Chapter Seven. Under Ground Cables

Size: px
Start display at page:

Download "Chapter Seven. Under Ground Cables"

Transcription

1 Chapter Seven Under Ground Cables Construction of cables In the fig (7.1)below, shows the general construction of (3-condctor) cable The various part of cable are : 1- Core or conductor A cable may have one or more than one core (conductor) depending upon the type of service for which it is intended. For instance, the 3- conductor cable shown in the fig. (7.1) is used for service. The conductors are made of tinned copper or aluminum an are usually stranded in order to provide flexibility to the cable.

2 2- insulation Each core or conductor is provide with a suitable thickness of insulator, the thickness of layer depending upon the voltage To be with stood by the cable. The commonly used materials for insulation are impregnated paper, varnished cambric or rubber mineral compound. 3- Metallic sheath. In order to protect the cable from moisture, gases or other damaging liquids (acids or alkalis) in the soil and atmosphere, a metallic sheath of lead or aluminum is provided over the insulation as shown in the fig. (7.1) 4- Bedding Over the metallic sheath is applied a layer of bedding which consists of a fibrous material like jute or hessian tape. The purpose of bedding is to protect the metallic a against corrosion of bedding is to protect the metallic against corrosion and from mechanical in jury due to armoring. 5- Armouring : Over the bedding armaouring is provide which consists of one or two layers of galvanized steel wire or steel tape. Its purpose is to protect the cable from mechanical injury while laying it and during the course of handling. Armouring may not be done in the case of some cable. 6- Serving :. In order to protect armouring from atmospheric condition. Layer of fibrous material (like jute) similar to bedding is providing over the armouring. This is known as serving. It may not be out of place to mention here that bedding, armouring and serving are only applied to the cable for protection of conductor insulation and to protect the metallic sheath from mechanical in jury.

3

4 Under Ground Cable The most materials that used for made the insulator of cable is the paper that saturate by oil like manila hemp or wood pulp or Ray. Also there is another impotent materials that used for made the insulator which is P.V.C. ( poly ving chloride). The fig. (7.2) represent a cross- section For a single core cable where r is the radius of the conductor R is the radius of the cable or ( the inside radius of the sheath) (q) represent the charge on the Surface of the conductor for Each on mater from the length Of the cable. is the electric flux density at aradius X meter from the center of the cable ( for one mater of the length of conductor) r R Fig. (7-2) Coulomb/ (1)

5 The electric field intensity or voltage gradient or electric stress at the same distance X is Volt / meter (2) Where o is the relative permittivity of free space ( o= and is the relative permittivit of insulator. V is the voltage difference between the conductor and sheath. Volt (3) The capacity for each meter of the length of single core cable is ( one meter of length of conductor ) F/m (4) MF/m (5)

6 Electric stress in single core cable :. The direction of the electric field in the insulator will be radial and the value of its will as follow : Where q is the charge Of the cable and Of the cable. As shown in eq.(2) at a distance x v/cm at a distance X (6) The maximum electric stress will be at the surface of the conductor (at x=r) v/cm (7)

7 The minimum electric stress will at the inside surface of the sheath of the cable (at X= R ) V/cm (8) Also * In the case of the stranded conductor. The electric stress will be increase by 15 %, 25% from the value of the smooth conductor. *If the value of the voltage V and the inside radius of the sheath R are constant and r is variable where ( r is the radius of the conductor of the cable ) *Most economical conductor size in the cable The minimum value of the electric stress on the surface of the conductor ( will be when is amaximum value. Now Assume The maximum value will be when

8 The grading of cables :. The grading of the cable is redistribution the electric stress on the insulator where the value of the electric stress will be increase at the outside layer of insulator and it is value will be remain constant at the surface of the conductor as before the grading. Also by this method we can reduce the thickness of the insulator. There are two method for grading the cable 1-Capacitive grading :. By using a different insulator layers have a different relative permittivity. 2-Metallic inter sheath grading :. By using the same insulator material for the different insulating layers and separate these layers by a metallic inter sheath in order to control the voltage across the insulator. Capacitive grading R Where is the maximum electric stress of the cable of the first layer is the minimum electric stress of the first layer

9 is the maximum electric stress of the second lager is the minimum electric stress of the second lager is the maximum electric Stress of the third layer is the minimum electric Stress of the third layer and for the cable

10 Ex1) single core cable covered by the lead and design for 66 kv. If the radius of the conductor is 0.5 cm and the insulator consists of three layers have a relative permittivity of 5,4,3 respectively and the electric stresses on these layers are 40,30,20 kv/cm respectively. Find inside of the sheath of the cable. So1) v r R Also

11

12 Ex2) 66 kv single core cable covered by the lead the radius of it's conductor is 0.5cm. The insulating materials consists of two layers the thickness of each layers is 1.5cm. The relative permittivity of inside layers is 3 and for the outside layer is 2.5 calculate the electric stress at the surface of the conductor. So1) r R

13 *Inter sheath grading In this method the insulator of the cable is consists of two layers or more than two layers from the same material and spate each of two next layers by a screen or metallic inter sheath has a cylindrical shape and the inter sheaths are connected to tapping from the supply transform where the voltage across these sheath make the layers of the insulator take each it's voltage from the total voltage. r V O Supply Transformer

