW LIFT PERSPECTIVE VIEW Y OTHERS ROLL-UP ARRIER MODULE INSTALLS IN THE INTERMEDIATE. FOR THE MODULE TO CLEAR DRIVE SHAFT, THE INTERMEDIATE ELEV MUST E NO LESS THAN 10" AOVE THE LOWER SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) MIN CLEAR DOOR OPENING LOWER NOTES: 1. MINIMUM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM DIMENSIONS. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24". VMW SIMPLE TEMPLATE FOOTPRINT SHOWN 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMW DETAILED LIFT TEMPLATE (TALL COLUMN) (SHORT COLUMN) ASE FRAME DRIVE MOTOR FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW TEMPLATE, LAYOUT F OF 1

32 2.00 DOOR Y OTHERS UPPER CENTER ETWEEN GEAROXES S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC UPPER.50 RUNNING CLEARANCE ROLL-UP ARRIER 8.78 COLUMN 3.19 INTERMEDIATE 7.00 WALL ENCASING COLUMN MIN MIN 6.72 (TYP) MIN MIN MIN 3.88 ASE FRAME 5.47 COLUMN MIN VMW LIFT Y OTHERS PERSPECTIVE VIEW LOWER ROLL-UP ARRIER MODULE INSTALLS IN THE INTERMEDIATE. FOR THE MODULE TO CLEAR DRIVE SHAFT, THE INTERMEDIATE ELEV MUST E NO LESS THAN 10" AOVE THE LOWER. SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) NOTES: 1. MINIMUM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM DIMENSIONS. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24" MIN CLEAR DOOR OPENING 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW SIMPLE TEMPLATE FOOTPRINT SHOWN VMW DETAILED LIFT TEMPLATE (TALL COLUMN) (SHORT COLUMN) ASE FRAME DRIVE MOTOR 7.45 VMW TEMPLATE, LAYOUT G OF 1

33 2.00 DOOR Y OTHERS UPPER CENTER ETWEEN GEAROXES S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPDATED PER CURRENT DESIGNS WAC UPPER.50 RUNNING CLEARANCE 7.00 WALL ENCASING COLUMN ROLL-UP ARRIER INTERMEDIATE MIN MIN 8.78 COLUMN (TYP) MIN MIN MIN ASE FRAME 5.47 COLUMN MIN 7.00 VMW LIFT PERSPECTIVE VIEW Y OTHERS ROLL-UP ARRIER MODULE INSTALLS IN THE INTERMEDIATE. FOR THE MODULE TO CLEAR DRIVE SHAFT, THE INTERMEDIATE ELEV MUST E NO LESS THAN 10" AOVE THE LOWER SCREW COLUMN (TALL COLUMN SHOWN, 12" SHORTER COLUMN AVAILALE) MIN CLEAR DOOR OPENING LOWER VMW SIMPLE TEMPLATE FOOTPRINT SHOWN NOTES: 1. MINIMUM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM DIMENSIONS. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 74" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES. VMW DETAILED LIFT TEMPLATE (TALL COLUMN) (SHORT COLUMN) ASE FRAME VMW TEMPLATE, LAYOUT H DRIVE MOTOR OF 1

34 33.00 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/ UPPER.50 RUNNING CLEARANCE UPPER MIN MIN WALL THK UNAFFECTED Y VMX LIFT MIN MIN Y OTHERS VMX LIFT PERSPECTIVE VIEW MIN PIT WIDTH MIN PIT LENGTH 2.00 DOOR Y OTHERS LOWER LOWER DRIVE MOTOR NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 72" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMX. 2. MAXIMUM VERTICAL TRAVEL IS 24" MIN CLEAR DOOR OPENING VMX SIMPLE TEMPLATE FOOTPRINT SHOWN 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION GUIDELINES. VMX DETAILED LIFT TEMPLATE 6.00 MIN PIT DEPTH ASE FRAME VMX TEMPLATE, LAYOUT A OF A

35 33.00 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 WALL THK UNAFFECTED Y VMX LIFT UPPER Y OTHERS UPPER WIDTH SEE TALE LENGTH SEE TALE MIN CLEAR DOOR OPENING LENGTH SEE TALE MINUS 1".50 RUNNING CLEARANCE VMX LIFT PERSPECTIVE VIEW 2.00 DOOR Y OTHERS MIN CLEAR DOOR OPENING LOWER VMX 90 DEG EGRESS WIDTH LENGTH 42" 60" 43" 59" 44" 58" 45" 57" 46" 56" 47" 55" 48" 54" 49" 53" TALE.50 WIDTH SEE TALE MINUS 1" MIN PIT WIDTH.50 LOWER MIN PIT LENGTH DRIVE MOTOR NOTES: 1. SPECIFIC TO THIS CONFIGURATION, THE MINIMUM WIDTH CORRESPONDS TO THE MINIMUM LENGTH - REFER TO TALE. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 72" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMX. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMX SIMPLE TEMPLATE FOOTPRINT SHOWN VMX DETAILED LIFT TEMPLATE 6.00 MIN PIT DEPTH ASE FRAME 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION GUIDELINES OF VMX TEMPLATE, LAYOUT A

36 2.00 DOOR Y OTHERS S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPPER UPPER MIN WALL THK UNAFFECTED Y VMX LIFT MIN MIN.50 RUNNING CLEARANCE VMX LIFT Y OTHERS PERSPECTIVE VIEW MIN MIN PIT WIDTH MIN PIT LENGTH MIN CLEAR DOOR OPENING VMX SIMPLE TEMPLATE FOOTPRINT SHOWN LOWER LOWER DRIVE MOTOR NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 72" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMX. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMX DETAILED LIFT TEMPLATE 6.00 MIN PIT DEPTH ASE FRAME 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION GUIDELINES VMX TEMPLATE, LAYOUT C 1 OF 1 A

37 33.00 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 UPPER UPPER MIN WALL THK UNAFFECTED Y VMX LIFT MIN MIN.50 RUNNING CLEARANCE Y OTHERS VMX LIFT PERSPECTIVE VIEW 2.00 DOOR Y OTHERS LOWER MIN MIN PIT WIDTH MIN PIT LENGTH MIN CLEAR DOOR OPENING VMX SIMPLE TEMPLATE FOOTPRINT SHOWN LOWER DRIVE MOTOR NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 72" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMX. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMX DETAILED LIFT TEMPLATE 6.00 MIN PIT DEPTH ASE FRAME FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION GUIDELINES. VMX TEMPLATE, LAYOUT D OF 1 A

38 UPPER S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 ROLL-UP ARRIER UPPER.50 RUNNING CLEARANCE WALL THK UNAFFECTED Y VMX LIFT INTERMEDIATE MIN MIN MIN MIN MIN VMX LIFT Y OTHERS 2.00 DOOR Y OTHERS LOWER ROLL-UP ARRIER MODULE INSTALLS IN THE INTERMEDIATE. THE INTERMEDIATE ELEV MUST E NO LESS THAN 6" AOVE THE LOWER MIN PERSPECTIVE VIEW MIN PIT WIDTH MIN PIT LENGTH MIN CLEAR DOOR OPENING LOWER DRIVE MOTOR VMX SIMPLE TEMPLATE FOOTPRINT SHOWN NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 72" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMX. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMX DETAILED LIFT TEMPLATE 6.00 MIN PIT DEPTH ASE FRAME 4. FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION GUIDELINES VMX TEMPLATE, LAYOUT E 1 OF 1 A

39 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE 2.00 DOOR Y OTHERS UPPER A RELEASED CAL 3/4/09 ROLL-UP ARRIER UPPER.50 RUNNING CLEARANCE WALL THK UNAFFECTED Y VMX LIFT INTERMEDIATE MIN MIN MIN MIN MIN VMX LIFT Y OTHERS ROLL-UP ARRIER MODULE INSTALLS IN THE INTERMEDIATE. THE INTERMEDIATE ELEV MUST E NO LESS THAN 6" AOVE THE LOWER MIN PERSPECTIVE VIEW MIN CLEAR DOOR OPENING LOWER.50 MIN PIT WIDTH.50 LOWER MIN PIT LENGTH DRIVE MOTOR VMX SIMPLE TEMPLATE FOOTPRINT SHOWN NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 72" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMX. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMX DETAILED LIFT TEMPLATE 6.00 MIN PIT DEPTH ASE FRAME FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION GUIDELINES. VMX TEMPLATE, LAYOUT F OF 1 A

40 UPPER S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED CAL 3/4/09 ROLL-UP ARRIER UPPER.50 RUNNING CLEARANCE WALL THK UNAFFECTED Y VMX LIFT INTERMEDIATE MIN MIN MIN MIN MIN VMX LIFT Y OTHERS 2.00 DOOR Y OTHERS LOWER ROLL-UP ARRIER MODULE INSTALLS IN THE INTERMEDIATE. THE INTERMEDIATE ELEV MUST E NO LESS THAN 6" AOVE THE LOWER MIN MIN PIT WIDTH PERSPECTIVE VIEW MIN PIT LENGTH MIN CLEAR DOOR OPENING LOWER DRIVE MOTOR VMX SIMPLE TEMPLATE FOOTPRINT SHOWN NOTES: 1. MINIMUM DIMENSIONS ARE SHOWN. S MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; UT SHOULD NOT EXCEED 25 SQ. FT. E ADVISED, 72" IN THE LONG DIRECTION IS 'S ASOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMX. 2. MAXIMUM VERTICAL TRAVEL IS 24". 3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH 'S STANDARD TEMPLATES, CONTACT FOR EVALUATION. VMX DETAILED LIFT TEMPLATE 6.00 MIN PIT DEPTH ASE FRAME FOR ADDITIONAL INFORMATION, INCLUDING INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION GUIDELINES. VMX TEMPLATE, LAYOUT G OF 1 A

