PL.P7.06.TransitionP5. Product Transition Guide GPD 506/P5 to P7

Size: px
Start display at page:

Download "PL.P7.06.TransitionP5. Product Transition Guide GPD 506/P5 to P7"

Transcription

1 PL.P7.06.TransitionP5 Product Transition Guide GPD 506/P5 to P7

2 GPD506/P5 to P7 NOTICE The information contained within this document is the proprietary property of Yaskawa Electric America, Inc., and may not be copied, reproduced or transmitted to other parties without the expressed written authorization of Yaskawa Electric America, Inc. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly improving its high-quality products, the information contained in this document is subject to change without notice. Every precaution has been taken in the preparation of this document. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication. Page 2 of 48

3 GPD506/P5 to P7 Contents FEATURE OVERVIEW... 5 BENEFITS OF THE NEW P7 WHEN COMPARED TO GPD506/P NEW/ADDITIONAL P7 PARAMETER FUNCTIONS NOT PRESENT IN THE GPD506/P P7 DIGITAL INPUTS (ADDITIONAL FUNCTIONS)... 6 P7 DIGITAL INPUTS (ADDITIONAL FUNCTIONS)... 6 P7 ANALOG INPUT (ADDITIONAL FUNCTIONS)... 6 P7 DIGITAL OUTPUT RELAY (ADDITIONAL FUNCTIONS)... 6 P7 ANALOG OUTPUTS (ADDITIONAL FUNCTIONS)... 6 P7 SERIAL COMMUNICATIONS... 7 P7 START-UP, INSTALLATION & MAINTENANCE IMPROVEMENTS... 7 P7 ADDITIONAL HARDWARE PROTECTION... 7 REASONS TO CONTINUE GPD506/P GPD506/P5 TO P7 SPECIFICATION DIFFERENCES... 9 DIGITAL OPERATOR COMPARISON GPD506/P5 TO P7 TERMINAL COMPARISON NETWORK COMMUNICATIONS DETAILS ON NEW P7 FEATURES & FUNCTIONS APPENDIX RATINGS AND HEAT LOSS COMPARISON NEC HP RATINGS FOR 240V NORMAL DUTY MODELS NEC HP RATINGS FOR 480V NORMAL DUTY MODELS HEAT LOSS DATA APPENDIX MECHANICAL DIMENSIONS PANEL CUT-OUT FOR EXTERNAL HEATSINK MOUNTING MOUNTING HOLE DATA APPENDIX 3 PARAMETER CROSS REFERENCE Page 3 of 48

4 GPD506/P5 to P7 Page Intentionally Left Blank Page 4 of 48

5 GPD506/P5 to P7 Feature Overview This document details differences between the GPD506/P5 and P7 product to assist in product transition and new product introduction. GPD506/P5 Drive The GPD 506/P5 inverter is intended for fan and pump applications in Building and Industrial Automation. It is available in constant and variable torque ratings, 3/4 to 500 horsepower. P7 Drive The P7 drive is an ideal choice for industrial applications, such as centrifugal fans and pumps. The P7 drive is provided in Normal Duty ratings with 110% overload capability. V/f control mode, network communication options, and an array of input/output choices are available. Benefits of the New P7 When Compared to GPD506/P5 New/Additional P7 Functions not Present in the GPD506/P5 New Motor preheat function with adjustable current setting to prevent condensation in motor, (b2-09) P7 is flash memory upgradeable Accel/Decel range now adjustable from 0.1 to 6000 sec. (GPD506/P5 max. range is 3600) Critical frequency rejection: 3 selectable, adjustable bands, d3-03 Jump frequency 3 (additional) (GPD506/P5 only has two) New Wait To Run Timer function allowing output of drive to delay start after a Run command (b1-11) Torque boost with adjustable filter time for better torque compensation response (C4-02) Power loss ride-thru time settable to 25 sec. (GPD506/P5 is 2 sec. Max.) Auto restart now has maximum restart time after fault if fault condition doesn t clear during the first try New "Up/Down" floating point control capability Primary resistance auto-tuning Customizable monitor display Run permissive input New PI Snooze function available in conjunction with Sleep mode (b5-21) Adjustable Undervoltage Detection level (L2-05) not available in GPD506/P5 Speed search function with new Speed Estimation mode and Bi-directional search mode (b3-01) New Setpoint PI features include: Two feedback capability, Output Limit, Offset adjustment, Primary delay, Output gain, Output reverse, Setpoint accel/decel, Setpoint display scaling, Selectable sleep input source, Snooze function, Setpoint boost, Fdbk square root function with output monitor. (b5-06, b5-07, b5-08, b5-10, b5-11, b5-17 thru 30) Separately adjustable e-stop times (C1-09) Accel/decel rate switchover via output frequency (C1-11) 14 more V/f presets than GPD506/P5 for a total of 15 V/f preset patterns (E1-03) Mid frequency and voltage V/f points on the custom V/f pattern (E1-11,12) Trim speed control function (d4-02) New/Additional P7 Functions not Present in the GPD506/P5 Page 5 of 48

6 GPD506/P5 to P7 Motor thermistor input with temperature filter and selectable fault,alarm settings (L1-02 to L1-05) Intelligent stall prevention on accel/decel with decel time 1 or 2 selections (L3-01,4,5) Extended 0.5 to sec. autorestart time between attempts vs secs for GPD506/P5 (L5-03) Hunting prevention function (n1-01,2) DC Injection braking (b1-03) Run command can be accepted while the drive is being programmed (b1-08) High slip braking function (n3-01,2,3,4) Selectable power-up monitor (o1-01,2) Keypad display contrast adjustment (o1-05) Two independent programmable over and under torque detection levels P7 Digital Inputs (Additional Functions) One more digital input for a total of seven More versatile PNP/NPN sinking/sourcing 24 VDC control logic Transmitter/option power supply 29 more programmable functions for digital inputs than GPD506/P5. 59 total : Motor Preheat MOP increase/decrease function Forward and reverse jog input Trim control increase and decrease functions 15 additional external fault action settings such as Faststop, Alarm only, Coast to stop with selectable N.O or N.C. for each fault action. PI integral hold and PI cancel functions Speed search 3 Serial Communication test mode High slip braking input Jog 2 P7 Analog Input (Additional Functions) A convenient PCB switch now changes analog input A2 between current and voltage, cutting PCB jumper for ma signal is no longer required. Adjustable analog input signal filter for added stability Terminal A2 is selectable for : Frequency bias Motor thermister PI differential Analog input filter Main and Aux frequency reference is selectable between terminals A1 and A2 P7 Digital Output Relay (Additional Functions) 27 possible programmable functions for the digital outputs, seven more than the GPD506/P5. One additional relay output, M3 and M4 relays DC bus under voltage output Reset command active output Reverse direction output Drive enable output OH frequency reduction output Restart Enabled P7 Analog Outputs (Additional Functions) Additional AM analog monitor output with bias and gain settings. Analog monitors now selectable between 0-10V and 4-20ma, GPD506/P5 only 0-10V 18 programmable selections for the analog outputs, 14 more than the GPD506/P5. Frequency reference monitor Terminal A1 or A2 monitor Motor SEC current monitor SFS output monitor PI- feedback, input, output and setpoint monitors PI feedback 2 monitor Output Voltage P7 Digital Inputs (Additional Functions) Drive enable, with selectable accept run command or cycle run command function Page 6 of 48

7 GPD506/P5 to P7 P7 Start-up, Installation & Maintenance Improvements Control terminal board: Quick disconnect Enhanced digital keypad, 5 Line x 16 Character LCD (Std) 6 new languages can be displayed on the keypad. GPD506/P5 has only English (A1-00) User password protection for 32 customizable user parameters (A1-04) A2-01 thru A2-32 User access level provides 32 user selectable parameters. copy function to another P7 using standard digital operator (o3-01) Improved fault storage, last 10 faults Quick disconnect I/O blocks for easy wiring Logged cooling fan hours for scheduled maintenance Modular cooling fan for easy replacement Automatic cooling fan run control to extend fan life P7 Serial Communications Built-in RS-485/422 modbus serial communications Optional communication interface: Devicenet, Profibus, and others Serial communications loss detection timeout function Drive Wizard upload/download and monitoring /graphing software P7 Additional Hardware Protection Adjustable heat-sink overheat pre-alarm level (L8-02) Selectable ground fault detection (L8-09) Selectable cooling fan operation with off delay (L8-10,11) Automatic ambient temperature compensation to protect the drive in environments exceeding its rating (L8-12) Adjustable OH frequency reference reduction (L8-19) Adjustable motor overload time constant (L1-02) Page 7 of 48

8 GPD506/P5 to P7 Page left intentionally blank Page 8 of 48

9 GPD506/P5 to P7 Specification Differences Feature Item or Function Performance Features HP Range Note: The voltage rating in the Item column is generalized. Refer to the Service Conditions section for rated input voltage requirements. Overload Rating Product Transition Guide GPD506/P5 to P7 Yaskawa GPD506/P5 Yaskawa P7 240V 0.75 to 125HP (VT) 5 to 150HP (ND2) 480V 0.75 to 500HP (VT) 5 to 500HP (ND2) 600V % for Minutes 2 to 200HP (VT) 150% for 1 min (CT) 200% peak 120% for 1 min (VT) 180% peak Available w/gpd506/p5 Not Available in P7 110% for 1 min (ND2) 150% peak PWM Carrier Frequency Range See Carrier Frequency Table See Carrier Frequency Table Max. Output Frequency Hz 400Hz 0 To 120Hz Speed Range V/f 40:1 40:1 Protective Features Heat Sink Temperature Fault Fault Action Coast, Ramp, Continue --Coast, Ramp, Continue or Continue with reduced speed --OH Pre-alarm level setting Design Features Keypad Design Qty of keys 7 11 Language 1 7 (w/lcd) Copy Function No Yes Display LCD display, alpha numeric, 16 char x 2 lines LCD display, alpha numeric, 16 char x 5 lines, backlit Page 9 of 48

