CHAPTER 4 LOCATION OF FAULTS IN TRANSFORMERS DURING IMPULSE TESTING

Size: px
Start display at page:

Download "CHAPTER 4 LOCATION OF FAULTS IN TRANSFORMERS DURING IMPULSE TESTING"

Transcription

1 99 CHAPTER 4 LOCATION OF FAULTS IN TRANSFORMERS DURING IMPULSE TESTING 4.1 INTRODUCTION A new technique for the location of faults in power transformers is described in this chapter, based on the spectral analysis of signals recorded during the lightning impulse test on transformers. Location of faults in windings is still a difficult task and requires the untanking of the test object in repair shops. The methods adopted to locate the site of the fault and to determine the extent of winding failure during the dielectric test are discussed in the ensuing sections based on an experimental analysis, and an analyical simulation of a transformer winding. It is based on the demarcation of certain specified parameters on the signal spectrum for the measurement and identification of winding failure. The temporal records of applied voltage, neutral current, the capacitive transferred current surge, the transferred surge voltage function and their corresponding frequency spectra are used for this. 4.2 STATEMENT OF THE PROBLEM It would be appropriate, as a first step, to analyse the behaviour of a uniform single layer winding when energised by an impulse voltage. This is not severely restrictive, as single layer windings have served to elucidate many features of the frequency response of windings as reported by Degeneff R.C (1977,1982),

2 100 Dick E.P and Erven C.C (1978). Further, with adequate mathematical underpinning, results from such a winding can form the basis for a more generalised treatment for power transformer applications. The aims of this chapter are as follows: 1) To propose methods for location of winding fault during impulse tests. 2) To assess the magnitude of failure of winding. 3) To confirm the utility of the methods with experimental results. In all cases, the term fault, here refers to a breakdown across a section of the winding during the impulse test. The following sections discuss the case of a breakdown of non-restoring insulation. This is not a trivial issue as several investigations use differing principles for analysing faults during impulse tests. For example, Malewski R and Poulin B (1985) state that the appearance of fault on the neutral current is similar to that observed when a portion of the winding is physically short by a piece of wire. Malewski R. and Poulin B (1988) used a diac across sections for elucidating certain features with the transfer function method for discharge analysis. This chapter progresses with the above conceptual approach to simulate fault phenomenon in windings. 4.3 SIMULATION OF FAULT Analysis is done on records obtained from experimental and analytical simulation during impulse testing. An exercise is done for this by deliberately connecting a fault simulating model across the section to be faulted which creates a destructive fault within windings. The applied voltage, and the winding current

3 101 response prior to and after placing the short are recorded and their difference is evaluated for failure analysis as explained in chapter EXPERIMENTAL ANALYSIS The experimental verification is done on a specially constructed layer winding transformer model having the high voltage coil built with 20 tapping arrangement over the length and housed with a grounded metal core and shield as described in Appendix 1. It differs from the Abetti coil in this respect that it has a secondary winding, which could be used for additional measurement and also has a low value ground capacitance Cg due to the presence of additional metallic former in the inner and outer diameter. The fault model for the experimental analysis of inter-section fault uses a neon bulb to directly short between sections of the layer winding. The impulse test is done using a Marx generator PU12 Haefley model for conducting an impulse or the chopped impulse test. The arrangement uses a voltage divider, current shunt, measuring cables, the 10-bit digital storage oscilloscope and the 12-bit HP-VXI based virtual instrument configured for the impulse testing as described in Appendix 3. The voltage signals and current signals are recorded while applying full or reduced level lightning impulse signal and tail chopped impulse signals as specified in IEC 76 (1980) standards. The experimental simulation is done by connecting the fault model deliberately between 5% or 10% tapping of the high voltage winding as shown in Fig The actual observation of current records measured using current shunt, shielded cables are as shown in Fig. 4.2.

4 102 -Q: CRO Tnmfemd sazge voltage Figure 4.1 Lightning impulse test terminal connections and methods of failure detection 43.2 DETAILS OF ANALYTICAL SIMULATION A single layer winding often adopted in literature as a 10-section Abetti coil and reported by Abetti P.A and Maginniss (1954), DegenefF R.C (1977),and Jayashankar V (1994) is used as the circuit model for analytical simulation, the details of which are given in Appendix 2. The RLC lumped parameter model has the first few resonant frequencies as 7.39K, 16.5K, 28K, 41K.etc.

5 103 The relative shifts in these frequencies are used for analysis. Analytical simulation of fault across sections of the coil is done using a time-operated switch. The fault is created with a switch Si being connected across the section that is to be faulted. The switch remains open for a time upto tj after the energisation of the coil by the Marx generator. At tj the switch closes and continues to stay in the closed position until the end of the simulation. This approach is adopted because in actual situations, the breakdown will always occur after a finite instance if the coil has originally not been subjected to catastrophic dielectric failure. This justifies the use of ft. The necessity of keeping the switch closed until breakdown is obvious since this work mainly caters to the breakdown of non- restoring insulation. The study uses PSPICE (Programmable Simulation Package for in Circuit Emulation, Version 7.0) for analytical simulation. During simulation the input voltage is obtained from a Marx generator circuit model as a constant source. Hence, further analysis of the minor faults is done on the current spectrum only. This is equivalent to using the transfer function (TF) analysis. In all impulse measurements the difference between currents at reduced and full voltages are of primary importance. The sequence of simulations is as follows: 1. The simulation is done for a standard lightning impulse (LI) signal initially with no fault across the winding. The records of the applied voltage V and winding current i are stored in files. 2. A fault is created with an initial value of tj (of 20 ps) on a portion of the winding between % of its length. The records of voltage V and winding current i are stored.

