1 Porcelain Insulators & Covered Conductors A Problem of Dielectric Compatibility EDUARDO HILSDORF

2 Porcelain Insulators and Covered Conductors A Problem of Dielectric Compa8bility Eduardo Riani Hilsdorf Isoladores Santana Brazil PPC Insulators Manuel Luis Barreira Martinez High Voltage Lab - Federal University of Itajubá M.G. Brazil 8/25/15 1

3 Objectives Check the possibility of application of porcelain line posts insulators solid core in compact lines (Spacer Cables); Comparatively evaluate the performance of polymeric pin type insulators and porcelain line posts solid core. Motivation Evidence that the geometry of the components influences the distribution of the electrical field; Existence of electric utilities in Brazil using in Spacer Cables systems porcelain, line post insulators; Evidence of problems with polyethylene pin type insulators applied under salt polluted conditions (coastal areas). 8/25/15 2

4 Background & Initial Discussions Spacer Cable Systems First systems operated at 5 kv, with acrylic spacers and porcelain pin type insulators For 15kV voltage this conception was maintained. Field experience shows the components which had worked at 5 kv don t work well in 15 kv. The increase of the dielectric stresses applied to conductors, resulted in tracking of the conductors insulation and subsequent erosion of spacers, reducing the system reliability; The majority of failures involved insulators; The trend to failure was accelerated by the replacing of common pin type from radio free pin type insulators; The development of new insulator conception was necessary to increase reliability; 8/25/15 3

5 Background & Initial Discussions Spacer Cable Systems The use of polyethylene for cables and spacers produced positive results that it rendered obvious the use of the same material for insulators; Consequently, mainly as for the application of porcelain pin type insulators, radio free, a habit was consolidated not to use porcelain insulators in compact networks; This practice spread out and utilities adopted, as a standard, polymeric pin insulator in compact networks. 8/25/15 4

6 Compact Lines Field Operation! Contamination! Electrical Field! Internal defects (bubbles)! Partial internal discharge! Dielectric compatibility! Mechanical, thermal and environmental stresses! Sun exposition (ultraviolet rays)! Tracking and erosion Figure 2 Electronic radiography of insulator containing internal air bubbles coming from the manufacturing process Figure 1 Photo of sections in polymeric spacers exhibiting non-uniform material. Figure 3 - Photos of insulators including internal defects, which degradated in operation a time after their installation in network. 8/25/15 5

7 Application of porcelains to electrical insulator Figure 4 - Radio - Free Treated Figure 5 Illustration of radio-free treatment effects on electrical field lines in ANSI 55-6 Class insulator.! Conventional Lines! Radio free treatment! Semiconducting glaze on the top and thread! Reduces the effects of radio-interference! Reduces punctures problems! Covered Cables incompatibility 8/25/15 6

8 EXPERIMENTAL METHODOLOGY Evaluations by Finite Element- Computational Simulation Using Comsol Multiphysics applied to 15 and 25 kv covered conductors, with pin type polymeric insulators, solid core line post porcelain insulators and solid core line post porcelain insulators with semi-conductor glaze (radio-free) were simulated; Voltage of 2U0, that is, 16 and 29 kv for systems with 15 kv and 25 kv class voltage respectively. Figure 6: a) Ceramic line post insulator P 1, b) Polymeric pin type insulator. 8/25/15 7

9 Evaluations by Finite Element 15kV Computational Simulation INSULATOR REFERENCE P 1 P STUDY P 2 P 3 POLYMERIC PIN TYPE 15KV P 1 - RT BASIC DIMENSIONS ( MM) H 210 D 125 / 45 H 208 D 125 / 45 H 208 D 125 / 55 H 205 D 125 / 63 H 133 D 139 H 200 D 125 / 60 Where: H height of insulator since support up to cable position; D diameter of shed / body diameter. E1 Electrical field gradient in the interface of conductor surface and insulating layer E2 Electrical field gradient in the interface of conductor and insulator support 8/25/15 8

