SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.
|
|
- Geoffrey Stokes
- 5 years ago
- Views:
Transcription
1 SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. 1. SCOPE: This specification covers design, manufacture, testing and supply of 6.64/10.12 KV 24/15.7, 30/19.7 & 45/29.5 Amps special design transformers. 2. The supplier shall have to produce an attested copy of the License of manufacturing the special Design Transformer from the patent holder of the concept (GUVNL). 3.1 AMBIENT CONDITIONS : i. Maximum ambient temperature in shade : 45 C ii. Max. weighted average ambient temp. : 40 C iii. Maximum temperature under sun : 55 C iv. Minimum ambient temperature : 0 C v. Maximum relative humidity : 95% vi. Average thunder storm days / annum : 15 vii. Average rainy days per annum : 90 viii. Average annual rail fall : 750/800Ml ix. Number of months of tropical monsoon : 3 x. Maximum wind pressure : 150 Kg/M INSTALLTION : Outdoor either pole mounted, hung or platform mounted. 3.3 SYSTEM : 11KV CLASS Single Phase, 50 Hz + 3% Voltage Class : volts Voltage variation : + 5% BIL : 75 KV peak 4. APPLICABLE STANDARDS : Unless otherwise specifically stated in this specification the transformers shall conform to the following standards considering this as single phase transformers. IS 2026 Part I, II, III & IV IS IS-6600/1972 IS 3347 IS IS IS
2 5. MATERIAL : 5.1 INSULATION : The insulation of wire / strip, inter-layers between two winding and to earth shall be of class A. Wherever wood is used it shall be well-seasoned and dry. Wire/strips shall be DPC. So far as paper, press Boards are used they shall be of reputed makes (Appendix A) and conform to ISI. 5.2 WINDING : Transformers shall have Copper windings except below 30 Amps 11 KV Class which shall have Aluminum winding. 6. STANDARD RATINGS : 6.1 The Standard continuous ratings are 24,30 & 45 Amps. 6.2 No load voltage ratio : 6.64/10.12 KV for 11 KV class. 7. FITTINGS : The following standard fittings shall be provided : i) Phase R should be identified as it is ground phase with symbol 1 ii) iii) iv) The Earthing terminals with symbol 1 with tinned copper lugs. Lifting lugs of adequate size for lifting the transformer and lifting the active parts assembly separately. The lifting lugs shall be made from minimum 8mm thick MS Plate with adequate base. Rating and terminal marking plates. The figures shall be etched and not anodized. The plates shall be riveted on oil level gauge side. v) Thermometer pocket for all ratings. The tube of thermometer pocket shall vi) vii) remain immersed in oil to the extent of at least 100mm. Oil conservator tank (a) filling hole and plug on the top. (b) Oil level gauge and (c) Breather of having aluminum die cast body and silica gel 0.5 Kg. Breather pipe shall be provided. Position of oil level gauge shall be towards rating and terminal marking plate. A drain cum sampling valve of 32 mm dia (1.1/4 Bsp) with plug on top cover of the transformers for drawing sample etc.
3 8. TECHNICAL PARTICULARS : 8.1 LOSSES AND IMPEDANCE : The no-load loss, load loss and impedance value for transformers shall be as under. The tolerance for percentage impedance shall be + 10% No-load current No load losses at rated voltage & frequency Load losses at 75 C Rating Wind- Impedance ing at 75 C Y-B Short Y-B Short A. a) 24 A/11KV Al. 1% 170 W 1250 W 2.5 % 7.64 % b) 24 A/11KV Cop. 1% 160 W 1140 W 2.5% 7.64 % B. 30 A/11KV Cop. 1% 180 W 1340 W 2.6% 7.75 % C. 45 A/11KV Cop. 1% 230 W 1840 W 2.6% 7.75 % Note : In actual execution if a unit records higher losses i.e. beyond permissible tolerance, the same will be rejected. 8.2 TEMPERATURE RISE LIMIT : a) Temperature rise in top oil by thermometer. : 40 C Max. b) Temperature rise in winding by resistance method : 50 C Max. 9. BUSHING AND METAL PARTS : The HV porcelain bushings and metal parts shall be as per following IS: IS 5621/80 IS 7421/88 IS 2099/86 IS 3347 (Part III/ Sec. I / 1988) IS 3347 (Part -I/ Sec. I / 1979) IS (Part III/ Sec. II / 1982) The metal parts shall be made from drawn or rolled quality tinned brass or copper of electro plated. 10. TRANSFORMER OIL : The Transformer oil to be supplied as first filling of transformer shall comply with IS-335/ TRANSFORMER TANK : 11.1 The tank will be made of prime quality MS sheet of thickness stated below with necessary stiffener to withstand the pressures built in during the expansion of oil due to temperature rise.
