1 SCHMIDT VibroSens 401 Operating Instructions

2 SCHMIDT Vibration Control VibroSens 401 Operating Instructions 1 Important information Use Description of functions Installation Electrical connections Start-up Help with setting Technical data Dimensions Konformitätserklärung Impressum: Copyright 2004 SCHMIDT Technology All rights reserved. Printed in Germany. Edition and modification date: Version 1.3 dt. Juni 2004 Valid for equipment with year of manufacture from 02/2003 2

3 1 Important information Before starting the device, these operating instructions are to be read through completely and carefully heeded. Failure to heed or adhere to these operating instructions can result in claims on manufacturer s liability becoming null and void for damages ensuing therefrom. Manual action of any manner on the device with the exception of proper procedures and those described in these operating instructions lead to forfeit of guarantee and exclusion from liability. The device is solely intended for the usage as described below (see chapter 2). It is particularly not intended for the direct or indirect protection of persons. SCHMIDT Technology assumes no liability whatsoever as regards suitability for some specific purpose and assumes no liability for errors found in this instruction manual, or for coincidental or subsequent damages related to shipment, capacity or use of this device. The guarantee is effective for 6 months as of delivery and covers material and workmanship defects. Within this time, SCHMIDT Technology can either repair a device proved defective, or replace it with a device of equivalent value. 3

4 2 Use The Schmidt VibroSens 401 Vibration Control is conceived for use on machines, aggregates and single driving mechanism parts as well as general sub-assemblies and machine components for the purpose of monitoring mechanical vibrations in accordance with DIN ISO The device measures and assesses the effective vibration speed (vibration amplitude) arising at the selected installation site. When a pre-set threshold value is exceeded, a relay on the device switches. Externally installed switch functions can be tripped via the corresponding switch outlets, like, f.i., an emergency-off for the machine. The momentary vibration amplitude can be registered over an analogue outlet. This makes possible a continuous, permanent monitoring and recognition of the trend of the machine s operating condition. 4

5 3 Description of functions 3.1 Structure of the device Fig. 1 shows the essential components of the VibroSens 401. (1) Potentiometer for setting the vibration threshold V threshold (2) Potentiometer for setting the vibration threshold V threshold (3) Digital switch for setting the switch delay time T threshold (4) Relay-change-over contact, floating 24 V/1 A (5) Casing (6) Attachment plate, electrically insulating (7) Attachment borehole (8) Casing cover plate Fig. 1: Structure of the device Fig. 1:equipment configuration 5

6 3.2 Monitoring function The Schmidt VibroSens 401Vibration Control registers and evaluates the effective vibration speed in accordance with ISO 2372/VDI Alarm condtion: The relay (4) (Fig. 1) signals a deviation from the normal operating condition of the monitored object, if the vibration amplitude V eff has exceeded the pre-set switch threshold V threshold for a pre-set minimum period of time T threshold. Sensitivity of response: If temporarily increased vibration amplitudes are expected in the range of normal operating conditions, switching of the relay can be suppressed by means of the switch delay time T threshold. Switching behavior is portrayed in detail in the time sequence diagram (Fig. 2). If the switch threshold V threshold is exceeded for a silent period of T > T threshold, the relay switches for a prescribed and fixed default switch time of 2 s. If the silent period is T < T threshold, the relay does not respond. Switch logic: The switch conditions of the relay (4) are portrayed in Table 1 according to operating condition and vibration amplitude. 6

7 Fig. 2: Time sequence diagram Fig. 3: Relay switch logic 7

8 Interrupting the voltage supply: As the control coil of the relay is energized under normal operating conditions for the device, the relay drops out and goes into alarm condition when the voltage supply is interrupted. Power failure or a wire-break in the supply circuit can clearly be recognized. Line monitoring: Since the switch contact (pi/gr) is closed in normal operating conditions (comp. Table 1), wire-break can be recognized in the switch voltage circuit. The time-dynamic switch logic furthermore makes possible a differentiation between alarm (switch time 2 s) and power failure or wire-break (switch time permanent). 3.3 Method of measurement The principle structure of the VibroSens 401 is represented in the functional diagram (Fig. 3). The vibration amplitude is registered with a piezoelectric acceleration sensor (1). The sensor signal which is proportional to the acceleration is filtered by a pre-amplifier (2) with a frequency band pass (3) and in step (4) integrated in real-time with a subsequent effective value formation (5). The relay (8) is operated and switched by the comparator step (6) with an adjustable switch threshold and the switch delay link (7) as soon as the vibration level V eff has exceeded the switch threshold V threshold longer than the switch delay time T threshold. 8

9 Fig. 4: Block diagram VibroSens 401 9

10 4 Installation When installing, make sure that the signal direction given on the device coincides as much as possible with the main actual signal direction of the surface of attachment. Only in this way can maximum response sensitivity of the Vibration Control and sure recognition of the vibration condition be achieved. (1) The signal direction of the built-in vibration sensor is marked (pictogram) on the device s name plate (Fig. 5). There are two different models: Code No. Signal direction Pictogram Parallel to surface of attachment Vertical to surface of attachment Fig. 5: Marking of the built-in vibration sensor on the device s name plate Establish a flat-surface non-power lock to the object to be measured! Attach the device preferably to a smooth surface. 10