14 Ex3) A single core cable covered by the lead and design for 100 kv. The radius of it's conductor is 1 cm the inside radius of the outside sheath is 4 cm. If an metallic inter sheath is placed at a radius 2.5 cm and connected to supply transformer through an switch. The relative permittivity of the insulator is 3.5. Find :. 1-The maximum electric stress of the cable and the voltage of the inter sheath to the surface of the conductor when this inter sheath is not connected to supply transformer ( the switch is open ) 2-When the switch is closed, find the electric stress on the surface of the conductor and on the two sides of the inter sheath when the voltage of the inter sheath to the conductor surface is 44 kv. Also find the voltage of the transformer. 3-Compare the cable in (2) which is a grading cable with section (1) which is not grading cable. So1) R r Supply Transformer

15 2) when the switch closed ( the voltage between surface of conductor and the inter sheath ) The electric stress at the inside surface of metallic inter sheath The electric stress at the outside of the inter sheath Where 3) Comparing The using of inter sheath grading cause a reduction in the maximum electric stress by

16 In the case of not grading cable in section (1), and order to reduce this max. electric stress to the value of grading cable without using metallic inter sheath grading with same cable :. We must increase the radius of cable in other words increase the distance of insulator as follow :. We must increase the thickness of insulator by 4.03 cm in order to get the same maximum electric stress of grading cable without using metallic inter sheath grading. Ex4) A single core cable covered by the lead and design for 120 kv and 50 HZ. The radius of it's conductor is 1cm and the inside radius of the outside sheath is 4.2cm. An metallic inter sheath of radius 2 cm is used for grading the cable. The relative permittivity of the insulator is 3.8. the length of the cable is 6.4 km. find :. 1-The capacity of each of the two layers that have the same insulator materials. 2-The overall efficiency 3-The maximum electric stress when the inter sheath is not connected to the supply to the supply transformer. 4-The voltage of the inter sheath to the surface of the conductor in order to keep the electric stress on the surface of the conductor at 55 kv/cm (the inter sheath is connected to supply transformer) 5-The charging current.

17 So1) R r 2) OR

18 3) 4) Not grading grading 5)

19 -- Optimal or best location of the inter sheath inside the cable If we have a cable having a two metallic inter sheath as shown in the fig. below:. And in order to get the Optimal or best location Of the inter sheath, we Must put R r O V

20 - The maximum and minimum electric stress of cable with optimal location of metallic inter sheath In order to make the maximum electric stress at the surface of conductor and the minimum electric stress at the inside surface of the sheath of cable we must put:.

21 Also Kv/cm For 3 layer 2 metallic inter sheath Kv/cm For 3 layers 2 metallic inter sheath

22 As before For the same distance of grading cable, we have un grading cable has the same distance of grading cable un Or... We see that if the voltage across the cable is constant and the volume (distance (r,r)) is constant the grading cable by the inter sheath grading cause a reduction in the value of maximum electric stress by...

23 Also in other sides For the same value of maximum electric stress and with remain the distance of cable constant (r,r) we can increase the voltage across the cable due to the inter sheath grading of cable. We see that if the voltage across the cable is constant and the volume (distance (r,r) ) is constant. The grading cable by the inter sheath grading cause a reduction in the value of maximum electric stress by -- Also in other side :. For the same value of maximum electric stress and with remain the distance of cable (r. R) constant, we can increase the voltage across the cable by due to the inter sheath grading of cable.

24 *Note When there is one metallic inter sheath R r Kv/ cm Also

25

26 Ex5) 33kv single core cable has a conductor diameter of 2.5cm and the diameter of the inside sheath of the cable is 6 cm. It is design to reduce the maximum electric stress by using a two metallic inter sheath. Determine the best position of the inter sheath and the reduction in electric stress. So1) Best position of inter sheath means = The reduction is

27 Ex6) single core cable of 66kv has a radius of conductor of 1cm. The radius of the cable is 6 cm. The insulator consists of one layer. If a two metallic inter sheath is placed into the insulator and connected to supply transformers through an switches. If the radius of first metallic inter sheath is 2.5cm, and the radius of second metallic inter sheath is 4 cm. 1-When the switches are open. Find the voltage between the first and second metallic inter sheath. 2- When the switches are closed and the voltage of first transformer is 30kv and the voltage of second transformer is 20 kv. Find the electric stress at the inside surface of second metallic inter sheath, also find the min. electric stress of cable. So1) 1) R r V

28 2) The voltage between the firs And second metallic inter sheath the voltage of the first transformer The voltage of the second transformer In order to find the min. electric stress of cable electric stress of cable is

29 Or in other way (1)

30 Ex7) find the most economical conductor diameter of single core cable to be used on 132 kv, also, find the overall diameter of insulator if the permissible stress is not to exceed. So1) For most economical conductor diameter The value of operating voltage per phase The diameter of the cable is

31 Resistance of cable :. R Where is the resistivity of insulator r L R is the length of cable is the radius of cable is the radius of conductor Ex8) single core cable of 33kv, consist of two layers of insulators, each of its have a relative permittivity of 5,3 respectively. If a metallic inter sheath is placed between the layers and connected to supply transformer through an switch. If the ratio of electric stress at the outside surface of metallic inter sheath to the electric tress at the inside surface of sheath of cable is. The radius of the conductor is 1.5 cm and the radius of the cable is 7cm. when the switch is open 1-Find the voltage between metallic inter sheath and the sheath of cable. 2-The electric stress at the inside surface of metallic inter sheath 3-Min electric stress of cable of cable

