Zone Selective Interlocking (ZSI)

Size: px
Start display at page:

Download "Zone Selective Interlocking (ZSI)"

Transcription

1 Zone Selective Interlocking () Functionality and Structure of For short circuit and ground fault as well Application Guide

2 Selective tripping? Objective: Selective tripping with minimum short-circuit duration, irrespective of the grading level in which the short-circuit occurs. Selectivity: A system with several protective devices connected in series is referred to as selective if - in the event of a shortcircuit - only the protective device (example: Q22) located directly in front of the fault location responds and clears the short-circuit by itself. Unaffected branch circuits continue to be supplied. -Q11 -Q21 -Q22 -Q1 -Q2 -Q Page 2

3 Selectivity achieved via the short-time delayed short-circuit release T kva Q11 WL1 + 5B In = 2,500A Q21 WL1 + 5B In = 1,600A Q1 WL1 + 5B In = 1,250A Q1 WL1 + 5B In = 800A Q51 WL1 + 5B In = 60A Ikmax = 9.9 ka Ikmin = 1.1 ka Ikmax =. ka Ikmin = 25.8 ka Ikmax = 0.8 ka Ikmin = 21.1 ka Ikmax = 27. ka Ikmin = 17. ka Ikmax = 21.2 ka Ikmin = 11.6 ka Settings for WL1 with ETU5B I sd t sd I i (12*I n =) ms OFF 0 ka 00 (12*I n =) ms OFF 19.2 ka 00 (12*I n =) ms OFF 15 ka 00 (12*I n =) ms OFF 9.6 ka 200 (12*I n =) ms OFF 7.56 ka 100 Solution: Example of time grading using a WL1 The WL is given a different delay time t sd in the individual grading levels. The objective is to delay the tripping of the upstream circuit breakers for the short-circuit duration until the circuit breaker closest to the fault clears the short-circuit. Q61 KL Q62 VL + TM Q6 NP Load Load Load In = 80 A Ikmax = 1. ka Ikmin = 5.5 ka In = 160 A Ikmax = 17.0 ka Ikmin = 7.0 ka In = 50 A Ikmax = 9.1 ka Ikmin =.6 ka Page

4 Selectivity achieved via the short-time delayed short-circuit release T kva Q11 WL1 + 5B In = 2,500A Ikmax = 9.9 ka Ikmin = 1.1 ka Settings for WL1 with ETU5B I sd t sd I i (12*I n =) ms OFF 0 ka 00 Problem 1: In this example, a grading level is missing from the time grading Q21 WL1 + 5B In = 1,600A Q1 WL1 + 5B In = 1,250A Q1 WL1 + 5B In = 800A Q51 WL1 + 5B In = 60A Ikmax =. ka Ikmin = 25.8 ka Ikmax = 0.8 ka Ikmin = 21.1 ka Ikmax = 27. ka Ikmin = 17. ka Ikmax = 21.2 ka Ikmin = 11.6 ka (12*I n =) ms OFF 19.2 ka 00 (12*I n =) ms OFF 15 ka 00 (12*I n =) ms OFF 9.6 ka 200 (12*I n =) ms OFF 7.56 ka 100 Q11 and Q21 trip simultaneously The reason: a) No time grading b) No current grading possible Q61 KL Q62 VL + TM Q6 NP Load Load Load In = 80 A Ikmax = 1. ka Ikmin = 5.5 ka In = 160 A Ikmax = 17.0 ka Ikmin = 7.0 ka In = 50 A Ikmax = 9.1 ka Ikmin =.6 ka Page

5 Selectivity achieved via the short-time delayed short-circuit release T kva Q11 WL1 + 5B In = 2,500A Q21 WL1 + 5B In = 1,600A Q1 WL1 + 5B In = 1,250A Q1 WL1 + 5B In = 800A Q51 WL1 + 5B In = 60A Ikmax = 9.9 ka Ikmin = 1.1 ka Ikmax =. ka Ikmin = 25.8 ka Ikmax = 0.8 ka Ikmin = 21.1 ka Ikmax = 27. ka Ikmin = 17. ka Ikmax = 21.2 ka Ikmin = 11.6 ka Settings for WL1 with ETU5B I sd t sd I i (12*I n =) ms OFF 0 ka 00 (12*I n =) ms OFF 19.2 ka 00 (12*I n =) ms OFF 15 ka 00 (12*I n =) ms OFF 9.6 ka 200 (12*I n =) ms OFF 7.56 ka 100 Problem 2: In the event of a short-circuit, e.g. directly after Q11, Q11 must still wait for the time t sd (00ms), even though the circuit-breaker could clear the short-circuit immediately. The result is that the system is exposed to the short-circuit for an unnecessarily long time. Q61 KL Q62 VL + TM Q6 NP Load Load Load In = 80 A Ikmax = 1. ka Ikmin = 5.5 ka In = 160 A Ikmax = 17.0 ka Ikmin = 7.0 ka In = 50 A Ikmax = 9.1 ka Ikmin =.6 ka Page 5

