ISO 9001:2000 SIA C. Dual Power Overcurrent Protection Relay INSTALLATION GUIDE. Guia_SIA-C_Rev / 32

Size: px
Start display at page:

Download "ISO 9001:2000 SIA C. Dual Power Overcurrent Protection Relay INSTALLATION GUIDE. Guia_SIA-C_Rev / 32"

Transcription

1 ISO 9001:2000 SIA Dual Power Overcurrent Protection Relay INSTALLATION GUIDE Guia_SIA-_Rev / 32

2 1.USER INTERFAE Revision A Revision B and Bistable magnetic indicators LED Indicators RS232 ommunication port LD and keypad SIom ommunications program Setting-up the session: Password and access levels FUNTIONAL DIAGRAM DIMENSIONS UTOUT PATTERN AND ONNETION DIAGRAMS Revision A utout mm Revision B utout mm onnection diagrams onnection diagrams. Three phase Ts and sensitive neutral: onnection diagrams. Three phase Ts and solid neutral: onnection diagrams. Three phase Ts for measuring and three phase Ts for supply and 1 T for sensitive neutral: onnection diagrams. Three phase Ts for measuring and three phase Ts for supply and solid neutral: Terminals Revision A Revision B and MODEL LIST PROTETION FUNTIONS AND SETTINGS Protections functions Function 50P. Phase instantaneous overcurrent Function 51P. Inverse time phase overcurrent Function 50N. Neutral instantaneous overcurrent Function 51N. Inverse time neutral overcurrent External trip Trip Bus Equipment settings urves IE255-4/BS Monitoring and control States and Events Self-diagnosis Date-time synchronisation ommunication Test program Guia_SIA-_Rev / 32

3 7.TEHNIAL SPEIFIATIONS AND STANDARDS Technical specifications FLOWHART Guia_SIA-_Rev / 32

4 1. USER INTERFAE 1.1. Revision A Leds LD (2x20 characters) Magnetic bistables Bistables reset Events erase Keypad RS Revision B and Revision B: 1 bistable Revision : 3 bistables LD (2x20 characters) Leds Magnetic bistables Keypad Bistables reset Events erase RS232 Guia_SIA-_Rev / 32

5 1.3. Bistable magnetic indicators The front panel is equipped with 3 bistable magnetic indicators which indicate the cause of the last trip. The indicators remain in position even when the equipment looses power, so that the maintenance service can see the cause of the trip even through the equipment is not powered. Once they have been activated, it is necessary to manually reset them by pressing the RESET button. The operation of the magnetic indicators can be checked from the test menu. Magnetic indicator 50P/51P activated Magnetic indicator 50/51N activated External trip magnetic indicator A trip has been caused by phase instantaneous overcurrent or phase inverse time overcurrent A trip has been caused by neutral instantaneous overcurrent or neutral inverse time overcurrent A trip has been caused by the activation of the direct trip input 1.4. LED Indicators The SIA- front panel has three LED pilot lights to show the type of power being used: self-power, battery or auxiliary power. The LEDs are switched off when the power type that they represent is not active, and they blink when the power type that they represent is active. Aside from showing the type of power that is being used by the equipment, one of the LEDs should be blinking under normal conditions. If they are all switched off, or some or all of them are permanently lit, this means that the equipment is not operational. Vaux LED Self-power LED Battery LED Activated (LED blinking) if it detects the auxiliary voltage Activated (LED blinking) if it detects the self-power current Activated (LED blinking) if it detects voltage from an external battery More than one type of power can be used simultaneously, and more than one LED can be activated as a result. The operation of the LED indicators can be checked from the test menu RS232 ommunication port The RS232 port can be found on the lower part of the front panel. The battery can be connected to this port through its kit, allowing the equipment to communicate with a local P and to be powered at the same time. P communication through the RS232 allows all the information and the settings parameters to be accessed LD and keypad The front of the SIA- relay is fitted with an alphanumeric LD screen, measuring 2x20. This screen provides the user with access to read information about the settings parameters, measurements, status and events. All of this information is arranged in a system of menus. Guia_SIA-_Rev / 32

6 A keypad is fitted to the relay front panel, which can be used to access the information shown on the LD screen and to navigate through the menu system. This membrane keyboard has 6 keys that can be used to navigate through the different menus and to change the setting parameters. The and keys can be used to navigate through the different menus, the different options in each menu and the different values for the settings parameters. The OK key is used to access the menus and the different options, as well as to approve changes to values. The key is used to delete and to go back through the menu levels. As well as the 6 keys, there is also a "Reset" key. When Reset is pressed, the bistable magnetic indicators return to their initial position. The Reset key can also be used to delete all of the events in the "Events" menu SIom ommunications program The SIcom program, which works with the Windows 2000/XP operating system is provided, and can be used to gain access to all of the equipment information, to modify the settings and to save events using a graphic user interface. The following operations can be carried out using the SIcom program: Status reading Measurement reading Reading and changing settings Reading and deleting events hanging the user passwords Loading settings files Date-time synchronisation hecking the versions of the equipment onfiguring the modbus address 1.8. Setting-up the session: Password and access levels Users must identify themselves with a password in order to start communications and to change the equipment settings or configuration using the HMI. Depending on the access level, it may or may not be possible to perform the operations shown on the table below. AESS LEVEL Read-only permission: Status and measurements Settings Permission to: hange settings Download and Delete the Events buffer Permission to: Execute ommands Permission to: hange onfiguration Permission to hange Protected Settings Events 1 YES YES NO NO YES 2 YES YES NO NO NO 3 YES NO YES NO NO 4 YES YES YES NO NO 5 YES YES YES YES NO Guia_SIA-_Rev / 32

7 Four passwords and their associated levels of access are set up when the equipment is configured using the SIcom program. By default, the equipment is programmed with the following passwords and their associated levels: PASSWORD AESS LEVEL The SIA- does not have a command feature. The SIA- does not have a protected settings feature. Guia_SIA-_Rev / 32

