A positive-sequence current based directional relaying approach for CCVT subsidence transient condition

Size: px
Start display at page:

Download "A positive-sequence current based directional relaying approach for CCVT subsidence transient condition"

Transcription

1 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 DOI /s Protection and Control of Modern Power Systems ORIGINAL RESEARCH A positive-sequence current based directional relaying approach for CCVT subsidence transient condition Monalisa Biswal * and Sandeep Biswal Open Access Abstract In this work, a directional relaying algorithm is proposed for transmission line to prevent relay maloperation during coupling capacitor voltage transformer (CCVT) subsidence transient. The effect of CCVT subsidence transient during single-pole-tripping condition is highlighted in this paper. The proposed method which is based on phase angle difference of post fault and prefault positive sequence current can help the directional relay to take accurate decision during erroneous CCVT secondary response. The available CCVT model in PSCAD is not able to generate significant subsidence transient in the secondary side. So, a new CCVT model is developed in EMTDC/PSCAD domain for transient response analysis and to check the relay operation. Next, the performance of different voltage and current information based directional relaying techniques have been analyzed and compared with the proposed method. The results are evaluated for different system and fault conditions. Results demonstrate the accuracy of the proposed method. Keywords: System impedance ratio (SIR), Voltage peak transient, Voltage zero transient, Ferroresonance suppression circuit (FSC), Fault resistance, Protection of transmission line 1 Introduction Directional relay decision is imperative for distance relay to maintain system integrity and stability [1]. However, the decision of directional relay is often affected by the instrument errors [, 3]. CCVT is generally applied in high voltage and extra high voltage system as it is capable of producing the exact replica of the line voltage in the secondary side at lower cost and with improved accuracy. The output response of CCVT is affected by subsidence transient which may contain decaying dc component, high frequency decaying and low frequency decaying components [4]. Under such conditions, the phasor estimation process will be either delayed or erroneous [3, 4]. The presence of subsidence transient in the secondary side of CCVT is either due to zero voltage fault, high source impedance ratio (SIR), fault with zero resistance path, close-in fault and several other causes such as configuration of ferroresonance suppression circuit (FSC), high burden on the secondary side etc. [ 8]. Fault during single-pole-operation is * Correspondence: monalisabiswal@gmail.com National Institute of Technology, Raipur 491, Chhattisgarh, India one of many causes behind CCVT subsidence transient [, 9]. Fault at voltage zero causes magnitude reduction and a phase angle shift of the CCVT output voltage [1, 11]. This reduced voltage magnitude if further supplied to directional relay may cause relay maloperation [7, 1]. In the past few years, researchers have been developed different CCVT model using various software packages to conduct the transient studies [1 16]. In [17], a detail review of different mathematical models of CCVT to represent the nonlinear behavior of the magnetic core is provided. Also in the literature several phasor estimation techniques have been proposed to reduce the impact of CCVT on distance relay [1, 18]. In [19], the performance report of CVT (capacitive voltage transformer) with electronic FSC under different system and fault conditions is provided. In the literature several mathematical modeling methods, phasor estimation techniques and distance relay algorithms have been reported to mitigate the impact of CCVT subsidence transient. However, no such specific research article providing the solution to mitigate the impact of directional relaying during CCVT The Author(s). 17 Open Access This article is distributed under the terms of the Creative Commons Attribution 4. International License ( which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made.

2 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page of 11 subsidence transient has been reported. With this motivation, the impact of CCVT subsidence transient generated during single-pole operation on directional relaying is investigated in this work and a solution is provided. In the literature several techniques have been reported to solve the directional relaying problems of transmission line [ 3]. The algorithms are mainly based on voltage or current information. With large CCVT error correct direction estimation is a challenging task for many relaying algorithm. Sometimes relay correctly see the fault direction but further asserted which causes line relay to operate incorrectly [, 1]. Distance relay algorithms are implemented with CCVT transient detection logic [4]. With such facility, new solutions can be provided to avoid relay malfunction. To obtain subsidence transient at the secondary side of CCVT, a new CCVT model is developed in EMTDC/PSCAD environment considering the nonlinear elements. Next, a current based approach is proposed which computes the phase angle difference between positive sequence post fault and prefault current. The impacts of voltage zero transient, voltage peak transient, passive FSC, different faults, fault resistance, high system SIR and fault location on the performance of proposed method are studied and results are compared with conventional techniques. The rest of the paper is organized as follows: directional relaying challenges with CCVT transient during SPT is described in Section. Section 3 explains the different directional methods and the proposed method. Simulation results are presented in Section 4. Finally, the conclusion is drawn in Section. Directional relaying challenges with CCVT transient during single-pole operation CCVT is generally applied over high voltage and extra-high voltage transmission system as it is inexpensive and not subject to ferroresonance condition. In modern numerical relays, fundamental voltage and current information based techniques are employed to estimate the actual fault direction. Relay algorithm either requires three phase information or sequence components for fault direction discrimination. Since, during single pole operation unavailability of faulty phase information may create challenges for relaying algorithm sequence component based algorithms are more advantageous as compared to phase information based techniques. However, with such phenomenon the reduced magnitude of sequence voltage computed using remaining healthy phase voltages is a further matter of concern for directional relaying algorithm []. Further any fault during such a period introduces transient at the secondary terminal of CCVT known as subsidence transient. Directional relay algorithms which rely on voltage information are affected during such a condition. In order to demonstrate the directional relaying issues with CCVT transients during SPT condition, a kv- Hz test system [18] as shown in Fig. 1 is considered. In the system, line segments are modeled with distributed parameter in EMTDC/PSCAD. The directional relay at bus Q is studied in this paper. The current and voltage signals required for directional relay are collected from CT and CCVT secondary having ratios of 1: A and kv: 11 V respectively. A schematic diagram of CCVT model as considered in the study is shown in Fig. [18]. The CCVT is represented by: coupling capacitors C1 and C, series inductance, step-down transformer (SDT). The active and passive ferroresonance suppression circuit models used in CCVT is shown in Fig. 3(a) and (b) respectively [1 17,, 6]. The line side CT and CCVT information is considered for the study and comparative assessment. The detailed system parameters are provided in Appendix 1. The internal parameters of CCVT are mentioned in the Appendix [18]. The CCVT is applied over high voltage system for several advantages [6, 7]. However, it is subjected to power system transients followed by faults. The transients at the secondary side of CCVT not present in the primary are introduced by the CCVT internal parameters. The nonlinear internal parameters of CCVT introduce small oscillations but can take the form of large distortions in voltage signal [8]. During steady state condition, the time response of CCVT is an actual replica of the primary side. While, the transient response includes high frequency decaying component, low frequency decaying component and dc decaying component [18]. The presence of various transient components depends on the fault inception point on voltage wave, type of FSC, system SIR, burden, fault resistance and fault location. In Fig. 4, the time response of CCVT including different transient components for any fault during single pole operation is shown. In the figure the transient response of CCVT is compared with the output response of an ideal potential transformer (PT) of same ratio which will not able to generate transient in it secondary output. Directional relay algorithm based on phasor components either uses voltage or current information as a reference quantity. Negative sequence directional element provides better directional security during SPT condition ~ P Q S I PFSPT B1 Line1 B B3 Line B4 ~ R Source 1 Fig. 1 Simulated three phase power system Fx Fy Source