11 Avoid contact resonance! Screw in two M6 x 16 fixing bolts through both fixing holes of the mounting plate in the appropriate threaded boreholes in the object to be measured. It is best to tighten the bolts evenly with a torque wrench. Suppress wire vibrations! Lay the connection cable along the surface of the object and attach firmly with clamps or the like. Avoid an earth short circuit with the object to be measured! The mounting plate of the Vibration Control is made of a stable structured, non-electrically conductive material, which results in the device s mounting being electrically insulated from the object to be measured. In order to avoid extended spatial earth loops over the connection cable and possible impairments to the device s functions through external electromagnetic disturbances, it is mandatory that the electrical separation between device and object be observed.» The casing may not be in direct contact with metal parts or other electrically conductive parts.» The distance between the device and the surrounding casing components must be great enough to exclude contact due to vibrations, even during dynamic operations and in the event of resonance. 11

12 5 Electrical connections The Schmidt VibroSens 401Vibration Control has on the casing a shielded, fixed, 6-core connection cable which preferably is connected by the customer to a screw clamp terminal strip. The shield connection (bk) and the earth connection (bl) are joined together electrically by the casing. Make the electrical connections (7 x 0.34 mm 2 ) in accordance with the name plate (see Fig. 4). The earth connection (bl) serves both as reference potential for the power outlet V eff (wh) and as negative connection for the voltage supply system U B (br). Tip: The shielding effect of the connection cable can be impaired by line-related disturbances depending on the disturbance field configuration and the earth line in the immediate vicinity of the mounting location. For optimum shielding it must be decided from case to case whether to connect the shield at the end of the cable (black line) in the external terminal block, or not connect it at all. 12

13 Function Seizure Value Color code: Anlalogueoutput 0 (4) ma white Switch relay Voltage Fig. 6:Connecting VibroSens V / 1 A V 0 V shielding yellow grey pink brown blue black 13

14 6 Start-up The Vibration Control has been adjusted at the factory and calibrated to the rated sensitivity of 0.4 ma/mms -1 at a sinus frequency of 100 Hz. After mounting and connection of the voltage supply system, the device is ready for operation after a 10 s start delay period.» The device has not been set up with a defined presetting. To be sure of the desired monitoring function, the operator must set the switch threshold V threshold and switch delay time T threshold himself. Device structure (Fig. 1) is to be heeded for setting the switch parameters. Loosen the four screws on top of the casing (5) and remove the casing cover plate (8). Set and check the switch threshold V threshold. - With a screw driver, set the switch threshold V threshold on the potentiometer (1). The setting range is 2 50 mm/s. a) Turning the set screw clockwise: increases the switch threshold b) Turning the set screw counter-clockwise: decreases the switch threshold - Check the set switch threshold. 14

15 Check the set value at both measuring terminals (2) with a voltmeter (digital). Use preferably laboratory wire clips for connecting the measuring wires. The voltage range of U P = 0, V (direct current) is equivalent to v threshold = mm/s according to the relation: v threshold = mm/s 10 U V P [V] Example: 3.5 V test voltage corresponds to a switch threshold of 35 mm/s» The test voltage at the measuring terminals (2) must be tapped floating. Otherwise faulty voltages occur, which result in a distortion of measurement results. Set the switch delay time T threshold. The minimum delay time is set with the measurement electronics and is 2 s. The effective switch delay time is yielded from the relationship T threshold = SV+ 2 s. SV is the set value in the range 0 10 s. It is set with the slide button on the digital switch (3). 15

16 Slide button on digital switch (3) a) in OFF position: additional switch delay is not effective b) In ON position: set value SV = sum of the given numeri Example: Set value SV = = 6 (s) cal values 1 s, 2 s, 3 s, 4 s Fig. 7sequence diagram Set value T threshold = SV + 2 = = 8 (s) The function of the switch delay time results from the time sequence diagram (Fig. 2). Tip: Move the slide button on the digital switch (3), f.i., with the blade of a screw driver. 16

17 7 Help with setting Setting the switch parameters requires as much knowledge as possible about the vibration behavior of the object to be monitored. Especially the threshold range between normal conditions and possible faulty conditions should be known. In general, vibration behavior is influenced by different factors. Among these factors are constructive design, site of erection, characteristics of the foundation, operating conditions and the measurement site where the Vibration Control is mounted. For this reason the switch threshold and switch delay time must be individually set for each vibrational environment. For orientation in assessing vibration behavior, the different machines can be divided into four classes or groups of machines. Class I/Group K: Firmly connected driving mechanism parts of power machines and work machines. Electric motors up to 15 kw. Class II/Group M: Medium-size machines and electric motors from 15 to 75 kw without a special foundation. Firmly erected driving mechanism parts on special foundations up to ca. 300 kw. Class III/Group G: Large machines, power and work machines on raised, rigid or heavy foundations. 17

18 Class IV/Group T: Large, power and work machines on low foundations, f.i., turbo aggregates with foundations designed following guidelines for light metal construction. The vibration amplitude V eff is divided into discrete intervals whose grades of assessment are allocated to the individual machine classes or groups (Table 1). The set value of the switch threshold V threshold should not exceed stage C (still allowed vibrational amplitude). Tip: These guides are for machines with circulating masses. Machine-specific settings must be made for machines with influences DIN ISO part as well as in the relevant, machine-specific guidelines. 18

