1 St. Thomas Retirement Home SWM Brief (2017) Storm Water Management and Servicing Design Report For St. Thomas Retirement Home 292 Wellington Street, St. Thomas, ON N5R 2S9 PREPARED FOR SUNRAY GROUP PREPARED BY GAMA Engineering Inc Weston Road, Suite 35B Vaughan, Ontario L4L 9P1 June 28, 2017 Gama Project No. 1710

2 St. Thomas Retirement Home SWM Brief (2017) Introduction Gama Engineering Inc. has been retained by API Development Consultants Inc., to provide a grading, site servicing and stormwater management design in support of a Site Plan Application for the proposed site development located at 292 Wellington Street in the City of St. Thomas. The stormwater management brief will outline the drainage concepts to be used for the proposed development, and the rational therefore. The subject property known as St. Thomas Retirement Home includes the construction of an existing building demolition, a new building, paved parking lots and driveway, grading and related servicing system. The proposed building involves six (6) storeys. The site will be accessed via three driveways off Wellington Street and Erie Street. The location plan is shown below as Figure 1. St. Thomas Retirement Home Reference Figure 1 Design Guidelines Manual, St. Thomas, 2017 Edition Design Guidelines for Sewage Works, Ministry of the Environment, 2008 Stormwater Management Planning and Design Manual, Ministry of the Environment, March 2003 Site characteristic The property is located at the south of Wellington Street, between First Avenue and Second Avenue, St. Thomas, Ontario. At present time there are some underground storm pipes at the existing developed area. The existing building and paved parking lots will be demolished with site servicing. The existing storm drain connection has not been found during survey. It will be site verified and capped. The pre development condition of the site is mostly hard surface with around 98%. The post development condition will be essentially 87% of hard surface. As such, the runoff generated by the site will be less under

3 St. Thomas Retirement Home SWM Brief (2017) the post development condition. The allowable stormwater release rate will not be controlled and stormwater quantity storage won t be required. In the proposed site, the total area is 3866 sq. m, including impervious areas such as building roof, asphalt paving parking lots and driveways, concrete sidewalks and pads, as 87% of the overall site. Refer to Appendix A for the Pre Development and Post Development Drainage Area Plans. The plans sized as 11 x17 are attached in this report. Refer to GP 3 and GP 4 in the civil drawing package for their full size copies. Alternatives and Rational According to the City s Design Guidelines Manual, minor storm design flows for the site is to be for the 1:5 year storm event. The release rate is 0.069m 3 /s which is less than pre development release rate of 0.073m 3 /s. Refer to Appendix B for Storm Sewer Design Sheet and Storm Structure Table. The stormwater discharges to existing 3000mm storm line at the west side of the property. The control of allowable release rate from post development to the pre development flow is not required since the proposed conditions have greater pervious area than the existing condition. Low Impact Development Low Impact Development methods and alternatives are not applied for the subject site. Rainfall Due to the size of site area and highly urbanized development, the IDF Curves provided in the City s Guidelines have been used in the simulation. Results The spreadsheet results indicated that the pre and post development flows as shown in the following Table 1: Table 1: Major System Overland Flow Measurement LOCATION AREA AREA NO. STREET AREA RUNOFF A.C ACCUM. TC INTENSITY DESIGN FROM TO COEFF. A.C. FLOW Q MANHOLE MANHOLE (Ha) C (min.) (mm/hr) (cu.m/s) ENTIRE SITE (PRE-DEVELOPMENT 2-YR) ENTIRE SITE (POST-DEVELOPMENT 2-YR) ENTIRE SITE (PRE-DEVELOPMENT 5-YR) ENTIRE SITE (POST-DEVELOPMENT 5-YR) ENTIRE SITE (PRE-DEVELOPMENT 10-YR) ENTIRE SITE (POST-DEVELOPMENT 10-YR) ENTIRE SITE (PRE-DEVELOPMENT 25-YR) ENTIRE SITE (POST-DEVELOPMENT 25-YR) ENTIRE SITE (PRE-DEVELOPMENT 50-YR) ENTIRE SITE (POST-DEVELOPMENT 50-YR) ENTIRE SITE (PRE-DEVELOPMENT 100-YR) ENTIRE SITE (POST-DEVELOPMENT 100-YR)

4 St. Thomas Retirement Home SWM Brief (2017) The storm sewer design sheet and the storm structure table are attached in Appendix B. Quality Control Stormceptor STC 300 is required to achieve 99% of TSS removal and 87% of runoff treatment for the overall site. The uncontrolled post development release flow rate for the whole site is considered for the quality control. Storm water from the building roof is cleaner than runoff from parking lots and driveways. In this case roof drainage is not necessary for quality control. The stormceptor is located to control runoff from parking lots and driveways so that it can deal with heavier storm events than designed. Refer to Appendix C for the detailed sizing of the stormceptor. Monitoring and Maintenance After completion of the installation, it is recommended the storm sewer system be flushed and cleaned to ensure the systems are free of sediments and construction debris. Annual inspection and flushing from the system are also recommended. Erosion and Sediment Controls Topsoil and vegetation, exiting asphalt surface will be removed from the majority of the developing site to accommodate site grading and construction of services. The resulting distributed ground will require sedimentation control measures to prevent silt from reaching the receiving storm sewer. Refer to civil drawing GP 8 for the Erosion and Sediment Control Plan. A mud tracking mat shall be installed at the entrance to the construction site to ensure that mud is not carried off the site on to existing roads. Any mud tracked on to the neighbouring roads during construction should be cleaned up. Siltation from surface runoff from the site can be prevented with the use of silt fences placed along the boundaries where runoff will occur. It will also be necessary to prevent siltation from entering the internal storm sewer system via catchbasins. This can be accomplished in the catch basins by placing filter cloth material over the grate, use of a silt sack. All the sediment control measures mentioned above shall require regular monitoring and maintenance. Further to these measures, once the building, the driveways and the parking lots are constructed, siltation arising from building activity should be reduced by regular cleaning of the driveway. In order to reduce the amount of sediment reaching Wellington Street and Erie Street, it is suggested that the grade at the property line be left approximately 200mm below the top of curb until such time as ground cover is about to be established. This will aid in the settlement of sediment, thus reducing sediment flow to the streets. Should building activity not commence soon after the servicing of the site, arrangement should be made to temporarily seed those areas not covered with vegetation.

5 St. Thomas Retirement Home SWM Brief (2017) Summary The recommendations and conclusions of this report regarding the storm drainage and the stormwater management issues for the proposed development are as follows: 1. The uncontrolled release flow shall be discharged below the pre development level. 2. The stormwater quantity storage won t be required. 3. Stormceptor STC 300 is required to achieve 99% of TSS removal and 87% of runoff treatment for the overall site. Roof water is cleaner than runoff from parking lots and driveways. It won t be quality control. 4. Siltation and erosion control measures shall be erected before construction activity commences and maintained throughout the construction process until adequate ground cover is established. We trust that the information provided is satisfactory and addresses City s concern. Prepared by: Lingyun Tu, M. Eng., P. Eng. Civil Engineer Gama Engineering Inc. June 28, 2017

6 St. Thomas Retirement Home SWM Brief (2017) Appendix A PRE DEVELOPMENT AND POST DEVELOPMENT DRAINAGE AREA PLANS

7 1710 St. Thomas Retirement Home Table A.01: Pre Development Area Plan Area, Ha Concrete / Asphalt Roof Grass Gravel Table A.02: Post Development Area Plan Area, Ha Concrete / Asphalt Roof Grass / Landscaping R R G G1 G C L L L L L L C L L Sub Total area, Ha L Total Area, Ha L C L AC L Avg. C Impervious Area Sub Total area, Ha XIMP Total Area, Ha TIMP C AC Avg. C Impervious Area XIMP TIMP XIMP: Ratio of total area directly connected impervious areas are those that form a continuous pathway from the point of runoff generation to the outlet point. TIMP: Ratio of total impervious area. Gravel