41 .25 RUNNING CLEARANCE S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED ADDED DROP-IN ANCHOR NOTES SA C DELETED FIXED-DEPTH DRILL IT ( ) SA INSTALL OPERALE STEP PRIOR TO. INSTALL WITH DROP-IN ANCHORS, OLTS & WASHERS ( P/N'S , , & ). (SUPPLIED Y ) DRILL 1/2" DIAMETER HOLE 1 5/8" DEEP. INSERT DROP-IN ANCHOR AND USE ANCHOR SETTING TOOL ( P/N ) TO SET DROP-IN ANCHORS PER MANUFACTURER INSTRUCTIONS. C NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED OPERALE STEP / INTERFACE. THE OPERALE STEP HEIGHT AND WIDTH WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT, LIFT ENVELOPE DIMENSIONS, AND OPERALE STEP MODULE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. PLAN VIEW WITH OPERALE STEP IN "STEP" POSITION STEP HEIGHT OVERALL STEP WIDTH OPERALE STEP IN "STEP" POSITION OPERALE STEP IN "RAMP" POSITION CUT FOR 1/4" TO 1/2" CLEARANCE ALL-AROUND OPERALE STEP R R OPERALE STEP / INTERFACE C 1 OF 1

42 ROLL-UP ARRIER (STOWED) ROLL-UP ARRIER (DEPLOYED) ARRIER DEPLOYS DURING LIFT OPERATION LIFT AT PARK LEVEL; ARRIER IS STOWED ACCESSOR LIFT WITH ROLL-UP ARRIER R R ROLL-UP ARRIER OVERVIEW OF 1 A

43 RETRACTALE STEP (DEPLOYED) RETRACTALE STEP (STOWED) RETRACTALE STEP IS DEPLOYED WHILE LIFT IS IN PARK POSITION RETRACTALE STEP IS STOWED DURING LIFT OPERATION ACCESSOR LIFT WITH RETRACTALE STEP R R RETRACTALE STEP OVERVIEW OF 1 A

44 OPERALE STEP (STEP POSITION) OPERALE STEP (RAMP POSITION) OPERALE STEP IS IN "STEP" POSITION WHILE LIFT IS PARKED OPERALE STEP IS IN "STEP" POSITION DURING LIFT OPERATION OPERALE STEP IS IN "RAMP" POSITION AT LOWER LEVEL FOR PASSENGER INGRESS/EGRESS ACCESSOR LIFT WITH OPERALE STEP R R OPERALE STEP OVERVIEW OF 1 A

45 ELECTRICAL CONTROL PANEL W/DISCONNECT (ELOW) 2.00 DOOR DRIVE MOTOR (ELOW) INTERIOR 2.00 DOOR TO E COVERED WITH THE SAME FLOORING MATERIAL AS ADJACENT AREAS. FLOOR COVERING TO E SUPPLIED AND INSTALLED Y OTHERS DOOR FRAME CLEAR DOOR OPENING A LENGTH WIDTH.50 RUNNING CLEARANCE A LIFT PARKS AT WITNESS LEVEL +8.5" ELEV CLEAR DOOR OPENING DOOR FRAME INTERIOR THIS DRAWING ILLUSTRATES A LIFT AND OPERATING MECHANISM WITHIN THE PARAMETERS OF WALLS. THE LIFT REQUIRES 3/8" MINIMUM TO 3/4" MAXIMUM RUNNING CLEARANCE WITH ADJACENT FINISHED SURFACES. THE MILL- WORK SHOWN IS FOR ILLUSTRATIVE REFERENCE ONLY. DIMENSIONAL EXTENTS OF THE IS THE RESPONSIILITY OF OTHERS. WALLS ARE SHOWN IN SHADED / TRANSPARENT MODE ON SHEET 1 OF 5 TO VIEW ENCASED LIFT ASSEMLY POWER NOTE: UILDING POWER TO E SUPPLIED AND ROUTED TO ELECTRICAL CONTROL PANEL Y OTHERS. FURNISH 115 VAC, 3 WIRE, 15 AMP, SINGLE PHASE SOURCE POWER ATTERY ACK-UP (ELOW) MANUAL OPERATING DEVICE (ELOW) JUDGE LEVEL " ELEV C 4.00 D C ROLL-UP ARRIER MODULE 4.00 COURTROOM LEVEL " ELEV ADVISORY NOTES: 1. THIS DRAWING IS SUJECT TO CHANGE PENDING APPLICALE STATE AND LOCAL CODES, AND CUSTOMER APPROVAL. 2. CUSTOMER MUST PROVIDE APPLICALE STATE AND LOCAL CODES TO PRIOR TO DESIGN. 3. PRIOR TO INSTALLATION, THE CUSTOMER MAY E REQUIRED TO OTAIN A VAIRANCE FROM THE PRESIDING AUTHORITY FOR NON-COMPLIANT FEATURES. 4. DRAWING MUST E SIGNED Y CUSTOMER AND RETURNED TO PRIOR TO PRODUCTION RELEASE. CUSTOMER APPROVAL SIGNIFIES THAT ALL DIMENSIONS ARE CORRECT TO THEIR SPECIFICATIONS. 5. SEE SHEET 5 OF 5 FOR LIFT SPECIFICATIONS. WITNESS LEVEL " ELEV.75 MIN. PANEL THK NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS PLAN VIEW SHOWN AT LOWER LEVEL (1) SCREW JACK COLUMN LIFT.50 RUNNING CLEARANCE DETAIL D REFERENCE ONLY LIFT CONFIGURATION, 7"-14" RISE OF 5 A

46 NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. LIFT SCREW JACK COLUMNS TO E ENCASED IN. IS SUPPLIED AND INSTALLED Y OTHERS. SIDES FACING THE TO E COMPLETED AFTER THE LIFT IS INSTALLED WALL INTERIOR 2.00 DOOR ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS INTERIOR 4.00 PANEL TO E REMOVALE TO ALLOW ACCESS TO SCREW COLUMNS EHIND CONTROL STATION DOOR JAM DOOR FRAME MAX F RAISED FLOOR 8.50 PROVIDE RELIEF CUTS IN VENEER PANELS TO ALLOW VERTICAL MOVEMENT OF THE LIFT SUPPORT RACKETS. SECTION A-A 1.60 FLOOR MUST E LEVEL (Y OTHERS) PRIOR TO LIFT INSTALLATION 6.22 DOOR MUST CLOSE FLUSH WITH FASCIA ELOW UPPER SILL SECTION SUPPORT RACKET E PROVIDE RELIEF CUTS IN VENEER FOR HINGED RISER CONTROL PIN AND GUIDE LOCK SUPPORT RACKET LIFT.75 MIN PANEL THK..50 RUNNING CLEARANCE REFERENCE ONLY DETAIL F SCREW COLUMN THK DETAIL E LIFT CONFIGURATION, 7"-14" RISE 2 OF A

47 INTERIOR PORTAL OPENING ROLL-UP ARRIER: REFER TO DRAWING FOR RECOMMENDED INTERFACE RAISED FLOOR SECTION C-C REFERENCE ONLY NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. R R LIFT CONFIGURATION, 7"-14" RISE A 3 OF 5

48 THREE CONTROL STATIONS SUPPLIED Y. LOCATION AND WALL CUT IN Y OTHERS. ELECTRICAL WIRING FURNISHED Y. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. E ADVISED - ALL INTERIOR SURFACES MUST E SMOOTH, i.e. NO PROTRUSIONS AND NO OPENINGS, OTHER THAN THOSE NECESSARY FOR THE OPERATION OF THE LIFT. INTERIOR PANELS SHOULD E MADE REMOVALE TO PROVIDE ACCESS TO LEVEL SWITCHES AND ENALE SERVICE OR REPLACEMENT OF SCREW JACKS, GEAROXES, AND DRIVE SHAFTS. MANUALLY OPERATED, SELF-CLOSING DOORS i.e. w/spring HINGES. DOORS, SELF-CLOSING SPRING HINGES,AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS.ELECTRIC STRIKE LATCHES, SPRING-LOADED LATCH OLTS, AND ELECTRICAL INTERLOCK WIRING FURNISHED Y AND INSTALLED Y OTHERS. SHOWN AT LOWER LEVEL (1) READY FOR PASSENGER INGRESS OR EGRESS DOORS ARE CLOSED AND LOCKED WHEN RAISES AND LOWERS SHOWN PARKED AT WITNESS LEVEL (2) FOR USE Y ALE-ODIED PERSONS SHOWN AT UPPER LEVEL (3) READY FOR PASSENGER INGRESS OR EGRESS PROVIDE AN ACCESS HATCH TO ENALE SERVICE ON MOTOR AND ELECTRONICS LOCATED ELOW UPPER. HATCH SHOULD E NO LESS THAN 30" x 36". A REMOVALE JOIST WITHIN THE FRAMED HATCH OPENING SHOULD E POSITIONED TO REINFORCE THE HATCH COVER. REVERSE ISOMETRIC VIEW ACK WALL AND DOORS NOT SHOWN FOR CLARITY F NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. REFERENCE ONLY ELECTRIC STRICK LATCH CUT INTO DOOR JAM DETAIL F TYPICAL 2 PLACES LIFT CONFIGURATION, 7"-14" RISE 4 OF A

49 TYP ASE FRAME NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. MANUAL OPERATING DEVICE DRIVE MOTOR SHEET METAL FLANGES ON SCREW JACK COLUMNS FACILITATE THE ATTACHMENT OF FRAMING AND VENEERED PANELS ( Y OTHERS). LEVEL 3 - TOP OF LIFT PLATE AT " ASE FRAME LEVEL 2 - TOP OF LIFT PLATE AT +8.50" HINGED RISER ASE FRAME DRIVE SHAFTS CONNECTING GEAROXES, AND CALE RACEWAYS NOT SHOWN AT THIS TIME. LEVEL 1 - TOP OF LIFT PLATE AT +1.60" LIFT ASE FRAME ANCHORS TO FLOOR. ANCHOR OLTS FURNISHED Y. ISOMETRIC VIEW ASE FRAME REFERENCE ONLY 7.65 LIFT ENVELOPE DIMENSIONS HINGED RISER WIDTH LIFT CONFIGURATION, 7"-14" RISE OF 5 A

