PART 1 GENERAL FINISH CARPENTRY

Size: px
Start display at page:

Download "PART 1 GENERAL FINISH CARPENTRY"

Transcription

1 SECTION (06200) PART 1 GENERAL 1.1 SUMMARY A. Section Includes:. 1. Wood Millwork a. Interior Standing and Running Trim 2. Wood Stairs 3. Shelving 4. Composition Siding and Soffits and Trim a. Continuous Soffit Vent 1.2 REFERENCES A. American Wood Council / American Forest & Paper Association (AF&PA) Publications: 1. ANSI/AF&PA NDS-2005: "National Design Specification (NDS) for Wood Construction". B. AWI Quality Standards C. American Wood-Preservers's Association (AWPA) Publications: 1. C20 "Structural Lumber - Fire-Retardant Treatment by Pressure Processes" D. ASTM International Publications: 1. E84-03: Test Method for Surface-Burning Characteristics of Building Materials 2. A153 "Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware" 3. C1185 "Standard Test Methods for Sampling and Testing Non-Asbestos Fiber-Cement Flat Sheet, Roofing and Siding Shingles, and Clapboards." 4. C1186 "Standard Specification for Flat Non-Asbestos Fiber-Cement Sheets." E. U.S. Department of Commerce, National Institute of Standards and Technology (NIST) 1. DOC PS 1 "Construction and Industrial Plywood" 2. DOC PS 20 "American Softwood Lumber Standard" F. Hardwood Plywood & Veneer Association (HPVA) 1. ANSI/HPVA HP-1: "American National Standard for Hardwood and Decorative Plywood" 1.3 SUBMITTALS A. General: Submit the following in accordance with Conditions of Contract and Division 01 Specification Sections: (06200)-Page 1 of 11

2 1. Submit Product Data and Shop Drawings indicating component profiles and fastening and joining details. 2. Samples for initial selection of the following in the form of manufacturer's color charts consisting of actual units or sections of units showing the full range of colors, textures, and patterns available for each type of material indicated. a. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. 3. Samples for verification of the following: a. Lumber products with factory-applied finish, 50 sq. in. for lumber for each finish system and color. b. Linear Moldings: 2-foot-long section with finished joint. Show complete pattern. c. Nonlinear Shapes: Full-size unit. 4. Shop Drawings: Show profiles, thicknesses, finishes, joints, ornamentation, installation tolerances, and anchorage details. Indicate attachment methods, embedded supports, reinforcement, fabrication methods, joint treatments, clearances, and supports. a. Show connection to suspension system and cutouts for sprinklers, diffusers, grilles, speakers, and lighting fixtures. 1.4 QUALITY ASSURANCE A. Factory-mark each piece of lumber and plywood with type, grade, mill, and grading agency identification; except omit marking from surfaces to receive transparent finish, and submit mill certificate that material has been inspected and graded in accordance with requirements if it cannot be marked on a concealed surface. B. Perform finish carpentry work in accordance with AWI Quality Standards, Custom Grade. C. Fire-Test-Response Characteristics: Provide glass-reinforced gypsum fabrications with the following surface-burning characteristics as determined by testing identical products per ASTM E84 by UL or another independent testing and inspecting agency acceptable to authorities having jurisdiction: 1. Flame Spread: 25 or less. 2. Smoke Developed: 450 or less. 1.5 DELIVERY, STORAGE, AND HANDLING A. Protect finish carpentry materials during transit, delivery, storage, and handling to prevent damage, soiling, and deterioration. B. Do not deliver finish carpentry materials, until painting, wet work, grinding, and similar operations which could damage, soil, or deteriorate woodwork have been completed in installation areas. If, due to unforeseen circumstances, finish carpentry materials must be stored in other than installation areas, store only in areas meeting requirements specified for installation areas. 1.6 PROJECT CONDITIONS A. Conditioning: Installer shall advise Contractor of temperature and humidity requirements for finish carpentry installation areas (06200)-Page 2 of 11

3 B. Environmental Limitations: Do not deliver or install interior finish carpentry until building is enclosed and weatherproof, wet-work in space is completed and nominally dry, and HVAC system is operating and will maintain temperature and relative humidity at occupancy levels throughout the remainder of construction period. 1. Maintain temperature and humidity in installation area as required to maintain moisture content of installed finish carpentry within a 1.0 percent tolerance of optimum moisture content, from date of installation through remainder of construction period. The fabricator of woodwork shall determine optimum moisture content and required temperature and humidity. C. Weather Limitations: Proceed with installing exterior finish carpentry only when existing and forecasted weather conditions will permit work to be performed according to manufacturer's recommendations and warranty requirements and at least one coat of specified finish to be applied without exposure to rain, snow, or dampness. D. Field Measurements: Where glass-reinforced gypsum fabrications are indicated to fit to other construction, verify dimensions of other construction by field measurements before fabrication and indicate measurements on Shop Drawings. Coordinate fabrication schedule with construction progress to avoid delaying the Work. PART 2 PRODUCTS 2.1 MATERIALS, GENERAL A. Lumber Standards: Comply with DOC PS 20, "American Softwood Lumber Standard," and with applicable grading rules of inspection agencies certified by ALSC's Board of Review. B. Inspection Agencies: Inspection agencies, and the abbreviations used to reference them, include the following: 1. Northeastern Lumber Manufacturers Association (NeLMA) 2. National Lumber Grades Authority (Canadian) (NLGA) 3. Redwood Inspection Service (RIS) 4. Southern Pine Inspection Bureau (SPIB) 5. West Coast Lumber Inspection Bureau (WCLIB) 6. Western Wood Products Association (WWPA) C. Grade Stamps: Provide lumber with each piece factory marked with grade stamp of inspection agency evidencing compliance with grading rule requirements and identifying grading agency, grade, species, moisture content at time of surfacing, and mill. 1. For exposed lumber, furnish pieces with grade stamps applied to ends or back of each piece, or omit grade stamps entirely and provide certificates of grade compliance issued by inspection agency. D. Softwood Plywood: Comply with DOC PS 1, "U.S. Product Standard for Construction and Industrial Plywood." E. Hardwood Plywood: Comply with ANSI/HPVA HP-1, "Interim Voluntary Standard for Hardwood and Decorative Plywood." (06200)-Page 3 of 11

