THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE

Size: px
Start display at page:

Download "THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE"

Transcription

1 MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE NOTICE 1. Read this manual thoroughly before using the VT210S, and store in a safe place for reference. 2. Make sure that this manual is delivered to the final user. MEIDENSHA CORPORATION QS210S Rev1 i Feb 2000

2 Warning This Quick Start Instruction Guide is intended as a guide only. Read the Instruction Manual thoroughly before using the VT210S. Use extreme caution during installation. Do not open the front cover while power is applied. Always ground the Inverter heatsink. If in doubt, refer to your supplier or MEIDEN DRIVELINE Tel: The information contained in this publication, including numerical data, has been prepared as a general guide to the product. No responsibility is assumed for errors herein. reserve the right to make changes to this document and Instruction Manual at any time. E&OE QS210S Rev 1 Page 1

3 Installation Install the Inverter vertically, so that the cable glands face downwards. Allow for the correct spacing around the Inverter for ventilation (X +>50mm, Y +>200mm). Fig. 1. Always ensure that the Inverter is switched off before wiring. Please note that TBA must be set in position shown (Fig. 2.) for V operation, and in position 1-2 for V operation. Connect wiring as shown in Fig. 2. Make sure that correct short circuit protection devices are fitted and best wiring practises are observed (see page 2-3 in the supplied manual). Fig.2. N.B. Terminal/Busbar arrangements differ on larger drives. (Refer to page 2-8 in the supplied manual). A Ferrite is supplied with the filter, which must be fitted to meet EMC compliance. The motor phase cables must be inserted through the output ferrite as per EMC Filter Kits Guide to Installation and Use. Voltage Surge For long motor cable lengths (>30m), a motor choke can be ordered which must be fitted between the Inverter and the motor. Motor cables must be screened at both ends. Connect inputs as shown in Fig. 3. or to suit your application. If using a potentiometer, connect the wiper to FSV terminal. Analogue signal cables MUST be screened. Connect one end of the screen to COM. The COM terminals are linked internally. RY0 is isolated and must NOT be connected to COM. (R RUN) (F JOG) (R JOG) Test Running the Drive Please note that VT210S drives are supplied either as Constant Torque or Variable Torque and cannot be changed by the user. Operating the drive type is identical in all other ways although maximum and minimum values of some parameters may vary. Default settings allow the basic running of the motor to prove the system, but first set: B00-1 set 31 assuming 415V, 50Hz B00-5 set motor rated current (A) supply, and max freq B00-4 Output Voltage may have requirement of 50Hz. to be set for non-standard motors. On power up, the Inverter display will cycle through a self-diagnostics check, and then show drive is in a ready state. confirming the Press FWD on the keypad and the motor will ramp up to 10Hz in a forward direction. The display will change from to ( local frequency setting A00-0). Press REV and check that the motor changes direction. Now press STOP, the motor will stop. Acceleration and Deceleration will be default values at this stage. QS210S Rev 1 Page 2

4 Configuration The Inverter parameter menu system is grouped into Modes and Blocks according to their functions and frequency of usage. To manoeuvre around the menu system, pressing the MOD key will change between the Monitor, A and B block parameters. Pressing the key will change through the parameters in that block. See Fig. 4. The display will alternate between the parameter number and its current value. Press SET to change the parameter value. Increase/decrease the value by using the and keys, and move to next digit by pressing the key. When you have set the parameter to the value you want, press SET. It is possible to reset to default values when the drive is not running, by setting parameter B06-3 to 9 (page 6-12). The parameter default values are such that the inverter can be quickly, and safely, checked after power on. However, some of the default values may need to be changed to suit specific applications. From default, only the Basic Function parameters can be accessed. Set parameter A05-0 from 2221 to 1111 to release further parameters blocks. Remote Running Fig.4. The inverter is set to run in Local (keypad) mode. With the drive display showing press STOP + LCL together to toggle between local and remote modes. From default settings, the inverter is set up to accept the following signal inputs: (page 6-11). FRUN Forward Run PSI1 Reverse Run RST Reset PSI2 Forward Jog EMS Emergency Stop ** PSI3 Reverse Jog FSV 0-10V signal reference ** by default is a normally open contact, coast to stop. Refer to manual (page 6-10) for options. Set B08-0 to 12 to power up in remote mode (page 6-16). If necessary, set new Accel/Decel times in A01-0 and A01-1 (page 6-3). Jog Accel/Decel can be set in B21-2 and B21-3 (page 6-21). Braking is set on from default. From default the signal reference is obtained from the 0-10V analogue input. This can be from a number of sources including a potentiometer as shown in Fig. 3. Torque Boost A02-0 Increase this value for loads with high Starting Inertia. (Refer to pages 6-3/6-6). QS210S Rev 1 Page 3

