CHAPTER 1 INTRODUCTION

Size: px
Start display at page:

Download "CHAPTER 1 INTRODUCTION"

Transcription

1 1 CHAPTER 1 INTRODUCTION 1.1 GENERAL The efficacy of a power system depends mainly on the reliability of the power equipment connected to the system. The power transformer is one of the most essential components of power generation and transmission system. Any failure in the power transformer will have a crucial impact on the system operation. The detailed survey of transformer failure reports shows that more than fifty percent of the failures in power transformers are due to insulation failures in windings (CIGRE JWG 12/13/23.21, 2002). For a successful operation, the transformer winding insulation has to withstand the electric stress during operation without any major damage for the expected life time. Most of the insulation failures are due to the gradual deterioration of insulation, which are mainly due to partial discharge (PD). PD may occur anywhere within the transformer winding where the insulation becomes weak. When the transformer insulations are highly stressed, the voids present within the solid or liquid or gaseous insulation generates PD. PDs are small electrical sparks (discharge) resulting from the localized dielectric breakdown of small voids in insulation system. PDs within an insulation system may or may not exhibit visible discharges and these discharge events tend to be more sporadic in nature than corona discharges. PDs can be prevented through careful design and proper selection

2 2 of insulation material. Once PD is initiated, PD causes progressive deterioration of insulating materials, ultimately leading to electrical breakdown. PDs are very short pulses of duration from tens of ns to 5µs. If the locations of PD are detected and rectified at an early stage, the incipient insulation faults can be minimized. Otherwise, the strength and frequency of PDs increases leading to catastrophic failure of transformer insulation. PD measurement is performed to assess the design adequacies and overall integration of the insulation systems and this has been accepted world wide as non-destructive quality-control to test the power equipment after manufacturing. For a quantitative judgment on the PDs, the apparent charges are used, which can be determined with the help of calibration pulses (Wenzel et al 1998). PD measurements are mainly affected by presence of noise. In order to enable diagnostic and maintenance procedures, location of the PD source is of major importance which is not straightforward due to the complex structure of the transformer. For the location of PD, a number of electrical methods (digital filtering, polarity location, capacitive location and traveling wave etc.,) and non-electrical methods (optical, chemical, acoustical method etc.,) have been used. Each method has its own merits and demerits. Generally, electrical methods are more sensitive and preferable for online PD (Wang et al 2005) and electrical methods are standardized by International Electrotechnical Commission (IEC) and Institute of Electrical and Electronics Engineers (IEEE). In this research, an attempt has been made to locate PD in transformer windings with the PD pulse durations of 0.1µs to 5µs using correlation methods.

3 3 1.2 A BRIEF REVIEW OF LITERATURE Surveying the literature helps to gain knowledge about the work done previously and steps to be taken to move forward in a particular field of interest. The literature survey is done under the following broad categories: Transformer failures PD in transformer windings PD measurements PD detection and location Transformer failures Many transformer industries and committees are conducting surveys on transformer failure statistics to improve the design of transformer. As per the international survey on transformer failures conducted in 1983 by CIGRE WG 12.05, typical failure rates for large power transformers with winding voltages upto kV are in the range of 1-2% per year. Though this is lesser in percentage, proper care should be taken because even a small winding failure in a transformer usually results in large expenses for the utility. An extensive survey by MSA Minhas et al (1990) in South Africa revealed that the most common cause of failure in the early service life of large power transformers is due to insulation failure. The Mexican Utility (CFE) (1999) reported that 53% of the failures in power transformers occur in the insulation system and mainly due to electromagnetic transient overvoltages. The transient overvoltages produce high dielectric stresses that can damage the turn insulation which can lead to failures like short circuit between turns, layers or discs of the transformer. The

4 4 short rate of rise of the surges (in the order of ns) and high amplitude (1.5pu-2.5pu) of the surges are dangerous for the insulation (Cornick et al 1992). The nonlinear voltage distribution in the windings is mainly due to short rate of rise and it may lead to failures on winding insulation. A five-year survey (from ) by William Bartley (2003) on the causes of the failures is shown in Table 1.1. It is seen from the table that the number of failures in power systems equipments is mainly due to insulation failure. Insulation failures due to defective installation, insulation deterioration and short circuits are only included in this report. But, the exterior surges such as lightning and line faults are not included in the insulation failures. Table 1.1 Number of failures in power system equipments (Cause of failures in five-year survey) Cause of failure Number of failures Insulation failures 24 Design/ material/ workmanship 22 Unknown 15 Oil contamination 4 Overloading 5 Fire/Explosion 3 Line surge 4 Improper operation 5 Flood 2 Loose connection 6 Lightning 3 Moisture 1