4 2.2 INTERIOR STANDING AND RUNNING TRIM A. Hardwood Lumber: Grading in accordance with AWI; maximum moisture content of 15 percent. 1. Stained Interior Wood Trim and Millwork: Species as shown below, solid lumber stock, sizes and shapes shown on Drawings, of straight grain type sufficient to receive stained finish, smooth surfaced. a. Maximum Moisture Content: 10 percent. b. Finger Jointing: Not allowed c. Red Oak, Grade 1 2. Painted Interior Wood Trim and Millwork: Species as shown below, solid lumber stock, sizes and shapes shown on Drawings, of grain type sufficient to receive painted finish, smooth surfaced. a. Poplar, Paint Grade b. Maximum Moisture Content: 15 percent. c. Finger Jointing: Not allowed B. Nominal sizes are indicated, except as shown by detailed dimensions. Provide dressed or worked and dressed lumber, as applicable, manufactured to the actual sizes as required by PS 20 or to actual sizes and patterns as shown, unless otherwise indicated. 2.3 INTERIOR WOOD STAIRS A. Treads: Structural Flooring, ¾-inch thickness as required to accept finish flooring B. Risers: Structural Flooring, ¾-inch thickness as required to accept finish flooring C. Stringers: 2 x 12 inch nominal size solid lumber, refer to Drawings. Notch to receive treads, risers and supports. Provide at least 3 stringers for each 36 inches of clear width of stair. D. Railings: Aluminum handrails, refer to Drawings. 2.4 MISCELLANEOUS MATERIALS A. Fasteners and Anchorages: Provide nails, screws, and other anchoring devices of the type, size, material, and finish required for application indicated to provide secure attachment, concealed where possible, and complying with applicable Federal Specifications. Provide in sufficient length to penetrate minimum of 1-1/2 inches into substrate, unless otherwise recommended by manufacturer. 1. Where finish carpentry is exposed on exterior or in areas of high relative humidity, provide fasteners and anchorages with a hot-dipped zinc coating complying with ASTM A153, or stainless steel. 2. For redwood, provide stainless-steel fasteners. 2.5 FABRICATION WOOD A. Wood Moisture Content: Comply with requirements of specified inspection agencies and manufacturer's recommendations for moisture content of finish carpentry on relative humidity conditions existing during time of fabrication and in installation areas (06200)-Page 4 of 11

5 B. Fabricate finish carpentry to dimensions, profiles, and details indicated. 1. Back out or kerf backs of the following members, except members with ends exposed in finished work: a. Interior standing and running trim, except shoe mold and crown mold. 2. Ease edges of lumber less than 1 inch in nominal thickness to 1-1/6 inch radius. 2.6 SHEET MATERIALS A. Shelving: 3/4" thick by width shown on Drawings, Hardwood Plywood; custom grade in accordance with AWI; core material of veneer; type of bond recommended for application; with minimum 3/4" x 1-1/4" hardwood nosing. B. Softwood Plywood: DOC PS 1, Medium Density Overlay. 2.7 FIRE RETARDANT TREATED (FRT) LUMBER A. Approved Manufacturers: 1. Lumber: a. "Dricon FRT"; Archwood Protection Inc. ( ) b. "Pyro-Guard ; Hoover Treated Wood Products, Inc. ( , ext. 211) c. "FirePRO FR Lumber"; Osmose Wood Preserving, Inc. ( ) 2. Plywood: a. "Exterior Fire-X"; Hoover Treated Wood Products, Inc. ( , ext. 211) B. Comply with performance requirements in AWPA C20, Exterior type. Kiln dry after treatment to a maximum moisture content of 19 percent. C. Flamespread and smoke developed ratings of 25 or less by ASTM E84, with no sign of progressive combustion when test is extended to 30 minutes. D. Materials: 1. All materials shall come from the factory pre-primed. 2. Type: Non-combustible fiber cement, exterior grade trim board complying with ASTM C1186, Grade I Type A fiber cement sheet. No asbestos fibers shall be contained in products. 3. Flame Spread Index of 0 and Smoke Generation Number of 0 in accordance with ASTM E Fasteners:. a. Wood Framing: face fastening: siding nails with minimum shank and head diameters, minimum 1-1/2 long.] E. Schedule of Components Composition Exterior Standing and Running Trim 1. Harditrim, James Hardie Co. a. Thickness: 7/16 b. Width: 11-1/ (06200)-Page 5 of 11

6 c. Length: 12-0 d. Surface Texture: Select Cedarmill. 2. Cemtrim, Cemplank, Inc. a. Thickness: 7/8. b. Width: 11-1/2 c. Length: 10-0 d. Surface Texture: Traditional Cedar 2.8 COMPOSITION SIDING AND SOFFITS A. Approved Manufacturers: 1. James Hardie Co. ( ) 2. Cemplank, Inc. ( ) B. Materials: 1. All materials shall come from the factory pre-primed. 2. Type: Non-combustible fiber cement, exterior grade siding and soffit board complying with ASTM C1186, Grade I, Type A. No asbestos fibers shall be contained in products. 3. Flame Spread Index of 0 and Smoke Generation Number of 0 in accordance with ASTM E Flexural strength per ASTM C1185: 1850 length direction; 2500 transverse direction of sheet. 5. Thermal resistance: Minimum R-values of 0.15 for Siding materials and for Soffit materials. C. Trim: Provide lineal trim, corner inserts, square and cove type; other trim pieces necessary to complete installation. D. Accessories: 1. Fasteners: a. Wood Framing: Corrosion resistant, shank head siding nails, size as recommended by manufacturer of siding. 2. Sealants or Caulking Compounds: Refer to Section Only use products as approved by composition siding manufacturer. 3. Cement patch: Macklanburg-Duncan Co., Oklahoma City, OK ( ) Acrylic Mortar Patch, or as approved by manufacturer of composition siding. E. Schedule of Components - Composition Siding & Soffits 1. HardiPlank Lap Siding ; James Hardie Co. a. Thickness: 5/16" b. Weight: 2.3 lbs/sf c. Width: 9-1/2" (8-1/4" coverage) (06200)-Page 6 of 11