50 2.00 DOOR INTERIOR 2.00 DOOR ELECTRICAL CONTROL PANEL w/disconnect (ELOW) TO E COVERED WITH THE SAME FLOORING MATERIAL AS ADJACENT AREAS. FLOOR COVERING TO E SUPPLIED AND INSTALLED Y OTHERS. THIS DRAWING ILLUSTRATES A LIFT AND OPERATING MECHANISM WITHIN THE PARAMETERS OF WALLS. THE LIFT REQUIRES 3/8" MINIMUM TO 3/4" MAXIMUM RUNNING CLEARANCE WITH ADJACENT FINISHED SURFACES. THE MILL- WORK SHOWN IS FOR ILLUSTRATIVE REFERENCE ONLY. DIMENSIONAL EXTENTS OF THE IS THE RESPONSIILITY OF OTHERS LENGTH.50 RUNNING CLEARANCE WALLS ARE SHOWN IN SHADED / TRANSPARENT MODE ON SHEET 1 OF 5 TO VIEW ENCASED LIFT ASSEMLY A WIDTH 4.00 A 2X, CLEAR DOOR OPENING 2X, DOOR FRAME INTERIOR POWER NOTE: UILDING POWER TO E SUPPLIED AND ROUTED TO ELECTRICAL CONTROL PANEL Y OTHERS. FURNISH 115 VAC, 3 WIRE, 15 AMP, SINGLE PHASE SOURCE POWER C ATTERY ACK-UP (ELOW) C 4.00 COURTROOM FLOOR LEVEL (1) +0" ELEV ADVISORY NOTES: 1. THIS DRAWING IS SUJECT TO CHANGE PENDING APPLICALE STATE AND LOCAL CODES, AND CYSTOMER APPROVAL. 2. CUSTOMER MUST PROVIDE APPLICALE STATE AND LOCAL CODES TO PRIOR TO DESIGN. 3. PRIOR TO INSTALLATION, THE CUSTOMER MAY E REQUIRED TO OTAIN A VAIRANCE FROM THE PRESIDING AUTHORITY FOR NON-COMPLIANT FEATURES. 4. DRAWING MUST E SIGNED Y CUSTOMER AND RETURNED TO PRIOR TO PRODUCTION RELEASE. CUSTOMER APPROVAL SIGNIFIES THAT ALL DIMENSIONS ARE CORRECT TO THEIR SPECIFICATIONS. 5. SEE SHEET 5 OF 5 FOR LIFT SPECIFICATIONS. WITNESS LEVEL (2) +12" ELEV NOTES: JUDGE LEVEL (3) +18" ELEV THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS INTERIOR ROLL-UP ARRIER MOULE PLAN VIEW SHOWN AT JUDGE LEVEL (3) REFERENCE ONLY LIFT CONFIGURATION, 6" - 18" RISE OF 5 A

51 2.00 DOOR INTERIOR DOOR JAM CONTROL STATION 2.00 DOOR DOOR MUST CLOSE FLUSH WITH FASCIA ELOW UPPER SILL INTERIOR DOOR FRAME DOOR JAM JUDGE LEVEL (3) (42.00) MAX WITNESS LEVEL (2) PARK LEVEL COURTROOM FLOOR LEVEL (1) PIT DEPTH MIN RECESSED SLA LENGTH RECESSED SLA MUST E LEVEL (Y OTHERS) PRIOR TO LIFT INSTALLATION MIN FASCIA CUTOUT MIN FASCIA CUTOUT MIN RECESSED SLA WIDTH 6.00 RECESSED FLOOR SECTION A-A SECTION - REFERENCE ONLY NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. LIFT CONFIGURATION, 6" - 18" RISE A 2 OF 5

52 ROLL-UP ARRIER: REFER TO DRAWING FOR RECOMMENDED INTERFACE INTERIOR PORTAL OPENING NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. SECTION C-C REFERENCE ONLY LIFT CONFIGURATION, 6" - 18" RISE A 3 OF 5

53 THREE CONTROL STATIONS SUPPLIED Y. LOCATION AND WALL CUT IN Y OTHERS. ELECTRICAL WIRING FURNISHED Y. MANUALLY OPERATED, SELF-CLOSING DOORS, i.e. w/spring HINGES. DOORS, SELF-CLOSING SPRING HINGES, AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. ELECTRIC STRIKE LATCHES, SPRING-LOADED LATCH OLTS, AND ELECTRICAL INTERLOCK WIRING FURN- ISHED Y AND INSTALLED Y OTHERS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. E ADVISED - ALL INTERIOR SURFACES MUST E SMOOTH, i.e. NO PROTRUSIONS AND NO OPENINGS, OTHER THAN THOSE NECESSARY FOR THE OPERATION OF THE LIFT. PARK LEVEL +6" ELEV WITNESS LEVEL 2 +12" ELEV SHOWN AT LOWER LEVEL (1) READY FOR PASSENGER INGRESS OR EGRESS NOTES: DOORS ARE CLOSED AND LOCKED WHEN RAISES AND LOWERS SHOWN AT PARK LEVEL FOR USE Y ALE-ODIED PERSONS ROLL-UP ARRIER IS STOWED ROLL-UP ARRIER MODULE SHOWN AT JUDGE LEVEL (3) READY FOR PASSENGER INGRESS OR EGRESS THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. D REVERSE ISOMETRIC VIEW ACK WALL AND DOORS NOT SHOWN FOR CLARITY PROVIDE AN ACCESS HATCH TO ENALE SERVICE ON MOTOR AND ELECTRONICS LOCATED ELOW UPPER. HATCH SHOULD E NO LESS THAN 30" x 36". A REMOVALE JOIST WITHIN THE FRAMED HATCH OPENING SHOULD E POSITIONED TO REINFORCE THE HATCH COVER. REFERENCE ONLY DETAIL D 2 PLACES ELECTRIC STRIKE LATCH CUT INTO DOOR JAM LIFT CONFIGURATION, 6" - 18" RISE A 4 OF 5

54 JUDGE LEVEL (3) - TOP OF LIFT PLATE AT +18" AOVE COURTROOM FLOOR DRIVE MOTOR LIFT ASE FRAME ANCHORS TO PIT FLOOR. ANCHOR OLTS FURNISHED Y. PERSPECTIVE VIEW NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED VMW LIFT / INTERFACE. COURTROOM FLOOR LEVEL (1) +0" ELEV THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS REFERENCE ONLY LIFT ENVELOPE DIMENSIONS LIFT CONFIGURATION, 6" - 18" RISE A 5 OF 5

55 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED WAC SINGLE GANG OUTLET OX (SUPPLIED Y OTHERS) INSTALL PER MANUFACTURERE'S INSTRUCTIONS ELECTROMAGNETIC DOOR HOLDER DETAIL A NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED ELECTROMAGNETIC DOOR HOLDER / INTERFACE. SEE SHEET 2 AND MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION. THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION, REFER TO ITS CORRESPONDING LIFT CONFIGURATION. CLEARANCE AND/OR OPENINGS INSIDE THE WALLS MUST E PROVIDED FOR ROUTING OF ELECTROMAGNETIC DOOR HOLDER WIRING. A CATCH PLATE COVER PLATE ELECTROMAGNETIC DOOR HOLDER LOCATION OF DOOR HOLDER IS FOR ILLUSTRATION PURPOSES ONLY. REFER TO DRAWING FOR ADDITIONAL RECOMMENDED WALL INTERFACE DESIGN PRINCIPLES. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. R R DOOR HOLDER / INTERFACE OF 2 A

56 1.80 ELECTROMAGNETIC DOOR HOLDER CATCH PLATE COVER PLATE PERSPECTIVE VIEW OF ELECTRIOMAGNETIC DOOR HOLDER R R DOOR HOLDER / INTERFACE OF 2 A

57 S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED SA DOOR OPERATOR DOOR CLOSED DOOR OPERATOR DOOR OPEN ACCESSOR LIFT WITH DOOR OPERATOR - DOOR CLOSED DOOR OPERATOR ACCESSOR LIFT WITH DOOR OPERATOR - DOOR OPEN R R DOOR OPERATOR OVERVIEW OF 1 A

58 DOOR OPERATOR NOTE: UNIT CAN E INSTALLED 90 DEGREES TO WHAT IS SHOWN IN DETAIL UT, INSIDE OF WALL DIMENSIONS MUST NOT E SMALLER THAN 3.50" x 5.50". R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED WAC 8/18/ NOMINAL RUNNING CLEARANCE (.38 MIN /.75 MAX) C STRUCTURAL FRAMING THRESHOLD RAMP LIFT WALL SEGMENT PLAN VIEW CUT OPENING IN INTERIOR PANEL TO ALLOW THE DOOR OPERATOR LINKAGE TO CONNECT TO THE DOOR DOOR OPERATOR A A C ENLARGED VIEW OF WALL SEGMENT WITH INTERIOR PANEL REMOVED (SEE SHEETS 2 FOR SECTIONS AND DETAILS) WALL SEGMENT ELEVATION VIEW NOTES: THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED DOOR OPERATOR / INTERFACE. CLEARANCE AND/OR OPENINGS INSIDE THE WALLS MUST E PROVIDED FOR ROUTING OF ELECTRIC DOOR OPERATOR WIRING. REFER TO DRAWING FOR ADDITIONAL RECOMMENDED WALL INTERFACE DESIGN PRINCIPLES. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. DOOR OPERATOR / INTERFACE OF 3 A

59 3.50 MIN. DOOR OPERATOR NOTE: UNIT CAN E INSTALLED 90 DEGREES TO WHAT IS SHOWN IN DETAIL UT, INSIDE OF WALL DIMENSIONS MUST NOT E SMALLER THAN 3.50" x 5.50". FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) 5.50 MIN. ADJUSTALE LINKAGE DOOR OPERATOR MIN MAX ENGAGEMENT WITH FRAMING SECTION A-A PUSH/PULL PLATE PLATE IS.135" THICK (5X, #10 FLAT HEAD SCREWS) X,.438 HOLES FOR 3/8" OLTS / ANCHORS LIFT DOOR OPERATOR SECTION C-C LIFT SECTION - DOOR OPERATOR / INTERFACE OF 3 A