10 Evaluations by Finite Element 25kV Computational Simulation INSULATOR REFERENCE P 4 P 1 POLYMERIC PIN TYPE - 25 KV BASIC DIMENSIONS (MM) H 305 D 150 / 80 H 210 D 125 / 45 H 152 D 190 Where: H height of insulator since support up to cable position; D diameter of shed / body diameter. E1 Electrical field gradient in the interface of conductor surface and insulating layer E2 Electrical field gradient in the interface of conductor and insulator support 8/25/15 9

11 Evaluations by Finite Element RF treatment Figure 7 - Study of electrical field around post type ceramic insulator P1 - RT radio-free. Figure 8 Study of electrical field on P1 ceramic insulator line post type without radio-treatment 8/25/15 10

12 Analysis by Corona Cameras (UV Camera)! Applied voltage was 38.5 kv, that is about 5U0 for a 13,8kV system class voltage. Figure 10 Image of corona effect on insulators designed for 15kV voltage class a) Ceramic insulator solid core line post type, b) Polymeric insulator pin type, c) Ceramic insulator pin type. 8/25/15 11

13 Test of Dielectric Compatibility with Multi-stresses. Parameters for test are:! Temperature on external surface of the cable: 60 ºC;! Rain cycles of 5 minutes aspersion followed by 15 minutes without rain;! Aspersion: 1 mm/minute;! Water conductivity: 750 µs/cm;! Applied voltage: 2U0;! After thirty continuous testing days, the sets, cable, insulators and spacers shall not exhibit any kind of damage, tracking, puncture or erosion. Figure 11 Basic installation diagram for the test of multistress electrical compatibility in conformity to LAT-EFEI. 8/25/15 12

14 Test of Dielectrical Compatibility with Multi-stresses. Two arrangements tested with two different cables. Gray color at left was manufactured with two layers, one internal semiconductive next to conductor, and the second, external, in standard XLPE. Black color at right was manufactured with one single layer in XLPE. Figure 12 Images of the starting of the dielectric compatibility test on 3 line post ceramic insulators, 15 kv voltage class, P2 reference, carried out on September 16th /25/15 13

15 Test of Dielectric Compatibility with Multi-stresses. Figure 13 Image of the dielectric compatibility test on line post type ceramic insulator, 15 kv voltage class, P2 reference, phase "b", on September 16th days. Figure 15 Image of the dielectric compatibility test on line post type ceramic insulator, 15 kv voltage class, P2 reference, phase "b" on September 16th days. Figure 16 Image of dielectric compatibility test on line post type ceramic insulator, 15kV voltage class, reference P2, phase "b", on September 16th days. 8/25/15 14

16 THE INFLUENCE OF CABLE DESIGN AND MANUFACTURING Since defects have arisen along the cable with semi-conductive layer developing towards insulators and along the entire cable without semi-conductive layer in a random way, the need to investigate this phenomenon was taken into account. Other types of covered conductors of North American origin exist. In general they are manufactured with three layers, where: A semi-conducting layer, independent from the cable class of voltage; A layer of low density polyethylene with predominant insulating function; An external layer of high density polyethylene HDPE with electro-mechanical function. In this case, a new test was carried out on 3 sets of 15kV voltage class insulators P2 reference A branch of covered conductor of North-American origin was used, duly followed up through daily visual inspection During the test and at the test end, no damage, tracking or erosion were observed on interface region between cable and insulators, as can be verified in the images on Figures 19 and 20. Therefore, the test set up withstood the combined stresses, as claimed by the standards. 8/25/15 15

17 THE INFLUENCE OF CABLE DESIGN Figure 19 Image of start of dielectrical compatibility test with 3 insulators ceramic post type, 15kV class voltage, P2 Figure 20 - Image of the end of dielectrical compatibility test on 3 ceramic reference, carried out in October insulators post type, 15kV class voltage, P2 reference carried out in October /25/15 16

