1 NUCLEAR POWER CORPORATION OF INDIA LIMITED (A Government of India Enterprise) TECHNICAL SPECIFICATION OF 220 KV CAPACITOR VOLTAGE ANSFORMERS FOR KAIGA GENERATING STATION-1&2

2 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 1 SECTION-C 1.0 SCOPE OF SUPPLY / WORKS / SERVICES. 1.1 This specification covers the design, engineering, material, construction features, manufacture, inspection and testing at the Contractor's/sub-contractor's works, packing, transportation and delivery at site. 1.2 It is not the intent to specify completely herein, all details of design and construction of the equipment. However, the equipment shall conform in all respects to high standards of engineering, design and workmanship and be capable of performing continuous commercial operation up to the CONACTOR'S guarantees in a manner acceptable to the PURCHASER, who will interpret the meaning of drawings and specifications and shall be entitled to reject any work or material which, in his judgement, is not in full accordance therewith. 1. The scope also includes but not limited to the following items / services described herein and elsewhere in the tender package Whether called for specifically or not all accessories required for normal operation of equipment are deemed to be considered as a part of the CONACTOR'S scope of supply Training of Purchaser's personnel at purchaser s site on installation, maintenance, carrying out adjustments etc. 1.4 In case of SF 6 gas filled CVT, scope of supply shall include SF 6 gas density monitor supply for remote annunciation and protection tripping of respective breaker in case of SF 6 leakage. 2.0 CONTENTS: Description Clause Codes and Standards Specification of Main Equipment and Accessories 4 Equipment Construction & Design Details 5 Inspection & Testing 6 Quality Surveillance 7.0 CODES AND STANDARDS.1 The design, material, manufacture, assembly, inspection, testing and performance of Capacitor Voltage Transformer and other associated equipments shall comply with latest editions (including amendments thereto) of all currently applicable statutes, regulations and safety codes in the locality where the equipment will be installed. The equipment shall also conform to the latest applicable standards. Nothing in this specification shall be construed to relieve the Contractor of his responsibility.

3 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 2.2 In case of conflict between the standards and this specification, requirements of this specification shall govern.. Other national standards are acceptable if they are established to be equal to or superior to the listed standards. In all such cases, however, copies of English translation of such national standards shall be attached to the tender. The tenders not complying with this requirement are liable for rejection..4 The list of some of the applicable codes and standards are given below. Sl No. Standard No. Title of the Standard 1 IS-5 Colours for ready mixed paints and enamels 2 IS-5 New Insulating Oil IS-51 Cold rolled low carbon steel sheets and strips. 4 IS- 800 General Construction in Steel- Code of Practice 5 IS- 808 Dimensions for hot rolled steel beams, columns, channels and angle sections 6 IS-129 Steel Tubes, Tubular and Other Wrought Steel Fittings 7 IS-189 Criteria for earthquake resistant design of structures 8 IS-1897 Copper strip for electrical purposes 9 IS-2551 Danger notice plates 10 IS-26 Methods of testing uniformity of coating of zinc coated articles 11 IS-2629 Recommended practice for hot dip galvanising on iron and steel 12 IS-4759 Hot-dip zinc coatings on structural steel and other allied products 1 IS-5561 Specification for Electric Power Connectors 14 IS-5621 Hollow insulators for use in electrical equipment 15 IS-1122 Methods for Partial Discharge Measurements 16 IS-826 Methods for radio interference test on high voltage insulators 17 IS-115 Guide for uniform System of Marking and Identification of Conductors and Apparatus. 18 IS / Instrument transformers - General requirements IEC IS / IEC Instrument Transformers - Additional Requirements for Capacitors Voltage Transformers 20 IS-948/ Coupling capacitor and capacitor dividers IEC IEC Coupling device for power line carriers system 22 IS-1072 / IEC-6076 Specification of technical grade Sulfur Hexafluoride (Sf6) for use in electrical equipment 2 IEC Composite hollow insulators - Pressurized and unpressurized insulators for use in electrical equipment with rated voltage greater than 1000 V 24 IEC Selection & dimensioning of HV insulators intended for use in polluted conditions

4 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 25 IS / IEC Degrees of protection provided by enclosures (IP code) 4.0 SPECIFICATION OF MAIN EQUIPMENT AND ACCEESSORIES Sl No. Particulars Specification 1.0 Type of mounting Pedestal mounted on GI structure 2.0 Highest voltage for equipment 245 KV at 50 Hz.0 Installation Outdoor 4.0 Insulation Withstand Characteristics 4.1 Power frequency withstand kv 460 (RMS) 4.2 Lightning impulse withstand voltage, 1050 kv (Peak) 5.0 Radio interference voltage 1000 μv at 154 kv (rms) 6.0 Partial discharge level at rated voltage Less than 10 (Pico Coulombs) for capacitance divider 7.0 Design requirements 7.1 Rated primary voltage 220,000/ 7.2 Rated secondary voltage S1 110/ V S2 110/ V S 110/ V 7. Method of connection Primary winding Star S1 Star S2 Star S Star 7.4 Application S1 Metering S2 Protection S Protection 7.5 Rated Burden/Phase S1 100 VA S2 100 VA S 100 VA 7.6 Rated total thermal burden 1000 VA 7.7 Accuracy class S1 0.2 S2 P S P 7.8 Rated voltage factor 1.2 continuous 1.5 for0 Sec 7.9 Total equivalent capacitance (pf) 8800 (+)10%, (-)5% 7.10 Material of primary & secondary windings of electromagnetic unit Copper

