General Specifications

Size: px
Start display at page:

Download "General Specifications"

Transcription

1 General Specifications MODEL 550 Digital Indicating Controller GS 05D0C00E General Model 550 Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful control capability and the userfriendly large numerical display. The 550 features as standard many functions which are necessary for various control applications, and all of these functions such as control function, control computation function, signal computation function, etc. can be configured by using the keys on the front panel. The instrument has eight types of control strategies and also an overshoot suppressing function "SUPER" and a hunting suppressing function "SUPER " as well as an autotuning function built in as standard. It is suitable for a diverse range of applications, with positionproportional control model and heating/cooling control model also available E E indicates the model with expanded functions. Main Features Extralarge digital display allows the indicated values to be read even from a long distance. LEDs of 0 mm height are used for the process variable display. This is a fivedigit display for higher resolution. Eight types of control function, including singleloop control, cascade control, loop control with autoselector, and loop control with hold function, enabling the operator to start control operation immediately after simply entering the settings. Parameters can be easily set using a personal computer. ("Parameter setting tool (model LL00)" sold separately is required.) Universal input and enables users to set or change freely the type of inputs, input range, type of control, etc. from the front panel. In addition to standard type (universal ), the positionproportional type (relay ) or the heating/ cooling type (universal ) can be specified. Contact inputs (up to points) and contact s (up to points) can be employed and functions can be assigned to each contact. (The maximum number of points varies the suffix code.) Note: See Hardware Specifications and Contact Outputs described later. Various communication function are provided. Communication is possible with personal computer, programmable logic controller, and other controllers. Functional Specifications Control Functions Mode The following types of basic control structure can be set as the mode by the user. Singleloop control ( mode ): The most simple and basic control function. Cascade primaryloop control ( mode ): Output tracking function and cascade control logic are provided. Suitable for cascade primaryloop control. Cascade secondaryloop control ( mode ): Setpoint and cascade control logic are provided. Suitable for cascade secondaryloop control. Cascade control ( mode ): Dual control function for cascade control is available in a single instrument. Loop control for backup ( mode 5): Output tracking function is provided to back up another control instrument. The local and remote control s are switched by a contact input. Loop control with switching ( mode 6): Two inputs are switched for control depending on the status of contact input or input. Loop control with autoselector ( mode 7): Two inputs are automatically selected for control with a high, low, average, or temperaturedifference value selector. Loop control with hold function ( mode ): This control holds a input and a control if an external sensor is switched. Control Computation Functions In each mode, the following control computation functions can be selected: Continuous PID control, Timeproportional PID control, Relay ON/ control, Positionproportional PID control (for 550, 550 )and Heating/Cooling control (for 550 ). Target setpoint and PID parameters: Maximum eight sets of target setpoint and PID parameters can be set. These eight sets can be set for both the main and slave loops in cascade control. GS 05D0C00E Copyright Feb. 000 (YK) nd Edition Sept. 000 (MC)

2 Zone PID selection: Dividing input range into maximum 7 zones by maximum 6 reference points, PID parameter set switching in up to 7 input zones. Autotuning: Available as standard. Possible to activate autotuning for both main and slave loops for cascade control. "SUPER" function: Overshoots generated by abrupt changes in the target setpoint or by disturbances can be suppressed. "SUPER " function: This function stabilizes the state of control that is unstable due to hunting, etc. without requiring any change in PID constants, when the load and/or gain varies greatly, or when there is a difference between the characteristics of temperature zones. Preset function: When the instrument is in STOP mode, input is burntout, or an abnormality is found in an input circuit, a preset value is as a control. Sampling period Each sampling period can be selected under the following conditions: 50 ms: Available for model code 55000, when mode is set to Singleloop control and the following functions are not used: "SUPER" function, "SUPER " function, heating/cooling control, input computation, setpoint rateofchange limiter, MV rateofchange limiter, deviation alarm, sensor grounding alarm, fault diagnosis alarm, and FAIL. 00 ms: Available when mode is not cascade control. 00 ms: Available when mode is cascade control. (Set value when shipped from the factory: 00 ms) 500 ms: Always available. Operation Mode Switching (Note: Communication enables all the following mode switching to be executed.) AO/MANU switching: Bumpless switching between automatic operation mode and manual control mode is available by using the front keys or contact input. The contact input has priority over front key input or switching by communication. The contact input is invalid for Cascade secondaryloop control or Cascade control. RUN/STOP switching: Switching by contact input (bumpless for switching from STOP to RUN). The contact input has priority over switching by communication. In RUN mode, control computation is activated. In STOP mode, control computation ceases and a preset value is as a control while other functions operate normally. OTE/LOC switching: Switching between remote setpoint and local setpoint by instrument operation or contact input. The contact input has priority over instrument operation or switching by communication. For remote to local switching, either bumpless tracking (employing the remote setpoint on switching as the local setpoint) or without tracking (directly switching the local setpoint) can be specified. CADE/AO/MANU switching: Switching by instrument operation or contact input. The contact input has priority over instrument operation or switching by communication. Valid for Cascade secondaryloop control or Cascade control. Output tracking ON/ switching: Provided for Cascade primaryloop control or Loop control for backup. External tracking signal and internal control are switched by the contact input. The contact input has priority over the switching by communication. Control Parameters Setting Range Proportional band: 0. to.% 0.0 to.% (for heating/cooling PID control), 0.0% available for ON/ control Integral time: to 6,000 s, or (for Manual reset) Derivative time: to 6,000 s, or ON/ control hysteresis: 0.0 to 00.0% of input range span Preset : 5.0 to 05.0% (0 ma or less cannot be ) Output limiter: Setting range: 5.0 to 05.0% for both high and low limits However, "low limit setpoint < high limit setpoint" must be satisfied. In case of heating/cooling PID control, upper limiter for heating and upper limiter for cooling. Shutdown function: When manual control is carried out with to 0 ma, control can be down to about 0 ma (shutdown is specified for 5.0% or less). Rateofchange limiter for : or 0. to 00.0%/s Deadband for heating/cooling control: 00.0 to 50.0% for value Deadband for positionproportional control:.0 to 0.0% for Configuration of Input/Output Signal Input Computations Input processing, Square root extraction (voltage input only, Input low cut 0.0 to 5.0%), Tensegment linearizer function, Tensegment bias, Bias addition (00.0 to 00.0%), and First order lag filter (, time constant to 0 s) Auxiliary Input Computations (Applied to remote setting input only) Input processing, Square root extraction (Input low cut 0.0 to 5.0%), Bias addition (00.0 to 00.0%), Ratio multiplication (0.00 to.), First order lag filter (, time constant to 0 s) All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

3 Alarm Functions Alarm types: high limit, low limit, Deviation high limit, Deviation low limit, Deenergized on deviation high limit, Deenergized on deviation low limit, Deviation high and low limits, High and low limits within deviation, Deenergized on high limit, Deenergized on low limit, SP high limit, SP low limit, Output high limit, Output low limit. Alarm setting range: /SP alarm: 00 to 00% of input range Deviation alarm: 00 to 00% of input range span Output alarm: 5.0 to 05.0% of value Alarm hysteresis: 0.0 to 00.0% of input range span Delay timer: 0.00 to.5 (minute, second) An alarm is when the delay timer expires after the alarm setpoint is reached. Setting for each alarm is possible. Standby action: Standby action can be set to make / deviation alarm during startup or after SP change until SP reaches the normal region. Timer function (stabilization of control status notification event) (Alarm only): This function sets the alarm to ON when a preset time (timer setting) elapses after a has reached the control target setpoint hysteresis band to notify that control has reached its stabilized status. Restarted in RUN/STOP or SP switching. Other alarm actions: Sensor grounding alarm: Detects sensor deterioration and s an alarm. Faultdiagnosis alarm: For input burnout, A/D conversion error, or thermocouple reference junction compensation error. FAIL : Abnormality in software or hardware. Number of alarm settings: (maximum) The alarm status can be read via communication in addition to as the above alarm. Alarm points (see also the item "Contact Outputs") Number of contact (relay) s: (standard) or (if a control relay is used for the alarm relay.) Number of contact (transistor open collector) s: (when optional function code is specified as or ) From the above, up to point s can be obtained (except for cascade control). Any of alarm, deviation alarm, SP alarm, alarm, Faultdiagnosis alarm, sensor grounding alarm and FAIL can be assigned to contacts for the above number of s. However, the timer delay alarm can be assigned to the alarm only. Also, the alarm only can be assigned to the control relay (if a relay is not used for control ). Display and Operation Functions Display is displayed in the 5digit display. or is displayed by switching them in cascade control. The number of display digits is or 5. For thermocouple or RTD, data below the decimal point can be set not to display. The display range is to 0000 and the display span is 0000 or less. [ appearing in the product photograph on page cannot actually be displayed.] Setpoint Display A parameter name is displayed in the digit display and data in the 5digit display. There are four kinds of displays : operating display, operating parameter setting display, setup parameter setting display and SELECT display. Operating display: Data necessary for operations, such as setpoint or control, are displayed depending on the mode. Operating parameters setting display: The Operating parameters, which are mainly changed during operations, such as PID constant, are displayed. Setup parameters setting display: The Setup parameters to configure the functions of the instrument before starting operation are displayed. mode is to be set in this display. SELECT display: Up to five displays which are frequently accessed can be selected from the Operating parameters setting display and Setup parameters setting display to be displayed in the SELECT display. Status Indicator Lamps Alarm indicator lamps: Four lamps,,,, and Status indicator lamps: (remote operation), MAN (manual mode operation), (cascade operation), and LP (cascade secondaryloop control) Deviation monitor: Plus deviation, Minus deviation, and deviation in normal range Operation Keys, keys: Increase or decrease setpoints and other parameters displayed in the setpoint display. key: Used for setting or changing set data, switching the displayed contents, and switching operation modes except for. key: Operation mode switching (Auto/Manual) Security Function Keylock by parameter setting and prohibiting operation by a password are available. All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