10 GPD506/P5 to P7 GPD506/P5 to P7 Specification Differences (continued) Feature or Function Item Yaskawa GPD506/P5 Yaskawa P7 Design Features (continued) Network Communications Diagnostics Standard Optional Fault Storage Modbus RTU via RS232 RS232 to RS485, DeviceNet, Lonworks, ApogeeFLN, MetasysN2 Last 4 Faults Quick Disconnect I/O Terminals Type No Auto-Tuning Rotating/Stationary No Modbus RTU via built in RS485/422 DeviceNet, Profibus-DP, Lonworks, Ethernet Last 10 Faults with Elapsed Time, Most Recent Fault with all Operating Conditions Yes (Phoenix) With split front cover for easy wiring Primary resistance auto-tuning Speed Search Bi/Uni-Directional Uni-Directional Bi-Directional Synchronized Start Method Current Current/Speed PI / PID Control Analog Input Signal Filter No Yes Two Feedback No Yes Sleep Function In Open Loop Mode No Yes Automatic Restart Time Between Attempts Not Adjustable sec (selectable) V/Hz Patterns Qty. 1 Preset, 1 Custom 15 Preset, 2 Custom Skip Frequencies Qty. 2 3 Custom Drive Software Embedded No Flash memory Upload/Download PC Software InverterWin Drive Wizard Software Accel/Decel Time Sec sec sec. Closed Loop PID Control Analog Input Filter No Yes Two Feedback No Yes DC Injection Function At Start/At Stop (adjustable) At Start/At Stop At Start/At Stop +HSB during stop Braking Function Built-in to 10HP (VT-230V) DB Transistor Built-in to 25HP (VT-460V) Built-in to 25HP Special No High Slip Braking all models (Faster stopping without options) Cooling Fan On/Off Control Power-up based Run Based Service Disassembly required Modular/pluggable fan select models Operating Hours Drive power-up hours logged Logged Timer Function On Delay at start (0-600 sec) On/Off Delay On/Off Delay ( sec) On/Off Delay Timer ( sec) Page 10 of 48

11 GPD506/P5 to P7 GPD506/P5 to P7 Specification Differences (continued) Feature or Function Item Yaskawa GPD506/P5 Yaskawa P7 Design Features (continued) Common DC Bus Capable - No Yes DC Link or AC Choke DC Link (Standard) 230V: 30HP to 125HP (VT) - 240V: 30HP to 150 HP 460V: 30 to 250HP (VT) 480V: 40 HP to 500 HP Harmonic Counter Measures 12 Pulse: 12 Pulse: 230V: 30HP and Above - 240V: 30HP to 150HP 460V: 30HP to 250HP 480V: 40HP to 500HP Unique Feature/Function - - HSB High Slip Braking Inputs and Outputs Digital Input Terminal Total Qty. 6 7 (optically isolated) NPN/PNP NPN Switchable NPN/PNP Digital Output Terminal Total Qty 2 3 Relay Output 1 x Form C, 1 x Form A, 2 x Form A, 1 x Form C Analog Input Qty. 2 2 Level Input 0-10V or 4-20mA 0-10 or 4-20mA Scan Rate 5 msec 5 msec Loss Detection Ramp or Continue Ramp, Coast or Continue Analog Output Qty. 1 2 Output Level 0-10V 0-10V or 4-20ma With independent level selections Resolution 9 bit 10 bit plus sign Service Conditions Rated Input Ambient Temperature - ºC 3-phase, Vac 3-phase, Vac Tolerance +10 to 15% 3-phase, Vac Tolerance +10 to 10% Frequency: 50/60 Hz +/- 5% (IP21/NEMA1) -10ºC ~ +40ºC (IP00/Protected Chassis) -10ºC ~ +45ºC 3-phase, Vac 3-phase, Vac Tolerance +10 to 15% Frequency: 50/60 Hz +/- 5% Note: P7 Models rated for Vac. -10ºC ~ +40ºC (IP21/NEMA1) -10ºC ~ +45ºC (IP00/Protected Chassis) (Automatic OL protection curve based on ambient temperature setting of L8-12) Storage Temperature ºC -10ºC ~ +60ºC -20ºC ~ +60ºC Enclosure Types NEMA 4X Optional N/A NEMA 3/3R Optional N/A Page 11 of 48

12 GPD506/P5 to P7 Digital Operator Comparison Enhanced LCD operator with built-in copy function and parameter verify for P7 Optional LED operator available for P7 LCD contrast adjustment Simplified parameter grouping for easier navigation and set-up GPD506/P5 Operator New P7 Operator Drive Mode Indicators LCD DISPLAY Frequency Ref U1-01 = 0.00Hz Menu Display -DRIVE- Rdy Frequency Ref U1-01= 60.00Hz U1-02= 60.00Hz U1-03= 10.05A Ready Display Drive can operate when a drive command is input Data Display Displays monitor data, parameter data and settings 1 line x 13 characters 3 lines x 16 charact ers Keys RUN & STOP Indicators -Rdy- -QUICK- Accel Time C1-01= 21.0secs (0.0~6000.0) 30.0 sec Present Setting (user adjusts) Allowed Setting Range Factory Default P7 copy keypad is capable of uploading all of the parameter settings from the P7 drive memory. o Upload of GPD506/P5 parameters to P7 not possible at this time o P7 Drives must have the same software version, model, and control mode to copy parameters. A Quick Start menu is added to aid in simple start-ups. The Quick Start menu consists of 64 parameters. The Advanced menu is the other menu choice. Simplified Menu Structure in P7: GPD506/P5 P7 -- Operation DRIVE Quick Start s Quick Setting QUICK Programming (All s) Programming ADV -- Modified Constants VERIFY -- Auto-Tuning A.TUNE -- Page 12 of 48

13 GPD506/P5 to P7 GPD506/P5 to P7 Terminal Comparison The factory default is 2-wire control as shown. GPD506/P5 Terminal Type GPD506/P5 Terminal Digital Input Signals Default Function & Description P7 Terminal P7 Terminal (Designations similar to GPD506/P5) Default Function Forward run/stop, Forward run when closed, and stop when S1 open. Photo-coupler insulation Input: +24VDC 8mA Reverse run/stop, Reverse run when closed, Stop when open. S2 Multi-function contact input (n036) Photo-coupler insulation Input: +24VDC 8mA External fault input, Fault when closed, normal state when open. S3 Multi-function contact input (n037) S3 External fault input Photo-coupler insulation Input: +24VDC 8mA Fault reset input, Reset when closed. S4 Multi-function contact input (n038) S4 Fault reset Photo-coupler insulation Input: +24VDC 8mA Multi-step speed reference 1, Enabled when closed. S5 Multi-function contact input Multi-step speed reference 1 S5 (n039) Photo-coupler insulation Input: +24VDC 8mA Multi-step speed reference 2, Enabled when closed. S6 Multi-function contact input (n040) S6 Multi-step speed reference 2 Photo-coupler insulation Input: +24VDC 8mA S7 Jog frequency reference SC Sequence input common terminal P7 Description S1 Forward run/stop command S2 Reverse run/stop command SN SC Digital input common Factory connected to SP SP Factory connected to SC Multi-function digital inputs. Functions set by: H1-01 to H VDC, 8mA Photo coupler isolation Factory connected for internal supply sinking mode. Refer to P7 User Manual for other methods. Page 13 of 48

14 GPD506/P5 to P7 GPD506/P5 Terminal Type GPD506/P5 Terminal Analog Input Signals FS FV FI FC Default Function & Description +15V Power supply output for analog command (Allowable current, 20mA max.) Frequency reference input (voltage) 0 to +10V/100%, n043 = FV=MSTR : FV enabled n043 = FI=MSTR : FI enabled 0 to +10V (20kW) Frequency reference input (current) 4 to 20mA/100% n043 = FV=MSTR : FV enabled n043 = FI=MSTR : FI enabled 4 to 20mA (250W) Common terminal 0V P7 Terminal P7 Terminal (Designations similar to GPD506/P5) Default Function +V +15Vdc power output A1 A2 Analog input or speed command Analog input or speed command P7 Description +15Vdc (Max. current: 20mA) 0 to +10Vdc=100% (20k ohm) 4 to 20mA=100%/(250 ohms) 0 to +10Vdc=100%/(20k ohm) Function set by H3-09. AC Analog common Digital Output Signals Analog Output Signals E(G) M1 M2 Connection to shield sheath of signal lead During running (N.O. contact) Closed when running. Multi-function contact output (n042) Dry contact capacity: 250VAC 1A or less 30VDC 1A or less E(G) M1 M2 M3 M4 MA MB MC AM Fault contact output (N.O./N.C. contact) Fault when closed between terminals MA and MC Fault when open between terminals MB and MC Multi-function contact output (n041) Dry contact capacity: 250VAC 1A or less 30VDC 1A or less Frequency meter output 0 to +10V/100% frequency Multi-function analog monitor 1 (n052) 0 to +10V 2mA or less MA MB MC FM Shield wire, optional ground line connection point During run (N.O. contact) Remote/Auto Operation (N.O. contact) Same function as GPD506/P5. Nonprogrammable Output frequency Form A Dry contacts capacity: 1 A max. at 250Vac 1 A max. at 30Vdc Multi-function digital output. Function set by H2-01. Form A Dry contacts capacity: 1 A max. at 250Vac 1 A max. at 30Vdc Multi-function digital output. Function set by H2-02. Form C Dry contacts capacity: 1 A max. at 250Vac 1 A max. at 30Vdc 0 to +10Vdc 10V=100% Output frequency (Max current 2mA). Function set by H4-01. Page 14 of 48