5 Setting Pre-set Speeds As well as running from 0-10V analogue reference, it is possible to set up to 8 pre-set speeds (plus Jog). Digital inputs PSI1-PSI5 can be programmed in a number of ways to suit the application. A worked example of using 10Hz, 13.20Hz, 25Hz, 40.32Hz and 50Hz pre-set speeds is shown below: Set B03-1 to 0 turns off F Jog Set B04-6 to 5 uses PSI5 as S2 Set B03-2 to 0 turns off R Jog Set B20-0 to Prog Freq 0-10Hz Set B04-2 to 2 uses PSI2 as PROG Set B20-1 to Prog Freq Hz to enable pre-set speeds Set B20-2 to Prog Freq 2-25Hz Set B04-4 to 3 uses PSI3 as S0 Set B20-3 to Prog Freq Hz Set B04-5 to 4 uses PSI4 as S1 Set B20-4 to 50 Prog Freq 4-50Hz Using inputs PSI3-PSI5 as binary inputs (see Fig. 5) it is possible to set any of the speeds. Please note that it is also possible to set independent accel/decel ramps to each pre-set speed. (Refer to B40-0, B41-x and B42-x on pages 6-37/6-40). Sequence Command Selected Frequency Prog S2 S1 S0 ON OFF OFF OFF Prog Freq 0-10Hz ON OFF OFF ON Prog Freq Hz ON OFF ON OFF Prog Freq 2-25Hz ON OFF ON ON Prog Freq Hz ON ON OFF OFF Prog Freq 4-50Hz ON ON OFF ON Prog Freq 5 - Unset ON ON ON OFF Prog Freq 6 - Unset ON ON ON ON Prog Freq 7 - Unset OFF ANY ANY ANY Analogue I/P Fig.5. Other Useful Features LCD Operator Panel - Upload/Download parameters, save 10 programs Contact you Supplier or for more information. Parameter (password) protection - B06-0 Pages 6-11/6-19 Programmable outputs - B05-0/2 Pages 6-11/6-18 Dynamic Braking - B80-1 Pages 7-3/7-4 Pattern Run - B5x-x Pages 6-38/6-39 PID Control - B43-x Pages 6-37/ mA input - B04-1 Page 6-11 Auxiliary Input - B24-0 Pages 6-22/6-29 Arbitary Scale - B05-2 Pages 6-11/6-18 QS210S Rev 1 Page 4

6 Param Description Parameter Listing Min - Max Param Description Min - Max Monitor/(Display) Parameters Output frequency D00-0 O/P frequency (Hz) D00-1 O/P frequency (%) D00-2 O/P frequency (AS) Frequency Setting D01-0 Set frequency (Hz) D01-1 Set frequency (%) D01-2 Set frequency (AS) Output (O/P) current D02-0 O/P current (A) D02-1 O/P current (%) D02-2 OLT monitor (%) D02-3 Heatsink temperature ( C) Voltage D03-0 DC voltage (V) D03-1 O/P voltage command (V) Sequence status D04-0 I/P D04-1 O/P Extended monitor D05-0 Fault history D05-1 Trace data entry D05-2 Non-default parameter list D05-3 Cumulative cond time (Hrs) D05-4 Cumulative run time (Hrs) D05-5 CPU version D05-6 ROM version Pattern run monitor D06-0 Step No. D06-1 Remaining time (s) Speed detection monitor (ASR) D07-0 Detection speed (Hz) D07-1 Detection speed (%) D07-2 Detection speed (AS) A Parameters Frequency setting A00-0 Set local frequency (Hz) A00-1 Set jog frequency (Hz) Acceleration/Deceleration times A01-0 Acceleration time - 1 (s) A01-1 Deceleration time - 1 (s) Torque boost A02-0 Torque boost voltage (%) A02-1 Reduced volt squ law trq (%) A02-2 Auto torque boost gain A02-3 Slip compensation gain (%) DC brake A03-0 DC braking voltage (%) A03-1 DC braking time (s) Custom parameters A04-0 Custom - 0 (Ref B07-0) A04-1 Custom - 1 (Ref B07-1) A04-2 Custom - 2 (Ref B07-2) A04-3 Custom - 3 (Ref B07-3) A04-4 Custom - 4 (Ref B07-4) A04-5 Custom - 5 (Ref B07-5) A04-6 Custom - 6 (Ref B07-6) A04-7 Custom - 7 (Ref B07-7) Block B skip parameters A05-0 Skip selector ( ) B Parameters - Basic Functions Output ratings B00-1 Preset V/F pattern B00-2 Max O/P freq (Fmax) (Hz) B00-3 Base freq (Hz) B00-4 O/P voltage (V) B00-5 Motor rated current (A) B00-6 Carrier frequency (khz) Control methods B01-0 Run/stop B01-1 Inhibit (EMS) B01-2 Control source Start/stop frequency B02-0 Start freq (Hz) B02-1 Stop freq (DC brake start) (Hz) Icrx0.3 - Irc B Parameters - Basic Functions Prog I/P config 1 - operating commands B03-0 R RUN B03-1 F JOG B03-2 R JOG B03-3 HOLD B03-4 BRAKE B03-5 PICK B03-6 COP B03-7 CSEL B03-8 IPASS Prog I/P config 2 - select commands B04-0 VFS B04-1 IFS B04-2 PROG B04-3 CFS B04-4 S0 B04-5 S1 B04-6 S2 B04-7 FUP B04-8 FDW B04-9 FUP/FDW step (Hz) Meter O/P gain/scale multiplier B05-0 O/P gain (FM) B05-1 O/P gain (AM) B05-2 AS display coeff (AS) Protection/operation (PP/O) locks B06-0 PP/O locks B06-1 Reverse lock B06-2 Fault history buffer clear B06-3 Default value load Custom parameter register B07-0 Custom - 0 (Ref A04-0) B07-1 Custom - 1 (Ref A04-1) B07-2 Custom - 2 (Ref A04-2) B07-3 Custom - 3 (Ref A04-3) B07-4 Custom - 4 (Ref A04-4) B07-5 Custom - 5 (Ref A04-5) B07-6 Custom - 6 (Ref A04-6) B07-7 Custom - 7 (Ref A04-7) Operation panel initial mode B08-0 Initial mode B08-1 Operation monitor B08-2 LCD OPU monitor B08-3 LCD OPU bar graph B Parameters - Extended Functions Program frequency setting B20-0 Program frequency - 0 (Hz) B20-1 Program frequency - 1 (Hz) B20-2 Program frequency - 2 (Hz) B20-3 Program frequency - 3 (Hz) B20-4 Program frequency - 4 (Hz) B20-5 Program frequency - 5 (Hz) B20-6 Program frequency - 6 (Hz) B20-7 Program frequency - 7 (Hz) Acceleration/deceleration times B21-0 Acceleration time 2 (s) B21-1 Deceleration time 2 (s) B21-2 Jog acceleration (s) B21-3 Jog deceleration (s) B21-4 S curve characteristics (s) B21-5 Time unit multiplier Frequency skip B22-0 Skip frequency 1 (Hz) B22-1 Skip band 1 (Hz) B22-2 Skip frequency 2 (Hz) B22-3 Skip band 2 (Hz) B22-4 Skip frequency 3 (Hz) B22-5 Skip band 3 (Hz) Ratio Interlock setting B23-0 Polarity setting (A&B) B23-1 Coefficient A value B23-2 Bias B value (Hz) B23-3 Upper limit (Hz) B23-4 Lower limit (Hz) I/P terminal function B24-0 I/P terminal mode B24-1 AUX I/P gain setting O/P terminal function B25-0 FM/AM O/P parameters B25-1 RUN terminal parameters B25-2 ATN terminal parameter QS210S Rev 1 Page 5

