Model UP750 Program Controller User s Manual for Dual-loop Control

Size: px
Start display at page:

Download "Model UP750 Program Controller User s Manual for Dual-loop Control"

Transcription

1 Instruction Manual Model UP750 Program Controller User s Manual for Dual-loop Control IM 05E0B0-5E IM 05E0B0-5E st Edition

2 Blank Page

3 <Toc> <Rev> Introduction i Thank you for purchasing the UP750 program controller. How to Use the Manuals Purpose Manual Title Description Setup. Installation Describes the tasks (installation, wiring, and others) required to make the controller ready for operations. Basic operation. Initial Settings Describes examples of setting input types and control output types. Making settings described herein and program creation in 3. Programming allows you to carry out basic control. Program creation 3. Programming Describes examples of creating basic programs. The use of the program pattern setup charts included in the 3.7 Program Pattern Setup Charts is recommended. General understanding of programming operations Operating procedures and troubleshooting Brief operation Function description and setpoint recording 3.5 Program Parameter Map 3.6 Lists of Program Parameter 4. Operations 6. Parameter Map 6. List of Parameters Contains a parameter map that serves as a guide to creating programs. Also includes a brief explanation of the functions of program parameters. Describes key operation sequences. For operation control through external contact inputs, see.5 Terminal Wiring Diagrams. Contains the parameter map used as a guideline for setting parameters. Briefly describes the functions of parameters. In addition, each parameter table has a User Setting column, where you can record your setpoints when setting them in the controller. Controllers Applicable to Dual-loop Control The specification codes of the UP750 applicable to dual-loop control are given in the table below. UP UP750-5 Regarding This User s Manual () This manual should be provided to the end user. Keep an extra copy or copies of the manual in a safe place. () Read this manual carefully to gain a thorough understanding of how to operate this product before starting operation. (3) This manual describes the functions of this product. Yokogawa M&C Corporation (hereinafter simply referred to as Yokogawa) does not guarantee the application of these functions for any particular purpose. (4) Under absolutely no circumstances may the contents of this manual, in part or in whole, be transcribed or copied without permission. (5) The contents of this manual are subject to change without prior notice. (6) Every effort has been made to ensure that the details of this manual are accurate. However, should any errors be found or important information be omitted, please contact your nearest Yokogawa representative or our sales office. Media No. IM 05E0B0-5E (CD) st Edition : May 000 (YK) All Rights Reserved Copyright 000, Yokogawa M&C Corporation IM 05E0B0-5E st Edition : May 3,000-00

4 <Toc> <Rev> ii Safety Precautions The following symbol is indicated on the controller to ensure safe use. CAUTION This symbol on the controller indicates that the operator must refer to an explanation in the instruction manual in order to avoid the risk of injury or death of personnel or damage to the instrument. The manual describes how the operator should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life. The following symbols are used in the hardcopy user s manuals and in the user s manual supplied on the CD-ROM. NOTE Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure. IMPORTANT Draws attention to information that is essential for understanding the operation and/or features of the controller. Regarding Force Majeure Yokogawa M&C Corporation assumes no liability for any loss or damage, direct or indirect, caused by the use of or unpredictable defects of the product. IM 05E0B0-5E st Edition : May 3,000-00

5 <Int> <Rev> Toc- Model UP750 Program Controller User s Manual for Dual-loop Control IM 05E0B0-5E st Edition CONTENTS. Installation Model and Suffix Codes How to Install How to Connect Wires Hardware Specifications Terminal Wiring Diagrams Initial Settings Names and Functions of Front Panel Parts Setting UP mode (Setting First at Power-on) Changing UP mode Setting Input Types of Loop and Loop Setting Control Output Types of Loop and Loop Initializing Parameters Programming Overview of Program Patterns Example of Program Pattern Setup Charts Creating Program Patterns Changing Program Patterns Program Parameter Map Lists of Program Parameters Program Pattern Setup Charts Explanation of Program Functions Operations Monitoring-purpose Operating Displays Available during Operation Performing/Canceling Auto-tuning of Loop Performing/Canceling Auto-tuning of Loop Setting PID Manually of Loop Setting PID Manually of Loop Selecting the Program Pattern Number (PT.No) Switching between RUN and RESET Modes Switching between AUTO and MAN of Loop Switching between AUTO and MAN of Loop Manipulating Control Output during Manual Operation of Loop IM 05E0B0-5E st Edition : May 3,000-00

6 <Int> <Rev> Toc- 4. Manipulating Control Output during Manual Operation of Loop Enabling/Disabling the Hold Mode of Program Operation Changing Program Setpoints when in Hold Mode Executing the Advance Function Switching to Local-mode (LOCAL) Operation Changing Setpoints during Local-mode Operation Troubleshooting and Maintenance Troubleshooting Maintenance Cleaning Replacing Brackets Attaching Terminal Cover Replacing Parts with a Limited Service Life Replacing Control Output Relays Parameters Parameter Map Lists of Parameters Function Block Diagram and Descriptions IM 05E0B0-5E st Edition : May 3,000-00

7 <Toc> <. Installation> -. Installation This chapter describes installation, wiring, and other tasks required to make the controller ready for operation.. Model and Suffix Codes Before using the controller, check that the model and suffix codes match your order. Model Suffix Code Description UP750 Program controller (provided with Custom Computing Function*) Type -0 Single-loop type -5 Dual-loop type Optional functions 0 None With communication, auxiliary analog input Check that the following items are provided: Program controller (of ordered model)... Brackets (mounting hardware)... pair Unit label... User s Manuals for Single-loop Control... 7 (A size) User s Manual (Reference) (CD-ROM version)... * Using an optional custom computation building tool (Model LL00-E0) that runs on a personal computer, you can build a variety of computations (e.g., four arithmetic operations, logical operations, ten-segment linearizer computations, temperature correction factor computations, and pressure correction factor computations) to be applied to the controller s I/O signals. IM 05E0B0-5E st Edition : May 3,000-00

8 <Toc>. How to Install <. Installation> - NOTE To install the controller, select a location where:. no one may accidentally touch the terminals,. mechanical vibrations are minimal, 50mm 3. corrosive gas is minimal, 4. temperature can be maintained at about 3 C and 50mm 50mm the fluctuation is minimal, 50mm 5. no direct radiant heat is present, 6. no magnetic disturbances are caused, 7. no wind blows against the terminal board (reference junction compensation element), 8. no water is splashed, 9. no flammable materials are around, Never place the controller directly on flammable items or equipment. If the controller has to be installed close to flammable items or equipment, be sure to provide shielding panels all around the controller, at least 50 mm away from every side; the panels should be made of either.43 mm-thick metal-plated steel plates or.6 mmthick uncoated steel plates. Installation Position Install the controller at an angle within 30 from horizontal with the front panel facing upward. Do not install it facing downward. The position of right and left sides should be horizontal. Front panel of controller Must not exceed Rear of controller IM 05E0B0-5E st Edition : May 3,000-00

9 <Toc> <. Installation> -3 External Dimensions and Panel Cutout Dimensions UP750 Unit: mm Large bracket E E 7 min. [(N-) 96+9] Small bracket to 0 mm (Panel thickness) General installation Side-by-side close installation (53) min. N stands for the number of controllers to be installed. However, the measured value applies if N (5) IM 05E0B0-5E st Edition : May 3,000-00

10 <Toc> How to Install <. Installation> -4 Turn off the power to the controller before installing it on the panel because there is a possibility of electric shock. CAUTION After opening the mounting hole on the panel, follow the procedures below to install the controller:. Insert the controller into the opening from the front of the panel so that the terminal board on the rear is at the far side.. Set the brackets in place on the top and bottom of the controller as shown in the figure below, then tighten the screws of the brackets. Take care not to overtighten them. Panel Large bracket (top mounting hardware) Direction to insert the controller Insert the controller into the opening at the front of the panel. Terminal board Insert a screwdriver into the brackets to tighten the screws. Small bracket (bottom mounting hardware) IM 05E0B0-5E st Edition : May 3,000-00

11 <Toc> <. Installation> -5.3 How to Connect Wires CAUTION ) Before carrying out wiring, turn off the power to the controller and check that the cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. ) Wiring must be carried out by personnel who have basic electrical knowledge and practical experience. NOTE ) Provide power from a single-phase instrument power supply. If there is a lot of noise in the power line, insert an insulating transformer into the primary side of the line and use a line filter (recommended part: ZAC05-00U from TDK) on the secondary side. As a countermeasures against noise, do not place the primary and secondary power cables close to each other. ) For thermocouple input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires. The cables to be used for wiring, terminal specifications, and recommended parts are as shown below. 3) Control output relays may be replaced. However, because they have a life of 00,000 times that of the resistance load, use auxiliary relays to turn on/off a load. 4) The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load. For DC Relay Wiring For AC Relay Wiring UP750 External DC power supply UP750 External AC power supply O.C Relay R R UP s contact Relay (Use one with a relay coil rating less than the UP s contact rating.) Diode (Mount it directly to the relay coil terminal (socket).) UP s contact Relay (Use one with a relay coil rating less than the UP s contact rating.) CR filter (Mount it directly to the relay coil terminal (socket).) IM 05E0B0-5E st Edition : May 3,000-00