8 WELLINGTON STREET ha L ha 0.5 G1 3 LYT ISSUED FOR SPA ha 0.9 C1 2 LYT ISSUED FOR 75% CLIENT REVIEW LYT ISSUED FOR 60% CLIENT REVIEW ISSUE BY DESCRIPTION DATE [YY-MM-DD) GENERAL NOTES ha L ha 0.5 ERIE STREET G ha L ha 0.9 C1 DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED " I SSUED FOR CONSTRUCTION". VERIF Y CONFIGURATIONS & DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF A N Y E R R O R S, O M I S S I O N S O R D I S C R E P A N C I E S. DEVELOPMENT CONSULTANT: OAKVILLEOFFICE P: ; 206 Project Co-ordinator: Cristy Wilson E: cwilson@apiconsultants.net ARCHITECT 610 FORD DRIVE,SUITE 338 OAKVILLE, ON L6J 7W4 E: llsaplys@apiconsultants.net Project Contact: David Barnard E: dbarnard@apiconsultants.net P: CLIENT SUNRAY GROUP Consumers Road, Toronto, ON, M2J 4Z2 ENGINEER NORTH PROJECT NAME PROJECT ADDRESS DRAWING TITLE BY GAMA ENGINEERING INC Weston Road, Suite 35B, Vaughan, Ontario L4L 9P1 Project Contact: Wajid Mansuri E: wmansuri@bellnet.ca P: LYT PROJECT No. SCALE 1710 TRUE NORTH WELLINGTON SENIOR RESIDENCE BUILDING CHECKED 292WELINGTONST,ST.THOMAS,ON ISSUED FOR SHEET No. PROFESSIONAL CERTIFICATION PRE-DEVELOPMENT STORM DRAINAGE AREA PLAN WAM AS SHOWN SPA - 1ST SUBMISSION GP-3 SHEET REVISION 3.1 DRAWING LOCATION: \\GAMAENGINEERING\PUBLIC\GAMA PROJECTS\2017 PROJECTS\ WELLINGTON, ST THOMAS\AUTOCAD\WORKING\CIVIL\LAURA TU\JUN DRAWING FILENAME: 1710-CIVIL-MODEL-1 PLOT DATE: June 29, 2017

9 WELLINGTON STREET EX. STM MH T/C S. INV ± ha L ha L2 CB #1 FH ha L3 17.7m - 200Ø CB 1.0% ha 0.9 C1 8m - 250Ø 2.0% PVC-SDR35 STMMH #2 T/C m - 250Ø 1.0%, PVC-SDR m - 250Ø 1.0% 200Ø 1.0% PVC-SDR35 STC-300 T/C m - 250Ø 1.0% 2.9m STMMH - 200Ø CB #1 LEAD T/C 1.0%, CB #2 42.4m - 200Ø CB 1.0% R4.50m 3 LYT ISSUED FOR SPA ha L8 2 LYT ISSUED FOR 75% CLIENT REVIEW LYT ISSUED FOR 60% CLIENT REVIEW ISSUE BY DESCRIPTION DATE [YY-MM-DD) 34.2m - 200Ø 1.0% CB # ha L ha ha PROPOSED 6 STOREY SENIOR RESIDENCE BUILDING L4 F. F. ELEVATION = M ha ERIE STREET R1 L7 SANMH #1 T/C M/E 3.5 m x 9.0 m LOADING SPACE ha EX. SAM MH T/C L ha CB #3 L9 GENERAL NOTES DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED " I SSUED FOR CONSTRUCTION". VERIF Y CONFIGURATIONS & DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF A N Y E R R O R S, O M I S S I O N S O R D I S C R E P A N C I E S. DEVELOPMENT CONSULTANT: OAKVILLEOFFICE P: ; 206 Project Co-ordinator: Cristy Wilson E: cwilson@apiconsultants.net ARCHITECT 610 FORD DRIVE,SUITE 338 OAKVILLE, ON L6J 7W4 E: llsaplys@apiconsultants.net Project Contact: David Barnard E: dbarnard@apiconsultants.net P: CLIENT SUNRAY GROUP Consumers Road, Toronto, ON, M2J 4Z2 ENGINEER NORTH PROJECT NAME PROJECT ADDRESS DRAWING TITLE BY GAMA ENGINEERING INC Weston Road, Suite 35B, Vaughan, Ontario L4L 9P1 Project Contact: Wajid Mansuri E: wmansuri@bellnet.ca P: LYT PROJECT No. SCALE 1710 TRUE NORTH WELLINGTON SENIOR RESIDENCE BUILDING CHECKED 292WELINGTONST,ST.THOMAS,ON ISSUED FOR SHEET No. PROFESSIONAL CERTIFICATION PRE-DEVELOPMENT STORM DRAINAGE AREA PLAN WAM AS SHOWN SPA - 1ST SUBMISSION GP-4 SHEET REVISION 3.1 DRAWING LOCATION: \\GAMAENGINEERING\PUBLIC\GAMA PROJECTS\2017 PROJECTS\ WELLINGTON, ST THOMAS\AUTOCAD\WORKING\CIVIL\LAURA TU\JUN DRAWING FILENAME: 1710-CIVIL-MODEL-1 PLOT DATE: June 29, 2017

10 Appendix B STORM SEWER DESIGN SHEET AND STORM STRUCTURE TABLE

11 RUNOFF COEFFICIENT 'C' VALUES FLOW Q = C x A x I / 360 WHERE: Q = PEAK FLOW IN LITYRES PER SECOND (m³/s) DATE: THE FOLLOWING 'C' VALUES APPLAY WHEN DESIGNING STORM SEWERS: A = AREA IN HECTARES (Ha) DESIGNED BY: L.Y.T PARKS, OPEN SPACE 0 C = RUNOFF COEFFICIENT SINGLE FAMILY / SEMI DETACHED RETURN PERIOD = 5 YEARS TOWNHOUSE / ROWHOUSE Tc = 15 min APARTMENTS I - RAINFALL INTENSITY (mm/hr) COMMERCIAL, INDUSTRIAL t = Tc/60, hr i 29.6*t^ DENSELY BUILT, PAVED PROJECT NO LOCATION AREA SEWER DESIGN PROFILE AREA NO. STREET AREA RUNOFF A.C ACCUM. TC INTENSITY DESIGN Manning's PIPE SIZE SLOPE CAPACITY VELOCITY LENGTH TIME OF TIME IN DROP IN HEADLOSS DROP IN INVERT ELEVATION FROM TO COEFF. A.C. FLOW Q n Q FLOW SEWER SEWER MANHOLE U.S. D.S. MANHOLE MANHOLE (Ha) C (min.) (mm/hr) (cu.m/s) (mm) (%) (cu.m/s) (m/s) (m) (min.) (min.) (m) (m) (m) (m) (m) Partial C1, Partial L1-L3 Parking Lot & Landscaping CB1 STMH % Partial C1, L1-L3, L8 Partial C1, L9 Partial C1, L6, L7 Partial C1, Partial L1, L4, L5 STORM SEWER DESIGN SHEET CITY OF ST. THOMAS PROJECT NAME: ST. THOMAS RETIREMENT HOME (292 WELLINGTON ST.) Parking Lot & Landscaping CB2 STMH % Driveway, Sidewalk CB3 STMH % & Landscaping Storm Sewer STMH1 STC % Courtyard & Landscaping Driveway & CB4 STC % Landscaping Storm Sewer STC-300 STMH % R1 ROOF BLD STMH % Storm Sewer STMH2 Ex. 3000Ø % Ex. 3000Ø ± Notes: * No orifice is required to control the release rate for the post-development condition is greater than the pre-development. ** Inverts at City Sewer STMH2337 is based on City's street sevicing profile Drawing No. P (PH: ) dated March 1987.