5 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Suitability for high frequency carrier Required coupling 7.12 Maximum winding temperature As per IEC Minimum Secondary cable size S1 10 Sq. mm stranded copper S2 4 Sq. mm stranded copper S 4 Sq. mm stranded copper 7.14 Specific Creepage distance 25 mm/kv 7.15 Corona extinction voltage 156 kv RMS 7.16 Power frequency withstand voltage i) Between LV (HF) terminal and earth 10kV for exposed terminals 4kV for enclosed terminals ii) For Secondary winding kv rms Damping device Passive ferroresonance suppression circuit comprising of permanently connected loading resistor, a saturable inductor and an air gap loading resistor. 5.0 EQUIPMENT CONSUCTION AND DESIGN DETAILS 5.1 General Technical Requirements The transformers shall be single phase units and shall be supplied with its terminal box The CVT shall be suitable for mounting on existing support structures at site. (Dimension drawing of existing CVT mounting is attached in Annexure-1 for reference) Its housing shall have profile meeting with IEC and with required minimum creepage distance corresponding to heavy pollution environment. The insulator shed configuration should be of the "Alternate" The transformer including hollow insulator shall be sufficiently strong to withstand stresses due to wind pressure, earthquake, conductor tension at the terminals and forces due to dynamic phase short circuit current. In addition, it shall withstand the stresses due to its own weight and internal pressure if any. Cantilever strength of the offered CVT shall be not less than 500 Kg The transformer shall be suitable for a trouble free and maintenance free performance. Therefore, the bidder shall ensure that the sealing of transformer is properly achieved. In this connection the arrangement provided by the bidder at various locations including the following ones shall be described, supported by sectional drawings.

6 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 5 Locations of emergence of primary and secondary terminals. Interface between porcelain/ composite housing and metal tank/s. Cover of the secondary terminal box Insulating oil / SF6 gas required for first filling of the instrument transformer shall be covered in bidder s scope of supply. The oil shall meet the requirements of IS 5 / SF6 gas shall meet the requirement of IS 1072 / IEC The wiring diagram for the interconnection of the three single phase CVTs shall be provided inside the marshalling box The primary terminal connector required for connection of the CVT to purchaser s bus bar (single ACSR moose conductor), shall be in bidder s scope The mounting base arrangement for CVT shall be submitted along with offer. 5.2 Constructional features The metal tanks shall have bare minimum number of welded joints so as to minimise possible locations of oil leakage / SF6 leakage. The metal tanks shall be made out of mild steel/stainless steel/aluminium alloy, depending on the requirement. The thickness and metal used for fabrication of tank shall be indicated by the bidder in general arrangement drawings to be submitted with the offer Surface Finish of all non current carrying metal surfaces exposed to atmosphere shall be given two primer coats of zinc phosphate and two coats of epoxy paint with epoxy base thinner. All metal parts not accessible for painting shall be made of corrosion resisting material. All machine finished or bright surfaces shall be coated with a suitable preventive compound and shall be suitably wrapped or otherwise protected. All paints shall be carefully selected to withstand tropical heat and extremes of weather within the limits specified. The paint shall not scale off or wrinkle or be removed by abrasion due to normal handling. All equipment shall be factory painted. The prime and finish coats shall have a combined minimum dry film thickness of 50 to 75 Microns The housing shall be made of homogeneous, vitreous glazed porcelain of high mechanical and dielectric strength. Glazing of porcelain shall be of uniform brown or dark brown colour with a smooth surface arranged to shed away rain water or condensed water particles. The details of location and type of joint, if provided on the porcelain, shall be furnished by the bidder along with the offer In case of SF6 filled CVT; insulator shall be explosion proof design, composite / porcelain. A controlled pressure relief device shall be provided to eliminate unacceptable mechanical stresses in the housing The hollow insulators shall be cemented to cast aluminum alloy flanges and hermetically sealed by non-ferrous metallic plate with neoprene rubber or equivalent O-ring gasket.

7 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Details of attachment of metallic flanges to the porcelain / composite insulators shall be brought out in the offer In case of SF6 filled CVT, SF6 leakage rate shall be less than 0.2% per year Oil filling, drain plug and oil sight glass having low oil level indication mark shall be provided in case of oil filled electromagnetic unit of CVT Oil filling and draining hermetically sealed plugs / SF6 gas online filling plug shall be provided In case of SF6 gas filled CVT, suitable SF6 gas density monitoring device with NO / NC contacts shall be provided to facilitate the remote annunciation and tripping in case of SF6 leakage. Provision shall be made of online gas filling also Secondary terminals of CVT shall be bought out in a weatherproof terminal box having enclosure protection of IP: 55 as per IS / IEC. The terminal box shall be provided with removable gland plate of adequate size and gland/s suitable. The dimensions of the terminal box and its openings shall be adequate to enable easy access and working space with use of normal tools Corona shields (grading rings) shall be of copper or corrosion resistant aluminium Nuts and bolts or screws used for fixation of the interfacing porcelain bushings for taking out terminals shall be provided on flanges cemented to the bushings and not on the porcelain For gasket joints wherever used nitrite butyl rubber gaskets shall be used. The gasket shall be fitted in properly machined groove with adequate space for accommodating the gasket under compression Terminal and polarity marks shall be indelibly marked on each CVT All ferrous parts including nuts, bolts, plain and spring washers of size M 10 and above, support channels, structures etc. shall be hot dip galvanised to conform latest version of IS 2629 or any other equivalent standard. All other fixing nuts, bolts, washers of size below M 10 shall be made out of stainless steel Metal tank of the CVT shall be provided with two separate earthing terminals for bolted connection to 50 x 5 mm MS flat for connection to station earth-mat The CVT shall be provided with suitable lifting arrangement, to lift the entire unit. The lifting arrangement shall be clearly shown in the general arrangement drawing. Lifting arrangement (lifting eye) shall be positioned in such a way as to avoid any damage to the porcelain housing or the tanks during lifting for installation/transport. Necessary string guides shall be offered which shall be of removable type. 5. Technical Particulars for Capacitor Voltage Transformers