15 GPD506/P5 Terminal Type GPD506/P5 Terminal RS-485/422 AC Default Function & Description Frequency meter output AM Common P7 Terminal AM R+ R- S+ S- Product Transition Guide Terminal Comparison P7 Terminal (Designations similar to GPD506/P5) Default Function Output current P7 Description 0 to +10Vdc or 10V=100% Drive output current (Max current 2mA) Drive's rated output current / Function set by H4-04. AC Analog common Modbus communication Differential input, PHC isolation Modbus communication Differential output, PHC isolation IG Signal common Page 15 of 48

16 Terminal Comparison L1 L2 L3 L11 L21 L31 GPD506/P5 Gate Drive T1 T2 T3 IM 3-Phase Power Supply 50/60Hz MCCB L1 L2 L3 PE Shorting Bar Standard: CIMR-P7U23P7 to 2018 CIMR-P7U43P7 to 4018 R/L1 S/L2 T/L3 U X P7 E7 DC Reactor Standard: CIMR-P7U2022 to 2110 CIMR-P7U4030 to 4300 U/T1 V/T2 W/T3 Motor M S1 - Fixed Multi-function Contact Inputs (Factory Default) Multi-Function Inputs S2 S3 S4 S5 S6 SC (Com) PWM 8 bit 0~10V AM (Com) AC Multi-Function Analog Outputs Foward Run/Stop Reverse Run/Stop External Fault Fault Reset Multi-step Speed Setting 1 Multi-step Speed Setting 2 Jog Frequency Reference S1 S2 S3 (H1-01) S4 (H1-02) S5 (H1-03) S6 (H1-04) S7 (H1-05) SN MA MB MC Multi-function (H2-01) M1 Digital Outputs M2 250VAC/30VDC, 1A (H2-02) M3 M4 Fault Contact Digital Output 250VAC/30VDC, 1A Digital Output 1 (Default: During RUN) Digital Output 2 (Default: Remote/ Auto Operation) SC SP G G External Frequency Reference E(G) E(G) Analog Inputs Input FI selectable 4~20mA or 0~10V 0~ + 10V 4~20mA FS FV FI FC (+15V) (20k Ω ) (250 Ω ) (0V) A/D 10 bit MA MB MC M1 M2 Multi-Function Relay Outputs 2k 4 to 20mA 2kΩ P P +V +15VDC, 20mA A1 0-10VDC, 20 K Ω A2 (H3-08) 4-20mA, 250 KΩ [0 to +10VDC, 20K Ω ] AC Terminating Resistance (H4-01) FM (H4-04) AM Multi-function Analog Outputs 0 to +10VDC, 2mA Serial Port RS-232 (10-pin) Digital Operator Modbus RS-485/422 R+ R- S+ S- 110 S1-1 AC IG Page 16 of 48

17 Network Communications Product Transition Guide GPD506/P5 to P7 GPD506/P5 P7 Not Available DeviceNet Not Available EtherNet Not Available Profi-Bus RS-232 PCB Port (2CN) RS-232 via Digital Operator Port SI-K2/P RS-485 Modbus Communication Card Standard Built-in RS-485 Lon Works Lon Works 2 Johnson Controls MetaSys N2 Not Applicable FLN Network for System 600/ Apogee Not Applicable Software Upload/Download Tool InverterWin 2 Available as an option based on market demands DriveWizard Network Communications Option Availability Note: Communication option release schedule is subject to change. Yaskawa Marketing Communications will provide official notice of product availability. Present Ready now, available at P7 launch P7 (CM058) available at P7 launch Modbus - Plus, testing, available at P7 launch Ethernet MODBUS TCP/IP Available at P7 launch Ready now, available at P7 launch Page 17 of 48

18 GPD506/P5 to P7 Details on New P7 Features & Functions Note: This section details only a few of the new P7 features. o New Auto Tuning The P7 comes with a Motor Auto-tuning function to help to optimize the drive performance. Feature GPD506/P5 P7 R1 Primary Resistance Tuning No Yes R1 Primary Resistance Auto-tuning method is for motor terminal resistance. This method involves no motor shaft rotation. o New High Slip Braking The P7 incorporates a new braking function called High Slip Braking (HSB). By using a method that utilizes increased rotor slip, the drive will gain the capability of stopping up to 50% faster than without a braking resistor. All of this without the need of any external equipment or resistors! Motor speed Motor voltage DC-Bus voltage Greater than 150% brake torque is possible. Motor speed Motor voltage DC-Bus voltage Page 18 of 48

19 Appendix 1 Ratings and Heat Loss Comparison Page 19 of 48

20 GPD506/P5 to P7 Page Intentionally Left Blank Page 20 of 48

21 Appendix 1 Ratings and Heat Loss Comparison NEC HP Ratings for 240V Normal Duty Models GPD506/P5 230V Models P7 240V Models Variable Torque (n116=1) Normal Duty (C6-01=2) NEC HP 230V NEC Amps GPD506/P5 Model CIMR-P5U Output Amps Fc khz Overload% VT 1 minute P7 Model CIMR-P7U Output Amps Fc khz Overload % ND 1 minute P P P P P P * * * * * * * * * * *Note: Optional NEMA1 kit required for NEMA1 rating. Input voltage rating is 230V on these models. Page 21 of 48

22 Appendix 1 Ratings and Heat Loss Comparison NEC HP Ratings for 480V Normal Duty Models GPD506/P5 460V Models P7 480V Models Variable Torque (n116=1) Normal Duty (C6-02=2) NEC HP 460V NEC Amps GPD506/P5 Model CIMR-P5U Output Amps Fc khz OL % VT 1 minute P7 Model CIMR-P7U Output Amps Fc khz Overload % ND 1 minute P P P P P P P P * * * * * * * * *Note: Optional NEMA1 kit required on these models for NEMA1 rating Page 22 of 48

23 Appendix 1 Ratings and Heat Loss Comparison Heat Loss Data Note: Ampacity ratings vary between GPD506/P5 and P7 models. Refer to NEC Ratings tables in Appendix 1 for the appropriate GPD506/P5 to P7 cross-reference. GPD506/ GPD506/P5 (W) P7 P7 (W) P5 Model Internal Heatsink Total Model Internal Heatsink Total 23P P P P P P P P P P P P P P P P P P Page 23 of 48

24 Appendix 1 Ratings and Heat Loss Comparison Page Intentionally Left Blank Page 24 of 48

25 Appendix 1 Ratings and Heat Loss Comparison Appendix 2 Mechanical Dimensions Page 25 of 48

26 GPD506/P5 to P7 Page Intentionally Left Blank Page 26 of 48

27 Appendix 2 Mechanical Dimensions Panel Cut-out for External Heatsink Mounting Note: Ampacity ratings vary between GPD506/P5 and P7 models. Refer to NEC Ratings tables in Appendix 1 for the appropriate GPD506/P5 to P7 cross-reference. GPD506/P5 Panel Cutout for External Heatsink P7 Panel Cutout for External Heatsink Model GPD506/P5 (mm) GPD506/P5 (in) Model P7 (mm) P7 (in) W H W H W H W H 23P P P P P P P P P P P P Page 27 of 48

28 Appendix 2 Mechanical Dimensions Mounting Hole Data Note: Ampacity ratings vary between GPD506/P5 and P7 models. Refer to NEC Ratings tables in Appendix 1 for the appropriate GPD506/P5 to P7 cross-reference. GPD506/P5 P7 Model Enclosure (in) (mm) (in) (mm) Model Enclosure H1 W1 H1 W1 H1 W1 H1 W1 23P71 NEMA P71 NEMA P51 NEMA P51 NEMA P51 NEMA P51 NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA Open (IP00) NEMA Open (IP00) Open (IP00) P71 NEMA P71 NEMA P51 NEMA P51 NEMA P51 NEMA P51 NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA NEMA Open (IP00) (1) Open (IP00) Open (IP00) (1) Open (IP00) Open (IP00) (1) Open (IP00) Note (1): 3 mounting holes top and 3 mounting holes bottom. Dimension is between each mounting hole. Page 28 of 48

29 Appendix 3 Cross Reference The following parameter list shows each GPD506/P5 parameter and the P7 equivalent. P7 parameters without a GPD506/P5 equivalent are omitted for brevity. For details on P7 parameters please refer to the P7 manual. s are listed numerically by GPD506/P5. Page 29 of 48