12 STORM STRUCTURE TABLE MARKED SIZE, MM RIM ELEV., M INVERT ELEVATION, M DEPTH, M OPSD N. W. S. SE. E. NE. CB#1 600X CB#2 600X CB#3 600X CB#4 600X STMH# STMH# STC

13 Appendix C DETAIL SIZING OF THE STORMCEPTOR

14 Stormceptor Design Summary PCSWMM for Stormceptor Project Information Date 2017/4/8 Project Name St. Thomas Retirement Home Project Number 1710 Location Designer Information Company Contact Notes N/A Drainage Area 292 Wellington St., St. Thomas Gama Engineering Laura Tu Total Area (ha) 0.39 Imperviousness (%) 0.9 The Stormceptor System model STC 300 achieves the water quality objective removing 99% TSS for a OK-110 (sand only) particle size distribution and 87% runoff volume. Rainfall Name LONDON A State ON ID 4475 Years of Records 1960 to 2002 Latitude 43?2'N Longitude 81?9'W Water Quality Objective TSS Removal (%) 75 Runoff Volume (%) 0 Upstream Storage Storage Discharge (ha-m) (L/s) 0 0 Stormceptor Sizing Summary Stormceptor Model TSS Removal Runoff Volume % % STC STC STC STC STC STC STC STC STC STC STC STC Stormceptor Design Summary - 1/2

15 Particle Size Distribution Removing silt particles from runoff ensures that the majority of the pollutants, such as hydrocarbons and heavy metals that adhere to fine particles, are not discharged into our natural water courses. The table below lists the particle size distribution used to define the annual TSS removal. OK-110 (sand only) Particle Size Distribution Specific Settling Specific Settling Particle Size Distribution Gravity Velocity Gravity Velocity µm % m/s µm % m/s Stormceptor Design Notes Stormceptor performance estimates are based on simulations using PCSWMM for Stormceptor version 1.0 Design estimates listed are only representative of specific project requirements based on total suspended solids (TSS) removal. Only the STC 300 is adaptable to function with a catch basin inlet and/or inline pipes. Only the Stormceptor models STC 750 to STC 6000 may accommodate multiple inlet pipes. Inlet and outlet invert elevation differences are as follows: Inlet and Outlet Pipe Invert Elevations Differences Inlet Pipe Configuration STC 300 STC 750 to STC STC 9000 to 6000 STC Single inlet pipe 75 mm 25 mm 75 mm Multiple inlet pipes 75 mm 75 mm Only one inlet pipe. Design estimates are based on stable site conditions only, after construction is completed. Design estimates assume that the storm drain is not submerged during zero flows. For submerged applications, please contact your local Stormceptor representative. Design estimates may be modified for specific spills controls. Please contact your local Stormceptor representative for further assistance. For pricing inquiries or assistance, please contact Imbrium Systems Inc., Stormceptor Design Summary - 2/2

16 Appendix D SITE SERVICING PLAN AND SITE GRADING PLAN

17 WELLINGTON STREET EX. STM MH T/C S. INV ± 300X250 TEE & SLEEVE 250mmØ GATE VALVE & VALVE BOX ABANDON EX. VALVE & VALVE BOX FIRE HYDRANT AND 150Ø GATE VALVE & VALVE BOX, SEE W-03 FOR INSTALLATION FH 250Ø WM PVC-DR18 CLASS 150 CAP AND ABANDON EX. 100Ø WM CB #1 17.7m - 200Ø CB 1.0% STMMH #2 T/C m - 250Ø 2.0% 9.8m - 250Ø STM 14.2m - 250Ø 1.0% SITE VERIFY INVERT OR EX. 3000MM STM PDC VERTICAL RISER INSTALLATION SEE S %, PVC-SDR35 200Ø 1.0% PVC-SDR35 STC-300 T/C m STMMH - 200Ø CB #1 LEAD T/C 1.0%, CB #2 42.4m - 200Ø CB 1.0% 22.3m - 250Ø 1.0% R4.50m 3 LYT ISSUED FOR SPA LYT ISSUED FOR 75% CLIENT REVIEW LYT ISSUED FOR 60% CLIENT REVIEW m - 200Ø 1.0% CB #4 CAP AND ABANDON EX. 100Ø WM 250mmØ STM, INV , FROM ROOF DRAINAGE. SEE MECH. DWG. STM, INV , FROM FOUNDATION DRAIN. SEE ARCH. DWG. PROPOSED 6 STOREY SENIOR RESIDENCE BUILDING F. F. ELEVATION = M ERIE STREET 250mmØ FIRE LINE 100mmØ DOMESTIC LINE 2.1m-150Ø 1.0% INV SANMH #1 T/C N. INV SE. INV DCDA M/E M BP 15.7m-150Ø 2.0% 3.5 m x 9.0 m LOADING SPACE EX. SAM MH T/C NW. INV EX. E. INV ± CB #3 GENERAL NOTES: 1. VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. 2. DO NOT SCALE DRAWINGS. 3. REPORT ALL DISCOVERIES OF ERRORS, OMISSIONS OR DISCREPANCIES TO THE ARCHITECT OR DESIGN ENGINEER AS APPLICABLE. 4. USE ONLY LATEST REVISED DRAWINGS OR THOSE THAT ARE MARKED "ISSUED FOR CONSTRUCTION" 5. DESIGN AND CONSTRUCTION OF THIS PROJECT SHALL COMPLY WITH THE PROVINCIAL AND LOCAL BUILDING CODES LATEST EDITION. 6. ALL WORKS AND MATERIALS USED SHALL COMPLY AS REQUIRED BY THE O.B.C. LATEST EDITION. 7. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL RELEVANT DRAWINGS & SPECIFICATIONS. 8. ALL DIMENSIONS SHOWN ARE IN MILLIMETER. 9. EVERYTHING IS TO BE CONSIDERED NEW UNLESS NOTED "EXISTING" OTHERWISE. 10. INSTALL NEW PRODUCT PIPING, WIRING AND MONITORING SYSTEM ALL AS SHELL STANDARD SPECIFICATIONS AND LIQUID FUELS HANDLING CODE. GENERAL NOTES DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED " I SSUED FOR CONSTRUCTION". VERIF Y CONFIGURATIONS & DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF A N Y E R R O R S, O M I S S I O N S O R D I S C R E P A N C I E S. DEVELOPMENT CONSULTANT: OAKVILLEOFFICE P: ; 206 Project Co-ordinator: Cristy Wilson E: cwilson@apiconsultants.net ARCHITECT CLIENT SUNRAY GROUP Consumers Road, Toronto, ON, M2J 4Z2 NORTH PROJECT NAME PROJECT ADDRESS DRAWING TITLE BY ISSUE BY DESCRIPTION 610 FORD DRIVE,SUITE 338 OAKVILLE, ON L6J 7W4 E: llsaplys@apiconsultants.net Project Contact: David Barnard E: dbarnard@apiconsultants.net P: ENGINEER GAMA ENGINEERING INC Weston Road, Suite 35B, Vaughan, Ontario L4L 9P1 Project Contact: Wajid Mansuri E: wmansuri@bellnet.ca P: LYT PROJECT No. SCALE 1710 TRUE NORTH WELLINGTON SENIOR RESIDENCE BUILDING CHECKED AS SHOWN 292WELINGTONST,ST.THOMAS,ON ISSUED FOR SHEET No. PROFESSIONAL CERTIFICATION SITE SERVICING PLAN WAM SPA - 1ST SUBMISSION GP-6 DATE [YY-MM-DD) SHEET REVISION 3.1 DRAWING LOCATION: \\GAMAENGINEERING\PUBLIC\GAMA PROJECTS\2017 PROJECTS\ WELLINGTON, ST THOMAS\AUTOCAD\WORKING\CIVIL\LAURA TU\JUN DRAWING FILENAME: 1710-CIVIL-MODEL-1 PLOT DATE: June 29, 2017