7 Param Description Parameter Listing Min - Max Param Description Min - Max B Parameters - Extended Functions Detect levels sequence O/P B26-0 ATN detect band (%) B26-1 Current det level (IDET) (%) B26-2 Speed det level 1 (SPD1) (%) B26-3 Speed det level 2 (SPD2) (%) Retry/Pick up B28-0 No. of retries B28-1 Retry wait time (s) B28-2 Pick-up wait time (s) B28-3 Pick-up voltage time (s) Overcurrent limit B29-0 Drive current limit (%) B29-1 Regen torque limit (%) Overload B30-0 Overload setting (%) B30-1 0Hz overload (%) B Ftrq overload (%) V/F middle point B31-0 Frequency 2 (GF2) (Hz) B31-1 Voltage 2 (GV2) (%) B31-2 Frequency 1 (GF1) (Hz) B31-3 Voltage 1 (GV1) (%) Start interlock B32-0 Start/stop frequency (Hz) B32-1 Start/stop freq hysterises (Hz) B32-2 Interlock frequency (Hz) B32-3 RUN delay timer (s) High-efficiency operation B33-0 High-efficiency time constant (s) B33-1 Voltage lower limit (%) S/W option configuration B40-0 S/W operation select Program ramp - acceleration B41-0 Acceleration time - 0 (s) B41-1 Acceleration time - 1 (s) B41-2 Acceleration time - 2 (s) B41-3 Acceleration time - 3 (s) B41-4 Acceleration time - 4 (s) B41-5 Acceleration time - 5 (s) B41-6 Acceleration time - 6 (s) B41-7 Acceleration time - 7 (s) Program ramp - deceleration B42-0 Deceleration time - 0 (s) B42-1 Deceleration time - 1 (s) B42-2 Deceleration time - 2 (s) B42-3 Deceleration time - 3 (s) B42-4 Deceleration time - 4 (s) B42-5 Deceleration time - 5 (s) B42-6 Deceleration time - 6 (s) B42-7 Deceleration time - 7 (s) Fmax Fmax B Parameters - Software Functions Pattern run step - 4 B54-0 Mode B54-1 Frequency (Hz) B54-2 Time (s) Pattern run step - 5 B55-0 Mode B55-1 Frequency (Hz) B55-2 Time (s) Pattern run step - 6 B56-0 Mode B56-1 Frequency (Hz) B56-2 Time (s) Pattern run step - 7 B57-0 Mode B57-1 Frequency (Hz) B57-2 Time (s) Pattern run step - 8 B58-0 Mode B58-1 Frequency (Hz) B58-2 Time (s) Pattern run step - 9 B59-0 Mode B59-1 Frequency (Hz) B59-2 Time (s) B Parameters - Software Functions PID control B43-0 Proportional gain B43-1 Integral time constant (s) B43-2 Differential time constant (s) B43-3 Upper limit (%) B43-4 Lower limit (%) Traverse option B44-0 Centre freq (FH) (Hz) B44-1 Amplitude - A (%) B44-2 Drop - D (%) B44-3 Acceleration time - B (s) B44-4 Acceleration time - C (s) B44-5 Deviated traverse - X (%) B44-6 Deviated traverse - Y (%) Pattern run step - 0 B50-0 Mode B50-1 Frequency (Hz) B50-2 Time (s) Pattern run step - 1 B51-0 Mode B51-1 Frequency (Hz) B51-2 Time (s) Pattern run step - 2 B52-0 Mode B52-1 Frequency (Hz) B52-2 Time (s) Pattern run step - 3 B53-0 Mode B53-1 Frequency (Hz) B53-2 Time (s) Fmax QS210S Rev 1 Page 6

8 Inverter.. Non-default Parameters Job No.. Reference.. Parameter Set To.. Notes Parameter Set To.. Notes QS210S Rev 1 Page 7

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE NOTICE 1. Read this manual thoroughly before using the VT110S, and store in

More information

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS CHAPTER 8 SUMMARY OF PARAMETER SETTINGS VFD-S Series!: The parameter can be set during operation, *: Twice the value for 460V class. Group 0 User Parameters Parameters Explanation s 0-00 Identity Code

More information

Contents. Introduction Chapter-1: Installation Procedure Chapter-2: Operation Panel (Digital Keypad)... 4

Contents. Introduction Chapter-1: Installation Procedure Chapter-2: Operation Panel (Digital Keypad)... 4 Contents Introduction... 1 Chapter-1: Installation Procedure... 2 Chapter-2: Operation Panel (Digital Keypad)... 4 Chapter-3: Initial Start-Up and Keypad Operation... 6 3-1 Selection of Control Mode...