6 Selectivity via the function? Zone Selective Interlocking () in the event of short-circuits and ground faults One possible solution to ensure selectivity for circuit breakers easily and safely is the function of the SENTRON WL and the SENTRON VL WL CubicleBus module VL COM20/21 Page 6

7 Structural principle of the function Each circuit breaker features a module The modules are connected to one another The output ( OUT), example of grading level #2, is connected to the input ( IN), example of the upstream grading level #1 modules within one grading level are connected in parallel Integration of a coupling switch is possible Integration of medium voltage is possible No configuration is required Page 7

8 Basic procedure of the function in the event of a short-circuit From the viewpoint of Q2: Short-circuit detected case a) or b) OUT Set signal! Yes Short-circuit current in the instantaneous range? No Tripping after approx. 20 ms IN Yes (case b) signal detected? No (case a) t sd = 00 ms start t = 50 ms start Tripping after approx. 50 ms Shorter tripping time via with full selectivity Yes Short-circuit still present? No Tripping after approx. 00 ms* No tripping * Applies to the reference point 12 x In. The tripping time can be longer for smaller short-circuit currents Page 8 No inherent circuit breaker times observed during the tripping

9 Basic procedure of the function in the event of a short-circuit Page Short-circuit detected! 2. Set OUT signal to upstream Q1. Check whether the short-circuit current is greater than or equal to I i (response value of the instantaneous short-circuit release)? => If so, an instantaneous tripping operation occurs. Check whether a IN signal from the downstream Q is present? 5. No IN signal present! The tripping operation occurs with the time t = 50 ms 6. A IN signal from Q detected. The time t sd = 00 ms is started 7. A check is made to see whether circuit breaker Q, which has also detected the short-circuit ( IN signal), has cleared the short-circuit. Thanks to, the tripping time of the circuit breakers, and therefore the load on the switchgear, is significantly reduced!

10 Basic procedure of the function in the event of a ground fault From the viewpoint of Q2: Ground fault detected case a) or b) OUT Set signal! IN Yes (case b) signal detected? No (case a) t g = 00 ms start t = 100 ms start Tripping after approx. 100 ms Shorter tripping time via with full selectivity Yes Ground fault still present? No Tripping after approx. 00 ms No tripping No inherent circuit breaker times observed during the tripping Page 10

11 Basic procedure of the function in the event of a short-circuit or ground fault short-circuit ON / OFF S -IN (1) -OUT (2) SD-Time Time OFF NO NO NO t SD 00 ms OFF YES NO YES t SD 00 ms ON NO YES NO t SD 00 ms ON YES YES YES t SD 00 ms ON NO NO NO t 50 ms ON YES NO YES t 50 ms ground fault ON / OFF GF -IN (1) -OUT (2) SD-Time Time OFF NO NO NO t g 00 ms OFF YES NO YES t g 00 ms ON NO YES NO t g 00 ms ON YES YES YES t g 00 ms ON NO NO NO t 100 ms ON YES NO YES t 100 ms Page 11

12 Possible applications of the function In the event of a short-circuit and a ground fault Ensuring a very short delay time with full selectivity => typically 80 ms to a maximum of 90 ms (t + mechanical tripping) in the event of a short-circuit t = 50 ms (delay time) in the event of a short-circuit t = 100 ms (delay time) in the event of a ground fault localizes the location of the short-circuit or ground fault Reduction of the loads / damage in the event of a short-circuit or ground fault in the system and for cables / lines Mixed system design with WL, VL, WN (not for new systems) Integration of coupling switches Integration of existing system parts (e.g. WN) Integration of the medium-voltage circuit breaker directly in front of the transformer Use in extensive, decentralized energy supply systems The "delay time" enables the integration of an additional, downstream protective device level without connection, provided that instantaneous tripping occurs Page 12