18 WELLINGTON STREET EX. STM MH T/C BC(229.20) TC(229.35) 18M-NEW DEPRESS CURB, REFER TO OPSD BC(229.17) TC(229.20) + BC(229.20) TC(229.35) SAW CUT EX. SIDEWALK AND INSTALL OPSD CONC. SIDEWALK TO MATCH NEW DRIVEWAY. (229.35) + CONC. BARRIER CURB, SEE OPSD (229.52) + BC(229.50) TC(229.65) + B/C(229.50) T/C(229.65) STMMH #2 T/C BC(229.50) 1.0% TC(229.65) % 4.0% 1.3% CONC. BARRIER CURB, SEE OPSD B/C(229.50) T/C(229.65) + BC(229.35) TC(229.50) BC(229.40) + TC(229.55) (229.43) + + BC(229.50) 1.0% 1.0% 1.7% (229.21) + + BC(229.06) TC(229.21) TC(229.65) + HP(229.50) B/C(229.38) + T/C(229.53) B/C(229.36) + T/C(229.51) (229.39) + (229.42) + 4% CB #4 2.7% B/C(229.38) + T/C(229.53) + HP(229.50) (229.35) + B/C(229.35) + T/C(229.50) BC(229.36) + TC(229.51) BC(229.40) + TC(229.55) 1.0% 1.4% + HP(229.35) + (B/C T/C ) STC-300 T/C (229.34) + (229.45) 1.5% 10.5M-NEW DEPRESS CURB, REFER TO OPSD BC(229.50) + TC(229.65) + (229.50) + (229.42) + HP(229.39) + (229.50) + (229.25) + BC(229.03) TC(229.06) + (229.34) + (229.34) + BC(229.48) TC(229.63) + (B/C T/C ) + BC(229.36) TC(229.51) + (229.60) + (229.53) + BC(229.30) TC(229.45) + (229.11) FH + (229.39) + (229.53) + BC(228.98) TC(229.13) 1.0% 1.3% 1.0% + (229.60) + (229.63) 1% + CONC.BARRIER CURB, SEE OPSD CB #1 STMMH #1 T/C % 1.1% CB #2 + B/C(229.32) T/C(229.47) 1.3% + BC(229.46) TC(229.61) 1.3% + B/C(229.43) T/C(229.58) PROPOSED 6 STOREY SENIOR RESIDENCE BUILDING (229.64) + (229.60) + (229.20±) + SAW CUT EX. SIDEWALK AND INSTALL OPSD CONC. SIDEWALK TO MATCH NEW DRIVEWAY. 1:12 RAMP + (BC TC ) 2.0% F. F. ELEVATION = M + (229.58) 1.5% 1.0% + (229.58) + (229.56) + (BC TC ) + BC(229.34) TC(229.49) (229.50) + ERIE STREET CONC.BARRIER CURB, SEE OPSD (229.58) 1.5% + (229.68) + (229.60) + (229.23±) CONC. RAMP TO MATCH EX. SIDEWALK + (BC TC ) + BC(229.46) + (229.32) TC(229.61) (229.58) + SANMH #1 T/C (229.62) + (229.60) + (229.57) + (229.49) + (229.63) + BC(229.45) + (229.57) SAW CUT EX. SIDEWALK AND INSTALL OPSD CONC. SIDEWALK TO MATCH NEW DRIVEWAY. M/E 1% + (229.57) 4% (229.48) + (229.47) + + (229.41) TC(229.60) 1% + BC(229.38) 1.9% TC(229.53) 4% + (229.50) (229.43) + + BC(229.22) + (BC TC ) 3.5 m x 9.0 m LOADING SPACE % + (229.34) 1. + BC(229.43) 1% + BC(229.47) 1% TC(229.37) 2.6% 4% EX. SAM MH T/C % 2.7% TC(229.58) TC(229.62) 1% + BC(229.52) TC(229.67) 1% 1% + HP(229.52) R4.50m + BC(229.38) CONC.BARRIER CURB, SEE OPSD BC(229.52) + TC(229.67) (229.43) + + BC(229.24) TC(229.27) 11M-NEW DEPRESS CURB, REFER TO OPSD TC(229.53) CB #3 CONC.BARRIER CURB, SEE OPSD (229.59) + BC(229.26) TC(229.41) 1. CITY OF ST. THOMAS GEODETIC MONUMENT No LOCATION: TABLET SET IN CONCRETE ON THE SOUTH WEST CORNER OF EDWARD STREET AND FIRST AVENUE, 4.75m WEST OF CONCRETE SIDEWALK AND 9.45m NORTHWEST OF MANHOLE. ELEVATION = METERS. GENERAL NOTES: 1. VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. 2. DO NOT SCALE DRAWINGS. 3. REPORT ALL DISCOVERIES OF ERRORS, OMISSIONS OR DISCREPANCIES TO THE ARCHITECT OR DESIGN ENGINEER AS APPLICABLE. 4. USE ONLY LATEST REVISED DRAWINGS OR THOSE THAT ARE MARKED "ISSUED FOR CONSTRUCTION" 5. DESIGN AND CONSTRUCTION OF THIS PROJECT SHALL COMPLY WITH THE PROVINCIAL AND LOCAL BUILDING CODES LATEST EDITION. 6. ALL WORKS AND MATERIALS USED SHALL COMPLY AS REQUIRED BY THE O.B.C. LATEST EDITION. 7. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL RELEVANT DRAWINGS & SPECIFICATIONS. 8. ALL DIMENSIONS SHOWN ARE IN MILLIMETER. 9. EVERYTHING IS TO BE CONSIDERED NEW UNLESS NOTED "EXISTING" OTHERWISE. 10. INSTALL NEW PRODUCT PIPING, WIRING AND MONITORING SYSTEM ALL AS SHELL STANDARD SPECIFICATIONS AND LIQUID FUELS HANDLING CODE.T/W GENERAL NOTES DO NOT SCALE DRAWINGS. USE ONLY DRAWINGS MARKED " I SSUED FOR CONSTRUCTION". VERIF Y CONFIGURATIONS & DIMENSIONS ON SITE BEFORE BEGINNING WORK. NOTIFY ARCHITECT IMMEDIATELY OF A N Y E R R O R S, O M I S S I O N S O R D I S C R E P A N C I E S. DEVELOPMENT CONSULTANT: OAKVILLEOFFICE P: ; 206 Project Co-ordinator: Cristy Wilson E: cwilson@apiconsultants.net ARCHITECT CLIENT SUNRAY GROUP Consumers Road, Toronto, ON, M2J 4Z2 NORTH PROJECT NAME PROJECT ADDRESS DRAWING TITLE BY PROJECT No. SCALE 3 LYT ISSUED FOR SPA LYT ISSUED FOR 75% CLIENT REVIEW LYT ISSUED FOR 60% CLIENT REVIEW ISSUE BY DESCRIPTION 610 FORD DRIVE,SUITE 338 OAKVILLE, ON L6J 7W4 E: llsaplys@apiconsultants.net Project Contact: David Barnard E: dbarnard@apiconsultants.net P: ENGINEER GAMA ENGINEERING INC Weston Road, Suite 35B, Vaughan, Ontario L4L 9P1 Project Contact: Wajid Mansuri E: wmansuri@bellnet.ca P: LYT 1710 TRUE NORTH WELLINGTON SENIOR RESIDENCE BUILDING CHECKED WAM AS SHOWN 292WELINGTONST,ST.THOMAS,ON ISSUED FOR SHEET No. PROFESSIONAL CERTIFICATION SITE GRADING PLAN SPA - 1ST SUBMISSION GP-7 DATE [YY-MM-DD) SHEET REVISION 3.1 DRAWING LOCATION: \\GAMAENGINEERING\PUBLIC\GAMA PROJECTS\2017 PROJECTS\ WELLINGTON, ST THOMAS\AUTOCAD\WORKING\CIVIL\LAURA TU\JUN DRAWING FILENAME: 1710-CIVIL-MODEL-1 PLOT DATE: June 29, 2017

Please remove and replace the entire Table of Contents, Section A to Section J and all Appendices.

Please remove and replace the entire Table of Contents, Section A to Section J and all Appendices. Please remove and replace the entire Table of Contents, Section A to Section J and all Appendices. The following is a list of changes to the Design Criteria: 1. A2.01 General Note 4 Utility Coordination

More information

City of Massillon Site Plan Checklist

City of Massillon Site Plan Checklist City of Massillon Site Plan Checklist The following information MUST be included with all Site Plans submitted for review and processing in order to constitute a complete Site Plan Package. Incomplete

More information

APPENDIX 4. Checklists. Township of King Design Criteria and Standard Detail Drawings

APPENDIX 4. Checklists. Township of King Design Criteria and Standard Detail Drawings APPENDIX 4 Checklists Township of King Design Criteria and Standard Detail Drawings Township of King Design Criteria and Standard Detail Drawings APPENDIX 4 CHECKLISTS Engineering Submissions : The following

More information

Town of Westlake Construction Plans Review Checklist

Town of Westlake Construction Plans Review Checklist CONSTRUCTION PLANS CONTENTS All Drawings 24 x 36 Cover Sheet Final Plat Site Plan Demolition Plan Utility Plan Drainage Area Map and Calculations Paving Plan & Profile Sheets Storm Drain Plan & Profile

More information

1 MUNICIPAL INFRASTRUCTURE

1 MUNICIPAL INFRASTRUCTURE Engineering Design Criteria & Standard Drawings Page 5 1 MUNICIPAL INFRASTRUCTURE 1.1 Drawing & Submission Requirements 1.1.1 General This section discusses the requirements for the submission of engineering

More information

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS March 2004 STANDARD DRAWINGS Partners With The Environment March 2004 FORWARD The March 2004 version of the City of Vaughan Design Standard

More information

CITY OF MUSKEGO DRAFTING STANDARDS

CITY OF MUSKEGO DRAFTING STANDARDS CITY OF MUSKEGO DRAFTING STANDARDS GENERAL - These standards apply to all plans. 1. Plans must be prepared on sheets measuring 36 inch across and 22 inch to 24 inch high unless otherwise specified under