18 CONCLUSIONS 1/2! It is possible to obtain suitable values of electric field gradients for porcelain insulators, solid core post type, calculating them through finite element method,! With a corona camera, was not possible observe any significant difference in corona level between ceramic insulators post type, and polymeric pin type insulators. On the contrary, for ceramic pin type, the electric activity level was extremely high, confirming that its usage is not recommendable with covered cables;! Through dielectric compatibility test, it was observed that it is possible to use solid core post type insulators in configurations applying covered conductors. It is, however, recommended to apply dielectric compatibility tests for the validation of each specific project, since the studies of electric field by finite elements indicate that the insulator design has a relevant influence on the result of electrical field distribution on the system parts involved;! The behavior of the interface between cables and insulators do not present noteworthy problems, as images emphasizing electric activities in UV field indicate. The same, however, cannot be said as regards to the cables, which are not suitable, even if the insulators spacers and remaining accessories are developed for this specific application, as indicated by results of tests and suitable studies. Therefore, in this paper it is not considered that the insulators were the inductors of the problems observed on the cables. 8/25/15 17

19 CONCLUSIONS 2/2! It is important to register that, due to cable insulating failures, in regions next to insulators, polymeric pin insulators can exhibit carbonization, transition of phase solid - liquid, or even fire development involving insulator and cable, taking to system interruptions and potential conditions of accidents involving third party: This problem does not occurs in porcelain insulators because, even when the cable loses the insulation, the porcelain insulator is able to maintain system operating, since, on account of the level of dissipated consumed power during failure process, they do not develop phase transitions and do not come up to flammability condition.! Part of the problem verified in this paper, that is, the failure aspect and development, is related to the fact that national normalization for covered conductors does not consider the application of the dielectric compatibility test. Therefore a lag exist between the manufacturing of covered conductors and that of their accessories, as demonstrated in this paper, for both porcelain and polymeric materials, as reported. This procedure creates distinct requirements for parts which must operate together, what is a problem for the purchaser, mainly with the ageing of compact networks, because it will be observed only when it will turn into an insoluble problem. 8/25/15 18

20 Thank you 8/25/15 19

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring Tsinghua University, Beijing, China, August -9, H-6 Evaluation of Distribution Line Spacers through the Leakage Current Monitoring A. G. Kanashiro *, W. Pinheiro and G. F. Burani Institute of Electrotechnics

More information

Evaluation of Distribution Line Spacers Located Near the Coast

Evaluation of Distribution Line Spacers Located Near the Coast Evaluation of Distribution Line Spacers Located Near the Coast WALTER PINHEIRO ARNALDO G. KANASHIRO 2 GERALDO F. BURANI 2 Consultant Engineer University of São Paulo Av. Prof. Luciano Gualberto, 289, São

More information

DECCA AUSTIN INSULATORS

DECCA AUSTIN INSULATORS DECCA AUSTIN INSULATORS A PRELIMINARY INVESTIGATION INTO SOME FAILURE MODES OF EGG TYPE INSULATORS WESTERN ASSOCIATION OF BROADCASTERS ENGINEERING SECTION VANCOUVER APRIL 29 MAY 1, 1975 TITLE A PRELIMINARY

More information

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison

More information

Introduction. Corona. Corona Cameras. Origo Proposed Corona Camera. Origo Corporation Corona Camera Product Inquiry 1

Introduction. Corona. Corona Cameras. Origo Proposed Corona Camera. Origo Corporation Corona Camera Product Inquiry 1 Origo Corporation Corona Camera Product Inquiry 1 Introduction This Whitepaper describes Origo s patented corona camera R&D project. Currently, lab and daylight proof-of-concept tests have been conducted

More information

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS 1. Introduction 2. Classification of High Voltage Tests 3. Test Voltages 4. High Voltage Testing of Electrical Apparatus 1. INTRODUCTION Purpose

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

Defects in Nonceramic Insulators: Can They be Detected in a Timely Manner?