19 Vibration amplitude V eff (mm/s) Group K Class I Group M Class II Group G Class III Group T Class IV 0,28 0,45 0,71 1,12 1,80 2,80 4,50 7,10 11,20 18,00 28,00 45,00 A B C D A B C D A B C D A B C D A = good B = usable C = still allowed D = not allowed Tabelle 1: Assessment of the vibrational intensity following DIN ISO

20 8 Technical data Measurement range (v eff ) Frequency range mm/s Hz (3 db) Switch threshold (v threshold ) mm/s Switch delay (T threshold ) s (typical +/-20%) Start delay Switch outlet Switch function Analogue outlet (v eff ) Load resistance Supply voltage Power consumption Operating temperature Storage temperature 10 s permanent Relay change-over contact 24 V /1 A potentialfrei Relay switches when switch threshold is exceeded or upon power failure. Automatic reset after 2 s upon excess ma or ma 300 Ω max VDC 45 ma max. (without load) C C Type of enclosure IP 65 20

21 9 Dimensions Bild 8: Dimensions of the housing 21

22 10 Konformitätserklärung 22

23 23

24 SCHMIDT Technology GmbH Feldbergstrasse 1 D St. Georgen Phone +49 (0)7724/899-0 Fax +49 (0)7724/ info@schmidttechnology.de 24 Art.Nr.

SCHMIDT Flow Sensor SS Quick Guide

SCHMIDT Flow Sensor SS Quick Guide SCHMIDT Flow Sensor SS 20.600 Quick Guide SCHMIDT Flow Sensor SS 20.600 Table of Contents 1 Important information... 3 2 Application range... 3 3 Assembly... 4 4 Electrical connection... 6 5 Commissioning...

More information

D7F. Detects Changes in Machine. Vibration. Vibration Sensor with Linear Output or Manual Setting. Ordering Information

D7F. Detects Changes in Machine. Vibration. Vibration Sensor with Linear Output or Manual Setting. Ordering Information with Linear Output or Manual Setting Detects Changes in Machine ON/OFF output can be set and checked quickly and easily from the vibration level meter. waveforms can be checked using the AC monitor output.

More information

Instruction Manual Inductive Gauging Sensor

Instruction Manual Inductive Gauging Sensor Instruction Manual Inductive Gauging Sensor EX-200 Series 96M0367 CONTENTS Page Part names and functions...3 Connections/Hints on correct use... 4 Installations... 5 Adjustment... 6 Specifications... 7

More information

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC.

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC. INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC. MANUAL PART NUMBER 180-0036 ORIGINAL: 1-17-83 REVISION: B (8-26-86) NOT TO BE CHANGED WITHOUT MSHA

More information

Acceleration Sensor AS - 022

Acceleration Sensor AS - 022 1 Application Acceleration Sensor AS - 022 The acceleration sensor AS-022 is used for measurement of vibration acceleration. Fig. 1 Acceleration Sensor AS - 022 2 Measuring Principle 3 Technical Data Acceleration

More information

Melt pressure Transmitter GREENLINE Type DTAI with Temperature element

Melt pressure Transmitter GREENLINE Type DTAI with Temperature element Melt pressure Transmitter GREENLINE Type DTAI with Temperature element Operation and Maintenance Manual English Mercury free NaK free Seite 1 / 9 Contents: 1. Introduction 2. Operating range and field

More information

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67G environment resistance

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67G environment resistance 1 High Accuracy Eddy Current Type Sensor SERIES Related Information General terms and conditions... F-3 Glossary of terms... P.1 guide... P.11~ General precautions... P.19 PHOTO PHOTO MEASURE panasonic.net/id/pidsx/global

More information

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67g environment resistance

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67g environment resistance 13 High Accuracy Eddy Current Type Sensor SERIES Related Information General terms and conditions... F- Glossary of terms... P.139 Sensor selection guide... P.9~ General precautions... P.1 PHOTO PHOTO

More information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information *09005137* BA_EN_DE50 Rev.A 11/12 *09005137* d e v e l o p i n g s o l u t i o n s DE50 Operating Manual Differential pressure transmitter Table of Contents 1 Safety guidelines 2 Application purpose 3

More information

Non-Ferrous-Metal-Detecting Proximity Sensor (Separate Amplifier Type)

Non-Ferrous-Metal-Detecting Proximity Sensor (Separate Amplifier Type) Non-Ferrous-Metal-Detecting Proximity Sensor (Separate Amplifier Type) ECY-SD Proximity Sensor with Separate Amplifier Unit for Detection of Non-ferrous Metals with Simple Adjustment Detects aluminum,

More information

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop. 41-101.3A Type CKO Overcurrent Relay switch, which allows the operation indicator target to drop. The front spring, in addition to holding the target, provides restraint for the armature and thus controls

More information

BC145 SIGNAL ISOLATOR BOARD

BC145 SIGNAL ISOLATOR BOARD BC145 SIGNAL ISOLATOR BOARD 4/17 Installation & Operating Manual MN1373 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com to download

More information

BDD-UM 3023 Digital Display

BDD-UM 3023 Digital Display BDD-UM 3023 Digital Display for analogue input signals instruction manual Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.f. Germany Phone +49 (0) 71 58/1 73-0 Fax +49 (0) 71 58/50 10 Servicehotline