60 STRUCTURAL FRAMING THE INTERIOR PANELS SHOULD E MADE REMOVALE TO PROVIDE ACCESS TO LEVEL SWITCHES AND ENALE SERVICE OR REPLACEMENT OF SCREW JACKS, GEAROXES, AND DRIVE SHAFTS. DOOR (OPEN) FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) DOOR OPERATOR NOTE: UNIT CAN E INSTALLED 90 DEGREES TO WHAT IS SHOWN IN DETAIL UT, INSIDE OF WALL DIMENSIONS MUST NOT E SMALLER THAN 3.50" x 5.50". LIFT PERSPECTIVE VIEW OF WALL SEGMENT DOOR OPERATOR / INTERFACE OF 3 A

61 LIFT S REV ECO DESCRIPTION CREATED DATE APPROVED DATE A RELEASED SA PW C PW = PORTAL WIDTH VARIES X, R ROLL-UP ARRIER MODULE 1.38 ROUTER x.74/.75 DEEP 2 - PLACES 1.56 ROUTER x.74/.75 DEEP C A PW UPPER PLAN VIEW DETAIL A FLOOR OPENING AND SUGGESTED PREP TO ACCOMMODATE ROLL-UP ARRIER MODULE NOTES: UPPER THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED ROLL-UP ARRIER / INTERFACE. THE ROLL-UP ARRIER PORTAL WIDTH, VERTICAL GUIDES, AND EXTENDED ARRIER HEIGHT WILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT, LIFT ENVELOPE DIMENSIONS, AND ROLL-UP ARRIER MODULE DIMENSIONS. ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED Y OTHERS. ALL, INCLUDING STRUCTURAL FRAMING AND VENEERED PANEL FINISHES, ARE Y OTHERS. LIFT REVERSE ISO VIEW FOR REFERENCE ROLL-UP ARRIER MODULE R R UPPER ROLL-UP ARRIER / INTERFACE OF 3 A

62 PW PW = PORTAL WIDTH 1.91 GREATER THAN 24 UP TO 42 MAX. VERTICAL GUIDE 42 MIN. D E F VARIES VARIES PW FASCIA SECTION - SECTION C-C SHIM AT INSTALLATION /.75 ROUTER DEPTH (TYP) 1.56 DETAIL D OR PROVIDE VERTICAL NOTCHES FOR CLIP NUT/OLT CLEARANCE 1.75 FLNG DETAIL E DETAIL F INSTALL FLUSH WITH FASCIA R R UPPER ROLL-UP ARRIER / INTERFACE OF 3 A

63 ARRIER VERTICAL GUIDES MAY E DRESSED OUT WITH TRIM (Y OTHERS) 3) SECURE VERTICAL GUIDES TO ADJACENT WALLS WITH FLAT HEAD WOOD SCREWS. SHIM GAP AS REQUIRED. FLOOR COVERING MATERIAL (Y OTHERS) 2) REMOVE COVER TO INSTALL FASTENERS THAT MATE THE ROLL-UP ARRIER MODULE TO PAN. RE-ASSEMLE COVER. ROLL-UP ARRIER MODULE ROLL-UP ARRIER PAN UPPER 1) PAN INSTALLS FIRST. USE FLAT HEAD WOOD SCREW TO ATTACH PAN TO WITNESS FLOOR. LIFT ROLL-UP ARRIER MODULE SUGGESTED INSTALLATION SEQUENCE ALL, INCLUDING STRUCTURAL FRAMING AND VENEERED PANEL FINISHES, ARE Y OTHERS. PERSPECTIVE VIEW FLOOR AND FRAMING TO E CONSTRUCTED TO SUPPORT AND ACCOMMODATE ROLL-UP ARRIER MODULE. R R UPPER ROLL-UP ARRIER / INTERFACE OF 3 A

64 1.63 (IN PANEL).61 DOOR OPERATOR INSIDE OF WALL DIMENSIONS MUST NOT E SMALLER THAN 3.50" x 5.50". R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED M 12/23/ (IN PANEL AND JAM) DOOR JAM.50 NOMINAL RUNNING CLEARANCE (.38 MIN /.75 MAX) DOOR JAM C STRUCTURAL FRAMING INTERIOR PANEL THRESHOLD RAMP LIFT DETAIL D DOOR AND PUSH/PULL PLATE NOT SHOWN FOR CLARITY DOOR JAM WALL SEGMENT PLAN VIEW STRUCTURAL FRAMING CUT OPENING IN INTERIOR PANEL & DOOR JAM TO ALLOW THE DOOR OPERATOR LINKAGE TO CONNECT TO THE DOOR. DOOR JAM CAN ALSO E MADE IN 2 PIECES IF OPENING REQUIRES. A A DOOR (OPEN) DOOR OPERATOR DOOR JAM D C ENLARGED VIEW OF WALL SEGMENT WITH INTERIOR PANEL & DOOR REMOVED (SEE SHEETS 2 FOR SECTIONS AND DETAILS) WALL SEGMENT ELEVATION VIEW NOTES: 1.) THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED DOOR OPERATOR / INTERFACE. 2.) CLEARANCE AND/OR OPENINGS INSIDE THE WALLS MUST E PROVIDED FOR ROUTING OF ELECTRIC DOOR OPERATOR WIRING. 3.) REFER TO DRAWING FOR ADDITIONAL RECOMMENDED WALL INTERFACE DESIGN PRINCIPLES. 4.) ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. DOOR OPERATOR / INTERFACE OF 3 A

65 .75 DOOR OPERATOR 5.50 MIN ADJUSTALE LINKAGE FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) DOOR OPERATOR 4.00 PUSH/PULL PLATE PLATE IS.135" THICK (5X, #10 FLAT HEAD SCREWS) 5.50 MIN MAX ENGAGEMENT WITH FRAMING SECTION A-A X,.438 HOLES FOR 3/8" OLTS / ANCHORS LIFT DOOR OPERATOR SECTION C-C LIFT.50 SECTION - DOOR OPERATOR / INTERFACE OF 3 A

66 THE INTERIOR PANELS SHOULD E MADE REMOVALE TO PROVIDE ACCESS TO LEVEL SWITCHES AND ENALE SERVICE OR REPLACEMENT OF SCREW JACKS, GEAROXES, AND DRIVE SHAFTS. DOOR (OPEN) FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) STRUCTURAL FRAMING DOOR (CLOSED) DOOR OPERATOR LIFT PERSPECTIVE VIEWS OF WALL SEGMENT DOOR OPERATOR / INTERFACE OF 3 A

67 THRESHOLD RAMP DOOR OPERATOR INSIDE OF WALL DIMENSIONS MUST NOT E SMALLER THAN 3.50" x 5.50". R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED M 12/23/ STRUCTURAL FRAMING.50 NOMINAL RUNNING CLEARANCE (.38 MIN /.75 MAX).50 LIFT STRUCTURAL FRAMING C WALL SEGMENT PLAN VIEW A A CUT OPENING IN END PANEL TO ALLOW THE DOOR OPERATOR LINKAGE TO CONNECT TO THE DOOR (CUTOUT IN END PANEL) DOOR OPERATOR 1.63 (CUTOUT IN END PANEL) DOOR (OPEN POSITION) ENLARGED VIEW OF WALL SEGMENT WITH INTERIOR PANEL REMOVED (SEE SHEETS 2 FOR SECTIONS AND DETAILS) C (DOOR AND PUSH/PULL PLATE NOT SHOWN FOR CLARITY) WALL SEGMENT ELEVATION VIEW NOTES: 1.) THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED DOOR OPERATOR / INTERFACE. 2.) CLEARANCE AND/OR OPENINGS INSIDE THE WALLS MUST E PROVIDED FOR ROUTING OF ELECTRIC DOOR OPERATOR WIRING. 3.) REFER TO DRAWING FOR ADDITIONAL RECOMMENDED WALL INTERFACE DESIGN PRINCIPLES. 4.) ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. DOOR OPERATOR / INTERFACE OF 3 A

68 5.50 MIN DOOR OPERATOR 1.75 FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) 2.00 DOOR OPERATOR MIN SECTION A-A PUSH/PULL PLATE PLATE IS.135" THICK (5X, #10 FLAT HEAD SCREWS) 1.62 MAX ENGAGEMENT WITH FRAMING ADJUSTALE LINKAGE DETAIL D 3X,.438 HOLES FOR 3/8" OLTS / ANCHORS DOOR OPERATOR SECTION C-C SECTION - LIFT DOOR OPERATOR / INTERFACE OF 3 A

69 FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) THE INTERIOR PANELS SHOULD E MADE REMOVALE TO PROVIDE ACCESS TO LEVEL SWITCHES AND ENALE SERVICE OR REPLACEMENT OF SCREW JACKS, GEAROXES, AND DRIVE SHAFTS. DOOR (OPEN) DOOR OPERATOR STRUCTURAL FRAMING LIFT PERSPECTIVE VIEWS OF WALL SEGMENT DOOR OPERATOR / INTERFACE OF 3 A