13 Benefits and advantages of the function Selective tripping for minimum short-circuit / ground fault duration No parameterization of the function required. This prevents setting errors. Optimization of cables, since t d always = 50 ms +5 ms (S 2 k 2 > I 2 t, the requiring energy is only dependent on I 2, since t d = const. < 100 ms) (blocking) signal is also set when the instantaneous trip unit (instantaneous release) trips Only the circuit breaker directly upstream from the fault location is switched off in the event of a short-circuit and/or a ground fault Increasing the grading levels, depending on the type of trip unit and the line length (maximum number of grading levels >20 with ETU 76B and t sd up to 000 ms) Time limitation of an arc fault short-circuit current to less than 100 ms Quick tripping time of the upstream circuit breaker if the short-circuit is "skipped". module can at any time be retrofitted without difficulty, depending on the trip unit type Connection of devices without possible (lowest level, instantaneous tripping) Page 1

14 Why is it important to clear a short-circuit quickly? The effect of the short-circuit increases as time progresses Thermal load on all equipment I cw for switching devices decreases considerably as time progresses High dynamic load on the switchgear Voltage dip during faulty operation of the other consumers Risk of persons getting an electric shock (touchable, electrically conductive external surfaces may be live) Risk for persons in front of the switchgear because of hot and toxic gases PE potential is increased near the short-circuit location, risk for electronic parts Strong magnetic fields Influence on auxiliary circuits and electronic signals Risk of arc faults and destruction of the switchgear Failure or destruction of the switching devices caused by overshooting of I cw Page 1

15 Determining the settings for t sd in a system In the event of a short-circuit, a circuit-breaker normally trips with a time of t = 50 ms. The delay time t sd is only required in a system to compensate for the potential non-tripping of an upstream circuit breaker (reserve protection). (example on the following page) Last (downstream) circuit breaker () with Setting for t sd = 0ms First upstream circuit breaker () with Setting for t sd = 100ms 50ms of delay time plus approx. 5ms of typical tripping time or 100ms minimum signal duration Second upstream circuit breaker (2) with Setting for t sd = 150ms or rounded up to the next highest setting 100ms t sd plus 5ms typical tripping time of the first circuit breaker Every additional upstream circuit breaker (1) t sd plus a maximum of 50ms action time of the downstream circuit breaker Settings of the delay time for ground fault tripping analogous under observance of the corresponding delay time Page 15

16 Determining the settings for t sd in a system Example of calculating the grading times For ETU25B ETU27B For ETU 5B to 76B Without With = ON tsd = 00 tsd = 200 => -Q11 => Arc quenching after approx. Arc quenching after approx = 5ms = 25ms 1 = ON tsd = 00 tsd = 150 => -Q21 => Arc quenching after approx. Arc quenching after approx = 5ms = 185ms 2 = ON tsd = 200 tsd = 100 => -Q1 => Arc quenching after approx. Arc quenching after approx = 25ms = 15ms = ON tsd = 100 tsd = 0 => -Q1 this makes tzsi = 50 ms = active Arc quenching after approx. => = 15ms Arc quenching after approx = 85ms tsd = 0 tsd = 0 => -Q51 => Arc quenching after approx. Arc quenching after approx = 5ms = 5ms 5 The delay times which need to be set are reduced thanks to! Page 16

17 Technical conditions Technical requirements for the line: twisted in pairs; at least 0.75mm²; maximum length: 00m recommended type LSYCY 2 x 0.75mm² Line lengths of more than 00m are possible; this depends on the cable cross-section and the protection against negative influences such as electromagnetic or transient faults A " IN" cannot be connected to more than 20 " OUT" (downstream); no more than 20 downstream circuit breakers connected in parallel A " OUT" cannot be connected to more than 8 " IN" (upstream); no more than 8 upstream circuit breakers connected in parallel The WL module must always be the first CubicleBus module to be connected to the COM15 or the terminal strip X8 (Cubicle Bus) of the WL Page 17

18 Withdrawal of the signal OUT in the event of a short-circuit after clearance of the short-circuit current, at the earliest after 100 ms, however OUT in the event of a ground fault after clearance of the short-circuit current, at the earliest after 100 ms, however MV OUT to the medium voltage after clearance of the short-circuit current, at the earliest after 500 ms, however The OUT signal is withdrawn after s at the latest Page 18

19 Example network without coupling switch SENTRON WL module 5 6 SENTRON WL module 5 6 SENTRON WL module 5 6 SENTRON WL SENTRON WL module 5 6 module 5 6 SENTRON VL SENTRON VL COM2x 5 6 Page 19

20 Example network with coupling switch without outgoing circuit breaker SENTRON WL module module SENTRON WL module 5 6 SENTRON WL Page 20

21 Example network with coupling switch and outgoing circuit breaker SENTRON WL module module SENTRON WL module 5 6 SENTRON WL SENTRON WL SENTRON WL module 5 6 module 5 6 Page 21