More information

INSTRUCTION MANUAL VIBRATION SWITCH CVS 100 LC

INSTRUCTION MANUAL VIBRATION SWITCH CVS 100 LC INSTRUCTION MANUAL VIBRATION SWITCH Meggitt GmbH Kaiserleistraße 51 63067 Offenbach am Main Deutschland / Germany Tel.: +49 69 97 99 05-0 Fax: +49 69 97 99 05-26 E-Mail: Web: info@meggitt.de www.meggitt.de

More information

Operator s Handbook. Suspended Arm

Operator s Handbook. Suspended Arm Operator s Handbook Suspended Arm SAR15 Z 5 Code: 010690/Z/5 SAR15 XZ 85 Code: 010690/XZ/85 SAR15 XYZ 855 Code: 010690/XYZ/855 KOLVER S.r.l. VIA MARCO CORNER, 19/21 36016 THIENE (VI) ITALIA TEL +39 0445

More information

Torque Sensor DML 500 S080S10X

Torque Sensor DML 500 S080S10X Bearing unit with integrated torque sensor Measurement range from 0 to 500Nm bidirectional High tolerable dynamic loads High tolerable transverse forces and bending moments Maintenance-free operation Torque

More information

7. Operating instructions: EFL 300

7. Operating instructions: EFL 300 7. Operating instructions: EFL 300 Copyright 2015 by Endecotts Ltd. 59 1. Setting up Technical specifications SIEVE SHAKER MODEL: EFL 300 General Information The new EFL 300 combines the best features

More information

Proportional amplifier type EV22K5

Proportional amplifier type EV22K5 Proportional amplifier type EV22K5 Assembly instructions Card design Supply voltage UB: Output current QA max: 9...32 V DC 1.8 A by HAWE Hydraulik SE. The forwarding and reproduction of this document,

More information

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity Documentation Measurement and Control Type: ELT-GP1 Content 1. Installation instructions 2. Data sheets 3. Declarations of conformity (Part No. 008Q520) eltherm GmbH Ernst-Heinkel-Str. 6-10 57299 Burbach

More information

ALM473 DUAL MONO \ STEREO AUDIO LEVEL MASTER OPERATION MANUAL IB

ALM473 DUAL MONO \ STEREO AUDIO LEVEL MASTER OPERATION MANUAL IB ALM473 DUAL MONO \ STEREO AUDIO LEVEL MASTER OPERATION MANUAL IB6408-01 TABLE OF CONTENTS GENERAL DESCRIPTION 2 INSTALLATION 2,3,4 CONNECTION AND SETUP 4,5,6,7 FUNCTIONAL DESCRIPTION 8,9 MAINTENANCE 9

More information

Copyright 2014 by Minarik Drives

Copyright 2014 by Minarik Drives Copyright 2014 by Minarik Drives All rights reserved. No part of this document may be reproduced or transmitted in any form without written permission from Minarik Drives. The information and technical

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

Technical description

Technical description STAHLWILLE Standard Manoskop 721 Service Manoskop 730 List of contents Technical description... 27 ã=important safety points... 30 Operation... 32 Maintenance... 42 Cleaning the Manoskop... 47 Accessories...

More information

IT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual

IT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual IT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual OVERVIEW IT6810 IT6811 The Model IT6810/IT6811/IT6812 Impact Transmitter uses new technology to measure impact severity on reciprocating machinery.

More information

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5 SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5 Phone: (905) 564-0801 Fax: (905) 564-0806 www.telecor.com E:\T2-108\T2-M108-ABC\T2-M108-B.doc/AD

More information

G7K. Latching Relay. Compact Mechanical Lock Latching Relays with Manual Buttons. Model Number Structure. Ordering Information

G7K. Latching Relay. Compact Mechanical Lock Latching Relays with Manual Buttons. Model Number Structure. Ordering Information Latching Relay CSM DS_E Compact Mechanical Lock Latching Relays with Manual Buttons Compact design with a height of 7 mm, width of. mm, and depth of 8. mm. Plus, one Relay only weighs 7 g. Quick set and

More information

SRVODRV REV7 INSTALLATION NOTES

SRVODRV REV7 INSTALLATION NOTES SRVODRV-8020 -REV7 INSTALLATION NOTES Thank you for purchasing the SRVODRV -8020 drive. The SRVODRV -8020 DC servo drive is warranted to be free of manufacturing defects for 1 year from the date of purchase.