70 THRESHOLD RAMP DOOR OPERATOR INSIDE OF WALL DIMENSIONS MUST NOT E SMALLER THAN 3.50" x 5.50". R E V I S I O N S LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE A RELEASED M 12/23/ (CUTOUT IN PANEL & DOOR JAM).50 NOMINAL RUNNING CLEARANCE (.38 MIN /.75 MAX) DOOR JAM STRUCTURAL FRAMING DOOR JAM DETAIL E LIFT WALL SEGMENT PLAN VIEW STRUCTURAL FRAMING C DOOR JAM DOOR (OPEN POSITION) DOOR JAM A A CUT OPENING IN END PANEL & DOOR JAM TO ALLOW THE DOOR OPERATOR LINKAGE TO CONNECT TO THE DOOR. DOOR JAM CAN E MADE IN 2 PIECES IF OPENING REQUIRES. E DOOR OPERATOR 1.63 (CUTOUT IN END PANEL) (CUTOUT IN END PANEL & DOOR JAM) ENLARGED VIEW OF WALL SEGMENT WITH INTERIOR PANEL REMOVED (SEE SHEETS 2 FOR SECTIONS AND DETAILS) C (DOOR AND PUSH/PULL PLATE NOT SHOWN FOR CLARITY) WALL SEGMENT ELEVATION VIEW NOTES: 1.) THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE 'S RECOMMENDED DOOR OPERATOR / INTERFACE. 2.) CLEARANCE AND/OR OPENINGS INSIDE THE WALLS MUST E PROVIDED FOR ROUTING OF ELECTRIC DOOR OPERATOR WIRING. 3.) REFER TO DRAWING FOR ADDITIONAL RECOMMENDED WALL INTERFACE DESIGN PRINCIPLES. 4.) ALL FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED AND INSTALLED Y OTHERS. DOOR OPERATOR / INTERFACE OF 3 A

71 MIN DOOR OPERATOR 1.75 FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) DOOR OPERATOR MIN PUSH/PULL PLATE PLATE IS.135" THICK (5X, #10 FLAT HEAD SCREWS) 1.62 MAX ENGAGEMENT WITH FRAMING SECTION A-A ADJUSTALE LINKAGE DETAIL D 3X,.438 HOLES FOR 3/8" OLTS / ANCHORS DOOR OPERATOR (VARIES) 3.75 (VARIES) 3.75 SECTION C-C 3.00 SECTION - LIFT DOOR OPERATOR / INTERFACE OF 3 A

72 FRAMING (LOCK AS REQUIRED) IS TO TIE INTO DOOR OPERATOR POST (6X, #10 FLAT HEAD SCREWS) THE INTERIOR PANELS SHOULD E MADE REMOVALE TO PROVIDE ACCESS TO LEVEL SWITCHES AND ENALE SERVICE OR REPLACEMENT OF SCREW JACKS, GEAROXES, AND DRIVE SHAFTS. DOOR (OPEN) STRUCTURAL FRAMING LIFT DOOR OPERATOR PERSPECTIVE VIEWS OF WALL SEGMENT DOOR OPERATOR / INTERFACE OF 3 A

LIFT APPLICATION GUIDELINES ACCESSOR III PERFORMANCE LIFT (MODEL APL-16)

LIFT APPLICATION GUIDELINES ACCESSOR III PERFORMANCE LIFT (MODEL APL-16) LIFT APPLICATION GUIDELINES ACCESSOR III PERFORMANCE LIFT (MODEL APL-16) Division of Hogan Mfg., Inc. APL-16 LIFT APPLICATION GUIDELINES TABLE OF CONTENTS GENERAL INFORMATION...3 PURPOSE...3 PRODUCT OVERVIEW...3

More information

VERTICAL PLATFORM LIFT

VERTICAL PLATFORM LIFT VERTICAL PLATFORM LIFT HERCULES DC INSTALLATION GUIDE Please read this installation guide carefully to ensure correct installation of your HERCULES Vertical Platform Lift. HERCULES RESIDENTIAL & COMMERCIAL

More information

TOOLS REQUIRED Metal Wood Wood and Metal Screws. #16 Drill #12-24 Tap. 1/8 Drill

TOOLS REQUIRED Metal Wood Wood and Metal Screws. #16 Drill #12-24 Tap. 1/8 Drill DEVICES COVERED IN THIS DOCUMENT: 4700S Surface Vertical Rod Device 4700SF Fire Exit Surface Vertical Rod Device TOOLS REQUIRED Metal Wood Wood and Metal Screws Sex Bolts #7 Drill ¼ -20 Tap #16 Drill #12-24

More information

Safety glasses Measuring tape Level Pencil Power drill Center punch Phillips screw driver Saw horse

Safety glasses Measuring tape Level Pencil Power drill Center punch Phillips screw driver Saw horse EX76 Concealed Vertical Rod Exit Device Preparation Guide and Installation Instructions Box Contents EX76 Concealed Vertical Rod Exit Device Back Bar Active Push Bar Filler Plate Door Kit with Templates

More information

D3976 RECESSED EXIT INSTALLATION INSTRUCTIONS

D3976 RECESSED EXIT INSTALLATION INSTRUCTIONS PACKAGE CONTENTS PRODUCT MUST BE INSTALLED ACCORDING TO ALL APPLICABLE BUILDING AND LIFE SAFETY CODES TEMPLATE INSTALLATION INSTRUCTIONS STRIKE HAND TOOL 5/32 HEX KEY ROD END CAPS EXIT DEVICE CRANK ARM

More information

Elite. PLANNING GUIDE builder & architect edition. AmeriGlide Accessibility Solutions RESIDENTIAL ELEVATOR. ASME A17.1, Part V, Section 5.

Elite. PLANNING GUIDE builder & architect edition. AmeriGlide Accessibility Solutions RESIDENTIAL ELEVATOR. ASME A17.1, Part V, Section 5. Elite RESIDENTIAL ELEVATOR builder & architect edition ASME A17.1, Part V, Section 5.3 June 18, 2018 All information found in s Elite Elevator Planning Guide reflects information at the time of printing.

More information

ED1300/1300F SERIES CONCEALED VERTICAL ROD DEVICE INSTALLATION INSTRUCTIONS

ED1300/1300F SERIES CONCEALED VERTICAL ROD DEVICE INSTALLATION INSTRUCTIONS ED1300/1300F SERIES CONCEALED VERTICAL ROD DEVICE INSTALLATION INSTRUCTIONS Ver.2 1300 SERIES CONCEALED VERTICAL ROD DEVICE Top Strike Latch Screws Strike Screws Release Plunger Top Latch Plunger Screws

More information

PUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE

PUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE Multilift PUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE Applicable Codes: ASME A17.1 ASME A18.1 CSA B613 CSA B355-09 Part No. 000790 16-m02-2017 Copyright 2017 Savaria Concord Lifts, Inc. All Rights Reserved

More information

VERTICAL PLATFORM LIFT

VERTICAL PLATFORM LIFT HERCULES II VERTICAL PLATFORM LIFT INSTALLATION GUIDE Please read this installation guide carefully to ensure correct installation of your HERCULES II Vertical Platform Lift. HERCULES II RESIDENTIAL &

More information

7130(F) Series Mortise Exit Devices Installation Instructions

7130(F) Series Mortise Exit Devices Installation Instructions 7130(F) Series Mortise Exit Devices Installation Instructions Outside Trim Device is packed ready for any Yale 650F or 660F Series Trim. End Clamp (3) 8-32 x 5/16" PUFHMS End Cap (2) 1/4-20 x 1" PPHMS

More information

PUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE

PUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE Multilift PUBLIC VERTICAL PLATFORM LIFT PLANNING GUIDE Applicable Codes: ASME A17.1 ASME A18.1 CSA B613 CSA B355-09 Part No. 000790 07-m03-2016 Copyright 2016 Savaria Concord Lifts, Inc. All Rights Reserved

More information

Infinity 20 Min. FIRE RATED DOORS WARNOCK HERSEY INFINITY - STANDARD RAISED - 20 MIN. RATING SOFTWOOD STILE

Infinity 20 Min. FIRE RATED DOORS WARNOCK HERSEY INFINITY - STANDARD RAISED - 20 MIN. RATING SOFTWOOD STILE Infinity 20 Min Note: 20 Minute (Positive Pressure) Category A & B Manufacturing Specifications MAXIMUM SIZES All doors shall have a minimum thickness of 1-3/4" + 1/16" Single Swing: 4/0 x 9/0 Standard

More information

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION SECTION R507 DECKS R507.1 Application. The provisions of this section shall provide prescriptive requirements for the design and construction of all uncovered, wood-framed, single-span exterior decks.

More information

Active Push Bar. Safety glasses Measuring tape Level Pencil Power drill Drill bits: 5/32, 3/4 Center punch Phillips screw driver

Active Push Bar. Safety glasses Measuring tape Level Pencil Power drill Drill bits: 5/32, 3/4 Center punch Phillips screw driver EX88 Interlocking Rim Exit Device Preparation Guide and Installation Instructions Box Contents EX88 Interlocking Rim Exit Device Back Bar Filler Plate Active Push Bar Cylinder and Trim Interface Kit Mounting

More information

Multilift (B613 & B355)

Multilift (B613 & B355) Multilift (B613 & B355) VERTICAL PLATFORM LIFT PLANNING GUIDE Applicable Codes: CSA B613 CSA B355-09 13-m03-2014 Part No. 000790 Copyright 2014 Savaria Corporation All rights reserved. Printed in Canada

More information

1530(F) Mortise Exit Devices Installation Instructions

1530(F) Mortise Exit Devices Installation Instructions 1530(F) Mortise Exit Devices Installation Instructions Singe Doors or Pairs (2) 12-12-24 PFHUM/WS 798 Universal Strike Standard Device Package Devices are packed ready for application reinforced metal

More information

33/3547A. Special tools needed: #10-24 tap Drill bits: #25, 5/16, 13/32, 1/2

33/3547A. Special tools needed: #10-24 tap Drill bits: #25, 5/16, 13/32, 1/2 911404-00 Concealed Vertical Rod Exit Device 33/3547A Installation Instructions Devices covered by these instructions: 33/3547A and 33/3548A Concealed Vertical Rod Exit Device 33/3547A-F and 33/3548A-F

More information

City of Manteca Boarding Requirements

City of Manteca Boarding Requirements City of Manteca Boarding Requirements There should be no boarding above the first floor unless entry is possible without use of a ladder, and the opening is large enough for a person to easily pass through.