Defects in Nonceramic Insulators: Can They be Detected in a Timely Manner? Defects in Nonceramic Insulators: Can They be Detected in a Timely Manner? S. Gorur and S. Sivasubramaniyam Department of Electrical Engineering, Arizona State University, Tempe, AZ, USA This work was

More information

HIGH PRESSURE MOULDING TECHNOLOGY

HIGH PRESSURE MOULDING TECHNOLOGY HIGH PRESSURE MOULDING TECHNOLOGY Romuald Lemaitre, Pierre Gaillard, Franck Tortey, Paul Woodward franck.tortey@alcatel-lucent.fr Alcatel - Lucent, 536 Quai de La Loire 62100 Calais Abstract: The Optical

More information

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV CABLE DESCRIPTION Single- or multi-phase electric cable for creating a weak external magnetic field,so as to obtain a cable wherein at last one of the conductors is assembled from two or more insulated

More information

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss. Detection of Partial Discharge Using Ultrasound Problem In electrical systems, especially above 1,000 Volts, sufficient and properly maintained equipment insulation helps ensure equipment longevity. However,

More information

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

Multilayered Functional Insulation System (MFIS) for AC Power Transmission in High Voltage Hybrid Electrical Propulsion

Multilayered Functional Insulation System (MFIS) for AC Power Transmission in High Voltage Hybrid Electrical Propulsion 2017 Multilayered Functional Insulation System (MFIS) for AC Power Transmission in High Voltage Hybrid Electrical Propulsion Team Lead Maricela Lizcano, PhD Research Materials Engineer Materials Chemistry

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012 High Frequency Voltage Stress Presented by: Flore Chiang Date: March 30, 2012 Now the additional data is available! ground rules: 1. intro to PD. 2. experimental results. 3. comparison with current practice.

More information

Life Prediction of Mold Transformer for Urban Rail

Life Prediction of Mold Transformer for Urban Rail , pp.13-18 http://dx.doi.org/10.14257/astl.2014.48.03 Life Prediction of Mold Transformer for Urban Rail Hyun-il Kang and Won-seok Choi Department of Electrical Engineering, Hanbat National University,

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

54. IWK Internationales Wissenschaftliches Kolloquium International Scientific Colloquium

54. IWK Internationales Wissenschaftliches Kolloquium International Scientific Colloquium 07-10 September 2009 PROCEEDINGS 54. IWK Internationales Wissenschaftliches Kolloquium International Scientific Colloquium Information Technology and Electrical Engineering - Devices and Systems, Materials

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

Condition-based maintenance of power transformers Complete three-phase system Turns Ratio: Recovery Voltage: Winding Resistance:

Condition-based maintenance of power transformers Complete three-phase system Turns Ratio: Recovery Voltage: Winding Resistance: ETP SYSTEM Condition-based maintenance of power transformers The predictive and condition based maintenance is nowadays accepted as the most efficient solution to guarantee the proper operation of critical

More information

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER Analysis of Major Changes to Arrester Standards IEC 60099-4 STEVE BREWER Analysis of Major Changes to Arrester Standard IEC 60099-4 Steve Brewer- Senior Product Manager - HPS Arrester Business Unit Agenda

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

Xu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP)

Xu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP) Xu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP) April 12, 2010 Slide 1 Content MV Machine Winding Insulation Stress LEAP Methodology LEAP Standard LEAP from

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

SAE AE-2 Lightning Committee White Paper

SAE AE-2 Lightning Committee White Paper SAE AE-2 Lightning Committee White Paper Recommended Camera Calibration and Image Evaluation Methods for Detection of Ignition Sources Rev. NEW January 2018 1 Table of Contents Executive Summary... 3 1.

More information

CHAPTER 2 POLARIZATION SPLITTER- ROTATOR BASED ON A DOUBLE- ETCHED DIRECTIONAL COUPLER

CHAPTER 2 POLARIZATION SPLITTER- ROTATOR BASED ON A DOUBLE- ETCHED DIRECTIONAL COUPLER CHAPTER 2 POLARIZATION SPLITTER- ROTATOR BASED ON A DOUBLE- ETCHED DIRECTIONAL COUPLER As we discussed in chapter 1, silicon photonics has received much attention in the last decade. The main reason is

More information

Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions

Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions R. Hajian M. Mirzaie Babol University of Technology, Iran Reza.hajian.7@gmail.com,

More information

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable Subrata Karmakar and Soumya Mishra Department of Electrical Engineering National Institute of Technology Rourkela-769008

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE

A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE Mojtaba Rostaghi-Chalaki, A Shayegani-Akmal, H Mohseni To cite this version: Mojtaba Rostaghi-Chalaki, A Shayegani-Akmal,