8 2. FUNTIONAL DIAGRAM 3. DIMENSIONS Guia_SIA-_Rev / 32

9 4. UTOUT PATTERN AND ONNETION DIAGRAMS 4.1. Revision A utout mm Frontal view 4.2. Revision B utout mm Frontal view Guia_SIA-_Rev / 32

10 4.3. onnection diagrams onnection diagrams. Three phase Ts and sensitive neutral: Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts Supply and measure 1 Sensitive neutral T Striker 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts Supply and measure 1 Sensitive neutral T AT + TM 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts Supply and measure 1 Sensitive neutral T AT 230Vac (by model) 24 Vdc (by model) Guia_SIA-_Rev / 32

11 onnection diagrams. Three phase Ts and solid neutral: Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts Supply and measure Solid neutral Striker 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts Supply and measure Solid neutral AT + TM 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts Supply and measure Solid neutral AT 230Vac (by model) 24 Vdc (by model) Guia_SIA-_Rev / 32

12 onnection diagrams. Three phase Ts for measuring and three phase Ts for supply and 1 T for sensitive neutral: Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts for supply 3 Ts for measure 1 Sensitive neutral T Striker 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Disparo Power Supply Optional Power Supply 3 Ts for supply 3 Ts for measure 1 Sensitive neutral T AT + TM 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Disparo Power Supply Optional Power Supply 3 Ts for supply 3 Ts for measure 1 Sensitive neutral T AT 230Vac (by model) 24 Vdc (by model) Guia_SIA-_Rev / 32

13 onnection diagrams. Three phase Ts for measuring and three phase Ts for supply and solid neutral: Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts for supply 3 Ts for measure Solid neutral Striker 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts for supply 3 Ts for measure Solid neutral AT + TM 230Vac (by model) 24 Vdc (by model) Phase Ts Neutral mode Trip Power Supply Optional Power Supply 3 Ts for supply 3 Ts for measure Solid neutral AT 230Vac (by model) 24 Vdc (by model) Guia_SIA-_Rev / 32

14 4.4. Bornas Revision A Revision B and Guia_SIA-_Rev / 32

15 A1 Phase A current input for measurement D5 Positive for the inputs A2 Phase A current output for measurement D6 Digital input 1 A3 Phase B current input for measurement D7 Digital input 2 A4 Phase B current output for measurement D8 ommon digital input A5 Phase current input for measurement D9 Ground A6 Phase current output for measurement D10 Digital output 1 N A7 Neutral current input for measurement D11 Digital 1 common output A8 Neutral current output for measurement D12 Digital output 1 NA B1 Phase A current input for power supply D13 Digital output 2 N B2 Phase A current output for power supply D14 Digital 2 common output B3 Phase B current input for power supply D15 Digital output 2 NA B4 Phase B current output for power supply D16 Trip output positive / AT free potential output B5 Phase current input for power supply D17 Trip output gnd / AT free potential output B6 Phase current output for power supply D18 RS485 ground D1 Auxiliary Voltage - D19 RS485 B - D2 Auxiliary Voltage + D20 RS485 A + D3-D4 External trip Earthing screw Guia_SIA-_Rev / 32

16 5. MODEL LIST TYPE PHASE MEASUREMENT NEUTRAL MEASUREMENT NETWORK FREQUENY POWER SUPPLY EXTRA FUNTIONS OMMUNIATIONS INPUTS/OUTPUTS PROESSORS AND MEMORY LANGUAGE REVISION 50P+51P+50N+51N A 5 A A 5 A Hz 60 Hz Vdc + Selfpowered 12 Vdc + Selfpowered Vac 12 Vdc + Selfpowered Vac 12 Vdc + Selfpowered + 24 Vdc With striker and without external trip With striker and with external trip With potential free contact and without external trip With potential free contact and with external trip 0 1 ModBus Local (RS 232). ModBus Local (RS 232) y Scada (485) Without inputs/outputs Signalling outputs Trip bus Without non volátil RAM memory With non volátil RAM memory With non volátil RAM memory and fast startup A B English, Spanish and French English, Spanish, French and Turkish English, Spanish, French and Polish A B Vertical Assembly Horizontal assembly with 1 FLAG bistable Horizontal assembly with 3 FLAG bistables Guia_SIA-_Rev / 32

17 6. PROTETION FUNTIONS AND SETTINGS 6.1. Protections functions Function 50P. Phase instantaneous overcurrent Function Description Minimum Maximum Step Unit Default 50P Phase instantaneour overcurrent Permission - - Yes/No - No Tap 0,10 30,00 0,01 Inominal 5,00 Operating time 0,02 300,0 0,01 s 0, Function 51P. Inverse time phase overcurrent Function Description Minimum Maximum Step Unit Default 51P Inverse time phase overcurrent Permission - - Yes/No - No urve - - (1*) - Extremely inverse Dial 0,05 1,25 0,01-1,25 Tap 0,10 7,00 0,01 I nominal 1,00 Operating time 0,02 300,0 0,01 s 0,02 (1*) Inverse, Very inverse, Extremely inverse, Defined time Function 50N. Neutral instantaneous overcurrent. Function Description Minimum Maximum Step Unit Default 50N Neutral instantaneous overcurrent Permission - - Yes/No - No Tap 0,10 30,00 0,01 I nominal 1,00 Operating time 0,02 300,0 0,01 s 0,02 Guia_SIA-_Rev / 32

18 Function 51N. Inverse time neutral overcurrent. Function Description Minimum Maximum Step Unit Default 51N Inverse time neutral overcurent Permission - - Yes/No - No urve - - (1*) - Extremely inverse Dial 0,05 1,25 0,01-1,25 Tap 0,10 7,00 0,01 I nominal 0,50 Operating time 0,02 300,0 0,01 s 0,02 (1*) Inverse, Very inverse, Extremely inverse, Defined time External trip The equipment has a direct trip input, normally connected to a bimetallic contact fitted to the power transformer. This serves as a backup to the overcurrent functions. The input is operational from 0.3 times the secondary rated current in case of single phase, allowing connecting a potential-free bimetallic contact which, when closed, activates the input. This input is especially protected against magnetic noise Trip Bus Function 68 allows the creation of a coordinated net of equipments installed in different levels of the line which enables the blocking or the tripping and whose objective is clearing the fault in the least damaging place of the application. phase blocking input ground blocking input SIA- supply phase pickup phase pickup ground pickup SIA- feeder a ground pickup SIA- feeder b Guia_SIA-_Rev / 32

