SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

Size: px
Start display at page:

Download "SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS."

Transcription

1 SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. 1. SCOPE: This specification covers design, manufacture, testing and supply of 6.64/10.12 KV 24/15.7, 30/19.7 & 45/29.5 Amps special design transformers. 2. The supplier shall have to produce an attested copy of the License of manufacturing the special Design Transformer from the patent holder of the concept (GUVNL). 3.1 AMBIENT CONDITIONS : i. Maximum ambient temperature in shade : 45 C ii. Max. weighted average ambient temp. : 40 C iii. Maximum temperature under sun : 55 C iv. Minimum ambient temperature : 0 C v. Maximum relative humidity : 95% vi. Average thunder storm days / annum : 15 vii. Average rainy days per annum : 90 viii. Average annual rail fall : 750/800Ml ix. Number of months of tropical monsoon : 3 x. Maximum wind pressure : 150 Kg/M INSTALLTION : Outdoor either pole mounted, hung or platform mounted. 3.3 SYSTEM : 11KV CLASS Single Phase, 50 Hz + 3% Voltage Class : volts Voltage variation : + 5% BIL : 75 KV peak 4. APPLICABLE STANDARDS : Unless otherwise specifically stated in this specification the transformers shall conform to the following standards considering this as single phase transformers. IS 2026 Part I, II, III & IV IS IS-6600/1972 IS 3347 IS IS IS

2 5. MATERIAL : 5.1 INSULATION : The insulation of wire / strip, inter-layers between two winding and to earth shall be of class A. Wherever wood is used it shall be well-seasoned and dry. Wire/strips shall be DPC. So far as paper, press Boards are used they shall be of reputed makes (Appendix A) and conform to ISI. 5.2 WINDING : Transformers shall have Copper windings except below 30 Amps 11 KV Class which shall have Aluminum winding. 6. STANDARD RATINGS : 6.1 The Standard continuous ratings are 24,30 & 45 Amps. 6.2 No load voltage ratio : 6.64/10.12 KV for 11 KV class. 7. FITTINGS : The following standard fittings shall be provided : i) Phase R should be identified as it is ground phase with symbol 1 ii) iii) iv) The Earthing terminals with symbol 1 with tinned copper lugs. Lifting lugs of adequate size for lifting the transformer and lifting the active parts assembly separately. The lifting lugs shall be made from minimum 8mm thick MS Plate with adequate base. Rating and terminal marking plates. The figures shall be etched and not anodized. The plates shall be riveted on oil level gauge side. v) Thermometer pocket for all ratings. The tube of thermometer pocket shall vi) vii) remain immersed in oil to the extent of at least 100mm. Oil conservator tank (a) filling hole and plug on the top. (b) Oil level gauge and (c) Breather of having aluminum die cast body and silica gel 0.5 Kg. Breather pipe shall be provided. Position of oil level gauge shall be towards rating and terminal marking plate. A drain cum sampling valve of 32 mm dia (1.1/4 Bsp) with plug on top cover of the transformers for drawing sample etc.

3 8. TECHNICAL PARTICULARS : 8.1 LOSSES AND IMPEDANCE : The no-load loss, load loss and impedance value for transformers shall be as under. The tolerance for percentage impedance shall be + 10% No-load current No load losses at rated voltage & frequency Load losses at 75 C Rating Wind- Impedance ing at 75 C Y-B Short Y-B Short A. a) 24 A/11KV Al. 1% 170 W 1250 W 2.5 % 7.64 % b) 24 A/11KV Cop. 1% 160 W 1140 W 2.5% 7.64 % B. 30 A/11KV Cop. 1% 180 W 1340 W 2.6% 7.75 % C. 45 A/11KV Cop. 1% 230 W 1840 W 2.6% 7.75 % Note : In actual execution if a unit records higher losses i.e. beyond permissible tolerance, the same will be rejected. 8.2 TEMPERATURE RISE LIMIT : a) Temperature rise in top oil by thermometer. : 40 C Max. b) Temperature rise in winding by resistance method : 50 C Max. 9. BUSHING AND METAL PARTS : The HV porcelain bushings and metal parts shall be as per following IS: IS 5621/80 IS 7421/88 IS 2099/86 IS 3347 (Part III/ Sec. I / 1988) IS 3347 (Part -I/ Sec. I / 1979) IS (Part III/ Sec. II / 1982) The metal parts shall be made from drawn or rolled quality tinned brass or copper of electro plated. 10. TRANSFORMER OIL : The Transformer oil to be supplied as first filling of transformer shall comply with IS-335/ TRANSFORMER TANK : 11.1 The tank will be made of prime quality MS sheet of thickness stated below with necessary stiffener to withstand the pressures built in during the expansion of oil due to temperature rise.