12 <Toc> Cable Specifications and Recommended Cables <. Installation> -6 Purpose Name and Manufacturer Power supply, grounding, relay contact outputs 600 V C insulated wires, JIS C 3307, 0.9 to.0 mm Thermocouple Shielded compensating lead wires, JIS C 60, X- - - (See Yokogawa Electric s GS 6BU-E.) RTD Shielded wires (three conductors), UL48 (Hitachi Cable) Other signals Shielded wires Recommended Terminal Lugs Applicable wire size Tightening torque 0.3 to.65 mm 0.8 N m or less 3.7mm 3.7mm 7 mm or less or 7 mm or less Terminal Covers Target Model Part Number Sales Unit For UP750 T95YD IM 05E0B0-5E st Edition : May 3,000-00

13 <Toc> <. Installation> -7.4 Hardware Specifications Input Signals Number of inputs: (Loop: terminals /Loop: terminals ) Input type: Universal input system. The input type can be selected with the software. Sampling period: Can be selected from 00, 00 and 500 ms. Burnout detection: Functions at TC, RTD, standard signal (0.4 to V or to 5 V) Upscale, downscale, and off can be specified. For standard signal, burnout is determined to have occurred if it is 0. V or less. Input bias current: 0.05 A (for TC or RTD b-terminal) Measurement current (RTD): About 0.3 ma Input resistance: M or more for thermocouple or mv input About M for DC voltage input Loop input of 0.00 to.5 V range is about 8 Allowable signal source resistance: 50 or less for thermocouple or mv input Effects of signal source resistance: 0. V/ or less k or less for DC voltage input Effects of signal source resistance: About 0.0%/00 Allowable wiring resistance: for RTD input Maximum 50 /wire: Conductor resistance between three wires should be equal However, 0 /wire for a maximum range of to 50.0 C. Wire resistance effect: 0. C/0 Allowable input voltage: 0 V DC for thermocouple, mv, or RTD input 0 V DC for DC voltage input Noise rejection ratio: 40 db (50/60 Hz) or more in normal mode 0 db (50/60 Hz) or more in common mode Reference junction compensation error:.0 C (5 to 35 C).5 C (0 to 5 C, 35 to 50 C) Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples and RTD Auxiliary Analog Input Signals Available only for controllers with auxiliary analog input terminals. Number of inputs: (terminals - ) Input type: Settable in a range of 0-, 0-0, , or -5 V DC Sampling period: 00, 00 and 500 ms The sampling period of a remote input signal is associated with the input s sampling period. Input resistance: About M Input accuracy: 0.3% digit of input span for 0 to V DC 0.% digit of input span for 0 to 0 V DC 0.375% digit of input span for 0.4 to.0 V DC 0.3% digit of input span for to 5 V DC Under standard operating conditions (3 C, 55 0% RH, power frequency of 50/60 Hz) IM 05E0B0-5E st Edition : May 3,000-00

14 <Toc> <. Installation> -8 Loop Power Supply Power is supplied to a two-wire transmitter. (5 V DC: terminals 4-5 ) A resistor (0 to 50 ) connected between the controller and transmitter converts a current signal into a voltage signal, which is then read via the input terminal. Supply voltage: 4.5 to 8.0 V DC, max. ma (provided with a protection circuit against a field short-circuit) Retransmission Output Either, program setpoint, or control output is output. Either the retransmission output or the loop power supply can be used with terminals 4-5. Number of outputs: or (terminals 4-5, terminals 6-7 ) Output signal: 4-0, 0-0, 0-4, or 0-0 ma DC (where, outputting signal levels of less than 0 ma is not feasible) Load resistance: 600 or less Output accuracy: 0.% of span ( 5% of span for ma or less.) Under standard operating conditions (3 C, 55 0% RH, power frequency of 50/ 60 Hz) Control Output Universal output system, The output type can be selected with the software. Current output (Loop: terminals 6-7 ; heating-side output: terminals 6-7, cooling-side output: terminals 4-5 ) (Loop: terminals ; heating-side output: terminals 46-47, cooling-side output: Not selected) Number of outputs Output signal Load resistance Output accuracy or 3 (two for heating/cooling type), switched between a voltage pulse output and current output. 4-0, 0-0, 0-4, or 0-0 ma DC 600 or less 0.% of span ( 5% of span for ma or less) Under standard operating conditions (3 C, 55 0% RH, power frequency of 50/60 Hz) Voltage pulse output (Loop: terminals 6-7 ; heating-side output: terminals 6-7, cooling-side output: Not selected) (Loop: terminals ; heating-side output: terminals 46-47, cooling-side output: Not selected) IM 05E0B0-5E st Edition : May 3,000-00

15 <Toc> <. Installation> -9 Relay contact output (Loop: terminals ; heating-side output: terminals - - 3, cooling-side output: terminals 4-7 ) (Loop: terminals ; heating-side output: terminals , cooling-side output: terminals 5-7 ) Number of outputs Output signal Contact rating Resolution or 4 (two for heating/cooling type) Three terminals (NC, NO, and common) 50 V AC or 30 V DC, 3 A (resistance load) 0 ms or 0.% of output, whichever is larger Contact Inputs Purpose: Program pattern no. selection, and run/reset switching Number of inputs: 7 points Input type: Non-voltage contact or transistor open collector input Input contact rating: V DC, 0 ma or more On/off determination: For non-voltage contact input, contact resistance of k or less is determined as on and contact resistance of 0 k or more as off. For transistor open collector input, input voltage of V or less is determined as on and leakage current must not exceed 00 A when off. Minimum status detection hold time: input s sampling period 3 Contact Outputs Purpose: Event output, FAIL output, and others Number of outputs: 7 points Relay contact rating: 40 V AC, A, or 30 V DC, A Transistor contact rating: 4 V DC, 50 ma Display Specifications display: 5-digit, 7-segment, red LEDs, character height of 0 mm Setpoint display: 3 8 dot LCD with back lighting Status indicating lamps: LEDs Safety and EMC Standards Safety: Compliant with IEC00-: 990 and EN600-: 99 Approved by CSA00 CSA00 installation category (overvoltage category) : CATII (IEC00-) Approved by UL508 EMC standards: This instrument complies with the following EMC standards (the instrument continues to operate at a measuring accuracy of within 0% of the range during tests): - EMI (emission), EN550: Class A Group - EMS (immunity), EN5008-: 995 IM 05E0B0-5E st Edition : May 3,000-00

16 <Toc> <. Installation> -0 Construction, Installation, and Wiring Construction: Only the front panel is dust-proof and drip-proof (protection class IP55) For side-by-side close installation the controller loses its dust-proof and drip-proof protection. Material: ABS resin and polycarbonate Case color: Black Weight: About kg or less Dimensions: 96 (W) 96 (H) 00 (depth from panel face) mm Installation: Panel-mounting type. With top and bottom mounting hardware ( each) Panel cutout dimensions: 9 0 (W) 9 0 (H) mm Installation position: Up to 30 upward facing (not designed for facing downward) Wiring: M3.5 screw terminals (for signal wiring and power/ground wiring as well) Power Supply Specifications Power supply: Rated voltage of 00 to 40 V AC ( 0%), 50/60 Hz Power consumption: Max. 0 VA (8.0 W max.) Data backup: Lithium cell with life expectancy of 0 years Withstanding voltage - Between primary terminals* and secondary terminals**: At least 500 V AC for minute (Note) - Between primary terminals* and grounding terminal: At least 500 V AC for minute (Note) - Between grounding terminal and secondary terminals**: At least 500 V AC for minute - Between secondary terminals**: At least 500 V AC for minute * Primary terminals indicate power terminals and relay output terminals ** Secondary terminals indicate analog I/O signal, voltage pulse output, and contact input terminals Note: The withstanding voltage is specified as 300 V AC per minute to provide a margin of safety. Insulation resistance: 0 M or more at 500 V DC between power terminals and grounding terminal Grounding: Class 3 grounding (grounding resistance of 00 or less) IM 05E0B0-5E st Edition : May 3,000-00

17 <Toc> <. Installation> - Signal Isolations Loop input terminals: Isolated from other input/output terminals. Not isolated from the internal circuit. Loop input terminals: Isolated from loop input terminals, other input/output terminals and internal circuit. Auxiliary analog input terminals: Isolated from other input/output terminals and the internal circuit. 5 V DC loop power supply terminals: Not isolated from analog current output and voltage pulse control output. Isolated from other input/output terminals and internal circuit. Analog output terminals (for control output and retransmission): Not isolated between analog outputs and from 5 V DC loop power supply and voltage pulse control output. Isolated from other input/output terminals and internal circuit. Voltage pulse control output terminals: Not isolated from analog outputs and 5 V DC loop power supply. Isolated from other input/output terminals and internal circuit. Relay contact control output terminals: Isolated between contact output terminals and from other input/output terminals and internal circuit. Contact input terminals: Not isolated between contact input terminals and from communication terminals. Isolated from other input/output terminals and internal circuit. Relay contact output terminals: Not isolated between relay contact outputs. Isolated from other input/output terminals and internal circuit. Transistor contact output terminals: Not isolated between transistor contact outputs. Isolated from other input/output terminals and internal circuit. RS-485 communication terminals: Not isolated from contact input terminals. Isolated from other input/output terminals and internal circuit. Power terminals: Isolated from other input/output terminals and internal circuit. Grounding terminals: Isolated from other input/output terminals and internal circuit. IM 05E0B0-5E st Edition : May 3,000-00

