Operating Instructions

Size: px
Start display at page:

Download "Operating Instructions"

Transcription

1 Level and Pressure Operating Instructions VEGAMET ESC OK CONNECT CONNECT on on in out

2 Contents Contents 1 Product description 1.1 Function and configuration Approvals Features Technical data Dimensions Mounting Electrical connection 3.1 Connection instructions Connection instructions for Ex approved applications Wiring plan Adjustment 4.1 Indicating and adjustment elements Adjustment system Adjustment via PC Configuration and parameter adjustment Setup Configuration 6.1 Configuration measurement loop, two independent single measurements Configuration measurement loop, linked applications Measurement loop name Fault signal Tare Moniring Configuration of inputs Configuration of outputs VEGAMET 515

3 Contents 7 Parameter adjustment 7.1 Adjustment with medium Adjustment without medium Adjustment with linked measurements Scaling Choose linearisation curve Integration time Meas. value limitation Adjustment of output parameters Simulation Special function: Special function: Manual and aumatic correction Additional functions 8.1 Linearisation curves Info Password Language VEGAMET Measuring results and units Diagnosis 9.1 Maintenance Simulation Fault signal Repair Error codes Safety information Note Ex area VEGAMET 515 3

4 Product description 1 Product description 1.1 Function and configuration VEGAMET 515 is a signal conditioning instrument for a number of applications, e.g.: - level measurement - gauge measurement - process pressure measurement - measurement with aumatic correction - etc. Function The signal conditioning instruments power the connected sensors and process their analogue measuring data. The conditioning is carried out by a special software consisting of functional components (FB), input components (EB), output components (AB) as well as DCS components (PB). Configuration The VEGAMET 515 signal conditioning instrument is constructed as module card in European size with 5 TE (= 25.4 mm) width. The front plate contains an adjustment module with LC display and keys. The front plate of VEGAMET 515 N does not contain an adjustment module. Software configuration component - continuous current input - contact input AB Output components - current output - voltage output - DISBUS outputs - failure output - MET display - relay outputs EB FB PC/DCS components - PC/DCS outputs Functional component - measurement loop TAG 1 PB 4 VEGAMET 515

5 Product description 1.2 Approvals VEGAMET are available with the following approvals: - explosion protection: appropriate operating instrument with intrinsically safe circuit (VEGAMET 515 Ex) - overfill protection acc. WHG For such applications, please note the appropriate official documents (general type approval, test and conformity certificates). They come with the respective instrument Ex approval For hazardous areas, certification acc. CENELEC defined in the conformity certificate PTB no. Ex-95.D.2161 X for VEGAMET 515 Ex. WHG approval Signal conditioning instrument as part of an overfill protection system acc. WHG (test certificate number see table). 1.3 Features - microcomputer-controlled signal conditioning instrument for continuous measurement - adjustment module with LC display and 6 keys (not with VEGAMET 515 N) - adjustable integration time - two fixed and three user-programmable linearisation curves - fault moniring - fault signal and failure diagnosis via display s: - 1 sensor input (capacitive electrode, pressure transmitter or another 4 20 ma sensor) - 2 correction inputs (for key, switch or level switch) Outputs: - 3 current outputs 0/4 20 ma - 3 voltage outputs 0/2 10 V - 2 relay outputs (spdt) - 1 DISBUS output for digital wiring and for connection of VEGADIS fail safe relay - adjustment also via PC with adjustment software VVO; connection via the interface adapter of the VEGACONNECT series Instrument Oscillar VEGAMET Test certificate Auxiliary level switch no. VEGASEL Capacitive electrodes E17 EX 515 EX Z EL 11 EX0, EL 21 EX0, E18 EX 643 EL 24 EX0, EL 29 EX, EL 31 EX0, EL 42 EX0 Pressure transmitters E23, 515 Z D80, D81, D84, D86, E23 Ex 515 EX 643 D84 EX, D86 EX Pressure transmitters E22, 515 Z D77, D85, D87, E22 Ex 515 Ex 643 D77 EX, D85 EX, D87 EX VEGAMET 515 5

6 Product description 1.4 Technical data Power supply Operating voltage U nom = V AC, 50/60 Hz = V DC Power consumption approx. 6 VA or approx. 4 W Meas. data input Number Type of input Range Possible sensors (loop powered) Voltage - at 4 ma approx. 18 V DC - at 20 ma approx. 15 V DC 2 inputs active two-wire input, analogue (sensor is powered by VEGAMET) 4 20 ma capacitive electrodes, pressure transmitters, process pressure transmitters, differential pressure transmitters Current limitation at approx. 26 ma, short-circuit proof Detection line break < 3.6 ma Detection short-circuit > 21 ma Min. adjustment delta 2 of the adjusted sensor values Connection cable 2-wire standard cable (screening recommended) max. resistance per wire 35 Ω Resolution 1 µa Linearity error at 4 20 ma Temperature error 0.04 /10 K at 4 20 ma Correction signal input Number Function Voltage Current External cable resistance 2 inputs switching signal for triggering corrections or special relay modes via external switching contact 5 V (from instrument) 5 ma 150 Ω Current output Number 3 outputs Function analogue output of the processing results Range individually adjustable in the range of 0 20 ma Load max. 500 Ω Resolution 1 µa Linearity error 0.05 (relating 20 ma) Temperature error 0.05 /10 K (relating 20 ma) 6 VEGAMET 515

7 Product description Voltage output Number 3 outputs Function analogue output of the processing results Range individually adjustable in the range of 0 10 V Current max. 1 ma Resolution 0.5 mv Linearity error 0.05 (relating 10 V) Temperature error 0.06 /10 K (relating 10 V) Relay outputs Number 2 switching relays 1 fail safe relay Contact floating spdt Contact material AgNi, hard gold plated Turn-on voltage min. 10 mv DC max. 250 V AC/DC Switching current min. 10 µa max. 3 A AC, 1 A DC Breaking capacitance max. 500 VA, 54 W Min. switching hysteresis (Low-/High-Delta) 0.5 DISBUS output Function Connection cable max. cable length for wiring between the signal conditioning instruments and for connection of digital indicating instruments 2-wire standard cable (screening recommended) 1000 m Indicating elements Clear text indication LC display (with VEGAMET 515N not available) - 4 lines, 6 digits each - background lighting Analogue indication LED row consisting of: (with VEGAMET 515N not available) - 11 segments shows the actual value of the selected measurement loop LEDs in front plate green: operating voltage on red: fault signal (LED lights with deenergised relay) yellow: relay switching condition (standard setting: LED lights with energised relay) Adjustment elements Front plate Circuit board 6 keys for configuration and parameter setting (with VEGAMET 515N not available) rotary switch for adjustment of the instrument address on DISBUS VEGAMET 515 7

8 Product description Ambient conditions Permissible ambient temperature Srage and transport temperature -20 C +60 C -40 C +80 C Electrical connection Multipoint connecr component acc. DIN , series F, 33-pole, 3 rows d, b, z (partly equipped) Carrier BGT 596 (Ex) connection appropriate module Housing type 505 connection screw terminals (max. 2.5 mm 2 ) Electrical protective measures Protection - unassembled IP 00 - mounted in carrier BGT front side completely equipped IP 40 - upper and lower side IP 20 - wiring side IP 00 - mounted in housing type 505 or terminal side IP 20 - housing in general IP 30 Protection class II (in housing type 505) Overvoltage category II Electrical separating measures Reliable separation acc. VDE 0106, part 1 between power supply, fail safe relay and level relay and meas. data inputs - reference voltage 250 V - insulation resistance 2.3 kv Galvanic separation among relay outputs - reference voltage 250 V - insulation resistance 1.4 kv Potential separation between DISBUS and outputs - reference voltage 50 V - insulation resistance 0.5 kv Common reference potential on voltage and current output, correction signal input Mechanical data Series module unit for carrier BGT 596 or housing type 505 Dimensions W = 25.4 mm (5 TE), H = mm, D = 162 mm CE conformity VEGAMET 515 and VEGAMET 515 Ex signal conditioning instruments meet the protective regulations of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. the following standards: EMC Emission EN : 1993 Susceptibility EN : 1995 NSR EN : VEGAMET 515