19 Function Description Minimum Maximum Step Unit Default TRIP BUS Trip Bus Aplication - - (1*) - No activated Permission trip bus 50P - - Yes/No - Yes Permission trip bus 51P - - Yes/No - Yes Permission trip bus 50N - - Yes/No - Yes Permission trip bus 51N - - Yes/No - Yes Phase blocking time ,01 s 0 Neutral blocking time ,01 s 0 Phase blocking signalling time ,01 s 0 Neutral blocking signalling time ,01 s 0 (1*) No activated, Feeder, Supply, Feeder and Supply Equipment settings The SIA- settings are listed below: Group Description Minimum Maximum Step Unit Default Generales Equipment identifier enter your text TI phase ratio TI neutral ratio Frequency /50 Hz 50 Language ENGLISH urves IE255-4/BS142 The SIA- relay complies with the curves shown in standard IE255-4/BS-142: Inverse urve Very Inverse urve Extremely Inverse urve There is a general mathematical equation that defines the time in seconds as a function of the current: Guia_SIA-_Rev / 32

20 Guia_SIA-_Rev / 32

21 6.2. Monitoring and control States and Events Group State ause Associated Event Phase inverse time overcurrent 51P 51P Phase A pick-up Activation/Deactivation Phase A current 51P Phase B pick-up Activation/Deactivation Phase B current 51P Phase pick-up Activation/Deactivation Phase current 51P Pick-up Activation/Deactivation - 51P A Trip Activation/Deactivation Phase A current 51P B Trip Activation/Deactivation Phase B current 51P Trip Activation/Deactivation Phase current 51P Trip Activation - Instantaneous phase overcurrent 50P 50P Phase A pick-up Activation/Deactivation Phase A current 50P Phase B pick-up Activation/Deactivation Phase B current 50P Phase pick-up t Activation/Deactivation Phase current 50P Pick-up Activation/Deactivation - 50P A Trip Activation/Deactivation Phase A current 50P B Trip Activation/Deactivation Phase B current 50P Trip Activation/Deactivation Phase current 50P Trip Activation - Neutral inverse time overcurrent 51N 51N Pick-up Activation/Deactivation Neutral current 51N Trip Activation Neutral current Instantaneous neutral overcurrent 50N 50N Pick-up Activation/Deactivation Neutral current 50N Trip Activation Neutral current Trip Bus Blocking 50P Activation/Deactivation - Blocking 51P Activation/Deactivation - Blocking 50N Activation/Deactivation - Blocking 51N Activation/Deactivation - Guia_SIA-_Rev / 32

22 Blocking signalling 50P Activation/Deactivation - Blocking signalling 51P Activation/Deactivation - Blocking signalling 50N Activation/Deactivation - Blocking signalling 51N Activation/Deactivation - Generals Trip Activation/Deactivation The maximum phase current between the activation of the trip and the deactivation of the event. External trip Activation/Deactivation - Trip circuit error Activation/Deactivation - Measurement error Activation/Deactivation - Protection error Activation/Deactivation - hange of settings Activation/Deactivation - Date-time adjustment Activation/Deactivation - Local communication Activation/Deactivation - Eeprom by default Activation/Deactivation - Eeprom Error Activation/Deactivation - Eeprom change Activation/Deactivation - Events error Activation/Deactivation - Auxiliary power Activation/Deactivation - Self power Activation/Deactivation - Battery power Activation/Deactivation - Equipment start Activation/Deactivation - Outputs Output 1 Activation/Deactivation - Output 2 Activation/Deactivation - Local communication Local communication - - HMI Activity Guia_SIA-_Rev / 32

23 Self-diagnosis Diagnostic algorithms are run while the equipment is being started up and continuously when the relay is operating. This diagnostic is a preventative process to guarantee that the equipment is in good operational condition. As general considerations, we should point the following: The communications between different processors are confirmed by the corresponding integrity checking. In continuous anomalies occur, the equipment will be reset. Data related to set values are confirmed by the corresponding checking. Also, all tables showing set values are doubled, and the relay will have the capability of operating with a damaged table, but not with two damaged tables. There is a WatchDog mechanism both between and in main PUs. If any PU goes out of operation the equipment will be reset and this condition will be identified as an event. The following status bits are associated with this process: Trip circuit error Measurement error Protection error Eeprom Error Events Error Problem in the trip circuit Problem in the measurement block Problem in the protection block Problem in the eeprom memory, default settings Error in the events register On the other hand, Default settings means that the equipment is operating under factory settings, being all protection functions disabled Date-time synchronisation The SIA- relay has a real time clock (RT) in all its models, which can be synchronized from the hmi or communications. The RT maintains the updated date for at least 72 hours even without any power supply. harging time of RT capacitor is 10 minutes. The clock can be synchronized by means of any of the two following procedures: From the HMI. In this case the date and time can be entered via the keyboard. The relay will store the new event indicating that it has been synchronized. Protocol. The behaviour is identical to the HMI. The relay will synchronize the date and time, and a new synchronization event is carried out ommunication The SIA- relay can communicate with a local computer through its front RS232 port, or through a remote SADA system through the rear RS485 port. The rear RS485 port is optional and must be specified on the list of models. The ports RS232 and RS485 are switched. The RS232 port has preference. When started, the equipment is switched to remote communication (RS485) provided no key in the HMI is pressed or no local communication (RS232) is tried Test program The SIA- equipment has a test menu that can be used to check the operation of the signalling components (LEDs and magnetic indicators), along with the trip output and the signalling outputs. This check is operative regardless of the type of power that is used. Guia_SIA-_Rev / 32