More information

22 Series Relays. Technical Data...1. Specifications...2. Model Number Structure - Relays...3. Model Number Selection

22 Series Relays. Technical Data...1. Specifications...2. Model Number Structure - Relays...3. Model Number Selection Relays 22 Technical Data...1 Specifications...2 Model Number Structure - Relays...3 Model Number Selection... 4-5 Electrical Characteristics...6 Accessories...7 Dimensions...8 Instructions...10 Safety

More information

Digital Function Generator

Digital Function Generator Digital Function Generator 13654-99 PHYWE Systeme GmbH & Co. KG Robert-Bosch-Breite 10 37079 Göttingen Germany Tel. +49 (0) 551 604-0 Fax +49 (0) 551 604-107 E-mail info@phywe.de Operating Instructions

More information

T22. Data Sheet. Torque transducer. Special features. Installation example with two bellows couplings. B en

T22. Data Sheet. Torque transducer. Special features. Installation example with two bellows couplings. B en T22 Torque transducer Data Sheet Special features - Nominal (rated) torques N m, 10 N m, 20 N m, 0 N m, 100 N m, 200 N m, 00 N m and 1 kn m - Nominal (rated) rotational speeds of 9000 rpm to 16 000 rpm

More information

T22. Torque transducer. Special features. Data sheet

T22. Torque transducer. Special features. Data sheet T22 Torque transducer Special features - Nominal (rated) torques 0.5 Nm, 1 Nm, 2 Nm, 5 Nm, Nm, Nm, 50 Nm, 0 Nm, 0 Nm, 500 Nm and 1 knm - Nominal (rated) rotational speed up to 000 rpm (depending on measuring

More information

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW MicroManager Torque Mode CTCW/Loadcell Control Instruction Manual MM3000-CTCW Table of Contents 1. General Description... 5 2. Specifications... 5 2.1 Electrical... 5 2.2 Physical... 6 3. Installation...

More information

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition UNICONT PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1 ST edition pmg4111a0600p_01 1 / 24 TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 3 2. ORDER CODE... 3 3. TECHNICAL DATA...

More information

THANK YOU FOR PURCHASING OUR STUDIO RTA CREATION STATION

THANK YOU FOR PURCHASING OUR STUDIO RTA CREATION STATION THANK YOU FOR PURCHASING OUR STUDIO RTA MODEL# 20672 IF YOU REQUIRE ANY ASSISTANCE WITH ASSEMBLY, PARTS, OR INFORMATION ON OTHER PRODUCTS, PLEASE VISIT OUR WEBSITE: www.studiorta.com OR CALL OR WRITE THE

More information

Torque Sensor Series 3000 and Series 4000

Torque Sensor Series 3000 and Series 4000 Properties Sensorshaft with integrated torque and angle measurement Non-contact measurement system, high robustness Plug & Play solution, no additional electronics required Performance Measurement range

More information

Instruction Sheet REB SERIES. Rotating Sliding Base REB18

Instruction Sheet REB SERIES. Rotating Sliding Base REB18 Instruction Sheet REB SERIES Rotating Sliding Base REB14 REB18 THANK YOU Thank you for purchasing the REB Series Rotating Sliding Base. Please read these instructions thoroughly before installing this

More information

AUC Cell Assembly Torque Stand. User Manual

AUC Cell Assembly Torque Stand. User Manual AUC Cell Assembly Torque Stand User Manual WARRANTY Spin Analytical Inc., warrants this product to be defect free in both material and workmanship for 90 days from the date of shipment. Labor services

More information

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009 User s Guide Publication number 34134-90001 April 2009 For Safety information, Warranties, Regulatory information, and publishing information, see the pages at the back of this book. Copyright Agilent

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL

ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL ESP Product Warranty Zener Electric warrant the Electronic Shear Pin against defective workmanship and materials for a period of 24 months from the

More information

COFFEE LABORATORY WHITE STONE VA TEL

COFFEE LABORATORY WHITE STONE VA TEL 1. Technical specifications 4. Operating instructions: Octagon 200 Copyright 2015 by Endecotts Ltd. 21 1. Setting up Technical specifications SIEVE SHAKER MODEL: Octagon 200 General Information The sieve

More information

Strain Gauge Measuring Amplifier BA 662

Strain Gauge Measuring Amplifier BA 662 Strain Gauge Measuring Amplifier BA 662 Original of the Manual Table of Contents 1. Safety precautions... 2 1.1. Field of application... 2 1.2. Installation... 2 1.3. Maintenance... 2 2. Function... 2

More information

TMC3 SERVO CARD For WEM/XEM Series Actuators Installation & Maintenance Manual

TMC3 SERVO CARD For WEM/XEM Series Actuators Installation & Maintenance Manual . GEERAL DESCRIPTIO The Triac TMC is a proportional AC Motor Controller, intended for use with split phase AC actuator motors. The actuator is controlled by comparing an external command signal to a feedback

More information

Precipitation Monitor ,

Precipitation Monitor , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021197/11/09 Precipitation Monitor 5.4103.10.000, 5.4103.10.700 ADOLF THIES GmbH & Co. KG Hauptstraße

More information

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0 Touch Switch Unique 18 mm Capacitive Touch Switch with Choice of Three Actuators is Activated with Only a Very Slight Physical Contact Lightweight objects, such as thin wire or foil can be accurately detected.

More information

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

English. Operating manual. Temperature measuring transducer MU125.  Save for later reference. Company / brands of GHM English Operating manual Temperature measuring transducer MU125 Company / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents Page 1. Intended use (areas of application)...