22 Example network with coupling switch and outgoing circuit breaker 1 t sd = 00 2 t sd = 00 Coupling switches are a grading level of their own t sd = t sd = 100 t sd = 0 The connection for the COM10 is different. Page 22

23 Example network with medium voltage Page 2 Blocking signal to medium voltage.

24 module WL Function via rotary coding switch OFF S G S+G Test module deactivated module only effective for short-time delayed short-circuit protection module only effective for ground fault protection module effective for short-time delayed short-circuit and ground fault protection Test position for checking functionality TIE BRKR Connection terminals for tie breaker IN Input for (blocking) signal -> this circuit breaker receives signal OUT Output for (blocking) signal -> this circuit breaker sends signal MV OUT Output for (blocking) signal for reporting to the medium voltage (floating contact; 50mA at 150 V AC/DC). Minimum signal duration 500ms Page 2

25 Test position Test position on rotary coding switch: signal is permanently sent to the upstream circuit breaker Module additionally sends a signal to the connected WL. In this way, a communication connection can be tested. (As if the blocking signal were coming from the downstream circuit breaker) The "Test of the S settings" function allows a potential "feeling" for the set time t sd. For t sd = 0, t = 50 ms applies Test button on module: Temporary testing of the signal displays and outputs on the module itself. Identical to all CubicleBus modules Page 25

26 TIE BRKR Modul SENTRON WL The TIE BRKR function (1, 2) ensure that even when the tie breaker is off, the IN signal (, ) directly transferred to the output OUT (5, 6). Without the TIE BRKR function the signal would not be forwarded Page 26

27 VL function or VL ETU with rotary knob: Short-circuit: Standard setting for the short-circuit protection function is = OFF. The function must be activated via communication. Ground fault: standard setting for the ground fault protection function is = OFF. The function must be activated via communication. VL ETU with LCD: plus Short-circuit: Standard setting is = OFF The short-circuit protection function can be activated via the menu in the display or via communication. Ground fault: Standard setting is = OFF The ground fault protection function can be activated via the menu in the display or via communication. Page 27

28 Required components, WL Short-circuit Ground fault For ETU5B Local parameterization WL CubicleBus module WL9111-0AT5-0AA0 ETU5B + + For ETU76B Local or remote parameterization WL9111-0AT56-0AA0 WL9111-0AT21-0AA0 ETU76B Page 28 Current converter 1200 A / 1 A

29 Required components, VL Short-circuit Ground fault VL COM20/21 ETU10* ETU10M* ETU20* ETU0M* + + VL9000-8AU00 VL9000-8AV00 ETU12* ETU22* * With communication function Page 29

30 for WL, VL, WN6 and WN1 WL / VL functionally identical WN6 Functionally identical to WL / VL Connection points can be found in the manuals of the respective circuit breakers For the technical data of the system, the weakest part is decisive in each case e.g.: WN6 upstream=> not more than parallel WN6 instead of 8 parallel WL WL VL WN6 Page 0

31 Example: function in the event of a short-circuit A) B) t sd = 00 ms OUT IN t sd = 00 ms OUT IN t sd = 200 ms OUT IN t = 50 ms OUT t = 50 ms OUT Page 1

32 Example: function in the event of a ground fault A) B) t g = 500 ms OUT IN t g = 500 ms OUT IN t g = 00 ms OUT IN t = 100 ms OUT t = 100 ms OUT Page 2

33 Example: function in the event of a short-circuit t sd = 00 ms OUT IN 1 With and without function in grading level t sd = ms Trip OUT 2 t sd = 0 ms t sd = 100 ms Trip t sd = 100 ms Page

34 List of abbreviations ETU G I I cw I i I n N MV Q S t d t t sd Electronic Trip Unit Ground fault protection Instantaneous trip unit, instantaneous short-circuit tripping Rated short-time withstand current Instantaneous short-circuit current Nominal current Neutral conductor Medium voltage Circuit breaker Short-time delayed short-circuit protection Delay time time = 50 ms (delay time) Delay time of the short-time delayed short-circuit protection Zone Selective Interlocking short-circuit identified and set OUTsignal active ( time = 50 ms) Page

35 Thank you for your attention! Rainer Huentemeier Productmanager IC LMV LV GP ACB&F V Huentemeier / Pikulicki

Maintenance/Connection/Installation Service life C/O cyclesx1000

Maintenance/Connection/Installation Service life C/O cyclesx1000 EasyPact MVS 2016 CPB100000 CPB100014 Circuit breaker. Switch disconnector. Common characteristics Number of poles Rated insulation voltage (V) Impulse withstand voltage (kv) Rated operational voltage