5 5 CIGRE, Doble clients, CEA, ZTZ-service clients and South Africa have done the survey on transformer failure statistics and different components are involved in these reports. Bjerkan (2005) has tabulated these failure reports in objective manner and is reproduced in Table 1.2. Table 1.2 Failure statistics of transformer components Defective component CIGRE survey CEA Survey Doble clients ZTZservice clients South Africa Bushings / accessories Tap-changer Major insulation Aging of winding Winding distortion Core Leads All the values are in percentage The detailed survey of these transformer failure reports shows that the reliability of transformer is mostly affected by insulation failure. The insulation failure is the predominant part of faults and highest risk for all types of transformer failures. Insulation failures result in two kinds of winding faults in a transformer namely series and shunt faults. Series fault implies insulation failure between the discs or between the turns, while shunt fault implies insulation failure between the winding and earthed components like tank, core etc. The winding fault occurs over the entire length of the winding and results in system outage and a very high maintenance cost of transformer. Thus, identification and characterization of insulation failures is a fundamental requirement for the purpose of condition based maintenance.

6 PD in transformer windings Most of the insulation failures in transformer are due to gradual deterioration of winding insulation, which are mainly due to PD (Wang Xiaorong et al 1991, Wang et al 1999 and Mazhab Jafari et al 2008 etc.). PD includes a wide group of discharge phenomena such as internal discharges, surface discharges, corona discharges, continuous impact of discharges (Kuffel et al 2000). PDs within an insulation system may or may not exhibit visible discharges and these discharge events tend to be more sporadic in nature than corona discharges (Kreuger 1989). When a discharge is initiated, high frequency transient pulses of pulse durations from ns to µs are generated. The PD pulses are considered to be harmful in HV insulation systems such as transformers because they cause energy loss and gradually degrade the winding insulation. Generally, discharge pulses can be characterized by amplitude and pulse shape. The PD pulse at the place of origin is strongly dependent on the insulation medium. Typically, the durations of discharge phenomena in liquid dielectric media are much longer than in other media. Yamashita et al (1993) conducted experimental studies to analyze PD pulse duration in idealized dielectric medium and reported that PD pulses are in the range of very short duration of 200ns. Tanaka (1995) analyzed on PD pulse distribution and reported that single PD pulse can be discriminated within 100µs for a 50Hz voltage supply. Ma et al (2002) analyzed the rise time and the pulse shape of the discharge current. The discharge pulses are recognized as having a very steep wave front in few ns and short duration in the order of 10ns. The pulse shape of the discharge current is determined by void dimension such as its radius, height and the external measuring circuit.

7 7 Hettiwatte et al (2002) investigated on the propagation of PD pulses in transformer windings. Generally, the PD pulse propagation is decided by the instantaneous field distribution and it is determined by applied voltage and charge distribution on the void surfaces. In most of the practical cases, the PD pulse duration can vary from 100ns-10µs. Jitka Fuhr (2006) reported that the rise time of the PD current impulse at the origin, depends on the insulating material in which the PD source is active and may vary in the range between picoseconds (gas discharge) to several hundreds of ns (discharge in oil). Palani et al (2007a) analyzed on PD events in the literature and reported that PD events can occur from tens of ns to few µs. Si Wenrong et al (2008) investigated about the time-frequency characteristics of PD pulse using Wigner-Ville distributions. The PD pulse shapes are defined as a mono-exponential pulse, mono-exponential attenuation oscillation pulse, double-exponential pulse, and doubleexponential attenuation oscillation pulse PD measurements Extensive research has been conducted on the sophistication of the PD measurement and data processing methods. The acceptance criteria for identification of PD sources in transformers are the measured value of apparent charge in picocoulomb (in pc as per IEC 60270, 2000) or in µv (as per IEEE revised standard 62, 1994) during PD tests (Jitka Fuhr 2005). When the insulation is partially damaged, turn-to-turn short circuits occur resulting in rise in temperature and finally in the worst case, to fire accidents. Due to known PD sensitivity, manufacturers have to prove that dry type transformers do not have any PD with apparent charge above 20pC