4 11 KV Rating Minimum thickness of plate in mm For sides For Top & Bottom 24 Amps Amps Amps The exterior of the transformer tank and other ferrous fittings shall be thoroughly cleaned, scraped/ sand blasted and given a priming coat and two finishing coats of durable oil and weather resistant paint of light admiralty Gray conforming to colour code No. 697 of IS-5/ Inside of the tank shall be thoroughly cleaned/scrapped/sand blasted and coated with oil resistant paint or epoxy coat or phonemic / melamine varnish coat. These protective coats shall not contaminate the oil due to due to peeling or decomposition during the life of the transformers All the screws, bolts and nuts exposed to atmosphere shall be hot dip galvanized if diameter is 12 mm or more. They shall be either electro galvanized or hot dip galvanized if diameter is less than 12 mm. The screws and clamps for fixing HV bushing shall also be electro-galvanized. The inside dimension of the tank and shape to clearly indicated in the drawings. Only positive 5% tolerance will be allowed in actual fabrication of tank, no negative tolerance will be allowed. 12. CORE : 12.1 CORE MATERIALS : Non edging, oxide film coated CRGO laminations of prime quality shall be used as core material CONSTRUCTION : Core shall be so constructed that there are adequate vertical cooling ducts to cool the core. The core when vertically standing shall be rigid. Insulated core / type bolts shall be provided wherever necessary The core shall be so constructed that the air-gaps in all the limbs are identical FLUX DENSITY : The flux density shall be so selected that over fluxing is limited to 5% over voltage (Max. 1.9 Tesla)
5 NO LOAD CURRENT : The percentage no load current shall be as under : Minimum percentage no load current at Normal voltage 5% over voltage 24 Amps Amps Amps WINDING : This is generally of round wire and coils are in form of packets and number of coils are connected in series to achieve the necessary voltage ratio. The coils assembly should be sand with type The number of coils per limb shall depend upon the necessary cooling surface and the mechanical strength CONNECTION : The coil series connections shall be crimped / brazed or screw connected after thoroughly cleaning the ends. The joint in the coil shall be buttwelded. However the brazing of copper wire shall be acceptable. All connections shall be insulated by paper wrapping, leads shall be properly supported and secured in place avoiding accidental short circuit. Coils supports shall be of rigid non-compressible insulating material. 14. ASSEMBLY : The core and coil assembly shall be supported by press channels and the coils fully pressed by the tie rods. Guides on all the four sides shall be provided to prevent shifting of the active parts and thereby accidental touching the tank. 15. DRAWING : The Tenderer shall submit the following drawings along with offer GENERAL ARRANGEMENT : G.A. drawing showing fittings shall be furnished. The details of cooling system, viz. Number of cooling tubes radiators, their size and position on tank must be very clearly indicated. The details on drawing shall be in line with G.T.P.
6 16. TERNIMAL ARRANGEMENT : 17. The HV bushings shall be of approved makes. (please refer Appendix A for approved suppliers) 17.1 TERNIMAL ARRANGEMENT : (a) Phase to phase (b) Phase to earth H.V. 11 KV 255mm 205mm 18. ROUTINE TESTS : All routine tests as per Appendix C attached. 19. DEVIATION FROM SPECIFICATION : There shall be no deviatio0n from these specifications, norms and procedures. However, if tenderer to do so, the same shall be indicated only of the guaranteed technical particulars. 20. PACKING : The packing shall be robust enough for the rough handling which is normal during rail / road transport. The details of the packing are however, left kto the discretion of the manufacturer. 21. GUARANTEED TECHNICAL PARTICULARS (GTP) : Tenderer should submit the details in Appendix B attached. 22. ESTING INSTRUMENTS : The class of accuracy of instruments shall be as under : (a) Watt meters class or better (b) Voltmeter & Ammeter class or better 23. GUARANTEE & WARANTEE : The guarantee period shall be 12 months from the date of supply for the manufacturing defect. If the transformer fails during guarantee period the supplier should arrange to repair the failed transformer with in one month on receipt of GP failed transformer at their works. To and fro arrangement shall be made by the Company. 24. TESTING OF TRANSFORMER OIL : The sample of transformer oil to be drained from one of the transformer selected randomly from the lot offered for inspection and the test results must match as per IS 335 / 1987.
