Remote Switching Unit nivotester FTL 320

Size: px
Start display at page:

Download "Remote Switching Unit nivotester FTL 320"

Transcription

1 Technical Information TI 203F/24/ae Remote Switching Unit nivotester For connection to intrinsically safe Liquiphant level limit switches Applications Limit detection of fluids and bulk solids in tanks and silos; suitable for applications in explosion-hazardous areas Liquid detection in pipes for dry run protection of pumps Overspill protection of tanks containing flammable or non-flammable water-polluting liquids Features and Benefits Intrinsically safe signal circuits [Class I, II, III] for problem-free use of sensors in explosion-hazardous areas High functional safety with: - interference-immune PFM signal transmission - cable monitoring right up to the piezocrystal drive in the sensor - monitoring for corrosion at the vibrating fork of the Liquiphant sensor Compact Minipac housing for simple row mounting on a standard rail in the control cabinet Simple wiring using plug-in terminal blocks

2 Measuring System Explosion-hazardous area a) Class I Liquiphant Safe area (non-ex) Nivotester The measuring system consists of: the Liquiphant or Soliphant sensor the Nivotester control or signaling systems a) Limit detection in a tank containing liquid with one Liquiphant FDL 30, FDL 31, FDL 35, FDL 36 or DL 17 Z sensor b) Class II Soliphant Nivotester b) Limit detection in a silo containing bulk solids with one Soliphant DM 90 Z, DM 91 Z or DM 92 Z sensor Operating Principle The Nivotester is a limit switch for single measuring points. Signal Transmission The intrinsically safe input of the Nivotester limit switch is electrically isolated from both the power supply and the output. The Nivotester supplies DC power to the Liquiphant or Soliphant sensor via a two-wire cable and receives a frequency indicating whether the sensor fork is cove (approximately 50 Hz) or free (approximately 150 Hz). The sensor signal is a pulsed current of approximately 10 ma with width approximately 200 µs which is superimposed on the power supply. Signal Evaluation The Nivotester evaluates the frequency and activates the relay of the level alarm output. The switching mode of the relay is indicated by a LED on the front panel of the Nivotester. Fail-Safe Mode By correct selection of the fail-safe, the relay always operates in a quiescent current mode. Minimum fail-safe: The relay de-energizes when the level falls below the switchpoint (fork free), when a fault occurs or when the power fails. Maximum fail-safe: The relay de-energizes when the level rises above the switchpoint (fork cove), when a fault occurs or when the power fails. Limit detection as a function of level and fail-safe mode Level Signal transmission Maximum fail-safe mode with jumper Minimum fail-safe mode no jumper Fault I approx. 150 Hz PFM signal base current I approx. 50 Hz PFM signal base current Function Monitoring The Nivotester has a function monitoring system to increase operational safety. A fault is indicated by an LED and the relay also de-energizes. A fault is indicated if the Nivotester no longer receives an input signal, for example, on short-circuiting or breakage of the sensor signal cable, corrosion of the Liquiphant fork, defective sensor electronics or input circuit of the Nivotester. Function monitoring can be checked at the terminals of the signal cable.

