Generator Users Group Annual Conference Core testing, low and high flux, tap. Mladen Sasic, IRIS Power
|
|
- Jeffry Hill
- 5 years ago
- Views:
Transcription
1 Generator Users Group Annual Conference 2015 Core testing, low and high flux, tap Mladen Sasic, IRIS Power
2 Stator Cores Cores provide low reluctance paths for working magnetic fluxes Support stator winding, together with stator wedges! Cores and wedges must be capable of withstanding operating forces: mechanical and magnetic Core provides primary heat removal from indirect cooled stator winding
3 Westinghouse Core
4 GE Core
5 What is in the slot?
6 Requirement for Wedge Testing Wedges are installed to hold coils firmly in place and eliminate vibration Vibration results in wear and erosion of insulation Over time, this can result in electrical failure Loose or improperly installed wedges have been identified as a major contributor to this problem All manufacturers agree on the need for well installed and maintained wedges
7 Various wedge types
8 Top Ripple Spring 1.8 mm 30 mm Thickness: 0.9 mm, length and width to fit the slot/wedge Normal compression in 75-90% range
9 Side Ripple Spring
10 Stator Bar Slot Vibration Control 10
11 Typical tests Visual inspection (end wedge/side filler migration) Evidence of greasing, dusting Displacement measurements Ripple Spring Compression measurement Tap tests (manual or electronic)
12 Typical Tools...
13 Typical Problems... LOOSE...???? TIGHT!!!
14 Typical Electronic Tools...
15 RTI Idea Measured (raw) values are compared to user selected references for tight and loose RTI (Relative Tightness Index, number from 0-100) is displayed as a result of comparison between measured values and references Different calibration references will produce different RTI RTIs are not saved in measurement file
16 RTI Summary
17 Tap test conclusion A lot of uncertainty with any method Personal feel often considered to be more accurate than electronic methods There is no unit for tightness and there is no agreement on tight and loose Introduction of on-line methods may be helpful
18 Stator Core Testing Mechanical and Electrical tests: Core tightness test Core vibration test Through Bolts Insulation Core loss test Rated flux test Low flux tests 18
19 Core Tightness Testing Visual inspection Suspected loose areas can be confirmed by a Knife Test. This involves trying to insert a knife with a 0.25 mm (10 thou) thick blade into the core bore (stator) or OD (rotor). If the knife penetrates more than 5.0 mm (0.2 ins) then the core is loose. EDF Crabe Bump test, slots tested on hydro core, more air in core= lower the acoustic wave speed. 19
20 Knife Test 20
21 When you test the core What do you actually measure? Core loss test: W/kg LOOP test: temperature Low power core test: ma or W
22 and what can affect your result? Core loss and LOOP test: quality of material, test time, induction level Low power tests: quality and uniformity of material, induction level Magnetic permeability and core loss variation may be detected with low power test but not with LOOP test
23 Core Loss Test Core is excited and power absorbed measured by a wattmeter Results are expressed as loss per mass of core Should not exceed about 6-10W/kg Increase from previous test should not be more than 5% 23
24 Purpose and Theory Rated Flux Test The induced flux will generate excessive heating in the areas of core where degraded core insulation exists Heat is generated by eddy currents flowing between lamination due to insulation degradation Excitation winding power supply system should be fitted with a voltage adjustment device, ammeter to obtain the correct ampere-turns to produced the required flux No agreement on excitation levels, test duration and acceptance criteria 24
25 Rated Flux Test 25
26 Rated Flux Test Two methods to calculate flux test level, i.e. turn voltage: -Winding diagram -Size of the core See IEEE 56 or IEEE
27 Magnetization curve 27
28 Rated Flux Test on Turbo 28
29 Rated Flux Test on Hydro Power Cables POWER SOURCE 29
30 Rated Flux Test ~15 C above ambient 30