More information

10kV XLPE cable ampacity improvement research in Guangzhou area

10kV XLPE cable ampacity improvement research in Guangzhou area 10kV XLPE cable ampacity improvement research in Guangzhou area Zhixin SUO Guopei WU Jian CHEN China Southern Power Grid China China Southern Power Grid China China Southern Power Grid China soney@126.com

More information

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Power Factor Insulation Diagnosis: Demystifying Standard Practices Power Factor Insulation Diagnosis: Demystifying Standard Practices Dinesh Chhajer, PE 4271 Bronze Way, Dallas Tx Phone: (214) 330 3238 Email: dinesh.chhajer@megger.com ABSTRACT Power Factor (PF) testing

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

International Journal on Electrical Engineering and Informatics - Volume 10, Number 2, June 2018

International Journal on Electrical Engineering and Informatics - Volume 10, Number 2, June 2018 International Journal on Electrical Engineering and Informatics - Volume 1, Number 2, June 218 The Study on Leakage Current Characteristics and Electrical Properties of Uncoated Ceramic, RTV Silicon Rubber

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

REPORT OF PERFORMANCE TIC

REPORT OF PERFORMANCE TIC REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE Ju-Chu Hsieh 1, Cheng-Chi Tai 1, Ching-Chau Su 1, Chien-Yi Chen 1, Ting-Cheng Huang 1, Yu-Hsun Lin 2 1 Department

More information

Performance Analysis of High Voltage Insulators Surface Condition Using Time-frequency Distribution

Performance Analysis of High Voltage Insulators Surface Condition Using Time-frequency Distribution Performance Analysis of High Insulators Surface Condition Using Time- Distribution A. Sulaiman, A. R. Abdullah, A. Aman, N.Norddin and N. Q. Zainal Abidin Faculty of Electrical Engineering Universiti Teknikal

More information

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

Field Measurement of Transmission Cable Dissipation Factor

Field Measurement of Transmission Cable Dissipation Factor Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 1 Field Measurement of Transmission Cable Dissipation Factor John H. Cooper, Power Delivery Consultants, Inc. Abstract This presentation

More information

Tratos High Voltage cables

Tratos High Voltage cables March 2013 Tratos High Voltage cables Cables for a moving world www.tratos.eu Introduction High Voltage Cables Tratos is an international manufacturer and supplier of High & Extra High Voltage cable up

More information

HARMONIC ANALYSIS OF LEAKAGE CURRENT OF SILICON RUBBER INSULATORS IN CLEAN-FOG AND SALT-FOG

HARMONIC ANALYSIS OF LEAKAGE CURRENT OF SILICON RUBBER INSULATORS IN CLEAN-FOG AND SALT-FOG HARMONIC ANALYSIS OF LEAKAGE CURRENT OF SILICON RUBBER INSULATORS IN CLEAN-FOG AND SALT-FOG Mojtaba Rostaghi-Chalaki, A Shayegani-Akmal, H Mohseni To cite this version: Mojtaba Rostaghi-Chalaki, A Shayegani-Akmal,

More information

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse A. Elzowawi, A. Haddad, H. Griffiths Abstract the electric discharge and soil ionization phenomena have a great effect

More information

Insulation Tester Manual

Insulation Tester Manual Insulation Tester Manual *******Insulation resistance tester dedicated to the measurement of water-cooled generator test, but also can be used for laboratory or field testing insulation testing to do.

More information

HIGH RELIABILITY SEMI-RIGID COAXIAL CABLE ASSEMBLIES

HIGH RELIABILITY SEMI-RIGID COAXIAL CABLE ASSEMBLIES 1/22 Titre / Title HIGH RELIABILITY SEMI-RIGID COAXIAL CABLE ASSEMBLIES Rédigé par / Written by Responsabilité / Responsibility Date Signature S. POIZAT Space Project Manager 25/10/2016 Vérifié par / Verified

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Capacitive Voltage Transformer (CVT) Commissioning Test

Capacitive Voltage Transformer (CVT) Commissioning Test Capacitive Voltage Transformer (CVT) Commissioning Test Fahad Rashid, Engineer, Revenue Metering, IESO June 12, 2018 Outline IT Checks Market Rule Reference Commissioning Market Manual Requirements Capacitive