3 Design and Installation The Nivotester limit switch must be installed in a control cabinet outside the explosion-hazardous area. The Minipac transmitters are designed for single or row mounting on a standard EN x7.5 or EN x15 symmetrical rail. Note the permissible ambient temperatures and the minimum distance allowed between rows of instruments (see Technical Data). Above: Row mounting on standard rail of the only 50 mm wide Nivotester limit switches A protective housing (IP 55) is available for two Nivotester transmitters mounted in the open. Please refer to Supplementary Documentation. Below: Two Nivotesters in one protective housing Electrical Connection Connecting the limit switch Nivotester ( * DC transmitters in preparation) Select the fail-safe mode by inserting or removing the jumper at terminals 12 and 13. For easy wiring, the removable terminal blocks are separated according to whether they are intrinsically safe connections (upper) or non-intrinsically safe connections (lower). Connecting the Sensor (to the upper terminal block) The two-core connection cable between the Nivotester and the Liquiphant or Soliphant sensor can be common, unshielded installation cable or two cores of a multicore cable. Cable resistance max. 25 Ω per core. Without jumper minimum fail-safe With jumper maximum fail-safe U~ or U _ * L1 N Nivotester L1 N PE L+ L _ Power supply Liquiphant or Soliphant Level alarm Non-Ex The cable should be shielded if it is to be laid in areas with strong electromagnetic interference, such as that caused by machines or walkie-talkies. Connect the shielding to the ground connection in the sensor only. Do not connect it to the Nivotester. Explosion-Hazardous Areas: Please observe all local regulations on explosion protection concerning the type and installation of intrinsically safe signal cabling. Please refer to the certificate of conformity for maximum permissible values of capacitance and inductance. Connecting the Signal and Control Systems (to the lower terminal block) Note relay function with regard to level and fail-safe mode. If an instrument with a high inductance is connected (for example, contactor, magnetic valve, etc.), then a spark arrester must be provided to protect the relay contact. Connecting the Power Supply (to the lower terminal block) See Order Code. A fine-wire fuse is not requi as there is a fuse in the power supply circuit. The DC version of the Nivotester has protection against reverse polarity.

4 Replacing the Instrument FTL 120 Z L1 N NO or NC Replacing the Previous FTL 120 Z Version with the Latest Nivotester Please note: The signal cable connection, fail-safe mode and the power supply connection are identical on both instruments. L1 N PE Power supply L1 N Normally-open or normally-closed contact The jumper between terminals 3 and 4 must be removed. The relay contact between terminals 5 and 6 on the FTL 120 Z can be connected as a NO or a NC contact. With the, this part of the change-over contact performs as a normally closed contact. (Quiescent current fail-safe mode: this contact is closed in cases of level alarm and fault.) Change the wiring if necessary! L1 N PE Please also note the information given in the approval certificates. The wiring of the lower terminal block must be modified Power supply change-over contact Technical Data Construction Housing: row housing (Minipac) in plastic Mounting: on standard rail to EN x7.5 or EN x15 Protection to DIN 40050: Housing IP 40, terminals IP 20 Weight: 11.3 oz. (320 g) Operating Data Permissible ambient temperatures single mounting: Nominal operating range: 32 to 140 F (0 to +60 C) Limits of operating range: -4 to 140 F ( _ 20 to +60 C) with row mounting without side spacing: Nominal operating range: 32 to 122 F (0 to +50 C) Limits of operating range: -4 to 122 F ( _ 20 to +50 C) mounted in protective housing (2 units): Nominal operating range: 32 to 104 F (0 to +40 C) Limit of operating range: -4 to 104 F ( _ 20 to +40 C) Storage: -13 to 185 F ( _ 25 to +85 C) Climatic operating class to DIN 40040: K U E Temperature range: 32 to 158 F (0 to +70 C) relative air humidity: annual mean max. 75% for 30 days continuously in the year max. 95% for other days occasionally 85% infrequent and light dew Interference-proof against electromagnetic fields: 10 V/m, 10 khz to 1 GHz, conf. to IEC DIN VDE 0843 (Part 3), EN and NAMUR recommendations Interference source below that stated in EN standards Power supply AC version: Voltage ranges see Order Code Power consumption max. 3 W DC version: Voltage range: 20 to 30 V Permissible residual ripple within tolerance: U pp = 2 V Current consumption: max. 56 ma Power consumption : max. 1.7 W Integrated fine-wire fuse (with protection against reverse polarity) Signal Input Input : electrically isolated from power supply and output Sensors: Liquiphant DL 17 Z, FDL 30, FDL 31, FDL 35, FDL 36, Soliphant DM 90 Z, DM 91 Z, DM 92 Z Power supply to sensor: supplied by the Nivotester Connecting cable: two-core, shielding not requi, Cable resistance: max. 25 Ω per core Signal transmission: Pulse Frequency Modulation (PFM) See approval certificates for further specifications.