24 This means that the trip circuit and the signalling outputs can be tested with just a simple battery or a 12V battery in a facility without electricity supply. The following table shows the components that can be tested, along with their status depending on whether they are activated or deactivated: Vaux power LED Self-power LED Battery LED 50/51P magnetic indicator 50/51N magnetic indicator External trip magnetic indicator Trip output (*) Signalling output 1 Signalling output 2 Deactivated Activated Deactivated Activated Deactivated Activated Deactivated Activated Deactivated Activated Deactivated Activated Deactivated Activated Deactivated Activated Deactivated Activated Vaux LED off Vaux LED blinking Self-power LED off Self-power LED blinking Battery LED off Battery LED blinking 50/51P magnetic indicator deactivated (black) 50/51P magnetic indicator activated (orange) 50/51N magnetic indicator deactivated (black) 50/51N magnetic indicator activated (orange) External trip magnetic indicator deactivated (black) External trip magnetic indicator activated (orange) Trip output deactivated Trip output activated Output 1 deactivated Output 1 activated Output 2 deactivated Output 2 activated (*) When self-power values are low or the battery is at the limit of its capacity, it is possible that the equipment may initialise. This is completely normal. The following key sequence is used to gain access to the test menu: from the main menu, press the keys,, and in sequence and then press and hold the "OK" key until the "Test menu" appears on the display. The test menu is accessed by pressing the "OK" key again, and the and keys can be used to navigate through the different menu items. Each item can be activated or deactivated by pressing "OK" on it (if the item is deactivated, it is activated by pressing OK; if the item is activated, it is deactivated by pressing OK ). Press the key to exit the test menu. To obtain more detailed information, the method for navigating the menus is explained graphically in the keypad and display section. Guia_SIA-_Rev / 32

25 7. TEHNIAL SPEIFIATIONS AND STANDARDS 7.1. Technical specifications External trip input harge level of 0,3 xin in single-phase Striker Trip output 24 Vdc 576 mj Activates the striker of the coil with the TM Potential Free trip output 250 Vac 8A 30 Vdc 8A Resisitive load (cos φ = 1) Activates the coil Signalling outputs Signalling inputs Frequency urrent measure 220 Vdc 1 A (30 W max) 250 Vac 1 A (62,5 VA max) Resisitive load (cos φ = 1) 5-24 Vdc 0,25 VA 50/60Hz RMS Sampling: 16 samples/cycle Accuracy ±2% in Inominal current ± 20%, and ±5% in the rest of the range ommunication RS232 port: Modbus RTU RS485port: Modbus RTU Auxiliary supply 230 Vca, ±20 % 110 Vca, ±20 % 24 Vcc Battery supply With adapter (Kitcom) port DB9 Self-power from current One phase self-power level: I > 0,2 x In Environment Operating temperature: -10 to 60º Storage temperature: -20 to 70 º Humidity: 95% Transformers Power supply and measurement T /5 or /1 Mechanical features Metallic box Panel Mounting 1/3 Rack 4 U IP-52 Guia_SIA-_Rev / 32

26 ISO 9001: FLOWHART OK OK hold Enter lower submenu Back upper submenu Navigate inside menu Direct access Direct access Enter numerical value Sequence for VERSIONS Sequence for TEST MENU SIA AA OK MEASUREMENTS States 1/4 OK IA = 0.00 A 2/4 IB = 0.00 A 3/4 I = 0.00 A 4/4 IO = 0.00 A States 50P OK OK Phase A Pickup: Phase B Pickup: Phase Pickup: Phase Pickup: Phase A Trip: Phase B Trip: Guia_SIA-_Rev / 32

27 Phase Trip: Phase Trip: States 51P OK Phase A Pickup: Phase B Pickup: Phase Pickup: Phase Pickup: Phase A Trip: Phase B Trip: Phase Trip: Phase Trip: States 50N OK Ground Pickup: Ground Trip: States 51N OK Ground Pickup: Ground Trip: States GNAL >Activated OK Trip: External Trip: Guia_SIA-_Rev / 32

28 SETTINGS GEN TripPower error: 50 Hz: <<ATIVATED>> Mag.M. error: Measure error: Ready: <<ATIVATED>> Protecti error: Setting change: Set Date/Time: Telecontrol NO: <<ATIVATED>> FactorySetting: Eeprom error: Eeprom changed: Event error: States OUTPUTS OK Output 1: Output 2: States LOAL >Activated OK Local OM.: MMI Activity: <<ATIVATED>> Guia_SIA-_Rev / 32

29 Settings 50P OK Function Enable NO OK OK urrent Tap: 5.00 xin(1.00) Time Delay 0.02 s Set Password -> 0 Set Password -> 5555 OK Function Enable NO -> NO Settings 51P Function Enable NO -> YES Function Enable NO OK OK urve type: ExtrInv Time Dial: 1.25 urrent Tap: 1.00 xin(1.00) Time Delay 0.02 s Function Enable NO > YES y/n SETTING HANGED OK Function Enable Function Enable OK YES Settings 50N OK Function Enable NO urrent Tap: 1.00 xin(1.00) Time Delay 0.02 s Settings 51N OK Function Enable NO urve type: ExtrInv Time Dial: 1.25 urrent Tap: 0.50 xin(1.00) Time Delay 0.02 s Set Password OK -> 0 Set Password -> 5555 Time Dial OK > 0 Guia_SIA-_Rev / 32

30 Identification enter your text T Phase Ratio 1 T Neutro Ratio 1 Frequency 50 Hz Language ENGLISH Time Dial > 0.5 Time Dial OK 1.25 > 0.5 y/n SETTING HANGED OK Time Dial Time Dial: OK 0.50 EVENTS There are 1 01/01/00 01:00:05675 OK Events erased 1/1: 0 OK Events erased DATE AND TIME 01/01/ :43:25 OK 01/01/ :43 Vers: OM DSP PI OK TEST MENU y/n? without protection! hold Set Password OK -> 0 Set Password -> 5555 OK TEST MENU V. aux Led: OK V. aux Led: OK OK <<ATIVATED>> self-power Led: self-power Led: OK OK <<ATIVATED>> battery Led: Guia_SIA-_Rev / 32