More information

11/0 IZM circuit-breakers, IN switch-disconnectors

11/0 IZM circuit-breakers, IN switch-disconnectors 11/0 IZM circuit-breakers, IN switch-disconnectors Contents IZM circuit-breakers, IN switch-disconnectors 11/1 from 630 A 6300 A Page Description 11/2 Technical overview 11/4 Overview of functions for

More information

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201 1SDC007402G0201 Index 1. Introduction... 2 2. Theoretical outline 2.1 Restricted earth fault... 3 2.2 Selectivity between medium and low voltage... 4 3. Application examples and wiring logic 3.1 Restricted

More information

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by: ENGINEERING SERVICES 1960 Research Drive, Suite 100, Troy, Michigan 48083 ARC FLASH REDUCTION with SEPAM RELAY ZONE SELECTIVE INTERLOCKING REVISION: December 10, 2007 (Supersedes previous versions) Prepared

More information

Documents and Addresses

Documents and Addresses Report No.: 14-041-MS Sheet: 2 Documents and Addresses Accreditation The Prüffeld der Schaltwerke, Berlin has been approved by the DAkkS (German accreditation body) according to EN ISO/IEC 17025 for tests

More information

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC DATA SHEET No. 1 December 2000 Issued by the French Lightning Protection Association Precautions to be considered for use of surge arresters tested according to Class 1 of IEC 61643-1 Foreword: The protection

More information

(With the possibility of a tripping coil for remote control) (Generally optional with an electronic tripping device)

(With the possibility of a tripping coil for remote control) (Generally optional with an electronic tripping device) Page 1 of 22 Personal tools Log in / create account Circuit-breaker From Electrical Installation Guide The circuit-breaker/disconnector fulfills all of the basic switchgear functions, while, by means of

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information

Standards for MV switchgear rated for arc flash protection

Standards for MV switchgear rated for arc flash protection Standards for MV switchgear rated for arc flash protection by Bryan Johnson, ABB Switchgear standards historically considered the electrical capability of switchgear with little regard to the effects of

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

GUIDELINES FOR SELECTIVE OVERCURRENT PROTECTION FOR ELECTRICAL SYSTEMS OF SHIPS

GUIDELINES FOR SELECTIVE OVERCURRENT PROTECTION FOR ELECTRICAL SYSTEMS OF SHIPS GUIDANCE NOTES GD 02-2007 CHINA CLASSIFICATION SOCIETY GUIDELINES FOR SELECTIVE OVERCURRENT PROTECTION FOR ELECTRICAL SYSTEMS OF SHIPS 2007 BeiJing CONTENTS CHAPTER 1 GENERAL...1 1.1 General requirements...1

More information

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems Presented for the IEEE Central TN Section / Music City Power Quality Group August 1, 2006 By Ed Larsen and Bill

More information

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

Miniature circuit-breakers S 280 UC series. System pro M. Technical data Technical data 11 Robbie Rd. / Avon, MA 02322 T:(508)513-1000 F:(508)513-1100 70 Ernest St. / Providence, RI 02905 T:(401)781-7100 www.controllerservice.com System pro M Prior to connection of aluminum

More information

Device circuit breakers Selective power distribution: branch out, individual adaptation, modular extension

Device circuit breakers Selective power distribution: branch out, individual adaptation, modular extension Power & Signal Quality TRABTECH Device circuit breakers Selective power distribution: branch out, individual adaptation, modular extension Interference-free mains supply and signal transmission A constant

More information

Electronic Circuit Breaker BASIC FIX

Electronic Circuit Breaker BASIC FIX Electronic Circuit Breaker - Number of available output channels: 2 / 4 - Non-adjustable rated current via channel - High capacitive loads start up reliably - The channels switch on sequentially and loaddependent

More information

FUNCTIONS OF CIRCUIT BREAKERS

FUNCTIONS OF CIRCUIT BREAKERS FUNCTIONS OF CIRCUIT BREAKERS Circuit breakers are designed to carry out the following functions: 1. They must be capable of closing on and carrying full-load currents at rated power factors continuously.

More information

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY Copyright Material IEEE Paper No. PCIC-2006-2 George Gregory Kevin J. Lippert Fellow Member, IEEE Senior Member, IEEE Schneider Electric

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

DESIGN STANDARD DS 29

DESIGN STANDARD DS 29 Assets Delivery Group Engineering DESIGN STANDARD DS 29 VERSION 1 REVISION 2 MAY 2018 FOREWORD The intent of Design Standards is to specify requirements that assure effective design and delivery of fit

More information

Technical collection. Cahier technique. no Energy-based discrimination for low-voltage protective devices. M. Serpinet R.