5 Output Relay output: one potential-free change-over contact for level alarm Quiescent current fail-safe mode: Minimum/maximum fail-safe mode, selectable by jumper on the terminal block Switching delay: approx. 0.5 s Switching capacity of relay contacts: U~ max. 250 V I~ max. 6 A P~ max VA at cos ϕ =1 P~ max. 750 VA at cos ϕ 0.7 U _ max. 250 V I _ max. 6 A P _ max. 200 W Operating life: min switchings with max. contact load Function indicators: three LEDs for operation, level alarm and fault Dimensions Dimensions of the Nivotester in Minipac format. Housing width: 2 in. (50 mm). 100 mm = 3.94 in 1 in = 25.4 mm 4.4 in. (113) [4.8 in. (121)] 4.4 in. (111) Mounting See diagram on left. 1 Row mounting on standard rail 1.4 in. x 0.3 in. or 1.4 in. x 0.6 in. (35 mm x 7.5 mm or 35 mm x 15 mm) 2 Minimum spacing between next row of instruments above and below: min. 2 in. (50 mm) when sensor used in explosion-hazardous area, min. 1 in. (25 mm) when used otherwise. Order Code Limit switch Nivotester Certificate, Approval R Standard, no special approval G [EEx ia] IIC (CENELEC) O IS Class I, II, III, Div. I, Groups A, B, C, D, E, F, G (FM) 2 Version 0 Minipac housing 3 Power supply A AC 180 to 253 V, 50/60 Hz B AC 90 to 140 V, 50/60 Hz C AC 38 to 52 V, 50/60 Hz D AC 21 to 27 V, 50/60 Hz E DC 20 to 30 V, in preparation 4 Output 1 Potential-free change-over contact

6 Supplementary Documentation Liquiphant FDL 30, FDL 31, FDL 35, FDL 36, Sensors for limit detection in liquids Technical Information 185F/24/ae United States Canada Mexico Regional Office 2350 Endress Place Greenwood, IN Kenrick, Ste. B-14 Phone: (317) Houston, TX Phone: (281) FAX: (317) FAX: (281) Fogarty Engineering Sterling IPC Sales Company Div. of Div. of Powell Road P.O. Box 901 P.O. Box 604 Harvey, LA Romeo, MI Phone: (504) Phone: (810) FAX: (504) FAX: (810) Canada, Ltd. Canada, Ltd Graham s Lane th Street, #100 Unit 1, Burlington Edmonton, AB T5S 1R5 ON, L7S 1W3 Phone: (403) Phone: (905) FAX: (403) FAX: (905) Canada Ltée 6800 Côte de Liesse, Ste. 100 St. Laurent, Que H4T 2A7 Téléphone: (514) Télécopieur: (514) Calle Camino Sta. Teresa 1384 C.P Mexico D.F. Phone: (525) FAX: (525) TI 203 F/24/ae/10.95 Printed in U.S.A.

Level Limit Switch nivotester FTL 370, FTL 372

Level Limit Switch nivotester FTL 370, FTL 372 Technical Information TI 98F/00/en Limit Switch nivotester FTL 370, FTL 37 With intrinsically-safe signal circuits for connection to sensors Liquiphant, Nivopuls, Soliphant. Features at a Glance High operational

More information

Level Limit Switch nivotester FTL 325 P

Level Limit Switch nivotester FTL 325 P Technical Information TI 350F/24/ae Level Limit Switch nivotester FTL 325 P With intrinsically safe signal circuit for connection to the Liquiphant and Soliphant measuring sensor Application Level limit

More information

Temperature transmitter itemp RTD DIN rail TMT 127

Temperature transmitter itemp RTD DIN rail TMT 127 Technical information TI 095R/24/ae Nr. 510 06165 Temperature transmitter itemp RTD DIN rail TMT 127 Pt100 transmitter for an economical, high accuracy temperature monitoring. Fixed range measurement,