7 A P E N D I X A APPROVED SUPPLIERS FOR VARIO9US MATERIALS ARE AS UNDER: (1) Bushings : H.V. 1. BEPCO 2. JAYASHREE 3. W.S.I. 4. ASSOCIATED PORCELAIN (Only 11KV) 5. SESHASAYEE 6. JAIPUR GLASS (Only 11KV) 7. LUSTER CERAMICS NOTE : Embossing showing the manufacturer s name should be clearly visible, even after fixing the same on transformer. (2) Insulation Paper : (1) Triveni Tissus or any other reputed make (2) Any other reputed imported make (3) Insulating Materials : (1) Senapati Whitely (2) Raman Boards (3) Shalimar (4) Permali-Wallace (5) Wipro
8 A P P E N D I X B Manufacturers name and address : G.T.P. Sr.No. Particulars Confirmation 1 It shall be conventional 2. Voltage H.V Impulse withstand voltage of 75 KV Peak for 11 KV Class. 4. Transformers shall Copper windings except below 30 Amps 11 KV Class which shall have Aluminum winding. 5. Insulation Class A 6. a) Top oil temperature rise limit of 40 C by thermometer with feeding of guaranteed load loss plus tolerance converted to 75 C and guaranteed no load loss plus tolerance. b) Temperature rise limit of 50 C of winding by resistance method. 7. LOSSES & IMPEDANCE : 7.1 Maximum no load current & losses at 50 HZ and rated voltage Rating Winding No-load current No load losses at rated voltage & frequency A. a) 24 A/11KV b) 24 A/11KV Al. Cop. 1% 1% 171 W 160 W B. 30 A/11KV Cop. 1% 180 W C. 45 A/11KV Cop. 1% 230 W
9 7.2 Maximum load losses at full load in watts & maximum percentage impedance at 75ºC Rating Winding Load losses at 75 C Impedance at 75 C Y-B Short Y-B Short A. a) 24 A/11KV b) 24 A/11KV Al. Cop W 1140 W 2.5 % 2.5% 7.64 % 7.64 % B. 30 A/11KV Cop W 2.6% 7.75 % C. 45 A/11KV Cop W 2.6% 7.75 % 7.3 Operating flux density at 50 Hz : 1.69 Tesla Max 7.4 Percentage no/load current (Max) at normal voltage and frequency a) 24 Amps 1 b) 30 Amps 1 c) 45 Amps do but at 105% normal voltage a) 24 Amps 2 b) 30 Amps 2 c) 45 Amps 2 8. Pressure test of tank as per IS-1180 Part - I 9. Outside paint Light admiralty Grey as per IS 5 colour code Transformer oil shall conform with IS 335/ Only GUVNL approved make of HV Bushing shall be used. 12. Minimum external clearance as under shall be maintained. 11 KV (a) HV Phase to phase 255mm (b) HV Phase to earth 205mm 13. Thickness of sheet metal in mm for tank shall be following minimum Ratings Sides Top & Bottom a) 24 Amps b) 30 Amps c) 45 Amps
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationProlific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2
Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II
More informationDATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %
More informationPOTENTIAL TRANSFORMER
POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More informationTECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s
TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only.
More informationGURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM
Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted
More informationTECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE
TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only. Separate
More informationCOMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS
006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR
More informationWESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)
WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices
More informationSOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)
E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION
More informationCONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationTECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C
TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil
More informationSPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS
-1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationEARTHING TRANSFORMER
EARTHING TRANSFORMER December 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More information51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE
More informationReference Number PPS 05 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed
More informationNo. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS
College of Agriculture, Maharana Pratap University of Agriculture & Technology, Bhilwara-311001 (Rajasthan) Phone: 01482-246118 (O), Email: coabhilwara@gmail.com, No. COA/BHL/2018/293 Dated: 07.06.2018
More informationS. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)
S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical
More informationMaharashtra State Electricity Distribution Company Limited
Maharashtra State Electricity Distribution Company Limited SPEC. NO. STORES: MSC-II/DT/ 630KVA ID OD/2011 TECHNICAL SPECIFICATION FOR 630 kva, 11/0.433 kv, 22/0.433 kv THREE PHASE, DISTRIBUTION TRANSFORMERS
More informationsave energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers
save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED
More informationGeneral Electricity Company of Libya
GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company
More information51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer
More informationAPDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL
PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV
More informationPURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS
PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules
More informationCONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS
CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationTECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)
TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +
More informationCAPACITOR VOLTAGE TRANSFORMER
CAPACITOR VOLTAGE TRANSFORMER March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN
More informationMGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested
More information012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)
012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0
More informationParticulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX
Particulate Control O&M Training APC/PCUG Conference July 12-16, 2009 The Woodlands, TX WPCA Particulate Training Seminar July 11, 2009 ESP Power Supply Choices Slide No 1 Precipitator Power Supplies Conventional
More informationTechnical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio
Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio 1.0 SCOPE : This section covers the design, manufacturing, assembly, testing at the manufacturer
More informationUser s Manual For CT Model IMB
User s Manual For CT Model IMB 2 of (13) Contents: A. Introduction... 3 B. Steps on receipt and opening the cases... 3 C. Transportation and handling... 3 D. Unpacking the transformer... 4 E. Storage...
More informationTECHNICAL SPECIFICATION FOR SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 )
TECHNICAL SPECIFICATION FOR 11/ 3 KV/250V 15 & 25 KVA OUTDOOR TYPE COMPLETELY SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 ) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION
More informationUNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationSPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers
SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationMGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide
MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888
More informationDISTRIBUTION TRANSFORMER kv
ELECTRICITY COMMISSION PLANNING AND STUDY DEP BAGHDAD, REPUBLIC OF IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER kv REVISION YEAR 2001 DISTRIBUTION TRANSFORMERS 1- SCOPE OF THE TENDER : Tenderer
More informationCompany Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers
Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5 Relating to 11kV Distribution Transformers Policy Summary This specification covers the requirements for Distribution Transformers from 16kVA single
More informationTECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. CIRCLE OFFICE, NADIAD TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before
More informationTECHNICAL SPECIFICATION FOR G. I. WIRE (4MM)
1. SCOPE: TECHNICAL SPECIFICATION FOR G. I. WIRE (4MM) This Specification provides for manufacture, testing before dispatch at manufacturer's work and supply and delivery of 4mm solid heavily coated Galvanized
More informationThis Manual Part recommends design criteria for resistors suitable for railway signaling circuits other than electronic.
2016 Part 14.2.15 Recommended Design Criteria for Resistors Revised 2016 (6 Pages) A. Purpose z00381hn 3/12/15 8:34 AM z00381hn 3/12/15 8:37 AM This Manual Part recommends design criteria for resistors
More information2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type
PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17
More informationDISTRIBUTION TRANSFORMER 11 / kv
Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The
More informationMaharashtra State Electricity Distribution Company Limited MATERIAL SPECIFICATIONS CELL
Maharashtra State Electricity Distribution Company Limited MATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION FOR TECHNICAL SPECIFICATION OF 10,16 AND 25kVA, 11/0.433 kv & 22/ 0.433 kv LEVEL-2 THREE
More information(TECHNICAL SPECIFICATIONS & GTP FORMATS) 11KV METERING UNITS
(TECHNICAL SPECIFICATIONS & GTP FORMATS) 11KV METERING UNITS SCHEDULE OF MATERIALS: Sl. No. Name of the Materials Unit Quantity 1 11KV 3Ph 4W CT/PT combined Metering Unit CT Ratio- 400/5A PT Ratio 11000/110V
More informationMESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head
More informationTECHNICAL SPECIFICATION FOR POWER TRANSFORMER
TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL
More informationTechnical Specification. for 1.1 KV Copper Control Cable
WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,
More informationBUREAU OF INDIAN STANDARDS. Draft Indian Standard TWO COMPONENTS HIGH BUILD EPOXY MICACIOUS IRON OXIDE (MIO) PIGMENTED INTERMEDIATE COAT SPECIFICATION
FOR BIS USE ONLY DOC:CHD 20 (1932)C December 2012 BUREAU OF INDIAN STANDARDS Draft Indian Standard TWO COMPONENTS HIGH BUILD EPOXY MICACIOUS IRON OXIDE (MIO) PIGMENTED INTERMEDIATE COAT SPECIFICATION (Not
More informationTECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS.