18 <Toc> <. Installation> - Environmental Conditions Normal operating conditions: Ambient temperature: 0 to 50 C (40 C or less for side-by-side close installation) Temperature change rate: 0 C/h or less Ambient humidity: 0 to 90% RH (no condensation allowed) Magnetic field: 400 A/m or less Continuous vibration at 5 to 4 Hz: Full amplitude of. mm or less Continuous vibration at 4 to 50 Hz: 4.9 m/s or less Short-period vibration: 4.7 m/s, 5 seconds or less Shock: 4.7 m/s or less, ms Installation height: Height above sea level of 000 m or less Warm-up time: 30 minutes or more after power on Transportation and storage conditions: Temperature: -5 to 70 C Temperature change rate: 0 C/h or less Humidity: 5 to 95% RH (no condensation allowed) Effects of changes in operating conditions - Effects from changes in ambient temperature: - On voltage or thermocouple input, V/ C or 0.0% of F.S./ C, whichever is larger - On auxiliary analog input, 0.0% of F.S./ C - On RTD input, 0.05 C/ C (ambient temperature) or less - On analog output, 0.05% of F.S./ C or less - Effects from power supply fluctuation (within rated voltage range) - On remote input, V/0 V or 0.0% of F.S./0 V, whichever is larger - On analog output, 0.05% of F.S./0 V or less IM 05E0B0-5E st Edition : May 3,000-00

19 <Toc> <. Installation> -3.5 Terminal Wiring Diagrams NOTE Do not use unassigned terminals as relay terminals. Terminal wiring diagrams are shown on and after the next page. IM 05E0B0-5E st Edition : May 3,000-00

20 IM 05E0B0-5E st Edition : May 3, UP750 Dual-loop Control (Model UP750-5 ) Loop input TC input NOTE Installation category (overvoltage category): II (IEC00-) * Factory-set to TC type-k. See. Initial Settings. RTD input 4 A 4 b 43 B mv/v input Power supply Power supply 8 9 L N 0 CAUTION Allowable range: V AC ( 0%) (free voltage) 50/60 Hz shared Relay Transistor event output event output Instrument alarm output Common Time event output Time event output Time event 3 output Time event 4 output Common Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. External contact outputs DO 6 DO 5 DO3 4 COM 7 DO4 34 DO DO6 3 DO7 COM 35 Relay contact rating: 40 V AC, A 30 V DC, A (resistance load) Transistor contact rating: 4 V DC, 50 ma Loop control output Current/voltage Relay contact output pulse output 0-0mADC, 4-0mADC Voltage pulse ( V) Loop control output Relay contact output NC NO COM Retransmission output * Default: Unspecified retransmission type 0-0mADC, 4-0mADC Default: 4-0 ma DC Note: Select this option from the OT parameter. Contact rating: 50 V AC, 3 A 30 V DC, 3 A (resistance load) Contact rating: 50 V AC, 3 A 30 V DC, 3 A (resistance load) * Retransmission output is available only when relay is selected as the Loop control output. UP NC NO COM Communication Communication (PSL) High performance RS-485 communication RS-485 communication SDB(+) SDA(-) RDB(+) RDA(-) SG (PSL) RDB(+) RDA(-) SG Loop control output * Wiring can only be carried out for controllers with communication functions. Current/voltage pulse output 0-0mADC, 4-0mADC * The functions of the external contact outputs are the defaults for dual-loop control. To change the functions, reconfigure the contact output registration setup parameters. OT=0 Correspondence between parameter OT and Loop control output types OT= OT= OT=3 Voltage pulse ( V) * OT is a setup parameter. You can change the settings of the parameter OT to change the Loop control output types. See. Initial Settings. Time proportional control Time proportional control Relay output Voltage pulse output (terminals, and ) (terminals and ) 3 OT=0 Note: Select this option from the OT parameter. 6 7 OT= Current output (terminals and ) 6 7 Auxiliary analog input + - Correspondence between parameter OT and Loop control output types OT= Specify in a range of -5 V DC, 0- V DC, or 0-0 V DC. On-off control Relay output (terminals, and ) 3 * OT is a setup parameter. You can change the settings of the parameter OT to change the Loop control output types. See. Initial Settings. Time proportional control Time proportional control Relay output Voltage pulse output (terminals, and ) (terminals and ) Current output (terminals and ) OT=3 Default: -5 V DC On-off control Relay output (terminals, and ) Loop input * Not configured at factory TC input * Wiring can only be carried out for controllers with auxiliary analog input. Note: Select this option from the OT parameter. * Retransmission output is available only when relay is selected as the Loop control output type. Retransmission output Default: Unspecified retransmission type 0-0mADC, 4-0mADC Default: 4-0 ma DC before shipment. See. Initial Settings. RTD input A b 3 B mv/v input Retransmission output * or 0-0 ma DC Default: 4-0 ma DC 5 V DC loop power supply* V DC ( ma DC max.) Receiving 4-0 ma DC Current * When receiving 4-0 ma DC current signals, set the input type to -5 V DC (setpoint 4 ). NOTE Signals with the Controller Ω 4-0mA Note: Connecting a 50 Ω resistor to the terminals is optional. Model: X (resistor with M3.5 crimp-on terminal lugs) Installation category (overvoltage category): II (IEC00-) * Factory-set to retransmission. Load resistance: 600 Ω or less * Retransmission output is not available if a 5 V DC loop power supply is used. * The functions of the external contact inputs are the defaults for dual-loop control. To change the functions, reconfigure the contact input registration setup parameters. External contact inputs UP +5V DI DI 9 +5V DI 8 DI +5V 8 DI3 40 DI3 +5V 40 DI4 DI V 39 Switch between the ON and OFF states of the DI to DI4 contact inputs to select from program pattern numbers to 5. (Select a number during a RESET state.) DI ON ON OFF ON ON OFF ON ON OFF ON ON DI ON ON ON ON ON ON ON ON DI3 ON ON ON ON ON ON ON ON DI4 ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Start of program operation when DI5 changes from OFF to ON Stop of program operation when DI6 changes from OFF to ON Start of local-mode operation when DI7 changes from OFF to ON Common Contact rating: V DC, 0 ma or more Contact DI5 DI V 38 DI6 DI V 37 DI7 DI COM COM 0 0 Transistor contact <Toc> <. Installation> -4