More information

Level Limit Measuring System liquiphant M/S with FEL 56 + nivotester FTL 325 N

Level Limit Measuring System liquiphant M/S with FEL 56 + nivotester FTL 325 N T T Safety Manual SD 168F/00/en/10.03 52018928 Level Limit Measuring System liquiphant M/S with FEL 56 + nivotester FTL 325 N Functional safety manual [Ex ia] [Ex ia] FTL 325 N FTL 325 N CH2 CH3 CH2 CH3

More information

Level Measurement silometer FMX 570

Level Measurement silometer FMX 570 Technical Information TI 01F/00/en Level Measurement silometer FMX 570 Measurement of liquids and bulk solids Suitable for explosion hazardous areas For use with capacitance and hydrostatic probes The

More information

Soliphant T FTM20, FTM21

Soliphant T FTM20, FTM21 Technical Information Soliphant T FTM20, FTM21 Level limit switch Robust vibration limit switch for bulk solids, also for dust incendive hazardous areas Application Soliphant T is a robust level limit

More information

Technical Information Nivector FTC968, FTC968Z

Technical Information Nivector FTC968, FTC968Z TI0007F/00/EN/7.6 7494 Products Solutions Services Technical Information Nivector FTC968, FTC968Z Capacitance Point level switch for powder and fine-grained bulk solids Application The Nivector is a small-sized

More information

Radar Level Measurement micropilot FMR 130 for stilling wells

Radar Level Measurement micropilot FMR 130 for stilling wells Technical Information TI 258F/24/ae Radar Level Measurement micropilot FMR 130 for stilling wells Smart transmitter for non-contact measurement in metallic by-pass pipes and stilling wells Suitable for

More information

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50 Technical Information Nivotester 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50 Area of application The Nivotester is suitable as a 1-channel switch amplifier for the Soliwave

More information

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the Soliwave M microwave barrier

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the Soliwave M microwave barrier Technical Information Nivotester FTR325 1-channel switch amplifier for the Soliwave M microwave barrier Area of application The Nivotester FTR325 is suitable as a 1-channel switch amplifier for the Soliwave

More information

Liquiphant M/S with electronic insert FEL57 + Nivotester FTL325P

Liquiphant M/S with electronic insert FEL57 + Nivotester FTL325P T T Functional safety manual Liquiphant M/S with electronic insert FEL57 + Nivotester FTL325P Level Limit Measuring System [Ex ia] FTL325P [Ex ia] FTL325P Application Overfill protection or operating maximum

More information

Operating Instructions

Operating Instructions Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description

More information

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC Switch Amplifier Features Assembly -channel isolated barrier 30 V AC supply Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL acc. to IEC

More information

Temperature Transmitter itemp RTD DIN rail TMT 127

Temperature Transmitter itemp RTD DIN rail TMT 127 Technical Information TI 095R/09/en No. 51004790 Temperature Transmitter itemp RTD DIN rail TMT 127 Temperature Transmitter for Pt100 Resistance Thermometer Application Temperature transmitter with fixed

More information

â itemp Pt100 TMT127 Technical information Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring

â itemp Pt100 TMT127 Technical information Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring Technical information itemp Pt100 TMT127 Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring Application Temperature transmitter with fixed measuring range for converting a

More information

Temperature Transmitters TMT 136, TMT 137

Temperature Transmitters TMT 136, TMT 137 Technical Information TI 066R/09/en Part No. 51000855 Temperature Transmitters TMT 136, TMT 137 For Pt100 Resistance Thermometers 2-wire head transmitter Standard- and instrinsically safe versions Head

More information

Temperature transmitter itemp PCP DIN rail TMT 121

Temperature transmitter itemp PCP DIN rail TMT 121 Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

Data Sheet KFD2-UFC-EX1.D. Supplied by. .com. Call us on +44 (0)

Data Sheet KFD2-UFC-EX1.D. Supplied by. .com. Call us on +44 (0) Data Sheet KFD-UFC-EX1.D Supplied by.com Call us on +44 (0)118 916 940 Email info@47able.com Frequency Converter with Trip Values Features Assembly 1-channel isolated barrier 4 V DC supply (Power Rail)