More information

Analog amplifier RA. RE Edition: Replaces:

Analog amplifier RA. RE Edition: Replaces: Analog amplifier RA RE 950 Edition: 08.05 Replaces: 0.006 For control of simple functions of electrohydraulic components Two power outputs (PWM) and one switching output Each output has a separately adjustable

More information

Installation / Monitoring Technique

Installation / Monitoring Technique Installation / Monitoring Technique VARIMETER RCM Residual Current Monitor, Type B for AC and DC Systems IP 5883 0249633 IP 5883 ND 5018/035 ND 5018/030 According to IEC/EN 62 020, VDE 0663 For AC and

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

Signal Isolation Module. Instruction Manual SIM

Signal Isolation Module. Instruction Manual SIM Signal Isolation Module Instruction Manual SIM200-000 Table of Contents 1. General Description... 3 2. Specifications... 3 2.1 Electrical... 3 2.2 Physical... 4 3. Installation... 4 3.1 Wiring Guidelines...

More information

2002-ALM USER MANUAL

2002-ALM USER MANUAL 00 - ALM DUAL TRIP AMPLIFIER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting from errors or omissions,

More information

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806 Series 500 Analog Transmitters by Data Industrial Data Industrial Owner s Manual Data Industrial 2/95 PN 72806 Table of Contents Introduction... 1 4-20 ma Loop Supply Requirements... 2 Installation...

More information

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Gain Electronic Co. Ltd. Table Of Contents Safety Considerations ------------------------------------------------------------2

More information

Series 7000 Torque Sensor for PTO-shafts

Series 7000 Torque Sensor for PTO-shafts Properties PTO (Power Take-Off) shaft with integrated torque and angle measurement Non-contact measurement system, high robustness Special for PTO shafts 1 ¾ und 1 3/8 Plug & Play solution, no additional

More information

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity

More information

T10F. Data Sheet. Torque Flange. Special features. Installation example T10F. B en

T10F. Data Sheet. Torque Flange. Special features. Installation example T10F. B en T10F Torque Flange Data Sheet Special features Extremely short design High permissible dynamic loads High permissible transverse forces and bending moments Very high torsional stiffness Contactless Selectable

More information

Model Number Structure

Model Number Structure Current Sensor CSM DS_E Solid-state, Plug-in Current Sensor Applicable to motor overcurrent protection and 3-phase AC current detection. Inverse-type, start-up lock type, and instantaneous type overcurrent

More information

Technical data. Your advantages

Technical data. Your advantages Technical data Nominal torque: 50 Nm to 2.000 Nm, bidirectional Rotational speed: 10.000 rpm Accuracy: ±0,2 % Temperature range: -40 C to +85 C Protection class: IP50, IP65 Output signals: 0-10 V/4-20

More information

Current consumption ma solenoid current consumption ( max 300 ma) Hz % V ma. Housing dimensions mm 120(d) x 99(h) x 23(w)

Current consumption ma solenoid current consumption ( max 300 ma) Hz % V ma. Housing dimensions mm 120(d) x 99(h) x 23(w) 89 610/112 ED EWM-A-SV ANALOG AMPLIFIER CARD SERVOVALVE CONTROL RAIL MOUNTING TYPE: DIN EN 50022 OPERATING PRINCIPLE This card is designed for a dynamic control of servovalves with the current output controlled

More information

AS440 AUTOMATIC VOLTAGE REGULATOR (AVR)

AS440 AUTOMATIC VOLTAGE REGULATOR (AVR) AS440 AUTOMATIC VOLTAGE REGULATOR (AVR) SPECIFICATION INSTALLATION AND ADJUSTMENTS General description Technical specification AS440 is a half wave phase controlled thyristor type AVR and forms part of

More information

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

Valve amplifier for proportional pressure valves

Valve amplifier for proportional pressure valves Valve amplifier for proportional pressure valves Type VT-MRMA1-1 RE 30214 Edition: 2017-03 Replaces: 04.13 Component series 1X Analog, modular design Suitable for controlling a direct current motor-operated

More information

Rev /13 SSRMAN-1B SERIES USERS MANUAL SSR INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 NUWAVE TECHNOLOGIES, INC.

Rev /13 SSRMAN-1B SERIES USERS MANUAL SSR INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 NUWAVE TECHNOLOGIES, INC. Rev.2.2 12/13 MAN-1B SERIES USERS MANUAL INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 MAN-1B Users Manual Page 2 TABLE OF CONTENTS 1. Ordering Codes... 2 2. Description... 2 2.1 Features... 3 3. Installation

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations

More information

Model 935A. Dual Tone Sender INSTRUCTION MANUAL

Model 935A. Dual Tone Sender INSTRUCTION MANUAL Model 935A Dual Tone Sender INSTRUCTION MANUAL Monroe Electronics 100 Housel Ave Lyndonville NY 14098 800-821-6001 585-765-2254 fax 585-765-9330 monroe-electronics.com Printed in USA Copyright Monroe Electronics,

More information

REE series digital interpolators

REE series digital interpolators Data sheet L-957-939-0-B REE series digital interpolators The REE digital series of interpolators is designed to accompany the RG ( µm) and RG (0 µm) encoder systems by offering a wide range of interpolation

More information

Model Number Structure

Model Number Structure Single-phase Voltage Relay CSM DS_E_3_1 Ideal for voltage monitoring for industrial facilities and equipment. Monitor for overvoltages or undervoltages. Manual resetting and automatically resetting supported

More information

WLL 170 Photoelectric switches with fibre-optic cable, red light, manual sensitivity adjustment -- DC. Dimensional drawing R1.6 2-R