6 The simulation is repeated at various locations of the winding length as top, middle, and bottom sections. Sectional short-circuit is created for 5%, 10%, 15% etc, of the percentile length of coil to simulate sectional winding fault. The short-circuiting is done between 20%-30%, 60%-70%, 70-80% % etc..tapping, and their files are stored. 4. The analytical simulations are also repeated for other values of h such as 5 jis, 40ps to simulate effects of breakdown at different instances of time. This approach is justified here since it is based on the fact that transformer windings with different insulation types have different breakdown strength. The existence of f will accentuate the difference, if any. The simulations are also done with impulse chopped on the tail at 2ps, 6ps as a part of type test as specified by IEC 76 (1980) for insulation integrity tests. Fig. 4.3 is a typical waveform showing the difference in neutral current before and after the occurrence of a 10% sectional short circuit fault. Fig. 4.4 shows the experimental measurement of the current signal for locating the site of the winding fault by shifting the disruptive fault simulating model at various sections as 10%-20%...50%-60%...90%-100%. The corresponding spectrum of the signals is calculated using the Fast Fourier Transform (FFT) algorithm as shown in Fig for faults from 0-10% to 50-60%. The spectral response is similar for the experimental and simulation model except that the resonant frequency values are different since these are system dependent. Coils of varying dimension have their impedance parameter differing, because of which the natural resonant inherent frequencies are also different. For the experimental coil used, a span of 0 to 560 khz has been used to analyse faults as low as 5%. The first three resonant frequencies of this coil are 85kHz, 156 khz, 243kHz. The spectrum showed a relative shift in resonant frequency poles when a fault occurred compared to the spectrum of the non-faulty winding as explained by

7 Voltage Time > 10ns Fig.4.2 Lightning impulse test records (1) Applied Impulse voltage (2) Neutral winding current (3) Capacitive transferred current prior to fault (4) Capacitive transferred current after a fault TeK stop: single Seq S.ooms/s Mathl Zoom: 1657oX Vert ~ i.ox Horz,-j is ar Jrutrv' m4ovoms cwrhr -tteohw1 Mathl loomv 10.0ms Fig. 4.3 Winding current (a) prior to fault (b) for 10% short circuit fault across a section (c) difference between record (b) and (a)

8 106 t,2s js/division > Fig. 4.4 Winding current for 10% short-circuit fault across sections

9 Fig. 4.5 Spectra of winding current records from Fig

10 Fig. 4.6 Spectra of neutral winding current (A) prior to (B) after short circuit fault 108

11 109 Degeneff R.C (1977), Malewski R and Poulin B (1988), and Jayashankar V (1994). This is enumerated in Fig PROCEDURE FOR ESTIMATING FAULT LOCATION It would appear at the first glance that time domain records would suffice for the analysis of fault location. However, this is not possible as the instance of fault ti can change and also in practice, the applied voltage can itself change between two successive applications. For this reason a frequency domain approach is used. The spectrum of the current i(f) is obtained from the time domain record by using a standard Fast Fourier Transform (FFT) routine. Similarly, the spectrum of the voltage v(f)is obtained from the time domain record of the voltage v(t). Various parameters are obtained from the frequency spectrum, and the variations for occurrences of fault at different locations are discussed based on the analytical and experimental simulation. We propose the estimation of the location of the winding fault using specially defined variables namely, the Pole Variation Response (PVR) Amplitude Variation Response (AVR) Uniform Coil Resonance Parameter (UCRP) The percentages of deviations are calculated using spectral analysis of signals prior to and after the occurrence of fault and is given as ((Afauit A nofault) / A nofault)* 100 (4.1)

12 110 where A is any of the mentioned variables. An exercise is done in the spectrum between unfaulted and faulted conditions of the winding model using the records of neutral winding current and transferred surge current. The computation of the three parameters is as follows: (1) Pole Variation Response (PVR) An arbitrary fault is created across the section of winding as 5%, 10% tapping to confirm the above method. The frequency spectrum of the uniform coil is obtained. Prior to a fault the first few resonant frequencies are f. After a fault the resonant frequency pole peaks are shifted. These are measured as f The percentage variation in the pole peaks are determined as PVR = I f'n-fn/fj *100 (4.2) The pole variation response evaluated with the first three resonant frequencies of the experimental coil, during simulation of a 10% short-circuit fault at various sections along the length of the coil is shown in Fig.4.7a. (2) Amplitude Variation Response (AVR) Similarly the amplitude of each of the resonant frequency pole peaks is determined as A prior to and A',, after simulating the section-section fault. The percentage variation in amplitude is evaluated as AVR= I A -A /A *100 (4.3)

13 Ill Fig.4.7b shows the AVR evaluated for a 10%, 20%, and 25% short- circuit fault at different locations between the line end and ground end of the experimental coil. (3) Uniform coil resonant parameter (UCRP). The basic frequency response (in terms of admittance) of a layer winding shows certain resonant peaks. The behavior at these peaks can be approximated to a series resonant behavior as shown by Glaninger P (1986). Under such circumstances the response close to the resonant peak can be approximated as series RLC circuit. Such circuit possesses a bandwidth that is computed from the 3 db points about the resonant frequency. This concept is invoked to define the parameter called uniform coil resonance (UCRP). This is computed as the area enclosed up to the 3 db points for each of the resonant frequency as UCRP = I AR -ARn / ARn I * 100 (4.4) Here AR' and AR are the area within each of the pole peaks in the faulted and non-faulted winding spectra respectively. Fig.4.7c shows the UCRP evaluated for the experimental coil for a 10%, 20%, 30% short-circuit fault at different locations between the line end and ground end of the experimental coil. At least the first three resonant frequencies are vital as reported by Udayakumar K and Vanaja R (2000). It has been found that if a fault occurs in the line end of the winding, the variation in the parameters AVR and UCRP is very high than if it is in the ground section. If fault is in the middle section, the variation of UCRP is very high and that of AVR is very low as shown in Fig The x-axis shows the n lh position of the