More information

KSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays

KSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays KSR-Level sensor KSR-Schwimmer-Magnetschalter 1001-5 KSR Contact Protection s 1 KSR Contact Protection Type KR230-Ex and KR24-Ex General Description The contact protection relays KR230-Ex and KR24-Ex transmit

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/ 3 Ex i Isolators Switching Repeater with Power Relay Intrinsically safe input [Ex ia] IIC Galvanic isolation between input, output and power supply Open-circuit / short-circuit monitoring and messaging

More information

Technical Information Barrier RB223

Technical Information Barrier RB223 TI00132R/09/EN/13.14 71275790 Products Solutions Services Technical Information Barrier RB223 One or two-channel barrier Loop-powered barrier for the safe separation of 4 to 20 ma standard signal circuits

More information

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched

More information

Isolators A3/1. Vibration Transducer Supply Unit Series

Isolators A3/1. Vibration Transducer Supply Unit Series > For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic

More information

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/. Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

Inductive sensor slot-type SI2-K08-AP7

Inductive sensor slot-type SI2-K08-AP7 SI2-K08-AP7 Slot sensor, height 8 mm Plastic, polypropylene Mechanical end stop, removable, for analog pointer instruments 3-wire DC, 10 30 VDC NO contact, PNP output Cable connection Wiring diagram Type

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

RMA42. Technical Information

RMA42. Technical Information Technical Information RMA42 Process transmitter with control unit Digital process transmitter for mounting on a top-hat rail for monitoring and visualizing analog measured values Application Plant and

More information

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5. Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

Binary Output Series 9175

Binary Output Series 9175 Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use

More information

Hydrostatic Level Measurement silometer FMB 672 Z, FMB 677 Z

Hydrostatic Level Measurement silometer FMB 672 Z, FMB 677 Z Technical Information TI 065F/00/en Hydrostatic Level Measurement silometer FMB 672 Z, FMB 677 Z Commutec transmitters for level measurement of liquids, pastes and sludge Certified for use in explosion

More information

SINEAX B 811 Power Pack with additional Functions

SINEAX B 811 Power Pack with additional Functions SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers

More information

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator SINEAX TI 807 without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically

More information

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 2 Safety Barriers Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Broad product range for all standard applications in the world of automation Flexible and space saving Time

More information

Single-Channel Safety Barriers Series 9001

Single-Channel Safety Barriers Series 9001 Single-Channel Safety Barriers Series 9001 > Broad product range for all standard applications in the world of automation > Flexible and space saving single and dual channel versions available > Time saving

More information

SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically insulate

More information

SALES SERVICE +358 (0)

SALES SERVICE +358 (0) SALES SERVICE +358 (0)17 262 3555 info@econosto.fi ADCATROL ELECTRO-PNEUMATIC POSITIONERS PE 986 (ATEX) DESCRIPTION The ADCATROL PE986 positioner requires an input signal of 4 20 ma for proportional control

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction VEGASEL 643 6 5 + + 3 5 + + max. min. on VEGASEL 643 5 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 1 Product description 1.1 Function

More information

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN Indicator and alarm signalling unit 10/30-2.10 EN Dimensions 36 mm x 144 mm Can either stand vertically or lie horizontally Comprehensively explosion-protected Robust moving-coil system Contactless alarm

More information

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No 9165/16-11-10s 207909 Compact one- and two-channel Ex i output isolating repeater wire-breakage and short-circuit monitoring system, which can be disconnected and features a signalling contact can be used

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. appmeas.co.uk +44 (0)

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. appmeas.co.uk +44 (0) DMP 4 Industrial Pressure Transmitter Without Media Isolation accuracy according to IEC 60770: 0.5 % FSO Nominal pressure from 0... 0 mbar up to 0... 000 mbar Product characteristics excellent linearity

More information

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition Converter Connection 1-channel EEx ia IIC for 4-wire and 6-wire bridges Analogue output 0/4 ma... 20 ma or 4mA...-12mA Full bridge load cells and strain gauges circuit for resistance bridges up to 17 Ω

More information

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs SINEAX V 6 for rail mounting in housing P/7 or P/7 St 00 II () GD Application SINEAX V 6 (Figs. and ) is designed for measuring temperature in combination with thermocouples or resistance thermometers.