8 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Capacitor voltage transformer shall consist of coupling capacitors (a capacitor divider) and an electromagnetic unit housed in independent, non-oil communicating hermitically sealed compartments. It shall be so designed and inter-connected that the secondary voltage of the electromagnetic unit is substantially proportional to and in phase with the primary voltage applied to the capacitor divider unit. The capacitance divider consists of primary and secondary capacitance housed in high quality porcelain insulators filled with oil/ SF 6. The electromagnetic unit comprises compensating reactor, intermediate transformer and protective and damping devices and should have a separate terminal box with the entire secondary terminal brought out CVT should have secondary windings, two of which are intended for protection and one for metering. 5.. CVTs shall be suitable for high frequency (HF) coupling required for power line carrier communication. Carrier signal must be prevented from flowing into potential transformer (EMU) circuit by means of a RF choke/reactor suitable for effectively blocking the carrier signals over the entire carrier frequency range i.e. 40 to 500 KHz. Details of the arrangement shall be furnished along with the bid. H.F. terminal of the CVT shall be brought out through a suitable bushing and shall be easily accessible for connection to the coupling filters of the carrier communication equipment, when utilised. Further, earthing link with fastener to be provided for HF terminal The coupling capacitor unit and the electromagnetic unit should be housed in independent, non-oil communicating hermitically sealed compartments Coupling Capacitor The coupling capacitor/capacitor divider unit shall consist of an assembly of capacitor elements of high grade aluminium foil and pure ultra thin cellulose paper, housed inside porcelain insulator with corrosion resistant aluminium alloy end fittings. The Unit is to be filled completely with degassed insulating oil / SF6 gas. The oil volume changes caused by temperature variations should be compensated by a stainless steel bellow. The bellow should be pressurized by inert gas so as to have a positive pressure even at low ambient temperature The material, construction and assembly of capacitor unit shall be such that the capacitance value does not change with time and that the influence of temperature is kept to a minimum The live mating surface used for the connections between two capacitor units shall be either of brass or tinned copper or corrosion resistant aluminium alloy to provide good electrical joint Electro-magnetic Unit (VT) The VT shall be housed in a hot dip galvanized tank at the base of the coupling capacitor.

9 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e The electro-magnetic unit comprising compensating reactor, intermediate transformer and protective and damping devices should have a separate hot dip galvanised terminal box with all the secondary terminals brought out. The damping devices, which should be permanently connected to one of the secondary windings, should be capable of suppressing the ferro-resonance oscillations Voltage transformers shall be given tropical treatment for satisfactory operation in hot and humid climate The secondary terminal box for the voltage transformers shall include 10A HRC fuses in each secondary circuit for metering and protection Hot dip galvanized terminal box shall be provided for mounting carrier protection device, surge protection device Voltage transformers shall be provided with the following accessories: Rating & diagram plate as required by relevant standards Bushings/connections/terminations required between the capacitor and the primary of the VT Performance Requirements The capacitor voltage transformers should be designed to meet the requirements for accuracy, burden and ferro-resonance requirements specified in this specifications and transient response specified in relevant standards The capacitor voltage transformers should be thermally and dielectrically safe when the secondary terminals are loaded with the guaranteed thermal burdens The maximum temperature rise shall not exceed the figures given in applicable standards for operation considering the design ambient temperature of 50 o C The capacitance shall be designed for a preferred capacitance rating of the value as stated in this specification for rated system voltage and rated power frequency. If the capacitor offered is designed for any other value, the TENDERER shall indicate reasons /advantages of the same The high frequency capacitance values shall be within the limits of 80% and 150% of the rated capacitance, for a frequency range from 40 to 500 KHz and at the temperature limits specified The values of stray capacitance and conductance of the low-voltage terminal, with respect to the earth terminal, shall be as low as possible. The terminal design and arrangement shall be such that adverse atmospheric effects of humidity, dust, etc. does not increase the generally recommended limiting values of the stray capacitance and conductance, for coupling capacitor/cvt as stated in applicable standards.