4 MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN MAN <<Contents>> <<Index>> Status indicator lamps Deviation (,, ) Cascade operation () and remote operation () Manual operation (MAN) Lit for secondary parameter indication (LP) Lightloader interface Parameters are set via communication from a personal computer. Measured value () display Displays and error codes when errors are detected. Setpoint display Displays setpoints (SP), values, valve opening, or parameters. Operation keys Increase/decrease of the setting data (, ) Screen switching/parameter selection/entry of set data () Auto/manual operation mode switching () Alarm indicator lamps Displays alarms (,,, or ). Communication Functions (For optional function code or only) This controller has four types of communication protocol with one communication interface. Communication is possible with personal computer, programmable logic controller, and other controllers. Communication Protocol Computer link communication: Communication protocol with a personal computer Ladder communication: Communication protocol with the ladder program on some programmable logic controllers. Coordinated operation: Protocol for coordinated operation with more than one GREEN SERIES controller. The 550 controller can be connected as a master or slave station. MODBUS communication: Communication protocol with a personal computer, or PLC. RS5 Communication Interface The RS5 communication interface (conforms to EIA RS5) can be used for personal computer link, MODBUS communication, ladder communication, or for coordinated operation. Maximum number of connectable controllers: GREEN SERIES controllers Maximum communication distance: 00 m Communication method: Twowire halfduplex or fourwire halfduplex, startstop synchronization, and nonprocedural Baud rate: 600, 00, 00, 00, or 600 bps Examples of Communication System Configuration Diagram () Personal computer link communication/ MODBUS communication Personal computer () Ladder communication MELSECA Programmable logic controllor 550, 50 Digital indicating controller () Coordinated operation UP750, UP550 Program controller or 750, 550, 50 Digital indicating controller 550, 50 Digital indicating controller 550, 50 Digital indicating controller All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

5 Hardware Specifications Input/Output Signal Specifications Input Signal Number of input points: Input type, instrument input range, and measurement accuracy: The type of input and instrument input range can be specified from the instrument input range codes shown in the table below. Sampling period: 50, 00, 00, or 500 ms (selectable) Burnout detection: Activated for thermocouple (TC) input, RTD input, or standard signal of 0. to V DC or to 5 V DC. Possible to specify a travel of upscale, downscale, or off. For standard signal input, set to burn out at 0. V or less. Input bias current: 0.05 µa (for TC or RTD bterminal) Measurement current(rtd): About 0. ma Input resistance: MΩ or more for TC or mv input About MΩ for DC voltage input Allowable signal source resistance: 50 Ω or less for TC or mv input Signal source resistance effect 0. µv/ω or less kω or less for DC voltage input Signal source resistance effect About 0.0%/00 Ω Allowable wiring resistance (for RTD input): Maximum 0 Ω/wire (Conductor resistance between three wires must be equal.) However, it must be 0 Ω/wire for a maximum range of 0.0 to 0.0 C. Effect of wiring resistance: ±0. C/0Ω Allowable input voltage: ±0 V DC for TC/mV/RTD input ±0 V DC for DC voltage input Noise rejection ratio: Normal mode 0 db (50/60 Hz) or more mode 0 db (50/60 Hz) or more Reference junction compensation error: ±.0 C ( to 5 C), ±.5 C (0 to C and 5 to 50 C) Applicable standards: JIS, IEC, and DIN (ITS0) for TC and RTD 5 Input Type Instrument Input Instrument Input Instrument Input Range Code Range ( C) Range ( F) Measurement Accuracy * Unspecified (When shipped from the factory) Set the data item input type IN to the option to leave the input type undefined. Thermocouple K 70.0 to 70.0 C 70.0 to C 00.0 to C 50.0 to F 50.0 to 00.0 F 00.0 to F ±0.% ± digit of instrument range at 0 C or more ±0.% ± digit of instrument range at less than 0 C However, ±% ± digit of instrument range for type K at temperatures less than 00 C. J 00.0 to 00.0 C 00.0 to 00.0 F However, ±% ± digit of instrument range for type T at temperatures less than 00 C. T to 00.0 C 50.0 to F to 00.0 C 00.0 to F B 0.0 to 00.0 C to 00 F ±0.% ± digit of instrument range at 00 C or more 7 ±5% ± digit of instrument range at less than 00 C S R 0.0 to C 0.0 to C to 00 F to 00 F ±0.% ± digit of instrument range N to 00.0 C 00.0 to 00.0 F ±0.% ± digit of instrument range ±0.5% ± digit of instrument range for temperature at less than 0 C E L (DIN) U (DIN) W (DIN) Platinel to C 00.0 to 00.0 C 00.0 to 00.0 C 0.0 to 00.0 C 0.0 to 00.0 C 0.0 to 0.0 C 50.0 to 00.0 F 00.0 to F 00.0 to F 00.0 to F to 00 F.0 to F ±0.% ± digit of instrument range at 0 C or more ±0.% ± digit of instrument range at less than 0 C However, ±.5% ± digit of instrument range for type E at temperature less than 00 C. ±0.% ± digit of instrument range ±0.% ± digit of instrument range PR to 00.0 C to 00 F ±0.5% ± digit of instrument range at 00 C or more 7 Accuracy not guaranteed for temperature less than 00 C RTD W7ReW75Re5 JPt00 Pt to C 00.0 to C 0.00 to 0.00 C 00.0 to 50.0 C 00.0 to C 0.00 to 0.00 C to 600 F 00.0 to F 00.0 to 00.0 F 00.0 to 60.0 F 00.0 to F 00.0 to 00.0 F ±0.% ± digit of instrument range ±0.% ± digit of instrument range (Note ) (Note ) ±0.% ± digit of instrument range (Note ) ±0.% ± digit of instrument range (Note ) (Note ) ±0.% ± digit of instrument range (Note ) Standard 0. to V to.000 V Display range ±0.% ± digit of instrument range signal to 5V.000 to V to to V 50 Display span 0000 or to.000 V less (Decimal point DC voltage 0 to 0V to 0.00 V position changeable) 0 to 0mV 0 to00mv to 0.00 mv 0.0 to 00.0 mv Note : The accuracy is ±0. C of instrument range ± digit for a temperature range from 0 to 00 C. Note : The accuracy is ±0.5 C of instrument range ± digit for a temperature range from 00 to 00 C. *: Performance in the standard operating conditions (at ± C, 55±0% RH, and 50/60Hz power frequency) All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