More information

Temperature head transmitter itemp TC TMT 188

Temperature head transmitter itemp TC TMT 188 Technical information TI 077R/24/ae No.: 510 06145 Temperature head transmitter itemp TC TMT 188 Universal head transmitter for thermocouples for an economical, high accuracy temperature monitoring. Fixed

More information

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series > Intrinsically safe output [Ex ib] IIC/IIB > Stable output voltage > Galvanic isolation between output and power supply > Power supply or 85... 230 V AC > Compact design www.stahl.de 07673E00 Basic function:

More information

SINEAX / EURAX 2I1 Passive DC signal isolator

SINEAX / EURAX 2I1 Passive DC signal isolator SINEAX / EURAX I without power supply 0 II () G resp. II () G Application The DC signal isolator SINEAX/EURAX I (Figs. and ) serve to isolate load-independent DC current signals. It suppressed noise voltages

More information

DS 400 DS 400. Intelligent Electronic Pressure Switch Completely in Stainless Steel. piezoresistive stainless steel sensor

DS 400 DS 400. Intelligent Electronic Pressure Switch Completely in Stainless Steel. piezoresistive stainless steel sensor GmbH Postal address: House address Fon (+49) 0 22 42-870-0 Postbox 26 Löhestr. 7 Fax (+49) 0 22 42-870-20 http: // www.tematec.de 5759 Hennef 577 Hennef e-mail: team@tematec.de Data Sheet Page /5 Intelligent

More information

Safety Instructions Nivotester FTC625, FTC325

Safety Instructions Nivotester FTC625, FTC325 XA01351F-A/00/EN/01.14 71273077 Products Solutions Services Safety Instructions FTC625, FTC325 [Ex ia Ga] IIC/IIB TÜV 13.0903 X Segurança TÜV INMETRO OCP 0004 Document: XA01351F-A Safety instructions for

More information

Resistance thermometer Model TR30, compact design

Resistance thermometer Model TR30, compact design Electrical temperature measurement Resistance thermometer Model TR30, compact design WIKA data sheet TE 60.30 Applications Machine building, plant and vessel construction Propulsion technology, hydraulics

More information

TT2780. Temperature head transmitter For resistance thermometers Pt100, settable using a PC, for installation in a sensor head Form B, BUZ, BUZ-H

TT2780. Temperature head transmitter For resistance thermometers Pt100, settable using a PC, for installation in a sensor head Form B, BUZ, BUZ-H Postal address: House address Fon (+49) 0 22 42-8703-0 Postbox 1261 Löhestr. 37 Fax (+49) 0 22 42-8703-20 http: // www.tematec.de 53759 Hennef 53773 Hennef e-mail: team@tematec.de TT2780 Data Sheet TT2780

More information

SINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar

SINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar For electrically insulating, amplifying and converting DC signals 0102 II (1) G Application The purpose of the isolating amplifi er SINEAX TV 808 (Fig. 1 and 2) is to electrically insulate input and output

More information

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation

More information

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0.35 % FSO. Nominal pressure

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0.35 % FSO. Nominal pressure DMP 4 Industrial Pressure Transmitter Without Media Isolation accuracy according to IEC 60770: 0.5 % FSO Nominal pressure from 0... 0 mbar up to 0... 000 mbar Product characteristics excellent linearity

More information

itemp HART DIN rail TMT112

itemp HART DIN rail TMT112 Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application