31 Rated Flux Concerns High Voltage, Current and Magnetic Field Fixed voltage supply Localized core burning General core overheating Temperature attenuation Labour intensive Uncertain power requirements Different flux patterns compared to normal operation 31
32 Low power core testing Recommended test level for low power tests is in range of 2-10 % of nominal flux. For 4% level, it is close to 5V/m of core length for two pole turbo generators, but It is NOT 5V/m for hydro and motor cores! To achieve 4%, about 10 At/m (vs in LOOP) of core circumference is required, or At. Different instruments exist
33 Purpose and Theory EL CID Test EL CID is the abbreviation for Electromagnetic Core Imperfection Detector Works on the principle that: If a low flux around 4% of rated flux is induced in back of core currents flow through defective core insulation Current is measured with Chattock Coil Chattock Coil gives voltage output proportional to fault current (I QUAD ) and current (I PHASE ) produced by the flux induced flux 33
34 EL CID principle Insulation breakdown causes fault currents to be set up as illustrated. These fault currents create hot spots which can cause further deterioration to the core. If left unchecked, this can lead to damage to the stator winding and the machine as a whole. 34
35 Measuring Fault Current with a Chattock Potentiometer 35
36 Positioning the Chattock 36
37 Understanding Fault Magnitude I QUAD 100mA at 4% equates to 5-10 C on LOOP Test
38 Data Display Normal Traces
39 Core Visualisation
40 Advantages of EL CID Low Excitation Power - 4% No Risk of Further core damage Fast, Portable - Easy to Setup Low Manpower Requirements Significant Reduction in Safety Hazards Instant Interpretation of Test Results Ability to Re-Test During Maintenance Cycle Can be done with rotor in place
41 Disadvantages of EL CID Requires competent trained test technician and experience to interpret data (also with LOOP Test) Difficult to detect small faults at the joints in hydro-generator cores Correlation to Ring Flux Test not perfect Faults on cores with insulated key-bars difficult to detect (also with LOOP Test) Does not create the same flux pattern as in operation (also with LOOP test) 41
42 What is an acceptable result? Core Loss: 6-10 W/kg Loop test: 5-10 K at 100% of nominal flux Low power tests: Less than 100 ma of quad current at 4% excitation level or 15 W dissipation at 3-10 %
43 Conclusions Evaluation of the condition of a core is a major technical challenge - C. Maughan Visual inspection is very important Both, high and low flux tests, have limitations Core problems are not that frequent, but
NEW DEVELOPMENTS IN FLUX MONITORING FOR TURBINE GENERATORS. M. Sasic, B. A. Lloyd and S.R. Campbell Iris Power LP, Mississauga, Ontario, Canada
NEW DEVELOPMENTS IN FLUX MONITORING FOR TURBINE GENERATORS M. Sasic, B. A. Lloyd and S.R. Campbell Iris Power LP, Mississauga, Ontario, Canada Abstract Flux monitoring via permanently installed air gap
More informationVerification of the Effectiveness of ELCID on a Hydrogenerator Stator Core
ABSTRACT Verification of the Effectiveness of ELCID on a Hydrogenerator Stator Core Electromagnetic Core Imperfection Detection (EL CID) was developed in the late 1970 s by the Central Electricity Generating
More informationA Practical Guide to Free Energy Devices
A Practical Guide to Free Energy Devices Part PatD14: Last updated: 25th February 2006 Author: Patrick J. Kelly This patent application shows the details of a device which it is claimed, can produce sufficient
More informationGenerator Advanced Concepts
Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves
More informationCONDITION ASSESSMENT OF ROTATING MACHINES THROUGH OFF- LINE DIAGNOSTIC TESTING
CONDITION ASSESSMENT OF ROTATING MACHINES THROUGH OFF- LINE DIAGNOSTIC TESTING Copyright Material PCIC Europe Paper No. PCIC Middle-East ME18_06 Howard Sedding Christoph Wendel Mladen Sasic Qualitrol Iris
More informationOn-line Hydrogenerator Rotor Winding Condition Assessment Using Flux Monitoring. S.R. Campbell, G.C. Stone, M. Krikorian, G.