6 Auxiliary Analog Input Signal (550,, or only) Functions: Remote setting input, tracking input, cascade control secondary loop input, etc. Input type: Settable within the range of voltage input 0 to V DC, 0 to 0 V DC, 0. to.0 V DC or to 5 V DC. Number of inputs: point Sampling period: 00, 00 or 500 ms Auxiliary analog input sampling period is linked with input sampling period. (If input period is 50 ms, auxiliary analog input period is 00 ms.) Input resistance: Approx. MΩ Input accuracy: ±0.% ± digit of input span for 0 to V DC input ±0.% ± digit of input span for 0 to 0 V DC input ±0.75% ± digit of input span for 0. to.0 V DC range ±0.% ± digit of input span for to 5 V DC range Performance in the standard operating conditions (at ± C, 55±0% RH, and 50/ 60Hz power frequency) Feedback Resistance Input Signal (550 only) Valid for position proportional PID control. Slidewire resistance: Total resistance 00 Ω to.5 kω (with burnout detection of slidewire) Measuring resolution ±0.% of total resistance V DC Loop Power Supply for Sensor Supplies power to the wire transmitter. The current signal is converted to a voltage signal by placing a resistor (arbitrary from 0 to 50 Ω) and is read by the input terminal..6 to.0 V DC, maximum supply current about 0 ma (only for models with V DC loop for sensor). V DC Power Supply Wiring to Twowire Sensor Twowire transmitter 0mADC External resistor (Note) 50Ω input to 5 V DC signal Loop power supply.6 to.0 V DC Note : Connecting a 50Ω resistor to the terminals is optional. Model : X0050 (resistor with M.5 crimpon terminal lugs) Retransmission Output Any of the, target setpoint or control is. Or this can be used for V DC loop. Number of points: or Retransmission is available only when relay is selected as the control type. Output signal: to 0 ma DC, 0 to 0 ma DC, 0 to ma DC or 0 to 0 ma DC (0 ma or less cannot be ) 6 Load resistance: 600 Ω or less Output accuracy: ±0.% of span (±5% for ma or less) Performance in the standard operating conditions (at ± C, 55±0% RH, and 50/ 60Hz power frequency) When using for V DC loop : Supply voltage.5 to.0 V DC, maximum supply current about ma (with the protection circuit at field shortcircuit). Control Outputs Select or points (550 ) from the following types depending on model type and mode. Relay contact for position proportional PID control ( ). Current Number of points: or (for heating/cooling type) (switchable to voltage pulse ) Output signal: to 0 ma DC, 0 to 0 ma DC, 0 to ma DC or 0 to 0 ma DC Load resistance: 600 Ω or less Output accuracy: ±0.% of span (±5% for ma or less) Performance in the standard operating conditions (at ± C, 55±0% RH, and 50/ 60Hz power frequency) Voltage pulse Number of points: or (for heating/cooling control) (switchable to current ) Output signal: ON voltage V DC or more (load resistance 600 Ω or more) voltage 0. V DC or less Resolution: 0 ms or 0.% of value, whichever is greater Relay contact Number of points: or (for heating/cooling control) Output signal: At three terminals of NC, NO, and Contact rating: 50 V AC, A or 0 V DC, A (resistance load) Resolution: 0 ms or 0.% of value, whichever is greater Contact Inputs Usage: Target setpoint switching, C/ mode switching, OTE/LOC switching, RUN/STOP switching, or input switching Number of input points: Varies with optional codes (as shown below): 550 0: points 550 : points 550 : points 550 : 7 points 550 : points Input type: Nonvoltage contact input or transistor open collector input Input contact rating: V DC, 0 ma or more On/off detection: For nonvoltage contact input, On.. contact resistance kω or less; Off.. contact resistance 0 kω or more For transistor contact input, On.. V or less; Off.. leak current 00 µa or less Minimum status detection hold time: input sampling period All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

7 Contact Outputs Usage: Alarm, FAIL Number of points: Varies with optional codes (as shown below): 550 0: Relay points 550 : Relay points, transistor points 550 : Relay points 550 : Relay points, transistor points 550 : Relay points However, when a relay is not used for control, the relay for control can be used for the alarm. For this reason, the number of relay points can be changed to by adding to the above. Relay contact rating: 0 V AC, A or 0 V DC, A Transistor contact rating: V DC, 50 ma Display Specifications Measured value () display: 5digit 7segment red color LED display; height of letters 0 mm Data display: digits 5 digits, 7segment red color LED display; height of letters. mm Status indicator lamps: LEDs Conformance to Safety and EMC Standards Safety standard: Conforms to IEC00: 0 and EN600 : Certified for CSA00 The overvoltage category of each input is CAT II (IEC00) Certified for UL50 application EMC standards: To the following EMC standards. During test, the controller continues to operate with the measurement accuracy within ±0% of the range: For EMI (emission), EN550, Class A Group For EMS (immunity), EN500: 5 Construction, Installation, and Wiring Construction: Dustproof and Dripproof front panel conforming to IP55. For sidebyside close installation, the controller loses its dustproof and dripproof protection. Material of the body: ABS resin and polycarbonate Case color: Black Weight: About kg or less External dimensions: 6W 6H 00D (from the panel face) (mm) Mounting: Direct panel mounting; mounting bracket, one each for upper and lower mounting Panel cutout dimensions: 0.W H (mm) Mounting attitude: Up to 0 degrees from horizontal; Must not face downward. Wiring connection: With M.5 screw terminals (for signal, power and grounding wiring) 7 Power Supply and Isolation Power supply: Rated voltage 00 to 0 V AC (±0%), 50/60 Hz Power consumption: Max. 0 VA (Max..0 W) Data backup: Nonvolatile memory. Service life about 00,000 times of writings Withstanding voltage: 00 V AC for min. (Note) between primary terminals and secondary terminals 00 V AC for min. (Note) between primary terminals and ground terminal 00 V AC for min. between ground terminal and secondary terminals 500 V AC for min. between secondary terminals where primary terminals stand for power and relay terminals and secondary terminals stand for analog input and signal terminals, voltage pulse terminals, and contact input terminals. Note: The withstanding voltage is specified as 00 V AC per minute to provide a margin of safety. Isolation resistance: 0 MΩ or more for 500 V DC applied between power terminals and ground terminal Grounding: Class grounding (grounding resistance of 00 Ω or less) Isolation Specifications input terminal: Isolated from other input/ terminals, but not isolated from internal circuit. Auxiliary analog input terminal: Isolated from other input/ terminals and internal circuit. V DC loop terminal: Not isolated from analog current and voltage pulse control, but isolated from other input/ terminals and internal circuit. V DC loop terminal: Isolated from 0mA analog ouptut, other input/ terminals and internal circuit. Control (current or voltage pulse ) and retransmission : Not isolated between control and retransmission, but isolated from other input/ terminals and internal circuit. Relay contact control terminals: Isolated between contact terminals, and from other input/ terminals and internal circuit. Contact input terminals: Not isolated between contact input terminals and from communication terminals, but isolated from other input/ terminals and internal circuit. Relay contact terminals: Not isolated between relay contact s, but isolated from other input/ terminals and internal circuit. All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

8 Transistor contact terminals: Not isolated between transister contact s, but isolated from other input/ terminals and internal circuit. RS5 communication terminals: Not isolated from contact input terminals, but isolated from other input/ terminals and internal circuit. Feedback slidewire resistance input terminals: Not isolated from control terminals (current or voltage pulse ) and retransmmision, but isolated from other input/ terminals and internal circuit. Power terminals: Isolated from other input/ terminals and internal circuit. Ground terminal: Isolated from other input/ terminals and internal circuit. Environmental Conditions Normal operating conditions: Ambient temperature: 0 to 50 C (0 C or less for sidebyside close mounting ) Temperature change rate limit: 0 C/h or less Ambient humidity: 0 to 0% RH (no condensation) Magnetic field: 00 A/m or less Continuous vibration (5 to Hz): Peaktopeak amplitude. mm or less Continuous vibration ( to 0 Hz):. m/s or less Shortperiod vibration:.7 m/s, s or less Shock: 7 m/s or less, ms Installation altitude: 000 m or less above sea level Warmup time: 0minutes or more after power on Transportation and storage conditions: Temperature: 5 to 70 C Temperature change rate: 0 C/h or less Humidity: 5 to 5% RH (no condensation) Effects of operating conditions Effect of ambient temperature: Whichever is greater, ± µv/ C or ±0.0% of F.S./ C for voltage or thermocouple inputs. ±0.0% of F.S./ C for Auxiliary input ±0.05 C/ C (ambient temperature) or less for RTD inputs. ±0.05% of F.S./ C or less for analog s. Effect of fluctuation (within rated voltage range): Whichever is greater, ± µv/0 V or ±0.0% of F.S./0 V for analog inputs. ±0.05% of F.S./0 V or less for analog s. All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

9 Function Block Diagram for Singleloop Control (Model 5500,550 or 550 ) input terminals, and Remote input Communication terminals and terminals to 7 Contact input INP INP RS5 DI DI DI5 DI6 DI DI DI Square root extraction 0seg. linearizer approx./bias Square root extraction Target setpoint selection Remote setting filter input bias input filter Aux. Input Communication RMS=RSP RMS= Ratio/bias calculation SPN Target setpoints to OTE R/L LOC OTE(ON)/LOC() switching Target setpoint ramprate function Manual operation Control computation MAN AO AO(ON)/MAN() switching Preset Output limiter STOP S/R RUN STOP(ON)/RUN() switching V loop OT V loop Retransmission Alarm function Control RT RT ON in normal condition LPS OP OP OP OP DO DO DO DO DO7 Terminals and Current or pulse terminals 6 and 7 Relay terminals, and Current* terminals 6 and 7 Current terminals and Alarm Alarm Alarm Alarm FAIL * Unavailable when control is current or pulse. Legend Terminal Parameter Function Analog Signal Contact Signal Front Panel Key All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

10 0 Function Block Diagram for Singleloop Heating/Cooling Control (Model 550 ) input terminals Remote input Communication, and terminals and terminals to 7 Contact input INP INP RS5 DI DI DI5 DI6 DI DI DI Square root extraction 0seg. linearizer approx./bias Square root extraction Target setpoint selection Remote setting filter input bias input filter Aux. Input Communication RMS=RSP RMS= Ratio/bias calculation SPN Target setpoints to OTE R/L LOC OTE(ON)/LOC() switching Target setpoint ramprate function Manual operation Control computation MAN AO AO(ON)/MAN() switching Heating/cooling computation Heatingside limiter Coolingside limiter Heatingside preset Coolingside preset S/R STOP(ON)/RUN() switching OT OT V loop Retransmission Alarm function Heatingside Coolingside RT RT ON in normal condition OP OP OP OP OP OP DO DO DO DO DO7 Current or Relay Current or pulse Relay pulse terminals terminals terminals terminals 6 and 7, and 6 and 7, and 50 Current* Current terminals terminals 6 and 7 and Alarm Alarm Alarm Alarm FAIL * Unavailable when heatingside is current or pulse. Legend Terminal Parameter Function Analog Signal Contact Signal Front Panel Key All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