21 IM 05E0B0-5E st Edition : May 3, UP750 Dual-loop Heating/Cooling Control (Model UP750-5 ) IMPORTANT Change the setting of the control output type (OT and OT) parameters to the Heating/Cooling Control. Loop input TC input NOTE Installation category (overvoltage category): II (IEC00-) Relay contact rating: 40 V AC, A 30 V DC, A (resistance load) Transistor contact rating: 4 V DC, 50 ma * Factory-set to TC type-k. See. Initial Settings. 4 A 4 b 43 B mv/v input Power supply Power supply 8 9 Relay Transistor RTD input L N 0 Loop heating-side control output Current/voltage Relay contact output pulse output Loop heating-side control output Relay contact output NC NO COM Contact rating: 50 V AC, 3 A 30 V DC, 3 A (resistance load) CAUTION Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock. Allowable range: V AC ( 0%) (free voltage) 50/60 Hz shared External contact outputs DO 6 DO 5 DO3 4 COM 7 DO4 34 DO DO6 3 DO Retransmission output * Default: Unspecified retransmission type Default: 4-0 ma DC Contact rating: 50 V AC, 3 A 30 V DC, 3 A (resistance load) * Retransmission output is available only when relay is selected as the Loop heating-side control output. * Select this option from the OT parameter * The functions of the external contact outputs are the defaults for dual-loop heating/cooling control. To change the functions, reconfigure the contact output registration setup parameters. COM 35 * Loop: Select from the OT parameter. Loop: Select from the OT parameter. * OT is a setup parameter. You can change the settings of the parameter OT to change the Loop control output types. See. Initial Settings. OT=4 Heating side: Relay output (terminals, and ) Cooling side: Relay output (terminals and ) 3 OT=4 Heating side: Relay output (terminals, and ) Cooling side: Relay output (terminals and ) OT=5 Heating side: Voltage pulse output (terminals and ) Cooling side: Relay output (terminals and ) 6 7 NC NO COM UP * Select this option from the OT parameter. Communication Communication (PSL) High performance RS-485 communication RS-485 communication Note : If you define the DO as the cooling-side control output, the DO5 serves as the Loop alarm output. Inversely, if you define the DO5 as the Loop cooling-side control output, the DO serves as the Loop alarm output. Note : If you define the DO3 as the Loop cooling-side control output, the DO4 serves as the Loop alarm 4 output. Inversely, if you define the DO4 as the Loop cooling-side control output, the DO3 serves as the Loop alarm 3 output. If the Loop cooling-side control output is the current, the DO3 serves as the Loop alarm 3 output, and the DO4 serves as the Loop alarm 4 output. SDB(+) SDA(-) RDB(+) RDA(-) SG (PSL) RDB(+) RDA(-) SG + - * Wiring can only be carried out for controllers with communication functions. Auxiliary analog input Loop heating-side control output Current/voltage pulse output Specify in a range of -5 V DC, 0- V DC, or 0-0 V DC. Default: -5 V DC 0-0mADC, 4-0mADC Voltage pulse ( V) Correspondence between parameter OT and heating-side output types/cooling-side output types of Loop Loop input * Not configured at factory Retransmission output Default: Unspecified retransmission type 0-0mADC, 4-0mADC Default: 4-0 ma DC TC input * Wiring can only be carried out for controllers with auxiliary analog input. * Select this option from the OT parameter. * Retransmission output is available only when relay is selected as the Loop heating-side control output. before shipment. See. Initial Settings. RTD input A b 3 B mv/v input NOTE * The functions of the external contact inputs are the defaults for dual-loop heating/cooling control. To change the functions, reconfigure the contact input registration setup parameters. Installation category (overvoltage category): II (IEC00-) OT=6 OT=7 OT=8 OT=9 OT=0 OT= OT= Heating side: Current output Heating side: Relay output Heating side: Current output Heating side: Relay output Heating side: Current output (terminals and ) (terminals, and ) (terminals and ) (terminals and ) (terminals, and ) (terminals and ) (terminals and ) Cooling side: Relay output Cooling side: Transistor output Cooling side: Transistor output Cooling side: Transistor output Cooling side: Current output Cooling side: Current output Cooling side: Current output (terminals and ) (terminals and ) (terminals and ) (terminals and ) (terminals and ) (terminals and ) (terminals and ) event output event output Instrument alarm output Common Time event output Time event output Time event 3 output Time event 4 output Common OT=5 0-0mADC, 4-0mADC Voltage pulse ( V) 3 * OT is a setup parameter. You can change the settings of the parameter OT to change the Loop control output types. See. Initial Settings. Heating side: Voltage pulse output Correspondence between parameter OT and heating-side output types/cooling-side output types of Loop Heating side: Voltage pulse output (terminals and ) Cooling side: Relay output (terminals and ) mADC, 4-0mADC Heating side: Voltage pulse output OT=6 OT=7 OT=8 OT=9 Heating side: Current output Heating side: Relay output Heating side: Current output (terminals and ) (terminals, and ) (terminals and ) (terminals and ) Cooling side: Relay output Cooling side: Transistor output Cooling side: Transistor output Cooling side: Transistor output (terminals and ) (terminals and ) (terminals and ) (terminals and ) Heating side: Voltage pulse output Switch between the ON and OFF states of the DI to DI4 contact inputs to select from program pattern numbers to 5. (Select a number during a RESET state.) 9 DI ON ON OFF ON ON OFF ON ON OFF ON ON DI ON ON ON ON ON ON ON ON DI3 ON ON ON ON ON ON ON ON DI4 ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Start of program operation when DI5 changes from OFF to ON Stop of program operation when DI6 changes from OFF to ON Start of local-mode operation when DI7 changes from OFF to ON Common Contact rating: V DC, 0 ma or more 6 7 Receiving 4-0 ma DC Current Signals with the Controller * When receiving 4-0 ma DC current signals, set the input type to -5 V DC (setpoint 4 ). 3 * Factory-set to retransmission. Retransmission output * or 0-0 ma DC Default: 4-0 ma DC Loop cooling-side control output 4-0 or 0-0 ma DC Default: 4-0 ma DC External contact inputs UP +5V DI DI 9 +5V DI 8 DI +5V 8 DI3 40 DI3 +5V 40 DI4 DI V 39 DI5 38 DI5 +5V 38 DI6 DI V 37 DI7 DI COM COM 0 0 Contact Ω 4-0mA Note: Connecting a 50 Ω resistor to the terminals is optional. Model: X (resistor with M3.5 crimp-on terminal lugs) 5 V DC loop power supply* V DC ( ma DC max.) * Retransmission output is not available if a 5 V DC loop power supply is used. * If you define the Loop cooling-side contorl output as continuous output,retransmission output and the 5 V DC loop power supply can no longer be used. Note: Select this option from the OT parameter. Transistor contact 6 7 <Toc> <. Installation> -5

22 Blank Page

23 <Toc> <. Initial Settings> -. Initial Settings This chapter describes examples of setting input types, control output types. Carrying out settings described herein allows you to perform basic control. Refer to examples of various settings to understand how to set parameters required. Refer to 6. Parameter Map for an easy to understand explanation of setting various parameters. If you cannot remember how to carry out an operation during setting, press the key no more than four times. This brings you to the display (operating display) that appears at power-on. After carrying out the settings described here, create programs in 3. Programming. Setup Procedure Power-on Denotes a step that must always be followed. Set UP Mode. (Factory-set to Single-loop Control UP Mode. ) See. Setting UP mode (Setting First at Power-on), or.3 Changing UP mode. Denotes a step that should be followed as necessary. Set input. (Factory-set to Not configured (Loop) / K-type thermocouple (Loop)) See.4 Setting Input Types of Loop and Loop. Set the control output. (Factory-set to Time Proportional Relay Output of Loop / Loop. ) Initialize parameters. See.5 Setting Control Output Types of Loop and Loop. See.6 Initializing Parameters. Be sure to follow this step whenever a change of setting is made to the UP Mode and the input type. Set the alarm type and other setup parameters. Set operating parameters. Set program patterns. See 3. Programming. Controller operation IM 05E0B0-5E st Edition : May 3,000-00

24 <Toc> <. Initial Settings>. Names and Functions of Front Panel Parts -. Indicator lamp for display. Program monitor lamps 3. Event indicator lamps 8. Instrument alarm indicator lamps 4. Status indicator lamps 5. Light-loader interface 9. key 3. PT.No key E E 6. Process variable () display 7. Setpoint display 0. key. key. and keys 5. RESET key 4. RUN key Name of Part Indicator lamp for. display. Program monitor lamps 3. Event indicator lamps 4. Status indicator lamps 5. Light-loader interface Setpoint display (LCD) 8. Process variable () display Instrument alarm indicator lamps 9. key 0. key Function Is lit when Loop is displayed on display. : Is lit (in green) when a program setpoint is increasing. : Is lit (in green) when a program setpoint is constant. : Is lit (in green) when a program setpoint is decreasing. Display the statuses of events, time events and instrument alarms in orange. E and E lamps: Come on when event and event turn on. TME to TME4 lamps: Come on when time event to time event 4 turn on. AL lamp: Comes on when instrument alarm turns on. Is lit (in green) to indicate the status of operation or control. PRG:Is lit when in program mode. RST:Is lit when in reset mode. HLD:Is lit when in hold mode. LOC:Is lit when in local mode. MAN:Is lit when in manual mode of Loop. MAN:Is lit when in manual mode of Loop. CAS:Not used in dual-loop control. Interface for an adapter cable used when setting and storing parameters from a PC. This requires an optional parameter setting tool. Displays. Displays an error code (in red) if an error occurs. Displays the name and value of a target setpoint (SP), output (OUT), deviation trend, or a parameter. Displays an error code if an error occurs. The AL lamp comes on in orange if instrument alarm turns on. Used to switch or register a parameter. Pressing the key for more than 3 seconds allows you to switch between the operating display and the main menu for operating parameter setting display alternately. Presents a display for switching between the hold, advance, local, AUTO and MAN modes.. key. and keys 3. PT.No key 4. RUN key 5. RESET key Used to switch between displays. Pressing this key while any operating display is shown lets you switch to another prearranged operating display. Pressing this key while any display other than an operating display is shown lets you go one display back. (One to four presses (maximum) of this key lets you return to the current operating display, though the number of presses depends on the operating status.) Used to change numerical values. On setting displays for various parameters, you can change target setpoints, parameters, and output values (in manual operation). Pressing the key decreases a numerical value, while pressing the key causes it to increase. You can hold down a key to gradually increase the speed of change. These keys also switch between menu displays when a main menu or submenu of parameter setting display is shown. PT.No Use this key when the controller is at a stop to select a program pattern number on an operating display. RUN RESET Pressing this key for more than seconds while an operating display is shown starts the controller. Pressing this key for more than seconds while an operating display is shown stops the controller. IM 05E0B0-5E st Edition : May 3,000-00

25 E E <Toc> <. Initial Settings> -3. Setting UP mode (Setting First at Power-on) NOTE The controller displays an operating display when the power is turned on. The submenu IN appears at this point if the type of input has not been defined yet. In this case, first set a UP mode to Dual-loop Control following the operating procedure described below. Then, input type, control output type and others. The following operation describes a procedure of setting a UP mode to Dual-loop Control. (set ). Display view at power on RST lamp ON. TME 3 4 AL PRG RST HLD LOC MAN MAN CAS Displays submenu IN. IN input set SETUP sub menu In steps and later, illustrations of the LCD are cited to explain the procedure.. Press the key once to display the submenu MD. 5. Press the setpoint. key once to register the MD UP mode set SETUP sub menu MENU:UPMD/MD # UP mode select SETUP UPM = 3. Press the key once to display the parameter UPM (controller mode). MENU:UPMD/MD # UP mode select SETUP UPM = 6. The controller re-starts (which is normal). Then, set input type. See.4 Setting Input Types of Loop and Loop. IN input set SETUP sub menu 4. Press the or key to display the setpoint. MENU:UPMD/MD # UP mode select changing! UPM = Blinks during change. IM 05E0B0-5E st Edition : May 3,000-00