9 Product description Ex technical data Power supply Operating voltage Reference voltage U nom corresponds the non-ex version U m = 250 V AC or 125 V DC Meas. data input (intrinsically safe circuit) Classification Max. values - voltage U O = 20 V - current I O = 128 ma - power P O = 640 mw Characteristics Effective inner inductance L I Effective inner capacitance C I [EEx ia] IIC, [EEx ia] IIB, [EEx ib] IIC or [EEx ib] IIB linear negligible negligible EEx ia IIC EEx ia IIB EEx ib IIC EEx ib IIB Max. permissible outer inductance L O (mh) Max. permissible outer capacitance C O (nf) The intrinsically safe circuits are reliably separated from the non-intrinsically safe circuits up a peak value of the nominal voltage of 375 V. The max. voltage on the non-intrinsically safe circuits must not exceed 250 V eff in case of failure. 1.5 Dimensions Circuit board 100 x 160 x 1.5 European size Multipoint connecr 5 TE ,4 15 5, ,4 VEGAMET 515 9

10 Mounting 2 Mounting VEGAMET 515 signal conditioning instruments can be either mounted with a module in a carrier BGT 596 or BGT 596 Ex.M or in a single housing type 505. Mounting in carrier Mount the respective module (standard or Ex version) in your carrier. Wire the connection of the multipoint connecr according the wiring plan. Module Multipoint connecr DIN , series F, 33- pole (d, b, z) with coded pins and mounting material for mounting in carrier BGT 596 or BGT 596 Ex.M. Module Ex Multipoint connecr DIN , series F, 33- pole (d, b, z) with coded pins, Ex separating chamber and mounting material for mounting in carrier BGT 596 Ex.M. The multipoint connecr is available in the following versions: - Wire-Wrap standard connection 1.0 x 1.0 mm - Plug connection 2.8 x 0.8 mm - Termi-Point standard connection 1.6 x 0.8 mm - Soldering connection - Screw terminals 2 x 0.5 mm 2 Transparent cover To protect the instrument against unauthorised adjustment, the front plate of VEGAMET can be provided with a lockable transparent cover (supplied with the instrument). Coding To prevent an interchanging of the different signal conditioning instruments, the multipoint connecr of carrier or the housing can be equipped with coded pins. Note: The coding is absolutely necessary for Ex instruments! The multiple plug of the signal conditioning instrument is equipped with respective holes (mechanical coding). Instrument coding ensures that the different signal conditioning instruments are not interchanged. The appropriate coded pins are supplied with each module or housing. Equip the multipoint connecr with these coded pins acc. the following table. Instrument Ex coding coding VEGAMET 515 a5 / c5 VEGAMET 515 Ex a5 / c5 c23 For further mounting information, see the operating instructions of the carrier. Mounting in single housing Either screw the housing socket directly the mounting plate or plug on a carrier rail (35 x 15 acc. EN or 32 acc. EN ). Connect the terminals according the wiring plans on the following pages. For further mounting information, see the operating instructions of the housing. a5 z b d a c o 1 o o 3 o o 5 o o 7 o o 9 o o11o o13o o15o o17o o19o o21o o23o o25o c5 c23 o27o o29o o31o 10 VEGAMET 515

11 Electrical connection 3 Electrical connection 3.1 Connection instructions Note the following instructions for electrical connection: - The connection must be made acc. the local installation standards (e.g. in Germany acc. the VDE-regulations). - The wiring between VEGAMET and sensor can be done with standard two-wire cable. - If strong electromagnetic interference is expected, screened cable is recommended. The screening must be earthed on both ends. - The line resistances stated in the technical data must not be exceeded. - If overvoltages are expected, we recommend a sensor electronics with integrated overvoltage protection or the installation of VEGA overvoltage arresters. - The voltage supply of VEGAMET must provide extra-low voltage ensure protection class II. When using VEGASTAB 593, a reliable separation from the mains circuits acc. DIN VDE 0106, part 101 is ensured. 3.2 Connection instructions for Ex approved applications The signal conditioning instruments must be generally mounted outside the hazardous areas or special Ex protective measures must be taken. Ex separating chamber To ensure sufficient "air and creep distance, an Ex separating chamber must be mounted the connections of VEGAMET. Lead the cables through the Ex separating chamber and connect them. Fasten the Ex separating chamber with the lower screw. Note the operating instructions of the carrier BGT 596 Ex.M. Protection in Ex applications In Ex applications, protection class IP 20 must be maintained. To do this, cover the gaps or unused module plugs with suitable blind covers. Mounting in carriers If you mount your VEGAMET with Ex approval in a carrier, you have use a VEGA- Ex module plug. Keep a distance of at least 10 mm (2 TE) module cards of other manufacturers. If you want mount VEGAMET at the utmost left position in the carrier, you have mount a blind cover with at least 20 mm width (4 TE) in front of the module plug of the instrument ESC OK CONNECT 1 2 on Blind cover (4 TE) VEGAMET

12 Electrical connection 3.3 Wiring plan Supply voltage L (+) N ( ) 2 6 d b z + Fail safe relay Current outputs1 3 Voltage outputs 1 3 Correction signal input 4 Correction signal input Level relay 1 Level relay 2 DISBUS output + Sensor 1 Sensor 2 Ex version For connection of Ex certified instruments, please note the instructions in the attached official documents as well as all relevant mounting regulations. Make sure that the Ex separating chamber is mounted the multipoint connecr. Always lead the cables through the Ex separating chamber. Also note the operating instructions of the carrier BGT 596 Ex.M and the Ex instructions. 12 VEGAMET 515

13 Adjustment 4 Adjustment 4.1 Indicating and adjustment elements A rotary switch is located on the circuit board. It is used for adjustment of the instrument address on DISBUS. This setting is necessary if the measured values are be transmitted via the DISBUS cable external instruments, e.g. VEGADIS 174 indicating instrument, VEGACOM 557 interface converter or other VEGAMETs. With these external instruments, the allocation of a received measured value a specific measurement loop can be determined by means of the address. The adjustment range 1 F corresponds the DISBUS addresses Facry setting: 1 Note: With address 0, the VEGAMET does not participate in the DISBUS communication. Rotary switch F A B E C D The set instrument address on the DISBUS can be indicated on the LC display. Note If several VEGAMET are linked via the DISBUS, each address must only be assigned once! Position of the rotary switch Rotary switch Front plate VEGAMET 515 without adjustment module 1 2 on CONNECT 515V 1 2 with adjustment module CONNECT 1 LCD (4 lines with 6 figures each, illuminated) for clear text indication 2 LED chain (yellow) for quasi-analogue indication of the measured value 3 Keys for menu adjustment 4 Connection socket for VEGACONNECT 5 LED (yellow) lights if the relay is energised (standard setting) 6 LED (red), lights if fail safe relay is deenergised 7 LED (green), lights if operating voltage is on - ESC on OK 515V 514 VEGAMET

14 Adjustment 4.2 Adjustment system Indicating and adjustment module Branching point, i.e. jump the next lower menu with [OK] Indication of - measured value - menu item - parameter Depending on the menu item, change value or choose out of a list Choose menu item Depending on the menu item, interrupt adjustment or change the next higher menu Depending on the menu item, save the set value or change the lower menu ESC OK Adjustment structure The adjustment is made via 6 keys in conjunction with the text display. The jump from the measured value display the lower menu item is made with [OK]. Use [ >] or [< ] change within this menu level from one menu item the other. A branching point is indicated by the symbol and enables with [OK] a jump the lower menu item. Parameters are indicated when the symbol is missing. The value of the parameters can be modified with [+] or [ ] or chosen out of a list. The modified value can be saved with [OK]. To interrupt a setting (without saving the modification), you have push [ESC]. The reset the next higher menu item is made with [ESC]. 15 minutes after pushing the key for the last time, an aumatic reset the measured value display is triggered. The reset the next higher menu level with [ESC] is possible from each menu item, even if no connection is shown in the menu schematics. ESC ESC ESC ESC Add l functions Password on Language English VEGA- MET ESC Service If you are in the utmost right menu item of a menu row and push the [ >] key, you will immediately reach the utmost left menu item of this row. You also reach immediately the utmost right menu item from the left one, if you push the [< ] key. The connections (shown with a broken line) are not shown in the menu schematics in order provide a better overview. Volt output 1 Edit lin. curve Info ESC prop. Percent Unit 0,0 Volt output 0/10V Failure mode 0V Volt limitation on 14 VEGAMET 515