3 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 3 of 11 R1 C1 RC LC RC LC SDT RC3 LC3 R C Rm Lm FSC Burden Fig. Schematic diagram of the studied CCVT circuit. (b) Active ferroresoance suppression circuit [9 3]. However, during high resistance fault the relaying decision based on negative sequence component is not reliable [33]. Relaying algorithm based on line side information finds problem due to CCVT secondary transient. In Fig. the angular plot for negative sequence voltage is provided for reverse side (Fx side) and forward side (Fy) side fault considering the effect of CCVT transient and without transient. Line side CCVT information is considered in the study. For fault in Fy side the negative sequence voltage is shifted more than 9. This creates problem for directional relay using negative sequence voltage as reference quantity. Fault direction estimation during SPT condition using positive sequence components can be possible. However, during single pole operation in applications with lineside potential, eventual corruption of polarizing quantity can occur if the input voltage to the memory circuit is corrupted. Invalid memory polarization may cause directional element malfunction. For this reason, the positive sequence voltage input to the polarizing memory is generally eliminated when the voltage is distorted [9]. To overcome from this problem a positive sequence current based approach is proposed in this paper. The method requires only current information measured at relay location to decide whether the fault is in forward side or reverse side. The performance of the method is independent of CT location. 3 Directional relaying techniques 3.1 Conventional directional algorithms To detect accurate fault direction different methods are available in the literature. Different directional methods are mentioned below: Method-1: Phase angle difference between negative sequence fault current and fault voltage [3] First method uses the phase angle difference between negative sequence fault current and fault voltage (ϕ 1 ¼ I FSPT V FSPT ). This method is commonly used for directional relaying during SPT condition. The value of ϕ 1 is positive for reverse fault and negative for forward side fault. The placement of CCVT and fault very close to relay location are the two cases which influence the performance of this method. a Fig. 3 Schematic diagram of a Passive ferroresoance suppression circuit. b Active ferroresonance circuit b 3.1. Method-: Phase angle difference between negative sequence fault current and prefault current [3] The second method is the angle difference between negative sequence fault current and prefault current (ϕ = Ī FSPT Ī PFSPT ) during SPT. The rule of decision with this method will be that positive angle corresponds to the reverse side fault and negative angle for the forward side fault. Fault with high resistance and high SIR creates problems to this method.

4 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 4 of 11 1 CCVT low frequency component Voltage (V) CCVT high frequency component Ideal PT CCVT DC component Time (ms) Fig. 4 Time response of both ideal PT and CCVT including different transient components Method-3: Phase angle difference between positive sequence superimposed voltage and current [3] The third method is the angle between superimposed voltage and current ( ϕ 3 ¼ ΔV 1SPT ΔI 1SPT ) during SPT. For reverse side fault the angle is positive and negative for forward fault. Such a method is affected during open pole situation as the memory voltage corrupted. The location CCVT is another source of relay maloperation. It was projected before that the different voltage information based techniques which are used for directional relaying during SPT condition have limitations due to CCVT transient. Instead of using voltage information, negative sequence based current-only techniques are also preferred during SPT. However, for high system SIR value the negative sequence component based technique will get affected. To solve these problems, in this paper a positive sequence current base approach is proposed as described below. 3. Proposed method A subsidence transient appear at the secondary side of CCVT either due to close-in fault or any fault during single-pole operation may be a damped, decaying, oscillatory or unidirectional signal. However, the presence of decaying dc component is more pronounced in subsidence transient [1]. Least square technique is more applicable in power network for filtering the decaying dc component. In this context, to filter the dc component and to extract the fundamental component least square approach is applied in this work. Fault current signal not only contain fundamental component but also harmonic and decaying dc component. In (1) the mathematical expression of fault current sample at an instant is given where both fundamental and harmonic components are expressed as a sinusoidal function. With CCVT transient 9 Without CCVT transient a Fig. Angular position of negative sequence voltage at relay location with and without presence of CCVT transient for fault. (a) AtF x side. (b) At F y side b