10 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e The accuracy of capacitor voltage transformer shall remain within the specified class when a carrier coupling device is connected to the earth lead of the intermediate voltage capacitor The internal insulation of CVTs shall be designed to safely withstand specified over voltage. 6.0 INSPECTION AND TESTING 6.1 General The routine tests, acceptance tests, special tests and type tests are covered in this section. Inspections and tests at raw material stage, semi finished or module level are detailed in the typical QAP given in Clause All the equipments offered should have been successfully type tested as per the relevant standards, amended up to date. In case the equipment of the type and design offered has already been type tested, bidder shall furnish type test reports before proceeding with manufacture. Type tests must not have been conducted earlier than five years from the date of opening of bids. In case the type tests were conducted earlier than five years, such type tests shall be carried out by the successful bidder free of cost before commencement of supply. The undertaking to this effect shall be furnished along with the offer without which the offer shall be liable for rejection. As a part of technical offer, bidder shall include a tabulation detailing various type tests on each type of equipment along with applicable type test certificate number, details of the equipment subjected to type test, place of testing and final results In the offered CVT, if there are changes in the components or in the design/type as compared to the CVT already type tested, the purchaser reserves the right to demand repetition of tests without any extra cost before commencement of supply. The bidder shall bring out in his offer all such changes made in components, materials, design etc. as the case may be and likely effects of such changes on type qualification Type Tests Sr. No. Test 1 Impulse voltage withstand test 2 Wet test for outdoor type transformers Power frequency voltage test 4 Temperature rise test 5 Test for accuracy/ errors 6 Corona inception and extinction test 7 Radio Interference Voltage measurement 8 Chopped impulse test 9 Short circuit withstand capability test 10 Ferro resonance tests

11 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Transient response tests 12 Tightness test of EMU 1 Type test for carrier frequency accessories 14 Measurement of capacitance and tan δ test 15 Seismic withstand capability 16 Verification of the degree of protection 18 Enclosure tightness test at ambient temperature 19 Pressure test for the enclosure 20 Type test for hollow insulators Type tests on capacitor divider units as per IEC Measurement of high frequency capacitance and equivalent series resistance Stray capacitance and stray conductance measurement on LV side Determination of temperature coefficient of capacitance Routine Tests Sr. No. Test 1 Verification of terminal marking and polarity 2 Partial discharge measurement Test for accuracy 4 Measurement of capacitance and dielectric dissipation factor 5 Power frequency withstand tests on primary terminals 6 Power frequency withstand tests on secondary terminals 7 Power frequency withstand tests between sections 8 Ferro-resonance check 9 Test for carrier frequency accessories 10 Pressure test 11 Enclosure tightness test at ambient temperature 12 Dew point measurement test for SF6 gas filled CVT. 1 SF6 alarm / lockout check for SF6 gas filled CVT Special tests Sr. No. Test Tightness design test of capacitor units Thermal coefficient test Mechanical tests Transmitted over voltage test Internal arc fault test Enclosure tightness test at low and high temperatures Corrosion test Fire hazard test 7.0 QUALITY SURVEILLANCE 7.1. General

12 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e The general requirements regarding quality assurance, organisational set up for quality surveillance, qualification and experience details of personnel of quality Assurance department, QA Manual, Mock up test procedures etc. are covered in Section C-0 and the GCC Quality control plan This indicates the requirements expected from the contractor/manufacturer of the Instrument Transformers. Subsequent to the placement of Purchase Order contractor/manufacturer shall submit for purchaser s approval a quality assurance plan in line with this document incorporating specific document numbers for format of records, acceptance norms and reference documents Abbreviations: V P W H Verified by Performed by Witnessed by (After lapse of due notice to NPCIL, manufacturer may proceed with manufacture) Hold (Unless a written clearance is obtained from NPCIL, manufacturer shall not proceed to next stage) 1 NPCIL QS 2 Prime Supplier / EPC Contractor Approved External Laboratory or Sub Vendor QC (if vendor QC / facility not available.) AD- PC Approved Document such as Tender Document, Purchase order, Drawings & Test Procedures - Test Report - Plant Standard CHP - Customer Hold Point (Customer is NPCIL) IS - Indian Standards IEC - International Electro-technical Commission standards - Institute of Electronics and Electrical Engineers standards Notes: Wherever V & W are both indicated, NPCIL QS to witness test or review s. s not more than five year old from date of opening of Part-I of tender shall be reviewed for acceptance. Otherwise test shall be carried out. Minor: The characteristic of a component, process or operation whose failure neither materially reduce the usability of the product in operation, nordoes it affect the aesthetic aspects. : The characteristic of a component, process or operation whose failure may cause operation failure which cannot be readily corrected at site or cause substandard performance, increased erection and maintenance cost, reduced life or seriously affect aesthetics or ergonomics.

13 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 1 2 Critical: The characteristics of a component, process or operation failure of which will surely cause operating failure or intermittent troubles which is difficult to rectify at site or render the unit unfit for use or safety hazards. Failure of a characteristic means failure to meet the acceptance norms. Sampling: Generally in accordance with IS: Sampling will be used as under:- If witness is carried out by Prime contractor, NPCIL will witness on sample basis, or if witness of tests is carried out by subcontractor, Prime contractor will witness on sample basis. Any deviation to this QAP shall be brought out by vendor in his offer failing which this QAP shall be complied with fully.