14 112 tapping of the winding from line end to ground end where n=0-10%, 10%-20%... and the y-axis shows the respective variables evaluated using Equation (4.1). As referred in Pritindra and Chowdhuri (1996), the transformer coil, subject to lightning impulse, responds like a system of capacitance and inductance. Corrective prevails in the beginning of the process with the voltage across line terminals given as V, = 2Vr [l-e'vzrcfr] (4.5) where Z = Surge impedance of winding CefT = Surge capacitance of coil Vf = Amplitude of signal V, = Voltage transmitted to the transformer The voltage distribution in winding is presented as V(x) - B,e(YX) + B2e('TX) (4.6) where 1 C9 Y = I - or nc. where Bj, B2 are boundary conditions with the origin (x=0), the line end V(0) = 1 per unit and the ground end V( ) ~ 0. Bi = - exp (-a)/2 sin ha and a (4.7) B2 = exp (a)/2 Sin ha (4.8) And thus V(x) = Sin h[a(l-x/^)]/(sin ha) (4.9) It is seen that the percentage variation AVR and UCRP are complements of each other for occurrence of failure in various locations between the line end and the ground end as presented in Table 4.1. The table presents the results for a 10% short-circuit fault. Similar charecteristics are observed for higher percentage faults also. Faults near the line end occur with resonant poles having higher UCRP in

15 113 contrast to faults near the ground end. This is due to the fact that the line end is stressed more. This is because if the oncoming voltage wave is with higher frequencies, then the critical frequency of the winding will pile up at the entrance of the winding, producing a stress concentration there, due to which the current signals have higher energy density spectrum. Hence line end faults report higher percentage deviation of amplitude and pole peak variations than the ground end faults of similar magnitude. This can be explained as due to the travelling wave causing a transition from the capacitive voltage distribution into the inductive voltage distribution through damped oscillations of the signal. Near the ground end, the signal hence has oscillatory current that is exponentially decaying. The decaying factor is deterministic of the coil dimensions and the reactive impedance of the windings. Failure analyses of the winding subjected to lightning impulse 1.2 /50 jjls and lightning impulse chopped at tail near 2 ps or 6 ps are studied using Equation (4.1) to Equation (4.4) on the Abetti coil designed for a = 4.0 to a = 14 where a = Vcg/cs. Here cg represents ground capacitance and cs represents series capacitance. The spatial distribution of the corresponding pole shifted resonant frequencies, namely the PVR near the line end, midwinding and ground end of the coil with grounded neutral is estimated along the length of the winding (xh). This is shown in Fig. 4.8 and Fig. 4.9, for the first three resonant frequencies for a 10% fault. The Fig.4.8 shows the relative shift of resonant frequency poles between the nonfaulted and faulted windings for a similar fault occurring at the line end, midwinding and ground end of the coil as explained in Equation (4.1). In the figures peak number represent the corresponding first few resonant frequency poles. Each resonant frequency oscillates in time around specific frequencies of the coil and these space harmonics are called the natural frequencies of the coil that are specific to coil dimensions. The space harmonics along the winding with grounded neutral present a pattern of maximum and minimum shift in the resonant

16 114 frequency poles by evaluation using Equation (4.1) and are shown in the y-axis. The Fig.4.9 represents clearly the relative shift for the first three space harmonics or resonant frequency poles, with (n=3) with different a for different impulse inputs. The first resonant frequency has a minimum deviation of the pole peak in the mid-section of the winding than at the line end or ground end. The second resonant frequency shows a minimum shift at the 1/4, 3/4 points and a maximum at the V2 point of the winding, and so on for higher resonant harmonics. From the analysis it is observed that, a fault near the line end shows a higher variation in the fundamental frequency compared to a fault near the midwinding and ground end. On the other hand, a fault near the midwinding shows second resonant frequency to have a predominantly higher shift in comparison to the odd harmonics. Similar patterns are observed for higher space harmonics also. Table 4.1 Percentile variation in AYR and UCRP for fault xi i Variation in % AVR Variation in % UCRP Top 10% tapping Middle 10% tapping Bottom 10% tapping ANALYSIS OF SIMULATION RESULTS FOR ESTABLISHING MAGNITUDE OF FAULTS At the first instance it might appear that an exercise similar to that carried out on the value of the resonant frequencies, might serve to elucidate the magnitude of faults. In practice this does not occur. More important is that, a different method is needed for analysing the percentage of faults. This is because while the value of

17 115 resonant frequencies is relevant for the case of a transformer with significant capacitances to ground, a degenerate case of pure inductances will not show resonant frequencies. However, the magnitude of failure is one that can be addressed even for the degenerate case. To explain this, a fault is simulated on a section of the inductance by a switch S that is closed after a finite time as explained in the previous section. Fig.4.10 shows the neutral current response of a coil modeled as a R-L circuit and energised with lightning impulse (LI). The current signals before and after a breakdown fault are as seen in figure for 2.5%, 5%, 10%, 15% magnitudes of winding breakdown. Fig.4.11 shows the corresponding magnitude spectrum of each. In principle, this implies that greater attention is to be paid to the low frequency regions of the response. The region before the first resonant peak, in particular, helps to identity the magnitude of the fault. In the method proposed here, the low frequency response of the coil is studied in order to estimate the magnitude of the fault. With reference to the equivalent circuit of the transformer, at the low frequencies the section is inductive. A bandpass filter is used such that the upper cutoff frequency is well before the first resonant frequency. The slope of the spectrum earlier to the fundamental resonant frequency is steeper for a higher percentage magnitude of sectional short-circuited fault. Fig.4.12 shows the magnitude spectrum of current with the magnitude of short simulated on 10%, 20%... 70%, of the experimental winding. The x-axis shows the lower frequency range of the coil and the y-axis shows the magnitude in linear scale.