5 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page of 11 s τ it ðþ¼i dc e kt þ Im sinðkω T s þ φþ ð1þ where I dc is the magnitude of the decaying dc offset at t =, τ is the time constant of the decaying dc offset, I m is the peak of the fundamental component, φ is the phase angle of the fundamental frequency component, ω is the fundamental frequency and T s is the sampling interval. In (1) the fundamental component of current using least square approach can be estimated taking N number of samples per cycle as described below: ½A ½X ¼ ½B ðþ where sinðω T s Þ cosðω T s Þ 1 T s T 3 s sinðω T s Þ cosðω T s Þ 1 T s ðt s Þ ½A ¼ : : 1 : : : : 1 : : and sinðω NT s Þ cosðω NT s Þ 1 NT s ðnt s Þ k ½X ¼ I m cosφ p I m sinφ p k τ k τ In (), the vector matrix [B] can be represented as [B]= ½it ð þ T s Þ it ð þ T s Þ : : it ð þ NT s Þ T. Using least square technique, the unknown parameters in [X] can be estimated by using ½X ¼ A T 1A T A ½B ¼ A ½B ð3þ where A is the left pseudoinverse of A. The first two rows of A contains the coefficients of sine and cosine digital filters. These two filters can be used to evaluate the fundamental frequency components. With fault inception, all the three phase currents can be calculated as ^X ¼ X c þ jx s T ð4þ where X c and X s are the real and imaginary part of ^X. During single pole operation the positive sequence current measured at relay location as shown in Fig. 1 will be Ī PFSPT. Further, with any fault during single pole operation either in the upsteam side i.e., in line-1 i.e., or in the downstream side i.e., in line-, the current calculated at relay location will be Ī FSPT. Using phase angle difference between prefault and fault currents the direction of fault can be discriminated as, þve forfxsidefault θ ¼ I FSPT I PFSPT ¼ ðþ ve for Fy side fault The above relation can be used to discriminate the forward and reverse side fault during CCVT subsidence transient with transmission line in single pole operation. The flow diagram of the proposed method is shown in Fig Simulation results The proposed directional algorithm is tested in the system as shown in Fig. 1. The line side CCVT information is used for the relaying algorithm. To create SPT condition a-g fault is created at certain distance in line-1 and. Fault is initiated at.3 s and cleared at.4 s by opening breaker B3 and B4 simultaneously. With single-pole operation further fault in the line causes transient at the secondary side of CCVT. To test the performance of proposed method for transient period during single-pole tripping, different fault cases are simulated using EMTDC/PSCAD. Simulations are carried out for various power system events, such as forward side fault, reverse side fault, fault with different SIR value, voltage zero and voltage peak fault, close-in fault, phase-to-phase fault, ground fault, high resistance fault, end zone fault etc. The AFSC and PFSC are considered separately for the performance evaluation of proposed method. Nonlinear CT model is considered in the simulation. Least square technique with decaying dc component is used for phasor estimation process. Sampling rate is maintained at 1 khz. The performance of proposed method along with different conventional techniques are evaluated and demonstrated below. 4.1 Impact of voltage zero transient To investigate the impact of voltage zero transient on the performance of proposed method, a phase-to-phase fault case is simulated during SPT. B-c fault at.3911 s in both reverse (Fx side) and forward side (Fy side) of relay at a location of km is simulated. The SIR is considered as. Fig. 7a and b compares the dynamic responses of different methods for faults in Fx and Fy side. Using (4) the fundamental voltage and current components of each phase are calculated. For b-c fault in line-1, the value of ϕ 1 is initially positive and inconsistent later. The value of ϕ 3 is in the negative side provides wrong fault direction. Since, both ϕ and θ are consistently in the positive side indicates the correct direction of fault. The value of θ is calculated using (). The response of different methods along with proposed technique is shown in Fig. 7a. Similarly, in Fig. 7b the dynamic responses of different methods for b-c fault at Fy side are provided. For forward side close-in fault during SPT at voltage zero point, negative sequence voltage based methods (method-1) is maloperated. Due to CT saturation, method- based on negative sequence current is also getting affected. The output of method-3 based on superimposed components and the proposed method are negative which is clear from Fig. 7b. The location of CCVT, high SIR and close-in fault condition

6 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 6 of 11 Fig. 6 Flow diagram for discriminating the forward and reverse fault condition has negative impact on the performance of method-1, and 3 as evident from the Fig. 7. However, the proposed method is not influenced by such conditions. Also it is concluded from the results that during voltage zero transient with single pole breaker operation the proposed method correctly declares the fault direction where other methods are not able to do so. 4. Impact of passive ferroresonance suppression circuit (FSC) The impact of passive ferroresonance circuit (PFSC) during different situations and system conditions with SPT operation are investigated in this section. Considering PFSC in CCVT secondary different fault cases are simulated. Phase fault and ground fault at different locations of the line-1 and line- (Fig. 1) are created. The system SIR is assumed as 3. The sensitivity of the proposed method is checked for different fault inception angles like, 4, 9 and Impact of voltage peak transient The impact of voltage peak CCVT transient for fault during SPT is investigated in this section. B-g fault at.384 s on both side of the relay at a distance of 4 km is created. The fault resistance is considered as 1 Ω. SIR is considered as 3. It should be noted that the ground fault case as shown in Fig. 8a is a worst case in which the voltage peak transient at CCVT secondary affect the performance of method-1 and 3 which are based on voltage information. The value of ϕ based on

7 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 7 of 11 a b Method Method Method Method Method Method- Proposed Method Time (sec) Proposed Method Time (sec) Fig. 7 Comparison of different methods during voltage zero transient for b-c fault a Fx side, b Fy side negative sequence fault and prefault current provided positive value for Fx side fault. Using proposed method, for Fx side fault relay measures the angle difference between prefault current during single-pole-operation i.e., Ī PFSPT and fault current Ī FSPT. So, for this case both the method- and proposed method provides correct decision on fault direction as clear from Fig. 8a. In Fig. 8b, the responses of different methods for forward side fault are provided. For this case, all the three methods i.e., method-1, and 3 are failed. The nonlinear response of CT, fault initiation point, location of CCVT, higher SIR and fault resistance have negative impacts on method-1, and 3. However, the proposed method performs well a b Method Method Method Method Method Method Proposed Method Time (sec) Proposed Method Time (sec) Fig. 8 Comparison of different methods during voltage peak transient for b-g fault a Fx side, b Fy side for these conditions also as cleared from Fig. 8b. As, it is a current only based method the impact of CCVT subsidence transient does not affect the relay performance. 4.4 Impact of end zone fault Directional relay decision is often erroneous during end zone faults. Sometimes the CCVT transient is more pronounced during end zone low resistance fault [18]. To see the impact of such a fault case on the performance of proposed method, a single-line-to-ground fault (c-g) at 4 km from relay terminal is created at Fy side i.e., forward side. The fault resistance is 1 Ω. The system SIR