14 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 1 Quality Assurance Plan for Capacitor Voltage Transformer Sr. No. Component Characteristic Categor y Method Extent of check Extent of check Accep tance norms Format of record Agency V P W H Rem arks 1.0 Aluminium Foil a. Presence of foreign particles and surface finish b. Dimensions c. Tensile strength d. Foil purity e. Wet ability Visual measurement physical chemical Physical Sampling - Do - - Do - - Do - - Do Condenser tissue paper 1.Damage 2. a. Thickness b. Density. Dielectric Strength 4. Mineral Ash content 5. PH Value 6. Conductivity aqueous extract 7. Freedom from conducting path 8. Chlorine content 9. Loss Angle Visual measurement physical Electrical Chemical Chemical Electrical Electrical Chemical Electrical Sampling - Do - - Do - - Do - - Do - - Do - Do - Do - Do -

15 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Enamelled Copper wire 1. Insulation defect. 2. Dimensions. Electrical resistance 4. Elongation 5. Jerk test 6. Resistance to Abrasion 7. Heat shock 8. Cut Through 9. Cure test 10. Solvent test 11. Break Down Voltage 4.0 Core 1. Surface Defects 2. Dimension. Magnetic property 5.0 Porcelain / composite insulator Electrical Measurement Electrical Physical Physical Physical Physical Physical Physical Chemical Electrical Visual Measurement Physical - Do - - Do - Do - Do - Do - Do - Do - Do - Do - Do - Do - Sampling Sampling 1. Dielectric strength HV Test IS/IEC IS/IEC 2. Visual, creepage & Measurement IS/IEC IS/IEC dimension. Temperature cycle Measurement IS/IEC IS/IEC 4. Pressure Test Measurement 5. Porosity Measurement Sample IS/IEC IS/IEC 6. Internal flaw Ultrasonic 7. Bending strength Measurement Sample IS IS 8. Bending Strength at 70 % of withstand bending strength Measurement IS IS

16 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Tank & Tank cover 7.0 H.V. Bushing 1. Surface Defects 2. Dimension. Dielectric tests 8.0 Spark gap 1. Dimension 2. Breakdown voltage 9.0 Oil / SF6 All characteristics as per standard 10.0 Capacitor foil 1. Destructive check winding of foil 11.0 Stack pressure 1. Pressure 2. Height 9. Parallelism & Mechanical IS IS eccentricity 10. Hydrophobicity Mechanical (For composite insulator) 11. Chemical Mechanical Samplin composition (For composite insulator) g 12. Acceptance and Measurement IEC / IEC / Routine tests IS IS 1. Type test Measurement Samplin g IEC / IS IEC / IS 1. Dimensions. Measurement Sampling 2. Leakage test Physical. Fabrication Physical 1 4. Galvanizing / Physical 1 painting Visual Measurement Electrical Measurement Electrical Test Sampling IS / IS / IEC IEC Physical -do- Physical Physical

17 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Drying & Impregnation 1.0 Pressing of stack after impregnation 14.0 Tests on complete Capacitor unit 15.0 Tests on Electromagnetic Unit 16.0 Tests on complete CVT. 1. Control of Process 1. Pressure 2. Height All routine tests Natural frequency test All routine tests Natural frequency test All routine tests All type tests Special tests Physical measurement Visual/Electrica l -do- Critical Critical -do- -do- Sampling Sampling IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC

18 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 1 7 SECTION-D 1. GUARANTEED TECHNICAL PARTICULARS The TENDERER along with his offer shall furnish following guaranteed technical particulars for the Capacitance Voltage Transformers covered by this specification: Sl No. Description UOM Bidders Compliance 1.0 Manufacturer's name 2.0 Type (Oil/SF6).0 Designation 4.0 Applicable standards 5.0 Rated frequency 6.0 Number of secondary windings 7.0 Rated primary voltage 8.0 Rated secondary voltage Sec. winding - 1 Sec. winding - 2 Sec. winding Method of connections 9.1 Primary winding 9.2 Secondary winding Sec. winding - 1 Sec. winding - 2 Sec. winding Rated voltage factor Continuous 5 sec. 0 Sec Rated VA burden on secondary windings Sec. winding - 1 Sec. winding - 2 Sec. winding Rated power factor for secondary windings at rated VA Sec. winding - 1 Sec. winding - 2 Sec. winding Accuracy class of secondary windings 14.0 Class of insulation of windings 15.0 Maximum temperature rise of windings at 110% excitation at rated burden and at rated

19 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 1 8 frequency, when referred to specified ambient temperature (50 C) 16.0 Whether CVTs are suitable for carrier coupling 17.0 Capacitance values at rated frequency and at rated temperature for i) High voltage capacitance ii) Intermediate voltage capacitance iii) Equivalent capacitance for carrier coupling Natural Frequency of coupling 19.0 Self tuning frequency (capacitor part) 20.0 Band width 21.0 Maximum permissible impedance at power frequency of carrier coupling device 22.0 Rated temperature at which above values are indicated 2.0 Capacitance temperature coefficient 24.0 Rated intermediate voltage 25.0 Rated primary voltage of electromagnetic unit 26.0 Insulation withstand test voltages i) Power frequency test voltage for CVT ii) Capacitor voltage divider unit iii) Low voltage terminal of the capacitor voltage divider iv) Primary winding of electromagnetic unit v) Secondary winding of electromagnetic unit /50 microsecond lightning impulse withstand test voltage for capacitor units of CVT /2500 micro sec switching impulse withstand test voltage for capacitor units of CVT 29.0 Radio interference voltage at 1.1 x Um/ for frequency between 0.5 MHz to 2 MHz