On-line Hydrogenerator Rotor Winding Condition Assessment Using Flux Monitoring S.R. Campbell, G.C. Stone, M. Krikorian, G. Proulx, Jan Stein Abstract: On-line monitoring systems to assess the condition
More informationFinal Publishable Summary
Final Publishable Summary Task Manager: Dr. Piotr Klimczyk Project Coordinator: Mr. Stefan Siebert Dr. Brockhaus Messtechnik GmbH & Co. KG Gustav-Adolf-Str. 4 D-58507 Lüdenscheid +49 (0)2351 3644-0 +49
More informationOn-line Flux Monitoring of Hydro-generator Rotor Windings
On-line Flux Monitoring of Hydro-generator Rotor Windings M. Sasic, S.R. Campbell, B. A. Lloyd Iris Power LP, Canada ABSTRACT On-line monitoring systems to assess the condition of generator stator windings,
More information1 K Hinds 2012 TRANSFORMERS
1 K Hinds 2012 TRANSFORMERS A transformer changes electrical energy of a given voltage into electrical energy at a different voltage level. It consists of two coils which are not electrically connected,
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationProtecting power transformers from common adverse conditions
Protecting power transformers from common adverse conditions by Ali Kazemi, and Casper Labuschagne, Schweitzer Engineering Laboratories Power transformers of various size and configuration are used throughout
More informationUpgrading from Stepper to Servo
Upgrading from Stepper to Servo Switching to Servos Provides Benefits, Here s How to Reduce the Cost and Challenges Byline: Scott Carlberg, Motion Product Marketing Manager, Yaskawa America, Inc. The customers
More informationDISCUSSION OF FUNDAMENTALS
Unit 4 AC s UNIT OBJECTIVE After completing this unit, you will be able to demonstrate and explain the operation of ac induction motors using the Squirrel-Cage module and the Capacitor-Start Motor module.
More informationUNIT II MEASUREMENT OF POWER & ENERGY
UNIT II MEASUREMENT OF POWER & ENERGY Dynamometer type wattmeter works on a very simple principle which is stated as "when any current carrying conductor is placed inside a magnetic field, it experiences
More informationPARTIAL DISCHARGE MEASUREMENT
PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of
More informationCAPACITIVE FOR WINDING ELECTRIC MOTORS, TRANSFORMERS AND ELECTRO-MAGNETS
CAPACITIVE FOR WINDING ELECTRIC MOTORS, TRANSFORMERS AND ELECTRO-MAGNETS The invention relates to a capacitive coil of copper wire that can be used for all electromagnetic energy converters and their inductive
More information3.1.Introduction. Synchronous Machines
3.1.Introduction Synchronous Machines A synchronous machine is an ac rotating machine whose speed under steady state condition is proportional to the frequency of the current in its armature. The magnetic
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationGOVERNMENT COLLEGE OF ENGINEERING, BARGUR
1. Which of the following is the major consideration to evolve a good design? (a) Cost (b) Durability (c) Compliance with performance criteria as laid down in specifications (d) All of the above 2 impose
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More informationIn this lecture. Electromagnetism. Electromagnetism. Oersted s Experiment. Electricity & magnetism are different aspects of the same basic phenomenon:
In this lecture Electromagnetism Electromagnetic Effect Electromagnets Electromechanical Devices Transformers Electromagnetic Effect Electricity & magnetism are different aspects of the same basic phenomenon:
More informationExcitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation
Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability
More informationInduction heating of internal
OPTIMAL DESIGN OF INTERNAL INDUCTION COILS The induction heating of internal surfaces is more complicated than heating external ones. The three main types of internal induction coils each has its advantages
More informationApplication of Fiber Optic Sensors for Stator End Winding Vibration Monitoring. M. Sasic, R. Sadanandan, G. Stone Iris Power Qualitrol
Application of Fiber Optic Sensors for Stator End Winding Vibration Monitoring M. Sasic, R. Sadanandan, G. Stone Iris Power Qualitrol What is endwinding? Endwinding Slot Objectives of the Support System
More informationWalchand Institute of Technology. Basic Electrical and Electronics Engineering. Transformer
Walchand Institute of Technology Basic Electrical and Electronics Engineering Transformer 1. What is transformer? explain working principle of transformer. Electrical power transformer is a static device
More informationStudy on monitoring technology of aircraft engine based on vibration and oil
Study on monitoring technology of aircraft engine based on vibration and oil More info about this article: http://www.ndt.net/?id=21987 Junming LIN 1, Libo CHEN 2 1 Eddysun(Xiamen)Electronic Co., Ltd,