8 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 8 of 11 is assumed to be 3. Fault is created at.4 s i.e., during reclosing period. The responses of method-1,, 3 and proposed method are shown in Fig. 9. During an end zone fault at reclosing period, method- and method-3 provides incorrect decision and thus the value of ϕ and ϕ 3 are negative. However, method-1 and proposed method perform correctly as observed from the dynamic response shown in Fig. 9. In the first case, faults are created at different locations on the line in reverse side and the obtained results are presented in Table-I. In Table-I, the positive values of ϕ 1 and ϕ measured after one cycle of fault inception indicates that the fault is in Fx side i.e., reverse side of relay, which is correct. However, for different fault in reverse side with the presence of PFSC in the circuit during SPT condition, ϕ 3 is consistently negative. This provides wrong information regarding fault direction. Hence, for such a system and fault condition superimposed based technique is not reliable enough. Moreover, the value of θ calculated using proposed method is consistently positive for different phase-fault in the reverse side of relay. This proves the correct operation of proposed method. From Table 1 it is clear that proposed directional relaying algorithm is not affected by the presence PFSC in CCVT secondary circuit during SPT condition. Similarly, different single-line-to-ground faults (b-g fault) at different locations in line- are created with different fault inception angles. The SIR is similar to the previous case i.e., 3. Fault resistance is considered as 1Ω. The obtained results are provided in Table. Φ 1 and ϕ are consistently positive for different b-g faults in the forward side of the relay. This indicates that the fault is in reverse side i.e., Fx side, which is not correct. For (rad) Angle Method Method Method Proposed Method Time (sec) Fig. 9 Comparison of different methods for end zone c-g fault in Fy side Table 1 Results for b-c in reverse side with PFSC in CCVT secondary, SIR = 3 Fault location in km Fault inception Angle Method-1 Method- Method-3 Proposed method ϕ 1 (rad) ϕ (rad) ϕ 3 (rad) θ (rad) Table Results for b-g in forward side with PFSC in CCVT secondary, SIR = 3, fault resistance =1Ω Fault location in km Fault inception angle Method-1 Method- Method-3 Proposed method ϕ 1 (rad) ϕ (rad) ϕ 3 (rad) θ (rad)

9 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 9 of 11 such a fault case, from the different obtained values ϕ 3 and θ as provided in Table, it is clear that method-3 fails during five cases. However, the proposed method correctly sees the fault direction as the value of θ is consistently negative (in Table ) for different fault inception angle and fault location. This shows that the positive sequence current based method is immune to the influence of PFSC, fault inception angle and higher SIR value. 4. Results for various faults The performance of proposed method is evaluated for various fault cases such as single-line-to-ground fault, double-line fault, and double-line-to-ground fault at different locations on the line. Fault is created at both forward and reverse side of the relay. Results are provided for different SIR values, such as 1,,, 1, and 3. For reverse side fault resistance is assumed as 1 Ω whereas, for forward side Ω. In Table 3, the simulation results for different reverse side faults initiated during reclosing period are presented. A shown in Table 3, the proposed method provides correct decision for different SIR values. In all reverse side fault conditions, the value of θ is consistently positive. In Table 4, the simulation results for different forward side faults initiated during reclosing period are presented. The performance of the proposed method does not adversely affected by the fault location and fault type which is clear from Table 4. For worst system condition (SIR = 3) when the chance of CCVT subsidence transient is more prominent [34], the proposed method operate correctly i.e., θ is negative. This indicates forward side fault. So, it is clear from the results that the proposed directional relaying method based on phase angle difference of fault to prefault positive sequence current has satisfactory performance for different critical system and Table 3 Results for different forward side fault during singlepole-tripping Fault type Fault θ (rad), Fault resistance =1 Ω location in km SIR =. SIR = 1 SIR = SIR = 1 SIR = 3 b-g b-g b-g bc bc bc bc-g bc-g bc-g Table 4 Results for different reverse side fault during singlepole-tripping Fault type Fault θ (rad), Fault resistance = Ω location in km SIR =. SIR = 1 SIR = SIR = 1 SIR = 3 c-g c-g c-g c-g bc bc bc bc bc-g bc-g bc-g bc-g fault conditions. CCVT subsidence transient during SPT condition is not an issue for this method as it is independent of voltage information. Also the other factors like fault on voltage point of wave, CT saturation, high SIR value, fault location and fault inception angle are not a cause of error for the method as cleared from the results. Conclusions CCVT subsidence transient is a major reason behind the directional relay malfunction. Fault during single-poletripping is one of many causes of CCVT secondary subsidence transient. Conventional directional techniques based on voltage information are affected by transient condition. Negative sequence based directional relaying methods are not reliable for higher SIR system condition. In this paper, a positive sequence current based directional relaying method is proposed for CCVT secondary transient during SPT condition. The method computes the fundamental components of fault and prefault current using least square technique. Then phase angle difference of fault and prefault positive sequence current is calculated for fault directional estimation. The positive sequence current based methods have although limitation for high resistance far end fault, and load change situation but during such situation CCVT transient is not possible. So, once the CCVT transient at the secondary side is detected, the proposed method can be applied as a stand-alone protection scheme to avoid any nuisance directional relay operation. The presence of AFSC and PFSC, higher system SIR value, fault type, fault location, fault resistance, and fault inception angle have negligible impact on the performance of proposed method. The proposed method is 1% efficient for