Technical collection. Cahier technique. no Energy-based discrimination for low-voltage protective devices. M. Serpinet R. Technical collection Cahier technique no. 167 Energy-based discrimination for low-voltage protective devices M. Serpinet R. Morel Cahiers Techniques are a collection of documents intended for engineers

More information

Low voltage circuit breakers

Low voltage circuit breakers Comprehensive Catalogue 2006 Super Solution Low voltage circuit breakers A-4. Technical information TD & TS MCCB Index Temperature derating Power dissipation / Resistance Application Primary use of transformer

More information

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device ABB AG - EPDS The worldʼs fastest limiting and switching device Agenda The world s fastest limiting and switching device Customers Function: Insert-holder with insert Comparison: I S -limiter Circuit-breaker

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

Circuit breakers for direct current applications

Circuit breakers for direct current applications Circuit breakers for direct current applications Complementary technical information schneider-electric.com Complementary technical information Circuit breakers for direct current applications Contents

More information

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-50 Delivery program Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection Part no. PKZM4-50 Catalog No. 222355 Eaton Catalog No. XTPR050DC1NL EL-Nummer 0004355161 (Norway)

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Technical T TECHNICAL. C o n t e n t s SPEEDFAX TM 2017

Technical T TECHNICAL. C o n t e n t s SPEEDFAX TM 2017 SPEEDFAX TM 2017 TSection C o n t e n t s Types of Power Distribution Systems T-2 T-4 Ground Fault Protection T-5 T-10 Overcurrent Protection and Coordination T-11 System Analysis T-12 Current Limiting

More information

3 - Protection components Circuit-breakers

3 - Protection components Circuit-breakers Contents - Protection components Circuit-breakers for the motor protection Selection guide..............................................page /2 Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Ecodial Advance Calculation. Technical help

Ecodial Advance Calculation. Technical help Ecodial Advance Calculation Technical help Contents Component names Main changes following the Cenelec TR50480 report Types of system earthing Types of transformer losses Diversity factor Ks Switchgear

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

Est Triplen Power Distribution Unit TPDU kVA

Est Triplen Power Distribution Unit TPDU kVA Est.1968 Triplen Power Distribution Unit TPDU 10 1600kVA Concept The Thycon Triplen Power Distribution Unit (TPDU) is designed to correct any third harmonic content on the current waveform while providing

More information

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION PROTECTION CDV 22, 62 Voltage Controlled Overcurrent Relay CDV22 relay is used for overload and fault protection for ac generators when the sustained short circuit current is less than the full load current.

More information

AGN 005 Fault Currents and Short Circuit Decrement Curves

AGN 005 Fault Currents and Short Circuit Decrement Curves Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 005 Fault Currents and Short Circuit Decrement Curves DESCRIPTION To facilitate the correct design of an electrical

More information

REF 610 Feeder Protection Relay. Technical Reference Manual

REF 610 Feeder Protection Relay. Technical Reference Manual REF 610 1MRS 755310 Issued: 05.10.2004 Version: A/05.10.2004 REF 610 Contents 1. Introduction...6 1.1. About this manual...6 1.2. The use of the relay...6 1.3. Features...6 1.4. Guarantee...8 2. Safety

More information

Electrical Arc Hazards

Electrical Arc Hazards Arc Flash Analysis 1996-2009 ETAP Workshop Operation Notes Technology, 1996-2009 Inc. Operation Workshop Technology, Notes: Arc Inc. Flash Analysis Slide 1 Electrical Arc Hazards Electrical Arcs can occur

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Electronic Circuit Breaker BASIC SMART. - Number of available output channels: 2 / 4 / 8

Electronic Circuit Breaker BASIC SMART. - Number of available output channels: 2 / 4 / 8 Electronic Circuit Breaker - Number of available output channels: 2 / 4 / 8 - Adjustable rated current via channel - High capacitive loads start up reliably - The channels switch on sequentially and loaddependent

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

Low Voltage Products & Systems. ABB Arc Guard System TM TVOC

Low Voltage Products & Systems. ABB Arc Guard System TM TVOC Low Voltage Products & Systems ABB Arc Guard System TM TVOC Accidents can occur whenever electrical energy is generated or distributed... Short circuits in electrical installations can be a hazard. This

More information

{40C54206-A3BA D8-8D8CF }

{40C54206-A3BA D8-8D8CF } Informative Annex D Incident Energy and Arc Flash Boundary Calculation Methods This informative annex is not a part of the requirements of this NFPA document but is included for informational purposes