11 Function Block Diagram for Singleloop Positionproportional Control (Model 550 or 550 ) input terminals Remote input Communication, and terminals and terminals to 7 Contact input INP INP RS5 DI DI DI5 DI6 DI DI DI Square root extraction 0seg. linearizer approx./bias Square root extraction Target setpoint selection Remote setting filter input bias input filter Aux. Input Communication RMS=RSP RMS= Ratio/bias calculation SPN Target setpoints to OTE R/L LOC OTE(ON)/LOC() switching In MAN operation, relay is ON when or key is hold down. Manual operation Target setpoint ramprate function Control computation Output limiter MAN AO AO(ON)/MAN() switching Preset STOP S/R RUN STOP(ON)/RUN() switching Signal comparison V loop L relay H relay ( key) ( key) RT Retransmission RT Alarm function ON in normal condition FEEDBACK terminals 5, 6 and 7 Feedback input Valve position sliding resistor OP terminals, and 50 M Relay Direct/reverse signal Motordriven valve Legend terminals : VDC loop OP OP OP OP terminals terminals 6 and 7 and DO Alarm DO Alarm DO Alarm DO Alarm Terminal Parameter Function DO7 FAIL Analog Signal Contact Signal Front Panel Key All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

12 Function Block Diagram for Cascade Control Cascade primary input terminals, and Communication terminals to 7 Secondary input terminals and Contact inputs INP RS5 INP DI DI DI5 DI6 DI DI DI DI7 Square root extraction Ratio/bias calculation Square root extraction Target setpoint selection Cascade ( ON) Automatic ( ON) Manual ( ON) 0seg. linearizer approx./bias 0seg. linearizer approx./bias input bias input bias input filter input filter RMS= R/L OTE Control computation SPN Primary target setpoint LOC Target setpoint ramprate function SPN Secondary target setpoint If receives the FAIL signal (burnout or A/D converter error) from primary input, operation is switched to AO. Output limiter Tracking in AO or MAN C/ Tracking signal AO, MAN Cascade switching Manual operation Control computation Preset STOP RUN Output limiter MAN C/, AO MAN switching S/R STOP(ON)/RUN() switching OT V loop V loop Retransmission Alarm function Control RT RT ON in normal condition OP Current or pulse Relay terminals terminals 6 and 7, and OP LPS OP OP Alarm Alarm Alarm Alarm Terminals Current* Current and terminals terminals 6 and 7 and * Unavailable when control is current or pulse. DO DO DO DO DO7 FAIL Legend Terminal Parameter Function Analog Signal Contact Signal Front Panel Key All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

13 Function Block Diagram for Loop Control for Backup input terminals, and Communication terminals to 7 Tracking signal (Manipulated from host) terminals and Contact inputs INP RS5 INP DI DI DI5 DI6 DI DI DI Square root extraction 0seg. linearizer approx./bias Ratio/bias calculation Target setpoint selection Tracking switching signal input bias input filter RMS= SPN Target setpoints to R/L OTE LOC Target setpoint ramprate function Manual operation Control can not be changed when contact input (DI) is set to ON. Control computation MAN AO AO(ON)/MAN() switching Tracking (ON) Preset Output limiter STOP RUN S/R STOP(ON)/RUN() switching V loop OT V loop Retransmission Alarm function Control RT RT ON in normal condition LPS OP OP OP OP DO DO DO DO5 DO Terminals and Current or Relay Current * Current pulse terminals terminals terminals terminals 6 and 7, and 6 and 7 and Alarm Alarm Alarm Alarm FAIL * Unavailable when control is current or pulse. Legend Terminal Parameter Function Analog Signal Contact Signal Front Panel Key All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept

14 Function Block Diagram for Loop Control with Switching input input Communication terminals terminals terminals, and and to 7 Contact inputs INP INP RS5 DI DI DI5 DI6 DI DI DI Square root extraction 0seg. linearizer approx./bias Square root extraction 0seg. linearizer approx./bias input Switching (Temp. range, Temp. upper limit, or DI) Burnout occurs when the burnout of input or input occurs. input bias input filter Ratio/bias calculation RMS= R/L OTE U U U Upper limit Lower limit Operation SPN Target setpoints to LOC Target setpoint selection input switching (U=) input ()/ input (ON) Target setpoint ramprate function Manual operation Control computation MAN AO AO(ON)/MAN() switching Preset Output limiter STOP RUN S/R STOP(ON)/RUN() switching V loop OT V loop Retransmission Alarm function Control RT RT ON in normal condition LPS OP OP OP OP DO DO DO DO DO7 Terminals and Current or Relay Current * Current pulse terminals terminals terminals terminals 6 and 7, and 6 and 7 and Alarm Alarm Alarm Alarm FAIL * Unavailable when control is current or pulse. Legend Terminal Parameter Function Analog Signal Contact Signal Front Panel Key All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

15 All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., Singleloop Control (Model 5500, 550 or 550 ), Terminal Arrangements *Wiring can only be carried out for controllers with V DC loop. V DC loop.6.0vdc (0 ma DC max.) Control Relay contact NC NO Contact rating: 50 V AC, A 0 V DC, A (resistance load) Relay Transistor Alarm Alarm Alarm Alarm FAIL (ON when normal) Note: Select this option from the OT parameter. *Time proportional PID relay contact is configured at factory before shipment. Power supply Power supply L N 0 CAION Allowable range: 000 V AC ( 0%) (free voltage) 50/60 Hz shared External contact s DO 6 DO 5 DO 7 DO DO5 DO6 DO7 5 Relay contact rating: 0 V AC, A 0 V DC, A (resistance load) Transistor contact rating: V DC, 50 ma *Alarm is available only when "current/voltage pulse" is selected as the type of control. RS5 communication * Wiring can only be carried out SDB() SDA() RDB() RDA() SG Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock for controllers with communication functions. Maximum baud rate: 600 bps * Wiring can only be carried out for controllers with remote input. Remote input Specify in a range of V DC, 0 V DC, or 00 V DC. * The functionality of a contact input can be varied by changing the setting of the contact input registration parameter. AO when DI=ON MAN when DI= STOP when DI=ON RUN when DI= When switching among target setpoints to :.SP.SP.SP.SP 5.SP6.SP7.SP.SP DI ON ON ON ON DI ON ON ON ON DI5 ON ON ON ON DI6 ON * If all of the contact inputs are set to, the controller uses the immediately preceding target setpoint. Remote when DI=ON Local when DI= External contact inputs DI DI DI DI DI 0 DI 0 DI DI DI5 DI5 DI6 DI6 7 7 DI7 DI DI 0 Contact DI Contact rating: V DC, 0 ma or more 0 Default: V DC Control Current/voltage pulse mADC, 0mADC Voltage pulse ( V) Transistor contact input * Not configured at factory before shipment TC input * Retransmission is available only when relay is selected as the type of control. Retransmission * mADC, 0mADC Default: 0 ma DC A b B Note: Select this option from the OT parameter. Default: Unspecified retransmission type Note: External Contact Input If the power is turned on when the external contact input is, the mode (SPN, R/L, or ) existing before the power is turned off will be continued. (except for RUN/STOP) RTD input mv/v input OT=0 (factoryset default) NOTE Installation category (overvoltage category): II (IEC00) OT= * Factoryset to retransmission. * Retransmission is not available if a V DC loop is used. * OT is a setup parameter. You can change the settings of the parameter OT to change the control type. Time proportional control Relay Retransmission * 0 or 00 ma DC Default: 0 ma DC V DC loop *.5.0 V DC ( ma DC max.) Correspondence between parameter OT and control types Time proportional control Voltage pulse 6 7 Receiving 0 ma DC Current Signals with the Controller * When receiving 0 ma DC current signals, set the input type to V DC (setpoint ). Note: Connecting a 50 Ω resistor to the terminals is optional. Model: X0050 (resistor with M.5 crimpon terminal lugs) Load resistance: 600 Ω or less OT= Current Ω 0mA OT= Onoff control Relay <<Contents>> <<Index>>