10 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 1 of 11 CCVT subsidence transient condition as based only current information. Results demonstrate the promise of the proposed method. 6 Appendix 1 Three phase, Hz power system (Fig. 1). System Voltage: kv Load Angle (δ): 3 Line-1 length: km Line- length: km CT ratio: 1/ A CCVT ratio: kv/11v Line Parameters: Positive Sequence Impedance: (.148+ j.3) Ω/km Negative Sequence Impedance: (.148+ j.3) Ω/km Zero Sequence Impedance: ( j.949) Ω/km Positive Sequence Shunt Capacitive Reactance:.636 MΩ.km Zero Sequence Shunt Capacitive Reactance:.4473 MΩ.km Source Impedance = SIR* Total line impedance 7 Appendix CCVT Parameters Capacitor Divider: R 1 = Ω, C1 =.16 μf, R = Ω, C = μf. Inductance: R E = 9.6 Ω, L E = 67.9 H. Step Down Transformer: R P =8. Ω, L P = H, RS =.467 Ω, L S = H, SDT ratio = Ferroresonance Suppression Circuit: R 1F =.8Ω, R F = 1.31 Ω, C 1F =16.36μF, L 1F =.43H,R 3F =13.333Ω. CCVT Burden (1 VA): R 1B = Ω, R 1B = Ω, L1B =.4994 mh. Funding The work is not supported by any funding agency. This is the authors own research work. Authors contributions M Biswal contributed to the conception of the study and helped to draft the manuscript. S Biswal contributed the modeling of CCVT and power system, manuscript preparation, result analysis and wrote manuscript. Both authors read and approved the final manuscript. Competing interests The authors declare that they have no competing interests. Received: 13 September 16 Accepted: 7 February 17 References 1. Ziegler, G. (6). Numerical Distance Protection Principles and Applications, Siemens.. Elmore, W. A. (1994). Protective relaying theory and applications: ABB Power T &D Company Inc. 3. Horowitz, S. H., & Phadke, A. G. (8). Power System Relaying: John Wiley & Son. 4. Working Group of the Relay Input Sources Subcommittee of the Power System Relay Committee. (1981). Transient response of coupling capacitor voltage transformers. IEEE Transactions on Power Apparatus and Systems, 1, Costello, D., & Zimmerman, K. (1). CVT transients revisited - distance, directional overcurrent, and communications-assisted tripping concerns (pp ). College Station: 6th Annual Conference for Protective Relay Engineers. 6. Khanna, A. (11). Method to improve transient performance of CVTs: Analysis and recommendations. European Transactions on Electrical Power, 1, Hou, D., & Roberts, J. (1996). Capacitive voltage transformers: Transient overreach concerns and solutions for distance relaying (pp ). Calgary: In Proc. Can. Conf. Elect. Comput. Eng. 8. Aboul-Zaheb, E. M., Eldin, E. S. T., Ibrahim, D. K., & Saleh, S. M. (7). High impedance fault detection in mutually coupled double-ended transmission lines using high frequency disturbances (pp. 4 8). Tampa: In Proc. International of the IEEE Power Engineering Society, General Meeting. 9. Bakar, H. A., Khan, S. A., Kwang, T. C., & Rahim, N. A. (1). A review of ferroresonance in capacitive voltage transformer. IEEJ Transactions on Electrical and Electronic Engineering, 1, Ajaei, F. B., Pasand, M. S., Davarpanah, M., Zare, A. R., & Iravani, R. (1). Mitigating the impacts of CCVT subsidence transients on the distance relay. IEEE Transactions on Power Delivery, 7, Angell,D.,&Hou,D.(7).Input source error concerns for protective relays (pp. 63 7). College Station: 6th Annual Conference for Protective Relay Engineers. 1. Ajaei, F. B., Sanaye-Pasand, M., & Rezaei-Zare, A. (9). Iravani, R. (9). Analysis and suppression of the coupling capacitor voltage transformer ferroresonance phenomenon. IEEE Transactions on Power Delivery, 4, doi:1.119/tpwrd Fernandes, D., Jr., Neves, W. L. A., & Vasconcelos, J. C. A. (7). Coupling capacitor voltage transformer: A model for electromagnetic transient studies. Electric Power Systems Research, 77, Iravani, M. R., Wang, X., Polishchuk, I., Ribeiro, J., & Sarshar, A. (1998). Digital time-domain investigation of transient behaviour of coupling capacitor voltage transformer. IEEE Transactions on Power Delivery, 13, Kezunovic, M., Kojovic, L. J., Skendzic, V., Fromen, C. W., Sevcik, D. R., & Nilsson, S. L. (199). Digital models of coupling capacitor voltage transformers for protective relay transient studies. IEEE Transactions on Power Delivery, 1, Lucas, J. R., McLaren, P. G., Keerthipala, W. W. L., & Jayasinghe, R. P. (199). Improved simulation models for current and voltage transformers in relay studies. IEEE Transactions on Power Delivery, 7, Working Group C of the Systems Protection Subcommittee of the IEEE Power System Relaying Committee. (). Mathematical models for current, voltage, and coupling capacitor voltage transformers. IEEE Transactions on Power Delivery, 1, Pajuelo, E., Ramakrishnan, G., & Sachdev, M. S. (8). Phasor estimation technique to reduce the impact of coupling capacitor voltage transformer transients. IET Generation Transmission and Distribution,, Venkatesh, C., & Shanti Swarup, K. (14). Performance assessment of distance protection fed by capacitor voltage transformer with electronic ferro-resonance suppression circuit. Electric Power Systems Research, 1, Gu, B., Tan, J., & Wei, H. (14). High speed directional relaying algorithm based on the fundamental frequency positive sequence superimposed components. IET Generation Transmission and Distribution, 8, Jalilian, A., Hagh, M. T., & Hasemi, S. M. (14). An innovative directional relaying scheme based on postfault current. IEEE Transactions on Power Delivery, 9, Fleming, B. (1998). Negative sequence impedance directional element Biswal, M., Pati, B. B., & Pradhan, A. K. (13). Directional relaying for double circuit line with series compensation. IET Generation, Transmission & Distribution, 7, Instruction Manual. (6). SEL-41 Relay Protection and Automation System, SEL, 11.. Graovac, M., Iravani, R., Wang, X., & McTaggart, R. D. (3). Fast ferroresonance suppression of coupling capacitor voltage transformers. IEEE Transactions on Power Delivery, 18, ANSI C (1999). American National Standard Requirements for Power-Line Carrier Coupling Capacitors and Coupling Capacitor Voltage Transformers (CCVT). 7. Electricity Association Services Limited. (199). Power system protection-1. London: The Institution of Electrical Engineers.

11 Biswal and Biswal Protection and Control of Modern Power Systems (17) :8 Page 11 of Hernandez, J. C., De La Cruz, J., Vidal, P. G., & Ogayar. (13). B. Conflicts in the distribution network protection in the presence of large photovoltaic plants: The case of ENDESA. International Transactions on Electrical Energy System, 3(), Calero, F., & Hou, D. (4). Practical considerations for single-pole-trip line-protection schemes. In Proc. Of the 31st Annual Western Protective Relay Conference, Spokane, WA, October. 3. Jena, P., & Pradhan, A. K. (13). Directional relaying during single-pole tripping using phase change in negative-sequence current. IEEE Transactions on Power Delivery, 8, doi:1.119/tpwrd Roberts, J., Guzman, A. Directional element design and evaluation Zhang, C., Tan, J., & Gu, B. (1). A novel negative sequence reactance based high speed directional relay algorithm. International Transactions on Electrical Energy System, (1), doi:1.1/etep Mooney, J., Jackie Peer, P.E. Application Guidelines for Ground Fault Protection Reis, R. L. A., Lopes, F. V., Neves, W. L. A., & Fernandes, D., Jr. (1). Influence of coupling capacitor voltage transformers on travelling wave-based fault locators (pp ). Cavtat: In Proc. International Conference on Power Systems Transients (IPST1). Submit your manuscript to a journal and benefit from: 7 Convenient online submission 7 Rigorous peer review 7 Immediate publication on acceptance 7 Open access: articles freely available online 7 High visibility within the field 7 Retaining the copyright to your article Submit your next manuscript at 7 springeropen.com