More information

TOWN of LAKESHORE SITE PLAN CHECKLIST

TOWN of LAKESHORE SITE PLAN CHECKLIST TOWN of LAKESHORE SITE PLAN CHECKLIST Last Revised December 17, 2009 Project Name: Project Location: Date Submitted: Name Phone Number E-mail Address Owner: Contractor/ Engineer: ( ) ( ) Applicant: ( )

More information

MILL HILL ARTS VILLAGE

MILL HILL ARTS VILLAGE OWNER CIVIL ENGINEER MACON-BIBB URBAN DEVELOPMENT AUTHORITY ALEX MORRISON, EXECUTIVE DIRECTOR 200 CHERRY STREET, SUITE 300 MACON, GA 31201 OFFICE PHONE : (478) 803-2402 TRIPLE POINT ENGINEERING DAN WALLACE,

More information

SCHEDULE 10 ENGINEERING DRAWING SUBMISSION

SCHEDULE 10 ENGINEERING DRAWING SUBMISSION SCHEDULE 10 ENGINEERING DRAWING SUBMISSION Subdivision, Development and Servicing Bylaw No. 1535 10. ENGINEERING DRAWING SUBMISSIONS TABLE OF CONTENTS 1.0 General 3 1.1. Introduction 3 1.2. General Requirements

More information

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360) CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA 98501 (360) 754-4180 Email: cdd@ci.tumwater.wa.us WATER-SEWER-STREET-STORM (IN CITY) Submittal Checklist TUM - RCVD BY DATE STAMP APPLICANT INFORMATION

More information

Council Policy Engineering Drawing Submission Requirements

Council Policy Engineering Drawing Submission Requirements POLICY 265 City of Kelowna 1435 Water Street Kelowna, BC V1Y 1J4 250 469-8500 kelowna.ca Council Policy Engineering Drawing Submission Requirements APPROVED June 4, 2001 RESOLUTION: R375/10/04/26 REPLACING:

More information

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY MSD M etr o p olitan S e w e r Di s t r ict STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY 40203-1911 STANDARD DRAWINGS DIVISION

More information

Authorized Agent: City of Manassas Check List Attached: Contact: Address: Phone Number: Fax Number: Developer s Name: Phone Number:

Authorized Agent: City of Manassas Check List Attached: Contact:   Address: Phone Number: Fax Number: Developer s Name: Phone Number: CITY OF MANASSAS DEPARTMENT OF COMMUNITY DEVELOPMENT DEVELOPMENT SERVICES DIVISION 9027 Center Street Room 201 Manassas, Virginia, 20110 Phone: 703-257-8278 Fax: 703-257-5831 Application Date: APPLICANT

More information

STANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN

STANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D ASPHALT 20 GUTTER LINE CONCRETE CURB FINISHED GRADE PRECAST GRADE RINGS, 2 50 100 MAX PRECAST CB LID GROUT ALL AROUND CB LEAD, INSIDE & OUTSIDE OF

More information

SUPPLEMENTARY STANDARD DETAIL DRAWINGS

SUPPLEMENTARY STANDARD DETAIL DRAWINGS CITY OF MAPLE RIDGE DESIGN AND CONSTRUCTION DOCUMENTS Part 4 SUPPLEMENTARY STANDARD DETAIL DRAWINGS September 2015 Updated: October 2015 THIS PAGE INTENTIONALLY LEFT BLANK City of Maple Ridge Supplementary

More information

CITY OF APACHE JUNCTION DEVELOPMENT SERVICES CIVIL ENGINEERING PLAN REVIEW CHECKLIST PROJECT: LOCATION:

CITY OF APACHE JUNCTION DEVELOPMENT SERVICES CIVIL ENGINEERING PLAN REVIEW CHECKLIST PROJECT: LOCATION: CITY OF APACHE JUNCTION DEVELOPMENT SERVICES CIVIL ENGINEERING PLAN REVIEW CHECKLIST PROJECT: LOCATION: LOG NO.: LEGEND REVIEW REVIEWED BY DATE / - Requirement satisfied 1 O Requirement not satisfied 2?

More information

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX 407-1 - MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX 407-1.1 GENERAL Tender Items Specifications Standard Drawings 407-1.1.1 Frame and Grate Selection 407-1.1.2 Selection of Structure

More information

ACSA PLAN REVIEW CHECKLIST (Guideline Only) (4) Standard water and sewer general plan notes (attached).

ACSA PLAN REVIEW CHECKLIST (Guideline Only) (4) Standard water and sewer general plan notes (attached). ACSA PLAN REVIEW CHECKLIST (Guideline Only) Revised: December 3, 2015 General (1) Proper Title (2) Vicinity map on first sheet. (3) Date and latest plan revision. (4) Standard water and sewer general plan

More information

CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST

CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST Tract Number and Subdivision Name: Engineering Firm: Contact Person: Address: City: State: Zip: Phone No. Fax No. Assessor s Parcel Number(s) Tentative

More information

SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS

SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS 101 General 102 Submittal Requirements A. Initial Submittal B. Second Submittal 103 Plan Requirements A. Subdivisions B. Site Plans 104 Approval of

More information

7000 Fifteen Mile Road Sterling Heights, Michigan

7000 Fifteen Mile Road Sterling Heights, Michigan 7000 Fifteen Mile Road Sterling Heights, Michigan Industrial Building With Excess Land and Rail Access As exclusive agents, we are pleased to offer the following property for lease: 128,648 Sq. Ft. Completely

More information

Porter County Plan Commission

Porter County Plan Commission Plan Type: Development Plan Administrative DRC PC Primary Plan Administrative DRC PC Secondary Plat/Replat Administrative DRC PC PUD Conceptual Detailed Final Project Information Project Name: Developer

More information

Survey Data and TOPO Checklist

Survey Data and TOPO Checklist Checklists Survey Data and TOPO Preliminary Plan Field Review Plans o Field Review Erosion Control Right-of-Way and Utility Meeting Plans Final Plan Field Review Plans Methods of Plan Markups Plan-in-Hand

More information

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1 UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1 ENGINEERING STANDARDS FOR UTILITY AND STREET CONSTRUCTION PLANS MARCH 2014 CONSTRUCTION PLAN SHEET FORMAT REQUIREMENTS REPRODUCIBLE MYLAR 1.

More information

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION 4.0. INTRODUCTION PART 4 STANDARD DRAWINGS FOR CONSTRUCTION In this document, Ivins City adopts the most recent edition (currently 2007), including all amendments, of the APWA Utah Chapter s Manual of

More information

CHAPTER 11. Plan Standards

CHAPTER 11. Plan Standards CHAPTER 11 Plan Standards A. Introduction The city requires uniform public improvement plans for ease of record keeping and understanding. The following standards govern most plan submittals to the city.

More information

SECTION 9.00 AS-BUILT DRAWING REQUIREMENTS SUB-INDEX

SECTION 9.00 AS-BUILT DRAWING REQUIREMENTS SUB-INDEX SECTION 9.00 AS-BUILT DRAWING REQUIREMENTS SUB-INDEX 9.00 AS-BUILT DRAWING REQUIREMENTS 9.01 As-Built Check List 1 Supp 1 2016 Supp # 2 Aug. 2017 AS-BUILT DRAWING REQUIREMENTS As-Built Review Fee is $200.00

More information

B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST

B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST YES* GENERAL SUBMISSION ITEMS Does the submission include: 1. Thirteen (13) copies of completed Application Form? 2. Thirteen (13) copies of the Preliminary

More information

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STORM DRAIN IMPROVEMENT PLAN REVIEW CHECKLIST

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STORM DRAIN IMPROVEMENT PLAN REVIEW CHECKLIST CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil ing Division STORM DRAIN IMPROVEMENT PLAN REVIEW CHECKLIST The following checklist consists of the minimum requirements for preparation

More information

City of Regina Standard Construction Specification SECTION 2999 LISTING OF ROADWAY STANDARD DRAWINGS

City of Regina Standard Construction Specification SECTION 2999 LISTING OF ROADWAY STANDARD DRAWINGS City of Regina Standard Construction Specification SECTION 2999 LISTING OF ROADWAY STANDARD DRAWINGS R-1 Alternate Pavement Structures July/10 R-2 Typical Cross Sections for Asphaltic Concrete Pavements

More information

Essential Skills: Reading and Interpreting Maps and Plans

Essential Skills: Reading and Interpreting Maps and Plans Essential Skills: Reading and Interpreting Maps and Plans Prepared for: NEW YORK STATE PLANNING FEDERATION April 14, 2015 Prepared by: BME ASSOCIATES Peter G. Vars, P.E. Stages of Plan Review Concept /

More information

Government Of Newfoundland & Labrador Municipal Water, Sewer And Roads Master Construction Specifications

Government Of Newfoundland & Labrador Municipal Water, Sewer And Roads Master Construction Specifications PAGE NO. : 1 OF 4 Revision Date: July 2009 STANDARD DRAWINGS TABLE OF CONTENTS DRAWING # DESCRIPTION 0030............ Work Adjacent to Roadway 0040............ Work at the Edge of Roadway 0050............