7 d. Length: 12' e. Surface Texture: Cedarmill 2. Cemplank, Inc.: a. Thickness: 5/16" b. Weight: 2 lbs/sf c. Width: 9-1/2" (8-1/4 coverage) d. Length: 12' e. Surface Texture: Traditional Cedar 3. Hardisoffit ; James Hardie Co. a. Thickness: 1/4" b. Weight: 1.9 lbs/sf c. Width: As Required d. Length: 8' e. Surface Texture: Smooth 4. Cemsoffit ; Cemplank, Inc.: a. Thickness: 5/16" b. Weight: 2.1 lbs/sf c. Width: As Required d. Length: 8 or 10' e. Surface Texture: Smooth F. Continuous Soffit Vent (For use with Cementitious Soffit) 1. Approved Manufacturers: a. EZVent ; R.H. Tamlyn & Sons ( ) 2. Materials: a. White PVC, sized for soffit thickness PART 3 EXECUTION 3.1 EXAMINATION A. Examine substrates, with Installer present, for compliance with requirements for installation tolerance and other conditions affecting installation and performance of finish carpentry. Do not proceed with installation until unsatisfactory conditions have been corrected. B. Do not install materials that are wet, moisture or mold damaged. 3.2 PREPARATION A. Clean substrates of projections and substances detrimental to application (06200)-Page 7 of 11

8 B. Condition finish carpentry to average prevailing humidity conditions in installation areas before installation, for a minimum of 24 hours unless longer conditioning is recommended by manufacturer. C. Prime and backprime lumber for painted finish exposed on the exterior not indicated as factory prefinished. Comply with requirements for surface preparation and application in Section Painting. D. Ensure that all electrical or other services are in place. 3.3 INSTALLATION A. Discard units of material which are unsound, warped, bowed, twisted improperly treated, not adequately seasoned or too small to fabricate work with minimum of joints or optimum jointing arrangements. Do not use manufactured units with defective surfaces, sizes, or patterns. B. Install the work plumb, level, true, and straight with no distortions. Shim as required using concealed shims. Install to a tolerance of 1/8" in 8'-0" for plumb and level countertops; and with 1/16" maximum offset in flush adjoining 1/8" maximum offsets in revealed adjoining surfaces. C. Scribe and cut work to fit adjoining work, and refinish cut surfaces or repair damaged finish at cuts. D. Countersink nails, fill surface flush, and sand where face nailing is unavoidable. E. Install to tolerance of 1/8 inch in 96 inches for plumb and level. Install adjoining finish carpentry with 1/32 inch maximum offset for flush installation and 1/16 inch maximum offset for reveal installation. F. Coordinate finish carpentry with materials and systems in or adjacent to standing and running trim and rails. Provide cutouts for mechanical and electrical items that penetrate exposed surfaces of trim and rails. G. Finish according to specified requirements. H. Anchor finish carpentry work to anchorage devices or blocking built-in or directly attached to substrates. Secure to grounds, stripping and blocking with countersunk, concealed fasteners and blind nailing as required for a complete installation. Except where prefinished matching fastener heads are required, use fine finishing nails for exposed nailings, countersunk and filled flush with finished surface, and matching final finish where transparent is indicated. 3.4 WOOD STANDING AND RUNNING TRIM INSTALLATION A. Install with minimum number of joints practical, using full-length pieces from maximum lengths of lumber available. Do not use pieces less than 24 inches long, except where necessary. Stagger joints in adjacent and related standing and running trim. Cope at returns and miter at corners to produce tight-fitting joints with full-surface contact throughout length of joint. Use scarf joints for end-to-end joints. Plane backs of casings to provide uniform thickness across joints, if required. 1. Match color and grain pattern across joints for transparent finish locations. 2. Install trim after gypsum board joint finishing operations are completed (06200)-Page 8 of 11

9 3. Drill pilot holes in hardwood before fastening to prevent spitting. Fasten to prevent movement or warping. Countersink fastener heads on exposed carpentry work and fill holes. B. ERECTION AND LOCATION TOLERANCES 1. Erection Tolerances: Install glass-reinforced gypsum fabrications so each unit complies with the following dimensional requirements: a. Plane Alignment (Panel to Panel): 1/16 inch. b. Variation from Plumb: Plus or minus 1/8 inch per 10 feet. c. Variation from Straightness: Plus or minus 1/4 inch per 25 feet. d. Assembly Deflection: Not greater than the length of the assembly divided by 240. e. Joint Alignment: Not more than 1/8 inch. f. Joint Width: Not more than 3/8 inch. 3.5 COMPOSITION STANDING AND RUNNING TRIM INSTALLATION A. Install in accordance with manufacturers recommendations. B. Install with minimum number of joints practical, using full-length pieces from maximum lengths of composition trim available. C. Fasten through trim into building structure D. Fasten maximum of 12 on center, stagger fasteners across trim width. E. Target fastener setback no closer than 1 inches from edges and ends of trim and no further than 2 inches from edges of trim. F. Fasteners shall be flush, do not overdrive. Protect over-driven fasteners from the weather and compliment with a second fastener, properly installed. G. Maintain clearance between trim and adjacent finished grade. H. Where 7/16 trim is used over composition siding, provide shims as required to five the trim a flat bearing surface. I. Overlay siding with trim molding at windows, doors and inside corners as indicated on the drawings. Fasten through overlapping boards. Do not nail between lap joints. J. Overlay siding with single board of outside corner board then align second corner board to outside edge of first corner board. Fasten boards to building structure. Do not fasten trim board to trim board. K. Shim frieze boards as required to align with corner trim in locations as indicated on drawings. L. Install trim fascia over structural sub-fascia in locations indicated on drawings. M. Seal all end cuts with masonry compatible sealer. 3.6 COMPOSITION SIDING INSTALLATION A. Air Infiltration Barrier Installation: 1. One layer of air infiltration barrier shall be installed horizontally on walls. Weatherlap edges and ends minimum 6" (06200)-Page 9 of 11