20 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e Partial discharge Test voltage Magnitude 1.0 Corona Extinction Voltage 2.0 Minimum creepage distance for insulator housing.0 Insulator shed configuration details 4.0 Insulator shed profile drawing furnished 5.0 Mechanical strength of CVT actually provided 6.0 Whether the earth terminal of the voltage divider is provided i) If yes, the rated voltage ii) One minute power frequency withstand voltage 7.0 Whether the protective gap across the primary side of electromagnetic unit is provided in case of CVT i) If yes, the spark over voltage 8.0 Whether the series reactance/ high voltage choke/ compensating coil is provided in case of CVT i) If yes, rated voltage ii) One minute power frequency withstand voltage 9.0 Terminal box details i) Degree of protection ii) Whether space heater or anti-condensation paint is provided iii) Whether the cable glands are supplied loose iv) If yes, the size and quantity 40.0 Whether the following items are provided in a separate housing for CVT HF ground switch, Drain coil, Over voltage suppressor for HF coupling unit, If yes, indicate the values for

21 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 2 0 i) Drain coil ii) Over voltage suppressor iii) Degree of protection for separate housing 41.0 Whether separate TB for VHF terminal provided for carrier coupling 42.0 Provision made for accepting the changes in oil volume 4.0 Make of hollow porcelain / composite insulator housing 44.0 Overall dimensions 45.0 Shipping dimensions 46.0 Weight 47.0 Shipping weight 48.0 Quantity of oil / SF6 gas and standard to which it conforms 49.0 All type tests as per Section C, Clause-6 carried out 50.0 Drawings/information as called for under Clause-6 submitted with the bid Mean Time between Failures (MTBF) 52.0 Recommended Test Frequency 5.0 Impact of ageing on equipment performance 54.0 Life in terms of i) Number of cycles of operation ii) Years of operation Recommended calibration frequency 56.0 SF6 gas filled pressure (if applicable) 57.0 SF6 gas alarm pressure (if applicable) 58.0 SF6 gas lockout pressure for CB tripping (if applicable) 59.0 SF6 gas pressure where refilling is required (if applicable)

22 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e SCHEDULE OF PROPOSED EQUIPMENT MANUFACTURER S GENERAL PARTICULARS The TENDERER shall furnish here the following general particulars of the Equipment manufacturers of all the equipment covered in this specification: 1.0 Name of the manufacturer: 2.0 Address of the manufacturer:.0 Telegraphic and addresses of the manufacturer: 4.0 Name and designation of the Officer of the manufacturer to whom all reference shall be made for expeditious technical co-ordination: 5.0 Place of manufacture & assembly: 6.0 Current registration number with DGS & D: 7.0 Whether service facilities available, if so details: 8.0 Whether sufficient spares are available in stock: 9.0 Are all technical particulars called for in the section D filled up: 10.0 Are all deviations pointed out in the schedule of deviation: SEAL OF COMPANY SIGNATURE DESIGNATION COMPANY DATE

23 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 2 2. DRAWINGS TO BE SUBMITTED ALONG WITH THE TENDER As part of the proposal the TENDERER shall furnish the following for preliminary study: a) General arrangement drawing for Capacitor Voltage Transformers, loading on foundation etc. b) Detailed literature/catalogues of the equipment being offered under this contract. f) Any other drawings necessary for the correct and complete understanding of the proposal. NOTE All drawings and data shall be annotated in English. SEAL OF COMPANY SIGNATURE DESIGNATION COMPANY DATE

24 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 2 4. PERFORMANCE DATA, INCLUDING PERFORMANCE CURVES ETC. TO BE SUBMITTED ALONGWITH THE TENDER Tenderer shall submit a tabulation indicating rating of the CVT type tested, type tests carried out, severity levels, place of type testing, type test certificate reference number, data of testing and whether any modification to the type tested equipment has been carried out after type testing and whether the type tested equipment and the equipment offered are identical. SEAL OF COMPANY SIGNATURE DESIGNATION COMPANY DATE

25 220 KV CAPACITOR VOLTAGE ANSFORMERS P a g e 2 4 Annexure-1 Existing CVT Mounting Dimension Drawing

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS 006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR

More information

CAPACITOR VOLTAGE TRANSFORMER

CAPACITOR VOLTAGE TRANSFORMER CAPACITOR VOLTAGE TRANSFORMER March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV

More information

POTENTIAL TRANSFORMER

POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS

TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. CIRCLE OFFICE, NADIAD TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio

Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio 1.0 SCOPE : This section covers the design, manufacturing, assembly, testing at the manufacturer

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS 400KV, 8800PF LINE CVT FOR EXISTING & NEW SUB- STATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS 400KV, 8800PF LINE CVT FOR EXISTING & NEW SUB- STATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 400KV, 8800PF LINE CVT FOR EXISTING & NEW SUB- STATIONS GETCO/E/TS-400KV

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. TECHNICAL SPECIFICATION FOR. 36 kv (PROTECTION CUM METERING) INSTRUMENT TRANSFORMERS