16 All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., Singleloop Heating/Cooling Control (Model 550 ), Terminal Arrangements *Alarm is available only when "current/voltage pulse" is selected as the type of coolingside control. *Alarm is available only when "current/voltage pulse" is selected as the type of heatingside control. Coolingside control Current/voltage pulse Heatingside control Relay contact NC NO 00 ma DC 0 ma DC, voltage pulse ( V) Power supply Power supply L N 0 Coolingside control Relay contact NC NO 50 Contact rating: 50 V AC, A 0 V DC, A (resistance load) Alarm Alarm Alarm Alarm 6 7 OT= (factoryset default) Heating side: Relay Cooling side: Relay Contact rating: 50 V AC, A 0 V DC, A (resistance load) Note: Select this option from the OT parameter. *Time proportional PID relay contact is configured at factory before shipment. CAION Allowable range: 000 V AC ( 0%) (free voltage) 50/60 Hz shared Relay Transistor FAIL (ON when normal) *Time proportional PID relay contact is configured at factory before shipment. Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. External contact s DO 6 DO 5 DO 7 DO DO5 DO6 DO7 5 Relay contact rating: 0 V AC, A 0 V DC, A (resistance load) Transistor contact rating: V DC, 50 ma * OT is a setup parameter. You can change the settings of the parameter OT to change the control type. OT=5 Note: Select this option from the OT parameter. Heating side: Voltage pulse Cooling side: Relay RS5 communication SDB() SDA() RDB() RDA() SG * Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 600 bps * Wiring can only be carried out for controllers with remote input. Remote input Specify in a range of V DC, 0 V DC, or 00 V DC. Default: V DC * The functionality of a contact input can be varied by changing the setting of the contact input registration parameter. AO when DI=ON MAN when DI= STOP when DI=ON RUN when DI= When switching among target setpoints to :.SP.SP.SP.SP5.SP6.SP7.SP.SP DI ON ON ON ON DI ON ON ON ON DI5 ON ON ON ON DI6 ON * If all of the contact inputs are set to, the controller uses the immediately preceding target setpoint. Remote when DI=ON Local when DI= TC input A b B RTD input mv/v input Correspondence between parameter OT and heating side types/cooling side types NOTE Installation category (overvoltage category): II (IEC00) OT=6 OT=7 OT= OT= OT=0 OT= OT= Heating side: Current Heating side: Relay Heating side: Current Heating side: Relay Heating side: Current Cooling side: Relay Cooling side: Current Cooling side: Current Cooling side: Current 6 7 External contact inputs DI DI DI DI DI 0 DI 0 DI DI DI5 DI5 DI6 DI6 7 7 DI7 DI DI 0 Cooling side: Voltage pulse DI 0 Heating side: Voltage pulse Cooling side: Voltage pulse The types of control, relay and voltage pulse shown in the table above refer to those of time proportional control. To change to a relay for onoff control, select Relay Terminals and change the setpoint of the proportional band to 0. Contact Contact rating: V DC, 0 ma or more Heatingside control Current/voltage pulse mADC, 0mADC Voltage pulse ( V) * Retransmission is available only when relay is selected as the type of control. Transistor contact Cooling side: Voltage pulse Retransmission * 0 or 00 ma DC Default: 0 ma DC V DC loop *.5.0 V DC ( ma DC max.) * Factoryset to retransmission. * Retransmission is not available if a V DC loop is used. Heating side: Voltage pulse input Note: Select this option from the OT parameter. Retransmission * 6 7 Default: Unspecified retransmission type 00mADC, 0mADC Default: 0 ma DC * Not configured at factory before shipment * When receiving 0 ma DC current signals, Note: Connecting a 50 Ω resistor to the terminals is optional. Model: X0050 (resistor with M.5 crimpon terminal lugs) Load resistance: 600 Ω or less Receiving 0 ma DC Current Signals with the Controller set the input type to V DC (setpoint ). 50 Ω 0mA Note: External Contact Input If the power is turned on when the external contact input is, the mode (SPN, R/L, or ) existing before the power is turned off will be continued. (except for RUN/STOP) <<Contents>> <<Index>> 6

17 7 550 Singleloop Position Proportional Control (Model 550 or 550 ), Terminal Arrangements *Wiring can only be carried out for controllers with V DC loop. Position proportional control Feedback input Relay contact H (Direct) L (Reverse) 50 Contact rating: 50 V AC, A 0 V DC, A (resistance load) Power supply L N V DC loop.6.0vdc (0 ma DC max.) Power supply CAION 0 00% Resistance: 00 to.5 k Allowable range: 000 V AC ( 0%) (free voltage) 50/60 Hz shared Alarm Alarm Alarm Alarm 0% Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. External contact s DO DO DO DO DO5 DO RS5 communication SDB() SDA() RDB() RDA() SG * Wiring can only be carried out for controllers with communication functions. Maximum baud rate: 600 bps * Wiring can only be carried out for controllers with remote input Remote input Specify in a range of V DC, 0 V DC, or 00 V DC. Default: V DC * The functionality of a contact input can be varied by changing the setting of the contact input registration parameter. DI DI DI5 DI6 AO when DI=ON MAN when DI= STOP when DI=ON RUN when DI= When switching among target setpoints to :.SP.SP.SP.SP ON ON ON ON ON 5.SP6.SP7.SP.SP ON ON ON ON ON ON * If all of the contact inputs are set to, the controller uses the immediately preceding target setpoint. ON Remote when DI=ON Local when DI= ON External contact inputs DI DI DI DI DI DI 0 0 DI DI DI5 DI5 DI6 DI6 7 7 DI7 DI DI 0 Contact Transistor contact DI 0 TC input RTD input A b B mv/v input Retransmission V DC loop.5.0vdc ( ma DC max.) NOTE Installation category (overvoltage category): II (IEC00) * retransmission is configured at factory before shipment. * If V DC loop is used, retransmission cannot be used. Relay Transistor FAIL (ON when normal) DO7 5 Relay contact rating: 0 V AC, A 0 V DC, A (resistance load) Transistor contact rating: V DC, 50 ma Retransmission 6 7 Default: Unspecified retransmission type 00mADC, 0mADC Default: 0 ma DC input * Not configured at factory before shipment 0 ma DC, 00 ma DC Default: 0 ma DC Receiving 0 ma DC Current Signals with the Controller * When receiving 0 ma DC current signals, set the input type to V DC (setpoint ). Load resistance: 600 Ω or less 50 Ω 0mA Note: Connecting a 50 Ω resistor to the terminals is optional. Model: X0050 (resistor with M.5 crimpon terminal lugs) * The following method of wiring is only possible when the controller is equipped with a V DC loop. V DC Power Supply Wired to Sensor in Twowire System Configuration Twowire transmitter External resistor (Note) 0mADC 50 input V DC signal Loop power supply.6.0 V DC Contact rating: V DC, 0 ma or more Note: External Contact Input If the power is turned on when the external contact input is, the mode (SPN, R/L, or ) existing before the power is turned off will be continued. (except for RUN/STOP) Note: Connecting a 50 resistor to the terminals is optional. Model: X0050 (resistor with M.5 crimpon terminal lugs) All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., 00000

18 All Rights Reserved. Copyright 000, Yokogawa M&C Corporation GS 05D0C00E nd Edition Sept., Cascade Control, Terminal Arrangements *Wiring can only be carried out for controllers with V DC loop. V DC loop.6.0vdc (0 ma DC max.) Control Relay contact NC NO Contact rating: 50 V AC, A 0 V DC, A (resistance load) Note: Select this option from the OT parameter. *Time proportional PID relay contact is configured at factory before shipment. Power supply Power supply L N 0 CAION Allowable range: 000 V AC ( 0%) (free voltage) 50/60 Hz shared * The functionality of a contact can be varied by changing the setting of the contact registration parameter. Relay Transistor Alarm Alarm Alarm Alarm FAIL (ON when normal) External contact s DO 6 DO 5 DO 7 DO DO5 DO6 DO7 5 Relay contact rating: 0 V AC, A 0 V DC, A (resistance load) Transistor contact rating: V DC, 50 ma RS5 communication * Wiring can only be carried out SDB() SDA() RDB() RDA() SG Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock for controllers with communication functions. Maximum baud rate: 600 bps Secondary input Auxiliary input Specify in a range of V DC, 0 V DC, or 00 V DC. * The functionality of a contact input can be varied by changing the setting of the contact input registration parameter. Cascade switching when DI changes to on Automatic switching when DI changes to on When switching among target setpoints to :.SP.SP.SP.SP 5.SP6.SP7.SP.SP DI ON ON ON ON DI ON ON ON ON DI5 ON ON ON ON DI6 ON * If all of the contact inputs are set to, the controller uses the immediately preceding target setpoint. STOP when DI7=ON RUN when DI7= Manual switching when DI changes to on External contact inputs DI DI DI DI DI 0 DI 0 DI DI DI5 DI5 DI6 DI6 7 7 DI7 DI DI 0 Contact DI Contact rating: V DC, 0 ma or more 0 Default: V DC Control Continuous/voltage pulse mADC, 0mADC Voltage pulse ( V) Transistor contact Primary input * Not configured at factory before shipment TC input * Retransmission is available only when relay is selected as the type of control. Retransmission * mADC, 0mADC Default: 0 ma DC A b B Note: Select this option from the OT parameter. Default: Unspecified retransmission type RTD input mv/v input OT=0 (factoryset default) NOTE Installation category (overvoltage category): II (IEC00) OT= * Factoryset to retransmission. * Retransmission is not available if a V DC loop is used. * OT is a setup parameter. You can change the settings of the parameter OT to change the control type. Time proportional control Relay Note: External Contact Input If the power is turned on when the external contact input (either of Cascade, Automatic, and Manual) is ON, the controller judges that the external contact input is changed to ON. Retransmission * 0 or 00 ma DC Default: 0 ma DC V DC loop *.5.0 V DC ( ma DC max.) Correspondence between parameter OT and control types Time proportional control Voltage pulse 6 7 Receiving 0 ma DC Current Signals with the Controller * When receiving 0 ma DC current signals, set the input type to V DC (setpoint ). Note: Connecting a 50 Ω resistor to the terminals is optional. Model: X0050 (resistor with M.5 crimpon terminal lugs) Load resistance: 600 Ω or less OT= Current Ω 0mA OT= Onoff control Relay <<Contents>> <<Index>>