8 8 according to the standards of IEC (2000). For this purpose, narrow band electrical PD measurements according to IEC (2000) are performed. PD measurement is normally conducted with narrow band detection instruments (Bartnikas 1987). During test on transformers, it is a common practice to use narrow band electrical PD pulse detectors (RLC detector type) that conform to ASTM (ASTM D1868, 2007), IEEE-62 (1994) and IEC (60270, 2000) standards and specifications. Conventional narrow band and wideband detectors can also be used to reduce the interference caused by signals. Narrow band detectors have a band pass filter/integrator with a bandwidth of about 10kHz or so, while wideband detectors have a band pass filter/integrator with a bandwidth of 100 to 400kHz. Ma et al (2002) reported that the narrow band detection technique can give an erroneous quantification and information loss due to the adoption of quasi-integration or existence of multiple overlapped pulses. The characteristic parameters which describe the shape of single discharge pulse cannot be described explicitly in narrow band detection. Vaillancourt et al (1985) reported that the transformer specimens function satisfactorily in a flat bandwidth of 200kHz, since spectral components of the discharge pulses undergo more attenuation between 200kHz to 1MHz. The frequency region of electrical PD detection methods mainly lies in the high-frequency (3MHz-30MHz), very high frequency (30MHz-300MHz) and ultra high-frequency (300MHz-3GHz) bands. Generally, the high frequency signals are measured by Hall Effect sensor or current measuring resistor or antenna. Different types of PD measuring techniques such as electrical detection method (according to IEC 60270, 2000), Ultra High Frequency (UHF) PD measurement (electromagnetic), acoustic PD measurement, optical

9 9 and chemical method are used for analyzing the PD phenomenon. Each method has its own merits and demerits. Masayuki Hikita et al (2008) analyzed the features of various PD measurement methods PD detection and location methods The PD signal detection and location is one of the main challenges for power utilities and equipment manufacturers. In practice, the accurate location of a PD source is difficult because of the complex insulation structure of a transformer. For the location of PD, a number of electrical methods (using UHF, digital filtering, polarity location, capacitive location and traveling wave) and non electrical methods (optical, chemical, acoustical method) have been used Electrical PD location method A reliable method to locate PD source in transformer would generally contribute to a better diagnostic tool for insulation failure. Jitka Fuhr et al (1993) reported that the PD signals at the measuring terminal represents the response of the transformer winding, core and insulating medium (RLC circuit) to the PD current pulse excitation. The measured PD signals can be categorized into capacitive components, traveling wave component (propagation of pulses along the conductor) and oscillating component. These components are strongly dependent on the design of the transformer and PD defect location. The capacitive component (visible in the signal at the neutral terminal) is caused by the transmission of PD pulse through the capacitive network of the transformer (high frequency range MHz) (James et al 1977) and it is immediately transmitted by winding parasitic capacitance. The

10 10 transfer of capacitive component of the current signal is used for location of PD and their limitations are as follows: Need for the capacitive component of the response is a restriction and adequate resolution cannot be obtained for all transformer windings (Bartnikas 1987 and Wang et al 1999). Very difficult to separate capacitive component (Bartnikas 1987 and Wang 1999). Valid over a limited frequency range and inadequate for studying PD propagation (James et al 1989). Cannot be used to locate the PD accurately if the neutral terminal of the winding is directly grounded. Traveling wave component is caused by the transmission of electro magnetic wave (120 to 180m/s) (Thoeng 1973) and it is dependent on the type of the winding (lower frequency range MHz). Jitka Fuhr (1993) suggested a method of comparison of voltage response by using traveling wave techniques. For PD location, the time delay between measured PD signals is used and the limitations of this method are as follows: Difficult to identify the time at which the start of the PD signal arrived at the two ends of the winding. This is particularly difficult when the neutral and bushing ends are terminated with different impedances (Wang 1999). It is better suited to high distribution constant (α) value of the winding. It is applicable in the low frequency range (James et al 1989).

11 11 Oscillating component is determined by the resonance frequency of LC circuit of insulating system (intermediate frequency range MHz). Frequency of oscillations used for PD location (Jitka Fuhr et al 1993). Wang et al (1998) developed simulation model for studying the propagation of PD pulse in transformer winding. The simulation model is constructed with frequency dependent circuit parameters of transformer windings. Wang et al (1999) developed a novel approach for PD location based on the PD pulse propagation characteristics. The differences in the responses of the measured current signals that result from a PD occurring at different locations are used for PD location. It is applicable to power transformers (continuous disc winding construction) operating upto 132kV. Wang et al (2000a and 2000b) developed feature template matching method based on zeros for PD location in main insulation and inter-disc insulation. Experimental studies are carried out on 110kV rating of continuous disc winding to validate the algorithm. Results indicate that location accuracy better than 5% of the winding length is normally achieved. Transfer function method is commonly used for different applications such as transient analysis, insulation coordination and design procedure at the high frequency range in power transformers. In recent years, application of transfer function method has been extended for diagnostic purpose. Stace et al (1997) used transfer function method for condition monitoring of power transformer to identifying faults such as winding displacement, inter-turn and inter-disc faults. Islam (1997) extended the transfer function method to identify the transformer faults through high frequency modeling of the transformer.