More information

TOSVERT TM VF-nC3 Parameter List

TOSVERT TM VF-nC3 Parameter List TOSVERT TM VF-nC Parameter List E658664 - Setting information * Please fill it in if necessary. Item Content Item Content Setting date / person Customer Application Application model Motor manufacturer

More information

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER AC DRIVE PARAMETERS. In This Chapter... CHAPTER AC DRIVE 4 PARAMETERS In This Chapter... GS2 Parameter Summary....................4 2 Detailed Parameter Listings.................4 11 Motor Parameters........................4 11 Ramp Parameters.........................4

More information

GS1 Parameter Summary Detailed Parameter Listings...4 9

GS1 Parameter Summary Detailed Parameter Listings...4 9 CHAPTER AC DRIVE 4 PARAMETERS Contents of this Chapter... GS1 Parameter Summary...............................4 2 Detailed Parameter Listings..............................4 9 Motor Parameters.........................................4

More information

VFS11 Parameter List for up to CPU version 105

VFS11 Parameter List for up to CPU version 105 E65824 VFS Parameter List for up to CPU version 5 Setting Date Customer End user Application Application No/Serial No Inverter s Type-Form Quantity Inverter s Serial No Motor s capacity If user s value

More information

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class HITACHI L1-M Series Inverter Quick Reference Guide Single-phase Input 1V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5741XD December 23 Caution: Be sure to read the L1 Inverter Manual

More information

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

CHAPTER 8 PARAMETER SUMMARY

CHAPTER 8 PARAMETER SUMMARY CHAPTER PARAMETER SUMMARY Group 0: System Parameter VFD-V Series 00-00 Identity Code Based on the model type 00-01 Rated Current Display 00-02 Parameter Reset 00-03 00-04 Star-up Display of the Drive Definitions

More information

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class HITACHI SJ1 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5821XD Dec.

More information

VFS9 Parameter List for Version110 or later

VFS9 Parameter List for Version110 or later VFS9 Parameter List for Version110 or later Setting Date Customer End user Application Application /Serial Inverter s Type-Form Quantity Inverter s Serial Motor s capacity If user s value is same as shipping

More information

6.9 Jump frequency - Avoiding frequency resonance

6.9 Jump frequency - Avoiding frequency resonance E581595.9 Jump frequency - Avoiding frequency resonance : Jump frequency : Jumping width Function Resonance due to the natural frequency of the mechanical system can be avoided by jumping the resonant

More information

VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC )

VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC ) VS-616G5 Series (Revision F) Programming Manual Constant Torque Inverter with Adaptive Control (AVC ) ! WARNING PRECAUTIONS NOTICE 1) Only turn ON the input power supply after replacing the front cover.

More information

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide The Invertek Optidrive E3 Frequency Inverter range is available to order from inverterdrive.com This guide is intended to complement

More information

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS CHAPTER DESCRIPTION OF PARAMETER SETTINGS.1 Group 0: User Parameters 0-00 Identity Code of AC Drive Factory setting: d# Settings None V HP 1/4 1/2 1 2 3 11V/230V d0 d2 d4 d6 d8 460V -- -- -- d3 d d7 d9

More information

vacon nx all in one application manual ac drives Phone: Fax: Web: -

vacon nx all in one application manual ac drives Phone: Fax: Web:  - vacon nx ac drives all in one application manual vacon 1 INDEX Document ID:DPD00903A Revision release date: 30.3.2012 1. Basic Application...5 1.1. Introduction...5 1.1.1. Motor protection functions in

More information

NX series Constant and variable torque Variable Speed Drives for induction motors

NX series Constant and variable torque Variable Speed Drives for induction motors Honeywell All in One Application Manual NX series Constant and variable torque Variable Speed Drives for induction motors Subject to changes without notice CONTENTS NX "All in One" APPLICATION MANUAL INDEX

More information

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps.

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps. VFD - D700 Series Specifications The latest low-cost variable speed control solution for centrifugal pumps. Built-in PID Control to maintain pressure, flow, measured value, and much more 125% overload

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

General Specifications FECA-TE /2010. Phone: Fax: Web:

General Specifications FECA-TE /2010. Phone: Fax: Web: General Specifications FECA-TE-117 06/2010 1. Standard Specifications 1) Three-phase 230V series Output ratings Input ratings Braking Item Specifications Type (FRN C1S-2U) F12 F25 F50 001 002 003 005 Nominal

More information

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Variable Frequency Drive / Inverter (0.4 ~ 280kW) Variable Frequency Drive / Inverter (0.4 ~ 280kW) & Standard Features Configuration Comparison Comparison Table Enclosure IP00 IP20 NEMA 1 Rating Single phase 0.4 2.2kW 0.4 1.5kW Three phase 0.4 4kW Constant

More information

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD.

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD. RYKO Manufacturing Company 116 N.W. 54th Ave. P.O.Box 38 Grimes, Iowa 5111 Phone (515) 986-37 www.ryko.com Fax (515) 986-3621 sales@ ryko.com INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life.