10 2. Stagger vertical joints. 3. At openings such as windows, refer to Section for flashing installation. B. Installation of Siding: 1. Install siding and accessories in accordance with manufacturer's directions. 2. Install siding level and plumb. Install for natural shed of water. Position cut ends over bearing surfaces. Sand cut edges smooth and clean. Maintain clearance between siding materials and adjacent finished grade as recommended by manufacturer. 3. Fasten through siding and/or trim into structural framing. Fasteners must penetrate a minimum of ¾. Place fasteners as recommended by siding manufacturer. 4. Provide for expansion and contraction of siding at location of installation. Do not drive nail heads tight against nailing lock. Size nails in accordance with manufacturer's printed literature. 5. Install flashings as indicated on Drawings and as recommended by siding manufacturer at all wall openings. 6. Joints or laps shall be in accordance with the manufacturer's printed instructions. Stagger end joints by at least two courses. Locate splices at least one stud away from door or window openings, minimum of Plan all butt joints between two planks to fall on building structure (studs.) Butt joints between planks shall be caulked or back-flashed to divert water onto the lower course of siding. Always fasten from one end to the other, not from both ends toward the middle. 8. Locate splices at lest one stud cavity away from window and door openings. 9. Hold siding 1/4" away from floors, soffits, doors, windows, and louver frames for sealant application. See Provide sealants at all locations recommended by manufacturer and provide sealant as approved by manufacturer of siding. C. Installation of Continuous Soffit Vent: 1. Install in accordance with soffit and vent manufacturer s recommendations. 2. Use corrosion resistant nails of sufficient length to penetrate wood blocking or studs a minimum of 1-inch. D. Finishing of Siding and Soffits: 1. Use only paints recommended directly by siding manufacturer. Do not use oil-based stains. 2. Siding will be factory primed. Provide finish coats immediately after application of siding to building, but in no case exceeding 90 days. 3. The use of acrylic latex-based caulking compounds is required. 3.7 INTERIOR WOOD STAIR INSTALLATION A. Treads and Risers: 1. Glue and nail treads and risers to supporting stringers (06200)-Page 10 of 11

11 B. Provide maximum of 3/16-inch variation between adjacent treads and risers and a maximum of 3/8-inch variation between largest and smallest treads and risers within each flight of stairs. 3.8 ADJUSTMENT, CLEANING, FINISHING, AND PROTECTION A. Repair damaged and defective finish carpentry work wherever possible to eliminate defects functionally and visually; where not possible to repair properly, replace woodwork. Adjust joinery for uniform appearance. B. Clean finish carpentry work on exposed and semi-exposed surfaces. Touch-up factory-applied finishes to restore damaged or soiled areas. C. Preparation for Finishing: Sand work smooth and set all nails and screws. Apply wood filler in exposed nail and screw indentations. D. Cleaning: Keep premises in a neat, safe, and orderly condition at all times during execution of this portion of the work, free from the accumulation of sawdust, cut-ends, and debris. E. Refer to Division 09 Sections for final finishing of installed finish carpentry work. F. Protection: Installer of finish carpentry work shall advise Contractor of final protection and maintained conditions necessary to ensure that work will be without damage or deterioration at time of acceptance. END OF SECTION (06200) (06200)-Page 11 of 11

SECTION INTERIOR FINISH CARPENTRY. A. Lumber grading agencies, and the abbreviations used to reference them, include the following:

SECTION INTERIOR FINISH CARPENTRY. A. Lumber grading agencies, and the abbreviations used to reference them, include the following: SECTION 06 2023 PART 1 GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior standing and running trim. 2. Interior stairs. 1.2 DEFINITIONS A. Lumber grading agencies, and the abbreviations

More information

Ash Brook Golf Course Scotch Plains, New Jersey

Ash Brook Golf Course Scotch Plains, New Jersey SECTION 062013 - EXTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION INTERIOR FINISH CARPENTRY

SECTION INTERIOR FINISH CARPENTRY SECTION 06 20 23 PART 1 - GENERAL 1.01 SUMMARY A. Section includes the following items for field-applied paint finish: 1. Interior standing and running trim. 2. Interior plywood paneling. B. Related Sections

More information

B. Related Requirements: 1. Section "Interior Painting" for priming and backpriming of interior finish carpentry.

B. Related Requirements: 1. Section Interior Painting for priming and backpriming of interior finish carpentry. 1 ~GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY

More information

SECTION FINISH CARPENTRY

SECTION FINISH CARPENTRY SECTION 06200 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to

More information

A. Provide all finish carpentry needed for a complete and proper installation.

A. Provide all finish carpentry needed for a complete and proper installation. SECTION 06200 - PART ONE GENERAL 1.1 SECTION INCLUDES A. Provide all finish carpentry needed for a complete and proper installation. B. Provide all wood, nails, bolts, screws, and all other items needed

More information

ADDENDUM NO. 1 THOROUGHBRED ROOM RENOVATION PHASE II DINING AREA MURRAY STATE UNIVERSITY, MURRAY, KY PROJECT #

ADDENDUM NO. 1 THOROUGHBRED ROOM RENOVATION PHASE II DINING AREA MURRAY STATE UNIVERSITY, MURRAY, KY PROJECT # ADDENDUM NO. 1 THOROUGHBRED ROOM RENOVATION PHASE II DINING AREA MURRAY STATE UNIVERSITY, MURRAY, KY PROJECT #13-046 10-23-2013 Bidders shall acknowledge receipt of this Addendum on the Bid Form, in the

More information

A. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension.

A. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension. HIGGINSVILLE HABILITATION CENTER MISC. BUILDING RENOVATIONS STATE OF MISSOURI HIGGINSVILLE, MISSOURI SECTION 061000 - ROUGH CARPENTRY PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

DIVISION 6 WOODS AND PLASTICS SECTION FINISH CARPENTRY

DIVISION 6 WOODS AND PLASTICS SECTION FINISH CARPENTRY DIVISION 6 WOODS AND PLASTICS SECTION 06 20 23 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 062023 - INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and type.

A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and type. SECTION 062000 - FINISH CARPENTRY PART 1 - GENERAL 1.1 SECTION REQUIREMENTS A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and

More information

SECTION FINISH CARPENTRY PART 1 GENERAL. 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section.

SECTION FINISH CARPENTRY PART 1 GENERAL. 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section. SECTION 06200 - FINISH CARPENTRY PART 1 GENERAL 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section. 1.2 RELATED SECTIONS A. Section 06100 - Rough Carpentry:

More information

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A SECTION 061050 - MISCELLANEOUS CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION ARCHITECTURAL WOOD CASEWORK

SECTION ARCHITECTURAL WOOD CASEWORK SECTION 06410 - ARCHITECTURAL WOOD CASEWORK PART 1 GENERAL 1.01 SECTION INCLUDES A. Wood cabinets for opaque finish. B. Flush wood paneling for transparent finish. C. Factory finishing. 1.02 RELATED REQUIREMENTS

More information

2. Wood grounds, nailers, blocking, miscellaneous framing, sleepers, etc.

2. Wood grounds, nailers, blocking, miscellaneous framing, sleepers, etc. 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 STIPULATIONS A. The specifications sections " General Conditions of the Construction Contract ", "Special Conditions", and "Division 1 - General Requirements"

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 06 1053 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Division 01 Specification

More information

SECTION CARPENTRY

SECTION CARPENTRY SECTION 06100 CARPENTRY PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Carpentry work including grounds, nailers, blocking, miscellaneous framing, plywood backing panels, plywood sheathing, preservative

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 06 2023 - INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION 6 WOOD AND PLASTICS

DIVISION 6 WOOD AND PLASTICS DIVISION 6 WOOD AND PLASTICS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

SECTION ARCHITECTURAL WOODWORK

SECTION ARCHITECTURAL WOODWORK SECTION 06400 ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Custom Cabinet Units a. Plastic Laminate b. Sound Barrier for Casework 2. Cabinet Hardware B. Related Sections:

More information

DIVISION 6 WOODS AND PLASTICS SECTION ROUGH CARPENTRY

DIVISION 6 WOODS AND PLASTICS SECTION ROUGH CARPENTRY DIVISION 6 WOODS AND PLASTICS SECTION 06 10 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 105116 - WOOD LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

A. Rough carpentry includes but is not limited to the following:

A. Rough carpentry includes but is not limited to the following: SECTION 06100 ROUGH CARPENTRY PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification Sections,

More information

SECTION MISCELLANEOUS ROUGH CARPENTRY

SECTION MISCELLANEOUS ROUGH CARPENTRY SECTION 06 1053 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

D. Product Certificates: Signed by manufacturers of casework certifying that products furnished comply with requirements.

D. Product Certificates: Signed by manufacturers of casework certifying that products furnished comply with requirements. SECTION 12356 - CASEWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Chevy Chase Club June 30, 2008 Bowie Gridley Architects

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION 081433 - STILE AND RAIL WOOD DOORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS SECTION 081433 - STILE AND RAIL WOOD DOORS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior stile and rail wood doors and sidelites. 2. Interior stile and rail wood doors. 3. Interior fire-rated,

More information

SECTION WOOD DOORS

SECTION WOOD DOORS SECTION 08211 WOOD DOORS Notice to Vendors: CANV prefers to purchase products that contain tropical wood only if they are certified according to the guidelines of the Forest Stewardship Council (FSC).

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06 10 00- ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Contracting Requirements and Division 1 Specification Sections, apply

More information

SECTION ARCHITECTURAL WOODWORK. B. Related Sections: 1. Section Paints and Coatings: Field applied painted finishes.

SECTION ARCHITECTURAL WOODWORK. B. Related Sections: 1. Section Paints and Coatings: Field applied painted finishes. PART 1 - GENERAL 1.1 SUMMARY SECTION 06 40 00 A. Provide architectural woodwork as shown and specified. Work includes: 1. Providing plastic laminate finished casework. 2. Providing plastic laminate clad

More information

SECTION PRE-MANUFACTURED CABINETS

SECTION PRE-MANUFACTURED CABINETS SECTION 12390 PRE-MANUFACTURED PART 1 GENERAL 1.1 DESCRIPTION OF WORK A. The work includes furnishing all labor, materials and equipment required to complete the Pre-Manufactured Cabinet work as shown

More information

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK:

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: SECTION 061000 - ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: A. Definition: Rough carpentry includes carpent~y work not specified as part of other sections and which is generally not exposed, except as otherwise

More information

Project Specifications Section SECTION ROUGH CARPENTRY Issued Final:

Project Specifications Section SECTION ROUGH CARPENTRY Issued Final: Project Specifications Section 061000 ROUGH CARPENTRY SECTION 061000 - ROUGH CARPENTRY Issued Final: 02-01-17 PART 1 - GENERAL 1.1 SUMMARY A. Scope: 1. Provide rough carpentry items where shown on the

More information

Lindenwold Boro Hall Lindenwold, NJ. Bishop & Smith Architects Laurel Springs, NJ. August 2, 2012 PART 1 - GENERAL 1.1 SUMMARY. A.