26 E E <Toc>.3 Changing UP mode <. Initial Settings> The following operation describes a procedure of changing a UP mode to Dual-loop Control. (set ) -4. Bring the operating display into view (display appears at power-on). RST lamp ON. TME 3 4 AL PRG RST HLD LOC MAN MAN CAS SP: PTNO: 0 TM= C SEGNO: 0/ 0 RCY: 0/ 0 In steps and later, illustrations of the LCD are cited to explain the procedure.. Press the key for more than 3 seconds to call up the main menu PROG. PROG programming main menu 6. Press the key once to display the setup parameter submenu MD. MD UP mode set SETUP sub menu 3. Press the key once to display the main menu STUP. STUP password input main menu 7. Press the key once to display the parameter UPM (controller mode). MENU:UPMD/MD # UP mode select SETUP UPM = 4. Press the key once to display the setup parameter main menu PARA. 8. Press the or key to display the setpoint. PARA setup parameter SETUP main menu MENU:UPMD/MD # UP mode select changing! UPM = Blinks during change. 5. Press the key once to display the setup parameter main menu UPMD. UPMD UP750 configuration SETUP main menu IM 05E0B0-5E st Edition : May 3,000-00

27 <Toc> <. Initial Settings> Press the key once to register the setpoint. MENU:UPMD/MD # UP mode select SETUP UPM = 0. The controller re-starts (which is normal). Then, set input type. See.4 Setting Input Types of Loop and Loop. IN input set SETUP sub menu How to return to a menu Press the key once during parameter setting. This lets you return to the parameter menu. IM 05E0B0-5E st Edition : May 3,000-00

28 E E <Toc> <. Initial Settings>.4 Setting Input Types of Loop and Loop The following operating procedure describes an example of setting the input type of Loop to K-type thermocouple (-00.0 to C) and a measurement range of 0.0 to 00.0 C. You can take the same steps for the input type (IN) and ranges (RH, RL) or scales (SH, SL) of Loop that are displayed after the Loop related parameters. input of Loop (Factory-set to Not configured ) input terminal Thermocouple/mV/V input RTD input input of Loop (Factory-set to K-type thermocouple ) input terminal Thermocouple/mV/V input RTD input Example of Temperature Input C Instrument input range C V V Example of Voltage Input Instrument input range 4V 5V 0.0 C Minimum value of input range (RL) input range Set a range to be controlled C Maximum value of input range (RH) Parameters to be set for temperature input. input type (IN): Set according to a sensor. Maximum value of input range (RH): Set the maximum value of the range to be controlled. 3. Minimum value of input range (RL): Set the minimum value of the range to be controlled. RL 0.0m 3 /h 50.0m 3 /h Minimum value of input scale (SL) input range input scale RH Maximum value of input scale (SH) Set a range to be controlled Parameters to be set for voltage input. input type (IN): Set according to an input signal. Maximum value of input range (RH): Set the maximum value of an input signal. 3. Minimum value of input range (RL): Set the minimum value of an input signal. 4. Position of input decimal point (SDP): Set the position of the decimal point for input display. 5. Maximum value of input scale (SH): Set the maximum value of the scale to be controlled. 6. Minimum value of input scale (SL): Set the minimum value of the scale to be controlled. NOTE The controller may automatically initialize the registered operating parameter setpoints if any change is made to the data item Input Type (IN, IN), Maximum Value of Input Range (RH, RH), Minimum Value of Input Range (RL, RL), Input Decimal Point Position (SDP, SDP), Maximum Value of Input Scale (SH, SH) or Minimum Value of Input Scale (SL, SL). After a change has been made to any of these data items, be sure to verify the registered operating parameter setpoints to ensure that they are correct. If any data item has been changed to its default, set it to a required value.. Bring the operating display into view (display appears at power-on). The display in the figure below shows the error code for input burnout ( ) if input wiring is not yet complete. The error code disappears when you wire the input terminals correctly. RST lamp ON. TME 3 4 AL PRG RST HLD LOC MAN MAN CAS SP: PTNO: 0 TM= C SEGNO: 0/ 0 RCY: 0/ 0 In steps and later, illustrations of the LCD are cited to explain the procedure. IM 05E0B0-5E st Edition : May 3,000-00

29 <Toc> <. Initial Settings> -7. Press the key for more than 3 seconds to call up the main menu PROG. PROG programming main menu 7. Press the key once to display the submenu IN. IN input set SETUP sub menu 3. Press the key once to display the main menu STUP. STUP password input main menu 8. Press the key once to display the parameter IN ( input type of Loop). MENU:UPMD/IN # input type select SETUP IN = OFF 4. Press the key once to display the main menu PARA. PARA setup parameter SETUP main menu 9. Press the or key to display the required setpoint. The figure below shows an example of setting the input type to a K-type thermocouple (-00.0 C to C). MENU:UPMD/IN # input type select changing! IN = typek3 Blinks during change. 5. Press the key once to display the main menu UPMD. UPMD UP750 configuration SETUP main menu 0. Press the key once to register the setpoint. MENU:UPMD/IN # input type select SETUP IN = typek3 6. Press the key once to display the submenu MD. MD UP mode set SETUP sub menu. Press the key once to display the parameter UNI. MENU:UPMD/IN # input unit select SETUP UNI = C IM 05E0B0-5E st Edition : May 3,000-00

30 E E <Toc> <. Initial Settings> -8. Press the key once to display the parameter RH (maximum value of input range of Loop). MENU:UPMD/IN #3 input range high SETUP RH = Press the key once to display the parameter RL (minimum value of input range of Loop). MENU:UPMD/IN #4 input range low SETUP RL = Press the or key to display the required setpoint. The figure below shows an example of setting the maximum value of the input range to 00.0 C. 6. Press the or key to display the required setpoint. The figure below shows an example of setting the minimum value of the input range to 0.0 C. MENU:UPMD/IN #3 input range high changing! RH = 00.0 Blinks during change. MENU:UPMD/IN #4 input range low changing! RL = 0.0 Blinks during change. 4. Press the setpoint. key once to register the 7. Press the setpoint. key once to register the MENU:UPMD/IN #3 input range high SETUP RH = 00.0 MENU:UPMD/IN #4 input range low SETUP RL = 0.0 If the type of Input is voltage, also configure the Input Decimal Point Position of Loop (SDP), Maximum Value of Input Scale of Loop (SH) and Minimum Value of Input Scale of Loop (SL) parameters that are displayed after this. 8. Press the key for more than 3 seconds. This returns you to the display shown at power-on (figure below). RST lamp ON. TME 3 4 AL PRG RST HLD LOC MAN MAN CAS SP: PTNO: 0 TM= C SEGNO: 0/ 0 RCY: 0/ 0 IM 05E0B0-5E st Edition : May 3,000-00

31 <Toc> <. Initial Settings> -9 Instrument Input Range Codes Input Unspecified K J T B S R Thermocouple N RTD Standard signal DC voltage Type Instrument Input Range Code OFF (0) typek () typek () typek3 (3) typej (4) typet (5) typet (6) typeb (7) types (8) typer (9) typen (0) Instrument Measurement Accuracy Input Range Set the data item Input Type IN to the OFF option to leave the input type undefined to C to F to C to F 0.% of instrument range digit at 0 C or more to C 0.% digit for temperatures below 0 C, to F where the accuracy is: % of instrument range to 00.0 C digit for temperatures below C for a type-k to F thermocouple, or % of instrument range digit for to C temperatures below C for a type-t thermocouple to F 0.0 to C to F 0.0 to C 0.5% of instrument range digit at 400 C or more 3 to 3300 F 5% of instrument range digit at less than 400 C 0.0 to C 3 to 300 F 0.5% of instrument range digit 0.0 to C 3 to 300 F to C to F E typee () to C to F L(DIN) typel () to C to F U(DIN) typeu (3) to C to F typeu (4) 0.0 to C to F W typew (5) 0.0 to C 3 to 400 F Platinel Plati (6) 0.0 to C 3 to F PR0-40 PR040 (7) 0.0 to C 3 to 3400 F W97Re3-0.0 to C W97Re3 (8) W75Re5 3 to 3600 F JPt00 JPt (30) to C to F JPt (3) to C to F Pt (35) to C to F Pt00 Pt (36) to C to F Pt3 (37) to C to F 0.4 to V 0.4 to V (40) to.000 V to 5 V to 5 V (4).000 to V 0 to V 0 to V (50) to.000 V 0 to 0 V 0 to 0 V (5) 0.00 to 0.00 V 0.00 to.5 V 0.00 to.5 V (5) (Note 3) to.00 V -0 to 0 mv mv (55) to 0.00 mv 0 to 00 mv mv (56) 0.0 to 00.0 mv 0.% of instrument range digit 0.5% of instrument range digit for temperatures below 0 C 0.% of instrument range digit at 0 C or more 0.% digit for temperatures below 0 C, where the accuracy is:.5% of instrument range digit for temperatures below C for a type-e thermocouple. 0.% of instrument range digit 0.% of instrument range digit 0.5% of instrument range digit at 800 C or more No accuracy is guaranteed at less than 800 C 0.% of instrument range digit 0.% of instrument range digit (Note ) (Note ) 0.% of instrument range digit (Note ) 0.% of instrument range digit (Note ) (Note ) 0.% of instrument range digit (Note ) 0.% of instrument range digit Display range is scalable in a range of to Display span is or less. Numbers in ( ) are the setting value that apply when the communication is used. * Performance in the standard operating conditions (at 3 C, 55 0%RH, and 50/60 Hz power frequency) Note : The accuracy is 0.3 C of instrument range digit for a temperature range from 0 C to 00 C. Note : The accuracy is 0.5 C of instrument range digit for a temperature range from -00 C to 00 C. Note 3: Only used for input of Loop (IN). * To receive a 4-0 ma DC signal, select a standard signal of to 5 V DC and connect it to a 50 resistor. This resistor is optional. Model: X (resistor with M3.5 crimp-on terminal lugs) IM 05E0B0-5E st Edition : May 3,000-00