WLL 170 Photoelectric switches with fibre-optic cable, red light, manual sensitivity adjustment -- DC. Dimensional drawing R1.6 2-R WLL 0 Photoelectric switches with fibre-optic cable, red light, manual sensitivity adjustment -- DC 0... 0 mm Through-beam systems Dimensional drawing R. -R. Scanning distance 0... 0 mm. Proximity systems

More information

IF30. User's manual. Description. Table of contents IF30

IF30. User's manual. Description. Table of contents IF30 User's manual IF30 Description IF30 is an encoder interface unit designed to convert the output signals delivered by so-called sine-cosine-encoders and similar measuring systems (devices which deliver

More information

Current Probes. User Manual

Current Probes. User Manual Current Probes User Manual ETS-Lindgren Inc. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall

More information

SCHMIDT Flow Sensor SS SS FB

SCHMIDT Flow Sensor SS SS FB Product description Flow sensor with integrated microcontroller transducer for the measurement of air-flow velocity and for the determination of the flow rate and flow volume. The aerodynamically styled

More information

Assembly & Installation Instructions

Assembly & Installation Instructions Wall Mount Hose Reel Model 04-GH Configuration Pulls the hose out straight away from the wall. Configuration Pulls the hose out along side the wall. Assembly & Installation Instructions Version 0409 A

More information

TETRIS 1000 High Impedance Active Probe. Instruction Manual

TETRIS 1000 High Impedance Active Probe. Instruction Manual TETRIS 1000 High Impedance Active Probe Instruction Manual Copyright 2015 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

Ordering Information. Stepping Relay Unit G9B. Model Number Legend

Ordering Information. Stepping Relay Unit G9B. Model Number Legend Stepping Relay Unit CSM DS_E_4_1 Ideal for Controlling Pumps and Production Lines with Six or Twelve Stepping Circuits Built-in relays switch 2 A at 250 VAC or 30 VDC. Initialization of stepping with reset

More information

User s Manual. Portable Chamfering Machine

User s Manual. Portable Chamfering Machine User s Manual Portable Chamfering Machine #535, Migun Techno World II 187 Techno 2-Ro, Yuseong-Gu, Daejeon, 305-500, S.Korea Tel : +82-31-335-7257 / Fax : +82-2-6008-2777 E-mail : overseas@ahaind.com /

More information

SCHMIDT Flow Sensor SS 25.60

SCHMIDT Flow Sensor SS 25.60 Product description Product advantages Form 107/06/09/1000/3 Art. No. 511 047.02 A Data subject to change The flow sensor is a mass flow sensor (thermal anemometer), designed for use in oxygen. Due to

More information

Electronic Thermostat TE-1 Version according to EN

Electronic Thermostat TE-1 Version according to EN JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 3639 Fulda, Germany Postal address: 3635 Fulda, Germany Phone: +49 661 63- Fax: +49 661 63-67 e-mail: mail@jumo.net Internet: www.jumo.net JUMO

More information

Electronic amplifier for the control of proportional valves without position control Model VT 3006, Series 3X H/A 4240/94 VT X

Electronic amplifier for the control of proportional valves without position control Model VT 3006, Series 3X H/A 4240/94 VT X Electronic amplifier for the control of proportional valves without position control Model T 3006, Series 3X RA 29 926/06.98 Replaces: 02.96 The amplifier T 3006-3X is suitable for the control of pilot

More information

High Accuracy Positioning Sensors EG Series Features

High Accuracy Positioning Sensors EG Series Features High ccuracy Positioning s EG Series Features Ultra-small sensor head Non-contact, stable detection in wide temperature range Highly stable amplifier provides 1 µm. Mil repeatability Hi/Lo tolerance detection

More information

LVDT. Inductive Position Transducer - Hydraulic Series. SM-HYD-F18 Hydraulic-Series. Key-Features:

LVDT. Inductive Position Transducer - Hydraulic Series. SM-HYD-F18 Hydraulic-Series. Key-Features: LVDT Inductive Position Transducer - Hydraulic Series SM-HYD-F18 Hydraulic-Series Key-Features: Content: - M18x1,5 mm integral thread - Operating pressure 150 bar - Ranges 2...200 mm - Linearity up to

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

Operating Manual MU2000K

Operating Manual MU2000K ZIEHL industrie elektronik GmbH + Co KG Daimlerstr.13, 74523 Schwäbisch Hall, Germany + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN

More information

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the

More information

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs Operating Manual Out 1 sin / cos 1Vpp Input: sin / cos 1 Vpp Out 2 sin / cos 1Vpp Out 3 sin / cos 1Vpp SV 211 Out 4 sin / cos 1Vpp Interface type SV211 SinCos signal splitter with 4 SinCos outputs Product

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

Installation Tech Note Dallas, Texas

Installation Tech Note Dallas, Texas AMC B40A40AC Installation Tech Note Dallas, Texas May, 2010 ! CAUTION! Do NOT apply air pressure to release the collet while the servo motor is rotating. The servo motor spindle must be FULLY STOPPED before

More information

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4.