30 Param Nxxx 001 Password Appendix 3- Cross Reference GPD506/P5 0: n001 read/write and parameter n002 ~ n116 read only. (Operator's FREF and F/R is read/write. Others are read only, 1: The 1st function (n001 ~ n036)are read/write, others read only 2: The 2nd function (n001 ~ n053) are read/write, others read only 3: The 1st, 2nd, and 3rd functions (n001 ~ n116) are read/write 6: 2-wire initialization (Japanese spec.) 8: Initialization (2wire sequence) 9: Initialization (3wire sequence) 002 Run Signal Value--Run Command Freq Reference 0: Operator Operator 1: Terminal block Operator 2: Operator Terminal block 3: Terminal block Terminal block 4: Operator Communication 5: Terminal block Communication 6: Communication Transmission 7: Communication Operator 8: Communication Terminal block 0: Operation Only 1: User Level (only available if A2 parameters have been set) 2: Advanced Level 0: No Initialize 1110: User Initialize (The user must first set their own parameter values and then store them using parameter o2-03.) 2220: 2-Wire Initialization 3330: 3-Wire Initialization 0: Operator - Digital preset speed U1-01 or d1-01 to d : Terminals - Analog input terminal A1 (or terminal A2 based on parameter H3 13). 2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-. 3: Option PCB - Option board connected on 2CN. 0: Operator - RUN and STOP keys on Digital Operator. 1:Terminals - Contact closure on terminals S1 or S2. 2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-. 3: Option PCB - Option board connected on 2CN. 003 Input voltage Set unit:0.1v and set ranges: v Set to the nominal voltage of the incoming line. Sets the maximum and base voltage used by preset V/F patterns, adjusts the levels of drive protective features (i.e. overvoltage, braking resistor turn-on, stall prevention, etc.). 004 Stop method selection 0: Deceleration stop 1: Coast to stop 2: Coast to stop 1 with timer 3: Coast to stop 2 with timer 005 Motor Rotation 0: Rotation CCW from load side. 1: Rotation CW from load side 006 Reverse inhibit 0: Reverse enabled 1: Reverse disabled 007 Remote/Local key 0: The function of the Remote/Local key is disabled. 1: The function of the Remote/Local key is enabled. 008 Function selection of STOP key 009 Frequency Reference selection 0: The STOP key is effective when run command is from the operator. 1: The STOP key is always enabled. 0: Frequency reference setting by the operator, the 'Enter' input is not required. 1: Frequency reference setting by the operator, the 'Enter' input is required. P7 0: Ramp to Stop 1: Coast to Stop 2: DC Injection to Stop 3: Coast with Timer (A new run command is ignored if received before the timer expires). Determines the forward rotation of the motor, and if reverse operation is disabled. 0: Reverse Enabled 1: Reverse Disabled 2: Exchange Phase - Change direction of forward motor rotation. 3: ExchgPhs, Rev Dsbl - Change direction of forward motor rotation and disable reverse operation. 0: Disabled 1: Enabled 0: Disabled 1: Enabled 0: Disabled - Data/Enter key must be pressed to enter a frequency reference. 1: Enabled - Data/Enter key is not required. The frequency reference is adjusted by the up and down arrow keys on the Digital Operator without having to press the data/enter key. Param. Access Level A1-01 Initialize s A1-03 Frequency Reference b1-01 Run Command b1-02 Input Voltage Setting E1-01 Stopping Method b1-03 Reverse Operation b1-04 Local/Remote Key Function STOP Key Function Frequency Reference Setting Method o2-01 o2-02 o2-05 Page 30 of 48

31 Param Nxxx 010 Appendix 3- Cross Reference GPD506/P5 V/f pattern selection 1: Fixed V/f pattern 0: Adjustible V/f pattern (Constant n011-n017 can be set) P7 There are 15 different preset V/F patterns to select from (E1-03 = 0 to E) with varying voltage profiles, base levels (base level = frequency at which maximum voltage is reached), and maximum frequencies. There are also settings for Custom V/F patterns that will use the settings of parameters E1-04 through E1-13. E1-03 = F selects a custom V/F pattern with an upper voltage limit and E1-03 = FF selects a custom V/F pattern without an upper voltage limit. 0: 50 Hz 1: 60 Hz 2: 60Hz (50 Hz Base) 3: 72 Hz (60 Hz Base) 4: 50 Hz VT1 5: 50 Hz VT2 6: 60 Hz VT1 7: 60 Hz VT2 8: 50 Hz HST1 9: 50 Hz HST2 A: 60 Hz HST1 B: 60 Hz HST2 C: 90 Hz (60Hz Base) D: 120 Hz (60Hz Base) E: 180 Hz (60Hz Base) F: Custom V/F FF: Custom w/o limit Param. V/F Pattern E Max. output frequency Set unit: 0.1Hz and set range: Hz 0.0 to Maximum Output Frequency E Maximum voltage Set unit: 0.1V and set ranges: V 0 to (240V), 0 to 510.0(480V) Maximum Output Voltage E Base Frequency Set unit: 0.1Hz and set range: Hz 0.0 to Base Frequency E Mid Freq output Set unit: 0.1Hz and set range: Hz 0.0 to Mid Output Frequency A E Mid Freq. voltage Set unit: 0.1V and set ranges: V 0 to (240V, ) 0 to (480V) Mid Output Voltage A E Min output frequency Set unit: 0.1Hz and set range: Hz 0.0 to Minimum Output Frequency E Min output voltage Set unit: 0.1V and set ranges: V 0 to (240V), 0 to (480V) Minimum Output Voltage E Acceleration time 1 Set unit: 0.1sec (1sec in 1000sec or more) Set range: 0 to 3600sec Deceleration time 1 Set unit: 0.1sec (1sec in 1000sec or more) Set range: 0.to 3600sec Acceleration Time 1 C1-01 Deceleration Time 1 C Acceleration time 2 Set unit: 1sec and set range: 0-255sec Acceleration Time 2 C Deceleration time 2 Set unit: 1sec and set range: 0-255sec S curve selection 0: No S curve 1 : 0.2sec 2 : 0.5sec 3 : 1.0sec 0.0 to to 2.50 Deceleration Time 2 C1-04 S-Curve Characteristic at Accel Start S-Curve Characteristic at Accel End C2-01 C2-02 Page 31 of 48

32 Appendix 3- Cross Reference GPD506/P5 P7 Param Nxxx Param. 023 Digital operator display mode Set range: : Hz with 0.1Hz 1: % speed with 0.1% 2-39: RPM. RPM =120 * freq ref(hz) /n023 (N023 is a motor pole) : n23 fourth digit = decimal point n23 1,2,3 digits = 100% freq set value (100% frequency = xxx*10 in case of 4xxx) Sets the units of the Frequency References (d1-01 to d1-17), the Frequency Reference Monitors (U1-01, U1-02, U1-05), and the Modbus communication frequency reference. 0: Hz 1: % (100% = E1-04) 2 to 39: RPM (Enter the number of motorpoles). 40 to 39999: User display. Set the number desired at maximum output frequency. 4 digit number Number of digits from the right of the decimal point Digital Operator Display o1-03 Example 1: o1-03 = 12000, will result in frequency reference from 0.0 to (200.0 = Fmax). Example 2: o1-03 = 21234, will result in frequency reference from 0.00 to (12.34 = Fmax). 024 Freq Ref 1 Set unit: Set range by constant n023 setting: to E1-04 Value Setting units are affected by o1-03 Frequency Reference 1 d Freq Ref 2 Set unit: Set range by constant n023 setting: Freq Ref 3 Set unit: Set range by constant n023 setting: Freq Ref 4 Set unit: Set range by constant n023 setting: Jog Ref Set unit: Set range by constant n023 setting: Output freq upper limit Output freq lower limit 0.00 to E1-04 Value Frequency reference when multi-function input Multi-step speed reference 1 is ON. Setting units are affected by o to E1-04 Value Frequency reference when multi-function input Multi-step speed reference 2 is ON. Setting units are affected by o to E1-04 Value Frequency reference when multi-function input Multi-step speed reference 1,2 is ON. Setting units are affected by o to E1-04 Value Frequency reference when: Jog frequency reference is selected via multi-function input terminals. Jog frequency reference has priority over multi-step speed reference 1 to 4. d1-17 is also the reference for the JOG key on the Digital Operator, and the multi-function inputs forward jog and reverse jog. Setting units are affected by o1-03. Set unit: 1% and set range:0-109% 0.0 to Determines maximum frequency reference, set as a percentage of maximum output frequency (E1-04). If the frequency reference is above this value, actual Drive speed will be limited to this value. This parameter applies to all frequency reference sources. Set unit: 1% and set range:0-100% 0.0 to Determines minimum frequency reference, set as a percentage of maximum output frequency (E1-04). If frequency reference is below this value, actual Drive speed will be set to this value. This parameter applies to all frequency reference sources. Frequency Reference 2 d1-02 Frequency Reference 3 d1-03 Frequency Reference 4 d1-04 Jog Frequency Reference d1-17 Frequency Reference Upper Limit Frequency Reference Lower Limit d2-01 d Rated motor current Set unit: 0.1A (In 1000A or more, every 1A) Set range:10-200% of drive rated current Set to the motor nameplate full load current in amperes (A). This value is automatically set during Auto-Tuning. Motor Rated Current E Motor protection selection (OL1) 0: Disabled. 1: Standard motor (eight minutes) 2: Standard motor (five minutes) 3: Inverter rated motor (eight minutes) 4: Inverter rated motor (five minutes) Sets the motor thermal overload protection (OL1) based on the cooling capacity of the motor. 0: Disabled 1: Standard Fan Cooled Motor Overload Protection L1-01 Page 32 of 48