12 12 A few research studies have located PD based on zeros and poles of the transfer functions. Malewski et al (1988) reported that a reduction of pole height of the transfer function indicates the PD location during LI excitation. Hettiwatte et al (2002) reported that zeros are used to locate the PD source. But zeros of the measured line-end signals are difficult to detect when the source of the discharge is near the line-end. Hettiwatte et al (2003) devised the transformer model for location of PD along the winding which is valid upto 10MHz. Each turn of the continuous disc winding (distribution transformer) is modeled by a transmission line with distributed parameters. The transfer function is obtained by using frequency spectra of the measured terminal signals for locating the position of PD along the winding. The transmission line model is validated experimentally by using PD calibrator as a PD source. Stone (2005) summarized the features of modern PD measurement systems to improve PD diagnostic methods and also addresses the salient features of PD detection methods. Mitchell et al (2007) utilized a narrowband high frequency distributed transformer model to estimate the PD location. The cost function is applied to the PD response to locate the PD. Naderi et al (2008) reported that the poles in the transfer functions always occur at fixed frequencies and it is not affected by the location of the PD, while various simulations show that zeros of the transfer functions might be considered as an indicator of the position of PD. Masayuki et al (2008) extensively analyzed the similarities, differences and features of various PD measurement methods and also described the noise removal, PD location and foreign particle identification to study the PD in transformer winding.

13 Acoustical PD location method The first published discussion on the acoustical method appeared in 1964 (Ogihara 1964). Recently, several studies have been done on location of PD using acoustical method. The principle of acoustic method is based on the detection of pressure waves (rapid flow of electrons and ions create a gas pressure waves acoustically) generated in the event of discharges within the insulation systems. An overview of the application and limitation of the acoustic method for detection of the PD signals in transformers is reported by Beyer et al (1987). Van Haeren (1985) reported that the acoustic pulse created by each discharge is concentrated in the range of 40kHz (ultrasonic range). The sensitivity of the method is related to distance between the sensor location and discharge location, angle of incidence of acoustic signals to sensor, PD magnitude, acoustic impedance between sensor and discharge source (Raja Kuppuswamy 2002). Van Haeren et al (1985) reported that if discharges are occurring on the surface of an insulation system, then the rapid flow of electrons and ions create a gas pressure wave which can be detected acoustically. The acoustic pulse created by each discharge is concentrated in the 40kHz (ultrasonic) range. The transmission losses in different media with their interface (Kemp 1993) and level of the discharge with interference (Lundgaard 1992) should be considered when using acoustic PD location. The primary advantage of using acoustic detection over chemical and electrical methods is that, position information is readily available from acoustic systems using sensors at multiple locations. This position information can help to identify the type of PD as well as the location and severity of an insulation fault.

14 14 Another advantage of acoustic detection over electrical detection is its immunity to electromagnetic interference. Jitka Fuhr (1993) reported that the acoustical methods for detection and location of PD defects in power transformers are found to be successful only for defects positioned closed to the walls of tank. Wang et al (2005) reported that the location results could be sometimes misleading especially when there is solid insulation between the discharge source and the sensor. Li-Jung Chen et al (2007) proposed a digital non-contact type acoustic PD measurement system and adopted Phase Resolved Partial Discharge (PRPD) pattern to examine the features of discharge signals. The wavelet transform is used to suppress the noise in the discharge signals. The proposed acoustic measurement system is validated for epoxy-resin transformers. Markalous (2008) reported that the precise measurements of acoustic signal arrival time and robust positioning algorithms are essential for estimation of the PD location. The following two approaches are discussed for PD location: (i) Alterations of the signal amplitude or deformations of the signals shape along the propagation path can give hints for a source location (ii) Measured arrival times are used to calculate the origin of signals PD detection during impulse test The Lightning Impulse (LI) test is a routine test for power transformers rated above 132kV in order to assess the dielectric integrity of the windings at the Basic Insulation Level (BIL). Failure identification during