More informationThree-Phase Induction Motors. By Sintayehu Challa ECEg332:-Electrical Machine I
Three-Phase Induction Motors 1 2 3 Classification of AC Machines 1. According to the type of current Single Phase and Three phase 2. According to Speed Constant Speed, Variable Speed and Adjustable Speed
More informationThe Fundamental Characteristics of Novel Switched Reluctance Motor with Segment Core Embedded in Aluminum Rotor Block
58 Journal of Electrical Engineering & Technology, Vol. 1, No. 1, pp. 58~62, 2006 The Fundamental Characteristics of Novel Switched Reluctance Motor with Segment Core Embedded in Aluminum Rotor Block Jun
More informationEEE, St Peter s University, India 2 EEE, Vel s University, India
Torque ripple reduction of switched reluctance motor drives below the base speed using commutation angles control S.Vetriselvan 1, Dr.S.Latha 2, M.Saravanan 3 1, 3 EEE, St Peter s University, India 2 EEE,
More informationMotoplat CV-014DS TESTER FOR DIAGNOSTICS OF ALTERNATOR STATOR WINDINGS AND DIODE BRIDGES USER MANUAL
2016.09.07 Motoplat CV-014DS TESTER FOR DIAGNOSTICS OF ALTERNATOR STATOR WINDINGS AND DIODE BRIDGES USER MANUAL QUALITY WARRANTY INNOVATION SERVICE TRAINING UNIQUENESS CONTENTS 1. DESCRIPTION... 4 2.
More informationTransformers handling and transport
Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary
More informationXu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP)
Xu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP) April 12, 2010 Slide 1 Content MV Machine Winding Insulation Stress LEAP Methodology LEAP Standard LEAP from
More informationDirect Current Motor Electrical Evaluation Using Motor Circuit Analysis
Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis Introduction Howard W. Penrose, Ph.D BJM Corp, ALL-TEST Division Old Saybrook, CT Electrical testing of Direct Current (DC) electric
More informationUnit FE-5 Foundation Electricity: Electrical Machines
Unit FE-5 Foundation Electricity: Electrical Machines What this unit is about Power networks consist of large number of interconnected hardware. This unit deals specifically with two types of hardware:
More informationCase Studies of Electric Power Equipment Diagnostics Using Acoustic Emission
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission Oswaldo G. SANTOS FILHO 1, Sergio L. ZAGHETTO
More informationDesign Considerations
Design Considerations Ferrite beads provide a simple, economical method for attenuating high frequency noise or oscillations. By slipping a bead over a wire, a RF choke or suppressor is produced which
More informationTarget Temperature Effect on Eddy-Current Displacement Sensing
Target Temperature Effect on Eddy-Current Displacement Sensing Darko Vyroubal Karlovac University of Applied Sciences Karlovac, Croatia, darko.vyroubal@vuka.hr Igor Lacković Faculty of Electrical Engineering
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationTHE UNDER HUNG VOICE COIL MOTOR ASSEMBLY REVISITED IN THE LARGE SIGNAL DOMAIN BY STEVE MOWRY
THE UNDER HUNG VOICE COIL MOTOR ASSEMBLY REVISITED IN THE LARGE SIGNAL DOMAIN BY STEVE MOWRY The under hung voice coil can be defined as a voice coil being shorter in wind height than the magnetic gap
More informationSIGNATURE ANALYSIS FOR ON-LINE MOTOR DIAGNOSTICS
Page 1 of 10 2015-PPIC-0187 SIGNATURE ANALYSIS FOR ON-LINE MOTOR DIAGNOSTICS Ian Culbert Senior Member, IEEE Qualitrol-Iris Power 3110 American Drive Mississauga, ON Canada Abstract - Stator current signature
More informationEE 340 Power Transformers
EE 340 Power Transformers Preliminary considerations A transformer is a device that converts one AC voltage to another AC voltage at the same frequency. It consists of one or more coil(s) of wire wrapped
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationELECTRICAL TECHNOLOGY
ELECTRICAL TECHNOLOGY Subject Code: (EC303ES) Regulations : R6 JNTUH Class :II Year B.Tech ECE I Semester Department of Electronics and communication Engineering BHARAT INSTITUTE OF ENGINEERING AND TECHNOLOGY
More informationBasics of electrical transformer
Visit: https://engineeringbasic.com Complete basics and theory of Electrical Transformer Electrical Transformer is the most used electrical machine in power system. Both in the power transmission and distribution
More informationContents. About the Authors. Abbreviations and Symbols
About the Authors Preface Abbreviations and Symbols xi xiii xv 1 Principal Laws and Methods in Electrical Machine Design 1 1.1 Electromagnetic Principles 1 1.2 Numerical Solution 9 1.3 The Most Common
More informationPES & IAS NY Chapter And NY LMAG June 23 rd, 2015
PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 High Temperature Insulation Systems and their use in Mobile Transformers Myron B. Bell, PE mbell@deltastar.com Delta Star, Inc. June 23 rd 2015 Introduction
More informationTIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M
SL. NO NOMINAL DIAMETER "D" mm GASKETED JOINT (Nm) WOODEN CORE CLAMP (Nm) STEEL FIXING STUD FOR BUSHING (Nm) BUSHING STEM (Nm) (BRASS /COPPER) COPPER BUSBAR (Nm) 1 M6 5 - - - - 2 M8 12 - - 10-3 M10 22
More informationROTOR FAULTS DETECTION IN SQUIRREL-CAGE INDUCTION MOTORS BY CURRENT SIGNATURE ANALYSIS
ROTOR FAULTS DETECTION IN SQUIRREL-CAGE INDUCTION MOTORS BY CURRENT SIGNATURE ANALYSIS SZABÓ Loránd DOBAI Jenő Barna BIRÓ Károly Ágoston Technical University of Cluj (Romania) 400750 Cluj, P.O. Box 358,
More informationTRANSFORMERS INTRODUCTION
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 TRANSFORMERS INTRODUCTION A transformer is a device that
More informationSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
More information1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST
1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST 1.1 INTRODUCTION. DESCRIPTION OF THE EXPERIMENT The three-phase induction motor carries a three-phase winding on its stator. The rotor is either a wound type or
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More informationModule 1. Introduction. Version 2 EE IIT, Kharagpur
Module 1 Introduction Lesson 1 Introducing the Course on Basic Electrical Contents 1 Introducing the course (Lesson-1) 4 Introduction... 4 Module-1 Introduction... 4 Module-2 D.C. circuits.. 4 Module-3
More informationKnowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators
Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com
More informationCHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION
18 CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION 2.1 INTRODUCTION Transformers are subjected to a variety of electrical, mechanical and thermal stresses during normal life time and they fail when these
More informationWDBR Series (RoHS compliant)
WDBR Series (RoHS compliant) This new range of thick film planar power resistors on steel, offering high pulse withstand capability, compact footprint and low profile, to many demanding applications including
More informationInductors & Resonance
Inductors & Resonance The Inductor This figure shows a conductor carrying a current. A magnetic field is set up around the conductor as concentric circles. If a coil of wire has a current flowing through
More informationApplication of Electrical Signature Analysis. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN
Application of Electrical Signature Analysis Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN Introduction Over the past months we have covered traditional and modern methods of testing electric
More informationEE171. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
EE171 Electrical Equipment & Control System: Electrical Maintenance Transformers, Motors, Variable Speed Drives, Generators, Circuit Breakers, Switchgears & Protective Systems H.H. Sheikh Sultan Tower
More informationROWTEST ROTOR WINDING RSO REFLECTOMETER TDR200
ROWTEST ROTOR WINDING RSO REFLECTOMETER TDR200 LOW VOLTAGE RSO TEST UNIT FOR DETECTING WINDING FAULTS IN POWER PLANT ALTERNATOR ROTORS THE ROWTEST TDR200 Rotor Winding RSO Reflectometer The Rowtest TDR200
More informationAnalysis of Partial Discharge Patterns for Generator Stator Windings
American Journal of Electrical Power and Energy Systems 2015; 4(2): 17-22 Published online March 11,2015 (http://www.sciencepublishinggroup.com/j/epes) doi: 10.11648/j.epes.20150402.11 ISSN: 2326-912X
More informationTRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K
UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of
More informationAnalysis of the electromagnetic acoustic noise and vibrations of a high-speed brushless DC motor
Analysis of the electromagnetic acoustic noise and vibrations of a high-speed brushless DC motor J. Le Besnerais, Q. Souron, E. Devillers EOMYS ENGINEERING, www.eomys.com 1 A. Introduction Square-wave-driven
More informationExercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers
Exercise 10 Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the basic operating principles of transformers, as well as with the different ratios of transformers:
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationUltrasonic. Advantages
Ultrasonic Advantages Non-Contact: Nothing touches the target object Measures Distance: The distance to the target is measured, not just its presence Long and Short Range: Objects can be sensed from 2
More informationOverview of IAL Software Programs for the Calculation of Electrical Drive Systems
for the Calculation of Electrical Drive Systems Combines FEM with analytical post-processing analytical Machine type Topic Electrically excited Salientpole rotor Synchronous machines Cylindrical rotor
More informationAligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.