31 battery Led: OK OK <<ATIVATED>> 50P/51P bistable: 50P/51P bistable: OK OK <<ATIVATED>> 50N/51N bistable: 50N/51N bistable: OK OK <<ATIVATED>> ext trip bistable: ext trip bistable: OK OK <<ATIVATED>> Trip ontact: Trip ontact: OK OK <<ATIVATED>> Output 1: Output 1: OK OK <<ATIVATED>> Output 2: Output 2: OK OK <<ATIVATED>> Guia_SIA-_Rev / 32

32 FANOX ELETRONI S.L. Parque Tecnológico de Bizkaia Astondo bidea, Edif DERIO ESPAÑA Tel Fax power-td@fanox.com Guia_SIA-_Rev / 32

SIA-C Dual & Self powered overcurrent & earth fault relay USER S MANUAL. EN_FANOXTD_MANU_SIA_Ocefsecondarydist_SIAC_R039.Docx

SIA-C Dual & Self powered overcurrent & earth fault relay USER S MANUAL. EN_FANOXTD_MANU_SIA_Ocefsecondarydist_SIAC_R039.Docx SIA- Dual & Self powered overcurrent & earth fault relay USER S MANUAL EN_FANOXTD_MANU_SIA_Ocefsecondarydist_SIA_R039.Docx 1. REEPTION, HANDLING, INSTALLATION... 6 1.1. Unpacking... 6 1.2. Reception of

More information

CT08-5 Taped A 5P80 CT16-5 Taped A 5P80. * In is the value of the primary nominal current of the transformer.

CT08-5 Taped A 5P80 CT16-5 Taped A 5P80. * In is the value of the primary nominal current of the transformer. SI-B Overcurrent and Earth Fault Protection Relay for Secondary istribution ual & Self Powered Main characteristics The SI-B is a ual & Self powered overcurrent protection relay using the operating current

More information

PBM. Motor management system USER S MANUAL. EN_PBM_User-Manual_R011.Docx

PBM. Motor management system USER S MANUAL. EN_PBM_User-Manual_R011.Docx PBM Motor management system USER S MANUAL EN_PBM_User-Manual_R011.Docx 1. RECEPTION, HANDLING, INSTALLATION... 6 1.1. Unpacking... 6 1.2. Reception of relays... 6 1.3. Handling electronic equipment...

More information

PD300. Transformer, generator and motor protection Data sheet

PD300. Transformer, generator and motor protection Data sheet PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information

PLA 33. Power line analyzer. User and service manual. version 2.4

PLA 33. Power line analyzer. User and service manual. version 2.4 PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

ENA33LCD. Power line analyzer. User and service manual. Obrezija 5 SI-1411 Izlake

ENA33LCD. Power line analyzer. User and service manual.   Obrezija 5 SI-1411 Izlake ENA33LCD Power line analyzer User and service manual version 2.9 (FW version 6.8 and newer) ETI, d.o.o. Obrezija 5 SI-1411 Izlake www.etigroup.eu/products-services 1. Front control panel and terminal plate

More information

FMR. Ultra Line FEEDER MANAGER RELAY

FMR. Ultra Line FEEDER MANAGER RELAY Ultra Line FEEDER MANAGER RELAY Protective Functions F49 : One Thermal Image element F50/51/67 : Three levels for phase overcurrent independentely programmable as directional or non directional F50N/51N/67N

More information

Digital Line Protection System

Digital Line Protection System Digital Line Protection System! Microprocessor Based Protection, Control and Monitoring System! Waveform Sampling! Proven Protection! Economical! Ease of Retrofit 1 DLP-D D Enhancements ASCII SUBSET Three

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

SVP CONTROL AND VISUALIZATION OF VOLTAGE, PHASE AND FREQUENCY IN THREE-PHASE LINES WITH NEUTRAL

SVP CONTROL AND VISUALIZATION OF VOLTAGE, PHASE AND FREQUENCY IN THREE-PHASE LINES WITH NEUTRAL 1/5 CONTROL AND VISUALIZATION OF VOLTAGE, PHASE AND FREQUENCY IN THREE-PHASE LINES WITH NEUTRAL Function Operating mode Voltage control Phase sequence control Control unbalance Ln-Ln Control unbalance

More information

e 2 TANGO-50 Short-Circuit Detector K Data Sheet

e 2 TANGO-50 Short-Circuit Detector K Data Sheet e 2 TANGO-50 Short-Circuit Detector K-31.2.1 Data Sheet We Create Ideas With Power! e 2 TANGO-50 short-circuit detector is a product of ELEKTROMETAL ENERGETYKA SA developed by our engineers with extensive

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

SUPPLY NETWORK ANALYZER. CVMk SERIES. CVMk-4C SERIES INSTRUCTION MANUAL. ( M / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A.

SUPPLY NETWORK ANALYZER. CVMk SERIES. CVMk-4C SERIES INSTRUCTION MANUAL. ( M / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A. SUPPLY NETWORK ANALYZER CVMk SERIES & CVMk-4C SERIES INSTRUCTION MANUAL ( M 981 171 / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A. ----- Supply network analyzer CVMk and CVMk-ITF ------ Manual 1 / 2 --- Page

More information

Earth Leakage Monitoring System IsoBase IsoHub IsoOut

Earth Leakage Monitoring System IsoBase IsoHub IsoOut 2014 11 21 Earth Leakage Monitoring System IsoBase IsoHub IsoOut User Manual Due to our policy of continual improvement, specifications may change without prior notice Page 2 (34) Contents Earth Leakage