15 15 the test is a non-trivial task and IEC (2000) standard provides some guidelines about the magnitude, shape and sequence of application of the voltages for help assessment. The test procedure involves the application of the voltages from a Marx generator in a standard sequences (Kamaraju and Naidu 2000, Kuffel et al 2000). The test procedure implicitly treats the transformer as a linear system. Reliable online PD location is a critical need for power industry to improve personnel safety and decrease the potential loss during service. The various techniques have been developed for fault identification; the transfer function method (Malewski 1988, Leibfried et al 1999, Vaessen et al 1992, Hanique 1994) has gained some acceptance during LI test. The transfer function method which has quite a few adherents is based on computing transfer function of the winding. The method has also been extended to incorporate features such as fault identification and magnitude of the fault using wavelet transform (Vanaja 2001). The transfer function method is not a successful method always for fault identification during Chopped lightning impulse (CLI) compared to lightning impulse (LI) test (Leibfried 1999). The transfer functions obtained using CLI and LI wave shape cannot be compared. The standard IEC (2000) portrays the drawbacks of the transfer function. Palani (2007a) reported that the transfer function becomes undefined at locations where the frequency content of the voltage signal approaches the noise level as in chopped LI. The transfer function method implicitly treats the device under test as linear, but faults are always not linear. Thus, the transfer function method is not adequate for the case of faults that occur at different instant. Satish (1998) proposed a time frequency analysis tool (short-time Fourier transform) for analyzing the neutral currents directly for fault diagnosis during impulse testing of power transformers. Advantages of the

16 16 method over the conventional transfer function method are demonstrated and it appears that the wavelet transform is better suited for the location of PD. Wavelet analysis is best suitable for non-stationary signal (LI Jun-hao et al 2008). This method ignores the finite energy deterministic nature of the input signal. The main limitation of this method is that it does not provide good resolution in both time and frequency domain because of its fixed window width (Naderi et al 2008). The wavelet transform is a tool that splits the data of functions or operators into different frequency components and then studies each component with a resolution matched to its scale. In comparison with shorttime Fourier transform, wavelets have a window that automatically adjusts to give the most appropriate resolution (Kim and Aggarwal 2000). The wavelet transform can give information in both time and frequency domains. The advantage of wavelet transform is that, the band of analysis can be adjusted so that the high frequency and low frequency components can be precisely detected. Butler and Bagriyanik (2003) used wavelet transform for analyzing the transient phenomena associated with the transformer fault. Unlike the basis function used in FT techniques, wavelets not only localize in frequency but also in time. This localization allows the detection of the time of a sudden fault occurrence. Wavelets can also provide higher precision time resolution for short duration higher frequency signals as well higher precision frequency resolution for long duration low frequency signals (Naderi et al 2008). The existing method of impulse testing involves the analysis of the response from current measuring resistor through High frequency current transformer (HFCT). Jayalalitha et al 2004a and 2004b suggested that the acquisition of the winding response through three analog filters (triple filter approach) namely low pass, band pass and high pass filter is used for detection of PD.

17 17 Gopalakrishnan et al (2003) and Jayalalitha et al (2006) proposed time domain correlation method (matched filter approach) for location of PD in transformer windings. The simulation and experimental studies are performed on lumped layer winding to validate the efficacy of method. The correlation method locates the PD in the presence of noise. A phase-sensitive detector is known to provide extremely high accuracy in identifying sinusoids in the presence of noise (Blair et al 1975). One can utilize the fact that the current response of the winding is measured and compared with fault current response. A PD phenomenon affects the current signal at a region close to noise floor. Palani et al (2007a) developed a Virtual Instrument (VI) based on phase-sensitive detection principle. A Virtual Instrument is developed for analysis of impulse test records in transformers. The front-end hardware has three analog filters that precede three digitizers with varying resolution. The breakdown and PD events can be identified clearly and the drawback of the transfer function method is highlighted. Palani et al (2007b) suggested a lock-in amplifier technique for detection of PD within the winding during impulse test on a transformer. The lock-in amplifier technique is implemented with a Virtual Instrument and it is validated with hardware implementation using lock-in amplifier (SR-830 DSP, 102 khz lock-in amplifier). Digital acquisition of waveforms has led to increasing research study in the area of failure analysis. Some of the techniques for achieving the foregoing task are analyzed for identification and location of PD. It can be noted that only limited success has been achieved for PD location. The limitation with several studies on PD location is that the most of the electrical methods are not optimal in the presence of noise. In this study, the efficacy of the correlation method is used for PD location in transformer windings.