18 Fig. 4.7a Pole variation response PVR (A) f, (B) f2 (C) f3 UCRP cp AVR 4.7b Amplitude variation response AVR (A) 10% (B) 20% (C)25% Percentage of winding Fig. 4.7c Uniform coil resonance parameter UCRP (A) 10% (B) 20% (C)30% Fig. 4.7 Percentage variation of parameter

19 117 Frequency, khz Frequency, khz 3 4 Peak number 3 4 Peak number Fig.4.8 Relative variation of pole peak of resonant frequencies for similar fault at (a) Top (b) middle (c) ground end of winding

20 116 PERCENTILE LENGTH (x/l) Fig.4.9b Pole variation response for an input of 1.2 /6 ps on a coil of a = 4

21 119 PERCENTILE LENGTH (xfl) Fig.4.9c Pole variation response for an inpnt of ps on a coil of a = 4 PERCENTILE LENGTH (x/l) Fig.4.9d Pole variation response for an input of 1.2 /2 ps on a coil of a = 14

22 Tim* (ms) o B e C g; ^ OQ o '» 2 M 2 vo Jm 0 1 ^ ^ s> fit ** a ^2 o as 3 S 3 5?» a «3 B s a l O sr OTP ts 5* m. 2. =? 2 O - n n n E.w o ^ 3 CTQ A m plitude, Ampere V) <s /-s * e <2 N» flj JD VJ (N

23 800 a) Frequency,kHz 10 Frequency, khz Amplitude, ma Amplitude, ma Amplitude, ma 03 ol ' r i i t 10 Frequency, khz Fig Winding current spectra for the inductive coil records shown in Fig 4.10 for (a) 2.5% (b)5% (c) 10% (d) 15% short circuit

24 122 A similar response is observed while simulating destructive faults on the Abetti coil model and the result is as shown in Fig In all the above cases the amplitude of current spectrum before the first resonant peak is indicative of the percentage magnitude of the fault. Fig presents another interesting result observed while simulating the fault at various sections, along x/f% of the winding. It is noted that for the same percentage magnitude of short-circuit fault (say 5%, 10%, 20%), across sections, a fault near the mid-section has a steeper slope of the initial dc line of the spectrum prior to the first resonant frequency. This indicates relatively a higher deviation in comparison to the spectrum of the current without a winding fault. This result can support the task for locating the site of fault. 4.6 CONFIRMATION BASED ON A RANDOM TEST A blind test is performed, by creating an arbitrary magnitude of fault across some section of the winding. The difference current observed is as shown in Fig.4.3. The estimation technique described earlier with Equation (4.1) to Equation (4.4) is applied to the waveform. Analysing the spectra as seen earlier in Fig 4.5, Fig.4.6, Fig.4.7, Fig.4.9, Fig.4.14 and Table 4.1, the probable location of the fault is identified. The magnitude of the fault between turns of winding is also determined from the slope of the signal prior to the first resonant frequency as demonstrated in Fig RESULTS FROM OTHER SUPPLEMENT OSCILLOGRAMS Two other supplementary oscillograms are available during the impulse test of a two winding transformer as specified in IEC 722(1982). They are either the transferred surge or the capacitive transferred current across the secondary.

25 123 Absolute magnitude, volts Frequency, khz Fig Identification of magnitude of fault as a variation in slope before the first resonant frequency for the experimental coil Frequency, khz Fig Identification of magnitude of fault as a variation in slope before the first resonant frequency for the analytical coil

26 124 Frequency for 10*/«fault, Hz Fig Identifying location of sectional fault from magnitude variation in slope of winding current

27 Fig.4.15 Signal records before occurrence of fault from neutral current method and transferred surge method a) Applied voltage V(t) b) Transferred surge output voltage Vwt(t) c) Applied voltage V(t) d) Neutral winding curent iwt(t)

28 Fig Voltage records for 10% fault from transferred surge method 126

29 Fig Spectrum of each record shown in Fig

30 ' i %......I.. Time > lops Fig. 4.18a Neutral winding current a. No fault b. 5% fault c. 10% fault d. 15% fault Time > lops Fig. 4.18b Capacitive transferred winding current a. No fault b. 5% fault c. 10% fault d. 15% fault Voltage > mv Voltage > mv Voltage > mv O t r <0 _o u Time > lops Fig. 4.18c Transferred winding response a. No fault b. 5% fault c. 10% fault d. 15% fault

31 129 Frequency---- > 50 KHz Fig. 4.19a Spectra of corresponding records in Fig. 4.18a Frequency---- > 100 KHz Fig. 4.19bSpectra of corresponding records in Fig. 4.18b Frequency---- > 50 KHz Fig. 4.19c Spectra of corresponding records in Fig. 4.18c

32 130 Experiments are also done to analyse the sensitivity of these two methods for fault location. Fig.4.15 shows typical records of voltage and winding current for the case of the transferred voltage and the neutral current method of an unfaulted winding. Fig.4.16 shows the records from transferred surge analysis for the experimental coil. Fig.4.17 shows the corresponding spectra of each. However, the estimated parameters with the neutral current are complementary to the results obtained from the transferred surge method. Fig.4.18 shows a sample of each of the experimental analysis using the neutral current method, capacitive transferred surge method and transferred surge voltage method. Fig shows the respective spectra for each of the records. Similar characteristics in the estimated parameters are observed with capacitive transferred current surge method and the transferred surge voltage method. 4.7 CONCLUSION An attempt is made in proposing a method for the location of non-restoring fault in transformer windings. The Abetti coil used here for simulation is a popularly acknowledged model used in simulation studies. The results presented from simulation and experimental study illustrate the above as a reliable method for locating the site of defect and in detecting the magnitude of fault prior to untanking of the transformer in test center. Having established methods for location and identification of faults and discharge, additional methods for fault location are possible using advanced timefrequency (t-f) response analysis as discussed in the following chapter. Further, the usefulness of the new t-f technique for an improved signal analysis in the presence of noise is shown.