4 11 KV Rating Minimum thickness of plate in mm For sides For Top & Bottom 24 Amps Amps Amps The exterior of the transformer tank and other ferrous fittings shall be thoroughly cleaned, scraped/ sand blasted and given a priming coat and two finishing coats of durable oil and weather resistant paint of light admiralty Gray conforming to colour code No. 697 of IS-5/ Inside of the tank shall be thoroughly cleaned/scrapped/sand blasted and coated with oil resistant paint or epoxy coat or phonemic / melamine varnish coat. These protective coats shall not contaminate the oil due to due to peeling or decomposition during the life of the transformers All the screws, bolts and nuts exposed to atmosphere shall be hot dip galvanized if diameter is 12 mm or more. They shall be either electro galvanized or hot dip galvanized if diameter is less than 12 mm. The screws and clamps for fixing HV bushing shall also be electro-galvanized. The inside dimension of the tank and shape to clearly indicated in the drawings. Only positive 5% tolerance will be allowed in actual fabrication of tank, no negative tolerance will be allowed. 12. CORE : 12.1 CORE MATERIALS : Non edging, oxide film coated CRGO laminations of prime quality shall be used as core material CONSTRUCTION : Core shall be so constructed that there are adequate vertical cooling ducts to cool the core. The core when vertically standing shall be rigid. Insulated core / type bolts shall be provided wherever necessary The core shall be so constructed that the air-gaps in all the limbs are identical FLUX DENSITY : The flux density shall be so selected that over fluxing is limited to 5% over voltage (Max. 1.9 Tesla)

5 NO LOAD CURRENT : The percentage no load current shall be as under : Minimum percentage no load current at Normal voltage 5% over voltage 24 Amps Amps Amps WINDING : This is generally of round wire and coils are in form of packets and number of coils are connected in series to achieve the necessary voltage ratio. The coils assembly should be sand with type The number of coils per limb shall depend upon the necessary cooling surface and the mechanical strength CONNECTION : The coil series connections shall be crimped / brazed or screw connected after thoroughly cleaning the ends. The joint in the coil shall be buttwelded. However the brazing of copper wire shall be acceptable. All connections shall be insulated by paper wrapping, leads shall be properly supported and secured in place avoiding accidental short circuit. Coils supports shall be of rigid non-compressible insulating material. 14. ASSEMBLY : The core and coil assembly shall be supported by press channels and the coils fully pressed by the tie rods. Guides on all the four sides shall be provided to prevent shifting of the active parts and thereby accidental touching the tank. 15. DRAWING : The Tenderer shall submit the following drawings along with offer GENERAL ARRANGEMENT : G.A. drawing showing fittings shall be furnished. The details of cooling system, viz. Number of cooling tubes radiators, their size and position on tank must be very clearly indicated. The details on drawing shall be in line with G.T.P.

6 16. TERNIMAL ARRANGEMENT : 17. The HV bushings shall be of approved makes. (please refer Appendix A for approved suppliers) 17.1 TERNIMAL ARRANGEMENT : (a) Phase to phase (b) Phase to earth H.V. 11 KV 255mm 205mm 18. ROUTINE TESTS : All routine tests as per Appendix C attached. 19. DEVIATION FROM SPECIFICATION : There shall be no deviatio0n from these specifications, norms and procedures. However, if tenderer to do so, the same shall be indicated only of the guaranteed technical particulars. 20. PACKING : The packing shall be robust enough for the rough handling which is normal during rail / road transport. The details of the packing are however, left kto the discretion of the manufacturer. 21. GUARANTEED TECHNICAL PARTICULARS (GTP) : Tenderer should submit the details in Appendix B attached. 22. ESTING INSTRUMENTS : The class of accuracy of instruments shall be as under : (a) Watt meters class or better (b) Voltmeter & Ammeter class or better 23. GUARANTEE & WARANTEE : The guarantee period shall be 12 months from the date of supply for the manufacturing defect. If the transformer fails during guarantee period the supplier should arrange to repair the failed transformer with in one month on receipt of GP failed transformer at their works. To and fro arrangement shall be made by the Company. 24. TESTING OF TRANSFORMER OIL : The sample of transformer oil to be drained from one of the transformer selected randomly from the lot offered for inspection and the test results must match as per IS 335 / 1987.