TECHNICAL SPECIFICATION OF 630 KVA, 11/ 0.415 KV DRY TYPE OUTDOOR TRANSFORMERS. 1. 0 Scope: This specification covers design, manufacture, testing and supply of 630 KVA, 11/0.415 KV, Dry Type Distribution
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More informationSECTION METAL FABRICATIONS
SECTION 05100 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for metal fabrications, including minimum requirements for fabricator, and galvanizing. 1.02 REFERENCE STANDARDS A. ASTM
More informationTIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M
SL. NO NOMINAL DIAMETER "D" mm GASKETED JOINT (Nm) WOODEN CORE CLAMP (Nm) STEEL FIXING STUD FOR BUSHING (Nm) BUSHING STEM (Nm) (BRASS /COPPER) COPPER BUSBAR (Nm) 1 M6 5 - - - - 2 M8 12 - - 10-3 M10 22
More informationMaharashtra State Electricity Distribution Co. Ltd.
Maharashtra State Electricity Distribution Co. Ltd. SPEC. NO. STORES:MSC-II/ conventional power Trf/ 2011 SPECIFICATION FOR 5 MVA and 10 MVA 33/11 kv, 33/22 kv & 22/11 kv POWER TRANSFORMERS FOR VARIOUS
More informationPUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT
PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT SPECIFICATION SS-25 / 14 POWER TRANSFORMERS 150/15.75-21kV, 40/50 MVA WITH AUTOMATIC LOAD-RATIO CONTROL CONNECTION
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationSECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS
SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS 26 Requirement of Transformer Repairing Material Tender Notice No-NESCO/TRW-01/1141 dt 27.01.12 Sl.No Desripition of Material Rating
More informationPRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS
PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established
More informationPPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS
PPC TECHNICAL SPECIFICATION D/ NCMD -01. 48/06. 2005 THREE-PHASE DISTRIBUTION TRANSFORMERS 1 CONTENTS 1. SCOPE... 5 2. KEYWORDS... 5 3. OPERATING CONDITIONS... 5 3.1. Environmental conditions... 5 3.2.
More informationElectrical Design Process
Electrical Design Process Jason Varnell Lead Design Engineer Jason.Varnell@spx.com SPX Transformer Solutions, Inc. September 26, 2018 Agenda 1. Bid Design Process Parameters Affecting Bid Design 2. Final
More informationThe NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:
Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.
More informationSingle-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL
Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with
More informationSECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS
SECTION-IV TECHNICAL SPECIFICATIONS FOR TRANSFORMER REPAIRING MATERIALS 26 Requirement of Transformer Repairing Material Tender Notice No-NESCO/TRW-03/06 dt 01.06.12 Sl.No Desripition of Material Rating
More informationBANGALORE ELECTRICITY SUPPLY COMPANY LIMITED
BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED Technical Specification for Energy Efficient(3Star Rated) 11/0.433kV, 3Phase, 50Cycle, Aluminium Wound Distribution Transformer of rating 25/63/100kVA 1. SCOPE:
More informationMaharashtra State Electricity Distribution Company Limited
Maharashtra State Electricity Distribution Company Limited SPEC. NO. STORES: MSC-II/DT/Conventional 63,100 CSP with metering /2011 TECHNICAL SPECIFICATION FOR 63, 100 kva, 11/0.433 kv, 22/0.433 kv THREE
More informationTitle Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control
More informationPS REV NO: 01 PAGE : 2 OF 22
PAGE : 2 OF 22 1.0 INTRODUCTION Bharat Heavy Electricals Limited (BHEL), Electronics Division, Bangalore is setting up a 10 MW Solar PV Grid-connected power plant for its customer BEL at O.F.BOL, Badmal,
More informationIntroduction. Centrado leading-edge transformer. Introduction
Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,
More informationLIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED
LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More informationMIL- B Rev NAVSEA 0900-LP
I: REQUIREMENTS 1. Identify the standard the supplier uses for performing brazing. MIL- B-007883B OTHER (IF Other, Specify :) MIL- B-007883 Rev NAVSEA 0900-LP-001-7000 II: ATTRIBUTES: YES NO 2a. Does a
More informationTransformers handling and transport
Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary
More informationMESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2
Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)
More informationVOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)
TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part
More informationMESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/2.14 70mm 2 Version: 1 Issued: January 2015 Owner: Engineering Division Approved By: Pat
More informationSCHEDULE A SR. NO. 1 No.