Aligarh College of Engineering & Technology (College Code: 19) Electrical Engg. (EE-11/21) Unit-I DC Network Theory 1. Distinguish the following terms: (a) Active and passive elements (b) Linearity and
More informationMAGNETOSCOP Measurement of magnetic field strengths in the range 0.1 nanotesla to 1 millitesla
MAGNETOSCOP Measurement of magnetic field strengths in the range 0.1 nanotesla to 1 millitesla Extremely high sensitivity of 0.1 nanotesla with field and gradient probe Measurement of material permeabilities
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationUNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES
UNIVERSITY OF TECHNOLOGY DEPARTMENT OF ELECTRICAL ENGINEERING Year: Second 2016-2017 By: Fadhil A. Hasan ELECTRICAL MACHINES І Module-II: AC Transformers o Single phase transformers o Three-phase transformers
More informationVariable Transformers Product Design & Engineering Data
Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,
More informationPage ENSC387 - Introduction to Electro-Mechanical Sensors and Actuators: Simon Fraser University Engineering Science
Motor Driver and Feedback Control: The feedback control system of a dc motor typically consists of a microcontroller, which provides drive commands (rotation and direction) to the driver. The driver is
More informationINDUCTORS WITH MAGNETIC FLUX CONTROLLERS FOR NEW INDUCTION BRAZING INSTALLATIONS. Auburn Hills, MI , USA,
Various Brazing стр. 1 HES 2004 INDUCTORS WITH MAGNETIC FLUX CONTROLLERS FOR NEW INDUCTION BRAZING INSTALLATIONS Dr. V. Nemkov (1) and Dr. V. Vologdin (2) (1) Centre for Induction Technology, Inc., 1388
More information1. Explain in detail the constructional details and working of DC motor.
DHANALAKSHMI SRINIVASAN INSTITUTE OF RESEARCH AND TECHNOLOGY, PERAMBALUR DEPT OF ECE EC6352-ELECTRICAL ENGINEERING AND INSTRUMENTATION UNIT 1 PART B 1. Explain in detail the constructional details and
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More information3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)
DHANALAKSHMI COLLEGE OF ENGINEERING, CHENNAI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE 6401 ELECTRICAL MACHINES I UNIT I : MAGNETIC CIRCUITS AND MAGNETIC MATERIALS Part A (2 Marks) 1. List
More informationComparison of Lamination Iron Losses Supplied by PWM Voltages: US and European Experiences
Comparison of Lamination Iron Losses Supplied by PWM Voltages: US and European Experiences A. Boglietti, IEEE Member, A. Cavagnino, IEEE Member, T. L. Mthombeni, IEEE Student Member, P. Pillay, IEEE Fellow
More informationPlacement Paper For Electrical
Placement Paper For Electrical Q.1 The two windings of a transformer is (A) conductively linked. (B) inductively linked. (C) not linked at all. (D) electrically linked. Ans : B Q.2 A salient pole synchronous
More informationFRAX Series Sweep Frequency Response Analyzers
FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software. FRAX 150 with built
More informationINDEX IEC:
60050-300 IEC:2001 173 INDEX A absolute absolute error... 311-01-05 (absolute) frequency deviation... 314-08-07 accessory accessory (of a measuring instrument)... 312-03-01 accessory of limited interchangeability...