Identification of Parameters for Coupling Capacitor Voltage Transformers

Identification of Parameters for Coupling Capacitor Voltage Transformers Identification of Parameters for Coupling Capacitor Voltage Transformers D. Fernandes Jr. W. L. A. Neves Departamento de Engenharia Elétrica UFPB Av. Aprígio Veloso, 88 Bodocongó 58.09-970, Campina Grande

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network

Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network Haidar Samet 1, Farshid Nasrfard Jahromi 1, Arash Dehghani 1, and Afsaneh Narimani 2 1 Shiraz University 2 Foolad Technic

More information

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES N. Perera 1, A. Dasgupta 2, K. Narendra 1, K. Ponram 3, R. Midence 1, A. Oliveira 1 ERLPhase Power Technologies Ltd. 1 74 Scurfield

More information

THE EFFECT OF VARIOUS PARAMETERS OF CVT ON ITS PERFORMANCE, AND THEIR ROLE ON POWER QUALITY

THE EFFECT OF VARIOUS PARAMETERS OF CVT ON ITS PERFORMANCE, AND THEIR ROLE ON POWER QUALITY Vol. 10, No. 1, pp. 3763-3769, ebruary 2016 Online ISSN: 1920-3853; Print ISSN: 1715-9997 Available online at www.cjpas.net THE EECT O VARIOUS PARAMETERS O CVT ON ITS PERORMANCE, AND THEIR ROLE ON POWER

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering

More information

Comparative Performance of Conventional Transducers & Rogowski Coil for Relaying Purpose

Comparative Performance of Conventional Transducers & Rogowski Coil for Relaying Purpose Comparative Performance of Conventional Transducers & Rogowski Coil for Relaying Purpose Ashish S. Paramane1, Avinash N. Sarwade2 *, Pradeep K. Katti3, Jayant G. Ghodekar4 1 M.Tech student, 2 Research

More information

Accurate Current Measurement Transducer for Relaying Purpose

Accurate Current Measurement Transducer for Relaying Purpose Accurate Current Measurement Transducer for Relaying Purpose Ashish S. Paramane 1, Dr.P.K.Katti 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere, Maharashtra

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,

More information

Paper Code: PSPC_2015_24 Designing a Compensating Electronic Circuit to Enhance Capacitive Voltage Transformer Characteristics

Paper Code: PSPC_2015_24 Designing a Compensating Electronic Circuit to Enhance Capacitive Voltage Transformer Characteristics Paper Code: PSPC_215_24 Designing a Compensating Electronic Circuit to Enhance Capacitive Voltage Transformer Characteristics Mohammad Hadi Zare, Ahmad Mirzaei Yazd University Yazd, Iran zare@yazd.ac.ir

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines

A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines M.M. Saha, T. Einarsson, S. Lidström ABB AB, Substation Automation Products, Sweden Keywords: Adaptive distance protection,

More information

Innovative Science and Technology Publications

Innovative Science and Technology Publications Innovative Science and Technology Publications Manuscript Title SATURATION ANALYSIS ON CURRENT TRANSFORMER Thilepa R 1, Yogaraj J 2, Vinoth kumar C S 3, Santhosh P K 4, 1 Department of Electrical and Electronics

More information

VOLTAGE and current signals containing information

VOLTAGE and current signals containing information Impact of Instrument Transformers and Anti-Aliasing Filters on Fault Locators R. L. A. Reis, W. L. A. Neves, and D. Fernandes Jr. Abstract Butterworth and Chebyshev anti-aliasing filters assembled in instrument

More information

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor Module 2 : Current and Voltage Transformers Lecture 8 : Introduction to VT Objectives In this lecture we will learn the following: Derive the equivalent circuit of a CCVT. Application of CCVT in power

More information

MANY protective relaying functions use the phasors

MANY protective relaying functions use the phasors 1 Phasor Estimation Using a Modified Sine Filter Combined with an Adaptive Mimic Filter Kleber M. Silva and Bernard F. Küsel Abstract This paper presents a phasor estimation algorithm, which combines a

More information

SATURATION ANALYSIS ON CURRENT TRANSFORMER

SATURATION ANALYSIS ON CURRENT TRANSFORMER Volume 118 No. 18 2018, 2169-2176 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu SATURATION ANALYSIS ON CURRENT TRANSFORMER MANIVASAGAM RAJENDRAN

More information

Improved differential relay for bus bar protection scheme with saturated current transformers based on second order harmonics

Improved differential relay for bus bar protection scheme with saturated current transformers based on second order harmonics Journal of King Saud University Engineering Sciences (2016) xxx, xxx xxx King Saud University Journal of King Saud University Engineering Sciences www.ksu.edu.sa www.sciencedirect.com ORIGINAL ARTICLES

More information

Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers

Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers I Gusti Ngurah Satriyadi Hernanda, I Made Yulistya Negara, Adi Soeprijanto, Dimas Anton Asfani, Mochammad

More information

MATHEMATICAL MODELING OF POWER TRANSFORMERS

MATHEMATICAL MODELING OF POWER TRANSFORMERS MATHEMATICAL MODELING OF POWER TRANSFORMERS Mostafa S. NOAH Adel A. SHALTOUT Shaker Consultancy Group, Cairo University, Egypt Cairo, +545, mostafanoah88@gmail.com Abstract Single-phase and three-phase

More information

A Novel Fuzzy Neural Network Based Distance Relaying Scheme

A Novel Fuzzy Neural Network Based Distance Relaying Scheme 902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 A Novel Fuzzy Neural Network Based Distance Relaying Scheme P. K. Dash, A. K. Pradhan, and G. Panda Abstract This paper presents a new