General Specifications

General Specifications General Specifications Model 0 Digital Indicating Controller GS 0D0C00E General Model 0 Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful

More information

General Specifications

General Specifications General Specifications MODEL UT0 Digital Indicating Controller GS 0D01C00E General Model UT0 Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful

More information

General Specifications

General Specifications General Specifications Model UT Digital Indicating Controller GS 0D01C0E General Model UT Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful

More information

General Specifications

General Specifications General Specifications MODEL UM0 Digital Indicator with Alarms GS 0F0D00E General Model UM0 Digital Indicator with Alarms is a precision alarm instrument with universal input /8DIN. For excellent monitoring

More information

General Specifications

General Specifications General Specifications GS 05F01D01E MODEL UM351 Digital Indicator with Alarms with Active Color PV Display General Model UM351 Digital Indicator with Alarms is a precision alarm instrument provided with

More information

General Specifications

General Specifications General Specifications Model UM350 Digital Indicator with Alarms GS 05F0D00E General Model UM350 Digital Indicator with Alarms is a precision alarm instrument with universal input. For excellent monitoring

More information

General Specifications

General Specifications General Specifications Model UM330 Digital Indicator with Alarms GS 05F0D00E General Model UM330 Digital Indicator with Alarms is a precision alarm instrument with universal input /8DIN. For excellent

More information

General Specifications

General Specifications General Specifications GS 0F01D0E Model UM1 Digital Indicator with Alarms with Active Color PV Display General Model UM1 Digital Indicator with Alarms is a precision 1/8 DIN alarm instrument provided with

More information

General Specifications

General Specifications General Specifications GS 0F01D01E Model UM1 Digital Indicator with Alarms with Active Color PV Display General Model UM1 Digital Indicator with Alarms is a precision alarm instrument provided with universal

More information

General Specifications

General Specifications General Specifications Model UT30 Digital Indicating Controller GS 05D0D00E General Model UT30 Digital Indicating Controller is a highly accurate /8 DIN controller, provided with universal input/ output.

More information

General Specifications

General Specifications General Specifications GS 05D01D01E Model UT351 Digital Indicating Controller with Active Color PV Display General Model UT351 Digital Indicating Controller is a highly accurate 1/4 DIN controller, provided

More information

General Specifications

General Specifications General Specifications MODEL UT50L Limit Controller GS 5DD-0E Overview The UT50L is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user.

More information

General Specifications

General Specifications General Specifications Model UP350 Program Controller GS 05E0D00E General Model UP350 program controller is a precision controller, featuring two program profiles and universal input/output. For easy operation,

More information

General Specifications

General Specifications General Specifications Model UT, UT Temperature Controller GS CE-E GENERAL UT series temperature controllers provide only the functions and size you require for your application. /6 DIN sizes is available.

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup Instruction Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup IM 05D01C02-45E IM 05D01C02-45E 1st Edition Blank Page Introduction Thank you

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control User s Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control IM 05D01C02-41E IM 05D01C02-41E 3rd Edition Blank Page Introduction i Thank you for purchasing

More information

General Specifications

General Specifications General Specifications GS 05D0B00E Model UT750 Digital Indicating Controller (with Custom Computation) General Model UT750 Digital Indicating Controller is an intelligent, microprocessor based digital

More information

Model UP350 Program Controller

Model UP350 Program Controller User s Manual Model UP350 Program Controller User s Manual IM 05E01D02-41E IM 05E01D02-41E 2nd Edition Blank Page Introduction i Thank you for purchasing the UP350 program controller. How to

More information

Models UT350/UT320 Digital Indicating Controllers

Models UT350/UT320 Digital Indicating Controllers User s Manual Models UT350/UT320 Digital Indicating Controllers User s Manual IM 05D01D02-41E IM 05D01D02-41E 4th Edition Blank Page Introduction i Thank you for purchasing the UT350/UT320

More information

Model UT551 Digital Indicating Controller with Active Color PV Display and Embedded Ethernet User s Manual for Single-loop Control

Model UT551 Digital Indicating Controller with Active Color PV Display and Embedded Ethernet User s Manual for Single-loop Control User s Manual Model UT551 Digital Indicating Controller with Active Color Display and Embedded Ethernet User s Manual for Single-loop Control IM 05D01C03-41E IM 05D01C03-41E 4th Edition Introduction

More information

Model UT750 Digital Indicating Controller User s Manual for Cascade Control

Model UT750 Digital Indicating Controller User s Manual for Cascade Control User s Manual Model UT750 Digital Indicating Controller User s Manual for Cascade Control IM 05D01B02-44E IM 05D01B02-44E 3rd Edition Blank Page Introduction i Thank you for purchasing the

More information

General Specifications

General Specifications General Specifications UM33A Digital Indicator with Alarms [Style: S9] Overview The UM33A digital indicator with Alarms employ an easy-to-read, 14-segment large color LCD display, along with navigation

More information

Model UP550 Program Controller User s Manual for Loop Control with PV Switching

Model UP550 Program Controller User s Manual for Loop Control with PV Switching User s Manual Model UP550 Program Controller User s Manual for Loop Control with Switching IM 05E0C0-46E IM 05E0C0-46E 3rd Edition Blank Page Introduction i Thank you for purchasing the UP550

More information

Model UP750 Program Controller User s Manual for Dual-loop Control

Model UP750 Program Controller User s Manual for Dual-loop Control Instruction Manual Model UP750 Program Controller User s Manual for Dual-loop Control IM 05E0B0-5E IM 05E0B0-5E st Edition Blank Page Introduction i Thank you for purchasing the UP750 program

More information

General Specifications

General Specifications General Specifications GS 05P01F31-01EN UT32A Digital Indicating Controller (Entry model) Functional Enhancement Overview The UT32A entry model digital indicating controller is an easily configurable single-loop

More information

How to Install CAUTION. Panel. 150mm. 150mm. Direction to insert the controller Insert the controller into the opening at the front of the panel.

How to Install CAUTION. Panel. 150mm. 150mm. Direction to insert the controller Insert the controller into the opening at the front of the panel. User s IM DDE This manual describes installation, wiring, and other tasks required to make the ler ready for operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to Connect Wires.

More information

indicate that the contacts are available. How to Install CAUTION Panel

indicate that the contacts are available. How to Install CAUTION Panel s Manual IM DCE This manual describes installation, wiring, and other tasks required to make the controller ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install How to Connect

More information

Model UP351 Program Controller

Model UP351 Program Controller User s Manual Model UP351 Program Controller User s Manual IM 05E01D12-41E IM 05E01D12-41E 4th Edition Blank Page Introduction i Thank you for purchasing the UP351 program controller. How to

More information

Model UP550 Program Controller User s Manual for Cascade Primary-loop Control

Model UP550 Program Controller User s Manual for Cascade Primary-loop Control Instruction Manual Model UP550 Program Controller User s Manual for Cascade Primary-loop Control IM 05E0C02-42E IM 05E0C02-42E st Edition Blank Page Introduction i Thank you for purchasing

More information

DIGITAL PROGRAM CONTROLLER

DIGITAL PROGRAM CONTROLLER KP1000 SERIES DIGITAL PROGRAM CONTROLLER The KP1000 series is a 96x96mm digital program controller with the indicating accuracy of ±0.1%, the control cycle of approximately 0.1 seconds and maximum 19 program

More information

Model UT750 Digital Indicating Controller User s Manual for Cascade Primary-loop Control

Model UT750 Digital Indicating Controller User s Manual for Cascade Primary-loop Control User s Manual Model UT750 Digital Indicating Controller User s Manual for Cascade Primary-loop Control IM 05D01B02-42E IM 05D01B02-42E 3rd Edition Blank Page Introduction i Thank you for purchasing

More information

General Specifications

General Specifications General Specifications Model UT350 Digital Indicating Controller GS 05D0D00E General Model UT350 Digital Indicating Controller is a highly accurate /DIN controller provided with universal input/ output.