More informationSynchronous Machines Study Material
Synchronous machines: The machines generating alternating emf from the mechanical input are called alternators or synchronous generators. They are also known as AC generators. All modern power stations
More informationTransformer Protection Principles
Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major
More informationUNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE
UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE 3.1 STATOR VOLTAGE CONTROL The induction motor 'speed can be controlled by varying the stator voltage. This method of speed control is known as stator
More informationEDDY CURRENT TESTING
NEW SOUTH WALES TECHNICAL AND FURTHER EDUCATION COMMISSION EDDY CURRENT TESTING NSW Module Number: Implementation Date: 6161C 01-Jan-1998 National Module Code: EA605 MANUFACTURING AND ENGINEERING MECHANICAL
More informationMAGNETIC LEVITATION SUSPENSION CONTROL SYSTEM FOR REACTION WHEEL
IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN 2321-8843 Vol. 1, Issue 4, Sep 2013, 1-6 Impact Journals MAGNETIC LEVITATION SUSPENSION CONTROL SYSTEM FOR REACTION
More informationUNIT II MEASUREMENT OF POWER AND ENERGY PART-A
UNIT II MEASUREMENT OF POWER AND ENERGY PART-A 1. A 3 500 V motor load has a pf of 0.4. Two wattmeters connected to measure the input. They show the input to be 30 kw. Find the reading of each instrument
More informationDC-Voltage fluctuation elimination through a dc-capacitor current control for PMSG under unbalanced grid voltage conditions
DC-Voltage fluctuation elimination through a dc-capacitor current control for PMSG under unbalanced grid voltage conditions P Kamalchandran 1, A.L.Kumarappan 2 PG Scholar, Sri Sairam Engineering College,
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationEE401,EC401,DEE19,DETE19
EE401,EC401,DEE19,DETE19 IV SEMESTER DIPLOMA EXAMINATION, JANUARY 2013 LINEAR & DIGITAL ICs Time: 3 Hours Max. Marks: 75 GROUP A : Answer any three questions. (Question No. 1 is compulsory) Q.1 What is
More informationVoltage-Versus-Speed Characteristic of a Wind Turbine Generator
Exercise 1 Voltage-Versus-Speed Characteristic of a Wind Turbine Generator EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the principle of electromagnetic induction.
More informationShaft encoders are digital transducers that are used for measuring angular displacements and angular velocities.
Shaft Encoders: Shaft encoders are digital transducers that are used for measuring angular displacements and angular velocities. Encoder Types: Shaft encoders can be classified into two categories depending
More informationCHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES
22 CHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES 2.1 INTRODUCTION For the accurate analysis of synchronous machines using the two axis frame models, the d-axis and q-axis magnetic characteristics
More informationSilent Transformers to Help Consolidated Edison Meet New York City s Ultrastrict Noise Ordinances
BY DR. RAMSIS GIRGIS, ABB INC. The Sound of Silence: Silent Transformers to Help Consolidated Edison Meet New York City s Ultrastrict Noise Ordinances S ilence is a source of great strength. Although these
More information9/28/2010. Chapter , The McGraw-Hill Companies, Inc.
Chapter 4 Sensors are are used to detect, and often to measure, the magnitude of something. They basically operate by converting mechanical, magnetic, thermal, optical, and chemical variations into electric
More informationDETECTING SHORTED TURNS
VOLTECH NOTES DETECTING SHORTED TURNS 104-029 issue 2 Page 1 of 8 1. Introduction Inductors are made up of a length of wire, usually wound around a core. The core is usually some type of magnetic material
More informationTesting Critical Medical Tubing Using High Frequency Eddy Current Coils
Testing Critical Medical Tubing Using High Frequency Eddy Current Coils Troy M Libby Magnetic Analysis Corporation, Mt. Vernon, NY, USA Phone: (914) 699-9450, Fax: (914) 699-9837; e-mail: info@mac-ndt.com
More informationMotor Bearing Damage and Variable Frequency Drives: - Diagnosing the Causes, - Implementing a Cure, and - Avoiding the Pitfalls
Motor Bearing Damage and Variable Frequency Drives: - Diagnosing the Causes, - Implementing a Cure, and - Avoiding the Pitfalls Tim Albers, Director of Product Mgt, NIDEC Motor Corporation Tim Jasina,
More informationLECTURE 10. Dr. Teresa D. Golden University of North Texas Department of Chemistry
LECTURE 10 Dr. Teresa D. Golden University of North Texas Department of Chemistry Components for the source include: -Line voltage supply -high-voltage generator -x-ray tube X-ray source requires -high
More information