More information

TOWN OF AJAX DESIGN CRITERIA SECTION A GENERAL INFORMATION

TOWN OF AJAX DESIGN CRITERIA SECTION A GENERAL INFORMATION TOWN OF AJAX DESIGN CRITERIA SECTION A GENERAL INFORMATION A1 SECTION A - GENERAL INFORMATION REVISED JUNE 2016 A 1.00 A 1.01 INTRODUCTION THE TOWN OF AJAX The Town of Ajax is part of a two tier municipal

More information

STANDARD BID ITEM NUMBERS

STANDARD BID ITEM NUMBERS 10701 TRAFFIC CONTROL LUMP SUM 10702 Traffic Control for Storm Sewer Installation LUMP SUM 10703 Traffic Control for Water Main Installation LUMP SUM 10704 Traffic Control for Sanitary Sewer Installation

More information

List of Figures. List of Forms

List of Figures. List of Forms City of Columbia Engineering Regulations PART 1: SUBMISSION OF PLANS Table of Contents Paragraph Description Page No. 1.1 General 1-1 1.2 Engineer s Report 1-1 1.3 Plans 1-3 1.4 Revisions to Approved Plan

More information

September 21, Mannik Smith Group 1771 North Dixie Highway Monroe, Michigan RE: LA Fitness City File No.: CVLP

September 21, Mannik Smith Group 1771 North Dixie Highway Monroe, Michigan RE: LA Fitness City File No.: CVLP CITY OF ANN ARBOR, MICHIGAN Public Services Area / Engineering 301 E. Huron Street, P.O. Box 8647 Ann Arbor, Michigan 48107 Phone (734) 794-6410 Fax (734) 994-1744 Web: www.a2gov.org Printed on recycled

More information

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards. PLAN REQUIREMENTS The plans for street design shall conform to the requirements of Sections 3 and 4. The following requirements shall also be shown on the plans where applicable. Road and Storm Plans:

More information

STORM M ANHOLE FOR 42" PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30"MAX 3 OR 3.5 PRECAST ECCENTIC CONC

STORM M ANHOLE FOR 42 PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30MAX 3 OR 3.5 PRECAST ECCENTIC CONC 01-APR-2015 13:33 = I:\MSV8i\Plotting\piblack.ptb V:\201001\\C\8x11_Howell_Det\stm_det01_8x11_st01.dgn TIME = MIN 3 CRSES MAX 5 CRSES 3 OR 3.5 PRECAST ECCENTIC CONC ID PIPE GRADE A CONC FILL 4" 8" 2-0"SUMP

More information

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil ing Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST The following checklist consists of the minimum requirements for preparation

More information

Miscellaneous. Demolition

Miscellaneous. Demolition Public Improvements Miscellaneous 1 Mobilization L.S. ** 2 Clearing and Grubbing L.S. *** 3 Structural Concrete Incl. Reinforcing C.Y. $1,325.00 4 6" PVC Sleeves L.F. $26.00 Demolition 5 Remove Asphalt

More information

Anne Arundel County Dept. of Inspections and Permits Storm Drain Checklist

Anne Arundel County Dept. of Inspections and Permits Storm Drain Checklist Project Name Project Number Engineer Plans are to be designed based on the standards set forth in the Anne Arundel County Design Manual Standards and Specifications, and all other manuals as stipulated

More information

Record Drawing Standards for Projects Version 2.1

Record Drawing Standards for Projects Version 2.1 for Projects Version 2.1 Updated September 21, 2016 Department: Spatial Data Group Engineering & Maintenance 1. INTRODUCTION... 1 2. GENERAL STANDARDS... 1 2.1 Drawing Standards... 1 2.2 Digital Submission

More information

CONSTRUCTION CERTIFICATION PACKAGE

CONSTRUCTION CERTIFICATION PACKAGE Purpose: The intent of this Construction Certification Package is to ensure that acceptable documentation is maintained during the construction of stormwater management practices (SMPs). For general information

More information

MINOR SUBDIVISION. [ ] [ ] [ ] [ ] B. Dimensions, bearings and curve data for all property lines and easements.

MINOR SUBDIVISION. [ ] [ ] [ ] [ ] B. Dimensions, bearings and curve data for all property lines and easements. MINOR SUBDIVISION 190-69. Minor subdivisions. In addition to the requirements indicated in 190-67 (SEE BELOW), the information below shall be shown on the plans for all minor subdivision applications.

More information

Clarifications in italics added July 2018

Clarifications in italics added July 2018 SECTION 10000 RECORD DRAWING CHECKLIST Clarifications in italics added July 2018 All entities who construct public infrastructure, private streets, private storm drain collection systems and travel lanes,

More information

City of Regina Standard Construction Specifications SECTION LIST OF SEWER STANDARD DRAWINGS

City of Regina Standard Construction Specifications SECTION LIST OF SEWER STANDARD DRAWINGS City of Regina Standard Construction Specifications SECTION 14999 LIST OF SEWER STANDARD DRAWINGS S-1 No Drawing Feb/10 S-2 Precast Manhole 1050mm Dia. July/10 S-2B Precast Manhole 1200mm Dia. Jan/17 S-3

More information

PRECISE GRADING PLAN CHECKLIST

PRECISE GRADING PLAN CHECKLIST PRECISE GRADING PLAN CHECKLIST PUBLIC WORKS DEPARTMENT / ENGINEERING DIVISION 8130 Allison Avenue, La Mesa, CA 91942 Phone: 619. 667.1166 Fax: 619. 667.1380 Grading plans shall address both rough grading

More information

APPENDIX D: DRAWING SUBMISSION STANDARDS

APPENDIX D: DRAWING SUBMISSION STANDARDS 1.0 FIRST SUBMISSION CONCEPTUAL DESIGN Once the Developer has obtained approval for a Development Application where Park or Open Space improvements are required, a detailed Park or Open Space submission

More information

WATER STRUCTURE LEGAL & SURVEY TOPOGRAPHY/GRADING LANDSCAPE/VEGETATION

WATER STRUCTURE LEGAL & SURVEY TOPOGRAPHY/GRADING LANDSCAPE/VEGETATION REVISION IDENTIFIER DETAIL LABEL CALLOUT LABEL 1 SHEET ABANDONED ASBESTOS CEMENT BALK OF WALK BEGINNING OF CURVE BENCH MARK BUILDING CAPACITY CAST IRON CATCH BASIN CATCH BASIN MANHOLE CENTER LINE CERTIFICATE

More information

Survey Requirements. Design Guidelines and Standards. June Office of the University Architect

Survey Requirements. Design Guidelines and Standards. June Office of the University Architect Design Guidelines and Standards Survey Requirements June 2004 Office of the University Architect Construction Management P.O. Box 210181 Cincinnati, Ohio 45221-0181 Table of Contents Survey Requirements

More information

Guidelines and Checklist For SAWS Sanitary Sewer. Developmental Engineering Division

Guidelines and Checklist For SAWS Sanitary Sewer. Developmental Engineering Division Guidelines and Checklist For SAWS Sanitary Sewer Developmental Engineering Division INITIAL CONSIDERATIONS UTILITY SERVICE AGREEMENT Utility Service Agreement A Utility Service Agreement (USA) will be

More information

CHECKLIST PRELIMINARY SUBDIVISION AND PRELIMINARY SITE PLAN

CHECKLIST PRELIMINARY SUBDIVISION AND PRELIMINARY SITE PLAN N/A Waiver (1) Four (4) copies of application form. (2) Fifteen (15) copies of plan (3) Subdivision/site plan application fee & professional review escrow deposit (4) Variance application fee & professional