Model UP550 Program Controller User s Manual for Cascade Primary-loop Control

Model UP550 Program Controller User s Manual for Cascade Primary-loop Control Instruction Manual Model UP550 Program Controller User s Manual for Cascade Primary-loop Control IM 05E0C02-42E IM 05E0C02-42E st Edition Blank Page Introduction i Thank you for purchasing

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup Instruction Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup IM 05D01C02-45E IM 05D01C02-45E 1st Edition Blank Page Introduction Thank you

More information

Model UP350 Program Controller

Model UP350 Program Controller User s Manual Model UP350 Program Controller User s Manual IM 05E01D02-41E IM 05E01D02-41E 2nd Edition Blank Page Introduction i Thank you for purchasing the UP350 program controller. How to

More information

Model UP550 Program Controller User s Manual for Loop Control with PV Switching

Model UP550 Program Controller User s Manual for Loop Control with PV Switching User s Manual Model UP550 Program Controller User s Manual for Loop Control with Switching IM 05E0C0-46E IM 05E0C0-46E 3rd Edition Blank Page Introduction i Thank you for purchasing the UP550

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control User s Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control IM 05D01C02-41E IM 05D01C02-41E 3rd Edition Blank Page Introduction i Thank you for purchasing

More information

Model UT750 Digital Indicating Controller User s Manual for Cascade Control

Model UT750 Digital Indicating Controller User s Manual for Cascade Control User s Manual Model UT750 Digital Indicating Controller User s Manual for Cascade Control IM 05D01B02-44E IM 05D01B02-44E 3rd Edition Blank Page Introduction i Thank you for purchasing the

More information

Models UT350/UT320 Digital Indicating Controllers

Models UT350/UT320 Digital Indicating Controllers User s Manual Models UT350/UT320 Digital Indicating Controllers User s Manual IM 05D01D02-41E IM 05D01D02-41E 4th Edition Blank Page Introduction i Thank you for purchasing the UT350/UT320

More information

Model UP351 Program Controller

Model UP351 Program Controller User s Manual Model UP351 Program Controller User s Manual IM 05E01D12-41E IM 05E01D12-41E 4th Edition Blank Page Introduction i Thank you for purchasing the UP351 program controller. How to

More information

Model UT551 Digital Indicating Controller with Active Color PV Display and Embedded Ethernet User s Manual for Single-loop Control

Model UT551 Digital Indicating Controller with Active Color PV Display and Embedded Ethernet User s Manual for Single-loop Control User s Manual Model UT551 Digital Indicating Controller with Active Color Display and Embedded Ethernet User s Manual for Single-loop Control IM 05D01C03-41E IM 05D01C03-41E 4th Edition Introduction

More information

Model UT750 Digital Indicating Controller User s Manual for Cascade Primary-loop Control

Model UT750 Digital Indicating Controller User s Manual for Cascade Primary-loop Control User s Manual Model UT750 Digital Indicating Controller User s Manual for Cascade Primary-loop Control IM 05D01B02-42E IM 05D01B02-42E 3rd Edition Blank Page Introduction i Thank you for purchasing

More information

General Specifications

General Specifications General Specifications GS 05F01D01E MODEL UM351 Digital Indicator with Alarms with Active Color PV Display General Model UM351 Digital Indicator with Alarms is a precision alarm instrument provided with

More information

General Specifications

General Specifications General Specifications MODEL UM0 Digital Indicator with Alarms GS 0F0D00E General Model UM0 Digital Indicator with Alarms is a precision alarm instrument with universal input /8DIN. For excellent monitoring

More information

General Specifications

General Specifications General Specifications Model UM350 Digital Indicator with Alarms GS 05F0D00E General Model UM350 Digital Indicator with Alarms is a precision alarm instrument with universal input. For excellent monitoring

More information

General Specifications

General Specifications General Specifications MODEL UT50L Limit Controller GS 5DD-0E Overview The UT50L is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user.

More information

General Specifications

General Specifications General Specifications Model UM330 Digital Indicator with Alarms GS 05F0D00E General Model UM330 Digital Indicator with Alarms is a precision alarm instrument with universal input /8DIN. For excellent

More information

General Specifications

General Specifications General Specifications GS 0F01D0E Model UM1 Digital Indicator with Alarms with Active Color PV Display General Model UM1 Digital Indicator with Alarms is a precision 1/8 DIN alarm instrument provided with

More information

General Specifications

General Specifications General Specifications GS 0F01D01E Model UM1 Digital Indicator with Alarms with Active Color PV Display General Model UM1 Digital Indicator with Alarms is a precision alarm instrument provided with universal

More information

General Specifications

General Specifications General Specifications Model UT, UT Temperature Controller GS CE-E GENERAL UT series temperature controllers provide only the functions and size you require for your application. /6 DIN sizes is available.

More information

How to Install CAUTION. Panel. 150mm. 150mm. Direction to insert the controller Insert the controller into the opening at the front of the panel.

How to Install CAUTION. Panel. 150mm. 150mm. Direction to insert the controller Insert the controller into the opening at the front of the panel. User s IM DDE This manual describes installation, wiring, and other tasks required to make the ler ready for operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to Connect Wires.

More information

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E User s Manual Model US1000 Digital Indicating Controller Functions 2nd Edition Introduction This instruction manual describes the functions of the US1000 Digital Indicating Controller in detail. Read

More information

General Specifications

General Specifications General Specifications Model UT Digital Indicating Controller GS 0D01C0E General Model UT Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful

More information

General Specifications

General Specifications General Specifications MODEL UT0 Digital Indicating Controller GS 0D01C00E General Model UT0 Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful

More information

UP550 O.C. Relay. UP s contact. 150mm. Relay. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs

UP550 O.C. Relay. UP s contact. 150mm. Relay. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs s Manual IM ECE This manual describes installation, wiring, and other tasks required to make the controller ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to Connect

More information

UT750. Relay. 150mm. UT s contact. Relay (Use one with a relay coil rating less than the UT s contact rating.) 150mm. Recommended Terminal Lugs

UT750. Relay. 150mm. UT s contact. Relay (Use one with a relay coil rating less than the UT s contact rating.) 150mm. Recommended Terminal Lugs User s Manual IM 5DBE This manual describes installation, wiring, and other tasks required to make the controller ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to

More information

UP750. Relay. UP s contact. Relay. 150mm. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs

UP750. Relay. UP s contact. Relay. 150mm. (Use one with a relay coil rating less than the UP s contact rating.) 150mm. Recommended Terminal Lugs s Manual IM EBE This manual describes installation, wiring, and other tasks required to make the ler ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install. How to Connect Wires.

More information

General Specifications

General Specifications General Specifications MODEL 550 Digital Indicating Controller GS 05D0C00E General Model 550 Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful

More information

General Specifications

General Specifications General Specifications UM33A Digital Indicator with Alarms [Style: S9] Overview The UM33A digital indicator with Alarms employ an easy-to-read, 14-segment large color LCD display, along with navigation

More information

General Specifications

General Specifications General Specifications Model UP350 Program Controller GS 05E0D00E General Model UP350 program controller is a precision controller, featuring two program profiles and universal input/output. For easy operation,

More information

General Specifications

General Specifications General Specifications Model 0 Digital Indicating Controller GS 0D0C00E General Model 0 Digital Indicating Controller is an intelligent, microprocessor based digital indicating controller with powerful

More information

General Specifications

General Specifications General Specifications GS 05P01F31-01EN UT32A Digital Indicating Controller (Entry model) Functional Enhancement Overview The UT32A entry model digital indicating controller is an easily configurable single-loop

More information

SHIMADEN DIGITAL INDICATORS

SHIMADEN DIGITAL INDICATORS Shimaden, Temperature and Humidity Control Specialists C %RH Series SD16A & SHIMADEN DIGITAL INDICATORS approved,ul applied BASIC FEATURES compliance DIN Size 48 x 96 mm ±.3% High Accuracy Indication Large

More information

SHIMADEN PROGRAM CONTROLLER

SHIMADEN PROGRAM CONTROLLER Shimaden, Temperature and Humidity Control Specialists C %RH SHIMADEN PROGRAM CONTROLLER approved BASIC FEATURES Full multi-input and multi-range performance User selectable Thermocouple, RTD, V, mv and

More information

General Specifications

General Specifications General Specifications GS 05D01D01E Model UT351 Digital Indicating Controller with Active Color PV Display General Model UT351 Digital Indicating Controller is a highly accurate 1/4 DIN controller, provided

More information

General Specifications

General Specifications General Specifications Model UT30 Digital Indicating Controller GS 05D0D00E General Model UT30 Digital Indicating Controller is a highly accurate /8 DIN controller, provided with universal input/ output.