More information

System Components Liquiphant M (NAMUR)/PROFIBUS-PA interface FXA 164

System Components Liquiphant M (NAMUR)/PROFIBUS-PA interface FXA 164 Technical Information TI 343F/00/en Operating Instructions 52004947 System Components Liquiphant M (NAMUR)/PROFIBUS-PA interface FXA 164 With intrinsically safe signal circuits for the connection of up

More information

Level Limit Measuring System liquiphant M/S with electronic insert FEL 52

Level Limit Measuring System liquiphant M/S with electronic insert FEL 52 Safety Manual SD 163F/00/en/10.03 52018425 Level Limit Measuring System liquiphant M/S with electronic insert FEL 52 Functional safety manual Application Overfill protection or operating maximum detection

More information

Temperature head transmitter itemp PCP TMT 181

Temperature head transmitter itemp PCP TMT 181 Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

Technical Information itemp TMT180

Technical Information itemp TMT180 TI00088R/09/EN/14.16 71315611 Technical Information itemp TMT180 Temperature head transmitter for resistance thermometers Pt100 Configurable using a PC, for installation in a terminal head, form B Application

More information

Technical Information RMA42

Technical Information RMA42 TI00150R/09/EN/05.16 71315973 Products Solutions Services Technical Information RMA42 Process transmitter with control unit Digital process transmitter for monitoring and visualizing analog measured values

More information

Contrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN

Contrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN Contrans T TEU 471, TEU 471-Ex Intelligent four-wire temperature transmitters Input/sensor connection: Resistance thermometers (2-, 3-, 4-wire circuit) Thermocouples (without, with internal/external reference

More information

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for

More information

Head mounted Temperature Transmitter TF02/TF02-Ex

Head mounted Temperature Transmitter TF02/TF02-Ex Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance

More information

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting Electrical Temperature Measurement Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting WIKA Data Sheet TE 12.03

More information

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet 2CDC 251 121 F0004 1 5 2 4 3 6 Characteristics Single-function impulse-off timer One device includes 10 time ranges, from 0.05 s to 300 h, for the adjustment of the pulse time Remote potentiometer connection

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant

More information

Conductivity measurement SmarTec S CLD 132

Conductivity measurement SmarTec S CLD 132 Technical Information TI 207C/24/ae Conductivity measurement SmarTec S CLD 132 Transmitter for measurement of conductivity and concentration with inductive sensor Areas of application Alkali/acid concentration

More information

Process display RIA 261

Process display RIA 261 Technical Information TI 083R/24/ae Process display RIA 261 Digital loop powered field display for 4 to 20 ma current loops Features and Benefits Loop powered display, no additional power supply cable

More information

LST100 Ultrasonic level transmitter for upstream oil and gas

LST100 Ultrasonic level transmitter for upstream oil and gas Data sheet DS/LST100-EN LST100 Ultrasonic level transmitter for upstream oil and gas Accurately track and measure the most expensive consumable on your site chemicals. Measurement made easy Features Keep

More information

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs Plug-in module, or channels Application The programmable transmitter (Fig. ) is designed for measuring temperature in combination with thermocouples or resistance thermometers. Thermocouple non-linearities

More information

Electronic timer CT-TGD.22

Electronic timer CT-TGD.22 2CDC 251 097 F0t06 a Rotary switch for the preselection of the time range of the ON time b Potentiometer with direct reading scale for the fine adjustment of the ON time c Rotary switch for the preselection

More information

Digital Input Output Module for Zone 2 Series 9470/33

Digital Input Output Module for Zone 2 Series 9470/33 www.stahl.de > 16 channels can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8

More information

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22 www.stahl.de > 16 channels for contacts and NAMUR proximity switches (EN 60947-5-6) > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

Level and Pressure. Product Information. Vibrating level switches

Level and Pressure. Product Information. Vibrating level switches Level and Pressure Product Information Vibrating level switches Contents Contents 1 Product description 1.1 VEGAVIB... 3 1.2 VEGASWING... 3 2 Function and application 2.1 Functional principle... 5 2.2

More information

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out.