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation W. Buesch 1) G. Palmieri M.Miesch J. Marmonier O. Chuniaud ALSTOM LTD 1) ALSTOM LTD High Voltage Equipment

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 2321-0613 Conditioning Monitoring of Transformer Using Sweep Frequency Response for Winding Deformation

More information

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding Research Journal of Applied Sciences, Engineering and Technology 10(10): 1102-1107, 2015 DOI: 10.19026/rjaset.10.1879 ISSN: 2040-7459; e-issn: 2040-7467 2015 Maxwell Scientific Publication Corp. Submitted:

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements EMEL ONAL Electrical Engineering Department Istanbul Technical University 34469 Maslak-Istanbul TURKEY onal@elk.itu.edu.tr http://www.elk.itu.edu.tr/~onal

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization International Journal of Electrical Engineering. ISSN 0974-58 Volume 4, Number 4 (0), pp. 499-50 International Research Publication House http://www.irphouse.com High Frequency Modeling of Two Limb Series

More information

Experiment No. 2 Pre-Lab Signal Mixing and Amplitude Modulation

Experiment No. 2 Pre-Lab Signal Mixing and Amplitude Modulation Experiment No. 2 Pre-Lab Signal Mixing and Amplitude Modulation Read the information presented in this pre-lab and answer the questions given. Submit the answers to your lab instructor before the experimental

More information

Contents. Core information about Unit

Contents. Core information about Unit 1 Contents Core information about Unit UEENEEH114A - Troubleshoot resonance circuits......3 UEENEEG102A Solve problems in low voltage AC circuits...5 TextBook...7 Topics and material Week 1...9 2 Core

More information

Switching Induced Transients:

Switching Induced Transients: Switching Induced Transients: Transformer switching is the most commonly performed operation in any power delivery system and most of the times this operation can be performed without any undesirable consequences.

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik,

More information

Basic electronics Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras Lecture- 17. Frequency Analysis

Basic electronics Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras Lecture- 17. Frequency Analysis Basic electronics Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras Lecture- 17 Frequency Analysis Hello everybody! In our series of lectures on basic electronics learning

More information

Chapter 2. The Fundamentals of Electronics: A Review

Chapter 2. The Fundamentals of Electronics: A Review Chapter 2 The Fundamentals of Electronics: A Review Topics Covered 2-1: Gain, Attenuation, and Decibels 2-2: Tuned Circuits 2-3: Filters 2-4: Fourier Theory 2-1: Gain, Attenuation, and Decibels Most circuits

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 GENERAL The efficacy of a power system depends mainly on the reliability of the power equipment connected to the system. The power transformer is one of the most essential

More information

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM

More information

CHAPTER 3 ACTIVE INDUCTANCE SIMULATION

CHAPTER 3 ACTIVE INDUCTANCE SIMULATION CHAPTER 3 ACTIVE INDUCTANCE SIMULATION The content and results of the following papers have been reported in this chapter. 1. Rajeshwari Pandey, Neeta Pandey Sajal K. Paul A. Singh B. Sriram, and K. Trivedi

More information

Comparison of Signal Attenuation of Multiple Frequencies Between Passive and Active High-Pass Filters

Comparison of Signal Attenuation of Multiple Frequencies Between Passive and Active High-Pass Filters Comparison of Signal Attenuation of Multiple Frequencies Between Passive and Active High-Pass Filters Aaron Batker Pritzker Harvey Mudd College 23 November 203 Abstract Differences in behavior at different

More information

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical

More information

Non-ideal Behavior of Electronic Components at High Frequencies and Associated Measurement Problems

Non-ideal Behavior of Electronic Components at High Frequencies and Associated Measurement Problems Nonideal Behavior of Electronic Components at High Frequencies and Associated Measurement Problems Matthew Beckler beck0778@umn.edu EE30 Lab Section 008 October 27, 2006 Abstract In the world of electronics,

More information

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14) Advances in UHV Transmission and Distribution Prof. B Subba Reddy Department of High Voltage Engg (Electrical Engineering) Indian Institute of Science, Bangalore Lecture 36 Measurements of High Voltages

More information

(i) Determine the admittance parameters of the network of Fig 1 (f) and draw its - equivalent circuit.