7 A P E N D I X A APPROVED SUPPLIERS FOR VARIO9US MATERIALS ARE AS UNDER: (1) Bushings : H.V. 1. BEPCO 2. JAYASHREE 3. W.S.I. 4. ASSOCIATED PORCELAIN (Only 11KV) 5. SESHASAYEE 6. JAIPUR GLASS (Only 11KV) 7. LUSTER CERAMICS NOTE : Embossing showing the manufacturer s name should be clearly visible, even after fixing the same on transformer. (2) Insulation Paper : (1) Triveni Tissus or any other reputed make (2) Any other reputed imported make (3) Insulating Materials : (1) Senapati Whitely (2) Raman Boards (3) Shalimar (4) Permali-Wallace (5) Wipro

8 A P P E N D I X B Manufacturers name and address : G.T.P. Sr.No. Particulars Confirmation 1 It shall be conventional 2. Voltage H.V Impulse withstand voltage of 75 KV Peak for 11 KV Class. 4. Transformers shall Copper windings except below 30 Amps 11 KV Class which shall have Aluminum winding. 5. Insulation Class A 6. a) Top oil temperature rise limit of 40 C by thermometer with feeding of guaranteed load loss plus tolerance converted to 75 C and guaranteed no load loss plus tolerance. b) Temperature rise limit of 50 C of winding by resistance method. 7. LOSSES & IMPEDANCE : 7.1 Maximum no load current & losses at 50 HZ and rated voltage Rating Winding No-load current No load losses at rated voltage & frequency A. a) 24 A/11KV b) 24 A/11KV Al. Cop. 1% 1% 171 W 160 W B. 30 A/11KV Cop. 1% 180 W C. 45 A/11KV Cop. 1% 230 W

9 7.2 Maximum load losses at full load in watts & maximum percentage impedance at 75ºC Rating Winding Load losses at 75 C Impedance at 75 C Y-B Short Y-B Short A. a) 24 A/11KV b) 24 A/11KV Al. Cop W 1140 W 2.5 % 2.5% 7.64 % 7.64 % B. 30 A/11KV Cop W 2.6% 7.75 % C. 45 A/11KV Cop W 2.6% 7.75 % 7.3 Operating flux density at 50 Hz : 1.69 Tesla Max 7.4 Percentage no/load current (Max) at normal voltage and frequency a) 24 Amps 1 b) 30 Amps 1 c) 45 Amps do but at 105% normal voltage a) 24 Amps 2 b) 30 Amps 2 c) 45 Amps 2 8. Pressure test of tank as per IS-1180 Part - I 9. Outside paint Light admiralty Grey as per IS 5 colour code Transformer oil shall conform with IS 335/ Only GUVNL approved make of HV Bushing shall be used. 12. Minimum external clearance as under shall be maintained. 11 KV (a) HV Phase to phase 255mm (b) HV Phase to earth 205mm 13. Thickness of sheet metal in mm for tank shall be following minimum Ratings Sides Top & Bottom a) 24 Amps b) 30 Amps c) 45 Amps

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2 Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

POTENTIAL TRANSFORMER

POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only.

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only. Separate

More information

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS 006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY) E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

EARTHING TRANSFORMER

EARTHING TRANSFORMER EARTHING TRANSFORMER December 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE

More information

Reference Number PPS 05 - (RIC Standard: EP SP)

Reference Number PPS 05 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed

More information

No. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS

No. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS College of Agriculture, Maharana Pratap University of Agriculture & Technology, Bhilwara-311001 (Rajasthan) Phone: 01482-246118 (O), Email: coabhilwara@gmail.com, No. COA/BHL/2018/293 Dated: 07.06.2018

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical

More information

Maharashtra State Electricity Distribution Company Limited

Maharashtra State Electricity Distribution Company Limited Maharashtra State Electricity Distribution Company Limited SPEC. NO. STORES: MSC-II/DT/ 630KVA ID OD/2011 TECHNICAL SPECIFICATION FOR 630 kva, 11/0.433 kv, 22/0.433 kv THREE PHASE, DISTRIBUTION TRANSFORMERS

More information

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED

More information

General Electricity Company of Libya

General Electricity Company of Libya GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company