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. TECHNICAL SPECIFICATION FOR. 36 kv (PROTECTION CUM METERING) INSTRUMENT TRANSFORMERS MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. TECHNICAL SPECIFICATION FOR 36 kv (PROTECTION CUM METERING) INSTRUMENT TRANSFORMERS FOR VARIOUS SUBSTATIONS IN MAHARASHTRA {(SPECIFICATION NO.: DIST/

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

GENERAL TECHNICAL SPECIFICATION (Turnkey Work)

GENERAL TECHNICAL SPECIFICATION (Turnkey Work) GENERAL TECHNICAL SPECIFICATION (Turnkey Work) March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

1.0 mh, 3150 A LINE TRAP

1.0 mh, 3150 A LINE TRAP GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 1.0 mh, 3150 A LINE TRAP GETCO/E/TS-400KV WT 0904/R0, Dt: 09.01.2012

More information

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only. Separate

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor

More information

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules

More information

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES KP/3CB/TSP/0/00 04-09-9 Page of 9 TABLE OF CONTENTS 0. Circulation List 0. Amendment Record FOREWORD. SCOPE. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING, LABELLING

More information

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only.

More information

Ritz Instrument Transformers GmbH. Welcome

Ritz Instrument Transformers GmbH. Welcome Ritz Instrument Transformers GmbH Welcome About Ritz together with over 200 years of experience in instrument transformer production since 1945 since 1945 since 1945 since 1904 RITZ Group - Organization

More information

User s Manual For CT Model IMB

User s Manual For CT Model IMB User s Manual For CT Model IMB 2 of (13) Contents: A. Introduction... 3 B. Steps on receipt and opening the cases... 3 C. Transportation and handling... 3 D. Unpacking the transformer... 4 E. Storage...

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

Form-IV. Form of Inspection/Test Report. (Under Regulation 43) Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Corporate Office, Sardar Patel Vidyut Bhavan, Race Course, VADODARA 390 007. TECHNICAL SPECIFICATIONS OF CVT / COUPLING CAPACITOR STRUCTURE SPECIAL INSTRUCTIONS

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

Inductive Voltage Transformers. Types VEOT and VEOS

Inductive Voltage Transformers. Types VEOT and VEOS Inductive Voltage Transformers Types VEOT and VEOS Inductive Voltage Transformers Introduction Trench is a recognized world leader in the design and manufacture of high voltage equipment for application

More information

4. CAPACITIVE VOLTAGE TRANSFORMERS AND COUPLING CAPACITORS Oil-paper insulation

4. CAPACITIVE VOLTAGE TRANSFORMERS AND COUPLING CAPACITORS Oil-paper insulation 4. CPCITIVE VOLTGE TRNSFORMERS ND COUPLING CPCITORS 420 kv Capacitive voltage transformers. Fingrid, Visulahti (Finland). 34 Instrument transformers High voltage INTRODUCTION Capacitive voltage transformers

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. 1. SCOPE: This specification covers design, manufacture, testing and supply of 6.64/10.12 KV 24/15.7, 30/19.7

More information

A. Extent of structural precast concrete work is shown on drawings and in schedules.

A. Extent of structural precast concrete work is shown on drawings and in schedules. SECTION 03 41 00 - STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification

More information

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2 TECHNICAL SPECIFICATIONS Rev 00 Page 1 of 2 0 IFI Release for Enquiry 14/12/18 SSS 14/12/18 HGG 14/12/18 RBU - Rev. Status Description Date Prepared Date Checked Date Approved AC Based on: PIN-QMC-03-F101

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

GENERAL TECHNICAL SPECIFICATION

GENERAL TECHNICAL SPECIFICATION GENERAL TECHNICAL SPECIFICATION September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS GETCO/E/06TS CT PT/R5+metering/Jan 10 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv CURRENT TRANSFORMER & 66

More information

SECTION METAL FABRICATIONS

SECTION METAL FABRICATIONS SECTION 05100 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for metal fabrications, including minimum requirements for fabricator, and galvanizing. 1.02 REFERENCE STANDARDS A. ASTM

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

Combined Instrument Transformers. Types IVOKT and TMC

Combined Instrument Transformers. Types IVOKT and TMC Combined Instrument Transformers Types IVOKT and TMC Combined Instrument Transformers Introduction Trench is a recognized world leader in the design and manufacture of high voltage equipment for application

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

High Votage Module AC/DC/Impulse Test System

High Votage Module AC/DC/Impulse Test System TSGADI Series High Votage Module AC/DC/Impulse Test System A digital control and measuring system is used to be control the difference output AC/DC/Impulse and related protection device such as over voltage

More information

Voltage Transformers type UMZ User s Manual, Operation and Maintenance

Voltage Transformers type UMZ User s Manual, Operation and Maintenance Voltage Transformers type UMZ User s Manual, Operation and Maintenance ÿþþ Safety at first Safety instructions: Installation, connecting, operation and maintenance should be carried out by the authorised

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

001: 2007 CEB STANDARD

001: 2007 CEB STANDARD 001: 2007 CEB STANDARD ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEYLON ELECTRICITY BOARD SRI LANKA Specification for ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEB Standard 001: 2007 CEYLON ELECTRICITY