More information

DETECTOR OF COVERED CONDUCTOR FAULTS

DETECTOR OF COVERED CONDUCTOR FAULTS DETECTOR OF COVERED CONDUCTOR FAULTS Stefan HAMACEK 1, Stanislav MISAK 1 1 Department of Electrical Power Engineering, Faculty of Electrical Engineering and Computer Science, VSB Technical University of

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction

More information

A. Product Description: Stranded conductor insulated wire.

A. Product Description: Stranded conductor insulated wire. SECTION 16120CPPR CONDUCTORS AND CABLE PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. Product Requirements: Provide products as follows: 1. All building wire shall be stranded copper (no aluminum wire). 2.

More information

The Application of TOFD Technique on the Large Pressure Vessel

The Application of TOFD Technique on the Large Pressure Vessel 17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China The Application of TOFD Technique on the Large Pressure Vessel Yubao Guangdong Special Equipment Inspection Institute Floor

More information

Transformer Engineering

Transformer Engineering Transformer Engineering Design, Technology, and Diagnostics Second Edition S.V. Kulkarni S.A. Khaparde / 0 \ CRC Press \Cf*' J Taylor & Francis Group ^ч_^^ Boca Raton London NewYork CRC Press is an imprint

More information

This Certificate consists of 75 pages in total.

This Certificate consists of 75 pages in total. Object Heat shrinkable indoor termination 1086-16 Type MZDNK-3-15-C Rated voltage, U 0 /U (U m ) 8,7/15 (17,5) kv Conductor material Cu Conductor cross-section 3 x 185 mm 2 Insulation material XLPE Manufacturer

More information

DETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, UNARMORED M17/74-RG213, AND ARMORED M17/74-RG215

DETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, UNARMORED M17/74-RG213, AND ARMORED M17/74-RG215 INCH-POUND MIL-DTL-17/74C 13 April 2010 SUPERSEDING MIL-C-17/74C 18 July 1985 DETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, UNARMORED M17/74-RG213, AND ARMORED M17/74-RG215

More information

B2-302 METHODS FOR LIMITING RADIO INTERFERENCE FROM EHV OHL INSULATOR SETS S.V.KRYLOV, L.V.TIMASHOVA JSC VNIIE. (Russia)

B2-302 METHODS FOR LIMITING RADIO INTERFERENCE FROM EHV OHL INSULATOR SETS S.V.KRYLOV, L.V.TIMASHOVA JSC VNIIE. (Russia) 21, rue d'artois, F-75008 Paris http://www.cigre.org B2-302 Session 2004 CIGRÉ METHODS FOR LIMITING RADIO INTERFERENCE FROM EHV OHL INSULATOR SETS S.V.KRYLOV, L.V.TIMASHOVA JSC VNIIE (Russia) Summary Radio

More information

ELEC Transmission i and

ELEC Transmission i and ELEC-1104 Lecture 5: Transmission i and Distribution ib ti Power System Layout Transmission and Distribution The transmission system is to transmit a large amount of energy from the power stations s to

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

Electric Field Analysis of High Voltage Condenser Bushing

Electric Field Analysis of High Voltage Condenser Bushing Proc. of Int. Conf. on Current Trends in Eng., Science and Technology, ICCTEST Electric Field Analysis of High Voltage Condenser Bushing Anguraja.R 1 and Pradipkumar Dixit 2 1 Research Scholar, Jain University,

More information

Insulator Testers Frequently Asked Questions. September Version: 1.1

Insulator Testers Frequently Asked Questions. September Version: 1.1 Insulator Testers Frequently Asked Questions September 2017 Version: 1.1 1 FAQ Contents Page Q1: When is it not safe to work on power lines?... 3 Q2: What is the tolerance of the Positron Insulator Tester

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

EE 1402 HIGH VOLTAGE ENGINEERING

EE 1402 HIGH VOLTAGE ENGINEERING EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency

More information

A6.6 9 th International Conference on Insulated Power Cables A6.6

A6.6 9 th International Conference on Insulated Power Cables A6.6 Development Process of extruded HVDC cable systems Dominik HÄRING, Gero SCHRÖDER, Andreas WEINLEIN, Axel BOSSMANN Südkabel GmbH, (Germany) dominik.haering@suedkabel.com, gero.schroeder@suedkabel.com, andreas.weinlein@suedkabel.com,

More information

GUJARAT TECHNOLOGICAL UNIVERSITY

GUJARAT TECHNOLOGICAL UNIVERSITY GUJARAT TECHNOLOGICAL UNIVERSITY POWER ELECTRONICS (24) HIGH VOLTAGE ENGINEERING SUBJECT CODE: 2162411 BE 6 th SEMESTER Type of Course: Engineering Science (Electrical) Prerequisite: NA Rationale: The

More information

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley ArborLec Solutions Inc. CIGRE WG 21:04 in 1994 Purpose of diagnostic test is: To evaluate and locate degradation phenomena

More information

Effects of ZnO varistor degradation on the overvoltage protection mechanism of electronic boards

Effects of ZnO varistor degradation on the overvoltage protection mechanism of electronic boards Effects of ZnO varistor degradation on the overvoltage protection mechanism of electronic boards H.Yadavari, B. Sal, M. Altun Istanbul Technical University, Istanbul, Turkey E.N. Erturk, B.Ocak ARCELIK

More information

Hendrix Tap, Tie & Ground Wire

Hendrix Tap, Tie & Ground Wire Hendrix Tap, Tie & Ground Wire MADE IN U.S.A. 53 Old Wilton Road Milford, NH 03055-3119 603-673-2040 www.marmonutility.com A Marmon Wire & Cable/Berkshire Hathaway Company Tap Wire Description Hendrix

More information

Standards Update Notice (SUN) Issued: June 6, 2017

Standards Update Notice (SUN) Issued: June 6, 2017 Standard Information Standard Number: UL 758 Standard Name: Standard for Safety for Appliance Wiring Material Standard Edition and Issue Date: 3 rd Edition Dated May 2, 2014 Date of Revisions: 2 nd Ed.

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

Modelling of Pulsed Eddy Current Testing of wall thinning of carbon steel pipes through insulation and cladding

Modelling of Pulsed Eddy Current Testing of wall thinning of carbon steel pipes through insulation and cladding Modelling of Pulsed Eddy Current Testing of wall thinning of carbon steel pipes through insulation and cladding S Majidnia a,b, J Rudlin a, R. Nilavalan b a TWI Ltd, Granta Park Cambridge, b Brunel University

More information

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION Erling ILDSTAD, NTNU, (Norway), Erling.Ildstad@elkraft.ntnu.no Mildrid SELSJORD, SINTEF Energy Research, (Norway), Mildrid.Selsjord@sintef.no

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

WHITE PAPER CIRCUIT LEVEL AGING SIMULATIONS PREDICT THE LONG-TERM BEHAVIOR OF ICS

WHITE PAPER CIRCUIT LEVEL AGING SIMULATIONS PREDICT THE LONG-TERM BEHAVIOR OF ICS WHITE PAPER CIRCUIT LEVEL AGING SIMULATIONS PREDICT THE LONG-TERM BEHAVIOR OF ICS HOW TO MINIMIZE DESIGN MARGINS WITH ACCURATE ADVANCED TRANSISTOR DEGRADATION MODELS Reliability is a major criterion for

More information

Transformer Technology Seminar What to consider at Design Reviews

Transformer Technology Seminar What to consider at Design Reviews Pomona CA, May 24-25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Why to perform Design Review Meetings? To ensure both parties having the same understanding of the

More information

OPERATING AND MAINTENANCE MANUAL CORONAFINDER UV VIEWER

OPERATING AND MAINTENANCE MANUAL CORONAFINDER UV VIEWER A Division of www.syntronics.net OPERATING AND MAINTENANCE MANUAL CORONAFINDER UV VIEWER SYNTRONICS, LLC 3500 Shannon Park Drive Fredericksburg, VA 22408 USA Telephone and fax: (540) 374-1000 E-mail: nightvision@syntronics.net