33 Appendix 3- Cross Reference GPD506/P5 P7 Param Nxxx Param. 035 Cooling fin overheat Stop method selection 0: Deceleration stop (Decelerate by deceleration time 1) 1: Coast to stop 2: Deceleration stop (Decelerate by deceleration time 2) 3: Operation continues (The alarm is displayed, and drive runs at 80% of the freq ref) Drive Operation upon OH Pre Alarm Detection. 0: Ramp to Stop (Decel Time C1-02). 1: Coast to Stop 2: Fast-Stop (Decel Time = C1-09). 3: Alarm Only *0 to 2 is recognized as fault detection, and 3 is recognized as alarm. (For the fault detection, the fault contact operates.) 4: OH Alarm & Reduce (Continue operation and reduce output frequency by L8-19) Overheat Pre-Alarm Operation L Multi-function contact input 1 (terminal S2) 037 Multi-function contact input 2 (terminal S3) 0: REV command (2wire sequence selection) 1: FWD/REV Command (3wire sequence selection) 2: External fault. (N.O contact input) 3: External fault. (N.C contact input) 4: Fault reset 5: LOCAL/REMOTE switch (run and freq ref) 6: Communication/Control circuit terminal switch (run and freq ref) 7: Emergency stop (N.O. contact input) 8: Emergency stop (N.C contact input) 9: FV/FI terminal switch 10: Multistep speed set 1 11: Multistep speed set 2 12: Multistep speed set 3 13: Jog frequency select 14: Accel/decel time switch 15: External base block instruction (N.O.contact input) 16: External base block instruction (N.C contact input) 17: Speed search command from Max frequency 18: Speed search command from set frequency 19: set enable/disable 20: PID integral value reset 21: PID control disable 22: Timer start command 23: Inverter overheat (blinking display of OH3) 24: Sample/holding of analog reference 25: KEB instruction (N.O. contact) 26: KEB instruction (N.C. contact) 27: Decel/accel prohibit 28: PID input characteristic switchover Set range: 2-28 (It is the same as constant n036) 0 to 70 Selects the function of terminal S3. 0: 3-wire control FWD/REV selection for 3-wire sequence 1: Local/Remote Sel Hand/Auto - Closed = Hand, Open = Auto 2: Option/Inv Sel Selects source of speed command and sequence Closed = Option Card, Open = b1-01 & b1-02 3: Multi-Step Ref 1 Closed = speed command from d1-02 or Terminal A2, Open = speed command determined by b1-01 4: Multi-Step Ref 2 Closed = speed command from d1-03 or d1-04 Open speed command determined by b1-01 Terminal S2 is not programmable in P7 : P7 default setting for terminal S2: Reverse run when closed, stopped when open. Initialization parameter A1-03 programs terminals S1 and S2 for 2-Wire or 3-Wire run control. Multi-Function Digital Input Terminal S3 Function - H1-01 Page 33 of 48

34 Appendix 3- Cross Reference Param Nxxx (con t) 037 GPD506/P5 Multi-function contact input 2 (terminal S3) Set range: : Jog Freq Ref Closed = speed command from d1-17 Open = speed command determined by b1-01 7: Multi-Acc/Dec 1 Closed = Accel & Decel Ramps determined by C1-03 & C1-04, Open = Accel & Decel Ramps determined by C1-01 & C1-02 8: Ext BaseBlk N.O. Closed = Output transistors forced off, Open = Normal operation 9: Ext BaseBlk N.C. Closed = Normal Operation, Open = Output transistors forced off A: Acc/Dec RampHold Closed = Acceleration suspended and speed held, Open = Normal Operation C: Term A2 Enable Closed = Terminal A2 is active, Open = Terminal A2 is disabled F: Term Not Used Terminal has no effect 10: MOP Increase Closed = Speed Command Increases, Open = Speed Command Held. Must be set in conjunction with MOP Decrease and b1-02 must be set to 1. 11: MOP Decrease Closed = Speed Command Decreases, Open = Speed Command Held. Must be set in conjunction with MOP Increase and b1-02 must be set to 1. 12: Forward Jog Closed = drive runs forward at speed command entered into parameter d : Reverse Jog Closed = drive runs in reverse at speed command entered into parameter d : Fault Reset Closed = Resets the drive after the fault and the run command have been removed. 15: Fast-Stop N.O. Closed = Drive decelerates using C1-09, regardless of run command status. 17: Fast-Stop N.C. Closed = Normal operation Open = Drive decelerates using C1-09, regardless of run command status. Closed = Normal operation Open = Drive decelerates using C1-09, regardless of run command status. 18: Timer Function Input for independent timer, controlled by b4-01 and b4-02. Used in conjunction with a multi-function digital output. 19: PI Disable Turns off the PI controller, and PI setpoint becomes speed command. 1B: Program Lockout Closed =All parameter settings can be changed. P7 Multi-Function Digital Input Terminal S3 Function Param. H1-01 Page 34 of 48

35 Appendix 3- Cross Reference Param Nxxx (con t) 037 GPD506/P5 Multi-function contact input 2 (terminal S3) Set range: 2-28 (It is the same as constant n036) Open = Only speed command at U1-01 can be changed. 1C: TrimCtl Increase Closed = Increase motor speed by value in d4-02. Open = Return to normal speed command. Not effective when using d1-01 thru d1-04 as a speed command. Must be used in conjunction with Trim Ctrl Decrease. 1D: Trim Ctl Decrease Closed = Decrease motor speed by value in d4-02 Open = Return to normal speed command. Not effective when using d1-01 thru d1-04 as speed command. Must be used in conjunction with Trim Ctrl Increase. 1E: Ref Sample Hold Analog speed command is sampled then held at time of input closure. 20: External fault, Normally Open, Always Detected, Ramp To Stop 21: External fault, Normally Closed, Always Detected, Ramp To Stop 22: External fault, Normally Open, During Run, Ramp To Stop 23: External fault, Normally Closed, During Run, Ramp To Stop 24: External fault, Normally Open, Always Detected, Coast To Stop 25: External fault, Normally Closed, Always Detected, Coast To Stop 26: External fault, Normally Open, During Run, Coast To Stop 27: External fault, Normally Closed, During Run, Coast To Stop 28: External fault, Normally Open, Always Detected, Fast-Stop 29: External fault, Normally Open, Always Detected, Fast-Stop 2A: External fault, Normally Open, During Run, Fast-Stop 2B: External fault, Normally Closed, During Run, Fast-Stop 2C: External fault, Normally Open, Always Detected, Alarm Only 2D: External fault, Normally Closed, Always Detected, Alarm Only 2E: External fault, Normally Open, During Run, Alarm Only 2F: External fault, Normally Closed, During Run, Alarm Only 30: PI Integral Reset Resets the PI Integral component to zero when closed 31: PI Integral Hold Holds the PI integral value when closed 34: PI SFS Cancel (SFS= SoftStart, also called Accel/Decel, See b5-17) 35: PI Input Level Sel Inverts the PI error signal when closed 36: Option/Inv Sel 2 Selects source of speed command and sequence Closed = b1-01 & b1-02, Open = Option Card P7 Multi-Function Digital Input Terminal S3 Function Param. H1-01 Page 35 of 48

36 Appendix 3- Cross Reference GPD506/P5 P7 Param Nxxx Param. (con t) 037 Multi-function contact input 2 (terminal S3) Set range: 2-28 (It is the same as constant n036) 60: Motor Preheat Applies current to create heat to avoid condensation Closed = Apply amount of current as set in parameter b : Speed Search 1 When closed as a run command is given, drive does a speed search starting at maximum frequency (E1-04). 62: Speed Search 2 When closed as a run command is given, drive does a speed search starting at speed command. 64: Speed Search 3 When opened, the Drive performs a baseblock (motor coasts). When closed, the Drive performs Speed Search from set frequency. 67: Com Test Mode - Used to test RS- 485/422 interface. 68: High Slip Braking - Closed = Drive stops using High Slip Braking regardless of run command status. 69: Jog2 - Closed = Drive runs at speed command entered into parameter d1-17. Direction determined by fwd/rev input. 3-wire control Only. 6A: Drive Enable - Closed = Drive will accept run command. Open = Drive will not run. If running, drive will stop per b1-03. Run Command must be cycled 6B: Com/Inv Sel - Selects source of Speed Command and Sequence. Closed = Serial Communication (R+,R-,S+,S-), Open = b1-01 & b1-02 6C: Com/Inv Sel 2 - Selects source of Speed Command and Sequence. Closed = b1-01 & b1-02, Open = Serial Communication (R+,R-,S+,S-) 6D: Auto Mode Sel - Hand/Auto - Closed = Auto, Open = Hand 6E: Hand Mode Sel - Hand/Auto - Closed = Hand, Open = Auto 70: Drv Enbl. Same as 6A except a run command is accepted Multi-Function Digital Input Terminal S3 Function H Multi-function contact input 3 (terminal S4) 039 Multi-function contact input 4 (terminal S5) 040 Multi-function contact input 5 (terminal S6) Set range: 2-28 (It is the same as constant n036) Set range: 2-28 (It is the same as constant n036) 0-70 Same selections as H Same selections as H1-01 Set range: Same selections as H1-01 Multi-Function Digital Input Terminal S4 Function Multi-Function Digital Input Terminal S5 Function Multi-Function Digital Input Terminal S6 Function H1-02 H1-03 H1-04 Page 36 of 48