15 Adjustment Demonstrations in the menu schematic Language English In white letters you see the parameters which can be modified with the [+] or [ ] key and can be saved with the [OK] key. Examples: - In the menu item "Language you can change from German English. Bolt print/italic inputs, e.g. the measurement loop name "" can differ when you have made the appropriate parameter adjustment or configuration of the measurement loop. In the menu schematics you see the facry setting. Volt at 0 0,000 Light grey menu items are only displayed if necessary (dependent on the adjustments in the other menu items). 4.3 Adjustment via PC Signal conditioning instrument with adjustment module Setup - directly via the keys of the adjustment module - or with a PC, equipped with VVO software (VEGA Visual Operating) and an interface adapter VEGACONNECT. Signal conditioning instrument without adjustment module Setup - with a PC, equipped with VVO software (VEGA Visual Operating) and an interface adapter VEGACONNECT ESC OK CONNECT 1 2 on 515 VEGACONNECT PC with VVO software VEGAMET

16 Adjustment 4.4 Configuration and parameter adjustment No matter whether you set up your VEGAMET via the keys of the adjustment module or via a PC with the software VVO, the procedure is always the same. Proceed in the following sequence: - configuration (if not already configured as facry setting) - parameter adjustment. In this operating instructions manual, the adjustment steps are described which are directly carried out on the keys of VEGAMET. The adjustment via the software VVO is described in a separate manual. Configuration Configuring means assigning or setting (once) functions. VEGAMET requires a (mostly once) basic co-ordination that determines the applications and the assignments of the inputs and outputs. Choices can be made from existing functions and options. This procedure is called configuration. The signal conditioning instruments are delivered with a configuration which only needs be changed in special cases. The basic configuration includes the following steps: 1 Configuration measurement loop Choose the kind of application (level, gauge ) Choose sensor type (capacitive, hydrostatic ) Determine application (standard, level difference ) Determine options (no option, corrections ) 2 Configuration of inputs Specify from where your VEGAMET receives the input data (sensor, other VEGAMET) Enter sensor characteristics values (meas. range, current range) 3 Configuration of outputs All outputs (except fail safe relay) can been assigned one sensor or can be switched off. After basic configuration, VEGAMET goes in operating mode and indicates the actual measured value. The other configurations should be carried out after the parameter adjustment. Parameter adjustment Parameter adjustment means changing the values. Signal conditioning instruments have many parameters, the values of which can be modified, such as for example the integration time of s. The modification of these values is called parameter adjustment. The parameter adjustment does not influence the configuration. Take notice that parameter adjustment is only possible after a configuration has been carried out (e.g. set values of the current input after the current output has been assigned). Note: The measurement loop configuration can only be modified if a " single measurement or " linked application has been carried out before (under "Additional functions ). 16 VEGAMET 515

17 Setup 5 Setup Adjust the VEGAMET instrument address with the rotary switch on the circuit board (if measured values should be transferred via the DISBUS cable external instruments, e.g. VEGADIS 174 indicating instrument, VEGACOM 557 interface converter or VEGAMET). Install VEGAMET. Connect sensor and power supply. After switching on, the display indicates for approx. 10 secs the instrument type and the software version, e.g. "MET 515 V1.12. If no measurement loop has yet been configured, the display shows "Configuration, the red fault indicar LED also lights. In this case, proceed as described under "6.1 Configuration measurement loop. If a measurement loop has already been configured, the display shows a value, e.g. " 21.8.You can now carry out the settings. VEGAMET

18 Configuration 6 Configuration 6.1 Configuration measurement loop, two independent single measurements Config inputs Config meas. loop TAG 1 Level TAG 2 Level 1) The settings in these menu items can only be modified if a " single measurement was carried out beforehand (under menu item "Additional functions ). Configuration like TAG1 1) 1) 1) 1) Application Mode Option Level 0/4-20mA Gauge Pressure Sensor type Hydrostatic Standard no option Offset cor. Real value cor. Density cor. DK-cor. Position A no.1 Sensor coordination TAGname from undefined Position D no.4 Fault signal on off PositionE no.4 Tare from undefined Capac. Difference VEGADIF VEGABAR Moniring The measurement loop configuration is usually provided as a facry setting. Should a general modification of the measurement loop configuration be necessary, first of all a " single measurement or " linked application should be carried out (with " single measurement the VEGAMET is prepared for configuration of two independent single measurements. With " linked application it is prepared for configuration of linked applications). Only then can adjustments in the menu items Application, Sensor type, Mode and Option be modified. Proceed in the menu items in the given sequence. The adjustment or selection possibilities always depend on what was adjusted in the previous menu item. When e.g. in the menu item Application "Level is adjusted, only one sensor type can be selected in the menu item "Sensor type which is suitable for level detection. As soon as you have made an adjustment in the menu item "Option and confirmed it, the display shows the message: "TAG being created!. You choose the application 4/20 ma if you want connect a sensor of another manufacturer VEGAMET. In the following illustrations, different types of applications are shown. In addition, you will see which adjustments you have carry out in the menu items "Sensor type and "Mode. The menu item "Position D only appears when in the menu item "Option either "Offset correction or "Real value correction has been set. The menu item "Position E only appears when in the menu item "Option either "Density correction or "DK correction has been set. 18 VEGAMET 515

19 Configuration In the menu items "Pos. D and "Pos. E you can determine if "Correction input 4 or "Correction input 5 is be used for one of the stated corrections. You only then have enter under "Parameter adjustment "Special functions in the menu items "Real value correction at or "Density correction at a value at which the correction should be carried out. Note! For tare and moniring, it is also possible assign input 4. However, it must not be used for tare, moniring and e.g., density correction, at the same time! Two independent single measurements Pos. A Pos. A Level measurement Pos. A In the menu item "Name, you can enter an individual name for the measurement loop. If you choose "Fault signal off, the fail safe relay and the fault indicar LED in the front plate do not function. For a description of the correction modes, see the following pages. Gauge measurement Pos. A Pos. A Process pressure measurement Pos. A Differential pressure measurement VEGAMET

20 Configuration Offset correction - with unpressurized sensor - parallel shift of the adjustment characteristics actual measured value in 100 incorrect course of measured values Measured value o low Measured value o high Pos. A Pos. D corrected measured value e.g. 0 Offset correction Real value correction - with available percentage value - parallel shift of the adjustment characteristics actual measured value in incorrect course of measured values Measured value o low 100 Measured value o high Pos. D Pos. A corrected measured value e.g. 20 Real value correction Density correction - only in conjunction with hydrostatic pressure transmitters - slope correction of the adjustment characteristics actual measured value in 100 Pos. E 40 incorrect course of measured values smaller density, measured value o low higher density, measured value o high Pos. A corrected measured value e.g. 40 Density correction DK correction - ε r correction - only in conjunction with capacitive electrodes - slope correction of the adjustment characteristics actual measured value in Pos. A 100 Pos. E 40 incorrect course of measured values Dielectric constant o low, measured value o low Dielectric constant o high, measured value o high DK correction corrected measured value e.g VEGAMET 515

21 Configuration 6.2 Configuration measurement loop, linked applications (note the explanations under "6.1 Configuration measurement loop, two independent single measurements ) Level measurement in pressurised vessels Pos. B Pos. A Level measurement in pressurised vessels Configuration Config inputs Config meas. loop Application Level Sensor type Hydrostatic 1) Mode Pressurized 1) 1) 1) Option no option Sensor coordination TAG 1 Level TAG 2 Gauge pressure TAG 3 Total pressure like TAG 1 1) The adjustments in these menu items can only be modified if a " combi measurement was carried out beforehand (under menu item "Additional functions ). TAGname Fault signal on off Tare from undefined Moniring from undefined Position A no.1 Position B no.2 Position D no.4 Position E no.5 VEGAMET