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life. ! Warning!! 1. Please read this manual completely before installing the drive. 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life. 3. Be sure

More information

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives Page 2 (68) Index Honeywell HVAC Application (Software [ALFIQ105] Ver.2.09) INDEX 1. INTRODUCTION... 3 2. CONTROL I/O... 3. HVAC APPLICATION

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual INDEX A AC Drive Cover: 1 6 Dimensions: 2 4 External Parts and Labels: 1 6 Heat Sink Fins: 1 6 Input Mode Switch (Sink/Source): 1 6 Introduction to DuraPulse GS3 AC drive: 1 3 Keypad: 1 6 Model Number

More information

3. Be aware of the ambient temperature. Use the unit within the specified ambient temperature only.

3. Be aware of the ambient temperature. Use the unit within the specified ambient temperature only. This document is a short guide to how to connect, do the configuration and start the unit in the easiest way. Refer to the Instruction Manual IMAE-01, appropriate revision of Axpert-Eazy Series AC Drive

More information

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL D SERIES LM16 COMPACT DRIVE V/f and SLV CONTROL LM16 COMPACT DRIVE V/f and SLV CONTROL 1 2 SERIES 1 2 page 4 page 6 Introduction Fields of application 3 page 7 4 page 8 Designation Product offer 5 6 page

More information

vacon nx ac drives all in one application manual

vacon nx ac drives all in one application manual vacon nx ac drives all in one application manual PREFACE VACON 3 PREFACE Document ID: DPD00903F Date: 14.8.2017 Software code: Basic Application = ASFIFF01 Standard Application = ASFIFF02 Local/Remote

More information

ADJUSTABLE SPEED DRIVES. AS1 Drive

ADJUSTABLE SPEED DRIVES. AS1 Drive ADJUSTABLE SPEED DRIVES AS1 Drive Toshiba s New ASD Product Line The AS1 drive builds on Toshiba s history of supplying powerful, reliable, and versatile drives. We have combined our best drive features

More information

5. ELECTRIC DRIVES. 5.1 General description

5. ELECTRIC DRIVES. 5.1 General description 5. ELECTRIC DRIVES 5.1 General description Electric drive is an electromechanical system (mechatronic system) intended to set into motion technological equipment. They consist of an electric motor (motors),

More information

BACnet- MS/TP COMMUNICATION V

BACnet- MS/TP COMMUNICATION V - MS/TP COMMUNICATION V1.00.08.17 11.1 Introduction The VFD can be controlled and monitored through the BACnet MS/TP protocol over an RS-485 connection. The VFD operates as an MS/TP master device, which

More information

Comp-AC. User s Manual for type ACS 140 frequency converters from 0.12 to 2.2 kw

Comp-AC. User s Manual for type ACS 140 frequency converters from 0.12 to 2.2 kw Comp-AC User s Manual for type ACS 140 frequency converters from 0.12 to 2.2 kw ACS 140 Frequency Converter User s Manual 3BFE 64273736 R0125 EN Effective: 8.3.2000 2000 ABB Industry Oy Safety Warning!

More information

Manual Overview...1 2

Manual Overview...1 2 GETTING STARTED CHAPTER 1 Contents of this Chapter... Manual Overview.....................................1 2 Overview of this Publication..................................1 2 Who Should Read This Manual...............................1

More information

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS CHAPTER DESCRIPTION OF PARAMETER SETTINGS.1 Group 0: System Parameter VFD-V Series 00-00 Identity Code Factory setting Read Only Settings Based on the model type 00-01 Rated Current Display Factory setting

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB DF5-... Frequency Inverters 1 st published 22, edition 02/02 Moeller GmbH, 53105 Bonn Author: Holger Friedrich Editor: Michael Kämper Translator: Dominik Kreuzer All brand and product names are trademarks

More information

Multi-purpose Control Application II

Multi-purpose Control Application II VACON CX /CXL/CXS FREQUENCY CONVERTERS Multi-purpose Control Application II USER'S MANUAL Subject to changes without notice Vacon Page 1 Multi-purpose Control Application II (par. 0.1 = 0) CONTENTS 1 General...

More information

user's manual nx frequency converters beam pump application asfiff13

user's manual nx frequency converters beam pump application asfiff13 user's manual nx frequency converters beam pump application asfiff13 2 vacon Introduction INDEX 1. Introduction... 3 2. Commissioning... 4 2.1 Commissioning unbalanced load... 4 2.2 Commissioning balanced

More information

AV-300i Specifications. Saftronics Inc. VG10 Product Specifications VG10. Dynamic Vector Drive

AV-300i Specifications. Saftronics Inc.   VG10 Product Specifications VG10. Dynamic Vector Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications VG10 Product Specifications VG10 Dynamic Vector Drive 1 Category Item Description Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3

More information

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control NEW FIRMWARE MAKES SETUP A SNAP Application based commissioning allows parameters

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

Caution. Three-phase 400V series FRN0.4C1S-4A FRN0.75C1S-4A FRN1.5C1S-4A FRN2.2C1S-4A FRN3.7C1S-4A

Caution. Three-phase 400V series FRN0.4C1S-4A FRN0.75C1S-4A FRN1.5C1S-4A FRN2.2C1S-4A FRN3.7C1S-4A Variation Caution The contents of this catalog are provided to help you select the product model that is best for you. Before actual use, be sure to read the User s Manual thoroughly to assure correct

More information

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB. For Immediate Delivery call KMParts.com at (866)

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB. For Immediate Delivery call KMParts.com at (866) DF5-... Frequency Inverters 1 st published 22, edition 02/02 Moeller GmbH, 53105 Bonn Author: Holger Friedrich Editor: Michael Kämper Translator: Dominik Kreuzer All brand and product names are trademarks

More information

Multi-function, Compact Inverters. 3G3MV Series

Multi-function, Compact Inverters. 3G3MV Series Multi-function, Compact Inverters 3G3MV Series There has been a great demand for inverters with more functions and easier motor control than conventional i OMRON's powerful, compact 3G3MV Series with versat

More information

VA TECH ELIN EBG Elektronik. Operating and Mounting instructions. >pdrive< CX profi. The Power Drives Company

VA TECH ELIN EBG Elektronik. Operating and Mounting instructions. >pdrive< CX profi. The Power Drives Company VA TECH ELIN EBG Elektronik Operating and Mounting instructions >pdrive< CX profi The Power Drives Company Safety instructions General information, note exactly! The requirements for a successfull commissioning

More information

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE 1 2 SERIES 1 2 pag. 4 pag. 5 Applications Model identification 3 pag. 5 4 pag. 6 Capacity