(i) Determine the admittance parameters of the network of Fig 1 (f) and draw its - equivalent circuit. I.E.S-(Conv.)-1995 ELECTRONICS AND TELECOMMUNICATION ENGINEERING PAPER - I Some useful data: Electron charge: 1.6 10 19 Coulomb Free space permeability: 4 10 7 H/m Free space permittivity: 8.85 pf/m Velocity

More information

Analysis and Design of Autonomous Microwave Circuits

Analysis and Design of Autonomous Microwave Circuits Analysis and Design of Autonomous Microwave Circuits ALMUDENA SUAREZ IEEE PRESS WILEY A JOHN WILEY & SONS, INC., PUBLICATION Contents Preface xiii 1 Oscillator Dynamics 1 1.1 Introduction 1 1.2 Operational

More information

Computer Aided-Program for Validation of HV Impulse Measuring Systems from Unit Step Response

Computer Aided-Program for Validation of HV Impulse Measuring Systems from Unit Step Response Computer Aided-Program for Validation of HV Impulse Measuring Systems from Unit Step Response P. YUTTHAGOWITH and S. PHOOMVUTHISARN Center of Excellence in Electrical Power Technology, Faculty of Engineering

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Introduction to Signals and Systems Lecture #9 - Frequency Response. Guillaume Drion Academic year

Introduction to Signals and Systems Lecture #9 - Frequency Response. Guillaume Drion Academic year Introduction to Signals and Systems Lecture #9 - Frequency Response Guillaume Drion Academic year 2017-2018 1 Transmission of complex exponentials through LTI systems Continuous case: LTI system where

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Table of Contents...2. About the Tutorial...6. Audience...6. Prerequisites...6. Copyright & Disclaimer EMI INTRODUCTION Voltmeter...

Table of Contents...2. About the Tutorial...6. Audience...6. Prerequisites...6. Copyright & Disclaimer EMI INTRODUCTION Voltmeter... 1 Table of Contents Table of Contents...2 About the Tutorial...6 Audience...6 Prerequisites...6 Copyright & Disclaimer...6 1. EMI INTRODUCTION... 7 Voltmeter...7 Ammeter...8 Ohmmeter...8 Multimeter...9

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

Emitter base bias. Collector base bias Active Forward Reverse Saturation forward Forward Cut off Reverse Reverse Inverse Reverse Forward

Emitter base bias. Collector base bias Active Forward Reverse Saturation forward Forward Cut off Reverse Reverse Inverse Reverse Forward SEMICONDUCTOR PHYSICS-2 [Transistor, constructional characteristics, biasing of transistors, transistor configuration, transistor as an amplifier, transistor as a switch, transistor as an oscillator] Transistor

More information

CHAPTER 6 INTRODUCTION TO SYSTEM IDENTIFICATION

CHAPTER 6 INTRODUCTION TO SYSTEM IDENTIFICATION CHAPTER 6 INTRODUCTION TO SYSTEM IDENTIFICATION Broadly speaking, system identification is the art and science of using measurements obtained from a system to characterize the system. The characterization

More information

ELECTRIC CIRCUITS. Third Edition JOSEPH EDMINISTER MAHMOOD NAHVI

ELECTRIC CIRCUITS. Third Edition JOSEPH EDMINISTER MAHMOOD NAHVI ELECTRIC CIRCUITS Third Edition JOSEPH EDMINISTER MAHMOOD NAHVI Includes 364 solved problems --fully explained Complete coverage of the fundamental, core concepts of electric circuits All-new chapters

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

CHAPTER 8 The PN Junction Diode

CHAPTER 8 The PN Junction Diode CHAPTER 8 The PN Junction Diode Consider the process by which the potential barrier of a PN junction is lowered when a forward bias voltage is applied, so holes and electrons can flow across the junction

More information

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation P.S.Diwakar High voltage Engineering National Engineering College Kovilpatti, Tamilnadu, India S.Sankarakumar Department

More information

SHOCK RESPONSE SPECTRUM SYNTHESIS VIA DAMPED SINUSOIDS Revision B

SHOCK RESPONSE SPECTRUM SYNTHESIS VIA DAMPED SINUSOIDS Revision B SHOCK RESPONSE SPECTRUM SYNTHESIS VIA DAMPED SINUSOIDS Revision B By Tom Irvine Email: tomirvine@aol.com April 5, 2012 Introduction Mechanical shock can cause electronic components to fail. Crystal oscillators

More information

EE 422G - Signals and Systems Laboratory

EE 422G - Signals and Systems Laboratory EE 422G - Signals and Systems Laboratory Lab 3 FIR Filters Written by Kevin D. Donohue Department of Electrical and Computer Engineering University of Kentucky Lexington, KY 40506 September 19, 2015 Objectives:

More information

Sirindhorn International Institute of Technology Thammasat University

Sirindhorn International Institute of Technology Thammasat University Sirindhorn International Institute of Technology Thammasat University School of Information, Computer and Communication Technology COURSE : ECS 34 Basic Electrical Engineering Lab INSTRUCTOR : Dr. Prapun

More information

VLSI is scaling faster than number of interface pins

VLSI is scaling faster than number of interface pins High Speed Digital Signals Why Study High Speed Digital Signals Speeds of processors and signaling Doubled with last few years Already at 1-3 GHz microprocessors Early stages of terahertz Higher speeds

More information

SHF Communication Technologies AG. Wilhelm-von-Siemens-Str. 23D Berlin Germany. Phone Fax

SHF Communication Technologies AG. Wilhelm-von-Siemens-Str. 23D Berlin Germany. Phone Fax SHF Communication Technologies AG Wilhelm-von-Siemens-Str. 23D 12277 Berlin Germany Phone +49 30 772051-0 Fax ++49 30 7531078 E-Mail: sales@shf.de Web: http://www.shf.de Application Note Jitter Injection

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends.

UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends. UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends. 2 What is tree of a network? It is an interconnected open

More information

Filter Considerations for the IBC

Filter Considerations for the IBC APPLICATION NOTE AN:202 Filter Considerations for the IBC Mike DeGaetano Application Engineering Contents Page Introduction 1 IBC Attributes 1 Input Filtering Considerations 2 Damping and Converter Bandwidth

More information

Laboratory 4. Bandwidth, Filters, and Diodes

Laboratory 4. Bandwidth, Filters, and Diodes Laboratory 4 Bandwidth, Filters, and Diodes Required Components: k resistor 0. F capacitor N94 small-signal diode LED 4. Objectives In the previous laboratory exercise you examined the effects of input

More information

High-Voltage Test and

High-Voltage Test and Eberhard Wolfgang Hauschild Lemke High-Voltage Test and Measuring Techniques ^ Springer Contents 1 Introduction 1 1.1 Development of Power Systems and Required High-Voltage Test Systems 1 1.2 The International

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

ECE 2006 University of Minnesota Duluth Lab 11. AC Circuits

ECE 2006 University of Minnesota Duluth Lab 11. AC Circuits 1. Objective AC Circuits In this lab, the student will study sinusoidal voltages and currents in order to understand frequency, period, effective value, instantaneous power and average power. Also, the

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Modeling and Analysis of Systems Lecture #9 - Frequency Response. Guillaume Drion Academic year

Modeling and Analysis of Systems Lecture #9 - Frequency Response. Guillaume Drion Academic year Modeling and Analysis of Systems Lecture #9 - Frequency Response Guillaume Drion Academic year 2015-2016 1 Outline Frequency response of LTI systems Bode plots Bandwidth and time-constant 1st order and

More information

Coherence and time-frequency analysis of impulse voltage and current measurements

Coherence and time-frequency analysis of impulse voltage and current measurements Coherence and time-frequency analysis of impulse voltage and current measurements Jelena Dikun Electrical Engineering Department, Klaipeda University, Klaipeda, Lithuania Emel Onal Electrical Engineering

More information

High-Voltage Test Techniques

High-Voltage Test Techniques High-Voltage Test Techniques Dieter Kind Kurt Feser 2nd Revised and Enlarged Edition With 211 Figures and 12 Laboratory Experiments Translated from the German by Y. Narayana Rao Professor of Electrical

More information

New Method for Transformer Winding Fault Detection

New Method for Transformer Winding Fault Detection POSTER 2015, PRAGUE MAY 14 1 New Method for Transformer Winding Fault Detection Martin KNENICKY Department of Electrical Power Engineering, Faculty of Electrical Engineering, Czech Technical University

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

ECE 201: Introduction to Signal Analysis

ECE 201: Introduction to Signal Analysis ECE 201: Introduction to Signal Analysis Prof. Paris Last updated: October 9, 2007 Part I Spectrum Representation of Signals Lecture: Sums of Sinusoids (of different frequency) Introduction Sum of Sinusoidal

More information

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the

More information

Lab 1: Basic RL and RC DC Circuits

Lab 1: Basic RL and RC DC Circuits Name- Surname: ID: Department: Lab 1: Basic RL and RC DC Circuits Objective In this exercise, the DC steady state response of simple RL and RC circuits is examined. The transient behavior of RC circuits

More information

Department of Electronic Engineering NED University of Engineering & Technology. LABORATORY WORKBOOK For the Course SIGNALS & SYSTEMS (TC-202)

Department of Electronic Engineering NED University of Engineering & Technology. LABORATORY WORKBOOK For the Course SIGNALS & SYSTEMS (TC-202) Department of Electronic Engineering NED University of Engineering & Technology LABORATORY WORKBOOK For the Course SIGNALS & SYSTEMS (TC-202) Instructor Name: Student Name: Roll Number: Semester: Batch:

More information

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 4 TRANSIENT ANALYSIS Prepared by: Dr. Mohammed Hawa EXPERIMENT 4 TRANSIENT ANALYSIS

More information

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com

More information

CHAPTER 8 The PN Junction Diode

CHAPTER 8 The PN Junction Diode CHAPTER 8 The PN Junction Diode Consider the process by which the potential barrier of a PN junction is lowered when a forward bias voltage is applied, so holes and electrons can flow across the junction

More information

TUNED AMPLIFIERS 5.1 Introduction: Coil Losses:

TUNED AMPLIFIERS 5.1 Introduction: Coil Losses: TUNED AMPLIFIERS 5.1 Introduction: To amplify the selective range of frequencies, the resistive load R C is replaced by a tuned circuit. The tuned circuit is capable of amplifying a signal over a narrow

More information

Measurement and Analysis for Switchmode Power Design

Measurement and Analysis for Switchmode Power Design Measurement and Analysis for Switchmode Power Design Switched Mode Power Supply Measurements AC Input Power measurements Safe operating area Harmonics and compliance Efficiency Switching Transistor Losses

More information

Improved Method for Winding Deformation Detection Sensitivity in Transformer

Improved Method for Winding Deformation Detection Sensitivity in Transformer International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 10ǁ October 2013 ǁ PP.48-55 Improved Method for Winding Deformation Detection Sensitivity

More information

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site

More information

Class E/F Amplifiers

Class E/F Amplifiers Class E/F Amplifiers Normalized Output Power It s easy to show that for Class A/B/C amplifiers, the efficiency and output power are given by: It s useful to normalize the output power versus the product

More information

Laboratory Exercise 6 THE OSCILLOSCOPE

Laboratory Exercise 6 THE OSCILLOSCOPE Introduction Laboratory Exercise 6 THE OSCILLOSCOPE The aim of this exercise is to introduce you to the oscilloscope (often just called a scope), the most versatile and ubiquitous laboratory measuring

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

BAKISS HIYANA BT ABU BAKAR JKE,POLISAS

BAKISS HIYANA BT ABU BAKAR JKE,POLISAS BAKISS HIYANA BT ABU BAKAR JKE,POLISAS 1 1. Explain AC circuit concept and their analysis using AC circuit law. 2. Apply the knowledge of AC circuit in solving problem related to AC electrical circuit.

More information

1.Explain the principle and characteristics of a matched filter. Hence derive the expression for its frequency response function.