22 Configuration Product with variable density Pos. C Pos. A Level measurement, product with variable density (density compensation) Configuration Config inputs Config meas. loop Application Level Sensor type Hydrostatic Mode variable density Option no option Sensor coordination TAG 1 Level TAG 2 Density TAG 3 uncor. level 1) 1) 1) 1) 1) The adjustments in these menu items can only be modified if a " combi measurement was carried out beforehand (under menu item "Additional functions ). Offset cor. Real value cor. Density cor. TAGname Fault signal on off like TAG 1 Tare from undefined Moniring from undefined Position A no.1 Position C no.2 Position D no.4 Position E no.5 22 VEGAMET 515

23 Configuration Level difference Pos. A Pos. B Level measurement, level difference Configuration Config inputs Config meas. loop Application Level Sensor type Hydrostatic Mode Difference Option no option Sensor coordination TAG 1 Level1 TAG 2 Level2 TAG 3 Difference 1) 1) 1) 1) 1) The adjustments in these menu items can only be modified if a " combi measurement was carried out beforehand (under menu item "Additional functions ). Real value cor. TAGname Fault signal on off like TAG 1 Tare from undefined Moniring from undefined Position A no.1 Position B no.2 Position D no.4 Position E no.5 VEGAMET

24 Configuration Gauge difference Pos. A Pos. B Gauge difference Configuration Config inputs Config meas. loop Application Gauge Sensor type Hydrostatic Mode Difference Option no option Sensor coordination TAG 1 Upstream water TAG 2 Downstream water TAG 3 Gauge diff. 1) 1) 1) 1) 1) The adjustments in these menu items can only be modified if a " combi measurement was carried out beforehand (under menu item "Additional functions ). Real value cor. TAGname Fault signal on off like TAG 1 Tare from undefined Moniring from undefined Position A no.1 Position B no.2 Position D no.4 Position E no.5 24 VEGAMET 515

25 Configuration Process pressure measurement as differential pressure measurement Pos. A Pos. B Process pressure measurement as differential pressure measurement Configuration Config inputs Config meas. loop Application Pressure Sensor type VEGA- BAR Mode Difference Option no option Sensor coordination TAG 1 Process press1 TAG 2 Process press2 TAG 3 Press. diff. 1) 1) 1) 1) like TAG 1 1) The adjustments in these menu items can only be modified if a " combi measurement was carried out beforehand (under menu item "Additional functions ). TAGname Fault signal on off Tare from undefined Moniring from undefined Position A no.1 Position B no.2 Position D undefined Position E undefined VEGAMET

26 Configuration 6.3 Measurement loop name 6.4 Fault signal Naming the measurement loop You can modify the measurement loop name ", if you want a more meaningful designation. Two lines with six figures each are available. To do this, move the menu item "TAG name. Name Push [+] or [ ] once. The first character of the measurement loop name, in this example the letter T, flashes (editing mode). Continue pushing the [+] or [ ] key, with this you scroll through the alphabet, through the row of numbers and through a list of characters. If you choose "Fault signal off at a certain measurement loop, the fail safe relays and the fault indicar LEDs in the front plate will not react when a failure occurs on this measurement loop, e.g. in case of short-circuit. Failures on other measurement loops, however, will be signalled. Only if on all measurement loops "Fault signal off is selected will the fail safe relay and the fault indicar LEDs be completely out of operation. Name When you have reached the requested character, push [ >]. The next character is activated and begins flash. Scroll again with [+] and [ ] the requested character. With [ >] you again reach the next character. Name Vess.4 Hall3 If you have finished the last position of the name and "written" the name of the measurement loop in this way, you have push [OK] save the setting. If you quit the menu item without saving, the name of the measurement loop will still be ". Vess.4 Hall3 27,8 In the display of measured value and all other menu items in which the measurement loop name is stated, you will now find the new designation. 26 VEGAMET 515

27 Configuration 6.5 Tare With the function "Tare a measured value beginning at 0 is created from the actual measured value. The tare function can be started via a key connected correction signal input 4. Choose in the menu item " from (under the menu item "Tare ) input 4. Taster Meas. values in 100 tared course actual course Adjustment Signal conditioning Outputs actual measured values tared measured values Curr. outputs Volt outputs Volt output 1 The following steps are necessary activate the tare function: Connect a key (closer) input 4. prop. Percent Volume Unit Tare Tare V Assign the tared values in the menu item "Unit the requested output (e.g. current, volt, DIS, PC/DCS output, MET indication). Configuration Config inputs Config meas. loop If you want delete the tare function again, you first have cancel taring in the menu item "Unit. Then you have cancel the allocation of the correction input (input 4) under the menu item "Tare. TAG 1 Level Application Level Tare from no.4 VEGAMET

28 Configuration 6.6 Moniring To activate moniring, the following prerequirements must be met: Configuration Config inputs Config meas. loop Adjustment Signal conditioning Outputs Curr. outputs Volt outputs Relay outputs TAG 1 Level Relay output1 Application Level Moniring prop. Percent Unit 0,0 Mode (moniring) Monit. Low & High Low 5,0 High 5,0 from no.4 Choose in the menu item " from (under the menu item "Moniring ) input 4. Connect a key switch (opener) input 4. Choose in the menu range "Parameter adjustment relay outputs in the menu item "Mode the mode "Moniring for the selected relay. The selected relay activates. By pushing the key switch (opener opens), the actual measured value is first of all frozen and, derived from this, the relay deactivates if this value is underrun (Low) or exceeded (High). After a reset and a repeated push of the key switch, the actual measured value is again frozen. Meas. value 50 High 5 Low 5 >55 <45 Relay deenergises If the moniring function has be deactivated, moniring must first be cancelled in the menu item "Mode. Then, the allocation of the correction input (input 4) must be cancelled under the menu item "Moniring. 28 VEGAMET 515

29 Configuration 6.7 Configuration of inputs Configuration Config inputs no. 1: VBUS input (measured value) no. 4: Correction input no. 1 no. 2 no. 4 no. 5 from local Met MET02 MET03 MET04. Channel no. S1 undefined Sensor characteristics Min. meas. range 0,00 like input 1 Max. meas. range 1,00 Min. sensor value 4,000 Max. sensor value 20,000 from local Met Channel no. K1 like input 4 undefined local MET: Here you can enquire another VEGAMET (e.g. Met 04) and hence determine that the input signal is not accepted from a directly connected sensor, but from a VEGAMET connected via DISBUS (e.g. VEGAMET 515). The enquired VEGAMET number corresponds the DISBUS address of the instrument (see chapter 4.1). Enter under "Sensor characteristics the values stated in the test certificate (of hydrostatic pressure transmitters). These settings are important if you carry out a differential measurement with your VEGAMET. The menu items "Min. meas. range and "Max. meas. range are only visible with hydrostatic pressure transmitters. If another VEGAMET has been chosen, the menu item " undefined" appears in which you can set the input number of the other VEGAMET (see example "Weir control ). VEGAMET

30 ESC OK CONNECT 1 2 on 515V ESC OK CONNECT 1 2 on 515V Configuration Example weir control Sensor 1 Weir 1 Sensor 2A 2 1 Weir 2 Upstream water Sensor 2B DISBUS "local MET "MET04 In the example illustrating weir control, two linked measurements are shown. The gauge difference is measured on each weir with one VEGAMET 515. Normally two sensors would be required for each VEGAMET. However, since the gauge value of the upstream water is valid for both VEGAMETs, one sensor is sufficient for the upstream water. The input signal of sensor 1 (upstream water) is transmitted via the DISBUS cable from one VEGAMET (MET04) the other VEGAMET. The value of sensor 1 is therefore available both signal conditioning instruments. 30 VEGAMET 515