37 Appendix 3- Cross Reference Param Nxxx GPD506/P5 041 Multi-function contact output 1 (terminal MA-MB-MC) 0: Fault 1: During run. 2: Frequency agree 3: At set frequency agree 4: Freq detect (output freq = set freq detection level) 5: Freq detect (output frequency = set freq detect level) 6: Overtorque detect. (N.O contact) 7: Overtorque detect. (N.C contact) 8: The base block. 9: Operation mode 10: Inverter drive ready 11: Timer function 12: Auto restart. (Fault retry) 13: OL pre-alarm (OL1,OL2) 14: Frequency reference loss 15: Closed from serial communication. 16: PID feedback loss 17: OH1 alarm Selects the function of terminals M1 to M4. 0: During RUN 1 = Closed when a run command is input or the drive is outputting voltage. 1: Zero Speed = Closed when drive output frequency is less than Fmin (E1-09) 2: Fref/Fout Agree 1 = Closed when drive output speed equals the speed command within the bandwidth of L : Fref/Set Agree 1 = Closed when the drive output speed and the speed command are equal to the value in L4-01 within the bandwidth of L : Freq Detect 1 = Closed when the drive output speed is less than or equal to the value in L4-01, with hysteresis determined by L : Freq Detect 2 = Closed when the drive output speed is greater than or equal to the value in L4-01, with hysteresis determined by L : Inverter Ready = Closed when the drive is not in a fault state, and not in program mode. 7: DC Bus Undervolt = Closed when the DC bus voltage falls below the UV trip level (L2-05) 8: Base Blk 1 = Closed when the drive is not outputting voltage. 9: Operator Reference = Closed when the speed command is coming from the digital operator. A: Remote/Auto Oper = Closed when the run command is coming from the digital operator. B: Trq Det 1 N.O. - Closes when the output current exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03. C: Loss of Ref - Closes when the drive has detected a loss of analog speed command. Speed command is considered lost when it drops 90% in 0.4 seconds. L4-05 determines drive reaction to a loss of speed command. E: Fault - Closes when the drive experiences a major fault. F: Not Used 10: Minor Fault - Closes when drive experiences a minor fault or alarm. 11: Reset Cmd Active - Closes when the drive receives a reset command from terminals or serial comms. 12: Timer Output - Output for independent timer, controlled by b4-01 and b4-02. Used in conjunction with a multi-function digital input. 17: Trq. Det 1 N.C. - Opens when the output current exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03. P7 Terminal M3-M4 Function Param. H2-01 Page 37 of 48

YASKAWA AC Drive. P7 to P1000 Product Transition Guide

YASKAWA AC Drive. P7 to P1000 Product Transition Guide TM YASKAWA AC Drive P7 to P1000 Product Transition Guide Type: CIMR-P7U Models: 200 V Class, Three-Phase Input: 1/2 to 150 HP 400 V Class, Three-Phase Input: 1/2 to 500 HP Type: CIMR-PU Models: 200 V Class,

More information

GS1 Parameter Summary Detailed Parameter Listings...4 9

GS1 Parameter Summary Detailed Parameter Listings...4 9 CHAPTER AC DRIVE 4 PARAMETERS Contents of this Chapter... GS1 Parameter Summary...............................4 2 Detailed Parameter Listings..............................4 9 Motor Parameters.........................................4

More information

G+ Mini Transition Guide. Product Transition Guide P3 Series 2 to G+ Mini

G+ Mini Transition Guide. Product Transition Guide P3 Series 2 to G+ Mini Transition Guide Product Transition Guide to Rev: Page Intentionally Left Blank Transition Guide September 2008 Page 2 of 24 Table of Contents 1.1 Overview...4 1.2 Drive Replacement Checklist...4 1.3 Ratings

More information

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER AC DRIVE PARAMETERS. In This Chapter... CHAPTER AC DRIVE 4 PARAMETERS In This Chapter... GS2 Parameter Summary....................4 2 Detailed Parameter Listings.................4 11 Motor Parameters........................4 11 Ramp Parameters.........................4

More information

TOSVERT TM VF-nC3 Parameter List

TOSVERT TM VF-nC3 Parameter List TOSVERT TM VF-nC Parameter List E658664 - Setting information * Please fill it in if necessary. Item Content Item Content Setting date / person Customer Application Application model Motor manufacturer

More information

PL.F7.02.Transition Guide. Product Transition Guide GPD 515/G5 to F7

PL.F7.02.Transition Guide. Product Transition Guide GPD 515/G5 to F7 PL.F7.02.Transition Guide GPD 515/G5 to F7 GPD515/G5 to F7 NOTICE The information contained within this document is the proprietary property of., and may not be copied, reproduced or transmitted to other

More information

ADJUSTABLE SPEED DRIVES FS1

ADJUSTABLE SPEED DRIVES FS1 ADJUSTABLE SPEED DRIVES FS1 Now Available With LonWorks BACnet & MetasysN2 FS1 Model FLA & Dimensions (in.)/ Weight (lbs.) VOLTAGE HP MODEL NUMBER FLA FRAME Dimensions (in.) SHIPPING H W D WEIGHT (lbs.)

More information

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class HITACHI L1-M Series Inverter Quick Reference Guide Single-phase Input 1V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5741XD December 23 Caution: Be sure to read the L1 Inverter Manual

More information

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

Fan and Pump AC Inverter

Fan and Pump AC Inverter Fan and Pump AC Inverter Key Features for Fan and Pump Applications PID and Auto Energy Saving Functions. Input Phase Loss and Output Phase Loss Protection. LCD Keypad can be used to copy parameter settings

More information

E3 Adjustable Speed Drive Engineering Specification

E3 Adjustable Speed Drive Engineering Specification E3 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba E3 AC Variable Frequency Drives, 6 pulse for 230V and 460V. 1.1 References A. National

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class HITACHI SJ1 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5821XD Dec.

More information

ADJUSTABLE SPEED DRIVES. AS1 Drive

ADJUSTABLE SPEED DRIVES. AS1 Drive ADJUSTABLE SPEED DRIVES AS1 Drive Toshiba s New ASD Product Line The AS1 drive builds on Toshiba s history of supplying powerful, reliable, and versatile drives. We have combined our best drive features

More information

Inverter Drive /Vector Drive Motors & Controls

Inverter Drive /Vector Drive Motors & Controls H2 Inverter/ Encoderless Vector Inverter Drive /Vector Drive & Controls 3/4 thru 50 180-264 VAC 3 Phase - 50/60 Hz 3/4 thru 60 340-528 VAC 3 Phase - 50/60 Hz 3/4 thru 60 515-660 VAC 3 Phase - 60 Hz HVAC

More information

VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC )

VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC ) VS-616G5 Series (Revision F) Programming Manual Constant Torque Inverter with Adaptive Control (AVC ) ! WARNING PRECAUTIONS NOTICE 1) Only turn ON the input power supply after replacing the front cover.

More information

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual INDEX A AC Drive Cover: 1 6 Dimensions: 2 4 External Parts and Labels: 1 6 Heat Sink Fins: 1 6 Input Mode Switch (Sink/Source): 1 6 Introduction to DuraPulse GS3 AC drive: 1 3 Keypad: 1 6 Model Number

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information

AV-300i Specifications. Saftronics Inc. VG10 Product Specifications VG10. Dynamic Vector Drive

AV-300i Specifications. Saftronics Inc.   VG10 Product Specifications VG10. Dynamic Vector Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications VG10 Product Specifications VG10 Dynamic Vector Drive 1 Category Item Description Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3

More information

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Variable Frequency Drive / Inverter (0.4 ~ 280kW) Variable Frequency Drive / Inverter (0.4 ~ 280kW) & Standard Features Configuration Comparison Comparison Table Enclosure IP00 IP20 NEMA 1 Rating Single phase 0.4 2.2kW 0.4 1.5kW Three phase 0.4 4kW Constant

More information

Multi-function, Compact Inverters. 3G3MV Series

Multi-function, Compact Inverters. 3G3MV Series Multi-function, Compact Inverters 3G3MV Series There has been a great demand for inverters with more functions and easier motor control than conventional i OMRON's powerful, compact 3G3MV Series with versat

More information

General Specifications FECA-TE /2010. Phone: Fax: Web:

General Specifications FECA-TE /2010. Phone: Fax: Web: General Specifications FECA-TE-117 06/2010 1. Standard Specifications 1) Three-phase 230V series Output ratings Input ratings Braking Item Specifications Type (FRN C1S-2U) F12 F25 F50 001 002 003 005 Nominal

More information

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps.

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps. VFD - D700 Series Specifications The latest low-cost variable speed control solution for centrifugal pumps. Built-in PID Control to maintain pressure, flow, measured value, and much more 125% overload

More information

VS-616PC5/P5 Series User s Manual

VS-616PC5/P5 Series User s Manual VS-616PC5/P5 Series User s Manual Variable Torque Inverter PRECAUTIONS! WARNING 1) Read this manual in its entirety before installing or operating the VS- 616PC5/P5 inverter. 2) Do not connect or disconnect

More information

VFS11 Parameter List for up to CPU version 105

VFS11 Parameter List for up to CPU version 105 E65824 VFS Parameter List for up to CPU version 5 Setting Date Customer End user Application Application No/Serial No Inverter s Type-Form Quantity Inverter s Serial No Motor s capacity If user s value

More information

NX series Constant and variable torque Variable Speed Drives for induction motors

NX series Constant and variable torque Variable Speed Drives for induction motors Honeywell All in One Application Manual NX series Constant and variable torque Variable Speed Drives for induction motors Subject to changes without notice CONTENTS NX "All in One" APPLICATION MANUAL INDEX

More information

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R INVERTER ROLL TO ROLL FUNCTION MANUAL FR-A820-00046(0.4K)-04750(90K)-R2R FR-A840-00023(0.4K)-06830(280K)-R2R FR-A842-07700(315K)-12120(500K)-R2R Roll to Roll Function The FR-A800-R2R inverter has dedicated

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

AF91 Adjustable Frequency Drives Series B

AF91 Adjustable Frequency Drives Series B Effective: January, 00 Page New Information AF9 Adjustable Model AF9 Description Model AF9 Adjustable Frequency AC Drives are designed to provide adjustable speed control of -phase motors. These microprocessor-based

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

vacon nx all in one application manual ac drives Phone: Fax: Web: -

vacon nx all in one application manual ac drives Phone: Fax: Web:  - vacon nx ac drives all in one application manual vacon 1 INDEX Document ID:DPD00903A Revision release date: 30.3.2012 1. Basic Application...5 1.1. Introduction...5 1.1.1. Motor protection functions in