32 So1) R r 1) 2) 3)

33 EX9) single core cable of 80kv has a radius of conductor of 1cm and the radius of cable is 7cm. his insulator consists of one material. If a two metallic inter sheath is placed into the insulator and connected to the supply transformer through an switches. The radius of first and second metallic inter sheath are 3,5cm respectively and the voltage of transformers are 4 cm So1) 1-When the switches are open find the voltage between the first metallic inter sheath and sheath of cable 2-When the first switch that connected to first transformer is closed and the second switch remain open. Find the voltage between second metallic inter sheath and sheath of cable. R r

34 2) OR 15.73= OR

35 EX10) single core cable of 66kv has a radius of conductor of 1.5cm. The insulator consists of two layer. The thickness of first layer is 2.5 cm and the thickness of second layer is 4cm. Also the relative permittivity of first and second layers are 5,4 respectively. If an metallic inter sheath is placed at a radius of 6cm and connected to supply transformer through an switch when the switch is open find -The voltage between metallic inter sheath and the sheath of cable also find. The electric stress at the outside surface of metallic inter sheath. So1) r

36 1) OR

37 Type of cable fault :. Cables are generally laid directly in the ground or in ducts in the underground distribution system. For this reason, there are little chances of fault in underground cables. However, if a fault does occur, it is difficult to locate and repair the fault because conductors are not visible. Never the less, the following are the fault most likely to occurs in underground cables 1-Open circuit fault 2-Short circuit fault 3-Earth fault. 1-Open circuit fault :. When there is a break in the conductor of a cable, it is called opencircuit fault. The open- circuit fault can be cheeked by a mugger. For this purpose, the three conductors of the 3- core cable at the for end are shorted and earthed. Then resistance between each conductor and earth is measured by a mugger. The mugger will indicate zero resistance in the circuit of the conductor that is not broken. However, if the conductor is broken, the mugger will indicate infinite resistance in its circuit. 2-Short- Circuit fault :. when two conductors of a malt- core cable come in electrical contact with each other due to insulation failure, it is called a short- circuit fault. A gain, we can seek the help of a megger to check the fault. For this purpose the two terminal of the megger are connected to any two conductors. If the megger gives zero reading. It indicates short circuit fault between these conductor the same step is repeated for other conductors taking two at a time.

38 3) Earth fault:. when the conductor of a cable comes in contact with earth it is called earth fault or ground fault. To indentify this fault, one terminal of the mugger is connected to the conductor and the other terminal connected to earth. If the mugger indicates zero reading, it means the conductor is earthed. The same procedure is requited for other conductor of the cable. \ Murray loop lest :. The Murray loop lest is the most common and accurate method of locating earth fault or short- circuit fault in underground cables. i-) Earth fault:. In fig. below : Fig. (7.3)

39 Fig.(7.3) shows the circuit diagram for locating the earth fault by Murray loop test. Here AB is the sound cable and CD is the fault cable; the earth fault occurring at point F. The foe and D of the faulty cable is joined to the for end B of the sound cable through a low resistance link. The variable resistance P and Q are joined to ends A and C respectively and serve as the ratio arms of the Wheatstone bridge. Let R= resistance of the conductor loop up to the fault from the test end X= resistance of the other length of the loop Note that P,Q,R and X are the four arms of the Wheatstone bridge. The resistances P and Q are varied till the galvanometer indicates zero deflection. In the balanced position of the bridge, we have II r is the resistance of each cable, then R+X=2r II L is the length of each cable in meters, then resistance per meter length of cable = Distance of fault point from test end is

40 Thus the position of the fault is located. Note that resistance of the fault is in the battery circuit and not in the bridge circuit. therefore, fault resistance does not a fact the balancing of the bridge However. If the fault resistance is height, the sensitivity of the bridge is reduced. M In the fig. (7.4) below: fig. (7.4) Shows the circuit P diagram for locating the short circuit fault by Murray loop test. A gain P,Q, R and X are the arms circuit and not in the bridge circuit. The bridge in balanced by adjusting the resistance P and Q. In the balanced position of the bridge

41 Thus the position of the fault is located

42 * Capacitance of 3-core cables The capacitance of a cable system is much more important than that of over head line because in cables 1- Conductors are nearer to each other and to the earthed 2- They are separated by a dielectric of permittivity much greater than that of air The fig. (7.5) below shows the system of capacitance in belted cable. fig (7.5) Since potential difference exists between pairs of conductors and between each conductor and sheath. The electrostatic fields are setup in the cable and gives arise to core-core capacitance Cc and conductorearth capacitance Ce as shown in the fig (7.5 ii) The three capacitance Cc are delta connected where's the three capacitance Ce are star connected, the sheath for many the star point as in the fig.( 7.5 iii) In order to find the whole equivalent capacitance of cable we must make the following steps. 1-Convert the three delta core capacitance Cc into star connection Where

43 2- It can be easily show that the equivalent star capacitance is in parallel with the sheath capacitance as shown in the fig.(7-6) below: Fig (7.6) If is the phase voltage then the charging current is