1.Explain the principle and characteristics of a matched filter. Hence derive the expression for its frequency response function. 1.Explain the principle and characteristics of a matched filter. Hence derive the expression for its frequency response function. Matched-Filter Receiver: A network whose frequency-response function maximizes

More information

A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2

A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2 A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2 1 Ministry of Electricity, Republic of Iraq 2 Institute of

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY EHV AC AND DC TRANSMISSION

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY EHV AC AND DC TRANSMISSION Generation of High A.. Voltages: Most of the present day transmission and distribution networks are operating on a.c. voltages and hence most of the testing equipment relate to high a.c. voltages. A single

More information

Downloaded From JNTU World. B.Tech II Year II Semester (R09) Supplementary Examinations December/January 2014/2015 GENERATION OF ELECTRIC POWER

Downloaded From JNTU World. B.Tech II Year II Semester (R09) Supplementary Examinations December/January 2014/2015 GENERATION OF ELECTRIC POWER Downloaded From Code: 9A02403 B.Tech II Year II Semester () Supplementary Examinations December/January 2014/2015 GENERATION OF ELECTRIC POWER Answer any FIVE questions 1 Discuss the advantages and disadvantages

More information

MAHALAKSHMI ENGINEERING COLLEGE

MAHALAKSHMI ENGINEERING COLLEGE MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK -------------------------------------------------------------------------------------------------------------- Sub. Code : EE2353 Semester

More information

FREQUENCY RESPONSE AND PASSIVE FILTERS LABORATORY

FREQUENCY RESPONSE AND PASSIVE FILTERS LABORATORY FREQUENCY RESPONSE AND PASSIVE FILTERS LABORATORY In this experiment we will analytically determine and measure the frequency response of networks containing resistors, AC source/sources, and energy storage

More information

Square Wave Testing for Frequency Response of Amplifiers

Square Wave Testing for Frequency Response of Amplifiers by Kenneth A. Kuhn Nov. 23, 2007, rev. Oct. 3, 2008 Introduction Square waves are rich in odd numbered harmonics and have a very simple shape that makes it easy to observe frequency response limitations

More information

Figure Derive the transient response of RLC series circuit with sinusoidal input. [15]

Figure Derive the transient response of RLC series circuit with sinusoidal input. [15] COURTESY IARE Code No: R09220205 R09 SET-1 B.Tech II Year - II Semester Examinations, December-2011 / January-2012 NETWORK THEORY (ELECTRICAL AND ELECTRONICS ENGINEERING) Time: 3 hours Max. Marks: 80 Answer

More information

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS Shashi Kumar 1, Brajesh Kumar Prajapati 2, Vikramjeet Singh 3 1, 2 Students, Electrical Engineering Department Greater Noida

More information

Improvements to Secondary Windings of Tesla Transformers

Improvements to Secondary Windings of Tesla Transformers Applied Physics Research; Vol. 9, No. 1; 2017 ISSN 1916-9639 E-ISSN 1916-9647 Published by Canadian Center of Science and Education Improvements to Secondary Windings of Tesla Transformers Richard M Craven

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

Effects of Transient Recovery Voltages on Circuit Breaker Ratings Effects of Transient Recovery Voltages on Circuit Breaker Ratings Term Project: - EE22 - Power System Transients. Spring 28 Instructor: - Dr. Bruce Mork Team: - Himanshu Bahirat Muhammad Ali Praveen KK

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

P a g e 1 ST985. TDR Cable Analyzer Instruction Manual. Analog Arts Inc.

P a g e 1 ST985. TDR Cable Analyzer Instruction Manual. Analog Arts Inc. P a g e 1 ST985 TDR Cable Analyzer Instruction Manual Analog Arts Inc. www.analogarts.com P a g e 2 Contents Software Installation... 4 Specifications... 4 Handling Precautions... 4 Operation Instruction...

More information

LC Resonant Circuits Dr. Roger King June Introduction

LC Resonant Circuits Dr. Roger King June Introduction LC Resonant Circuits Dr. Roger King June 01 Introduction Second-order systems are important in a wide range of applications including transformerless impedance-matching networks, frequency-selective networks,

More information

Series and Parallel Resonance

Series and Parallel Resonance School of Engineering Department of Electrical and Computer Engineering 33:4 Principles of Electrical Engineering II aboratory Experiment 1 Series and Parallel esonance 1 Introduction Objectives To introduce

More information

Experiment 2: Transients and Oscillations in RLC Circuits

Experiment 2: Transients and Oscillations in RLC Circuits Experiment 2: Transients and Oscillations in RLC Circuits Will Chemelewski Partner: Brian Enders TA: Nielsen See laboratory book #1 pages 5-7, data taken September 1, 2009 September 7, 2009 Abstract Transient

More information

Panasonic, 2 Channel FFT Analyzer VS-3321A. DC to 200kHz,512K word memory,and 2sets of FDD

Panasonic, 2 Channel FFT Analyzer VS-3321A. DC to 200kHz,512K word memory,and 2sets of FDD Panasonic, 2 Channel FFT Analyzer VS-3321A DC to 200kHz,512K word memory,and 2sets of FDD New generation 2CH FFT Anal General The FFT analyzer is a realtime signal analyzer using the Fast Fourier Transform

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

Discrete Fourier Transform (DFT)

Discrete Fourier Transform (DFT) Amplitude Amplitude Discrete Fourier Transform (DFT) DFT transforms the time domain signal samples to the frequency domain components. DFT Signal Spectrum Time Frequency DFT is often used to do frequency

More information

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2009 Statistical analysis of overvoltages due to

More information

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks Mohammad Tavakoli Bina, G.N.Alexandrov and Mohammad Golkhah Abstract A new shunt reactive power compensator,

More information