More information

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric ADJUSTABLE SPEED DRIVES VF-S11 The Next Generation of Micro Inverters is Here. The S11 provides maximum torque with precise speed control. It features an easy-to-use, quiet and compact design. In addition,

More information

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse ADJUSTABLE SPEED DRIVES W7 Series 18 Pulse Meets or Exceeds Your Specifications Standard Specifications Item Voltage Class 460V Maximum HP 60 75 100 125 150 200 250 300 400 500 600 700 800 Drive Rating

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web: -

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web:  - ADJUSTABLE SPEED DRIVES HX7 Series 18 Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

Phoenix DX Clean Power (18 Pulse) AC Drive

Phoenix DX Clean Power (18 Pulse) AC Drive PHOENIX DX Phoenix DX Clean Power (18 Pulse) AC Drive Poor power quality can be costly. Nonlinear loads, including AC Drives, introduce undesirable harmonic currents into the power system that can damage

More information

6.9 Jump frequency - Avoiding frequency resonance

6.9 Jump frequency - Avoiding frequency resonance E581595.9 Jump frequency - Avoiding frequency resonance : Jump frequency : Jumping width Function Resonance due to the natural frequency of the mechanical system can be avoided by jumping the resonant

More information

CHAPTER 8 PARAMETER SUMMARY

CHAPTER 8 PARAMETER SUMMARY CHAPTER PARAMETER SUMMARY Group 0: System Parameter VFD-V Series 00-00 Identity Code Based on the model type 00-01 Rated Current Display 00-02 Parameter Reset 00-03 00-04 Star-up Display of the Drive Definitions

More information

BACnet- MS/TP COMMUNICATION V

BACnet- MS/TP COMMUNICATION V - MS/TP COMMUNICATION V1.00.08.17 11.1 Introduction The VFD can be controlled and monitored through the BACnet MS/TP protocol over an RS-485 connection. The VFD operates as an MS/TP master device, which

More information

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Inverter STARVERT ig5a LS Starvert ig5a is very competitive in its price

More information

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL D SERIES LM16 COMPACT DRIVE V/f and SLV CONTROL LM16 COMPACT DRIVE V/f and SLV CONTROL 1 2 SERIES 1 2 page 4 page 6 Introduction Fields of application 3 page 7 4 page 8 Designation Product offer 5 6 page

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

Design Specifications Operator Keypad Environmental and Operating Conditions

Design Specifications Operator Keypad Environmental and Operating Conditions Series 15J Mini Inverters Big inverter features do come in small packages! Take a look at Baldor s Series 15J Inverter control. Designed to save cabinet space without giving up the features available on

More information

MagneTek. GPD 503 Technical Manual

MagneTek. GPD 503 Technical Manual MagneTek GPD 503 Technical Manual GPD 503 SIMPLIFIED START-UP PROCEDURE This procedure will quickly get you up and running by Digital Operator keypad or user supplied remote operator control. It assumes

More information

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE 1 2 SERIES 1 2 pag. 4 pag. 5 Applications Model identification 3 pag. 5 4 pag. 6 Capacity

More information

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters. ~ ~ SX High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse ADJUSTABLE SPEED DRIVES HX7 Series 18-Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives Page 2 (68) Index Honeywell HVAC Application (Software [ALFIQ105] Ver.2.09) INDEX 1. INTRODUCTION... 3 2. CONTROL I/O... 3. HVAC APPLICATION

More information

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control NEW FIRMWARE MAKES SETUP A SNAP Application based commissioning allows parameters

More information

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81)

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81) BOSTON GEAR CONTROLLERS ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers ACE 20 Series Offering full-featured control in high torque, low speed applications from 1/8 to 10 HP,

More information

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS CHAPTER 8 SUMMARY OF PARAMETER SETTINGS VFD-S Series!: The parameter can be set during operation, *: Twice the value for 460V class. Group 0 User Parameters Parameters Explanation s 0-00 Identity Code

More information

Enhanced PID for Air Compressors F7 Drive Software Technical Manual

Enhanced PID for Air Compressors F7 Drive Software Technical Manual Software Number: VSF11020X, Drive Models: CIMR-F7UXXXXXX-096 Document Number: TM.F7SW.096, Date: 08/01/05, Rev: 05-08 Enhanced PID for Air Compressors F7 Drive Software Technical Manual This document is

More information

PowerFlex 400 Submittal

PowerFlex 400 Submittal PowerFlex 400 Submittal Submittal Date: Project Name: Project Location: Consulting Engineer: Contractor: Contractor PO #: Distributor Name: Distributor Contact: Distributor Reference #: Note: This is general

More information

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6 CHAPTER KEYPAD OPERATION 3 AND QUICKSTART In This Chapter... The GS2 Digital Keypad.....................3 2 LED Display.........................................3 2 LED Indicators.......................................3

More information

VFS9 Parameter List for Version110 or later

VFS9 Parameter List for Version110 or later VFS9 Parameter List for Version110 or later Setting Date Customer End user Application Application /Serial Inverter s Type-Form Quantity Inverter s Serial Motor s capacity If user s value is same as shipping

More information

616 PC5 Instruction Manual

616 PC5 Instruction Manual 66 PC5 Instruction Manual Power Drive Services Ltd. Unit, Victoria St. Ind. Est. Leigh, WN7 5SE UK Tel +44 (0)942 260206 Fax +44 (0)942 260525 www.inverter.co.uk GPD 505 SIMPLIFIED START-UP PROCEDURE This

More information

AV-300i Specifications. Saftronics Inc. PC10 Product Specifications PC10. Mini Vector AC Drive

AV-300i Specifications. Saftronics Inc.  PC10 Product Specifications PC10. Mini Vector AC Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications PC10 Product Specifications PC10 Mini Vector AC Drive 1 (1) T hree-phas e 230V input Drive Hp 1/8 1/4 1/2 1 2 3 5 7.5 10 Nominal applicable

More information

Manual Overview...1 2

Manual Overview...1 2 GETTING STARTED CHAPTER 1 Contents of this Chapter... Manual Overview.....................................1 2 Overview of this Publication..................................1 2 Who Should Read This Manual...............................1

More information

ACH550 HVAC Drive Submittal

ACH550 HVAC Drive Submittal ACH550 HVAC Drive Submittal DATE: PROJECT NAME: CONTRACTOR: ENGINEER: SUBMITTED BY: SUBMITTALS FOR: RECORD APPROVAL (Return a copy of the approved submittal) ACH550 Features Standard Features UL and cul

More information

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1 SV9000 Page 0-1 SV9000 SVReady USER MANUAL CNTENTS A General...0-2 B Application selection...0-2 C Restoring default values of application parameters...0-2 D Language selection...0-2 1 Standard Control

More information

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE NOTICE 1. Read this manual thoroughly before using the VT210S, and store in

More information

SX (400V) System configuration

SX (400V) System configuration ~ ~ SX (400V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts iga Compact AC Drive ~1.kW(0.~2HP) 1-phase 200~230Volts ~22kW(0.~30HP) 3-Phase 200~230Volts ~22kW(0.~30HP) 3-Phase 380~480Volts Drive STARVERT iga LS Starvert iga is very competitive in its price and shows

More information

The new Yaskawa Varispeed G7 Inverter

The new Yaskawa Varispeed G7 Inverter The new Yaskawa Varispeed G7 Inverter Unique new 3-level PWM flux vector Constant or variable torque applications control method 0.4 kw to 300 kw power range Exceptional low speed/high torque control Quick

More information

AF-300 G11 Specifications. GE Industrial Systems. Product Specifications AF-300 G11

AF-300 G11 Specifications. GE Industrial Systems. Product Specifications AF-300 G11 apple GE Industrial Systems Product Specifications AF-300 G11 TM 1 Category Item Description Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3 Phase 1/2 Hp to 450 Hp Braking Torque (Standard)

More information

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive Compact & Powerful Drive iga ~1.kW (0.~2HP) 1phase 200~230Volts ~22kW (0.~30HP) 3Phase 200~230Volts ~22kW (0.~30HP) 3Phase 380~480Volts Drive Starvert iga LS Starvert iga is very competitive in its price

More information

SUPPLEMENTAL MANUAL COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL)

SUPPLEMENTAL MANUAL COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL) VS-66V7 Series SUPPLEMENTAL MANUAL COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL) Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for

More information

SX (400 V) System configuration

SX (400 V) System configuration ~ ~ SX (400 V) High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

SX (690 V) System configuration

SX (690 V) System configuration SX (690 V) High performance Vector Control IP54 full range Compact design & Robustness Built-in Filter according to C3 Class Built-in Fuses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

KBDA SERIES STANDARD FEATURES DESCRIPTION PERFORMANCE FEATURES PROTECTION FEATURES

KBDA SERIES STANDARD FEATURES DESCRIPTION PERFORMANCE FEATURES PROTECTION FEATURES KBDA SERIES ADJUSTABLE FREQUENCY DRIVES FOR 3-PHASE AC MOTORS NEMA-4X / IP-65 Washdown and Watertight for Indoor and Outdoor use MULTI-FUNCTION KEYPAD WITH 4-DIGIT LED DISPLAY Simplified Group Programming

More information

Multi-purpose Control Application II

Multi-purpose Control Application II VACON CX /CXL/CXS FREQUENCY CONVERTERS Multi-purpose Control Application II USER'S MANUAL Subject to changes without notice Vacon Page 1 Multi-purpose Control Application II (par. 0.1 = 0) CONTENTS 1 General...