31 Configuration 6.8 Configuration of outputs Configuration Config inputs Config meas. loop Config outputs Config curr. output Config volt output Config relay output Config PC/ DCS output Config VEGA- DIS Opera ting relay Fail safe relay PC/DCS meas. values DIS PC/DCS relay status off PC/DCS input status off DIS Rel Rel. 1 DCS Rel. 2 Standarfined unde- Hold 4 function of alarm function Standarfined unde- Hold 4 function of alarm functions Rel DCS Relay Standard Volt1 Volt2 No. 2 Volt3 No. 3 ma1 ma2 No. 2 ma3 No. 3 PC/PLC output and DIS output: The PC/PLC signal as well as the DIS signal are transmitted via the DISBUS. The PC/PLC output delivers output signals from VEGAMET an interface converter VEGACOM 557. This interface converter transfers the signals from VEGAMET via different standard procols connected systems (DCS/PLC). In the menu items "DCS 1 up "DCS 7 the measurement loop can be allocated or switched off. In the menu items "PC/DCS relay status and "PC/DCS input status you can order the relay mode and input status be transmitted via the DISBUS. Up three external indicating instruments (VEGADIS 174) can be connected DISBUS. In the menu items "DIS 1 up "DIS 7 the measurement loop can be allocated or switched off. VEGAMET

32 Configuration Relay outputs A hold function or a function for reset of alarm functions can be allocated each operating relay. In this case, the menu item " undefined appears. There, " 4 or " 5 (correction inputs) can be assigned the relay. For a description of the relay functions, see drawing. Hold function Parameter High Low Key t d bz Relay output of alarm functions Parameter High Low Key t d bz Relay output The relay modes "Hold function and " of alarm functions are configured as described above and activated each with an external signal (correction signal input). 32 VEGAMET 515

33 Parameter adjustment 7 Parameter adjustment 7.1 Adjustment with medium You can either carry out the adjustment with medium or without medium. To carry out an adjustment with medium, it is necessary that you know the percentage values of the vessel for the actual filling. Adjustment example Maxadjust at 100,0 You know that your vessel is presently filled up 80. Move the menu item "Max-adjust at Briefly push the [ ] key, so that the figure flashes (editing mode). Maxadjust at 80,0 Continue pushing [ ] until the figure 80.0 appears on the display. Now push [OK] save the adjustment. Signal conditioning Minadjust at 0,0 mode). Then if your filling is for example 10, move the menu item "Minadjust at 0.0. Briefly push the [+] key until the figure 0,0 flashes (editing with medium Adjustment Minadjust at 0,0 Scaling Maxadjust at 100,0 Lin. curve linear Integr ation time s 0 Density in kg/dm DK value (Er) For this procedure, percentage values must be entered for min. and max. that correspond the actual fillings. The sequence of the min. or max. value is not important. For example, if you know that your filling is presently 80, you can enter in the menu item Max. adjustment the value "80. Then if your filling is, for example, 10, you enter in the menu item Min. adjustment the value "10. The larger the difference between the two adjustment points, the more exact the measurement over the whole measuring curve. It follows that adjustment at 0 and 100 would be best. For practical reasons, however, it is not always possible completely fill or empty a vessel. The distance between the two adjustment points, however, should be at least 10 of the sensor range. Minadjust at 10,0 Continue pushing [+] until "10 appears on the display. Now push [OK] save the adjustment. Of course, you can carry out the adjustment with medium also at 0 and 100 filling. Please note: The figures 0 and 100 must flash (editing mode) before they can be saved with the [OK] key. Note: If the medium is later changed (medium with another density value or dielectric constant) and no new adjustment is possible or if the MET indication and the DIS outputs refer height in metres, note the following: For applications with hydrostatic pressure transmitters, the adjusted density value must correspond the value of the medium. For applications with capacitive electrodes, the adjusted dielectric constant must correspond the value of the medium (water has a density of 1.0 kg/dm 3 and a dielectric constant of 81.00). The menu items "Density or "DK value are displayed if the respective sensor type was selected under "Configuration measurement loop. VEGAMET

34 Parameter adjustment 7.2 Adjustment without medium Adjustment example Adjustment Meas. value indication You know the data of your sensor, i.e. you know the sensor delivers at 0 filling a current of 4.2 ma and at 100 filling a current of 15.5 ma. Enter these values in the menu items ma at 100 with medium w.o. medium Adjustment ma bar m Offset correction Sensor unpres sur d? 0 at ma 4, at ma 20, ma at 0 Offset corr. Now! 0 at ma 4, at ma 15,500 For the "Adjustment without medium, two anticipated levels, gauges etc., corresponding 0 and 100 must be entered. Depending on the sensor type used, the adjustment can be carried out in ma, bar or m. In these two menu items, you enter the sensor values. Use the [+] and [ ] keys set the values and [OK] save the values. The menu item "Offset correction is activated when connecting hydrostatic pressure transmitters. The offset correction should be carried out after installation of the sensors because the sensor values can differ slightly in various installation positions (vertical or horizontal mounting). With the offset correction, the measured data of an unpressurized sensor (vessel empty) are detected as a corrective value and taken in account in all all subsequent measurements. 34 VEGAMET 515

35 Parameter adjustment 7.3 Adjustment with linked measurements Linked measurements are possible with VEGAMET 515. For this reason, two sensors are connected which carry out one measurement each (TAG1 and TAG2). VEGAMET 515 calculates from the two sensor values a third value, e.g. a gauge difference (TAG3). When adjusting linked measurements, facrs other than those with single measurement will possibly have be taken in account. For all linked measurements, it is important enter the sensor characteristics values before the adjustment. To do this, move the menu item under "Sensor characteristics. No. 2 No. 3 No. 2 No. 3 Configuration Config inputs no. 1 no. 2 from local Met MET02 MET03 MET04. Channel no. S1 undefined Sensor characteristics Min. meas. range XXX like input 1 Max. meas. range XXX Min. sensor value XXXX Max. sensor value XXXX Enter here the characteristics values. The data are stated in the test certificate of your sensor. VEGAMET

36 Parameter adjustment Adjustment of gauge difference Upstream water Gauge difference TAG1 TAG2 TAG3 Downstream water The adjustment of the individual measurement loops TAG1 and TAG3 is the same as the adjustment of single measurement loops, see "7.1 Adjustment with medium and "7.2 Adjustment without medium. It is also possible carry out the adjustment only for measurement loop TAG3. If you want adjust all three measurement loops, the sequence is not important. Make sure the gauge is the same (difference = 0 ). Enter in the menu item "Min-adjust at the figure "0.0 (push the "+ or "- key until the figure "0.0 flashes, then push the "OK key). Mark the position of the sensor in the downstream water. Suspend the sensor 30 cm higher (if 30 cm should correspond 100 ). A 30 cm lower gauge is now simulated. Enter in the menu item "Max-adjust at the figure "100.0 (push the "+ or "- key until the figure "100.0 flashes, then push the "OK key). Suspend the sensor in the original position. Note: You can also suspend the sensor in upstream water in a lower position carry out the max. adjustment. Adjustment of the gauge difference measurement loop (TAG3) Suspend the sensors the same level. Note that a difference of 30 cm (e.g. with weir control) can correspond 100. Adjustment without medium The easiest way would be carry out the adjustment without medium in the adjustment unit "m. Adjustment with medium Adjustment Adjustment with medium w.o. medium with medium Minadjust at 0,0 Maxadjust at 100,0 Adjustment m bar ma Offset correction Sensor unpres sur d? 0 at m 0, at m 0,300 Offset corr. Now! 36 VEGAMET 515

37 Parameter adjustment Adjust in the menu item "Adjustment the unit "m. Enter in the menu item "0 at m and "100 at m the values 0.00 and 0.30 (if 30 cm should correspond 100 ). Only carry out the offset correction at this point when both sensors are unpressurised. If you want carry out the adjustment in ma or bar, you have enter the difference values of the sensor currents or the pressures. If you want that the gauge difference of 30 cm is shown in the meas. value indication in cm, you can carry out a scaling (see "7.4 Scaling ). No. 3 Adjustment with level measurement in pressurized vessels For the adjustment of measurement loop TAG1 (level) you can proceed in the same manner as for the adjustment of a single measurement loop. The adjustment can be either carried out with or without medium (product). Measurement loop TAG2 (gauge pressure) is adjusted without medium, preferably in "bar. For level measurement (TAG1), an adjustment of TAG2 is not necessary. Also, the adjustment of measurement loop TAG3 (tal pressure) must not be carried out if you only want know the level of TAG1. Often, the tal pressure is requested as measured value, if e.g. in a filling system, the filling pressure should be measured and controlled. In this case carry out the adjustment without medium in "bar. Adjustment Signal conditioning Scaling 0 corres ponds corres ponds 300 Decimal point 888,8 prop. Height Unit cm Adjustment with level difference and pressure difference The adjustment with this linked measurement corresponds that of the adjustment with gauge difference and is therefore not described separately. VEGAMET