More information

SECTION FINISH HARDWARE

SECTION FINISH HARDWARE SECTION 08710 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work under this Section shall include all materials and installation necessary to provide Finish Hardware as shown and detailed on the Drawings

More information

W INCLUDES PAYLOAD, LIFTING DEVICE, & TOOLING

W INCLUDES PAYLOAD, LIFTING DEVICE, & TOOLING MODEL MAX MOMENT AT MAIN POST TOOLING AND PAYLOAD MOMENT ALLOWED AT MAIN EARING 1 LOADING EXAMPLE TOOLING AND PAYLOAD MOMENT ALLOWED AT MIDDLE JOINT 1 A C D REACH (FT) CAPACITY** (LS) AJ-60 60,000 R X

More information

Encore 20 Min. FIRE RATED DOORS WARNOCK HERSEY ENCORE - STANDARD PANEL - 20 MIN. RATING

Encore 20 Min. FIRE RATED DOORS WARNOCK HERSEY ENCORE - STANDARD PANEL - 20 MIN. RATING Encore 20 Min 20 Minute (Positive Pressure) - Category B Manufacturing Specifications MAXIMUM SIZES All doors shall have a minimum thickness of 1-3/4" + 1/16" Single Swing: 4/0 x 8/0 Standard Pair: 8/0

More information

33/3527A. Devices covered by these instructions: 33/3527A-F (Fire) Surface Vertical Rod Exit Device

33/3527A. Devices covered by these instructions: 33/3527A-F (Fire) Surface Vertical Rod Exit Device *911403-00* 911403-00 Surface Vertical Rod Exit Device 33/3527A Installation Instructions Devices covered by these instructions: 33/3527A Surface Vertical Rod Exit Device 33/3527A-F (Fire) Surface Vertical

More information

7110(F), 7170(F)(LBR) Surface Vertical Rod Exit Device Series Installation Instructions

7110(F), 7170(F)(LBR) Surface Vertical Rod Exit Device Series Installation Instructions 7110(F), 7170(F)(LBR) Surface Vertical Rod Exit Device Series Installation Instructions Shim (2) Supplied Strike Plate 791 Strike (3) 10-24 x 3/4 (19mm) PFHMS Strike Angle Must Engage Strike 12-24 FHPMS

More information

Entry Mortise Handleset

Entry Mortise Handleset 1. Pencil 2. No. 2 and No. 3 Phillips Head Screwdrivers 3. No. 1 and No. 2 Slotted Screw Drivers 4. 1/8" Allen Head Wrench 5. 3/4" Wood Chisel or Corner Chisel 6. Measuring Device 7. Lock Mortising Tool

More information

FOR PROFESSIONAL GARAGE DOOR INSTALLERS

FOR PROFESSIONAL GARAGE DOOR INSTALLERS Composite Garage Doors Installation Instructions FOR PROFESSIONAL GARAGE DOOR INSTALLERS Tools required Screwdriver Claw Hammer Locking Pliers Power Drill Level with a 3/32" Drill Bit Utility Knife 9/16",

More information

* * 9875/ Customer Service #10-24 # Dogging Key (use to lock down pushbar)

* * 9875/ Customer Service #10-24 # Dogging Key (use to lock down pushbar) *911374-00* 911374-00 Mortise Exit Device 9875/9975 Installation Instructions #10-24 #12-24 Dogging Key (use to lock down pushar) Customer Service 1-877-671-7011 www.allegion.com/us Allegion 2015 Printed

More information

4. Components and Stairs

4. Components and Stairs 4. Components and Stairs 4.1 BUILDING WINDOW AND DOOR COMPONENTS 4.2 BUILDING STAIRS Tools needed by volunteer: Hammer Nail apron Tape measure Square Utility knife Pencil Tools and equipment needed: Materials

More information

CRL JACKSON 900 SERIES

CRL JACKSON 900 SERIES INSTALLATION INSTRUCTIONS CRL JACKSON 900 SERIES FLOOR MOUNTED DOOR CLOSERS CENTER HUNG AND OFFSET crlaurence.com crlaurence.com MODEL No. 990 crlaurence.com Phone: (800) 421-6144 Fax: (800) 262-3299 crlaurence.com

More information

1510(F) Surface Vertical Rod Exit Devices Installation Instructions

1510(F) Surface Vertical Rod Exit Devices Installation Instructions 1510(F) Surface Vertical Rod Exit Devices Installation Instructions Top Mounting Plate (2) 1/4-20 x 3/4" PFHMS Rod Guide Top Rod Shim (2 Supplied) Strike Plate 791 Strike (3) 10-24 x 3/4" PFHMS or (3)

More information

Installation Manual. Solid Plastic Toilet Partitions. IN CANADA & AREAS OTHER THAN U.S.A.: IN THE U.S.A.:

Installation Manual. Solid Plastic Toilet Partitions.   IN CANADA & AREAS OTHER THAN U.S.A.: IN THE U.S.A.: Installation Manual Solid Plastic Toilet Partitions Toilet Partitions & Lockers IN THE U.S.A.: Hadrian Inc., 7420 Clover Avenue, Mentor, OH 44060 Telephone: 440-942-9118 Fax: 440-942-9618 U.S. toll free

More information

INSTALLATION INSTRUCTIONS CRL JACKSON

INSTALLATION INSTRUCTIONS CRL JACKSON INSTALLATION INSTRUCTIONS CRL JACKSON 2085 CONCEALED VERTICAL ROD PANIC EXIT DEVICE crlaurence.com Phone: (800) 421-6144 Fax: (866) 921-0531 crlaurence.com usalum.com crl-arch.com 11M0250 ORDER OF ASSEMBLY

More information

Installation Instructions - Model V4JSD 1

Installation Instructions - Model V4JSD 1 Installation Instructions - Model V4JSD 1 Support Assemblies: Parts list: (Note see enclosed cut sheet for quantities and dimensional information) A vertical structural member (1 ½ x 1 ½ modular frame)

More information

Dura-Lock Roof System

Dura-Lock Roof System DLR-14 Dura-Lock Roof System Assembly and Installation Instructions Read the instructions before starting the job. They explain the steps required to produce a finished product that will meet factory specifications.

More information

FIXED PANEL SLIDER QCI5241

FIXED PANEL SLIDER QCI5241 INSTALLATION INSTRUCTIONS FIXED PANEL SLIDER QCI5241 FRAMELESS PANEL / DOOR / PANEL FRAMELESS DOOR / PANEL QCI5241 REV. 0 Page 1 Certified 06/16/2016 Parts List *Quantities may vary QCI5241 REV. 0 Page

More information

SLIDE 06 Solutions Document/Installation Manual

SLIDE 06 Solutions Document/Installation Manual SLIDE 06 Solutions Document/Installation Manual 1 The Slide 06 door system from 3form is a completely unframed panel door that uses the same sophisticated, tried-and-true rollers and track as Slide 05.

More information

Storefront Installation Guide

Storefront Installation Guide Storefront General Notes: 1. Check Contract Documents and Shop Drawings. Understand and clarify any Field Verify Notes and approvals of drawings and products to be familiar with the project. Installation

More information

WALKS AND SIDEWALKS REQUIREMENTS:

WALKS AND SIDEWALKS REQUIREMENTS: DOUBLE PARKING STALLS DIAGONAL PARKING STALLS EXTERIOR ROUTES OF TRAVEL: From accessible parking spaces, provide most practical direct accessible route of travel to all building entrances and exteriorground

More information

Chapter 4. Accessible Routes

Chapter 4. Accessible Routes ICC/ANSI A117.1-2003 401 General 401.1 Scope. Accessible routes required by the scoping provisions adopted by the administrative authority shall comply with the applicable provisions of Chapter 4. 402

More information

Senior Swing. Caution

Senior Swing. Caution *740132* 740132 2800 Overhead Concealed Series 9500 Surface Applied Series Senior Swing Installation Instructions Caution LCN Senior Swing The Senior Swing Power Operator System is a low energy product

More information

7210 Surface Vertical Rod Exit Device Installation Instructions. Outside Trim

7210 Surface Vertical Rod Exit Device Installation Instructions. Outside Trim 7210 Surface Vertical Rod Exit Device Installation Instructions Top Mounting Plate (2) 1/4-20 x 3/4" PFHMS Blade Stop Block Shim (2 Supplied) Strike Plate 791 Strike (3) 10-24 x 1-1/4" PFHMS Top Latch

More information

BioPrism Solid Surface

BioPrism Solid Surface Please read all instructions before installing products. These instructions are intended for use with InPro s standard toilet partitions, which include 58 high doors and wall panels, when deviating from

More information

For installation assistance, contact SARGENT at DOORS SHOWN HERE SWING IN FOR ILLUSTRATION PURPOSES ONLY.

For installation assistance, contact SARGENT at DOORS SHOWN HERE SWING IN FOR ILLUSTRATION PURPOSES ONLY. SARGENT Installation Instructions for LP8600 x LR8600 & 12-LP8600 x 12-LR8600 Series Low Profile Panic and Fire Exit Devices on Double Egress & Double Doors or LS8600 & 12-LS8600 Low Profile Exit Device

More information

Victory Fire Door Inspections

Victory Fire Door Inspections Vickie Evans, FDAI Over 30 years in door and hardware industry DHI instructor and Education Advocate Certified Fire Door Inspector To compartmentalize a building Deter the spread of smoke and flames Fire

More information

OPERATOR ADAPTER APCABVA

OPERATOR ADAPTER APCABVA OPERATOR ADAPTER APCABVA Installation Instructions for Allen-Bradley Bulletin 1494V (Variable Depth) 1494C, 140G and 140U Cable Controlled For floor-mounted enclosures with disconnect on the right flange

More information

98/9927. Devices covered by these instructions: Surface Vertical Rod Exit Device

98/9927. Devices covered by these instructions: Surface Vertical Rod Exit Device 911375-00 Surface Vertical Rod Exit Device 98/9927 Installation Instructions Devices covered by these instructions: 98/9927 Surface Vertical Rod Exit Device 98/9927-F (Fire) Surface Vertical Rod Exit Device

More information

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available. SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence MILWAUKIE OR #3144-00 ADDENDUM #5 NARRATIVE: 11-08-12 WAL-MART SUPERCENTER #3144-00; Milwaukie, OR: SPECIFICATIONS SPECIFICATIONS Revisions to Specification 02822 Fence Spec division 02822 has been revised

More information

Installation Instructions

Installation Instructions VON DUPRIN Installation Instructions 98/9947WDC Concealed Vertical Rod Exit Device Wood Door Applications Devices covered by these instructions: 98/9947WDC Concealed Vertical Rod Device 98/9947WDC-F (Fire)

More information

PAINT & MISC. Notes. Table of Contents. Front Handrail Posts Front Handrails Closet Shelving Exterior Deck...