More information

Controls Contactors and Contactor Assemblies Special Applications

Controls Contactors and Contactor Assemblies Special Applications Controls Contactors and Contactor Assemblies Special Applications Price groups 1B, 1H /2 Introduction More information can be found on the Internet: see the opening information, page 13 - Contactors for

More information

SPAJ 111 C. Sensitive earth-fault relay SPAJ 111 C. User s manual and Technical description. U aux V ~ V. f n. n ( I o>> SPCJ 1C7

SPAJ 111 C. Sensitive earth-fault relay SPAJ 111 C. User s manual and Technical description. U aux V ~ V. f n. n ( I o>> SPCJ 1C7 SPAJ 111 C Sensitive earth-fault relay User s manual and Technical description I n = 1A 5A ( I ) f n = 50Hz 60Hz 2 5 B I o I IRF SPAJ 111 C 80...265V ~ 18...80V U aux STEP I o > [%] I n 1.0 6.0 10 STEP

More information

How to maximize reliability using an alternative distribution system for critical loads

How to maximize reliability using an alternative distribution system for critical loads White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies

More information

Switching Devices Contactors and Contactor Assemblies for Switching Motors

Switching Devices Contactors and Contactor Assemblies for Switching Motors Switching Devices Contactors and Contactor Assemblies for Switching Motors groups 41B, 41H / Introduction Power contactors for switching motors /5 General data /11 SIRIUS RT10 contactors, -pole,... 50

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Effective System Grounding

Effective System Grounding Effective System Grounding By Andrew Cochran of I-Gard and John DeDad of DeDad Consulting The costs associated with losses stemming from ground faults are staggering. For example, over a seven year period,

More information

SPAJ 110 C. Earth-fault relay SPAJ 110 C. User s manual and Technical description. U aux V ~ V f n. n ( I o>> SPCJ 1C8

SPAJ 110 C. Earth-fault relay SPAJ 110 C. User s manual and Technical description. U aux V ~ V f n. n ( I o>> SPCJ 1C8 SPAJ 110 C Earth-fault relay User s manual and Technical description I n = 1A 5A ( I ) f n = 50Hz 60Hz 2 5 B I o I IRF SPAJ 110 C 80...265V ~ 18...80V U aux STEP I o > I n 0.1 0.35 0.8 STEP SPCJ 1C8 REGISTERS

More information

Coordination of LV protection devices

Coordination of LV protection devices Technical collection Coordination of LV protection devices Low voltage expert guides n 5 DBTP107EN_Couv.indd 1 12/06/2009 14:32:52 Sans titre-1 1 12/06/2009 14:13:13 Contents Glossary 2 The requirements

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

6000 W, 2450 MHz Microwave Generator GMP 60K SM 56T400 FST 3 IR

6000 W, 2450 MHz Microwave Generator GMP 60K SM 56T400 FST 3 IR 6000 W, 2450 MHz Microwave Generator GMP 60K SM 56T400 FST 3 IR Power supply It is based upon the latest switch mode power supply technology, offering size reduction (smallest 6 kw available on the market,

More information

GE Multilin technical note

GE Multilin technical note GE Digital Energy Multilin GE Multilin technical note GE Multilin releases fast and dependable short circuit protection enhanced for performance under CT saturation GE publication number: GER-4329 GE Multilin

More information

TeSys circuit-breakers Thermal-magnetic motor circuit-breakers types GV2, GV3 and GV7

TeSys circuit-breakers Thermal-magnetic motor circuit-breakers types GV2, GV3 and GV7 Presentation Thermal-magnetic motor circuit-breakers types GV, GV and GV7 GV-ME, GV-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the control

More information

Ft Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity

Ft Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity Ft Worth IEEE-PES Presented by: Doug Harris Specifications Engineer Dallas, TX Arc-Flash Hazard Mitigation & Selectivity Electrical hazards Energized circuit/conductor Today s power system engineer must

More information

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

The CABLETROLL 3600 FCI is capable of discriminating between PTP and PTG faults, and indicating the direction of the latter type.

The CABLETROLL 3600 FCI is capable of discriminating between PTP and PTG faults, and indicating the direction of the latter type. Directional fault current indicator for underground systems Presentation CABLETROLL 3600 directional Fault Current Indicators (FCI) are designed to help the operator locate faults on underground lines.