More information

indicate that the contacts are available. How to Install CAUTION Panel

indicate that the contacts are available. How to Install CAUTION Panel s Manual IM DCE This manual describes installation, wiring, and other tasks required to make the controller ready f operation.. Safety Precautions. Model and Suffix Codes. How to Install How to Connect

More information

DIGITAL PROGRAM CONTROLLER

DIGITAL PROGRAM CONTROLLER KP1000 SERIES DIGITAL PROGRAM CONTROLLER The KP1000 series is a 96x96mm digital program controller with the indicating accuracy of ±0.1%, the control cycle of approximately 0.1 seconds and maximum 19 program

More information

SHIMADEN DIGITAL INDICATOR

SHIMADEN DIGITAL INDICATOR Shimaden, Temperature and Humidity Control Specialists C %RH Series SD24 & KR16A SHIMADEN DIGITAL INDICATOR BASIC FEATURES ohigh Accuracy ±0.1% FS+1 digit o1/1000ºc Resolution Indication Possible (Pt input

More information

SHIMADEN DIGITAL INDICATORS

SHIMADEN DIGITAL INDICATORS Shimaden, Temperature and Humidity Control Specialists C %RH Series SD16 & SHIMADEN DIGITAL INDICATORS & NRTL /C approved BASIC FEATURES DIN Size 48 x 96 mm ±.3% High Accuracy Indication Large 2 mm bright

More information

General Specifications

General Specifications General Specifications MODEL UP750 ler GS 5EB0-0E General Model UP750 ler is an intelligent, microprocessor based program controller that has the capacity of 00 program s, ful control capability, custom

More information

MODEL: R30US4. Remote I/O R30 Series

MODEL: R30US4. Remote I/O R30 Series Remote I/O R30 Series UNIVERSAL INPUT MODULE (4 points, isolated) Functions & Features 4 points universal input I/O module Isolation between the channels Input range of each channel is individually adjustable

More information

DIGITAL INDICATING CONTROLLER

DIGITAL INDICATING CONTROLLER DB00 SERIES DIGITAL INDICATING CONTROLLER The DB00 series is a digital indicating controller with the indicating accuracy of ±0.% and the control cycle of approximately 0. seconds. Various functions including

More information

MICRO-CONTROLLER X (48 48 mm)

MICRO-CONTROLLER X (48 48 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

MODEL: M2XU MODEL: M2XU [1][2] [3][4]

MODEL: M2XU MODEL: M2XU [1][2] [3][4] Super-mini Signal Conditioners Mini-M Series UNIVERSAL TRANSMITTER (PC programmable) Functions & Features Accepts direct inputs from various sensors and provides a standard process signal I/O types and

More information

General Specifications

General Specifications General Specifications GS 05P03D21-01EN UM33A Digital Indicator with Alarms Functional Enhancement Overview The UM33A digital indicator with Alarms employ an easy-to-read, 14-segment large color LCD display,

More information

Digital Controller Intelligent, User-friendly Digital Controller and Programmer Controlled with ease with a support software which is input via the communication jack on the front panel. Minute adjustment

More information

6/12/24 Dot Printing Model Smart Recorder SRF206/212/224

6/12/24 Dot Printing Model Smart Recorder SRF206/212/224 No. CP-SS-E // Dot Printing Model Smart Recorder SRF0// The Smart Recorder SRF 0// Dot Printing Model accepts DC voltage, thermocouple, resistance temperature detector (RTD), communications and ON/OFF

More information

General Specifications

General Specifications General Specifications GS 05P08D81-01EN UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) Functional Enhancement Overview The UT32A-D/MDL controller is a dual-loop controller

More information

CompoBus/D-type Digital Controller

CompoBus/D-type Digital Controller CompoBus/D-type Digital Controller Digital Controller for the CompoBus/D and Conforming the DeviceNet Conforms the DeviceNet and connects a Programmable Controller without any programming. High performance

More information

MODEL: M6SXU MODEL: M6SXU [1][2] [3][4]

MODEL: M6SXU MODEL: M6SXU [1][2] [3][4] Tension-Clamp Ultra-Slim Signal Conditioners M6S Series UNIVERSAL TRANSMITTER (PC programmable) Functions & Features Maintenance-free tension clamp connection Universal input (mv, V, ma, T/C, RTD and potentiometer)

More information

Process Controller. PX series INSTRUCTION MANUAL. Thank you for the purchase of HANYOUNG product. Please read this manual carefully.

Process Controller. PX series INSTRUCTION MANUAL. Thank you for the purchase of HANYOUNG product. Please read this manual carefully. Process Controller PX series INSTRUCTION MANUAL Thank you for the purchase of HANYOUNG product. Please read this manual carefully. Contents. SAFETY INFORMATION. INSTRUCTION 3. ORDERING INFORMATION 4. SPECIFICATION

More information

Model PR300 Power and Energy Meter

Model PR300 Power and Energy Meter User s Manual Model PR300 Power and Energy Meter 4th Edition Introduction Thank you for purchasing the PR300 Power and Energy Meter. This manual provides information about the procedure for installing,

More information

PROGRAMMABLE CONTROLLER

PROGRAMMABLE CONTROLLER Shimaden, Temperature and Humidity Control Specialists C %RH Series FP2 PROGRAMMABLE CONTROLLER approved UL applied BASIC FEATURES 2-channel controller (Basic type: 1-channel controller) Independent 2-loop

More information

RUN HLD MAN PRG. Features

RUN HLD MAN PRG. Features DCP3 Digital Controller Programmer 57-77-3-15 5/ Page 1 of 16 Specification Function The DCP3 is a high-function digital controller programmer supporting up to 19 program profiles with up to 3 segments

More information

General Specifications

General Specifications General Specifications GS J0U0-0E Model MU Universal Temperature Converter (Free Range Type) General The MU is a plug-in type universal temperature converter that converts input signal (thermocouple, RTD

More information

DCP551B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning.

DCP551B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning. No. CP-SS-1852E DCP551B Mark II DIGITRONIK TM Programmable Controller Overview The DIGITRONIK TM DCP551B Mark II is a high-function programmable controller supporting up to 99 program patterns to which

More information

General Specifications

General Specifications General Specifications GS 77J01Q08-01E Model VJQ8 Pulse to Analog Converter (Multi-function) (Isolated Single-output and Isolated Dual-output Types) General This plug-in type pulse to analog converter

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A

INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A Preface Thank you for purchasing our Programmable Controller PCD-33A. This manual contains instructions for the mounting, functions, operations and

More information

MICRO-CONTROLLER X (96 96 mm)

MICRO-CONTROLLER X (96 96 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

SDC40A. DigitroniK TM Digital Indicating Controller RSW. Control unit PID (8) Auto tuning+ Neuro & Fuzzy RUN/READY R/L LSP.

SDC40A. DigitroniK TM Digital Indicating Controller RSW. Control unit PID (8) Auto tuning+ Neuro & Fuzzy RUN/READY R/L LSP. No. CP-SS-580E SDC40A DigitroniK TM Digital Indicating Controller Overview The DigitroniK TM SDC40A is a compact (96mm x 96mm) digital controller. The SDC40A features a wide variety of input options: thermocouples,

More information

DCP551 Digital Control Programmer Specifications

DCP551 Digital Control Programmer Specifications DCP551 Digital Control Programmer Specifications 57-77-03-16 January 2009 Introduction The DCP551 is a high-function programmer/controller supporting up to 99 program patterns to which thermocouple, resistance

More information

DCP552B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning.

DCP552B Mark II. DIGITRONIK TM Programmable Controller. Control operation block. Mode transition. PID control Auto-tuning. No. CP-SS-1853E DCP552B Mark II DIGITRONIK TM Programmable Controller Overview The DIGITRONIK TM DCP552B Mark II is a high-function programmable controller supporting two channels (up to 49 program patterns

More information

Temperature Controllers E5 J

Temperature Controllers E5 J Temperature Controllers Advanced PID Controller with Fuzzy Logic-Based Adaptive Tuning Provides Optimum Performance Available in 3 standard DIN sizes: Choose 1/4, 1/8 and 1/16 DIN Fuzzy adaptive tuning

More information

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models Solid-state Power OFF-delay Timer H3DE-H Timers Two delay-time models available. 0.1 to 12 seconds (S Series) 1 to 120 seconds (L Series) Covers wide range of supply voltage. Model Number Structure Model

More information

User s Manual. Model MS5 Potentiometer Converter (Free Range Type) MODEL AND SUFFIX CODES CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT

User s Manual. Model MS5 Potentiometer Converter (Free Range Type) MODEL AND SUFFIX CODES CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT User s Manual Model MS5 Potentiometer Converter (Free Range Type) IM 77J04S05-0E Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 80-8750 Japan Phone: +8-422-52-779 Facsimile:

More information

PROGRAM CONTROLLER OUTLINE

PROGRAM CONTROLLER OUTLINE Specifications Sheet No.SPEC-1232E (1st Edition) EC1200A PROGRAM CONTROLLER OUTLINE The EC1200 can, totally and with high precision, control and monitor such factors as temperature, temperature balance