18 SCOPE OF THE PRESENT WORK Scope of this study lies in PD location within the transformer windings for different PD pulse durations. In this study, correlation based methods are proposed for PD location with the PD pulse durations of 0.1µs to 5µs. Amongst the various methods that have been developed for PD detection, transfer function method have gained some acceptance. The fundamental issues in transfer function method have always been frequency resolution and Signal-to-noise ratio (SNR) at higher frequencies. It would be useful to develop methods that can work under circumstances of improving the SNR too. Hence, in communication theory, the correlation method is known to be the optimum method for detecting a pulse of known shape contaminated by additive noise with known spectral density of the signal. In other words, the correlation method is optimal for detection of PD signal in the presence of noise provided that only the reference responses are known (Whalen 1971, Veen et al 2003, Jayalalitha et al 2006). Hence, the principle of correlation method is used for PD location in transformer windings. The correlation method is only valid if one can physically inject known / reference pulses at various sections and then to establish correlation. In practice, this might not be possible. Hence, the correlation method can be adopted to a general case as follows. The responses of the transformer winding for PD are estimated theoretically using an accurate equivalent winding circuit model by injecting reference / known pulse across the different section of the transformer winding and the measured winding responses is used as reference signals (reference responses) for correlation. In practice, if a PD response of the winding is measured at the current measuring resistor across HFCT, one can identify the PD location by correlating reference responses and real PD response using correlation method.

19 19 To study the responses of the transformer windings with different PD durations from 0.1µs to 5µs at different sections, it becomes necessary to use a simple model which can be realized in practice with ease. To fulfill this requirement, a PD model in terms of a voltage pulse source is suggested to simulate the PD in transformer winding with different pulse duration. The correlation methods are validated on 22kV transformer windings namely layer, continuous disc and interleaved windings. All the windings are provided with tappings at every 10% of the winding for injection of PD with different pulse durations. The present work starts with voltage pulse represented as a PD across the sections of the windings for studying the efficacy of the correlation method. The PD location using correlation method is performed by injecting a PD pulse durations and the winding responses are analyzed both in time domain as well as in frequency domain to characterize the behaviour of the transformer windings. Generally, the frequency domain measurements will always contain noise at higher frequencies. This has led to the use of Butterworth bandpass filter. The proposed methodologies are applied for all types of transformer windings, demonstrated by measurements and validated with PD calibrator and live discharges to locate the PD within the transformer windings. The proposed methodologies are validated with 25MVA, 220/6.7kV power transformer to locate the PD using circuit simulation package (PSPICE).

20 ORGANIZATION OF THE THESIS This thesis is organized into seven chapters as detailed below: Chapter 2 presents a simple PD model which can be easily realizable to understand the transformer winding behaviour both simulation and in practice for PD of different pulse durations. The experimental winding responses of commonly used transformer windings viz. layer, continuous disc and interleaved windings are presented, when different duration of PD pulses are injected across each section. Chapter 3 presents the normalized and orthonormalized correlation methods for PD location with different pulse durations from 0.1µs to 5µs. The experimental test PD response due to injection of different pulse duration is effectively used for correlation methods. The Butter worth bandpass filter is also used to improve the performance of the correlation methods. Chapter 4 presents the least difference methods for PD location to locate the PD in transformer windings. Chapter 5 presents regression analysis with statistical correlation method for PD location. Chapter 6 deals with validation of the correlation based methods with PD calibrator and live discharges. An attempt has also been made to validate the correlation methods on 25MVA, 220kV/6.7kV power transformer for PD location by using circuit simulation (PSPICE). Chapter 7 presents the summary and conclusions. The scope of the future work is also highlighted.

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization International Journal of Electrical Engineering. ISSN 0974-58 Volume 4, Number 4 (0), pp. 499-50 International Research Publication House http://www.irphouse.com High Frequency Modeling of Two Limb Series

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics Journal of Energy and Power Engineering 9 (215) 289-295 doi: 1.17265/1934-8975/215.3.8 D DAVID PUBLISHING Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and

More information

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation P.S.Diwakar High voltage Engineering National Engineering College Kovilpatti, Tamilnadu, India S.Sankarakumar Department

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material

More information

A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2

A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2 A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2 1 Ministry of Electricity, Republic of Iraq 2 Institute of

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

REFERENCES. 6. Bernald Sklar (2006), Digital Communications, Pearson, Second Edition, India.