38 Parameter adjustment 7.4 Scaling Scaling example Meas. value indication You have a raised tank and you want the level be indicated in meters with three places after the decimal point. 100 Adjustment Signal conditioning 0 h=4.5 m Scaling m h=1.5 m 0 corres ponds corres ponds 1000 Decimal point 888,8 prop. unde fined Unit The adjustments under scaling determine which number values and which unit will be actually displayed on the measured value indication (upper menu item). In the menu items "0 corresponds and "100 corresponds you can enter with [+] or [ ] and [OK] values which should be displayed at 0 and at 100 filling. In the menu item "Decimal point you determine the position of the decimal point. In the next menu item "prop. you get a choice of parameters: push [+] or [ ] select percent, mass, volume, pressure etc. and save with [OK]. According this adjustment, the menu item "Unit provides a new choice, e.g. m, dm, cm, mm, ft, yd and in, if you have selected the parameter "Height (compare chapter "8 Measuring results and units ). 0 corres ponds 1500 Set the number 1500 (with keys [+], [ ] and [OK]) in this menu item. This corresponds the level at 0 (if you want have a lower resolution of the meas. value indication, you can also set 150 or 15). 100 corres ponds 4500 Decimal point 8,888 prop. Height Percent Pressure Mass Set the number 4500 (with keys [+], [ ] and [OK]) in this menu item. This corresponds the level at 100. Adjust the decimal point as shown (with keys [+], [ ] and [OK]). Choose the term "Height in this menu item (with keys [+], [ ] and [OK]). After scaling, the requested output can be assigned the scaled value in the menu range "Parameter adjustment outputs (menu items "prop. and "Unit ). Unit m dm cm. If you have chosen "Height in the previous menu item, you get a choice of several units (mm, dm, cm, m, yard ). Choose m (with the keys [+], [ ] and [OK]). m 2,341 In the meas. value indication, the scaled value is now shown. 38 VEGAMET 515

39 Parameter adjustment 7.5 Choose linearisation curve 7.6 Integration time Meas. value indication Meas. value indication Adjustment Signal conditioning Adjustment Signal conditioning Scaling Lin. curve linear Cylindrical tank Spherical tank Lin. curve1 Lin. curve2 Lin. curve3 VEGAMET's evaluation routines can be adapted different vessel forms. To do this, you can choose between different linearisation curves: - linear (facry setting) - cylindrical tank - spherical tank - Lin-curve 1 - Lin-curve 2 - Lin-curve 3 You can edit or modify lin. curves 1 3 yourself (see appropriate chapter). Scaling Lin. curve linear Integr ation time s 0 If the integration time is set 0 s (facry setting), each quick change of the product surface (e.g. waves) will be immediately detected and interpreted as level change. All output values of VEGAMET will follow the wave movements. To avoid this, the integration time can be increased (max. 600 s are possible with VEGAMET). The higher the time setting, the slower the measurement reacts. After a linearisation, the requested output can be assigned the linearised value in the menu range "Parameter adjustment outputs (menu items "prop. and "Unit ). VEGAMET

40 Parameter adjustment 7.7 Meas. value limitation Meas. value indication Adjustment Signal conditioning Scaling Lin. curve linear Integr ation time s 0 Density in kg/dm DK value (Er) Meas. value limitation negative values yes no Failure mode Standard >110 Under "Meas. value limitation, you can exclude negative values on the display (and on the outputs). Failure mode standard means that the fail safe relay responds at a sensor current of 3.6 ma or 21 ma. Failure mode > 110 generates an additional fault signal at a measured value of more than 110 or less than VEGAMET 515

Operating Instructions

Operating Instructions Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction VEGASEL 643 6 5 + + 3 5 + + max. min. on VEGASEL 643 5 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 1 Product description 1.1 Function

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction VEGAVIB and signal conditioning instruments Contents Contents Safety information... 1 Product description 1.1 Function and configuration... 3 1. Types and versions...

More information

Operating Instructions. Indication and adjustment module PLICSCOM

Operating Instructions. Indication and adjustment module PLICSCOM Operating Instructions Indication and adjustment module PLICSCOM 8888 Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6

More information

Level and Pressure. Product Information. Conductive level detection

Level and Pressure. Product Information. Conductive level detection Level and Pressure Product Information Conductive level detection Contents Contents 1 Product description 1.1 Application... 1. Function... 5 1. Types/Versions... 6 1.4 Application examples... 8 1.5 Adjustment...

More information

Level and Pressure. Product Information. Vibrating level switches

Level and Pressure. Product Information. Vibrating level switches Level and Pressure Product Information Vibrating level switches Contents Contents 1 Product description 1.1 VEGAVIB... 3 1.2 VEGASWING... 3 2 Function and application 2.1 Functional principle... 5 2.2

More information

Level Measurement silometer FMX 570

Level Measurement silometer FMX 570 Technical Information TI 01F/00/en Level Measurement silometer FMX 570 Measurement of liquids and bulk solids Suitable for explosion hazardous areas For use with capacitance and hydrostatic probes The

More information

KSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays

KSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays KSR-Level sensor KSR-Schwimmer-Magnetschalter 1001-5 KSR Contact Protection s 1 KSR Contact Protection Type KR230-Ex and KR24-Ex General Description The contact protection relays KR230-Ex and KR24-Ex transmit

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction Capacitive electrodes EK 4 20 ma - compact Safety information Safety information The described module must only be installed and operated as described in this operating

More information

Level Limit Switch nivotester FTL 370, FTL 372

Level Limit Switch nivotester FTL 370, FTL 372 Technical Information TI 98F/00/en Limit Switch nivotester FTL 370, FTL 37 With intrinsically-safe signal circuits for connection to sensors Liquiphant, Nivopuls, Soliphant. Features at a Glance High operational

More information

Hydrostatic Level Measurement silometer FMB 672 Z, FMB 677 Z

Hydrostatic Level Measurement silometer FMB 672 Z, FMB 677 Z Technical Information TI 065F/00/en Hydrostatic Level Measurement silometer FMB 672 Z, FMB 677 Z Commutec transmitters for level measurement of liquids, pastes and sludge Certified for use in explosion

More information

SINEAX B 811 Power Pack with additional Functions

SINEAX B 811 Power Pack with additional Functions SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers

More information

SALES SERVICE +358 (0)

SALES SERVICE +358 (0) SALES SERVICE +358 (0)17 262 3555 info@econosto.fi ADCATROL ELECTRO-PNEUMATIC POSITIONERS PE 986 (ATEX) DESCRIPTION The ADCATROL PE986 positioner requires an input signal of 4 20 ma for proportional control

More information

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN Indicator and alarm signalling unit 10/30-2.10 EN Dimensions 36 mm x 144 mm Can either stand vertically or lie horizontally Comprehensively explosion-protected Robust moving-coil system Contactless alarm

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction Capacitive electrodes EK with signal conditioning instrument Safety information Safety information The described module must only be installed and operated as described

More information

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition Converter Connection 1-channel EEx ia IIC for 4-wire and 6-wire bridges Analogue output 0/4 ma... 20 ma or 4mA...-12mA Full bridge load cells and strain gauges circuit for resistance bridges up to 17 Ω

More information

RMA42. Technical Information

RMA42. Technical Information Technical Information RMA42 Process transmitter with control unit Digital process transmitter for mounting on a top-hat rail for monitoring and visualizing analog measured values Application Plant and

More information

VEGAFLEX 80 two-wire 4 20 ma/hart

VEGAFLEX 80 two-wire 4 20 ma/hart VEGAFLEX 80 two-wire 4 20 ma/hart.3.0 2/206 Function extensions New functions and modifications: Bulk solids applications Standard deactivation of the automatic false signal suppression Standard deactivation

More information

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator SINEAX TI 807 without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically

More information

SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically insulate

More information

SET Installation and Operating Instructions. Level switch for two sensors

SET Installation and Operating Instructions. Level switch for two sensors Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 20.2.2013 Internet: www.labkotec.fi 1/14 SET-2000 Level switch for two sensors Copyright 2013 Labkotec

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

Temperature transmitter itemp PCP DIN rail TMT 121

Temperature transmitter itemp PCP DIN rail TMT 121 Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

ISOMETER IRDH575. Approvals

ISOMETER IRDH575. Approvals Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with control and display function for EDS insulation fault location systems IRDH575_D00089_02_D_XXEN/09.2018 Insulation

More information

Transmitter for temperature and direct current variables in four-wire circuit. Contrans T TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex 11-3.