III/IV B.Tech (Regular/Supplementary) DEGREE EXAMINATION

III/IV B.Tech (Regular/Supplementary) DEGREE EXAMINATION Hall Ticket Number: 14EE503 October, 2018 Fifth Semester Time: Three Hours Answer Question No.1 compulsorily. Answer ONE question from each unit. III/IV B.Tech (Regular/Supplementary) DEGREE EXAMINATION

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

Power Cables and their Application

Power Cables and their Application Power Cables and their Application Parti Materials Construction Criteria for Selection Project Planning Laying and Installation Accessories Measuring and Testing Editor: Lothar Heinhold 3rd revised edition,

More information

CUSTOM DESIGN COAXIAL CABLES BY SICAB

CUSTOM DESIGN COAXIAL CABLES BY SICAB CUSTOM DESIGN COAXIAL CABLES BY SICAB. COAX RG 58 C/U Application: Coaxial Cable 50 Ohm For indoor installation as well as in industrial areas in conduits and cable ducts, for transmission of high frequency

More information

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240

More information

Kerman & Kavian Cable Industries ( KCI )

Kerman & Kavian Cable Industries ( KCI ) KCI Kerman & Kavian Cable Industries ( KCI ) KCI Cables for control and instrumentation circuits 150/250 V (300 V) According to of IEC 60092-376 (2003) Electrical installations in ships - Part 376: Kerman

More information

EDS LV WAVEFORM MAINS CABLE RATINGS

EDS LV WAVEFORM MAINS CABLE RATINGS Document Number: EDS 02-0033 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 02-0033 LV WAVEFORM MAINS CABLE RATINGS EPN, LPN, SPN This standard details the technical and practical information required

More information

CORFLEX VFD CORFLEX VFD Part Number: Drive Cable

CORFLEX VFD CORFLEX VFD Part Number: Drive Cable Part Number: Drive Cable Armored Variable Frequency Drive Cable UL Type MC HL, 600V, 90 C rated - LEAD FREE Description 3 conductor with 3 ground wires, continuous corrugated and welded, impervious aluminum

More information

SUBMERSIBLE PUMP CABLES

SUBMERSIBLE PUMP CABLES 12 SUBMERSIBLE PUMP CABLES 1-450 / 750 V Termoplastic rubber, round orflat flexibe cable ACCORDING TO NF C -102 HD 22.4 S2 Water absorption tests: IEC 811.1.3 VDE 0472 Teil 2 NF C -026 HD 505-1-3 s1 Maximum

More information

14 AWG 2 AWG: 600 Volt

14 AWG 2 AWG: 600 Volt INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.70 600V Type MC Metal Clad and Teck-Style Cables Overview Metal Clad Interlocked PVC Outer Jacket Teck-Style PVC Outer Jacket Introduction Polyester Wrap

More information

Question 3.1: The storage battery of a car has an emf of 12 V. If the internal resistance of the battery is 0.4Ω, what is the maximum current that can be drawn from the battery? Emf of the battery, E =

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

Notes 3 Explanatory Information 4-10

Notes 3 Explanatory Information 4-10 Low Voltage Cables Section Three SECTION THREE - LOW VOLTAGE CABLES PAGE Notes 3 Explanatory Information 4-10 Construction 4 Current Ratings 5 Rating Factors 6 Voltage Drops 8 Selection Procedures 10 Minimum

More information

Field Instrument Cable. Electrical Noise

Field Instrument Cable. Electrical Noise Field Instrument Cable Electrical Noise 1 Electrical Noise Instrument Cables are Susceptible to 4 Types of Noise: Static Magnetic Cross-Talk Common Mode 2 Static Noise Static Noise is caused by an electric

More information

Measurement of Resistance and Potentiometers

Measurement of Resistance and Potentiometers Electrical Measurements International Program Department of Electrical Engineering UNIVERSITAS INDONESIA Measurement of Resistance and Potentiometers Jahroo Renardi Lecturer : Ir. Chairul Hudaya, ST, M.Eng.,

More information

A battery of emf 10 V and internal resistance 3 Ω is connected to a resistor. If the current

A battery of emf 10 V and internal resistance 3 Ω is connected to a resistor. If the current Question 3.1: The storage battery of a car has an emf of 12 V. If the internal resistance of the battery is 0.4Ω, what is the maximum current that can be drawn from the battery? Emf of the battery, E =

More information

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured) WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY.

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY. INTRODUCTION Nuhas Oman LLC, an integral part of The Al Bahja Group of Companies, is a Quality producer of: HV, MV and LV Cables Enamelled Copper Wires Oxygen Free Continuous Cast Copper Wire Rods Drawn

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

Factors Affecting the Sheath Losses in Single-Core Underground Power Cables with Two-Points Bonding Method

Factors Affecting the Sheath Losses in Single-Core Underground Power Cables with Two-Points Bonding Method International Journal of Electrical and Computer Engineering (IJECE) Vol. 2, No. 1, February 2012, pp. 7~16 ISSN: 2088-8708 7 Factors Affecting the Sheath Losses in Single-Core Underground Power Cables

More information

2008 D AI Prove that the current density of a metallic conductor is directly proportional to the drift speed of electrons.