More information

Distance Element Performance Under Conditions of CT Saturation

Distance Element Performance Under Conditions of CT Saturation Distance Element Performance Under Conditions of CT Saturation Joe Mooney Schweitzer Engineering Laboratories, Inc. Published in the proceedings of the th Annual Georgia Tech Fault and Disturbance Analysis

More information

Direct Harmonic Analysis of the Voltage Source Converter

Direct Harmonic Analysis of the Voltage Source Converter 1034 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003 Direct Harmonic Analysis of the Voltage Source Converter Peter W. Lehn, Member, IEEE Abstract An analytic technique is presented for

More information

Analysis of Modern Digital Differential Protection for Power Transformer

Analysis of Modern Digital Differential Protection for Power Transformer Analysis of Modern Digital Differential Protection for Power Transformer Nikhil Paliwal (P.G. Scholar), Department of Electrical Engineering Jabalpur Engineering College, Jabalpur, India Dr. A. Trivedi

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying

Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying V.S.Kale S.R.Bhide P.P.Bedekar Department of Electrical Engineering, VNIT Nagpur, India Abstract

More information

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main

More information

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third one of Distance Relays M. Azari, M. Ojaghi and K. Mazlumi* Electrical Engineering Department University of anjan anjan,

More information

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay Anurag Choudhary Department of Electrical and Electronics Engineering College of Engineering Roorkee, Roorkee

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

INFLUENCE OF INSTRUMENT TRANSFORMERS ON POWER SYSTEM PROTECTION. A Thesis BOGDAN NAODOVIC

INFLUENCE OF INSTRUMENT TRANSFORMERS ON POWER SYSTEM PROTECTION. A Thesis BOGDAN NAODOVIC INFLUENCE OF INSTRUMENT TRANSFORMERS ON POWER SYSTEM PROTECTION A Thesis by BOGDAN NAODOVIC Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements

More information

Harmonics Elimination Using Shunt Active Filter

Harmonics Elimination Using Shunt Active Filter Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.

More information

Effect of Fault Resistance and Load Encroachment on Distance Relay- Modeling and Simulation PSCAD/EMTDC

Effect of Fault Resistance and Load Encroachment on Distance Relay- Modeling and Simulation PSCAD/EMTDC Effect of Fault Resistance and Load Encroachment on Distance Relay- Modeling and Simulation PSCAD/EMTDC Naitik Trivedi 1, Vatsal Shah 2, Vivek Pandya 3 123 School of Technology, PDPU, Gandhinagar, India

More information

CCVT Failures and Their Effects on Distance Relays

CCVT Failures and Their Effects on Distance Relays CCVT Failures and Their Effects on Distance Relays Sophie Gray, CenterPoint Energy Derrick Haas and Ryan McDaniel, Schweitzer Engineering Laboratories, Inc. Abstract Distance relays rely on accurate voltage

More information

CHAPTER 9. Sinusoidal Steady-State Analysis

CHAPTER 9. Sinusoidal Steady-State Analysis CHAPTER 9 Sinusoidal Steady-State Analysis 9.1 The Sinusoidal Source A sinusoidal voltage source (independent or dependent) produces a voltage that varies sinusoidally with time. A sinusoidal current source

More information

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer

More information

A Modeling Methodology for Inductive and Capacitive Voltage Transformers for High- Frequency Electrical Transients Analysis

A Modeling Methodology for Inductive and Capacitive Voltage Transformers for High- Frequency Electrical Transients Analysis A Modeling Methodology for Inductive and Capacitive Voltage Transformers for High- Frequency Electrical Transients Analysis M. C. Camargo, G. Marchesan, L. Mariotto, G. Cardoso Junior, L. F. F. Gutierres

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

DESIGN AND DEVELOPMENT OF ADVANCED NUMERICAL DISTANCE RELAYING TECHNIQUES

DESIGN AND DEVELOPMENT OF ADVANCED NUMERICAL DISTANCE RELAYING TECHNIQUES SYNOPSIS OF DESIGN AND DEVELOPMENT OF ADVANCED NUMERICAL DISTANCE RELAYING TECHNIQUES A THESIS to be submitted by C. VENKATESH for the award of the degree of DOCTOR OF PHILOSOPHY DEPARTMENT OF ELECTRICAL

More information

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated

More information

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Omar G. Mrehel Hassan B. Elfetori AbdAllah O. Hawal Electrical and Electronic Dept. Operation Department Electrical

More information

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier.

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier. Oscillators An oscillator may be described as a source of alternating voltage. It is different than amplifier. An amplifier delivers an output signal whose waveform corresponds to the input signal but

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor

Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor Durga Prasad Ananthu Assistant Professor, EEE dept. Guru Nanak Dev Engg College, Bidar adp.ananthu@gmail.com Rami Reddy

More information

Power Quality and Digital Protection Relays

Power Quality and Digital Protection Relays Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

Identification of network models parameters for simulating transients

Identification of network models parameters for simulating transients Identification of network models parameters for simulating transients D. Cavallera, J-L. Coulomb, O. Chadebec, B. Caillault, F-X. Zgainski and A.Ayroulet Abstract In case of electrical black-out, one of

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Resonant Controller to Minimize THD for PWM Inverter

Resonant Controller to Minimize THD for PWM Inverter IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 3 Ver. III (May Jun. 2015), PP 49-53 www.iosrjournals.org Resonant Controller to

More information

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage 1 New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage B. B. Pimple, V. Y. Vekhande and B. G. Fernandes Department of Electrical Engineering, Indian Institute of Technology Bombay,

More information

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1 Electromagnetic Oscillations and Currents March 23, 2014 Chapter 30 1 Driven LC Circuit! The voltage V can be thought of as the projection of the vertical axis of the phasor V m representing the time-varying

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

Simulation and Analysis of Ferroresonance in Power System

Simulation and Analysis of Ferroresonance in Power System Simulation and Analysis of Ferroresonance in Power System Mitra Patel 1, Manish N Sinha 2 P.G. Student, Department of Electrical Engineering, BVM Engineering College, V.V.Nagar, Gujarat, India 1 Assistant

More information

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

Innovative Solutions Improve Transmission Line Protection

Innovative Solutions Improve Transmission Line Protection Innovative Solutions Improve Transmission Line Protection Daqing Hou, Armando Guzmán, and Jeff Roberts Schweitzer Engineering Laboratories, Inc. Presented at the 1998 Southern African Conference on Power