More information

THYFREC-VT230S 200V System 0.4 to 90kW 400V System 0.4 to 370kW INSTRUCTION MANUAL

THYFREC-VT230S 200V System 0.4 to 90kW 400V System 0.4 to 370kW INSTRUCTION MANUAL MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT230S 200V System 0.4 to 90kW 400V System 0.4 to 370kW INSTRUCTION MANUAL NOTICE 1. Read this manual thoroughly before using the VT230S, and store in a safe place

More information

Application Note: Replacing J300 with SJ300 Series Inverters

Application Note: Replacing J300 with SJ300 Series Inverters Application Note: Replacing J300 with SJ300 Series Inverters Please refer also to the SJ300 Inverter Instruction Manual AN101001-1 Hitachi America, Ltd. 2002 Hitachi America, Ltd. Chapter 1 Introduction

More information

9. RS485 Communication (Option)

9. RS485 Communication (Option) 9. RS485 (Option) The communication between inverter and external controller is doing by RS485 using modular connector in cling to inverter controller. Function Initial Minimum Maximum code Value Unit

More information

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R INVERTER ROLL TO ROLL FUNCTION MANUAL FR-A820-00046(0.4K)-04750(90K)-R2R FR-A840-00023(0.4K)-06830(280K)-R2R FR-A842-07700(315K)-12120(500K)-R2R Roll to Roll Function The FR-A800-R2R inverter has dedicated

More information

13. Before making a service call Trip information and remedies

13. Before making a service call Trip information and remedies . Before making a service call Trip information and remedies.1 Trip causes/warnings and remedies When a problem arises, diagnose it in accordance with the following table. If it is found that replacement

More information

L100-M Series Inverters

L100-M Series Inverters L100-M Series Inverters Addendum to L100 Series Inverter Instruction Manual In This Addendum... page Getting Started... 3 Inverter Mounting and Installation... 10 Configuring Drive Parameters... 15 Operations

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1 SV9000 Page 0-1 SV9000 SVReady USER MANUAL CNTENTS A General...0-2 B Application selection...0-2 C Restoring default values of application parameters...0-2 D Language selection...0-2 1 Standard Control

More information

9. RS485 Communication

9. RS485 Communication 9. RS485 The communication between inverter and external controller is doing by RS485 using modular connector in cling to inverter controller. Function Initial Minimum Maximum code Value Unit Description

More information

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control. Section 16680 VARIABLE SPEED DRIVE SYSTEMS OR AFD Part I - GENERAL I.01 Description A. This specification is to cover a complete adjustable frequency motor drive consisting of a pulse width modulated (PWM)

More information

Configuring Drive Parameters

Configuring Drive Parameters 3 In This Chapter... page Choosing a Programming Device... 2 Using Keypad Devices... 3 D Group: Monitoring Functions... 6 F Group: Main Profile Parameters... 8 A Group: Standard Functions... 9 B Group:

More information

Operating Instructions

Operating Instructions 4XH35QB151210 Small General Frequency Converter Operating Instructions 220V 0.75KW 5.5KW 400V 0.75KW 15KW Please read the instruction carefully and understand the contents so that it can be installed and

More information

E3 Adjustable Speed Drive Engineering Specification

E3 Adjustable Speed Drive Engineering Specification E3 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba E3 AC Variable Frequency Drives, 6 pulse for 230V and 460V. 1.1 References A. National

More information

AC SPEED CONTROL EQUIPMENT. VAT2000 3ph 200V-230V System 0.4 to 45kW 3ph 380V-460V System 0.4 to 370kW INSTRUCTION MANUAL

AC SPEED CONTROL EQUIPMENT. VAT2000 3ph 200V-230V System 0.4 to 45kW 3ph 380V-460V System 0.4 to 370kW INSTRUCTION MANUAL GE Power Controls AC SPEED CONTROL EQUIPMENT VAT2000 3ph 200V-230V System 0.4 to 45kW 3ph 380V-460V System 0.4 to 370kW INSTRUCTION MANUAL --------------------------------- NOTICE ------------------------------------------

More information

System Manual MOVITRAC LT E. Edition 04/2005 EA / EN

System Manual MOVITRAC LT E. Edition 04/2005 EA / EN Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services MOVITRAC LT E EA390000 Edition 04/2005 11336617 / EN System Manual SEW-EURODRIVE Driving the world Inhaltsverzeichnis

More information

MD310 Quick Start Manual. General-Purpose AC Drive

MD310 Quick Start Manual. General-Purpose AC Drive MD310 Quick Start Manual General-Purpose AC Drive ersion 0.1 Dated 14 th OCT, 2013 CONTENTS CHAPTER 1 PRODUCT INFORMATION... 1 1.1 Designation... 1 1.2 Nameplate... 1 1.3 General Specifications... 2 CHAPTER

More information

INSTRUCTION MANUAL GENERAL-PURPOSE INVERTER R ADLEEPOWER

INSTRUCTION MANUAL GENERAL-PURPOSE INVERTER R ADLEEPOWER R ADLEEPOWER INSTRUCTION MANUAL GENERAL-PURPOSE INVERTER THANK YOU VERY MUCH FOR YOUR PURCHASE OF ADLEE INVERTER AS SERIES. PLEASE READ THIS INSTRUCTION MANUAL BEFORE INSTALLATION OF THE INVERTER. PREFACE

More information

QUick StARt guide. Customised to your machine Model: 3G3RX 200 V Class Three-Phase Input 0.4 to 55 kw 400 V Class Three-Phase Input 0.