REFERENCES. 6. Bernald Sklar (2006), Digital Communications, Pearson, Second Edition, India. 129 REFERENCES 1. Abetti P.A. (1953), Transformer models for the determination of transient voltages, Transactions on American Institute of Electrical Engineers, New York, Vol. 72, pp. 468-480. 2. Arunkumar

More information

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements EMEL ONAL Electrical Engineering Department Istanbul Technical University 34469 Maslak-Istanbul TURKEY onal@elk.itu.edu.tr http://www.elk.itu.edu.tr/~onal

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring

More information

PARTIAL DISCHARGE MEASUREMENT

PARTIAL DISCHARGE MEASUREMENT PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of

More information

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical

More information

The importance of partial discharge testing throughout the development and operation of power transformers

The importance of partial discharge testing throughout the development and operation of power transformers The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense

More information

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding Research Journal of Applied Sciences, Engineering and Technology 10(10): 1102-1107, 2015 DOI: 10.19026/rjaset.10.1879 ISSN: 2040-7459; e-issn: 2040-7467 2015 Maxwell Scientific Publication Corp. Submitted:

More information

Partial Discharge Monitoring and Diagnosis of Power Generator

Partial Discharge Monitoring and Diagnosis of Power Generator Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

Improved Method for Winding Deformation Detection Sensitivity in Transformer

Improved Method for Winding Deformation Detection Sensitivity in Transformer International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 10ǁ October 2013 ǁ PP.48-55 Improved Method for Winding Deformation Detection Sensitivity

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

Transformer Shunt Fault Detection using Two Techniques

Transformer Shunt Fault Detection using Two Techniques Transformer Shunt Fault Detection using Two Techniques Swathy Sasikumar 1, Dr. V. A. Kulkarni 2 P.G. Student, Department of Electrical Engineering, Government College of Engineering, Aurangabad, Maharashtra,

More information

Software System for Finding the Incipient Faults in Power Transformers

Software System for Finding the Incipient Faults in Power Transformers Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In

More information

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer Send Orders for Reprints to reprints@benthamscience.ae 784 The Open Automation and Control Systems Journal, 2015, 7, 784-791 Open Access Application of Partial Discharge Online Monitoring Technology in

More information

Prepared by Mick Maytum

Prepared by Mick Maytum IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not

More information

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

Electrical Equipment Condition Assessment

Electrical Equipment Condition Assessment Feature Electrical Equipment Condition Assessment Using On-Line Solid Insulation Sampling Importance of Electrical Insulation Electrical insulation plays a vital role in the design and operation of all

More information

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM

More information

Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges

Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges , June 30 - July 2, 2010, London, U.K. Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges Jesus Rubio-Serrano, Member, IAENG, Julio E. Posada

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial

More information

High Field Electrical Conduction and Breakdown in Solid Dielectrics

High Field Electrical Conduction and Breakdown in Solid Dielectrics High Field Electrical Conduction and Breakdown in Solid Dielectrics R.S.Pote 1, V.N.Gohokar 2, D.G.Wakde 3, R.S.Kankale 4 Associate Professor, Department of Electrical Engineering, SSGMCOE, Shegaon, India

More information

MAHALAKSHMI ENGINEERING COLLEGE

MAHALAKSHMI ENGINEERING COLLEGE MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK -------------------------------------------------------------------------------------------------------------- Sub. Code : EE2353 Semester

More information

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe PARTIAL DISCHARGE IN PLANAR TRANSFORMER Ing. Anar MAMMADOV, Doctoral Degreee Programme (1) Dept. of Microelectronics, FEEC, BUT E-mail: xmamed00@stud.feec.vutbr.cz Supervised by Dr. Jaroslav Boušek ABSTRACT

More information

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),

More information

IEEE Transactions on Power Delivery. 15(2) P.467-P

IEEE Transactions on Power Delivery. 15(2) P.467-P Title Author(s) Citation Detection of wide-band E-M signals emitted from partial discharge occurring in GIS using wavelet transform Kawada, Masatake; Tungkanawanich, Ampol; 河崎, 善一郎 ; 松浦, 虔士 IEEE Transactions

More information

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD

CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD 63 CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD 3.1 INTRODUCTION PD measurements on high-voltage equipment, e.g. transformers, could be grouped into two major tasks. First, evidence

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics CASE STUDY 1 (Doble Client Conference 2011, ACCA committee meeting) Dissolved Gas Analysis (DGA)

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS 136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West

More information

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER N. R. Bhasme 1 and Bhushan Salokhe 2 1 Associate Prof., 2 M.E. Student, Dept. of Electrical Engg., Govt. College of Engineering

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 BACKGROUND The increased use of non-linear loads and the occurrence of fault on the power system have resulted in deterioration in the quality of power supplied to the customers.