2008 D AI Prove that the current density of a metallic conductor is directly proportional to the drift speed of electrons. 2008 D 1. Prove that the current density of a metallic conductor is directly proportional to the drift speed of electrons. 2. A number of identical cells, n, each of emf E, internal resistance r connected

More information

Medium Voltage Power Cables

Medium Voltage Power Cables N2XSY 6/0, /20, /30 NA2XSY 6/0, /20, /30 N2XS2Y 6/0, /20, /30 NA2XS2Y 6/0, /20, /30 N2XS(F)2Y 6/0, /20, /30 NA2XS(F)2Y 6/0, /20, /30 N2XSEY 3 x 6/0 Medium Voltage Power Cables Photo: HELUKABEL Q 47 Medium

More information

CHAPTER 3: ELECTRIC CURRENT AND DIRECT CURRENT CIRCUIT

CHAPTER 3: ELECTRIC CURRENT AND DIRECT CURRENT CIRCUIT CHAPTER 3: ELECTRIC CURRENT AND DIRECT CURRENT CIRCUIT PSPM II 2005/2006 NO. 3 3. (a) Write Kirchhoff s law for the conservation of energy. FIGURE 2 (b) A circuit of two batteries and two resistors is

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

OFFSHORE CABLES GENERAL CATALOGUE. Offshore Cables. technergy INTEGRATED CABLING SOLUTIONS

OFFSHORE CABLES GENERAL CATALOGUE. Offshore Cables. technergy INTEGRATED CABLING SOLUTIONS OFFSHORE CABLES GENERAL CATALOGUE Offshore Cables technergy INTEGRATED CABLING SOLUTIONS TM 1 TEOF Offshore Cables INTEGRATED CABLING SOLUTIONS TM technergy Introduction Every offshore platform requires

More information

CIR (Crush & Impact Resistant) VFD Power Cable

CIR (Crush & Impact Resistant) VFD Power Cable 37-2 CIRVFD CIR (Crush & Impact Resistant) VFD Power Cable Gexol Insulated Three Conductor 2kV Rated 90 C UL Listed as Type TC-ER Power Conductors (x3) Soft annealed flexible stranded tinned copper per

More information

A. Product Description: Stranded conductor insulated wire.

A. Product Description: Stranded conductor insulated wire. SECTION 16120CPPR CONDUCTORS AND CABLE PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. Product Requirements: Provide products as follows: 1. All building wire shall be stranded copper (no aluminum wire). 2.

More information

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another. TRANSMISSION LINES PRELIMINARIES Generators and loads are connected together through transmission lines transporting electric power from one place to another. Transmission line must, therefore, take power

More information

For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation.

For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation. Telecommunication and fire alarm cables For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation. J-YY Bd 14 J-YY BMK 15 J-Y(St)Y Lg 16 J-Y(St)Y

More information

ENERGY CORDAFLEX (SMK) (N)SHTOEU Low Voltage Reeling Cable

ENERGY CORDAFLEX (SMK) (N)SHTOEU Low Voltage Reeling Cable ENERGY (N)SHTOEU Low Voltage Reeling Cable Technical Data Type Type designation Approvals/standards Application (N)SHTOEU-J/-O DIN VDE 0250, Part 814; VDE-Reg.-Nr. 7519; GOST R Flexible reeling cable for

More information

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION

More information

VSD CABLES. KSXCY Series MDXCY Series HDXCY Series FDXCY Series P: (09)

VSD CABLES. KSXCY Series MDXCY Series HDXCY Series FDXCY Series P: (09) KSXCY Series... 72 MDXCY Series... 73 HDXCY Series... 74 FDXCY Series... 76 P: (09) 264 1000 www.firstflex.co.nz KSXCY High Performance Fixed Copper Tape VSD Cable Flexible Conductors for Fixed Applications

More information

Collection of standards in electronic format (PDF) 1. Copyright

Collection of standards in electronic format (PDF) 1. Copyright Collection of standards in electronic format (PDF) 1. Copyright This standard is available to staff members of companies that have subscribed to the complete collection of SANS standards in accordance

More information

Technical Specification. for 1.1 KV Copper Control Cable

Technical Specification. for 1.1 KV Copper Control Cable WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

Cores layed up around conductive filler with aramid rope in the center Rubber, special compound, mechanical properties acc.

Cores layed up around conductive filler with aramid rope in the center Rubber, special compound, mechanical properties acc. ()TSCGEWOEU TEAX TTS-LWL 3,6/6 kv: Application Flexible medium voltage reeling cable with integrated fibre-optics for the combined transmission of energy and data, for application under high mechanical

More information

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M SL. NO NOMINAL DIAMETER "D" mm GASKETED JOINT (Nm) WOODEN CORE CLAMP (Nm) STEEL FIXING STUD FOR BUSHING (Nm) BUSHING STEM (Nm) (BRASS /COPPER) COPPER BUSBAR (Nm) 1 M6 5 - - - - 2 M8 12 - - 10-3 M10 22

More information

Armoured Power and Control Cables to BS7917

Armoured Power and Control Cables to BS7917 1 Armoured Power and Control Cables to BS Fire Resistant, TAC. MGT. EPR. ZH. GSWB. SW, 00/00 V. Low Smoke Zero Halogen Application Armoured cables for fixed wiring in ships and offshore units where circuit