Transmitter for temperature and direct current variables in four-wire circuit. Contrans T TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex 11-3. TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex Transmitter for temperature and direct current variables in four-wire circuit Transmitters TEU 315 and TEU 325 are designed for direct and alternating voltage measurement

More information

Operating instructions Electronic level sensor LK / / 2008

Operating instructions Electronic level sensor LK / / 2008 Operating instructions Electronic level sensor LK31 UK 704046 / 00 01 / 2008 Contents Safety instructions...2 Menu structure...3 Controls and indicating elements...4 Function and features...5 Functional

More information

Monitoring Relay MR 50

Monitoring Relay MR 50 Monitoring Relay MR 50 Standard signals 0/4... 20 m, 0/2... 10 V DC Features M Input standard signals 0/4... 20 m, 0/2... 10 V DC M Measuring range programmable M Basic accuracy 0.1 % +/- 1 Digit M Installed

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

SINEAX / EURAX 2I1 Passive DC signal isolator

SINEAX / EURAX 2I1 Passive DC signal isolator SINEAX / EURAX I without power supply 0 II () G resp. II () G Application The DC signal isolator SINEAX/EURAX I (Figs. and ) serve to isolate load-independent DC current signals. It suppressed noise voltages

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Weighing Instruments. Applications. Characteristics. DMS strain gauges (load cells), DMS amplifier

Weighing Instruments. Applications. Characteristics. DMS strain gauges (load cells), DMS amplifier GHM GROUP CORPORATE GHM Messtechnik GmbH Schloßstr. 6 88453 Erolzheim GERMANY Phone +49 7354 937233-76 Fax +49 7354 937233-88 Weighing System Evaluation Mounting DMS strain gauges (load cells), DMS amplifier

More information

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched

More information

Weighing Instruments

Weighing Instruments GHM Messtechnik GmbH Sales Center International Schloßstraße 6 88453 Erolzheim Germany Fon +49-7354-937233-0 Fax -88 www.ghm-messtechnik.de info@ghm-messtechnik.de Weighing Instruments System Evaluation

More information

DS 400 DS 400. Intelligent Electronic Pressure Switch Completely in Stainless Steel. piezoresistive stainless steel sensor

DS 400 DS 400. Intelligent Electronic Pressure Switch Completely in Stainless Steel. piezoresistive stainless steel sensor GmbH Postal address: House address Fon (+49) 0 22 42-870-0 Postbox 26 Löhestr. 7 Fax (+49) 0 22 42-870-20 http: // www.tematec.de 5759 Hennef 577 Hennef e-mail: team@tematec.de Data Sheet Page /5 Intelligent

More information

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals Accessories High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals WIKA data sheet AC 80.03 Applications Machine building

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter

More information

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/ 3 Ex i Isolators Switching Repeater with Power Relay Intrinsically safe input [Ex ia] IIC Galvanic isolation between input, output and power supply Open-circuit / short-circuit monitoring and messaging

More information

Level Switch NRS 2-50 NRS Original Installation Instructions English

Level Switch NRS 2-50 NRS Original Installation Instructions English Level Switch NRS 2-50 NRS 2-51 EN English Original Installation Instructions 819179-03 1 Contents Important Notes Page Usage for the intended purpose...4 Function...4 Safety note...4 Directives and Standards

More information

Binary Output Series 9175

Binary Output Series 9175 Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use

More information

Pressure measurement. Process pressure/hydrostatic VEGAWELL 72. Product Information

Pressure measurement. Process pressure/hydrostatic VEGAWELL 72. Product Information Pressure measurement Process pressure/hydrostatic VEGAWELL 7 Product Information Content Content Description of the measuring principle........................................................... Type overview..............................................................................

More information

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation

More information

DIGEM f 96 x 48 EK. Applications. Description

DIGEM f 96 x 48 EK. Applications. Description 3-349-002-03 1/7.98 Front panel dimensions: 96 x 48 mm LED display: red or green, 14 mm high Max. display range: 19 999 to + 32 765 Modular connectors for flexible use Simple adjustments at front panel

More information

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting Electrical Temperature Measurement Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting WIKA Data Sheet TE 12.03

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

Design and applications

Design and applications Design and applications The measuring device operates largely independent of viscosity and is suitable for indicating the flow rate of water, acids, alkaline solutions and gases. Every device is calibrated

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net

More information

Isolators A3/1. Vibration Transducer Supply Unit Series

Isolators A3/1. Vibration Transducer Supply Unit Series > For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic

More information

GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50

GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50 GESTRA Steam Systems LRS 1-50 EN English Installation & Operating Instructions 819223-02 Conductivity Switch LRS 1-50 Contents Important notes Page Usage for the intended purpose...4 Function...4 Safety

More information

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/. Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas. MG-1000-EEx USAGE STRUCTURE AND DESIGN

Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas. MG-1000-EEx USAGE STRUCTURE AND DESIGN Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas Mimablad: 176GB/1999-10-25 Ersätter: MG-1000-EEx USAGE MG-1000-EEx is suitable for use in measurement

More information

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC71, PPC71

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC71, PPC71 Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC71, PPC71 DPC71 PPC71 TRMS 3-phase over and under voltage, phase sequence, phase loss, asymmetry and tolerance monitoring relay Detect

More information

DIN Rail Devices. CEAG Sicherheitstechnik GmbH 194

DIN Rail Devices. CEAG Sicherheitstechnik GmbH 194 DIN Rail Devices Description DIN rail devices serve as low cost signal conditioning modules between the field device and the control system. The new enclosures mounted on the 35 mm standard rail are equipped

More information

Positioner with HART Communication Type 3780

Positioner with HART Communication Type 3780 Positioner with HART Communication Type 780 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Supplied with an electric input signal from to 20 ma Travels

More information

OEM radar transmitter, for aggressive media level measurement

OEM radar transmitter, for aggressive media level measurement OEM radar transmitter, for aggressive media level measurement C ompact for level measurement up to 20 m 4... 20 ma/hart - 2 wires Adjustable with P C ATEX approvals Type 8136 can be combined with... Type

More information

Installation instructions Dec. 2002

Installation instructions Dec. 2002 Elect. Iss. 01 REFLEX VF Series Installation instructions Dec. 2002 Product liability and warranty: The VF SERIES level gauge is designed solely for measuring the distance, level and volume of liquids,

More information

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01 Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01 DPC01 PPC01 TRMS 3-phase over and under voltage, phase sequence, phase loss, asymmetry and tolerance monitoring relay Detect

More information

Technical Information RMA42

Technical Information RMA42 TI00150R/09/EN/05.16 71315973 Products Solutions Services Technical Information RMA42 Process transmitter with control unit Digital process transmitter for monitoring and visualizing analog measured values

More information

Insulation Guard IW 1000 Monitoring of ungrounded AC- and DC voltage systems up to 690V

Insulation Guard IW 1000 Monitoring of ungrounded AC- and DC voltage systems up to 690V Insulation Guard IW 0 Monitoring of ungrounded AC- and DC voltage systems up to 690V Features M Time optimized pulse measuring method M Safe monitoring at extreme conditions (frequency converter, phase

More information

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01 Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01 Product Description 3-phase or 3-phase+neutral line voltage monitoring relay for phase sequence, phase loss, asymmetry, over and

More information

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting Electrical Temperature Measurement Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting WIKA Data Sheet TE 24.01 Applications T Machinery, plant construction T Process industry

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

RCMS460 and RCMS490 Series

RCMS460 and RCMS490 Series 4 T M RCMS460 and RCMS490 Series Digital Multi-Channel Ground Fault Monitor / Ground Fault Relay Grounded and High-Resistance Grounded AC/DC Systems Technical Bulletin NAE1042060 / 04.2013 BENDER Inc.