QUick StARt guide. Customised to your machine Model: 3G3RX 200 V Class Three-Phase Input 0.4 to 55 kw 400 V Class Three-Phase Input 0. Cat. No. I130E-EN-02 RX Customised to your machine Model: 3G3RX 200 V Class Three-Phase Input 0.4 to 55 kw 400 V Class Three-Phase Input 0.4 to 132 kw QUick StARt guide Notice: OMRON Product References

More information

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications 3 to 75 HP Models- MA7200-2003-N1 Thru MA7200-2040-N1 (230V) & MA7200-4003-N1 Thru MA7200-4075-N1 (460V) speed time Rev.

More information

G+ Mini Transition Guide. Product Transition Guide P3 Series 2 to G+ Mini

G+ Mini Transition Guide. Product Transition Guide P3 Series 2 to G+ Mini Transition Guide Product Transition Guide to Rev: Page Intentionally Left Blank Transition Guide September 2008 Page 2 of 24 Table of Contents 1.1 Overview...4 1.2 Drive Replacement Checklist...4 1.3 Ratings

More information

Series Concepts. Ideal functions to meet various needs. New, compact design. Simple operation. Flexible through optionals

Series Concepts. Ideal functions to meet various needs. New, compact design. Simple operation. Flexible through optionals MEH441a Series Concepts Ideal functions to meet various needs New, compact design Simple operation Flexible through optionals A broad range of model variations Actual size Global products The FRENIC-Mini

More information

1. INTRODUCTION Fire Mode PID Application Parameter lists DESCRIPTION OF PARAMETERS... 8

1. INTRODUCTION Fire Mode PID Application Parameter lists DESCRIPTION OF PARAMETERS... 8 U S E R ' S M A N U A L NX F R E Q U E N C Y C O N V E R T E R S A D D O N P A G E S F O R T H E F I R E M O D E P I D A P P L I C A T I O N F O R S M O O T H C O N T R O L INDEX 1. INTRODUCTION... 3 2.

More information

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Inverter STARVERT ig5a LS Starvert ig5a is very competitive in its price

More information

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/ QUICK GUIDE PUMP CONTROL High performance Compact Inverter Date Version 22/9/29 1..3 Version Details Date Written Checked Approved 1.. Draft J. M. Ibáñez J. Català 1..1 Second Version 17/9/29 J. M. Ibáñez

More information

Max. sp Min. spe Negativ speed s Synchro out speed refere selection Menu 13. g t x (-1) UMV 4301

Max. sp Min. spe Negativ speed s Synchro out speed refere selection Menu 13. g t x (-1) UMV 4301 Réf. 335-4.33 / a -.98.5 X-.39 Synchro output speed reference Menu 3 Max. sp Min. spe Negativ speed s.4 Synchro out speed refere selection Menu 3 Skip frequency Skip width.29.3.3 g t Run Run FWD REV 27

More information

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive... CHAPTER KEYPAD OPERATION 3 AND QUICKSTART Contents of this Chapter... The GS1 Digital Keypad................................3 2 LED Display..............................................3 2 Function Keys............................................3

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web: -

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web:  - ADJUSTABLE SPEED DRIVES HX7 Series 18 Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

Inverter Drive /Vector Drive Motors & Controls

Inverter Drive /Vector Drive Motors & Controls H2 Inverter/ Encoderless Vector Inverter Drive /Vector Drive & Controls 3/4 thru 50 180-264 VAC 3 Phase - 50/60 Hz 3/4 thru 60 340-528 VAC 3 Phase - 50/60 Hz 3/4 thru 60 515-660 VAC 3 Phase - 60 Hz HVAC

More information

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric ADJUSTABLE SPEED DRIVES VF-S11 The Next Generation of Micro Inverters is Here. The S11 provides maximum torque with precise speed control. It features an easy-to-use, quiet and compact design. In addition,

More information

KBDA SERIES STANDARD FEATURES DESCRIPTION PERFORMANCE FEATURES PROTECTION FEATURES

KBDA SERIES STANDARD FEATURES DESCRIPTION PERFORMANCE FEATURES PROTECTION FEATURES KBDA SERIES ADJUSTABLE FREQUENCY DRIVES FOR 3-PHASE AC MOTORS NEMA-4X / IP-65 Washdown and Watertight for Indoor and Outdoor use MULTI-FUNCTION KEYPAD WITH 4-DIGIT LED DISPLAY Simplified Group Programming

More information

AV-300i Specifications. GE Industrial Systems. Product Specifications. A New Concept in Automation. AV-300i

AV-300i Specifications. GE Industrial Systems. Product Specifications. A New Concept in Automation. AV-300i GE Industrial Systems Product Specifications AV-300i A New Concept in Automation. TM 1 General Item Description Nominal Motor 230V, 3 Phase 15 Hp to 100 Hp 460V, 3 Phase 3/4 Hp to 200 Hp Enclosure, Standard

More information

Before you operate the inverter, the parameters that you must first program are the basic parameters.

Before you operate the inverter, the parameters that you must first program are the basic parameters. . Main parameters Before you operate the inverter, the parameters that you must first program are the basic parameters..1 Searching for changes using the history function () : History function History

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual vacon 1 TABLE OF CONTENTS Document: DPD01083A Version release date: 16.11.12 Corresponds to software package FW0159V121106.vcx 1. Vacon 100 FLOW - Quick Startup

More information

FREQUENCY INVERTER VFR-013 QUICK START GUIDE

FREQUENCY INVERTER VFR-013 QUICK START GUIDE FREQUENCY INVERTER VFR-013 QUICK START GUIDE Inoréa Automation & Industry 9 rue du Lugan 33130 BEGLES www.inorea.com Table of contents 1. PEOPLE SAFETY... 3 2. MATERIAL SAFETY... 3 3. NAME PLATE... 4 a.