Lindenwold Boro Hall Lindenwold, NJ. Bishop & Smith Architects Laurel Springs, NJ. August 2, 2012 PART 1 - GENERAL 1.1 SUMMARY. A. SECTION 061000 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Wood blocking and nailers. 2. Wood furring and grounds. 3. Plywood backing panels. 1.2 ACTION SUBMITTALS A. Product

More information

Shapes Siding. Perfection Shingles. Chalk Line

Shapes Siding. Perfection Shingles. Chalk Line Snap a Chalk Line Shapes Siding Perfection Shingles Chalk Line To establish a straight reference line to guide the positioning of the starter strip and the first course of siding, snap a chalk line. starter

More information

1. Division 6 Section "Rough Carpentry" for furring, blocking, and other carpentry work that is not exposed to view.

1. Division 6 Section Rough Carpentry for furring, blocking, and other carpentry work that is not exposed to view. SECTION 06402 INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION LAP SIDING. A. Fiber cement lap siding, panels, single, trim, fascia, moulding and accessories.

SECTION LAP SIDING. A. Fiber cement lap siding, panels, single, trim, fascia, moulding and accessories. SECTION 07460 LAP SIDING PART 1 GENERAL 1.1 SECTION INCLUDES A. Fiber cement lap siding, panels, single, trim, fascia, moulding and accessories. B. Factory-finished fiber cement lap siding, panels, single,

More information

DIVISION 6 WOOD, PLASTICS AND COMPOSITES

DIVISION 6 WOOD, PLASTICS AND COMPOSITES DIVISION 6 WOOD, PLASTICS AND COMPOSITES PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 06 1000 ROUGH CARPENTRY A. Rough opening framing for doors, windows, and roof openings. B. Roofing nailers. C. Preservative

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

1.03 QUALITY ASSURANCE A. Inspection Agencies: 1. SPIB: Southern Pine Inspection Bureau; for all structural framing of roof joists and headers.

1.03 QUALITY ASSURANCE A. Inspection Agencies: 1. SPIB: Southern Pine Inspection Bureau; for all structural framing of roof joists and headers. DIVISION 6 - WOOD AND PLASTICS SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Rough carpentry for: a. Wood framing and sheathing for the new Rest Area building additions.

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06100 ROUGH CARPENTRY PART 1 GENERAL 1.1 DESCRIPTION OF WORK A. The work includes furnishing all labor, materials and equipment required to complete the Rough Carpentry work as shown on the Drawings

More information

SECTION MANUFACTURED CASEWORK

SECTION MANUFACTURED CASEWORK 1 GENERAL 1.1 SECTION INCLUDES SECTION 12300 MANUFACTURED CASEWORK A. Work required to complete the manufactured casework indicated by the Contract Documents, and the items necessary for its proper installation.

More information

SECTION HOLLOW METAL DOORS AND FRAMES

SECTION HOLLOW METAL DOORS AND FRAMES SECTION 081113 HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: Include construction details, material

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY PART 1 GENERAL 1.1 RELATED SECTIONS SECTION 061000 ROUGH CARPENTRY A. Drawings and general provisions of the Construction Contract, including General Conditions and Division 1 Specification Sections, apply

More information

Installation Instructions for Standard Lap and Self-Aligning Lap Siding

Installation Instructions for Standard Lap and Self-Aligning Lap Siding Installation Instructions for Standard Lap and Self-Aligning Lap Siding 7/16 in. Standard Laps Include: All Old Mill Widths, Cedar Shake Lap and Smooth Lap 1/2 in. Self-Aligning Include: 8 in. and 12 in.

More information

SECTION WOOD ARCHITECTURAL CABINETS AND QUARTZ COUNTERTOPS

SECTION WOOD ARCHITECTURAL CABINETS AND QUARTZ COUNTERTOPS SECTION 064113- WOOD ARCHITECTURAL CABINETS AND QUARTZ COUNTERTOPS PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

1.04 QUALITY ASSURANCE

1.04 QUALITY ASSURANCE SECTION 07312 ARCHITECTURAL ASPHALT SHINGLES PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding

Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding Includes: Cove, Craftsmen Staggered, Diamond, Fish Scale, Octagon, Round and Old Mill Shingle Lap Important: Read and understand

More information

A. ASTM D Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position.

A. ASTM D Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position. SECTION 074600 VINYL SIDING PART 1 GENERAL 1.1 SECTION INCLUDES A. Vinyl siding. B. Vinyl soffits. C. Accessories and trim. 1.2 RELATED SECTIONS A. Section 06100 - Framing and Sheathing. B. Section 07260

More information

B. Shop Drawings: For residential casework. Include plans. elevations, details, and attachments to other work.

B. Shop Drawings: For residential casework. Include plans. elevations, details, and attachments to other work. HVAC 1Sunporch 1Fire Alarm Renovation SECTION 123530 RESIDENTIAL CASEWORK PART 1 - GENERAL 1.1 SUMMARY A. Section includes laundry room cabinets. 1.2 ACTION SUBMITTALS A. Product Data: For each type of

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06 10 00 ROUGH CARPENTRY PART 1 - GENERAL 1.01 SUMMARY A. Section includes: 1. Framing with dimension lumber. 2. Wood blocking and nailers. 3. Plywood backing panels. 1.02 ACTION SUBMITTALS A.