More information

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) FIGURE 1.2 Fig.1 Earth fault loop path. Figure 1 shows the earth fault system which provides

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

600 Volt MULTICONDUCTOR EPR MC Low Voltage Commercial & Industrial Cables

600 Volt MULTICONDUCTOR EPR MC Low Voltage Commercial & Industrial Cables Applications Multiconductor cable with stranded copper conductors, extruded high dielectric strength thermosetting EPR-based insulation, Type XHHW-2, cabled with bare copper grounding conductors and fillers,

More information

Testing Manual for Electrical Equipment

Testing Manual for Electrical Equipment EPPM, Singapore, 20-21 Sep 2011 Abstract Testing Manual for Electrical Equipment Nahed Al-Hajeri 1 and Anantha Madhavan 2 Quality Assurance (QA) refers to a program for the systematic monitoring and evaluation

More information

Armoured Power and Control Cables Fire Resistant

Armoured Power and Control Cables Fire Resistant Armoured Power and Control Cables Fire Resistant Low Smoke Zero Halogen TAC. MGT. EPR. ZH. GSWB. SW, 00/00V Application Armoured cables for fixed wiring in ships and offshore units where circuit integrity

More information

P Low Voltage Catalogue Cables Australia Powering your Project

P Low Voltage Catalogue Cables Australia Powering your Project P +61 8 9367 8978 Low Voltage Catalogue Cables Australia Powering your Project CABLES AUSTRALIA PTY LTD LOW VOLTAGE CATALOGUE ABOUT US Cables Australia is a locally owned and operated distributor of high

More information

Module 2 Unit 6, 7, 8

Module 2 Unit 6, 7, 8 Module 2 Unit 6, 7, 8 1. What is the definition of an ideal conductor? Material that will carry the greatest current with the lowest temperature rise 2. How much does copper weigh compared to aluminum?

More information

Mongoose PT Platform Shale Shaker

Mongoose PT Platform Shale Shaker Mongoose PT Platform Shale Shaker (UL VERSION) Revision: A By: MT Mongoose Platform Page 1 of 10 NOTE: Mongoose PT Platform Shale Shaker The attached is a reference to M-I SWACO s STANDARD Mongoose Platform

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables NO: 452-1 Office

More information

Cable Data Collector (CDC): Application Guide

Cable Data Collector (CDC): Application Guide Cable Data Collector (CDC): Application Guide Contents 1. Introduction... 1 2. PD in cables... 1 3. Principle of operation... 2 4. Advantages and disadvantages... 6 5. Assessing circuit suitability...

More information

EDS KV TRIPLEX CABLE RATING

EDS KV TRIPLEX CABLE RATING Document Number: EDS 02-0027 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE RATING This engineering design standard provides the cable ratings and important

More information

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV CABLE DESCRIPTION Single- or multi-phase electric cable for creating a weak external magnetic field,so as to obtain a cable wherein at last one of the conductors is assembled from two or more insulated

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

SINGLE CORE CABLE-2491X PVC H05V-K CABLE 300/500V

SINGLE CORE CABLE-2491X PVC H05V-K CABLE 300/500V LEDBURN CABLES IS AN INDEPENDENTLY OWNED CABLE DISTRIBUTOR. SINGLE CORE CABLE-2491X PVC H05V-K CABLE 300/500V Internal equipment wire. Also used in instrumentation panels of power switchgear. Suitable

More information

Armoured Instrumentation Cables to BS6883

Armoured Instrumentation Cables to BS6883 Armoured Instrumentation Cables to BS Low Smoke Zero Halogen Pairs/Triples - Collectively Screened. TAC, EPR, SCRN, SW, GSWB, SW 0/0V Application Armoured control and instrumentation cables for fixed wiring

More information

600 Volt MULTICONDUCTOR XLPE MC Low Voltage Commercial & Industrial Cables

600 Volt MULTICONDUCTOR XLPE MC Low Voltage Commercial & Industrial Cables Applications Multiconductor cable with stranded copper conductors, extruded high dielectric strength cross-linked polyethylene (XLPE) insulation, Type XHHW-2, cabled with bare copper grounding conductors

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

Canadian OSP Copper I-1. Table of Contents

Canadian OSP Copper I-1. Table of Contents Canadian OSP Copper Premises Copper Table of Contents CELFIL BJBB, BJAB, BJMB and BJTB................................. I-2 Canadian ALPETH BHBB, BHAB, BKMB and BKTB.................... I-4 SEALPAP BHBF,

More information

AC Voltage- Pipeline Safety and Corrosion MEA 2015

AC Voltage- Pipeline Safety and Corrosion MEA 2015 AC Voltage- Pipeline Safety and Corrosion MEA 2015 WHAT ARE THE CONCERNS ASSOCIATED WITH AC VOLTAGES ON PIPELINES? AC concerns Induced AC Faults Lightning Capacitive coupling Safety Code Induced AC Corrosion

More information

Date: / TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND CABLES

Date: / TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND CABLES 1 Date:19.09.2013/08.01.2014 TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND 1.0 SCOPE: CABLES 1.1 The scope of this specification covers the design, manufacture, stage inspection at works,