More information

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer

More information

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules

More information

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

CAPACITOR VOLTAGE TRANSFORMER

CAPACITOR VOLTAGE TRANSFORMER CAPACITOR VOLTAGE TRANSFORMER March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX Particulate Control O&M Training APC/PCUG Conference July 12-16, 2009 The Woodlands, TX WPCA Particulate Training Seminar July 11, 2009 ESP Power Supply Choices Slide No 1 Precipitator Power Supplies Conventional

More information

Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio

Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio 1.0 SCOPE : This section covers the design, manufacturing, assembly, testing at the manufacturer

More information

User s Manual For CT Model IMB

User s Manual For CT Model IMB User s Manual For CT Model IMB 2 of (13) Contents: A. Introduction... 3 B. Steps on receipt and opening the cases... 3 C. Transportation and handling... 3 D. Unpacking the transformer... 4 E. Storage...

More information

TECHNICAL SPECIFICATION FOR SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 )

TECHNICAL SPECIFICATION FOR SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 ) TECHNICAL SPECIFICATION FOR 11/ 3 KV/250V 15 & 25 KVA OUTDOOR TYPE COMPLETELY SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 ) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

HOW TO SAFE GUARD THE TRANSFORMER..???

HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

DISTRIBUTION TRANSFORMER kv

DISTRIBUTION TRANSFORMER kv ELECTRICITY COMMISSION PLANNING AND STUDY DEP BAGHDAD, REPUBLIC OF IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER kv REVISION YEAR 2001 DISTRIBUTION TRANSFORMERS 1- SCOPE OF THE TENDER : Tenderer

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5 Relating to 11kV Distribution Transformers Policy Summary This specification covers the requirements for Distribution Transformers from 16kVA single

More information

TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS

TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. CIRCLE OFFICE, NADIAD TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before

More information

TECHNICAL SPECIFICATION FOR G. I. WIRE (4MM)

TECHNICAL SPECIFICATION FOR G. I. WIRE (4MM) 1. SCOPE: TECHNICAL SPECIFICATION FOR G. I. WIRE (4MM) This Specification provides for manufacture, testing before dispatch at manufacturer's work and supply and delivery of 4mm solid heavily coated Galvanized

More information

This Manual Part recommends design criteria for resistors suitable for railway signaling circuits other than electronic.

This Manual Part recommends design criteria for resistors suitable for railway signaling circuits other than electronic. 2016 Part 14.2.15 Recommended Design Criteria for Resistors Revised 2016 (6 Pages) A. Purpose z00381hn 3/12/15 8:34 AM z00381hn 3/12/15 8:37 AM This Manual Part recommends design criteria for resistors

More information

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17

More information

DISTRIBUTION TRANSFORMER 11 / kv

DISTRIBUTION TRANSFORMER 11 / kv Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The

More information

Maharashtra State Electricity Distribution Company Limited MATERIAL SPECIFICATIONS CELL

Maharashtra State Electricity Distribution Company Limited MATERIAL SPECIFICATIONS CELL Maharashtra State Electricity Distribution Company Limited MATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION FOR TECHNICAL SPECIFICATION OF 10,16 AND 25kVA, 11/0.433 kv & 22/ 0.433 kv LEVEL-2 THREE

More information

(TECHNICAL SPECIFICATIONS & GTP FORMATS) 11KV METERING UNITS

(TECHNICAL SPECIFICATIONS & GTP FORMATS) 11KV METERING UNITS (TECHNICAL SPECIFICATIONS & GTP FORMATS) 11KV METERING UNITS SCHEDULE OF MATERIALS: Sl. No. Name of the Materials Unit Quantity 1 11KV 3Ph 4W CT/PT combined Metering Unit CT Ratio- 400/5A PT Ratio 11000/110V

More information

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head

More information

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL

More information

Technical Specification. for 1.1 KV Copper Control Cable

Technical Specification. for 1.1 KV Copper Control Cable WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

BUREAU OF INDIAN STANDARDS. Draft Indian Standard TWO COMPONENTS HIGH BUILD EPOXY MICACIOUS IRON OXIDE (MIO) PIGMENTED INTERMEDIATE COAT SPECIFICATION

BUREAU OF INDIAN STANDARDS. Draft Indian Standard TWO COMPONENTS HIGH BUILD EPOXY MICACIOUS IRON OXIDE (MIO) PIGMENTED INTERMEDIATE COAT SPECIFICATION FOR BIS USE ONLY DOC:CHD 20 (1932)C December 2012 BUREAU OF INDIAN STANDARDS Draft Indian Standard TWO COMPONENTS HIGH BUILD EPOXY MICACIOUS IRON OXIDE (MIO) PIGMENTED INTERMEDIATE COAT SPECIFICATION (Not

More information

TECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS.

TECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS. TECHNICAL SPECIFICATION OF 630 KVA, 11/ 0.415 KV DRY TYPE OUTDOOR TRANSFORMERS. 1. 0 Scope: This specification covers design, manufacture, testing and supply of 630 KVA, 11/0.415 KV, Dry Type Distribution

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

SECTION METAL FABRICATIONS

SECTION METAL FABRICATIONS SECTION 05100 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for metal fabrications, including minimum requirements for fabricator, and galvanizing. 1.02 REFERENCE STANDARDS A. ASTM

More information

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M SL. NO NOMINAL DIAMETER "D" mm GASKETED JOINT (Nm) WOODEN CORE CLAMP (Nm) STEEL FIXING STUD FOR BUSHING (Nm) BUSHING STEM (Nm) (BRASS /COPPER) COPPER BUSBAR (Nm) 1 M6 5 - - - - 2 M8 12 - - 10-3 M10 22

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPEC. NO. STORES:MSC-II/ conventional power Trf/ 2011 SPECIFICATION FOR 5 MVA and 10 MVA 33/11 kv, 33/22 kv & 22/11 kv POWER TRANSFORMERS FOR VARIOUS

More information

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT SPECIFICATION SS-25 / 14 POWER TRANSFORMERS 150/15.75-21kV, 40/50 MVA WITH AUTOMATIC LOAD-RATIO CONTROL CONNECTION

More information

Basic Principles and Operation of Transformer

Basic Principles and Operation of Transformer Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core

More information

SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS

SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS 26 Requirement of Transformer Repairing Material Tender Notice No-NESCO/TRW-01/1141 dt 27.01.12 Sl.No Desripition of Material Rating

More information

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established

More information

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS PPC TECHNICAL SPECIFICATION D/ NCMD -01. 48/06. 2005 THREE-PHASE DISTRIBUTION TRANSFORMERS 1 CONTENTS 1. SCOPE... 5 2. KEYWORDS... 5 3. OPERATING CONDITIONS... 5 3.1. Environmental conditions... 5 3.2.

More information

Electrical Design Process

Electrical Design Process Electrical Design Process Jason Varnell Lead Design Engineer Jason.Varnell@spx.com SPX Transformer Solutions, Inc. September 26, 2018 Agenda 1. Bid Design Process Parameters Affecting Bid Design 2. Final

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with

More information

SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS

SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS 26 Requirement of Transformer Repairing Material Tender Notice No-NESCO/TRW-03/06 dt 01.06.12 Sl.No Desripition of Material Rating

More information

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED Technical Specification for Energy Efficient(3Star Rated) 11/0.433kV, 3Phase, 50Cycle, Aluminium Wound Distribution Transformer of rating 25/63/100kVA 1. SCOPE:

More information

Maharashtra State Electricity Distribution Company Limited

Maharashtra State Electricity Distribution Company Limited Maharashtra State Electricity Distribution Company Limited SPEC. NO. STORES: MSC-II/DT/Conventional 63,100 CSP with metering /2011 TECHNICAL SPECIFICATION FOR 63, 100 kva, 11/0.433 kv, 22/0.433 kv THREE

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information

PS REV NO: 01 PAGE : 2 OF 22

PS REV NO: 01 PAGE : 2 OF 22 PAGE : 2 OF 22 1.0 INTRODUCTION Bharat Heavy Electricals Limited (BHEL), Electronics Division, Bangalore is setting up a 10 MW Solar PV Grid-connected power plant for its customer BEL at O.F.BOL, Badmal,

More information

Introduction. Centrado leading-edge transformer. Introduction

Introduction. Centrado leading-edge transformer. Introduction Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,

More information

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

MIL- B Rev NAVSEA 0900-LP

MIL- B Rev NAVSEA 0900-LP I: REQUIREMENTS 1. Identify the standard the supplier uses for performing brazing. MIL- B-007883B OTHER (IF Other, Specify :) MIL- B-007883 Rev NAVSEA 0900-LP-001-7000 II: ATTRIBUTES: YES NO 2a. Does a

More information

Transformers handling and transport

Transformers handling and transport Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary

More information

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)

More information

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS) TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part

More information

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/2.14 70mm 2 Version: 1 Issued: January 2015 Owner: Engineering Division Approved By: Pat

More information

SCHEDULE A SR. NO. 1 No.