More information

A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors

A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors 452 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors Ying-Hong Lin,

More information

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Engr.Kavitha Vasantha 1 Lecturer, BSIE, College of Engineering, Salmabad, Kingdom of Bahrain 1 Abstract: As end

More information

Detection of Fault Direction and Location in Compensated System using Sequence Component

Detection of Fault Direction and Location in Compensated System using Sequence Component Indian Journal of Science and Technology, Vol 9(12), DOI: 10.17485/ijst/2016/v9i12/86209, March 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 Detection of Fault Direction and Location in Compensated

More information

Wavelet Based Transient Directional Method for Busbar Protection

Wavelet Based Transient Directional Method for Busbar Protection Based Transient Directional Method for Busbar Protection N. Perera, A.D. Rajapakse, D. Muthumuni Abstract-- This paper investigates the applicability of transient based fault direction identification method

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

Software Models for Relays

Software Models for Relays 238 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 2, APRIL 2001 Software Models for Relays P. G. McLaren, K. Mustaphi, G. Benmouyal, S. Chano, A. Girgis, C. Henville, M. Kezunovic, L. Kojovic, R. Marttila,

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

Current Transformer Performance study Using Software Tools.

Current Transformer Performance study Using Software Tools. Current Transformer Performance study Using Software Tools. A. Mechraoui, A. Draou, A. Akkouche, and S. AL Ahmadi Department of Electronics Technology Madinah College of Technology, Madinah Council of

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

Defining and Measuring the Performance of Line Protective Relays

Defining and Measuring the Performance of Line Protective Relays Defining and Measuring the Performance of Line Protective Relays Edmund O. Schweitzer, III, Bogdan Kasztenny, Mangapathirao V. Mynam, Armando Guzmán, Normann Fischer, and Veselin Skendzic Schweitzer Engineering

More information

Distance Protection Scheme for Series Compensated Transmission Lines

Distance Protection Scheme for Series Compensated Transmission Lines RESEARCH ARTICLE OPEN ACCESS Distance Protection Scheme for Series Compensated Transmission Lines Vanitha.V*, Hemalatha.P** *PG Scholar, M.P.N.M.J Engineering College, Erode, Tamilnadu, India. **Assistant

More information

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc. Chapter 30 Inductance, Electromagnetic Oscillations, and AC Circuits 30-7 AC Circuits with AC Source Resistors, capacitors, and inductors have different phase relationships between current and voltage

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line

Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 7, Number 8 (2014), pp. 827-835 International Research Publication House http://www.irphouse.com Performance Evaluation

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear International Journal of Smart Grid and Clean Energy Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear Zaipatimah Ali a,b*, Vladimir Terzija b a Universiti

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Class XII Chapter 7 Alternating Current Physics

Class XII Chapter 7 Alternating Current Physics Question 7.1: A 100 Ω resistor is connected to a 220 V, 50 Hz ac supply. (a) What is the rms value of current in the circuit? (b) What is the net power consumed over a full cycle? Resistance of the resistor,

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK SPECIAL ISSUE FOR NATIONAL LEVEL CONFERENCE "Technology Enabling Modernization

More information

Protection of Extra High Voltage Transmission Line Using Distance Protection

Protection of Extra High Voltage Transmission Line Using Distance Protection Protection of Extra High Voltage Transmission Line Using Distance Protection Ko Ko Aung 1, Soe Soe Ei Aung 2 Department of Electrical Power Engineering Yangon Technological University, Insein Township

More information

Volume I Issue VI 2012 September-2012 ISSN

Volume I Issue VI 2012 September-2012 ISSN A 24-pulse STATCOM Simulation model to improve voltage sag due to starting of 1 HP Induction-Motor Mr. Ajay Kumar Bansal 1 Mr. Govind Lal Suthar 2 Mr. Rohan Sharma 3 1 Associate Professor, Department of

More information

Distance protection closed-loop testing using RTDS

Distance protection closed-loop testing using RTDS Energy Equip. Sys./ Vol. 5/No.2/ June 2017/197-210 Energy Equipment and Systems http://energyequipsys.ut.ac.ir www.energyequipsys.com Distance protection closed-loop testing using RTDS Authors Zahra Moravej

More information

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER S. Tara Kalyani 1 and G. Tulasiram Das 1 1 Department of Electrical Engineering, Jawaharlal Nehru Technological University, Hyderabad,

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS SIMUATION OF D-STATCOM AND DVR IN POWER SYSTEMS S.V Ravi Kumar 1 and S. Siva Nagaraju 1 1 J.N.T.U. College of Engineering, KAKINADA, A.P, India E-mail: ravijntu@gmail.com ABSTRACT A Power quality problem

More information

Ultra-High-Speed Relaying for Transmission Lines

Ultra-High-Speed Relaying for Transmission Lines Ultra-High-Speed Relaying for Transmission Lines Copyright SEL 2015 Focus for Today Benefits of faster line protection Limitations of present-day phasor-based protection Principles of time-domain protection

More information

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Switching and Fault Transient Analysis of 765 kv Transmission Systems Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department

More information

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component International Journal Of Computational Engineering Research (ijceronline.com) Vol. 3 Issue. 3 Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component 1, Mr. R.V.KATRE,

More information

Use of Advanced Digital Simulators for Distance Relay Design and Application Testing

Use of Advanced Digital Simulators for Distance Relay Design and Application Testing 1 Use of Advanced Digital Simulators for Distance Relay Design and Application Testing J. Schilleci, G. Breaux M. Kezunovic, Z. Galijasevic T. Popovic Entergy Services, Inc. Texas A&M University Test Laboratories

More information

Superimposed Quantities: Their True Nature and Application in Relays

Superimposed Quantities: Their True Nature and Application in Relays Superimposed Quantities: Their True Nature and Application in Relays Gabriel Benmouyal and Jeff Roberts Schweitzer Engineering Laboratories, Inc. Presented at the 26th Annual Western Protective Relay Conference

More information

TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE

TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE K.Satyanarayana 1, Saheb Hussain MD 2, B.K.V.Prasad 3 1 Ph.D Scholar, EEE Department, Vignan University (A.P), India, ksatya.eee@gmail.com

More information