More information

Utility Interconnection and System Protection

Utility Interconnection and System Protection Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

5/2 Introduction. Unequipped Distribution Boards 5/4 Modular distribution boards 5/5 Add-on parts

5/2 Introduction. Unequipped Distribution Boards 5/4 Modular distribution boards 5/5 Add-on parts ALPHA AS Modular Distribution Boards /2 Introduction Unequipped Distribution Boards /4 Modular distribution boards / Add-on parts Assembly Kits for Unequipped Distribution Boards /6 8GK4 assembly kits

More information

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

FINAL - ET 60 - Electrician Theory Examination Marking Schedule FINAL - ET 60 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

Digital Grid Products. SICAM Fault Sensor Indicator (FSI) The Guardian for your Overhead Line Networks

Digital Grid Products. SICAM Fault Sensor Indicator (FSI) The Guardian for your Overhead Line Networks Digital Grid Products SICAM Fault Sensor Indicator (FSI) The Guardian for your Overhead Line Networks SICAM Fault Sensor Indicator (FSI) System Diagram of FSI and FCG Description SICAM Fault Sensor Indicator

More information

COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS

COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS Joost Vrielink Hans Picard Wilbert Witteman Eaton Eaton SABIC-IP Europalaan 202 7559 SC Hengelo Europalaan 202 7559 SC Hengelo Plasticslaan

More information

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources Introduction Ground fault sensing detects current that flows between a source and a (faulted) load traveling on other than

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

Chapter 4 Power Distribution Planning in Commercial, Institutional and Industrial Buildings

Chapter 4 Power Distribution Planning in Commercial, Institutional and Industrial Buildings Chapter Power Distribution Planning in Commercial, Institutional and Industrial Buildings.1 Basics for Drafting Electrical Power Distribution Systems 30.2 Network Configurations and Supply Concepts 36.3

More information

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New) XP2-R Power and reverse power relay (January 2006) Manual XP2-R (Revision New) Woodward Manual XP2-R GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS P Other accessories DELAY UNIT Type Product code Description Weight [kg] Package [pc] BZ-BX-X230-A 36696 enables to delay the undervoltage release tripping

More information

White paper. Protection against electric arc Integration between Arc Guard System TM (TVOC-2) and Emax air-circuit breakers

White paper. Protection against electric arc Integration between Arc Guard System TM (TVOC-2) and Emax air-circuit breakers White paper Protection against electric arc Integration between Arc Guard System TM (TVOC-2) and Emax air-circuit breakers Protection against electric arc Integration between Arc Guard System TM (TVOC-2)

More information

XP2-R Power and Reverse Power Relay

XP2-R Power and Reverse Power Relay XP2-R Power and Reverse Power Relay Manual XP2-R (Revision C) Woodward Manual XP2-RE Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

Solid-State Switching Devices

Solid-State Switching Devices SIRIUS Solid-State Switching Devices Contents Pages Introduction.................................. 8/2 Solid-state switching devices General data.................................. 8/3 Solid-state switching

More information

General Application Notes Remote Sense Remote On / Off Output Trim Series Operation Parallel Operation...

General Application Notes Remote Sense Remote On / Off Output Trim Series Operation Parallel Operation... General... 28 Remote Sense... 29 Remote On / Off... 30 Output Trim... 30 Series Operation... 32 Parallel Operation... 33 Synchronization... 33 Power Good Signal... 34 Electro Magnetic Filter (EMI)... 34

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Adam T. Powell, PE President Emerald Engineering, Inc. Jeffrey L. Small, Sr. Senior

More information

Improving Network Availability with Intelligent Electronic Devices

Improving Network Availability with Intelligent Electronic Devices Improving Network Availability with Intelligent Electronic Devices Guillaume Verneau - Schneider Electric - France Yves Chollot - Schneider Electric - France Pascal Cumunel - Schneider Electric - France

More information

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201 Low Voltage Products Enclosed Third Harmonic Filter and star Enclosed units Brochure S1GB 3_4 1SCC333C21 The Third Harmonic - a Growing Problem Today's electrical networks and plants are under much more

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

Electronic Circuit Breaker ECONOMY SMART. - Number of available output channels: 2 / 4 / 8

Electronic Circuit Breaker ECONOMY SMART. - Number of available output channels: 2 / 4 / 8 Electronic Circuit Breaker - Number of available output channels: 2 / 4 / 8 - Adjustable rated current for each channel - High capacitive loads start up reliably - The channels switch on sequentially and

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

SUBJECT HEADING: Switching Programmes ISSUE: 18

SUBJECT HEADING: Switching Programmes ISSUE: 18 SUBJECT: Switchgear/Switching PROCEDURE: S04 SUBJECT HEADING: Switching Programmes ISSUE: 18 DATE: Apr 2017 1. INTRODUCTION 1.1 A written programme of switching operations shall be prepared. This programme

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also, delete any other item or

More information