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out. Technical Data Sheet Theta 60R 60 R 60 R Fig. Theta R, channel version, in housing S7 clipped on to a top - hat rail. Fig. Theta R, channel version, in housing S7 hole mounting brackets pulled out. Theta

More information

ph / ORP Measurement mypro CPM 431

ph / ORP Measurement mypro CPM 431 Technical Information TI 173C/24/ae ph / ORP Measurement mypro CPM 431 Two-wire transmitter for ph and ORP with HART communication for use in hazardous or non-hazardous areas Areas of application The analysis

More information

KINAX WT 707 Transmitter for angular position

KINAX WT 707 Transmitter for angular position Ruggedized version pplication The KINX WT 707 (Figs. 1 to 6) converts the angular position of a shaft into a load-independent direct current signal, proportional to the angular position. The unit is contact

More information

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting Electrical Temperature Measurement Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting WIKA Data Sheet TE 24.01 Applications T Machinery, plant construction T Process industry

More information

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/ > 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35 www.stahl.de > 16 channels can be adjusted in pairs as digital inputs or outputs > Suitable for NAMUR proximity switches, 3-wire PNP proximity switches, contacts and solenoid valves (24 V / 0.5 A). > Up

More information

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact Data sheet Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact The CT-TGD.12 is an electronic time relay with the function pulse generator. It is from the CT-D range. With their MDRC profile

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

Analog Universal Module HART for Zone 2 Series 9468/33

Analog Universal Module HART for Zone 2 Series 9468/33 > 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on

More information

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet 1SVR 430 103 F0200 CT-ERS 1 7 2 6 5 4 8 3 1 10 selectable time ranges, from 0.05 s to 300 h 2 Potentiometer with direct reading scale for the fine adjustment of the time delay 3 Sliding switch to set the

More information

Binary Output without Power Supply Series 9176

Binary Output without Power Supply Series 9176 Binary Output without Power Supply Series 9176 > For intrinsically safe operation of Ex i solenoid valves, indicators and horns > Power supply by control circuit, loop powered > Intrinsically safe output

More information

TR 104, TR 104-Ex Rail mounted Temperature Transmitters

TR 104, TR 104-Ex Rail mounted Temperature Transmitters Data Sheet 10/-8.48-EN Rev. A TR 104, TR 104-Ex Rail mounted Temperature Transmitters Analog, Pt 100 (RTD), fixed measuring ranges Input Resistance thermometer (two-wire and three-wire circuit) Optionally

More information

Positioner with HART Communication Type 3780

Positioner with HART Communication Type 3780 Positioner with HART Communication Type 780 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Supplied with an electric input signal from to 20 ma Travels

More information

Process Protection Acoustic sensors for pump monitoring

Process Protection Acoustic sensors for pump monitoring coustic sensors for pump monitoring acoustic diagnostic unit Overview The acoustic diagnostic unit acoustically measures the structure-borne noise In the version for pump monitoring; on oscillating displacement

More information

SITRANS F flowmeters SITRANS F US. SONOFLO SONO 3000 transmitter. 4/152 Siemens FI Overview

SITRANS F flowmeters SITRANS F US. SONOFLO SONO 3000 transmitter. 4/152 Siemens FI Overview Overview Design The transmitter is available in different enclosure to fit any demands: IP67 enclosure for compact or wall mounting IP00 as a 19 insert IP65 for wall mounting IP65 enclosure in stainless

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 Applications Machine building, plant and vessel construction Propulsion

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Single-Channel Safety Barriers with Electronic Current Limitation > Broad product range for all standard applications in the world of automation > Flexible and space saving > Time saving installation due

More information

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description RAD-IN/OUT-D Digital extension modules for the bidirectional wireless system INTERFACE Data sheet 102122_en_0 PHOENIX CONTACT 2010-02-2 1 Description The RAD-ISM-...-SET-BD-BUS-ANT bidirectional wireless

More information

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction VEGAVIB and signal conditioning instruments Contents Contents Safety information... 1 Product description 1.1 Function and configuration... 3 1. Types and versions...

More information