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

TECHNICAL SPECIFICATION FOR LEVEL CONTROL VALVE HANDLING WATER

TECHNICAL SPECIFICATION FOR LEVEL CONTROL VALVE HANDLING WATER ANNEXURE-C TO TENDER BAP/FGD/2012/OT-1 BONGAIGAON 3X250 MW FLUE GAS DESULFURIZATION SYSTEM TECHNICAL SPECIFICATION LEVEL CONTROL VALVE HANDLING WATER CUSTOMER : NATIONAL THERMAL POWER CORPORATION LIMITED

More information

Outdoor Instrument Transformers Buyer s Guide

Outdoor Instrument Transformers Buyer s Guide Outdoor Instrument Transformers Buyer s Guide Table of content Page Products Introduction 3 Explanations 4 Silicone Rubber (SIR) Insulators 7 Design features and Advantages Currrent transformers IMB 8

More information

Oil insulated Outdoor Instrument Transformers Buyer s Guide

Oil insulated Outdoor Instrument Transformers Buyer s Guide Oil insulated Outdoor Instrument Transformers Buyer s Guide Table of content Page Products Introduction 3 Explanations 4 Silicone Rubber (SIR) Insulators 7 Design features and Advantages Current transformers

More information

TECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) S. No. PARTICULARS BHEL SPECIFICATIONS

TECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) S. No. PARTICULARS BHEL SPECIFICATIONS TECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) BIDDER s OFFER S. No. PARTICULARS BHEL SPECIFICATIONS 1.0 Area of Application The 300kV Constant potential

More information

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:

More information

Basic Principles and Operation of Transformer

Basic Principles and Operation of Transformer Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core

More information

This Manual Part recommends design criteria for resistors suitable for railway signaling circuits other than electronic.

This Manual Part recommends design criteria for resistors suitable for railway signaling circuits other than electronic. 2016 Part 14.2.15 Recommended Design Criteria for Resistors Revised 2016 (6 Pages) A. Purpose z00381hn 3/12/15 8:34 AM z00381hn 3/12/15 8:37 AM This Manual Part recommends design criteria for resistors

More information

Reactor and inductor are names used interchangeably for this circuit device.

Reactor and inductor are names used interchangeably for this circuit device. Recommended Design Criteria for Air-Cooled Reactor for Line and Track Circuits Revised 2015 (7 Pages) A. Purpose This Manual Part recommends design criteria for an air-cooled reactor for line and track

More information

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) 1.0 General This specification covers the electrical characteristics and

More information

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL

More information

3. COMBINED TRANSFORMERS Oil-paper insulation

3. COMBINED TRANSFORMERS Oil-paper insulation 3. COMBINED TRANSFORMERS Oil-paper insulation 123 kv Combined transformers. 26 Instrument transformers High voltage INTRODUCTION Combined instrument transformers contain a current transformer and an inductive

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX Particulate Control O&M Training APC/PCUG Conference July 12-16, 2009 The Woodlands, TX WPCA Particulate Training Seminar July 11, 2009 ESP Power Supply Choices Slide No 1 Precipitator Power Supplies Conventional

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv June 2016 Issue 1 1. INTRODUCTION Introduction of contestability and the ability of all major customers to become contestable

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

CAST RESIN DRY TRANSFORMER

CAST RESIN DRY TRANSFORMER CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,

More information

(

( (www.xatianhong.com) Introduction to XATH Xi'an Tianhong Electric Co., Ltd. (XATH) is a solely state-owned enterprise, set up by China Shipbuilding Industry Corporation (CSIC). It is one of the largest

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

Your safety first! This is the reason why our manual begins with the following guidelines:

Your safety first! This is the reason why our manual begins with the following guidelines: High Voltage Products Current Transformers PA 123a and PA 145a Installation and operation manual Your safety first! This is the reason why our manual begins with the following guidelines: Use the transformer

More information

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0 Touch Switch Unique 18 mm Capacitive Touch Switch with Choice of Three Actuators is Activated with Only a Very Slight Physical Contact Lightweight objects, such as thin wire or foil can be accurately detected.

More information

DISTRIBUTION TRANSFORMER 11 / kv

DISTRIBUTION TRANSFORMER 11 / kv Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

HOW TO SAFE GUARD THE TRANSFORMER..???

HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MSC-III/LT CAP/1/2009/R2(071009) SPECIFICATIONS FOR APP TYPE L.T. CAPACITOR UNITS OF 25 / 30 KVAR CAPACITY (FOR 63 / 100

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS SAUDI STANDARD NO. SASO IEC 60669-2-2: 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS Part 2-2: Particular requirements Electromagnetic remote-control switches (RCS) SAUDI ARABIAN

More information

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE

More information

SPECIAL SPECIFICATION 1806 Spread Spectrum Wireless Modem

SPECIAL SPECIFICATION 1806 Spread Spectrum Wireless Modem 1993 Specifications CSJ s 0902-48-442 & 0902-48-432 SPECIAL SPECIFICATION 1806 Spread Spectrum Wireless Modem 1. General. This Item shall govern for the furnishing and installation of Spread Spectrum Wireless

More information

Outdoor Instrument Transformers. Buyer s Guide

Outdoor Instrument Transformers. Buyer s Guide Outdoor Instrument Transformers Buyer s Guide Contents Table of Contents Products Chapter - Page Introduction A - 2 Definitions B - 1 Silicone Rubber (SIR) Insulators C - 1 Enquiry and Ordering Data D

More information