SCHEDULE A SR. DESCRIPTION OF MATERIAL QUANTITY Nos. NO. Tender Offered 1. Power Transformer 3500KVA, 11 KV / 6.9KV Voltage Ratio, 183 A / 293 A current ratio, YNyn0 vector, ON cooling, with NGR on LV
More informationSingle & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank
Single & Three Phase Transformers Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank Product Code: 5634 Table of Contents Introduction... 5 Section 1. Transformer
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationSPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION
More information1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)
WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,
More informationHoward Smart Transformer Specification Guide
Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as
More informationTECHNICAL SPECIFICATION FOR OUTDOOR 160 KVA AMORPHOUS / CRGO CORE CSP ALUMINIUM CONDUCTOR DISTRIBUTION TRANSFORMERS WITH BEE 5 STAR RATING
10.09.2013/20.01.2014 TECHNICAL SPECIFICATION FOR OUTDOOR 160 KVA AMORPHOUS / CRGO CORE CSP ALUMINIUM CONDUCTOR DISTRIBUTION TRANSFORMERS WITH BEE 5 STAR RATING 1. SCOPE : 1.1 This specification covers
More informationMiniature Steam Pty Ltd (Incorporating Live Steam Supplies)
Miniature Steam Pty Ltd (Incorporating Live Steam Supplies) Materials List 28 May 2013 The attached listings outline products we offer and their retail prices as at the above date. We reserve the right
More informationExcavating, Backfilling, and Compaction for Utilities Piping (Plumbing).
SECTION 15047 - IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Identification including necessary accessories indicated on Construction Documents and specified in this section or as required
More informationAnodising is the process where Aluminum Oxide film is created on the section to avoid corrosion. (The tanks used are nos. 16, 17, 19 and 20)
ABOUT ANODISING Our New anodizing plant was commissioned in October 2012. Ours is a fully automated plant and the plant is completely designed and commissioned by the Monti Engineering from Italy. The
More informationLiquid-Filled Transformers
Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of
More informationWEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LTD.
WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LTD. TECHNICAL SPECIFICATION OF 315 11/0.433 KV BOTH OUTDOOR TYPE WITH OUDOOR BUSHING AT BOTH ENDS AND INDOOR TYPE WITH CABLE END BOX AT BOTH ENDS : 3
More informationMIL- B B. MIL- B Rev NAVSEA 0900-LP II: ATTRIBUTES: YES NO N/A
XXVIII BRAZE/BRAZING PROCESS I: REQUIREMENTS 1. Identify the standard the supplier uses for performing brazing. MIL- B-007883B MIL- B-007883 Rev OTHER (IF Other, Specify :) NAVSEA 0900-LP-001-7000 II:
More informationSYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR
SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY () SPECIFICATIONS FOR 20/0.4 KV DISTRIBUTION TRANSFORMER OPEN TERMINAL BUSHINGS AND HERMETICALLY SEALED
More informationSPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES
KP/3CB/TSP/0/00 04-09-9 Page of 9 TABLE OF CONTENTS 0. Circulation List 0. Amendment Record FOREWORD. SCOPE. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING, LABELLING
More informationMETAL FABRICATION SECTION 8: METAL FABRICATION SCOPE MATERIAL.
METAL FABRICATION SCOPE This specification applies to all metal intended to be rubber lined. Metals furnished must conform to this specification with respect to suitability for rubber lining or covering.
More information