More information

DETAIL SPECIFICATION SHEET CABLE, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, M17/75-RG214 AND M17/75-RG365

DETAIL SPECIFICATION SHEET CABLE, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, M17/75-RG214 AND M17/75-RG365 INCH-POUND 20 April 2016 SUPERSEDING w/amendment 2 23 February 20 DETAIL SPECIFICATION SHEET CABLE, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 0 OHMS, M17/7-RG214 AND M17/7-RG36 Inactive for new design after

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor Dielectric response and partial discharge measurements on stator insulation at varied low frequency Nathaniel Taylor Rotating Electrical Machines : The Stator and its Windings turbo-generator motor hydro-generator

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60099-4 Edition 2.1 2006-07 Edition 2:2004 consolidated with amendment 1:2006 Surge arresters Part 4: Metal-oxide surge arresters without gaps for a.c. systems IEC 2006 Copyright

More information

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION *

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION * Morris, E.A. and Siew, W.H. (2018) A comparison of AC and DC partial discharge activity in polymeric cable insulation. In: 2017 IEEE 21st International Conference on Pulsed Power (PPC). IEEE, Piscataway,

More information

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE 09-1026 TYPE TEST CERTIFICATE OF COMPLETE TYPE TEST OBJECT single-core power cable TYPE 76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE Rated voltage, U o /U (U m ) 76/132 (145) kv Conductor material

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

SURFACE CORONA INCEPTION ON STRESS GRADING SYSTEM IN END-TURN REGIONS OF ROTATING MACHINES

SURFACE CORONA INCEPTION ON STRESS GRADING SYSTEM IN END-TURN REGIONS OF ROTATING MACHINES SURFACE CORONA INCEPTION ON STRESS GRADING SYSTEM IN END-TURN REGIONS OF ROTATING MACHINES A. Kumada, D. Onishi, T. Nakamura, K. Hidaka, (Univ. of Tokyo) S. A. Boggs (Nonlinear Systems., Inc), Y. Tsuboi,

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

Pulse Arrested Spark Discharge (PASD) Wiring Diagnostic**

Pulse Arrested Spark Discharge (PASD) Wiring Diagnostic** 8 th Joint FAA/DoD/NASA Conference on Aging Aircraft February, 5 Pulse Arrested Spark Discharge (PASD) Wiring Diagnostic** Larry X Schneider *, M. Dinallo, R. K. Howard, S. F. Glover, G. E. Pena **, T.

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:

More information

Simulation Model of Partial Discharge in Power Equipment

Simulation Model of Partial Discharge in Power Equipment Simulation Model of Partial Discharge in Power Equipment Pragati Sharma 1, Arti Bhanddakkar 2 1 Research Scholar, Shri Ram Institute of Technology, Jabalpur, India 2 H.O.D. of Electrical Engineering Department,

More information

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): 2321-0613 Evaluation of String Efficiency and Voltage Distribution of 400 KV over a String of Glass

More information

Remote Assessment of High Voltage. Porcelain Insulators Using Radiated. Electromagnetic Field Signature

Remote Assessment of High Voltage. Porcelain Insulators Using Radiated. Electromagnetic Field Signature Remote Assessment of High Voltage Porcelain Insulators Using Radiated Electromagnetic Field Signature by Ehsan Azordegan A Thesis Submitted to the Faculty of Graduate Studies of The University of Manitoba

More information

Superconducting RF Cavity Performance Degradation after Quenching in Static Magnetic Field

Superconducting RF Cavity Performance Degradation after Quenching in Static Magnetic Field Superconducting RF Cavity Performance Degradation after Quenching in Static Magnetic Field T. Khabiboulline, D. Sergatskov, I. Terechkine* Fermi National Accelerator Laboratory (FNAL) *MS-316, P.O. Box

More information

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe PARTIAL DISCHARGE IN PLANAR TRANSFORMER Ing. Anar MAMMADOV, Doctoral Degreee Programme (1) Dept. of Microelectronics, FEEC, BUT E-mail: xmamed00@stud.feec.vutbr.cz Supervised by Dr. Jaroslav Boušek ABSTRACT

More information