More information

SEWER CORRECTION SHEET

SEWER CORRECTION SHEET Engineering Services Division 23920 Valencia Boulevard, Suite 300 Santa Clarita, California 91355 (661) 255-4942 SEWER CORRECTION SHEET MC# Master Case No. Assessor s Parcel No. Tract / Parcel No. / Address

More information

MINIMUM C/L RADII OF CURVATURE OF LOCAL ROADS IN SUBDIVISIONS

MINIMUM C/L RADII OF CURVATURE OF LOCAL ROADS IN SUBDIVISIONS 75m 70m 65m 60m DEFLECTION ANGLE C/L RADII OF CURVATURE 55m 50m 45m 40m 35m 30m 25m 20m 15m 90 80 70 60 50 40 30 20 10 0 DEFLECTION ANGLE - MINIMUM C/L RADII OF CURVATURE OF LOCAL ROADS IN SUBDIVISIONS

More information

PUBLIC WORKS DEPARTMENT. File: E-2000 July 11, Town of Whitby Design Criteria and Engineering Standard Drawing Revisions

PUBLIC WORKS DEPARTMENT. File: E-2000 July 11, Town of Whitby Design Criteria and Engineering Standard Drawing Revisions PUBLIC WORKS DEPARTMENT File: E-2000 July 11, 2011 To: All Manual Holders and Engineering Standard Drawing Revisions Please find attached a list of the revisions to the and the Engineering Standard Drawings.

More information

Type A. BWSC CAD Standards for Site Plans (Design and As-Built) Format. Scale. Fonts, Linetypes, Shapes

Type A. BWSC CAD Standards for Site Plans (Design and As-Built) Format. Scale. Fonts, Linetypes, Shapes BWSC CAD Standards for Site Plans (Design and As-Built) Type A The following CAD standards are for Type A application and involve no work in Public Street, except for connection(s) to the Boston Water

More information

Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D

Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (14-02) MANUAL: Standard

More information

Oil-Water Separator Design Checklist

Oil-Water Separator Design Checklist CHECKLIST C3 Revised 5/2/2016 Oil-Water Separator Design Checklist DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling private oil-water

More information

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual. MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Technical Support Design Services Section TRANSMITTAL LETTER NO. (0-03) MANUAL: Standard Plates DATED: September

More information

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS 9. STANDARD DETAILS SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS j:\clerical\royse city\1-4086 general services\168-tech const standards review\tcss manual\2018 tcss manual\sec-9a

More information

DEVELOPMENT CONSULTANT MAJOR DRAINAGE AREA PUBLIC WORKS AND ENGINEERING DEPARTMENT STORM DRAINAGE DESIGN CHART FOR CIRCULAR DRAINS FLOWING FULL SHEET

DEVELOPMENT CONSULTANT MAJOR DRAINAGE AREA PUBLIC WORKS AND ENGINEERING DEPARTMENT STORM DRAINAGE DESIGN CHART FOR CIRCULAR DRAINS FLOWING FULL SHEET DEVELOPMENT CONSULTANT MAJOR DRAINAGE AREA PUBLIC WORKS AND ENGINEERING DEPARTMENT STORM DRAINAGE DESIGN CHART FOR CIRCULAR DRAINS FLOWING FULL SHEET No. OF DATE DESIGNED BY CHECKED BY LOCATION FROM TO

More information

MAJOR GRADING PLAN CHECKLIST

MAJOR GRADING PLAN CHECKLIST MAJOR GRADING PLAN CHECKLIST PUBLIC WORKS DEPARTMENT / ENGINEERING DIVISION 8130 Allison Avenue, La Mesa, CA 91942 Phone: (619) 667-1166 Fax: (619) 667-1380 Grading plans shall address both rough grading

More information

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED:

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED: ARKANSAS DEPARTMENT OF TRANSPORTATION CA0801 HWY. 110 - CLINTON (WIDENING) (S) FEDERAL AID PROJECT ACNHPP-0071(31) THE PURPOSE OF THIS PROJECT IS TO WIDEN HIGHWAY 65 IN VAN BUREN COUNTY. THIS PROJECT CONSISTS

More information

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST Project Name Checked By Date Designer Check List marks to be

More information

SUBDIVISION APPLICATION FOR DRT SUBMITTAL PUBLIC WORKS DEPARTMENT

SUBDIVISION APPLICATION FOR DRT SUBMITTAL PUBLIC WORKS DEPARTMENT Case #: SUBDIVISION APPLICATION FOR DRT SUBMITTAL PUBLIC WORKS DEPARTMENT 171 North Ross Street, Suite 200 Auburn, AL 36830 (334) 501-3000 ~ Fax: (334) 501-7294 Applicant Name: Mailing Address: Email Address:

More information

Application for Site Plan Review

Application for Site Plan Review Application for Site Plan Review 3275 Central Blvd., Hudsonville, Michigan 49426-1450, 616.669.0200 fax 616.669.2330 It is STRONGLY recommended that any application that must go before the Planning Commission

More information

1.1 GENERAL RECORD DRAWING REQUIREMENTS

1.1 GENERAL RECORD DRAWING REQUIREMENTS Page 1 of 5 VILLAGE OF ROMEOVILLE RECORD DRAWINGS CHECKLIST PART I GENERAL Record drawings are required to provide a means of schematic verification that the intent of the approved engineering design has

More information

PARKING IMPROVEMENT AIRPORT CAMPUS AMENDED SITE PLAN APPROVAL DRAWINGS 113 KING STREET TOWN OF NORTH CASTLE, NEW YORK AIRPORT CAMPUS I-V LLC

PARKING IMPROVEMENT AIRPORT CAMPUS AMENDED SITE PLAN APPROVAL DRAWINGS 113 KING STREET TOWN OF NORTH CASTLE, NEW YORK AIRPORT CAMPUS I-V LLC AMENDED SITE PLAN APPROVAL DRAWINGS PARKING IMPROVEMENT AIRPORT CAMPUS CLIENT: AIRPORT CAMPUS I-V LLC 113 KING STREET TOWN OF NORTH CASTLE, NEW YORK JMC DRAWINGS SITE PLANNER, CIVIL ENGINEER, SURVEYOR

More information

Engineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings

Engineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings Engineering and Construction Services Division Construction Drawings for Sewers and Watermains Revision No. 8 April All T drawings New title block for each drawing is now standardized. Revision numbers

More information

1. Denver Water is not the provider. [C1 Cover] Baseline Response: Revised to show Thornton Water Department as the provider.

1. Denver Water is not the provider. [C1 Cover] Baseline Response: Revised to show Thornton Water Department as the provider. Nate Hatleback Project Manager City of Thornton 303 538 7694 Nate.Hatleback@cityofthornton.net Re: Topgolf Review The City of Thornton has provided comments regarding several submittals on June 14 th,

More information

PLANNING AND DEVELOPMENT

PLANNING AND DEVELOPMENT OVERVIEW Effective January 1, 1992 all applications for multi-family residential and all non-residential building permits require site plan approval before permit issuance. All new developments and existing

More information

3. DESIGN SPECIFICATIONS

3. DESIGN SPECIFICATIONS Schedule H to Bylaw 7452, Subdivision Bylaw Page 10 3. DESIGN SPECIFICATIONS 3.1 General 3.1.1 The Design Specifications apply to the design of sanitary sewers, storm drains, waterworks, roadways, and

More information

Date Requested, 200_ Work Order No. Funding source Name of project Project limits: Purpose of the project

Date Requested, 200_ Work Order No. Funding source Name of project Project limits: Purpose of the project Bureau of Engineering SURVEY DIVISION REQUEST FOR TOPOGRAPHIC SURVEY Date Requested, 200_ Work Order No. Funding source Name of project Project limits: Purpose of the project Caltrans involvement (must

More information

REQUIREMENTS. for ENGINEERING SERVICES PUBLIC CONSTRUCTION PROJECTS

REQUIREMENTS. for ENGINEERING SERVICES PUBLIC CONSTRUCTION PROJECTS REQUIREMENTS for ENGINEERING SERVICES on PUBLIC CONSTRUCTION PROJECTS April, 2007 David W. Johnson Senior Engineer Design & Construction Requirements for Engineering Services on Public Construction Projects

More information

Immediately following the Committee of the Whole meeting Mukwonago Municipal Building/Board Room, 440 River Crest Court

Immediately following the Committee of the Whole meeting Mukwonago Municipal Building/Board Room, 440 River Crest Court Dated 06-29-17 SPECIAL VILLAGE BOARD MEETING Notice of Meeting and Agenda Wednesday, July 5, 2017 Time: Place: Immediately following the Committee of the Whole meeting Mukwonago Municipal Building/Board

More information

PRELIMINARY PLAT CHECK LIST

PRELIMINARY PLAT CHECK LIST Name of Proposed Subdivision: The following items must be included with the initial submittal of a Preliminary Plat: Application, filled out completely Project Narrative Pre-application Conference Report

More information

Standard Plate 7036 is discontinued. It is replaced by Standard Plan Pedestrian Curb Ramp Details.