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4. An American Control Electronics Brand PCM4 SERIES PCM4 USER MANUAL www.minarikdrives.com Dear Valued Consumer: Congratulations on your purchase of the PCM4 Series isolation card. This User Manual was created

More information

USER S MANUAL PROCESS CONTROL MODULE PCM3

USER S MANUAL PROCESS CONTROL MODULE PCM3 USER S MANUAL PROCESS CONTROL MODULE PCM3 Copyright 2002 by Minarik Corporation All rights reserved. No part of this manual may be reproduced or transmitted in any form without written permission from

More information

Precipition Sensor with analogue Intensity Output ,

Precipition Sensor with analogue Intensity Output , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021335/11/09 Precipition Sensor with analogue Intensity Output 5.4103.20.041, 5.4103.20.741 ADOLF THIES

More information

Electronic Amplifier Model VT 3017 and VT 3018 (Series 3X) for the control of proportional directional valves, without positional feedback

Electronic Amplifier Model VT 3017 and VT 3018 (Series 3X) for the control of proportional directional valves, without positional feedback RA 29 939/06.98 Electronic Amplifier Model T 301 and T 3018 (Series 3X) for the control of proportional directional valves, without positional feedback RA 29 939/06.98 Replaces: 09.94 Electronic amplifier

More information

Instruction Sheet SNE SERIES. Cable Chase

Instruction Sheet SNE SERIES. Cable Chase Instruction Sheet SNE SERIES Cable Chase THANK YOU Thank you for purchasing the SNE Series Cable Chase. Please read these instructions thoroughly before installing this product. PRODUCT FEATURES The 45

More information

JTY2 PULSE DURATION RECEIVER BEFORE USE... COMPONENT IDENTIFICATION

JTY2 PULSE DURATION RECEIVER BEFORE USE... COMPONENT IDENTIFICATION INSTRUCTION MANUAL PULSE DURATION RECEIVER (field-programmable; built-in excitation) MODEL JTY JTY BEFORE USE... Thank you for choosing M-System. Before use, check the contents of the package you received

More information

OWNER S MANUAL Linear 3 Rev F 1 19/8/05, 2:37 pm

OWNER S MANUAL Linear 3 Rev F 1 19/8/05, 2:37 pm OWNER S MANUAL 1 Contents Page Section 1 Introduction 1 2 Handling 1 3 Installation 2 4 Positioning 3 5 Connecting 4 6 Amplifiers 4 7 Listening 4 8 Specification 5 9 The Linear Range 5 10 Warranty 5 11

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

Technical Explanations. SKiiP 3 Parallel Board. Technical Explanation SKiiP 3 Parallel Board. This document is valid for the following part numbers:

Technical Explanations. SKiiP 3 Parallel Board. Technical Explanation SKiiP 3 Parallel Board. This document is valid for the following part numbers: Technical Explanations Revision: 2 Issue Date: 30.08.17 Prepared by: Approved by: This document is valid for the following part numbers: - L5064101 - L5064102 - L5064103 with date code(jjww) 1245. Schiller

More information

Instruction Manual DT3010-U15-A-C3 DT3010-U15-M-C3 DT3010-S2-A-C3 DT3010-S2-M-C3 DT3010-U3-A-C3 DT3010-U3-M-C3 DT3010-U6-A-C3 DT3010-U6-M-C3

Instruction Manual DT3010-U15-A-C3 DT3010-U15-M-C3 DT3010-S2-A-C3 DT3010-S2-M-C3 DT3010-U3-A-C3 DT3010-U3-M-C3 DT3010-U6-A-C3 DT3010-U6-M-C3 Instruction Manual DT3010-U05-A-C2 DT3010-U05-M-C2 DT3010-U1-A-C3 DT3010-U1-M-C3 DT3010-S1-A-C3 DT3010-S1-M-C3 DT3010-S2-A-C3 DT3010-S2-M-C3 DT3010-U3-A-C3 DT3010-U3-M-C3 DT3010-U6-A-C3 DT3010-U6-M-C3

More information

Valve amplifier for proportional valves. Type VT-MSPA2-1. Contents. Features. RE Edition: Replaces:

Valve amplifier for proportional valves. Type VT-MSPA2-1. Contents. Features. RE Edition: Replaces: Valve amplifier for proportional valves Type VT-MSPA2-1 RE 30228 Edition: 2014-01 Replaces: 2011-04 Component series 1X Suitable for controlling direct operated proportional directional valves without

More information

T40FM. Data Sheet. Torque flange. Special features. Overall concept. B en

T40FM. Data Sheet. Torque flange. Special features. Overall concept. B en T40FM Torque flange Special features Data Sheet - Nominal (rated) torque: 15 kn m, 20 kn m, 25 kn m, 30 kn m, 40 kn m, 50 kn m, 60 kn m, 70 kn m and 80 kn m - Nominal (rated) rotational speed up to 8000

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

OPERATION AND MAINTENANCE MANUAL TRIAXIAL ACCELEROMETER MODEL PA-23 STOCK NO

OPERATION AND MAINTENANCE MANUAL TRIAXIAL ACCELEROMETER MODEL PA-23 STOCK NO OPERATION AND MAINTENANCE MANUAL TRIAXIAL ACCELEROMETER MODEL PA-23 STOCK NO. 990-60700-9801 GEOTECH INSTRUMENTS, LLC 10755 SANDEN DRIVE DALLAS, TEXAS 75238-1336 TEL: (214) 221-0000 FAX: (214) 343-4400

More information