More information

WHITE W/OAK TRIM NATURAL MEDIUM NORTHPORT OAK

WHITE W/OAK TRIM NATURAL MEDIUM NORTHPORT OAK WHITE W/OAK TRIM NATURAL MEDIUM NORTHPORT OAK Accessories. We believe that functionality is at the heart of any great kitchen. Above are a few of the accessories available with Merillat Essentials. The

More information

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06100 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide Rough Carpentry as shown and detailed on the Drawings and

More information

Product Guide Specification

Product Guide Specification JELD-WEN, inc. November 2014 825 Shiner Road, PO Box 311 Towanda, Pennsylvania 18848 Toll Free 800-255-0785 Website www.miratectrim.com E-mail miratec@jeld-wen.com Product Guide Specification Specifier

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

INTEX Millwork Solutions SECTION EXTERIOR PVC PERGOLAS (IBC Compliant)

INTEX Millwork Solutions SECTION EXTERIOR PVC PERGOLAS (IBC Compliant) SECTION 066030 EXTERIOR PVC PERGOLAS (IBC Compliant) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and other Contract Documents, listed in the agreement between the Owner and Contractor, apply to

More information

DETAILED STILE AND RAIL WOOD DOOR SPECIFICATION

DETAILED STILE AND RAIL WOOD DOOR SPECIFICATION DETAILED STILE AND RAIL WOOD DOOR SPECIFICATION UNIVERSITY CONTACT: Structural Services, Maintenance & Operations (302) 831-8456 PART 1 GENERAL DOORS 1.01 GENERAL PROVISIONS 1. The Drawings and General

More information

A. Product Data: For each type of process and factory-fabricated product indicated.

A. Product Data: For each type of process and factory-fabricated product indicated. SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 061000 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The General Conditions, any Supplementary General Conditions and Division 1, General Requirements, are hereby made a part of

More information

ADDENDUM TO THE CONTRACT. for the GLACIER FIRE STATION KITCHEN AND CLASSROOM RENOVATION. Contract No. E16-181

ADDENDUM TO THE CONTRACT. for the GLACIER FIRE STATION KITCHEN AND CLASSROOM RENOVATION. Contract No. E16-181 ADDENDUM TO THE CONTRACT for the ENGINEERING DEPARTMENT GLACIER FIRE STATION KITCHEN AND CLASSROOM RENOVATION Contract No. E6-8 ADDENDUM NO.: ONE CURRENT DEADLINE FOR BIDS: May 9, 206 PREVIOUS ADDENDA:

More information

PRIMED STRAND REVERSIBLE SHAKE

PRIMED STRAND REVERSIBLE SHAKE PRIMED STRAND REVERSIBLE SHAKE PRIOR TO INSTALLATION Inspect product for any issues before installing (breakage, surface defects, foreign objects). Do not install questionable product. Report any problems

More information

A. Dimension Lumber: Lumber of 2 inches nominal or greater but less than 5 inches nominal in least dimension.

A. Dimension Lumber: Lumber of 2 inches nominal or greater but less than 5 inches nominal in least dimension. SECTION 06 10 53 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 07311 - ASPHALT SHINGLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Product Guide Specification For Nonrated & 20-Minute Rated Doors

Product Guide Specification For Nonrated & 20-Minute Rated Doors Woodtech Trading Company 455 Fourth Avenue E.N. P.O. Box 2609 Columbia Falls, MT 59912 800-775-1352 (phone) 800-775-1353 (fax) www.woodtechdoor.com Product Guide Specification For Nonrated & 20-Minute

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section includes standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

PANELTEK ENGINEERED SIDING/PANELLING INSTRUCTIONS

PANELTEK ENGINEERED SIDING/PANELLING INSTRUCTIONS PANELTEK ENGINEERED SIDING/PANELLING INSTRUCTIONS This product can be used for interior and exterior installations. Much of this guide refers to exterior installation, however, many of the construction

More information

DIVISON 6 WOODS AND PLASTICS SECTION PLASTIC LAMINATE FACED ARCHITECTUAL CABINETS

DIVISON 6 WOODS AND PLASTICS SECTION PLASTIC LAMINATE FACED ARCHITECTUAL CABINETS DIVISON 6 WOODS AND PLASTICS PART 1 - GENERAL 1:1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Bovard Studios Inc. Section April 6, 2004 Page 1

Bovard Studios Inc. Section April 6, 2004 Page 1 April 6, 2004 Page 1 This section includes solid flush and surface articulated wood doors, may have veneer facing, solid or glazed (stained glass) design, factory pre-fit, may be factory finished or site

More information

SECTION INTERIOR ARCHITECTURAL WOODWORK

SECTION INTERIOR ARCHITECTURAL WOODWORK SECTION 06402 - INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications.

Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications. Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications. EXTERIOR INSULATION & FINISH SYSTEM CONSTRUCTION Data Published Courtesy

More information

WoodWORKS Channeled Plank

WoodWORKS Channeled Plank CEILING&WALL SYSTEMS Between us, ideas become reality WoodWORKS Channeled Plank Assembly and Installation Instructions 1. General 1.1 Product Description WoodWorks Channeled acoustical ceiling and wall

More information

SECTION CUSTOM CASEWORK

SECTION CUSTOM CASEWORK PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 06 41 00 CUSTOM CASEWORK A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification sections,

More information

Installation Instructions for TruWood Reversible Trim

Installation Instructions for TruWood Reversible Trim Installation Instructions for TruWood Reversible Trim Important: Read and understand all pages of the installation instructions before starting the trim application. For TruWood care and maintenance information,

More information

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available. SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

4. Metal roof jacks at penetrations and attachments

4. Metal roof jacks at penetrations and attachments - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SECTION 07 61 00 METAL SHINGLE ROOFING - - - - - - - - - - -

More information

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1 Fitness Facility Addition Page 1 PART 1 GENERAL 1.1 SECTION INCLUDES.1 Finish carpentry items including shop prefabricated casework and countertops..2 Hardware and attachment accessories..3 Wood Benches..4

More information

COMPOSITE SIDING INSTALLATION GUIDE

COMPOSITE SIDING INSTALLATION GUIDE CENTURY HOME LIVING COMPOSITE SIDING INSTALLATION GUIDE Read all instructions prior to installing any siding product. Failure to install and finish this product in accordance with all local building codes,

More information

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018 SECTION 055000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Slate Shingle Specifications

Slate Shingle Specifications Slate Shingle Specifications California Slate is a proud member of the Slate Roofing Contractors Association of North America, Inc. (SRCA) which publishes Section 07310 Slate Shingles setting forth architectural