Standard Plate 7036 is discontinued. It is replaced by Standard Plan Pedestrian Curb Ramp Details. DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management & Technical Support, Design Support Section TRANSMITTAL LETTER NO. (12-02) MANUAL: Standard Plates DATED: May 11, 2012 SUBJECT: Standard

More information

City of Beaumont. Public Works Engineering. Street Improvement Plan Checklist REV 4/18/16

City of Beaumont. Public Works Engineering. Street Improvement Plan Checklist REV 4/18/16 City of Beaumont Public Works Engineering Project Name: TR: Project No.: Date: Street Improvement Plan Checklist Chk A. All Sheets 1. 24" x 36" 2. Signed by the engineer-of-work 3. Marked with the contact

More information

10010 RECORD DRAWING INFORMATION

10010 RECORD DRAWING INFORMATION SECTION 10000 RECORD DRAWING CHECK LIST All entities who construct public infrastructure, private streets, private storm drain collection systems and travel lanes, shall submit to the Town of Cary Engineering

More information

CHECKLIST 9-O. 24. Area of project in square feet and acres? C-1 d

CHECKLIST 9-O. 24. Area of project in square feet and acres? C-1 d Development Name: Submitted by: Highlands County Engineering Department Improvement Plan Checklist Date Received: Due Date: Y N E N / S O A Permits/Approvals 1. Copy of water management district permit

More information

SUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends)

SUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends) MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (14-01) MANUAL: Standard

More information

MINIMUM DRAWING REQUIREMENTS FOR WATER AND SEWER LINE PROJECTS

MINIMUM DRAWING REQUIREMENTS FOR WATER AND SEWER LINE PROJECTS Public Works Department Water & Wastewater Services WATER & WASTEWATER ENGINEERING DIVISION 2555 West Copans Road Pompano Beach, Florida 33369 954-831-0745 FAX 954-831-0798/0925 MINIMUM DRAWING REQUIREMENTS

More information

WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL

WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL This summary is not all inclusive of the requirements set forth by the York County Planning & Development Services, York County

More information

STORM SEWER SCHEDULE STRUCTURES ALIGNMENT CODES: 'CW'= COMANCHE WAY PIPES BURNING WOOD, COMANCHE, 4TH SHEET NO. UTIL W RESURF ASSESSMENT DISTRICT-2015 U-3 PROJECT NO. 53W1930 COMANCHE WAY STORM SEWER SCHEDULE

More information

VARIANCE APPLICATION (NO SITE PLAN OR SUBDIVISION)

VARIANCE APPLICATION (NO SITE PLAN OR SUBDIVISION) VARIANCE APPLICATION (NO SITE PLAN OR SUBDIVISION) 190-66. General procedure for completeness review. A. In order to be determined complete for review by the Board, all of the required information must

More information

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD. Q:\VillaPark_IL\11283000 Astor-Myrtle Sewer Separation Preliminary Design\D.4 CAD\Sheets\North\1. Cover.dwg INDEX OF SHEETS 1 COVER 2 GENERAL NOTES 3 SUMMARY OF QUANTITIES 4 ALIGNMENT 5-9 DRAINAGE AND

More information

VICINITY MAP LOCATION MAP GRAPHIC SCALES

VICINITY MAP LOCATION MAP GRAPHIC SCALES VICINITY MAP LOCATION MAP GI-01 LEGEND TABLE OF CONTENTS CONSTRUCTION SEQUENCE NOTES GENERAL NOTES SEDIMENTATION & EROSION CONTROL ABBREVIATIONS GI-02 M P P P P M EXISTING HYDRAULIC PROFILE AND DEMOLITION

More information

Ecological Restoration Drafting & Design Guidelines

Ecological Restoration Drafting & Design Guidelines Ecological Restoration Drafting & Design Guidelines Version 2.0 July 2017 Philadelphia Water Ecological Restoration Drafting & Design Guidelines Table of Contents 1.0 INTRODUCTION...2 2.0 GENERAL PLAN

More information

Documents: Response letter and attachments, Prepared by: AMEC Massachusetts, Inc., Dated February 17, 2016.

Documents: Response letter and attachments, Prepared by: AMEC Massachusetts, Inc., Dated February 17, 2016. GCG ASSOCIATES, INC. CIVIL ENGINEERING AND LAND SURVEYING 84 Main Street Wilmington, Massachusetts 01887 Phone: (978) 657-9714 Fax: (978) 657-7915 February 23, 2016 Mr. Nathaniel Strosberg, Town Planner

More information

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist Project Name Project Number Engineer Plans are to be designed based on the standards set forth in the Anne Arundel County Design Manual Standards and Specifications, and all other manuals as stipulated

More information

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Project Name: BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Phase: Unit: # Lots: Development Type (residential, commercial, industrial, etc.) Braselton Project No.

More information

Section E NSPS MODEL STANDARDS FOR TOPOGRAPHIC SURVEYS Approved 3/12/02

Section E NSPS MODEL STANDARDS FOR TOPOGRAPHIC SURVEYS Approved 3/12/02 Section E NSPS MODEL STANDARDS FOR TOPOGRAPHIC SURVEYS Approved 3/12/02 1. INTRODUCTION This standard is written to provide the professional surveyor (Surveyor) and the client with a guideline for producing

More information

KC Water Rules and Regulations For Water Main Extensions and Relocations

KC Water Rules and Regulations For Water Main Extensions and Relocations KC Water Rules and Regulations For Water Main Extensions and Relocations MAY 2017 NOTE: Changes from 2016 are highlighted in yellow and appear on Pages 5, 8, 10-11, 13, and 15. Additional changes made

More information

M I N N E S O T A D O T BID TABULATION SUMMARY JOB PAGE 1 ON 01/14/97 MINNESOTA PROJECT NO.S: DPI 015-8(021) DPI 015-8(022)

M I N N E S O T A D O T BID TABULATION SUMMARY JOB PAGE 1 ON 01/14/97 MINNESOTA PROJECT NO.S: DPI 015-8(021) DPI 015-8(022) BID TABULATION SUMMARY JOB 970010 PAGE 1 STATE PROJECT NO. 27-618-70 BIDS RECEIVED UNTIL 2:00 P.M. ON 01/14/97 MINNESOTA PROJECT NO.S: DPI 015-8(021) DPI 015-8(022) AT THE JUNCTION OF AUTO CLUB ROAD AND

More information

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012)

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012) MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management & Technical Support, Design Support Section TRANSMITTAL LETTER NO. (12-04) MANUAL: Standard

More information

Minimum Drawing & Electronic Submittal Requirements For Record Drawings /As-Builts

Minimum Drawing & Electronic Submittal Requirements For Record Drawings /As-Builts Minimum Drawing & Electronic Submittal Requirements For Record Drawings /As-Builts PUBLIC WORKS ENGINEERING DEPARTMENT Revised: February 1, 2017 MINIMUM DRAWING REQUIREMENTS A. GENERAL PLAN REQUIREMENTS:

More information

6'' W 8'' W 8'' W 4'' SAN 4'' SAN 2'' W 6'' W 6'' W INSTALL C.U. PAD (SEE MECHANICAL). M FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM TOP OF TOP OF SW

More information

City of Hamilton INFORMATION FOR CONDITIONAL USE PERMIT

City of Hamilton INFORMATION FOR CONDITIONAL USE PERMIT City of Hamilton INFORMATION FOR CONDITIONAL USE PERMIT There is a $200.00 non-refundable fee for each request. Requests must be completed and submitted to the Public Works Department, City of Hamilton,

More information

CHECKLIST 8-O. Highlands County Engineering Department Improvement Plan Checklist

CHECKLIST 8-O. Highlands County Engineering Department Improvement Plan Checklist Development Name: Submitted by: Highlands County Engineering Department Improvement Plan Checklist Date Received: Due Date: Y N E N / S O A This checklist is used for subdivision, mobile home parks, and

More information