More information

Single Loop Controller SDC35/36

Single Loop Controller SDC35/36 No. CP SS 180E Single Loop Controller SDC35/36 Features The DigitroniK SDC35/36 is a digital indicating controller featuring multi-range inputs and PID control system using new algorithms "RationaLOOP"

More information

User s Manual. Model MXS Universal Computing Unit (1-input, Isolated 2-output Type) MODEL AND SUFFIX CODES

User s Manual. Model MXS Universal Computing Unit (1-input, Isolated 2-output Type) MODEL AND SUFFIX CODES User s Manual Model MXS Universal Computing Unit (1-input, Isolated 2-output Type) IM 77J04X11-01E Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan Phone: 81-422-52-7179

More information

DC1010/DC1020/DC1030/DC1040

DC1010/DC1020/DC1030/DC1040 05/0 0-10-10-0-EN Page 1 of DC1010/DC1020/DC100/DC1040 DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of functionality and

More information

DCP551 Digital Control Programmer

DCP551 Digital Control Programmer DCP551 Digital Control Programmer 57-77-03-16 January 2009 Page 1 of 12 Specification and Model Selection Guide Introduction The DCP551 is a high-function programmer/controller supporting up to 99 program

More information

DigitroniK TM Digital Indicating Controller SDC20

DigitroniK TM Digital Indicating Controller SDC20 No. CP SS 47E DigitroniK TM Digital Indicating Controller SDC The DigitroniK SDC is a compact digital controller with multi-range and PID autotuning systems for various inputs, with time proportional (on/off)

More information

APPENDIX APPENDIX A 1

APPENDIX APPENDIX A 1 A 1 SPECIFICATIONS Ratings Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 7VA 4VA/2.5W Sensor input Thermocouple

More information

General Specifications

General Specifications General Specifications GS 77J0A070E Model VJA7 Distributor (Multifunction) (Isolated Singleoutput and Isolated Dualoutput Types) Overview This plugin type distributor is used in combination with wire type

More information

Universal Alarm Indicator

Universal Alarm Indicator Universal Alarm Indicator Model: PCA13 User s Manual CM2-PCA100-2001 4th edition Copyright, Notices and Trademarks 1996-2012 Azbil Corporation All Rights Reserved. While this information is presented in

More information

User s Manual. Model MA5 Distributor (Free Range Type) CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT MODEL AND SUFFIX CODES

User s Manual. Model MA5 Distributor (Free Range Type) CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT MODEL AND SUFFIX CODES User s Manual Model MA5 Distributor (Free Range Type) IM 77J04A05-0E Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 80-8750 Japan Phone 8-422-52-779 Facsimile 8-422-52-6793 Please

More information

User s Manual Model PR300 Power and Energy Meter

User s Manual Model PR300 Power and Energy Meter User s Manual Model PR300 Power and Energy Meter Yokogawa Electric Corporation st Edition Model PR300 Power and Energy Meter Contents Introduction...i Notices... ii Checking the Package... iii Checking

More information

Fuzzy Temperature Controllers E5AF

Fuzzy Temperature Controllers E5AF Fuzzy Temperature Controllers 1/4 DIN Controller Combines Fuzzy and PID Control For Fast Response to Process Disturbances Advanced PID control provides optimal response during start-up and steadystate

More information

MICRO-CONTROLLER X (48 96 mm)

MICRO-CONTROLLER X (48 96 mm) PX series digital temperature controller MICRO-CONTROLLER X ( mm) DATA SHEET PXG PXG is a compact size temperature controller of front panel size mm. To cope with any of versatile uses as a temperature

More information

General Specifications

General Specifications General I/O Adaptors (for N-IO) GS 33J62F30-01EN [Release 6] GENERAL This General (GS) describes the hardware specifications of I/O adaptors that enable extended functions setting for analog digital I/O

More information

MODEL: M2EXT. Super-mini Signal Conditioners with Display Mini-M M2E Series

MODEL: M2EXT. Super-mini Signal Conditioners with Display Mini-M M2E Series Super-mini Signal Conditioners with Display Mini-M ME Series THERMOCOUPLE TRANSMITTER (PC programmable) Functions & Features Accepts direct input from a thermocouple and provides a linearized process signal

More information

TxBlock-USB Transmitter

TxBlock-USB Transmitter Transmitter TEMPERATURE TRANSMITTER - OPERATING MANUAL V1.0x I INTRODUCTION The TxBlock-USB is a 4-20 ma 2-wire temperature transmitter for head mount, powered by the current loop. The output current is

More information

Model VJCE-01A VJ Mounting Base for Communication

Model VJCE-01A VJ Mounting Base for Communication User s Manual IM 77J01C51-11E Model VJCE-01A VJ Mounting Base for Communication Please read through this manual as well as the manual for respective instruments of JUXTA VJ series mounted on the VJ mounting

More information

General Specifications

General Specifications General Specifications GS 77J04H0-0E Model MH Isolator (Free Range Type) General The MH is a plug-in type isolator that converts DC current or DC voltage signals into isolated DC current or DC voltage

More information

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification 01 May 20 30-10-10--EN Page 1 of DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification Overview The DC1000 Series are microprocessorbased controllers designed with a high degree of

More information

µr SERIES RECORDERS VIEW RECORDERS 4365 & 4375 Recorders FUNCTIONS FEATURES

µr SERIES RECORDERS VIEW RECORDERS 4365 & 4375 Recorders FUNCTIONS FEATURES 4365 & 4375 Recorders VIEW RECORDERS Splash and dust-proof door permits use even in poor environments. (Based on DIN 40050-IP54). Depth is a mere 220 mm, enabling significant instrument panel space savings.

More information

General Specifications

General Specifications General Specifications Signal Conditioner Cards OUTLINE Signal Conditioner Cards, which interface to the process, are installed in Signal Conditioner Nests. [Release 6] The signal conditioner cards can

More information

General Specifications

General Specifications General Specifications GS J0X-0E Model MXT Universal Computing Unit (-input, Isolated -output Type) General This plug-in type universal computing unit receives DC current or DC voltage signals, applies

More information

MODEL: TC10EM. Temperature Controller TC10 Series

MODEL: TC10EM. Temperature Controller TC10 Series Temperature Controller TC0 Series TEMPERTURE CONTROLLER (Modbus, 5 digit, LED display type, size 9 x 9 mm) Functions & Features Two PID controllers* Universal input x points, control output x points, discrete

More information

SHIMADEN DIGITAL CONTROLLER

SHIMADEN DIGITAL CONTROLLER Shimaden, Temperature and Humidity Control Specialists C %RH Series SR9 SHIMADEN DIGITAL CONTROLLER ASIC FEATURES Multi-input and multi-range performance Large mm bright display (SR9) Readable from a distance

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

This Errata Sheet contains corrections or changes made after the publication of this manual.

This Errata Sheet contains corrections or changes made after the publication of this manual. Errata Sheet This Errata Sheet contains corrections or changes made after the publication of this manual. Product Family: DL4 Date: September 12, 218 Manual Number D4-ANLG-M Revision and Date th Ed., Rev.

More information

Analogue temperature controllers

Analogue temperature controllers Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications

More information

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition UNICONT PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1 ST edition pmg4111a0600p_01 1 / 24 TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 3 2. ORDER CODE... 3 3. TECHNICAL DATA...

More information

Multi-point Temperature Controller

Multi-point Temperature Controller Multi-point Temperature Controller Controls Up to Eight Zones, Built-in DeviceNet Communications Applications include plastic injection and extrusion machines, and continuous temperature control processes

More information

SMART TEMPERATURE TRANSMITTERS. smar

SMART TEMPERATURE TRANSMITTERS. smar SMART TEMPERATURE TRANSMITTERS FEATURES Single unit accepts signal from: - Standart RTDs and Thermocouples - Single ended or differential sensing - mv signals from radiation pyrometers, load cells, etc.

More information

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional) Temperature Controller with Built-in SSR SB SB General Description SB is a channel temperature controller with Built-in SSR (Solid state relay) designed for flexible heating solutions such as heat trace

More information

Model Number Structure

Model Number Structure Digital Controller CSM DS_E_3_1 Advanced Digital Controllers Ideal for Worldwide Use Modular structure High-accuracy: 100 ms sampling (for analog input) Auto-tuning and fuzzy self-tuning Conforms to international

More information

General Specifications

General Specifications General Specifications Signal Conditioner Cards GS 33K50H80-50E OUTLINE Signal Conditioner Cards, which interface to the process, are installed in Signal Conditioner Nests. [Release 5] The signal conditioner

More information

LT23A SERIES. Digital Indicating Controller PSE x48mm compact body Easy to use small size controller at reasonable price CE RoHS compliance

LT23A SERIES. Digital Indicating Controller PSE x48mm compact body Easy to use small size controller at reasonable price CE RoHS compliance Digital Indicating Controller LTA SERIES 48x48mm compact body Easy to use small size controller at reasonable price CE RoHS compliance LT A series is a 4848mm digital indicating controller with indicating

More information

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION ADVANCED - CONTROLLERS - SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION (ma) OUTPUTS - 4x EVENT OR ALARM OUTPUTS

More information