More information

Commissioning Instructions Rev. 03

Commissioning Instructions Rev. 03 Power Factor regulator BLR-CM-T/RT L1 L2 L3 Einspeisung Supply Last Load BLR-CM-T + - Triggereingang/ Triggerinput BEL-TSXX N PE L1 L2 L3 Einspeisung Supply Last Load BLR-CM-RT + - Triggereingang/ Triggerinput

More information

SPECIFICATION FOR OVERCURRENT RELAYS

SPECIFICATION FOR OVERCURRENT RELAYS SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous

More information

MBD-8F Automatic Antenna Switch Controller

MBD-8F Automatic Antenna Switch Controller - 1 - MBD-8F Automatic Antenna Switch Controller MBD-8F is an intelligent controller compatible with all eight-antenna switches manufactured by Hamplus. It has a band decoder to receive the information

More information

NETWORK ANALYZERS Analyzers

NETWORK ANALYZERS Analyzers CONTENTS PRODUCTS RANGE NA.03 NETWORK ANALYZER - LCC NETWORK ANALYZER - LCA NETWORK ANALYZER - LDA NETWORK ANALYZER - LAB96 NETWORK ANALYZER - LABM NA.04 NA.06 NA.09 NA.10 NA.13 NETWORK ANALYZER - LCCM

More information

Protection Relays. U-MLEs-PLv-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80

Protection Relays. U-MLEs-PLv-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80 Ultra-Ts DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80 D.C. Feeder protection relay with setting parameters programmable locally or via serial communication. Suitable

More information

Transformer Protection M 3310

Transformer Protection M 3310 PROTETION Transformer Protection M 3310 Integrated Protection System for Transformers of ll Sizes Unit shown with optional M 3931 HMI Module and M 3910 Target Module Fully Digital Multifunction Relay with

More information

REF 610 Feeder Protection Relay. Technical Reference Manual

REF 610 Feeder Protection Relay. Technical Reference Manual REF 610 1MRS 755310 Issued: 05.10.2004 Version: A/05.10.2004 REF 610 Contents 1. Introduction...6 1.1. About this manual...6 1.2. The use of the relay...6 1.3. Features...6 1.4. Guarantee...8 2. Safety

More information

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE)

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE) USER MANUAL ATS-I Tel.+39.0522.832004 P1/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.1/17 Index General description...3 Electrical specifics...3 Device operative logic...4 Manual mode...4

More information

Protection Relays. U-MLEs-PLv. Ultra Line. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80

Protection Relays. U-MLEs-PLv. Ultra Line. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80 Ultra Line DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 3, 45, 49, 64, 76, 79, 80 D.C. Feeder protection relay with setting parameters programmable locally or via serial communication. Suitable

More information

Protection Relays. U-MLEs-PLs-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (single voltage Line Test) 32, 45, 49, 64, 76, 79, 80

Protection Relays. U-MLEs-PLs-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (single voltage Line Test) 32, 45, 49, 64, 76, 79, 80 Ultra-Ts DC SUBSTATION PROTECTIVE RELAY (single voltage Line Test) 32, 45, 49, 64, 76, 79, 80 D.C. Feeder protection relay with setting parameters programmable locally or via serial communication. Suitable

More information

ULTRA RAPID POWER QUALITY ANALYZER

ULTRA RAPID POWER QUALITY ANALYZER ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with

More information

vacon 100 ac drives application manual

vacon 100 ac drives application manual vacon 100 ac drives application manual vacon 0 INDEX Document: DPD00927D Version release date: 5.5.12 Corresponds to software package FW0072V00.vcx 1. Vacon 100 - Startup... 2 1.1 Startup Wizard... 2

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

RUDOLF Digital power analyzer. Advanced Version

RUDOLF Digital power analyzer. Advanced Version RUDOLF Digital power analyzer Advanced Version Digital power analyzer Advanced Version Company Introduction Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

IDA 4 XM V 1.X. Installation and configuration of IDA 4 XM User Manual

IDA 4 XM V 1.X. Installation and configuration of IDA 4 XM User Manual IDA 4 XM V 1.X Installation and configuration of IDA 4 XM User Manual IMPORTANT SAFETY INSTRUCTIONS - Switch the device s power off before any maintenance operation (changing the CU card, etc.) - The 24V

More information

WPE 48N USER MANUAL Version1.1

WPE 48N USER MANUAL Version1.1 Version1.1 Security instructions 1. Read this manual carefully. 2. Follow all instructions and warnings. 3. Only use accessories specified by WORK PRO. 4. Follow the safety instructions of your country.

More information

Kyongbo Electric Co., Ltd.

Kyongbo Electric Co., Ltd. Digital Motor Protection Relay User's Manual TYPE : GDR-M02 2010. 04. 12 Version 1.00 Kyongbo Electric Co., Ltd. 1 / 76 KyongBo Electric Co.,Ltd Safety Precautions This document is for the safety of the

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual vacon 1 TABLE OF CONTENTS Document: DPD01083A Version release date: 16.11.12 Corresponds to software package FW0159V121106.vcx 1. Vacon 100 FLOW - Quick Startup

More information

ASHIDA Numerical OC/EF Protection Relay

ASHIDA Numerical OC/EF Protection Relay ASHIDA Numerical OC/EF Protection Relay Features: 4 Element (3 Phase + EF) over current IDMT with instant trip. Back - lit LCD display for settings. Display of fault current. / Load current. Selection

More information

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12 INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

MiCOM P120, P121, P122 and P123 Universal Overcurrent Relays

MiCOM P120, P121, P122 and P123 Universal Overcurrent Relays MiOM P120, P121, P122 and P123 : Universal Overcurrent Relays MiOM P120, P121, P122 and P123 Universal Overcurrent Relays T & D Energy utomation & Information MiOM P120, P121, P122 and P123 whole range

More information

Application and features

Application and features Power Measurement Unit PM 2214 Power Measurement Unit PM 2214 Application and features PM 2214 Power supervision / SCADA system Feeder automation / Customized 0.05% high accuracy Cost saving for 4 feeder