PAINT & MISC. Notes. Table of Contents. Front Handrail Posts Front Handrails Closet Shelving Exterior Deck... 118 PAINT & MISC. Table of Contents Front Handrail Posts... 119 Front Handrails... 122 Closet Shelving... 125 Exterior Deck... 127 Look for painter s tape on the hammer drill for where to set the depth.

More information

ED5800 (A) Series. Installation Instructions. Concealed Vertical Rod. Exit Device WARNING

ED5800 (A) Series. Installation Instructions. Concealed Vertical Rod. Exit Device WARNING Strike Shim (2) Supplied Strike Plate (3) 10-24 x 3/4" PFHMS (6) 10-24 x 1/2" PFHMS Top Latch TopTube Concealed Vertical Rod Exit Device Important: For use with metal doors only. Device is packed ready

More information

Preference Collection 5580 Treatment Console INSTALLATION GUIDE

Preference Collection 5580 Treatment Console INSTALLATION GUIDE Preference Collection 5580 Treatment Console INSTALLATION GUIDE 0 WARNING Failure to install the 5580 as described in this installation guide may cause the unit to collapse, resulting in serious injury

More information

INSTALLATION INSTRUCTIONS FOR INSTALLING T-SERIES EXTRA HEAVY DUTY LEVER LOCKSET

INSTALLATION INSTRUCTIONS FOR INSTALLING T-SERIES EXTRA HEAVY DUTY LEVER LOCKSET HIGH EDGE 2 1/4"(57mm) 03079400070 INSTALLATION INSTRUCTIONS FOR INSTALLING T-SERIES EXTRA HEAVY DUTY LEVER LOCKSET IMPORTANT: THIS LOCK IS NON-HANDED. LOCK IS FACTORY PACKED PREADJUSTED FOR 1³ ₄" (45mm)

More information

APPLICATION FOR A BUILDING PERMIT

APPLICATION FOR A BUILDING PERMIT APPLICATION FOR A BUILDING PERMIT City of San Jacinto 595 S. San Jacinto Ave San Jacinto CA 92583 95.487.7330 fax 95.654.9896 Must print legibly, submit (3) sets of building and plot plans. Fill out all

More information

TURBOTWISTER TM ASSEMBLY AND INSTALLATION INSTRUCTIONS

TURBOTWISTER TM ASSEMBLY AND INSTALLATION INSTRUCTIONS TURBOTWISTER TM ASSEMBLY AND INSTALLATION INSTRUCTIONS CORPORATE HEADQUARTERS WESTERN SALES AND MANUFACTURING PLANT P.O. Box 400 1017 SW Berg Parkway Canby, Oregon 97013 Phone: (503) 266-2231 Fax: (503)

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Special-Lite Restroom Partitions IMPORTANT - BEFORE YOU START... 1. Read through these installation instructions first to understand the order of work. 2. Check all components

More information

2010 ADA Standards Courtroom Requirements

2010 ADA Standards Courtroom Requirements 2010 ADA Standards Courtroom Requirements LIFT-U Division of Hogan Mfg., Inc. P.O. Box 398 Escalon, CA 95320 http://liftu.hogan.com Slide 1 of 50 2010 ADA Standards Courtroom Requirements LIFT-U Division

More information

TS-20KD-1010 LOW PROFILE CARGO SCALE INSTALLATION GUIDE

TS-20KD-1010 LOW PROFILE CARGO SCALE INSTALLATION GUIDE TS-20KD-1010 LOW PROFILE CARGO SCALE INSTALLATION GUIDE Triner Scale & Mfg. Co., Inc. 8411 Hacks Cross Rd. Olive Branch, MS 38654 Phone: 800-238-0152 Fax: 662-809-2386 Description The Triner Scale Model

More information

INFUSIONS and METALWORKS Wings Accent and Acoustical Clouds

INFUSIONS and METALWORKS Wings Accent and Acoustical Clouds INFUSIONS and METALWORKS Wings Accent and Acoustical Clouds Assembly and Installation Instructions 1. GENERAL 1.1 Product Description Wings is a decorative ceiling element consisting of a 10 foot long

More information

American Safe Room. Explosion Resistant Blast Hatch with Integrated Riser

American Safe Room. Explosion Resistant Blast Hatch with Integrated Riser American Safe Room Explosion Resistant Blast Hatch with Integrated Riser Drawing: ASR-50-RBH Revision: H May 17, 2012 Table of Contents Description... 3 Options... 4 Order form... 5 Option: left or right

More information

Rolling Curtain door Manual

Rolling Curtain door Manual Rolling Curtain door Manual Installation Maintenance parts Model 944 PHONE 800 448 8979 FAX 800 236 8722 website www.tracrite.com EMAIL tr@tracrite.com ADDRESS 216 Wilburn Road Sun Prairie, WI 53590 This

More information

western window systems westernwindowsystems.com installation instructions non-pocket 2-1/4 panels

western window systems westernwindowsystems.com installation instructions non-pocket 2-1/4 panels series 2600 multi-slide non-pocket 2-1/4 panels windowsystems.com windowsystems.com movement, which can cause warping and other problems. Frame kit components: Each door will have a head assembly, a threshold

More information

TURBOTWISTER ASSEMBLY AND INSTALLATION INSTRUCTIONS

TURBOTWISTER ASSEMBLY AND INSTALLATION INSTRUCTIONS TURBOTWISTER ASSEMBLY AND INSTALLATION INSTRUCTIONS CORPORATE HEADQUARTERS WESTERN SALES AND MANUFACTURING PLANT P.O. Box 400 1017 SW Berg Parkway Canby, Oregon 97013 Phone: (503) 266-2231 Fax: (503) 266-4334

More information

Shim (2) Supplied. Strike Plate. (3) x 5/8" PFHMS or 10 x 1" PFHWS. Top Latch. (3) x 1/4" PRHMS. Latch Cover. (2) 8 x 3/8" PFH AB SMS

Shim (2) Supplied. Strike Plate. (3) x 5/8 PFHMS or 10 x 1 PFHWS. Top Latch. (3) x 1/4 PRHMS. Latch Cover. (2) 8 x 3/8 PFH AB SMS Installation Instructions ED5400 (A) Series ED5470 (B) Series Surface Vertical Rod Exit Devices Strike Angle Must Engage Strike Top Strike 10-24 PFHMS Top Bracket and Strike required for ED5470. Shim (2)

More information

EXIT DEVICE OPERATION FIRE DOOR LABELS, STRIKES AND FRAME SCREWS FOR INFORMATION CALL OR VISIT RITEDOOR.COM

EXIT DEVICE OPERATION FIRE DOOR LABELS, STRIKES AND FRAME SCREWS FOR INFORMATION CALL OR VISIT RITEDOOR.COM RECORD & LABELS WHAT THIS OWNER'S CAN DO FOR YOU It explains exactly how The Rite Door operates. It explains periodic maintenance requirements necessary to assure reliable operation. It explains simple

More information

MPA-9000 Universal Ceiling Projector Mount Kit

MPA-9000 Universal Ceiling Projector Mount Kit I N S T R U C T I O N M A N U A L Universal Ceiling Projector Mount Kit The Universal Ceiling Projector Mount provides a unique, simplified method of ceiling mounting your inverted projector. This low

More information

Shetland Stalls Installation Instructions

Shetland Stalls Installation Instructions Shetland Stalls Installation Instructions RAMM Horse Fencing and Stalls 13150 Airport Hwy. Swanton, OH 43558-9615 1-800-434-8456 Rev. 1/9/18 Before you start Kit can accommodate up to 12 wide stall front

More information

Installation of Balustrade Systems

Installation of Balustrade Systems Installation of Balustrade Systems IMPORTANT: Be sure to mark the center point of each newel post's location prior to installation to insure proper spacing. All product interfaces must use PL Premium Adhesive

More information

Full Height Ladder Safety Gate

Full Height Ladder Safety Gate Full Height Ladder Safety Gate Installation Instructions/Operation and Maintenance Manual Models Powder Coat Yellow (PCY) 304 Stainless Steel (SS) Hot Dipped Galvanized (GAL) Table of Contents Product

More information

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. PAGE 1 PART 1 GENERAL 1.1 REFERENCE.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. 1.2 RELATED WORK SPECIFIED ELSEWHERE.1 Installation

More information

ACORNWIRE.COM MESH PARTITIONS DIVISION 10 - SPECIALTIES WIRE MESH PARTITION FOLDING GATE

ACORNWIRE.COM MESH PARTITIONS DIVISION 10 - SPECIALTIES WIRE MESH PARTITION FOLDING GATE acorn WIRE ACORNWIRE.COM MESH PARTITIONS DIVISION 10 - SPECIALTIES 10 22 13 WIRE MESH PARTITION 10 22 16 FOLDING GATE GUIDE Page 4 / 5 No. 130A All wire type for normal industrial use. 7, 8, 9, 10 and

More information

MobileTrak5 Installation Instructions

MobileTrak5 Installation Instructions MobileTrak5 Installation Instructions PLEASE OPEN ALL BOXES & CHECK TO MAKE SURE YOU HAVE ALL PIECES REQUIRED READ ALL INSTRUCTIONS BEFORE STARTING Tools Required for Assembly 7/16, 1/2 Wrench Phillips

More information

Design Considera ons & Installa on Guidance

Design Considera ons & Installa on Guidance Design Considera ons & Installa on Guidance LiteSpace Interior Aluminum Framing provides a slim profile for glass walls and office fronts. It is designed to be cut to length on project sites for finished,

More information

Table of Contents Holders & Stops

Table of Contents Holders & Stops Copyright 2003, 2007, 2009-2018, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved. Table of Contents Overview.... 1 General Information.... 2 Features and Details.... 3 590