More information

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs Plug-in module, or channels Application The programmable transmitter (Fig. ) is designed for measuring temperature in combination with thermocouples or resistance thermometers. Thermocouple non-linearities

More information

itemp HART DIN rail TMT112

itemp HART DIN rail TMT112 Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant

More information

SINEAX TV 808, 1 channel Isolating Amplifier, output Ex or non-ex

SINEAX TV 808, 1 channel Isolating Amplifier, output Ex or non-ex for electrically insulating, amplifying and converting DC signals, also designed for FSK 1 0102 II (1) G Application The purpose of the isolating amplifi er SINEAX TV 808 (Fig. 1) is to electrically insulate

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

2-WiRE LEvEL TRansmiTTER PRELEvEL 5343 ConTEnTs

2-WiRE LEvEL TRansmiTTER PRELEvEL 5343 ConTEnTs 2-wire level transmitter PRelevel 5343 Contents EC declaration of conformity... 14 Application... 15 Technical characteristics... 15 Mounting / installation... 15 Applications... 16 Electrical specifications...

More information

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5. Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

3DLevelScanner. Technical Data Sheet. Level Sensor. Non-Contact, Multiple-Point Measurement

3DLevelScanner. Technical Data Sheet. Level Sensor. Non-Contact, Multiple-Point Measurement Technical Data Sheet Non-Contact, Multiple-Point Measurement The 3DLevelScanner is a noncontact, dust-penetrating bin measurement device that detects irregular surfaces in powder or solid materials and

More information

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50 Technical Information Nivotester 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50 Area of application The Nivotester is suitable as a 1-channel switch amplifier for the Soliwave

More information

Technical Information Nivector FTC968, FTC968Z

Technical Information Nivector FTC968, FTC968Z TI0007F/00/EN/7.6 7494 Products Solutions Services Technical Information Nivector FTC968, FTC968Z Capacitance Point level switch for powder and fine-grained bulk solids Application The Nivector is a small-sized

More information

Portable equipment for insulation fault location for unearthed and earthed systems (IT and TN systems) to be used in conjunction with or without an

Portable equipment for insulation fault location for unearthed and earthed systems (IT and TN systems) to be used in conjunction with or without an EDS309 Portable equipment for insulation fault location for unearthed and earthed systems (IT and TN systems) to be used in conjunction with or without an equipment for insulation fault location EDS309x_D00012_00_D_XXEN/05.2015

More information

1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01

1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01 Monitoring Relays -Phase True RMS AC/DC Over and Under Current Types DIC0, PIC0 DIC0 PIC0 TRMS AC/DC over + under, over+over, under+under current and voltage monitoring relays DC process signal plus/minus

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

... for hydraulic and general applications in hazardous areas

... for hydraulic and general applications in hazardous areas ATEX Approved Inductive... for hydraulic and general applications in hazardous areas Inductive Namur sensors Explosion protected Ignition class "intrinsically safe" when used together a suitable certified

More information

Submersible pressure sensor For oils and fuels Model LF-1

Submersible pressure sensor For oils and fuels Model LF-1 Level measurement Submersible pressure sensor For oils and fuels Model LF-1 WIKA data sheet LM 40.04 Applications Level measurement in vessel and storage systems for oils and fuels Overfilling and dry-run

More information

PRetrans Table of contents

PRetrans Table of contents HART TRANSPARENT REPEATER PRetrans 5106 Table of contents Warnings 16 Safety instructions 17 EC Declaration of Conformity 19 How to demount SYSTEM 5000 20 Application 21 Technical characteristics 21 Mounting

More information

Level detection in liquid. Conductive. VEGAKON 61 VEGAKON 66 Probes EL 1, 3, 4, 6, 8. Product Information

Level detection in liquid. Conductive. VEGAKON 61 VEGAKON 66 Probes EL 1, 3, 4, 6, 8. Product Information Level detection in liquid Conductive VEGAKON 6 VEGAKON 66 Probes EL,, 4, 6, 8 Product Information Content Content Description of the measuring principle...........................................................

More information

ED701 General Industry Pressure Transmitter

ED701 General Industry Pressure Transmitter ED701 General Industry Pressure Transmitter Standard industrial process connections Complete range of electrical connections 4... 20 ma and Voltage outputs Accuracy: 0.1%, 0.2% and 0.4% FS Quick response

More information

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Installation and Operational Instructions for ROBA -switch Type 017._00.2 OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive

More information

ISOMETER iso685- -B. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Preliminary data sheet

ISOMETER iso685- -B. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Preliminary data sheet Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Preliminary data sheet iso685-x-b_d00177_04_d_xxen/04.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems

More information

Preset counters, electronic

Preset counters, electronic The Codix 716 / 717 can be used universally. These preset pulse, tachometers or preset timers with up to 2 presets can solve a wide variety of control and monitoring tasks in every application. With their

More information

Instruction manual SMART 96-2 / WG-2 ph

Instruction manual SMART 96-2 / WG-2 ph Instruction manual SMART 96-2 / WG-2 ph Stand: 06.09.2015 SMART 96-2 / WG-2 ph / mv Instructions for Installation Configuration PH-mV / Temp. 0...20 ma 4...20mA 20 ma PH-mV / Temp. 0...20 ma 4...20mA 20

More information

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active Technical manual BA 0318 Signal converter Isolation amplifier active for galvanic isolation, conversion and adjustment of electrical standard signals Evaluable input signals Direct voltage 0...10V / 0...1V

More information

Connection. Input EEx ia IIC. Input I. Input II R 1 R 1 A B A 2+ B LB SC. yellow. red. Composition

Connection. Input EEx ia IIC. Input I. Input II R 1 R 1 A B A 2+ B LB SC. yellow. red. Composition solated switch amplifier Output: relay Connection Control circuit EEx ia C 24 V DC nominal supply voltage Reversible mode of operation Lead monitoring (short-circuit LK and interruption LB) with LED indicator

More information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information *09005137* BA_EN_DE50 Rev.A 11/12 *09005137* d e v e l o p i n g s o l u t i o n s DE50 Operating Manual Differential pressure transmitter Table of Contents 1 Safety guidelines 2 Application purpose 3

More information

Contrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN

Contrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN Contrans T TEU 471, TEU 471-Ex Intelligent four-wire temperature transmitters Input/sensor connection: Resistance thermometers (2-, 3-, 4-wire circuit) Thermocouples (without, with internal/external reference

More information

Remote Switching Unit nivotester FTL 320

Remote Switching Unit nivotester FTL 320 Technical Information TI 203F/24/ae Remote Switching Unit nivotester For connection to intrinsically safe Liquiphant level limit switches Applications Limit detection of fluids and bulk solids in tanks

More information

Original operating instructions Fail-safe inductive sensor GG507S / / 2013

Original operating instructions Fail-safe inductive sensor GG507S / / 2013 Original operating instructions Fail-safe inductive sensor GG507S 80005283 / 00 05 / 2013 Contents 1 Preliminary note...3 1.1 Explanation of symbols...3 2 Safety instructions...4 2.1 Safety-related requirements

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL Version 2.2 MS1016 MTF SERIES VIBRATING PROBES FOR LIQUIDS AND HYC-PKK-312 SWITCHING ISOLATOR INSTALLATION AND OPERATION MANUAL Hycontrol Limited, Larchwood House, Orchard Street, Redditch, Worcestershire,

More information

Binary Output without Power Supply Series 9176

Binary Output without Power Supply Series 9176 Binary Output without Power Supply Series 9176 > For intrinsically safe operation of Ex i solenoid valves, indicators and horns > Power supply by control circuit, loop powered > Intrinsically safe output

More information

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

Original operating instructions Fail-safe inductive sensor GM504S / / 2010 Original operating instructions Fail-safe inductive sensor GM504S 704070 / 01 06 / 2010 Contents 1 Preliminary note 3 1.1 Explanation of symbols 3 2 Safety instructions 4 2.1 Safety-related requirements

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

Analog Universal Module HART for Zone 2 Series 9468/33

Analog Universal Module HART for Zone 2 Series 9468/33 > 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on

More information