More information

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS CHAPTER DESCRIPTION OF PARAMETER SETTINGS.1 Group 0: User Parameters 0-00 Identity Code of AC Drive Factory setting: d# Settings None V HP 1/4 1/2 1 2 3 11V/230V d0 d2 d4 d6 d8 460V -- -- -- d3 d d7 d9

More information

Operation Instructions NORDAC SK 400E. Frequency Inverter. SK 400E B / SK 400E B (0.4kW / 0.7kW, 1~ 115V)

Operation Instructions NORDAC SK 400E. Frequency Inverter. SK 400E B / SK 400E B (0.4kW / 0.7kW, 1~ 115V) NORDAC SK4E Safety Instructions Operation Instructions NORDAC SK 4E Frequency Inverter SK 4E-2-111-B / SK 4E-4-111-B (.4kW /.7kW, 1~ 115V) SK 4E-2-123-B... SK 4E-151-323-B (.2kW 1.5kW, 1/3~ 23V, 3~ 23V)

More information

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive... CHAPTER KEYPAD OPERATION 3 AND QUICKSTART Contents of this Chapter... The GS1 Digital Keypad................................3 2 LED Display..............................................3 2 Function Keys............................................3

More information

vacon nx ac drives all in one application manual

vacon nx ac drives all in one application manual vacon nx ac drives all in one application manual PREFACE VACON 3 PREFACE Document ID: DPD00903F Date: 14.8.2017 Software code: Basic Application = ASFIFF01 Standard Application = ASFIFF02 Local/Remote

More information

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life.

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life. ! Warning!! 1. Please read this manual completely before installing the drive. 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life. 3. Be sure

More information

PID Software Kit. Part No. SK-PID1-L503. For GPD 503 Adjustable Frequency Drives CT: 1-30HP, 230V; 1-60HP, 460V VT: 1-40HP, 230V; 1-75HP, 460V

PID Software Kit. Part No. SK-PID1-L503. For GPD 503 Adjustable Frequency Drives CT: 1-30HP, 230V; 1-60HP, 460V VT: 1-40HP, 230V; 1-75HP, 460V PID Software Kit Part No. SK-PID-L53 For GPD 53 Adjustable Frequency Drives CT: -3HP, 23V; -6HP, 46V VT: -4HP, 23V; -75HP, 46V DESCRIPTION The PID Software Kit consists of two EPROMs and this instruction

More information

Micro and Mini Inverters

Micro and Mini Inverters Micro and Mini Inverters Why Baldor? For over 85 years, Baldor has strived to provide customers with the best value and reliability in industrial electric motors. That dedication shows in customer preference

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives 3.0 50HP @ 200 to 240V AC 3.0 350HP @ 380 to 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum

More information

For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications:

For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications: Product Overview Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley PowerFlex 4 and 40 AC drives are the smallest and most cost-effective members of

More information

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control. Section 16680 VARIABLE SPEED DRIVE SYSTEMS OR AFD Part I - GENERAL I.01 Description A. This specification is to cover a complete adjustable frequency motor drive consisting of a pulse width modulated (PWM)

More information

Yaskawa Electric America Unit Troubleshooting Manual Section Two: Power Checks GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW)

Yaskawa Electric America Unit Troubleshooting Manual Section Two: Power Checks GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW) Yaskawa Electric America Unit Troubleshooting Manual Section Two: Power Checks GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW) Page 1 Section Two: Power Checks Page 2 Check box when completed Power Checks TEST

More information

Before you operate the inverter, the parameters that you must first program are the basic parameters.

Before you operate the inverter, the parameters that you must first program are the basic parameters. . Main parameters Before you operate the inverter, the parameters that you must first program are the basic parameters..1 Searching for changes using the history function () : History function History

More information

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE NOTICE 1. Read this manual thoroughly before using the VT110S, and store in

More information

VLT MICRO Series Adjustable Frequency Drive Instruction Manual

VLT MICRO Series Adjustable Frequency Drive Instruction Manual VLT MICRO Series Adjustable Frequency Drive Instruction Manual 1/00 23-6127-00 Revision DR 2 Table of Contents Chapter 1 Chapter 2 Chapter 3 Introduction Getting Started... 5 Receiving, Inspection, and

More information

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD.

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD. RYKO Manufacturing Company 116 N.W. 54th Ave. P.O.Box 38 Grimes, Iowa 5111 Phone (515) 986-37 www.ryko.com Fax (515) 986-3621 sales@ ryko.com INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+

More information

Caution. Three-phase 400V series FRN0.4C1S-4A FRN0.75C1S-4A FRN1.5C1S-4A FRN2.2C1S-4A FRN3.7C1S-4A

Caution. Three-phase 400V series FRN0.4C1S-4A FRN0.75C1S-4A FRN1.5C1S-4A FRN2.2C1S-4A FRN3.7C1S-4A Variation Caution The contents of this catalog are provided to help you select the product model that is best for you. Before actual use, be sure to read the User s Manual thoroughly to assure correct

More information

SYSDRIVE 3G3XV Inverter 3G3XV- -EV2 Operation Manual

SYSDRIVE 3G3XV Inverter 3G3XV- -EV2 Operation Manual SYSDRIVE 3G3XV Inverter 3G3XV- -EV2 Operation Manual Revised November 1997 iv Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes

More information

vacon nxs robust drive for heavy use

vacon nxs robust drive for heavy use vacon nxs robust drive for heavy use the reliable choice The Vacon is a compact AC drive in the power range of 0.7 560 kw and supply voltages of 208 690 V for heavy use in machines, buildings and all branches

More information

Industrial Inverter for Fan and Pump. STARVERT ip5a. 5.5~30kW(7.5~40HP) 3Phase 200~230Volts 5.5~450kW(7.5~600HP) 3Phase 380~480Volts.

Industrial Inverter for Fan and Pump. STARVERT ip5a. 5.5~30kW(7.5~40HP) 3Phase 200~230Volts 5.5~450kW(7.5~600HP) 3Phase 380~480Volts. Industrial Inverter for Fan and Pump STARVERT ip5a 5.5~30kW(7.5~40HP) 3Phase 200~230Volts 5.5~450kW(7.5~600HP) 3Phase 380~480Volts Drive Solution STARVERT ip5a LS Starvert ip5a is basically created for

More information

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/ QUICK GUIDE PUMP CONTROL High performance Compact Inverter Date Version 22/9/29 1..3 Version Details Date Written Checked Approved 1.. Draft J. M. Ibáñez J. Català 1..1 Second Version 17/9/29 J. M. Ibáñez

More information

Operating Instructions

Operating Instructions 4XH35QB151210 Small General Frequency Converter Operating Instructions 220V 0.75KW 5.5KW 400V 0.75KW 15KW Please read the instruction carefully and understand the contents so that it can be installed and

More information

user's manual nx frequency converters beam pump application asfiff13

user's manual nx frequency converters beam pump application asfiff13 user's manual nx frequency converters beam pump application asfiff13 2 vacon Introduction INDEX 1. Introduction... 3 2. Commissioning... 4 2.1 Commissioning unbalanced load... 4 2.2 Commissioning balanced

More information

Version number A=standard P=Cold Plate (Frame A only) T=Brake chopper (Frame A only) Input voltage 11=115VAC 21=230VAC 1φ 23=230VAC 3φ 43=400VAC

Version number A=standard P=Cold Plate (Frame A only) T=Brake chopper (Frame A only) Input voltage 11=115VAC 21=230VAC 1φ 23=230VAC 3φ 43=400VAC Type number key VFD 007 E 43 A Version number A=standard P=Cold Plate (Frame A only) T= (Frame A only) Input voltage 11=115VAC 21=230VAC 1φ 23=230VAC 3φ 43=400VAC VFD-E series Power 007=0.75kW 022=2.2kW

More information

VS-616PS5 Series Installation & Quick-start Manual

VS-616PS5 Series Installation & Quick-start Manual VS-66PS5 Series Installation & Quick-start Manual Brushless Motor Drive WARNING YASKAWA manufactures component parts that can be used in a wide variety of industrial applications. The selection and application

More information

PRODUCT OFFERING ADJUSTABLE SPEED DRIVES

PRODUCT OFFERING ADJUSTABLE SPEED DRIVES PRODUCT OFFERING ADJUSTABLE SPEED DRIVES ONE CALL. ONE SOLUTION. Toshiba International Corporation is proud to be a single-source solution for our customers, offering a complete product lineup of electric

More information

Bypass Panels FRENIC-EcoPAK. Fuji Electric Corp. of America FECA-IN-105 / Information subject to change without notice.

Bypass Panels FRENIC-EcoPAK. Fuji Electric Corp. of America FECA-IN-105 / Information subject to change without notice. Instruction Manual Bypass Panels FRENIC-EcoPAK Fuji Electric Corp. of America FECA-IN-105 / 122010 Information subject to change without notice. Safety Precautions Read this manual thoroughly before proceeding

More information

Installation, Programming Operation, & Maintenance Manual V

Installation, Programming Operation, & Maintenance Manual V Base Drive, Bypass Drive, Drive with Disconnect 200~480V (3~28A) Q-Link Manual Fan & Pump Optimized Variable Frequency Drive Installation, Programming Operation, & Maintenance Manual V2.00.09.17 CAUTION,

More information

M-Max series drives. The next generation of OEM drives

M-Max series drives. The next generation of OEM drives M-Max series drives The next generation of OEM drives Continue learning more about Eaton drives, services and solutions. Please visit us at: www.eaton.com/drives CD CONTENTS MaxConnect MaxLoader Firmware

More information