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE Ju-Chu Hsieh 1, Cheng-Chi Tai 1, Ching-Chau Su 1, Chien-Yi Chen 1, Ting-Cheng Huang 1, Yu-Hsun Lin 2 1 Department

More information

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2 ACTA UNIVERSITATIS APULENSIS Special Issue SIMULATION OF LIGHTNING OVERVOLTAGES WITH ATP-EMTP AND PSCAD/EMTDC Violeta Chiş, Cristina Băla and Mihaela-Daciana Crăciun Abstract. Currently, several offline

More information

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View Evaluation and Limitations of Corona Discharge Measurements An Application Point of View P. Mraz, P. Treyer, U. Hammer Haefely Hipotronics, Tettex Instruments Division 2016 International Conference on

More information

1409. Comparison study between acoustic and optical sensors for acoustic wave

1409. Comparison study between acoustic and optical sensors for acoustic wave 1409. Comparison study between acoustic and optical sensors for acoustic wave Malik Abdulrazzaq Alsaedi Department of Electrical, Faculty of Engineering, University of Misan, Amarah, Iraq E-mail: maliksaady@yahoo.com

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 2321-0613 Conditioning Monitoring of Transformer Using Sweep Frequency Response for Winding Deformation

More information

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga

More information

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

Software for Partial Discharge and Localization

Software for Partial Discharge and Localization 48 PIERS Proceedings, Taipei, March 25 28, 2013 Software for Partial Discharge and Localization M. Cap, P. Drexler, P. Fiala, and R. Myska Department of Theoretical and Experimental Electrical Engineering

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH Giuseppe Cappai, Bernhard Heinrich, Giuseppe Simioli, Leonardo Trevisan Weidmann Electrical Technology AG, Switzerland Abstract: A large solar

More information

Insulation Level and Test Technology of. 1000kV Power Transformer

Insulation Level and Test Technology of. 1000kV Power Transformer Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal Abdolrahman Peimankar, Arman Kazemi, and Seyed Mohammad Taghi Bathaee Khaje

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

EE059: Transformer Operation, Maintenance, Diagnosis & Testing

EE059: Transformer Operation, Maintenance, Diagnosis & Testing EE059: Transformer Operation, Maintenance, Diagnosis & Testing EE059 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: Power and distribution transformers are essential devices in electricity

More information

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse A. Elzowawi, A. Haddad, H. Griffiths Abstract the electric discharge and soil ionization phenomena have a great effect

More information

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method

More information

TRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting

TRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting TRANSFORMER OPERATIONAL Principles, Selection & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Power and distribution transformers

More information

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink ISSN (Online) 2321 24 Vol. 4, Issue 6, June 2 Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink C Sunil kumar 1, Harisha K S 2, Gouthami N 3, Harshitha V 4, Madhu C Assistant Professor,

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing

Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing Journal of Electroceramics, 13, 487 492, 2004 C 2004 Kluwer Academic Publishers. Manufactured in The Netherlands. Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing

More information

TECHNIQUES AND STANDARD

TECHNIQUES AND STANDARD TRANSFORMER TESTING TECHNIQUES AND STANDARD DEVELOPMENT BY DIEGO M. ROBALINO, PhD, PMP, MEGGER-AVO Training Institute Transformer manufacturers and field operators have always benefitted when new technologies

More information

Effect of Shielded Distribution Cable on Very Fast Transients

Effect of Shielded Distribution Cable on Very Fast Transients IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 857 Effect of Shielded Distribution Cable on Very Fast Transients Li-Ming Zhou and Steven Boggs, Fellow, IEEE Abstract Fast transients in

More information

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik,

More information

Simulation of Partial Discharge in High Voltage Power Equipment

Simulation of Partial Discharge in High Voltage Power Equipment International Journal on Electrical Engineering and Informatics Volume 3, Number 2, 2011 Simulation of Partial Discharge in High Voltage Power Equipment Asima Sabat and S. Karmakar Department of Electrical

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Electrical Discharges HYEON-KYU CHA, SUN-JAE KIM, DAE-WON PARK, GYUNG-SUK KIL Division of Electrical and Electronics Engineering Korea Maritime

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

A1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS

A1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS 21, rue d'artois, F-75008 Paris http://www.cigre.org A1-209 Session 2004 CIGRÉ EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS CARLOS AZUAJE* WILLIAM TORRES C.V.G.

More information

MONTRANO. Continuous monitoring system for power transformers

MONTRANO. Continuous monitoring system for power transformers MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in

More information

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform > REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1 Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform Guomin Luo

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information