More information

General Specifications

General Specifications General Specifications GS 05P08D81-01EN UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) Functional Enhancement Overview The UT32A-D/MDL controller is a dual-loop controller

More information

MICRO-CONTROLLER X (48 48 mm)

MICRO-CONTROLLER X (48 48 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION ADVANCED - CONTROLLERS - SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION (ma) OUTPUTS - 4x EVENT OR ALARM OUTPUTS

More information

General Specifications

General Specifications General Specifications GS 05P08D3101EN UT32AD Digital Indicating Controller (Dualloop, Panel Mounting Type) Functional Enhancement Overview The UT32AD dualloop digital indicating controllers employ an

More information

General Specifications

General Specifications General Specifications GS 05P03D21-01EN UM33A Digital Indicator with Alarms Functional Enhancement Overview The UM33A digital indicator with Alarms employ an easy-to-read, 14-segment large color LCD display,

More information

General Specifications

General Specifications General Specifications MODEL UP750 ler GS 5EB0-0E General Model UP750 ler is an intelligent, microprocessor based program controller that has the capacity of 00 program s, ful control capability, custom

More information

SDC40A. DigitroniK TM Digital Indicating Controller RSW. Control unit PID (8) Auto tuning+ Neuro & Fuzzy RUN/READY R/L LSP.

SDC40A. DigitroniK TM Digital Indicating Controller RSW. Control unit PID (8) Auto tuning+ Neuro & Fuzzy RUN/READY R/L LSP. No. CP-SS-580E SDC40A DigitroniK TM Digital Indicating Controller Overview The DigitroniK TM SDC40A is a compact (96mm x 96mm) digital controller. The SDC40A features a wide variety of input options: thermocouples,

More information

UT750. Relay. 150mm. UT s contact. Relay (Use one with a relay coil rating less than the UT s contact rating.) 150mm. Recommended Terminal Lugs

UT750. Relay. 150mm. UT s contact. Relay (Use one with a relay coil rating less than the UT s contact rating.) 150mm. Recommended Terminal Lugs User s Manual IM 5DBE This manual describes installation, wiring, and other tasks required to make the controller ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to

More information

General Specifications

General Specifications General Specifications 35A/32A Digital Indicating Controllers [Style: S1] Overview The 35A/32A digital indicating controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation

More information

General Specifications

General Specifications General Specifications GS 77J0A070E Model VJA7 Distributor (Multifunction) (Isolated Singleoutput and Isolated Dualoutput Types) Overview This plugin type distributor is used in combination with wire type

More information

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E User s Manual Model US1000 Digital Indicating Controller Functions 2nd Edition Introduction This instruction manual describes the functions of the US1000 Digital Indicating Controller in detail. Read

More information

Temperature Controllers E5 J

Temperature Controllers E5 J Temperature Controllers Advanced PID Controller with Fuzzy Logic-Based Adaptive Tuning Provides Optimum Performance Available in 3 standard DIN sizes: Choose 1/4, 1/8 and 1/16 DIN Fuzzy adaptive tuning

More information

Digital Controller Intelligent, User-friendly Digital Controller and Programmer Controlled with ease with a support software which is input via the communication jack on the front panel. Minute adjustment

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

SHIMADEN PROGRAM CONTROLLER

SHIMADEN PROGRAM CONTROLLER Shimaden, Temperature and Humidity Control Specialists C %RH SHIMADEN PROGRAM CONTROLLER approved BASIC FEATURES Full multi-input and multi-range performance User selectable Thermocouple, RTD, V, mv and

More information

SHIMADEN DIGITAL INDICATORS

SHIMADEN DIGITAL INDICATORS Shimaden, Temperature and Humidity Control Specialists C %RH Series SD16A & SHIMADEN DIGITAL INDICATORS approved,ul applied BASIC FEATURES compliance DIN Size 48 x 96 mm ±.3% High Accuracy Indication Large

More information

MICRO-CONTROLLER X (96 96 mm)

MICRO-CONTROLLER X (96 96 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

Single Loop Controller SDC35/36

Single Loop Controller SDC35/36 No. CP SS 180E Single Loop Controller SDC35/36 Features The DigitroniK SDC35/36 is a digital indicating controller featuring multi-range inputs and PID control system using new algorithms "RationaLOOP"

More information

K3P ENG.qxd 23/10/ Pagina 1

K3P ENG.qxd 23/10/ Pagina 1 K3P ENG.qxd 23/10/2003 12.30 Pagina 1 - CLEAR PROGRAM STATUS DISPLAY - DIRECT PROGRAM PARAMETER ADJUSTMENT - 8 INDEPENDENT PROGRAMS - 10 SEGMENTS FOR EACH PROGRAM - "SET - POINT TRACKING " AND "GUARANTEED

More information

DIGITAL INDICATING CONTROLLER

DIGITAL INDICATING CONTROLLER DB00 SERIES DIGITAL INDICATING CONTROLLER The DB00 series is a digital indicating controller with the indicating accuracy of ±0.% and the control cycle of approximately 0. seconds. Various functions including

More information

Ramp/Soak Temperature Controller REX-P250

Ramp/Soak Temperature Controller REX-P250 EX-P0 General The EX-P0 is a high performance ramp/soak controller with a storage capacity of segments in patterns. Each pattern consists of up to segments and patterns can be linked for maximum pattern

More information

DC1010/DC1020/DC1030/DC1040

DC1010/DC1020/DC1030/DC1040 05/0 0-10-10-0-EN Page 1 of DC1010/DC1020/DC100/DC1040 DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of functionality and

More information

General Specifications

General Specifications General Specifications GS 05P01D3181EN 35A/RSP, 32A/RSP Digital Indicating Controller (with Nonisolated Remote Input) Functional Enhancement Overview The 35A/RSP and 32A/RSP are singleloop controller with

More information

General Specifications

General Specifications General Specifications GS 77J01Q08-01E Model VJQ8 Pulse to Analog Converter (Multi-function) (Isolated Single-output and Isolated Dual-output Types) General This plug-in type pulse to analog converter

More information

APPENDIX APPENDIX A 1

APPENDIX APPENDIX A 1 A 1 SPECIFICATIONS Ratings Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 7VA 4VA/2.5W Sensor input Thermocouple

More information

HA400 HA900 HA401 HA901

HA400 HA900 HA401 HA901 A/ R/L R/S High-Speed Digital Controller - or loops HA Series HA00 HA900 HA0 HA90 General Description he HA series are digital PID controllers with a high speed sampling time of ms (0.0 sec) with high-resolution

More information

General Specifications

General Specifications General Specifications GS 05P01D3101EN 35A, 32A Digital Indicating Controller (Panel Mounting Type) Functional Enhancement Overview The 35A and 32A digital indicating controllers employ an easytoread,

More information

MICRO-CONTROLLER X (48 96 mm)

MICRO-CONTROLLER X (48 96 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

DigitroniK TM Digital Indicating Controller SDC20

DigitroniK TM Digital Indicating Controller SDC20 No. CP SS 47E DigitroniK TM Digital Indicating Controller SDC The DigitroniK SDC is a compact digital controller with multi-range and PID autotuning systems for various inputs, with time proportional (on/off)

More information

High Performance Process & Temperature Controllers

High Performance Process & Temperature Controllers C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal

More information

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER MULTI - FUNTION ONTROLLERS - SMART TUNE - PID ONTROL - UNIVERSAL, 3 WIRE - T, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER WITH POTENTIOMETER FEEDBAK -

More information

UP550 O.C. Relay. UP s contact. 150mm. Relay. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs

UP550 O.C. Relay. UP s contact. 150mm. Relay. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs s Manual IM ECE This manual describes installation, wiring, and other tasks required to make the controller ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to Connect

More information

Basic module X-TIO FAIL/RUN RX/TX EVENT1 EVENT2 EVENT3 EVENT4 X10 FAIL/RUN RX/TX EVENT1 EVENT2 EVENT3 EVENT4 X10. Communications (RS-485)

Basic module X-TIO FAIL/RUN RX/TX EVENT1 EVENT2 EVENT3 EVENT4 X10 FAIL/RUN RX/TX EVENT1 EVENT2 EVENT3 EVENT4 X10. Communications (RS-485) Module type High-speed Digital ler SRX SRX General Description The SRX is a module type digital controller with a super high speed sampling of control updating cycle time of ms (0.0 sec). Dual loop control

More information

General Specifications

General Specifications General Specifications Signal Conditioner Cards OUTLINE Signal Conditioner Cards, which interface to the process, are installed in Signal Conditioner Nests. [Release 6] The signal conditioner cards can

More information

General Specifications

General Specifications General Specifications GS 05P01C3101EN 55A, 52A Digital Indicating Controller (Panel Mounting Type) Functional Enhancement Overview The 55A and 52A digital indicating controllers employ an easytoread,

More information

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional) Temperature Controller with Built-in SSR SB SB General Description SB is a channel temperature controller with Built-in SSR (Solid state relay) designed for flexible heating solutions such as heat trace

More information

Process and Temperature Controllers

Process and Temperature Controllers Process and Temperature Controllers www.durexindustries.com Input Input Input break action Input short action Sampling time Influence of external resistance Influence of lead resistance PV bias Input

More information

SHIMADEN DIGITAL INDICATOR

SHIMADEN DIGITAL INDICATOR Shimaden, Temperature and Humidity Control Specialists C %RH Series SD24 & KR16A SHIMADEN DIGITAL INDICATOR BASIC FEATURES ohigh Accuracy ±0.1% FS+1 digit o1/1000ºc Resolution Indication Possible (Pt input

More information

DIGITAL THERMOMETER Digital Thermometer FEATURES INDEX RECORDERS

DIGITAL THERMOMETER Digital Thermometer FEATURES INDEX RECORDERS Digital Thermometer 23 88 350 mm 3 kg (8-5/8 3-/2 3-3/4" 6.6 lbs) The Digital Thermometer has 6 ranges of temperature sensors and measuring functions of DC V and Ω. YOKOGAWA-original A/D converter (feedback

More information

General Specifications

General Specifications General Specifications 35A/32A Digital Indicating Controllers [Style: S5] Overview The 35A/32A digital indicating controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation

More information

UP750. Relay. UP s contact. Relay. 150mm. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs

UP750. Relay. UP s contact. Relay. 150mm. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs s Manual IM EBE This manual describes installation, wiring, and other tasks required to make the ler ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to Connect Wires.