SCHEDULE A SR. NO. 1 No. SCHEDULE A SR. DESCRIPTION OF MATERIAL QUANTITY Nos. NO. Tender Offered 1. Power Transformer 3500KVA, 11 KV / 6.9KV Voltage Ratio, 183 A / 293 A current ratio, YNyn0 vector, ON cooling, with NGR on LV

More information

Single & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank

Single & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank Single & Three Phase Transformers Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank Product Code: 5634 Table of Contents Introduction... 5 Section 1. Transformer

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION

More information

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured) WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

Howard Smart Transformer Specification Guide

Howard Smart Transformer Specification Guide Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as

More information

TECHNICAL SPECIFICATION FOR OUTDOOR 160 KVA AMORPHOUS / CRGO CORE CSP ALUMINIUM CONDUCTOR DISTRIBUTION TRANSFORMERS WITH BEE 5 STAR RATING

TECHNICAL SPECIFICATION FOR OUTDOOR 160 KVA AMORPHOUS / CRGO CORE CSP ALUMINIUM CONDUCTOR DISTRIBUTION TRANSFORMERS WITH BEE 5 STAR RATING 10.09.2013/20.01.2014 TECHNICAL SPECIFICATION FOR OUTDOOR 160 KVA AMORPHOUS / CRGO CORE CSP ALUMINIUM CONDUCTOR DISTRIBUTION TRANSFORMERS WITH BEE 5 STAR RATING 1. SCOPE : 1.1 This specification covers

More information

Miniature Steam Pty Ltd (Incorporating Live Steam Supplies)

Miniature Steam Pty Ltd (Incorporating Live Steam Supplies) Miniature Steam Pty Ltd (Incorporating Live Steam Supplies) Materials List 28 May 2013 The attached listings outline products we offer and their retail prices as at the above date. We reserve the right

More information

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing). SECTION 15047 - IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Identification including necessary accessories indicated on Construction Documents and specified in this section or as required

More information

Anodising is the process where Aluminum Oxide film is created on the section to avoid corrosion. (The tanks used are nos. 16, 17, 19 and 20)

Anodising is the process where Aluminum Oxide film is created on the section to avoid corrosion. (The tanks used are nos. 16, 17, 19 and 20) ABOUT ANODISING Our New anodizing plant was commissioned in October 2012. Ours is a fully automated plant and the plant is completely designed and commissioned by the Monti Engineering from Italy. The

More information

Liquid-Filled Transformers

Liquid-Filled Transformers Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of

More information

WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LTD.

WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LTD. WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LTD. TECHNICAL SPECIFICATION OF 315 11/0.433 KV BOTH OUTDOOR TYPE WITH OUDOOR BUSHING AT BOTH ENDS AND INDOOR TYPE WITH CABLE END BOX AT BOTH ENDS : 3

More information

MIL- B B. MIL- B Rev NAVSEA 0900-LP II: ATTRIBUTES: YES NO N/A

MIL- B B. MIL- B Rev NAVSEA 0900-LP II: ATTRIBUTES: YES NO N/A XXVIII BRAZE/BRAZING PROCESS I: REQUIREMENTS 1. Identify the standard the supplier uses for performing brazing. MIL- B-007883B MIL- B-007883 Rev OTHER (IF Other, Specify :) NAVSEA 0900-LP-001-7000 II:

More information

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY () SPECIFICATIONS FOR 20/0.4 KV DISTRIBUTION TRANSFORMER OPEN TERMINAL BUSHINGS AND HERMETICALLY SEALED

More information

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES KP/3CB/TSP/0/00 04-09-9 Page of 9 TABLE OF CONTENTS 0. Circulation List 0. Amendment Record FOREWORD. SCOPE. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING, LABELLING

More information

METAL FABRICATION SECTION 8: METAL FABRICATION SCOPE MATERIAL.

METAL FABRICATION SECTION 8: METAL FABRICATION SCOPE MATERIAL. METAL FABRICATION SCOPE This specification applies to all metal intended to be rubber lined. Metals furnished must conform to this specification with respect to suitability for rubber lining or covering.

More information