More information

Appendix A. Datum Systems PSM-2100/512 Satellite Modem. Technical Specification

Appendix A. Datum Systems PSM-2100/512 Satellite Modem. Technical Specification Appendix A Datum Systems PSM-2100/512 Satellite Modem Technical Specification PSM-2100 and PSM-512 VSAT / SCPC - Modem Specification Revision History Rev 1.0 6-15-97 Preliminary Release. Rev 1.1 10-10-97

More information

presentation contents application advantages

presentation contents application advantages presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual PREFACE VACON 3 PREFACE Document ID: DPD01083D Date: 15.10.2014 Software version: FW0159V010 ABOUT THIS MANUAL This manual is copyright of Vacon Plc. All Rights

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

SVAC3. 400W AC Powered Servo Drive. Accessories C IP IP IP C IP. Control Options* For more information, visit:

SVAC3. 400W AC Powered Servo Drive. Accessories C IP IP IP C IP. Control Options* For more information, visit: Feedback E = Encoder board 3 = 3.5A cont, 7.4A peak, 120VA 1.8A cont, 5.4A peak, 220VA ontrol S = Basic version Q = Q Programming = EtherNet/ BLuA5-Si SVA3-S-E120 SVA3-S-E220 SVA3-Q-E120 SVA3-Q-E220 SVA3--E120

More information

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges. APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring

More information

SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE

SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE 1.0 GENERAL SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE STANDARD: OES-22F THREE PHASE KILOWATT-HOUR DIGITAL METERS, CURRENT TRANSFORMER OPERATED, CONNECTED FOR SERVICE CONNECTIONS Electronic three

More information

REB500 TESTING PROCEDURES

REB500 TESTING PROCEDURES Activate HMI 500/REBWIN ver 6.10 or 7.xx. The following screen will appear. Check out the Read Only box & type the password System. Click ok. Connect the black communication cable from the Com port until

More information

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with

More information

PQM3000RGW Class A rack 19 power quality analyzer with Rogowski coils

PQM3000RGW Class A rack 19 power quality analyzer with Rogowski coils Class A rack 19 power quality analyzer with Rogowski coils Rack 19 mounting Current inputs for direct connection of Rogowski coils Harmonics and interharmonics measurement Data recording for further EN

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

Multifunction network analyzer Q15U Q96U2L - Q96U4... Q15E Q96E MCU - MCUH Programmable transducer MCUU

Multifunction network analyzer Q15U Q96U2L - Q96U4... Q15E Q96E MCU - MCUH Programmable transducer MCUU Multifunction network analyzer Q15U2... - Q96U2L - Q96U4... Q15E2... - Q96E2... - MCU - MCUH Programmable transducer MCUU OPERATING MANUAL Ipm0163.8 - Edition 06.09 Langer Messtechnik GmbH Soyerhofstrasse

More information

FCR 06, FCR 12. Power factor correction controller. User and service manual

FCR 06, FCR 12. Power factor correction controller. User and service manual FCR 06, FCR 12 Power factor correction controller User and service manual version 2.3 Czech Republic Czech Republic 1 Content 1. Control and signal elements... 3 2. Device description... 4 3. Instruction

More information

DIVISIONE ELETTRONICA E SISTEMI UHR4N DIGITAL MULTIFUNCTION PROTECTION RELAY 100% AND 95% GENERATOR STATOR EARTH FAULT USER MANUAL

DIVISIONE ELETTRONICA E SISTEMI UHR4N DIGITAL MULTIFUNCTION PROTECTION RELAY 100% AND 95% GENERATOR STATOR EARTH FAULT USER MANUAL DIVISIONE ELETTRONICA E SISTEMI UHR4N DIGITAL MULTIFUNCTION PROTECTION RELAY 100% AND 95% GENERATOR STATOR EARTH FAULT USER MANUAL P500D824 September 2004 INDEX INDEX 1 GENERAL CHARACTERISTICS... 1 1.1

More information

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Generator Protection M 3420

Generator Protection M 3420 PROTECTION Generator Protection M 3420 Integrated Protection System for Generators of All Sizes Unit shown with optional M 3920 Target Module and M 3931 HMI (Human-Machine Interface) Module Microprocessor-based

More information

Kyongbo Electronics Co., Ltd.

Kyongbo Electronics Co., Ltd. Digital Overcurrent & Ground Overvoltage & Selective Ground Relay Manual TYPE : GDR-AEF01 2006. 7. 18 Version 1.00 Kyongbo Electronics Co., Ltd. Safety Precautions This document is for the safety of the

More information

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time IRD SCOPE This test procedure covers the testing and maintenance of Westinghouse IRD relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to

More information

Energy Management Energy Meter Type EM111

Energy Management Energy Meter Type EM111 Energy Management Energy Meter Type EM111 Easy connection or wrong current direction detection Other versions available (not certified, option X: see how to order on the next page Single phase energy meter

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

Energy Management Energy Meter Type EM112

Energy Management Energy Meter Type EM112 Energy Management Energy Meter Type EM112 Easy connection or wrong current direction detection Other versions available (not certified, option X: see how to order on the next page Single phase energy meter

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

Position Indicator model MFC-300/IP. Technical Manual. Licht

Position Indicator model MFC-300/IP. Technical Manual. Licht Position Indicator model MFC-300/IP Technical Manual Licht Contents 1 Introduction 2 2 Front panel indication 3 3 Error indication 4 4 Manual commands 5 5 Configuration 6 5.1 Parameter reset 6 6 Programmable

More information

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA

More information

SYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.

SYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A. SYNCHRONISM RELAY SYNCRO-96 (Code 2 28 913-2 28 914-2 28 915) INSTRUCTION MANUAL ( M 981 196 / 99A ) (c) CIRCUTOR S.A. ----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 1 Synchronism relay

More information

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet PowerLogic power-monitoring units PM700 series power meter Technical data sheet 2009 Functions and characteristics The PowerLogic PM700 series power meter offers all the measurement capabilities required

More information

SUPPLY NETWORK ANALYZER CVM-96 SERIES

SUPPLY NETWORK ANALYZER CVM-96 SERIES SUPPLY NETWORK ANALYZER CVM-96 SERIES (Power Demand) INSTRUCTION MANUAL ( M 981 326 / 00B - GB) (c) CIRCUTOR S.A. ----- Supply network analyzer CVM-96 ------ User's manual --- Page No. 1 CVM-96 SUPPLY

More information

Prometer 100. User Manual. High-precision meter BGX R01

Prometer 100. User Manual. High-precision meter BGX R01 Prometer 100 High-precision meter User Manual BGX501-943-R01 Copyright 2014, SIHPL Page 2 of 72 Prometer 100 User Manual BGX501-943-R01 Table of Contents 1 Important Safety Information... 5 2 Disclaimer...

More information

PQM3000 Class A rack 19 power quality analyzer for CTs or current clamps

PQM3000 Class A rack 19 power quality analyzer for CTs or current clamps Class A rack 19 power quality analyzer for CTs or current clamps Two different models, for CTs or current clamps Rack 19 mounting Harmonics and interharmonics measurement Data recording for further EN

More information

AQ F201 Overcurrent and Earthfault

AQ F201 Overcurrent and Earthfault INSTRUCTION MANUAL AQ F201 Overcurrent and Earthfault Relay Instruction manual AQ F201 Overcurrent and Earth-fault Relay 2 (198) Revision 1.00 Date 8.1.2013 Changes - The first revision for AQ-F201 Revision

More information

PQM4000RGW Class A DIN 192x144 power quality analyzer with Rogowski coils

PQM4000RGW Class A DIN 192x144 power quality analyzer with Rogowski coils Class A DIN 192x144 power quality analyzer with Rogowski coils Current inputs for direct connection of Rogowski coils Harmonics and interharmonics measurement Data recording for further EN 50160 analysis

More information

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

T 1000 PLUS Secondary Injection Relay Test Set

T 1000 PLUS Secondary Injection Relay Test Set Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

Synchroniser Relay SYN-7

Synchroniser Relay SYN-7 Synchroniser Relay SYN-7 1/19 Index 1 General Remarks...3 2 Operating Principle...3 2.1 Isolated Operation (Firmware Version V1.14 or higher)...4 2.2 Usage as a locking Relay...4 2.3 Switching onto Dead

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator High power outputs Large graphical display Compact

More information

Specification DataFile

Specification DataFile DATUM U & U Ultrasonic Level System Specification DataFile 6-digit backlit l.c.d. and bargraph clear display of measured level Echo Processing using 'DATEM' software true level measurement, overcoming

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

ENGLISH. General features 2. Technical features 3. Installation 10. Preliminary operations 12. Front panel description 13.

ENGLISH. General features 2. Technical features 3. Installation 10. Preliminary operations 12. Front panel description 13. LDI 35 OPERATING INSTRUCTIONS General features 2 Technical features 3 Installation 10 Preliminary operations 12 Front panel description 13 Operating mode 15 Important: We suggest you keep the original

More information

DIGITAL EARTH FAULT RELAY

DIGITAL EARTH FAULT RELAY DIGITAL IDMT / DEFINITE TIME / INSTANTANEOUS Features ŸCompact ŸIDMT (4 IEC curves), Definite Time & Instantaneous ŸWide setting ranges ŸFully digital acquisition & processing of data ŸWide operating voltages

More information

MT174 Three-Phase Static Electricity Multi Tariff Meter with Maximum Demand Indicator and Load-profile

MT174 Three-Phase Static Electricity Multi Tariff Meter with Maximum Demand Indicator and Load-profile Energy Measurement and Management MT174 Three-Phase Static Electricity Multi Tariff Meter with Maximum Demand Indicator and Load-profile Technical Description Version 1.0, 05.05.2010 Index: MT174 Electronic

More information

Power Meter Series PM3200 Functions and characteristics

Power Meter Series PM3200 Functions and characteristics Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact size and DIN rail mounting, the PM3200 allows mains and feeders monitoring

More information

Z-10-D-IN. RS485 Modbus Module 10 Digital Inputs

Z-10-D-IN. RS485 Modbus Module 10 Digital Inputs S SENECA Z-PC Line EN Installation Manual Contents: - General specifications - Technical specifications - Installation rules - Electrical connections - Modbus connection rules - DIP-switches settings -

More information

JOINT STOCK COMPANY. MULTICHANNEL RECEIVER RI-4010M (version RM ) User guide

JOINT STOCK COMPANY. MULTICHANNEL RECEIVER RI-4010M (version RM ) User guide JOINT STOCK COMPANY MULTICHANNEL RECEIVER RI-4010M (version RM1-60619) User guide Safety requirements Before using the multichannel receiver RI-4010M read this user guide and follows safety requirements!

More information

Generator Protection M 3425

Generator Protection M 3425 PROTECTION Generator Protection M 3425 Integrated Protection System for Generators of All Sizes Unit shown with optional M 3925 Target Module and M 3931 HMI (Human Machine Interface) Module Provides all

More information

IPS INTELLIGENT PUMP STARTER. Integrated Tru-power electronic motor and pump protection

IPS INTELLIGENT PUMP STARTER. Integrated Tru-power electronic motor and pump protection IPS INTELLIGENT PUMP STARTER With TM Smartstart Ø & Ø, 0/60 Hz, 20~600 VAC, /~00HP Integrated electronic pump protection overload Power metering and data logging options Motor Protection Key dealer yr.

More information

Application Note Assigning and Reducing the DNP V3.0 Points List on the ABB PCD Timothy S. Fahey, PE

Application Note Assigning and Reducing the DNP V3.0 Points List on the ABB PCD Timothy S. Fahey, PE Application Note Assigning and Reducing the DNP V3.0 s List on the ABB PCD Timothy S. Fahey, PE Introduction This document defines a subset of the full points list given in the DNP 3.0 Implementation Details

More information

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Data Bulletin 0613IB1201 06/2012 Retain for future use. 0613IB1201 Modbus Communications System for Micrologic A, P, and H

More information