More information

V&T Technologies Co., Ltd. Vectorque TM V6-H-M1 SERIES INVERTER ADDITIVE MANUAL (M1) V6-H Series ADDITIVE MANUAL V& T

V&T Technologies Co., Ltd.   Vectorque TM V6-H-M1 SERIES INVERTER ADDITIVE MANUAL (M1) V6-H Series ADDITIVE MANUAL V& T Vectorque TM V6-H-M1 SERIES INVERTER ADDITIVE MANUAL (M1) V6-H Series ADDITIVE MANUAL V& T Change Scope Increase control function of vector control 2 with encoder speed feedback to support machine tool

More information

Document number: Document version: r2 Date of release: Copyright Emotron AB 1998 Emotron AB reserves the right to alter product

Document number: Document version: r2 Date of release: Copyright Emotron AB 1998 Emotron AB reserves the right to alter product Document number: 01-0861-01 Document version: r2 Date of release: Copyright Emotron AB 1998 Emotron AB reserves the right to alter product specifications without prior notification. No part of this document

More information

AF-300 G11 Specifications. GE Industrial Systems. Product Specifications AF-300 G11

AF-300 G11 Specifications. GE Industrial Systems. Product Specifications AF-300 G11 apple GE Industrial Systems Product Specifications AF-300 G11 TM 1 Category Item Description Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp 460 VAC, 3 Phase 1/2 Hp to 450 Hp Braking Torque (Standard)

More information

Enhanced PID for Air Compressors F7 Drive Software Technical Manual

Enhanced PID for Air Compressors F7 Drive Software Technical Manual Software Number: VSF11020X, Drive Models: CIMR-F7UXXXXXX-096 Document Number: TM.F7SW.096, Date: 08/01/05, Rev: 05-08 Enhanced PID for Air Compressors F7 Drive Software Technical Manual This document is

More information

Design Specifications Operator Keypad Environmental and Operating Conditions

Design Specifications Operator Keypad Environmental and Operating Conditions Series 15J Mini Inverters Big inverter features do come in small packages! Take a look at Baldor s Series 15J Inverter control. Designed to save cabinet space without giving up the features available on

More information

AF91 Adjustable Frequency Drives Series B

AF91 Adjustable Frequency Drives Series B Effective: January, 00 Page New Information AF9 Adjustable Model AF9 Description Model AF9 Adjustable Frequency AC Drives are designed to provide adjustable speed control of -phase motors. These microprocessor-based

More information

Altivar 68 Telemecanique

Altivar 68 Telemecanique Altivar 68 Telemecanique Programming manual Variable speed drives for asynchronous motors Contents Installation recommendations 3 Control 7 A - Display of references and actual values and configuration

More information

Comp-AC. User s Manual for type ACS 100 frequency converters from 0.12 to 2.2 kw

Comp-AC. User s Manual for type ACS 100 frequency converters from 0.12 to 2.2 kw Comp-AC User s Manual for type ACS 100 frequency converters from 0.12 to 2.2 kw ACS 100 Frequency Converter User s Manual 3BFE 64307622 R0125 EN Effective: 8.3.2000 2000 ABB Industry Oy Safety Warning!

More information

AV-300i Specifications. Saftronics Inc. PC10 Product Specifications PC10. Mini Vector AC Drive

AV-300i Specifications. Saftronics Inc.  PC10 Product Specifications PC10. Mini Vector AC Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications PC10 Product Specifications PC10 Mini Vector AC Drive 1 (1) T hree-phas e 230V input Drive Hp 1/8 1/4 1/2 1 2 3 5 7.5 10 Nominal applicable

More information

General Specifications

General Specifications General Specifications FECA-TE-116 07/2010 Braking Input ratings Output ratings 1. Standard specifications 1) Three-phase 230V class series (1/8 to 20HP) Items Type (FRN E1S-2U) Nominal applied motor *1

More information

SJ300 Series Inverter Quick Reference Guide

SJ300 Series Inverter Quick Reference Guide SJ3 Series Inverter Quick Reference Guide Three-phase Input Three-phase Input 2V Class 4V Class UL Version Models CE Version Models Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB6131XF September

More information

OPC-E1-PG3 Specifications

OPC-E1-PG3 Specifications OPC-E1-PG3 Specifications Power Electronics Business Group Drive Division Development Dept. b DATE NAME APPROVE a DRAWN 2006-06-05 O. Mizuno CHECKED 2006-06-06 T. Ichihara K. Fujita Fuji Electric Co.,

More information

ADJUSTABLE SPEED DRIVES FS1

ADJUSTABLE SPEED DRIVES FS1 ADJUSTABLE SPEED DRIVES FS1 Now Available With LonWorks BACnet & MetasysN2 FS1 Model FLA & Dimensions (in.)/ Weight (lbs.) VOLTAGE HP MODEL NUMBER FLA FRAME Dimensions (in.) SHIPPING H W D WEIGHT (lbs.)

More information

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6 CHAPTER KEYPAD OPERATION 3 AND QUICKSTART In This Chapter... The GS2 Digital Keypad.....................3 2 LED Display.........................................3 2 LED Indicators.......................................3

More information

PID Software Kit. Part No. SK-PID1-L503. For GPD 503 Adjustable Frequency Drives CT: 1-30HP, 230V; 1-60HP, 460V VT: 1-40HP, 230V; 1-75HP, 460V

PID Software Kit. Part No. SK-PID1-L503. For GPD 503 Adjustable Frequency Drives CT: 1-30HP, 230V; 1-60HP, 460V VT: 1-40HP, 230V; 1-75HP, 460V PID Software Kit Part No. SK-PID-L53 For GPD 53 Adjustable Frequency Drives CT: -3HP, 23V; -6HP, 46V VT: -4HP, 23V; -75HP, 46V DESCRIPTION The PID Software Kit consists of two EPROMs and this instruction

More information