More information

DIGITAL THERMOMETER VIEW RECORDERS Digital Thermometer FEATURES

DIGITAL THERMOMETER VIEW RECORDERS Digital Thermometer FEATURES Digital Thermometer High-Accuracy Reference Junction Compensation: Compensation accuracy (±0.2 C) Input terminals are provided on both front and rear panels, and an input site is switch selectable. The

More information

General Specifications

General Specifications General Specifications GS J0U0-0E Model MU Universal Temperature Converter (Free Range Type) General The MU is a plug-in type universal temperature converter that converts input signal (thermocouple, RTD

More information

Excellent low-cost Process & Temperature Controllers

Excellent low-cost Process & Temperature Controllers C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200

More information

CompoBus/D-type Digital Controller

CompoBus/D-type Digital Controller CompoBus/D-type Digital Controller Digital Controller for the CompoBus/D and Conforming the DeviceNet Conforms the DeviceNet and connects a Programmable Controller without any programming. High performance

More information

Fuzzy Temperature Controllers E5EF

Fuzzy Temperature Controllers E5EF Fuzzy Temperature lers EEF / DIN lers Combine Fuzzy and PID For Fast Response to Process Disturbances dvanced PID control for optimal response during startup and steadystate operation Fuzzy and PID control

More information

MODEL: M2XU MODEL: M2XU [1][2] [3][4]

MODEL: M2XU MODEL: M2XU [1][2] [3][4] Super-mini Signal Conditioners Mini-M Series UNIVERSAL TRANSMITTER (PC programmable) Functions & Features Accepts direct inputs from various sensors and provides a standard process signal I/O types and

More information

General Specifications

General Specifications General Specifications Signal Conditioner Cards GS 33K50H80-50E OUTLINE Signal Conditioner Cards, which interface to the process, are installed in Signal Conditioner Nests. [Release 5] The signal conditioner

More information

DigitroniK Digital Indicating Controller SDC30

DigitroniK Digital Indicating Controller SDC30 No. CPSS86E DigitroniK Digital Indicating Controller SDC0 The DigitroniK SDC0 is a compact (48 mm x 96 mm) digital indicating controller offering standard PID control and an advanced neural/fuzzy PID that

More information

6/12/24 Dot Printing Model Smart Recorder SRF206/212/224

6/12/24 Dot Printing Model Smart Recorder SRF206/212/224 No. CP-SS-E // Dot Printing Model Smart Recorder SRF0// The Smart Recorder SRF 0// Dot Printing Model accepts DC voltage, thermocouple, resistance temperature detector (RTD), communications and ON/OFF

More information

DigitroniK TM Digital Indicating Controller SDC40A

DigitroniK TM Digital Indicating Controller SDC40A No. CPSS580E DigitroniK TM Digital Indicating Controller SDC40A The DigitroniK TM SDC40A is a compact (96mm x 96mm) digital controller. The SDC40A features a wide variety of input options: thermocouples,

More information

General Specifications

General Specifications General Specifications GS 77J04H0-0E Model MH Isolator (Free Range Type) General The MH is a plug-in type isolator that converts DC current or DC voltage signals into isolated DC current or DC voltage

More information

PROGRAM CONTROLLER OUTLINE

PROGRAM CONTROLLER OUTLINE Specifications Sheet No.SPEC-1232E (1st Edition) EC1200A PROGRAM CONTROLLER OUTLINE The EC1200 can, totally and with high precision, control and monitor such factors as temperature, temperature balance

More information

Fuzzy Temperature Controllers E5AF

Fuzzy Temperature Controllers E5AF Fuzzy Temperature Controllers 1/4 DIN Controller Combines Fuzzy and PID Control For Fast Response to Process Disturbances Advanced PID control provides optimal response during start-up and steadystate

More information

MODEL: M6SXU MODEL: M6SXU [1][2] [3][4]

MODEL: M6SXU MODEL: M6SXU [1][2] [3][4] Tension-Clamp Ultra-Slim Signal Conditioners M6S Series UNIVERSAL TRANSMITTER (PC programmable) Functions & Features Maintenance-free tension clamp connection Universal input (mv, V, ma, T/C, RTD and potentiometer)

More information

PROGRAMMABLE CONTROLLER

PROGRAMMABLE CONTROLLER Shimaden, Temperature and Humidity Control Specialists C %RH Series FP2 PROGRAMMABLE CONTROLLER approved UL applied BASIC FEATURES 2-channel controller (Basic type: 1-channel controller) Independent 2-loop

More information

DCP551B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning.

DCP551B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning. No. CP-SS-1852E DCP551B Mark II DIGITRONIK TM Programmable Controller Overview The DIGITRONIK TM DCP551B Mark II is a high-function programmable controller supporting up to 99 program patterns to which

More information

MODEL: R30US4. Remote I/O R30 Series

MODEL: R30US4. Remote I/O R30 Series Remote I/O R30 Series UNIVERSAL INPUT MODULE (4 points, isolated) Functions & Features 4 points universal input I/O module Isolation between the channels Input range of each channel is individually adjustable

More information

SRX. General Description. Features. Module type High-speed Digital Controller SRX. Multi-Zone Space-Saving. High-speed Feedback Control

SRX. General Description. Features. Module type High-speed Digital Controller SRX. Multi-Zone Space-Saving. High-speed Feedback Control SX General Description The SX is a module type digital controller with a super high speed sampling of control updating cycle time of ms (0.0 sec). Dual loop control can be performed with a single compact

More information

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification 01 May 20 30-10-10--EN Page 1 of DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of

More information

REX-F400 REX-F700 REX-F900

REX-F400 REX-F700 REX-F900 REX-F REX-F REX-F General The F series controller provides precise control with high accuracy of.% full scale and short sampling time of. second. ewly developed and unique logic, rilliant PID control and

More information

Process displays For standard signals, temperature, resistance measurement

Process displays For standard signals, temperature, resistance measurement Features Inputs: Voltage ±10 V, ±200 V / Current ±20 ma / thermocouples J,K,T,N,Pt100,Pt1000 / resistance measurement / potentiometer Display range can be linearised Two limits output Min, Max functions

More information

Network Instrumentation Module Controller Module NX-D15/25/35

Network Instrumentation Module Controller Module NX-D15/25/35 No. CP-SS-1861E Network Instrumentation Module Controller Module NX-D15/25/35 Overview Network Instrumentation Modules make optimal distributed configuration a reality. Distributed modules execute cooperative

More information

SHIMADEN DIGITAL INDICATORS

SHIMADEN DIGITAL INDICATORS Shimaden, Temperature and Humidity Control Specialists C %RH Series SD16 & SHIMADEN DIGITAL INDICATORS & NRTL /C approved BASIC FEATURES DIN Size 48 x 96 mm ±.3% High Accuracy Indication Large 2 mm bright

More information

DCP552B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning.

DCP552B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning. No. CP-SS-1853E DCP552B Mark II DIGITRONIK TM Programmable Controller Overview The DIGITRONIK TM DCP552B Mark II is a high-function programmable controller supporting two channels (up to 49 program patterns

More information

SDC45V/46V. DigitroniK TM Digital Indicating Controller. Control Operation

SDC45V/46V. DigitroniK TM Digital Indicating Controller. Control Operation No. CP-SS-848E SDC45V/46V DigitroniK TM Digital Indicating Controller Overview The SDC45V/46V DigitroniK is a highly advanced, highprecision compact digital indicating controller, featuring a 5-digit indicator,

More information

General Specifications

General Specifications 35A/MDL, 32A/MDL Controllers General Specifications l tiona Func ment nce Enha (Mount on DIN Rail) GS 05P0D80EN n Overview The 35A/MDL and 32A/MDL controllers can be mounted in a panel. A ladder sequence

More information

AK48 SPECIFICATIONS APPLICATIONS GENERALS FEATURES. 1/16 DIN Process controller

AK48 SPECIFICATIONS APPLICATIONS GENERALS FEATURES. 1/16 DIN Process controller /6 DIN Process controller AK48 Three control types The user can select among three different control actions: ON/OFF, PID or PID ( PI with automatic derivative action). PID and PID include two differente

More information