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 06 WOOD, PLASTICS AND COMPOSITES

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 06 WOOD, PLASTICS AND COMPOSITES SECTION 064023 - INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior standing and running trim. 2. Interior frames and jambs. 3. Stairwork and

More information

SECTION WOOD ARCHITECTURAL CABINETS AND LAMINATE COUNTERTOPS

SECTION WOOD ARCHITECTURAL CABINETS AND LAMINATE COUNTERTOPS SECTION 064113- WOOD ARCHITECTURAL CABINETS AND LAMINATE COUNTERTOPS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

PROJECT INSTRUCTIONS Roofing

PROJECT INSTRUCTIONS Roofing PROJECT INSTRUCTIONS Roofing This handout outlines some basic regulations contained within the 2015 Minnesota State Building Code, as well as other good building practices. However, this handout is not

More information

Installation Instructions for Panel Siding and Soffit

Installation Instructions for Panel Siding and Soffit Installation Instructions for Panel Siding and Soffit 7/16 in. Panels Include: Sturdy Panel, Square Edge, 3/4 in. Channel and Reverse Board and Batten (RB&B) 1/2 in. Panels Include: Adobe Shiplap and 808

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Music Area Casework General 1.01 Summary Related Sections Definitions Qualifications and Quality Assurance

Music Area Casework General 1.01 Summary Related Sections Definitions Qualifications and Quality Assurance 1.00 General 1.01 Summary Music Area Casework A. This section includes the following Scope of Work as referred to in the plans: 1. Thermally Fused Laminate manufactured casework, for use in music areas,

More information

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. PAGE 1 PART 1 GENERAL 1.1 REFERENCE.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. 1.2 RELATED WORK SPECIFIED ELSEWHERE.1 Installation

More information

The City of Winnipeg Section St. Vital Park Pavilion Page 1 of 1

The City of Winnipeg Section St. Vital Park Pavilion Page 1 of 1 The City of Winnipeg Section 06 10 13 WOOD BLOCKING AND CURBING St. Vital Park Pavilion Page 1 of 1 Part 1 General 1.1 SECTION INCLUDES.1 Roof curbs..2 Blocking in wall and roof openings..3 Wood furring

More information

eco-shake INSTALLATION INSTRUCTION

eco-shake INSTALLATION INSTRUCTION 1 eco-shake INSTALLATION INSTRUCTION NOTE: Shuffling the eco-shakes during installation may be necessary to obtain a uniform color throughout the roof. Due to the natural wood content in the ecoshakes,

More information

LP SmartSide Soffit ON SITE STORAGE PREPARATION. Application Instructions Vented and Non-Vented Smooth Finish or Cedar Texture. General Information

LP SmartSide Soffit ON SITE STORAGE PREPARATION. Application Instructions Vented and Non-Vented Smooth Finish or Cedar Texture. General Information Application Instructions Vented and Non-Vented Smooth Finish or Cedar Texture A B A - Open / Closed (Page 5) B - Vented (Page 6) ON SITE STORAGE Store off the ground well supported, on a flat well-drained

More information

A. Product Data: For each type of product indicated cabinet hardware and accessories, and finishing materials and processes.

A. Product Data: For each type of product indicated cabinet hardware and accessories, and finishing materials and processes. SECTION 06402 - INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

Section Rough Carpentry

Section Rough Carpentry Section 06 10 00 Rough Carpentry 06 10 00-1 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Blocking in wall and roof openings; wood furring and grounds; electrical panel back boards, concealed wood blocking.

More information

SECTION INTERIOR ARCHITECTURAL WOODWORK

SECTION INTERIOR ARCHITECTURAL WOODWORK SECTION 06 40 23 INTERIOR ARCHITECTURAL WOODWORK PART 1 GENERAL 1.01 SECTION INCLUDES A. Laminate clad cabinets and custom components. B. Laminate clad countertops. C. Cabinet hardware including countertop

More information

SECTION INTERIOR ARCHITECTURAL WOODWORK. A. Section includes interior woodwork items indicated not specified elsewhere and as specified.

SECTION INTERIOR ARCHITECTURAL WOODWORK. A. Section includes interior woodwork items indicated not specified elsewhere and as specified. SECTION 06 40 23 INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 SUMMARY A. Section includes interior woodwork items indicated not specified elsewhere and as specified. B. Options: 1. Where casework

More information

SECTION ASPHALT SHINGLES

SECTION ASPHALT SHINGLES SECTION 07311 ASPHALT SHINGLES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Asphalt shingle roofing. 2. Flexible sheet membranes for eave protection, underlayment, and valley protection. 3. Associated

More information

HOLLOW METAL DOORS AND FRAMES

HOLLOW METAL DOORS AND FRAMES SECTION 081113 HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Copyright 2017 AIA MasterSpec Premium 05/17 PRODUCT MASTERSPEC LICENSED BY ARCOM TO WEREVER PRODUCTS, INC.

Copyright 2017 AIA MasterSpec Premium 05/17 PRODUCT MASTERSPEC LICENSED BY ARCOM TO WEREVER PRODUCTS, INC. This Product MasterSpec Section is licensed by ARCOM to Werever Products, Inc. ("Licensee"). This proprietary Product MasterSpec Section uses modified original MasterSpec text. Revisions made to the original

More information

Kenai Courthouse Expansion 2007 Section 06100

Kenai Courthouse Expansion 2007 Section 06100 Kenai Courthouse Expansion 2007 Section 06100 Rough Carpentry SECTION 06100 - ROUGH CARPENTRY PART 1 GENERAL 1.01 SECTION INCLUDES A. Structural wall framing. B. Preservative treated wood materials. C.

More information

application instructions

application instructions application instructions architectural collection cedar shake 76 series lap siding General At the time of manufacture, siding meets or exceeds the performance standards set forth in Composite Panel Association

More information