More information

CY CONTROL FLEXIBLE PVC INSULATED / TINNED COPPER WIRE BRAID (TCWB) / PVC SHEATHED

CY CONTROL FLEXIBLE PVC INSULATED / TINNED COPPER WIRE BRAID (TCWB) / PVC SHEATHED PVC INSULATED / TINNED COPPER WIRE BRAID (TCWB) / PVC SHEATHED ISSUE DATE: 04/02/2016 PAGE: 1 Manufactured generally to BS EN 50525-2-11 Plain Annealed Flexible Copper Conductors / PVC Insulated / Tinned

More information

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

Filled Solid ALPETH Cable

Filled Solid ALPETH Cable I. Exchange Cables Filled Solid ALPETH Cable REA/RUS PE-39 2.39.01 CONDUCTORS: Solid, annealed copper wires, in 2, 24, 22 and 19 AWG. INSULATION: Solid, high-density polyeylene or polypropylene in distinctive

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

VFD CABLES 100% EMI CONTAINMENT FOR INDUSTRIAL APPLICATIONS

VFD CABLES 100% EMI CONTAINMENT FOR INDUSTRIAL APPLICATIONS VFD CABLES 100% EMI CONTAINMENT FOR INDUSTRIAL APPLICATIONS INDUSTRIAL VFD CABLES Index n Variable Frequency Drive (VFD) Power Cables Extra Flexible VFD Power Cable............... 2-3 Crush & Impact Resistant

More information

ELECTRICAL MEASUREMENTS

ELECTRICAL MEASUREMENTS R10 Set No: 1 1. a) Derive the expression for torque equation for a moving iron attraction type instrument and comment up on the nature of scale [8] b) Define the terms current sensitivity, voltage sensitivity

More information

Basic Principles and Operation of Transformer

Basic Principles and Operation of Transformer Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core

More information

SY CONTROL FLEXIBLE PVC INSULATED, BEDDED AND SHEATHED WITH GALVANISED STEEL BRAID

SY CONTROL FLEXIBLE PVC INSULATED, BEDDED AND SHEATHED WITH GALVANISED STEEL BRAID ISSUE DATE: 05/02/2016 PAGE: 1 Manufactured generally to BS EN 50525-2-11:2011 Plain Annealed Flexible Copper Conductors / PVC Insulated / PVC Bedding / GSWB (Galvanised Steel Wire Braid) / PVC Sheathed.

More information

Armoured Power and Control Cables to BS6883

Armoured Power and Control Cables to BS6883 Armoured Power and Control Cables to BS Low Smoke Zero Halogen Single-Core - T.A.C EPR, SW, TPBWB. SW 00/00 V Multicore - T.A.C EPR, SW, GSWB, SW 00/00 V Application Armoured cables for fixed wiring in

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

Premoulded cable joint SMPGB

Premoulded cable joint SMPGB Premoulded cable joint SMPGB 362-420 Premoulded for safe and easy installation Active pressure Reliable Joint bodies routinetested according to IEC before delivery Bolt connector technology Compact joint

More information

Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking

Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking A Technical data Special PVC control cables, adapted to DINVDE0 part3 Temperature range flexing -5 C ) to +0 C fixed installation

More information

E 1 Ι 1 R 1 R 2 Ι 3 R 3 E 2 Ι 2

E 1 Ι 1 R 1 R 2 Ι 3 R 3 E 2 Ι 2 1 (a) A student has been asked to make an electric heater. The heater is to be rated as 12 V 60 W, and is to be constructed of wire of diameter 0.54 mm. The material of the wire has resistivity 4.9 x 10

More information

UNCONTROLLED 3 STANDARD PROCEDURES FOR PREPARING 33KV CABLES

UNCONTROLLED 3 STANDARD PROCEDURES FOR PREPARING 33KV CABLES 3 STANDARD PROCEDURES FOR PREPARING 33KV CABLES 3.1 Single-Core Copper Wire Screened Polymeric Cables 3.1.1 Removing the Outer Sheath Clean and abrade the outer sheath with an approved abrasive paper for

More information

BASIC ELECTRICITY/ APPLIED ELECTRICITY

BASIC ELECTRICITY/ APPLIED ELECTRICITY BASIC ELECTRICITY/ APPLIED ELECTRICITY PREAMBLE This examination syllabus has been evolved from the Senior Secondary School Electricity curriculum. It is designed to test candidates knowledge and understanding

More information

BASIC ELECTRICITY/ APPLIED ELECTRICITY

BASIC ELECTRICITY/ APPLIED ELECTRICITY BASIC ELECTRICITY/ APPLIED ELECTRICITY PREAMBLE This examination syllabus has been evolved from the Senior Secondary School Electricity curriculum. It is designed to test candidates knowledge and understanding

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

HO7RN-F 450/750V BS EN Highly Flexible Rubber Cable

HO7RN-F 450/750V BS EN Highly Flexible Rubber Cable Rubber Insulation and Rubber Sheathed Application Range Heavy duty flexible cables for medium mechanical stress For dry and wet applications Can be used for domestic electric tools According to HD 516

More information

Electrical Characteristics Nominal electrical characteristics are shown in Table 1. Attenuation, Comply with ANSI T1.102; discrete values Table 1a.