More information

YUKON PATIO COVER INSTALLATION INSTRUCTIONS

YUKON PATIO COVER INSTALLATION INSTRUCTIONS YUKON PATIO COVER INSTALLATION INSTRUCTIONS Before You Begin: Consult your local building department for any required permits You may be required to obtain a building permit for this structure. Contact

More information

DC3210. Recommended Closer Size

DC3210. Recommended Closer Size Installation Instructions For Non-Hold Open or A Hold Open Arm Option DC3200 Series Multi-Sized thru 6 Regular Arm Universal Door Closers Parallel Arm Jamb Mount See pages 2&3 See pages 4&5 See pages 6&7

More information

CRT-52-SS KIT SERIES INSTRUCTION SHEET

CRT-52-SS KIT SERIES INSTRUCTION SHEET CRT-52-SS KIT SERIES INSTRUCTION SHEET (COMPLETE CRT-52-SS KIT ILLUSTRATED) CROWDERTRACK S CRT-52-SS SERIES SYSTEM LOAD CAPACITY 150LS. (TWO HANGERS) EXPOSED STAINLESS STEEL HARDWARE SHOCK ASORING STOPS

More information

S6 User s Manual USER S MANUAL ver. 1.0

S6 User s Manual USER S MANUAL ver. 1.0 S6 User s Manual SKEETER - 1U LOW PROFILE SOLUTION Table of Contents Tabletop Configuration 2 Tabletop Configuration Accessories 4 Slide Configuration 5 slide configuration accessories 7 rack Mount configuration

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION METAL LOCKERS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION METAL LOCKERS PART 0 A/E INSTRUCTIONS 0.01 GENERAL DESIGN REQUIREMENTS A. Architect shall coordinate with the DPS Project Manager the type, layout and size of lockers required on the project. B. Varsity athletic Lockers

More information

DIY Field Guide ANDYMARK, INC.

DIY Field Guide ANDYMARK, INC. ANDYMARK, INC. Intro For the 2014-2015 FTC Game Cascade Effect, teams can purchase official field hardware from AndyMark, or they can build do-it-yourself (DIY) versions of the same hardware. The competitions

More information

End of Row Doors. Revision Number 1

End of Row Doors. Revision Number 1 End of Row Doors Single Swing Door Café Style Doors Revision Number 1 Wright Line LLC 160 Gold Star Boulevard Worcester, MA 01606 Tel: 800-225-7348 508-852-4300 Fax: 508-365-6178 www.wrightline.com info@wrightline.com

More information

MSP-DCCLFSD LCD Flat Screen Swing-Down Mount

MSP-DCCLFSD LCD Flat Screen Swing-Down Mount INSTALLATION INSTRUCTIONS LCD Flat Screen Swing-Down Mount Perfect for home applications under kitchen cabinets or other rooms with a soffit. The LCD Flat Screen Swing-Down mount is a sturdy, versatile

More information

WD WD7000 Series

WD WD7000 Series WD-7000 12-WD7000 Series Wood Door Concealed Vertical Rod Multi-Point Lock Installation Instructions Copyright 2015, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved. Reproduction

More information

INSTALLATION INSTRUCTIONS LARGE FLAT PANEL IN WALL ENCLOSURE Model: PAC-500

INSTALLATION INSTRUCTIONS LARGE FLAT PANEL IN WALL ENCLOSURE Model: PAC-500 INSTALLATION INSTRUCTIONS LARGE FLAT PANEL IN WALL ENCLOSURE Model: PAC-500 Specifications: Designed for in-wall installation spanning a minimum of 3 wood studs, 16" on center. Accomodates MWR, PWR and

More information

Preference Collection and Treatment Console INSTALLATION GUIDE

Preference Collection and Treatment Console INSTALLATION GUIDE Preference Collection 5580.69 and 5580.96 Treatment Console INSTALLATION GUIDE WARNING Failure to install the 5580 as described in this installation guide may cause the unit to collapse, resulting in serious

More information

PHTM200 - Phantom 200 Flat Screen Wall Mount with Wafer Thin Projection Fits Screens up to 50 lbs with 200mm Mounting Patterns

PHTM200 - Phantom 200 Flat Screen Wall Mount with Wafer Thin Projection Fits Screens up to 50 lbs with 200mm Mounting Patterns PHTM200 - Phantom 200 Flat Screen Wall Mount with Wafer Thin Projection Fits Screens up to 50 lbs with 200mm Mounting Patterns Features: Durable high quality gloss black baked on powder coat finish Fits

More information

Mobile Weapons Storage System Specifications

Mobile Weapons Storage System Specifications Mobile Weapons Storage System Specifications Whatever your weapon storage needs, Hi-Density s customized Weapons Storage System will be designed to fit your unique specifications. We recognize that security

More information

Please read and understand all instructions before beginning. These instructions cover the non-impact aluminum sliding glass door.

Please read and understand all instructions before beginning. These instructions cover the non-impact aluminum sliding glass door. The performance and proper operation of a door is only as good as the installation. By following these instructions, the probability of a good installation greatly increases. Please read and understand

More information

4600 Series Rim Narrow Stile Exit Device Installation Instructions I-ED01162

4600 Series Rim Narrow Stile Exit Device Installation Instructions I-ED01162 DEVICES COVERED IN THIS DOCUMENT: 4600 Series Rim Panic Narrow Stile Exit Device 4600 Series Rim Fire Narrow Stile Exit Device OVERVIEW Outside of Door RHR LHR Inside of Door APPLICATIONS 4950 BLADE STOP

More information

ALUMINUM FENCE. Additional freight charges may apply depending on order size. Please call for quote at

ALUMINUM FENCE. Additional freight charges may apply depending on order size. Please call for quote at ALUMINUM FENCE Additional freight charges may apply depending on order size. Please call for quote at 1-888-662-1788 Powder Coat Finish FORGERIGHT Fences are offered in the choice of three colors: Black,

More information

Tools Required. Bench Hardware. Bench Parts. Planter Hardware. Planter Parts. BENCH/PLANTER INSTALLATION GUIDELINES for

Tools Required. Bench Hardware. Bench Parts. Planter Hardware. Planter Parts. BENCH/PLANTER INSTALLATION GUIDELINES for Arbor Collection / Harvest Collection / Terra Collection Page 1 Please read all instructions completely before starting any part of the installation. Each AZEK and Kit comes complete with all hardware,

More information

NARROW, MEDIUM AND WIDE STILE, THERMASTILE AND DURASTILE. Installation Instructions

NARROW, MEDIUM AND WIDE STILE, THERMASTILE AND DURASTILE. Installation Instructions NARROW, MEDIUM AND WIDE STILE, THERMASTILE AND DURASTILE Installation Instructions PART Y015 JUNE 2016 Table of Contents Section 1. GENERAL NOTES AND GUIDELINES... 2. DOOR HARDWARE A. Locks B. Push/Pulls

More information

Office Installation Guidelines

Office Installation Guidelines UH Structures Inc. dba Ebtech Industrial 2241 Industrial Drive Connellsville, PA 15425-6181 Telephone: 724-628-6100 Fax: 1-412-774-2429 www.ebtechindustrial.com Office Installation Guidelines INTRODUCTION

More information

METALWORKS Wings Accent and Acoustical Clouds Installation Instructions

METALWORKS Wings Accent and Acoustical Clouds Installation Instructions CEILING SYSTEMS Between us, ideas become reality METALWORKS Wings Accent and Acoustical Clouds Installation Instructions 1. GENERAL 1.1. Product Description MetalWorks Wings is a decorative ceiling element

More information

Installation *HDWL-INSTR-001* IMPORTANT. Plastic Laminate Restroom Partitions Floor-Mounted with Overhead Brace Series 400

Installation *HDWL-INSTR-001* IMPORTANT. Plastic Laminate Restroom Partitions Floor-Mounted with Overhead Brace Series 400 Plastic Laminate Restroom Partitions Floor-Mounted with Overhead race Series 400 For Standard Height Doors and Panels Only Table of ontents Pre- Information...2 Layout Dimensions for rackets...3 Mounting

More information

SERIES 5001 SLIDING GLASS DOOR PATIO DOORS INSTALLATION GUIDE

SERIES 5001 SLIDING GLASS DOOR PATIO DOORS INSTALLATION GUIDE PATIO DOORS INSTALLATION GUIDE These instructions cover general installation conditions. Improper installation could affect your doors operation and warranty. Deviations from these instructions should

More information

Guide Specification Section Interior Aluminum Doors and Frames

Guide Specification Section Interior Aluminum Doors and Frames Guide Specification Section 08 11 16 Interior Aluminum Doors and Frames SECTION 08 11 16 The Sliding Door Company s door and frame system includes glazed swing doors, sidelights, transoms, and fixed panels

More information

Installation Instructions for Vista Air Vertically Folding Walls

Installation Instructions for Vista Air Vertically Folding Walls Installation Instructions for Vista Air Vertically Folding Walls Use these instructions in conjunction with your shop drawings to see the specifics that are particular to the model you are installing.

More information

ANDORRA PLAY SYSTEM F24140C

ANDORRA PLAY SYSTEM F24140C ANDORRA PLAY SYSTEM F24140C INSTALLATION AND OPERATING INSTRUCTIONS 28 8.5m 14 5 (4.4 m) 9 2.7m 22 3 / 6.8m 10 3 / 3.1m 18 8 (5.7 m) WARNING To reduce the risk of serious injury or death, you must read

More information

CertainTeed INSTALLATION GUIDE SIMTEK FENCE PRODUCTS. Fence Installation Guide 3', 4' & 6' High

CertainTeed INSTALLATION GUIDE SIMTEK FENCE PRODUCTS. Fence Installation Guide 3', 4' & 6' High CertainTeed INSTALLATION GUIDE SIMTEK FENCE PRODUCTS Fence Installation Guide 3', 4' & 6' High INSTALLATION GUIDE These instructions are designed to assist both professional installers and do-it-yourselfers

More information