Electrical Characteristics Nominal electrical characteristics are shown in Table 1. Attenuation, Comply with ANSI T1.102; discrete values Table 1a. 734A COAXIAL CABLE Application Intended for interconnection of transmission and switching systems equipment. Features UL listed as NEC Type CMR and CSA certified as Type CMR. NORDX/CDT 734A coaxial was

More information

HYDROFIRM (T) Cables. for use in Ground Water and Drinking Water

HYDROFIRM (T) Cables. for use in Ground Water and Drinking Water HYDROFIRM (T) Cables for use in Ground Water and Drinking Water Finely stranded copper conductor EPR insulation Special synthetic rubber sheath Until now, the renowned HYDROFIRM TGK cables were available

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s EC 200 EC200 - Rev. 3-23.06.11 Characteristic impedance 50 ± 2 Material copper wire Nominal capacity (pf/m) 80.5 Construction - Relative propagation velocity (%) 83 Diameter (mm) 1.05 Inductance (µh/m)

More information

POWER AND COMMUNICATION CABLES Theory and Applications

POWER AND COMMUNICATION CABLES Theory and Applications POWER AND COMMUNICATION CABLES Theory and Applications Edited by R. Bartnikas, Editor Institut de Recherche dhydro-quebec Varennes, Quebec, Canada K. D. Srivastava, Coeditor University of British Columbia

More information

CATALOG OF PRODUCTS. Your Best Supplier of Electrical Cables

CATALOG OF PRODUCTS. Your Best Supplier of Electrical Cables CATALOG OF PRODUCTS Isolated Copper Wire THHN/MTW/THWN-2 600V, single conductor having flame-retardant and heat-resistant thermoplastic insulation with a jacket of extruded nylon or equivalent material.

More information

SANS 1339:2010 Electric cables Cross-linked polyethylene (XLPE) insulated cables for rated voltages 3,8/6,6 kv to 19/33 kv

SANS 1339:2010 Electric cables Cross-linked polyethylene (XLPE) insulated cables for rated voltages 3,8/6,6 kv to 19/33 kv DRAFT SOUTH AFRICAN STANDARD (DSS): PUBLIC ENQUIRY STAGE Document number: 66/1339/4 Reference: SANS 1339 Date of circulation: 2009-12-08 Closing date: 2010-02-08 Number and title: SANS 1339:2010 Electric

More information

IMPORTANCE OF INSULATION RESISTANCE

IMPORTANCE OF INSULATION RESISTANCE IMPORTANCE OF INSULATION RESISTANCE What is Good Insulation? Every electric wire in your plant whether it s in a motor, generator, cable, switch, transformer, etc., is carefully covered with some form

More information

Installation Recommendations

Installation Recommendations Installation Recommendations Cable pulling recommendations The process of pulling electrical cables on board marine vessels is a relatively standard procedure. Nevertheless, NEXANS would suggest the following

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

VSD cables in. Working with. industrial & automation applications

VSD cables in. Working with. industrial & automation applications Cable Efficiency in Automation Connectivity Cabinet Control Working with VSD cables in industrial & automation applications Description of a VSD System A functional VSD system consists of at least three

More information

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of

More information

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 High Temperature Insulation Systems and their use in Mobile Transformers Myron B. Bell, PE mbell@deltastar.com Delta Star, Inc. June 23 rd 2015 Introduction

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

GEXOL WORLD CLASS OIL & GAS CABLES

GEXOL WORLD CLASS OIL & GAS CABLES GEXOL WORLD CLASS OIL & GAS CABLES Severe Cold Durability Exceeds CSA Cold Bend / Cold Impact (-0 C/-35 C) Drilling Mud Resistant Flame Retardant Certified to IEC 9-3 (33-3A) and IEEE 580 Oil Resistant

More information

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS) TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part

More information

UNIT-2 CURRENT ELECTRICITY

UNIT-2 CURRENT ELECTRICITY UNIT-2 CURRENT ELECTRICITY 1 Marks Question 1. A wire of resistance R is cut into n equal parts.these parts are then connected in parallel with each other. The equivalent resistance of the combination

More information

TRANSFORMER TECHNOLOGY GPT

TRANSFORMER TECHNOLOGY GPT Core-Form TRANSFORMER TECHNOLOGY GlobalPT Corporation performs research and engineering developments and co-ordination of works of technical partners in the field of technological progress and commercial

More information

Electrical Design Process

Electrical Design Process Electrical Design Process Jason Varnell Lead Design Engineer Jason.Varnell@spx.com SPX Transformer Solutions, Inc. September 26, 2018 Agenda 1. Bid Design Process Parameters Affecting Bid Design 2. Final

More information

DNVGL-CP-0400 Edition December 2015

DNVGL-CP-0400 Edition December 2015 CLASS PROGRAMME Type approval DNVGL-CP-0400 Edition December 2015 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Cables. Cables. Power. Fire Resistant WILSON CABLES PRIVATE LIMITED. Distributed By :

Cables. Cables. Power. Fire Resistant WILSON CABLES PRIVATE LIMITED. Distributed By : Power Cables Fire Resistant Cables Distributed By : WILSON CABLES PRIVATE LIMITED 142, Gul Circle, Jurong Industrial Estate, Singapore 629602 Tel : + 65 68617888 Fax : + 65 68617871 E-mail : exports@wilson-cables.com.sg

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information