[u] u in. Case, polycarbonate IP20 Figure 1. Measured voltage and frequency pulse Wire connectors max 4 mm 2. output

Size: px
Start display at page:

Download "[u] u in. Case, polycarbonate IP20 Figure 1. Measured voltage and frequency pulse Wire connectors max 4 mm 2. output"

Transcription

1 MF4 CAREAY MF4 is a frequency and oss of Mains relay (ROCOF type). Additionally MF4 measures a rotational speed of an asynchronous generator when generator is not connected to grid (generator circuit breaker open). The device is microprocessor controlled and functional parameters can be changed with a computer program or with industrial PC using RS485 bus and MODBUSRTU protocol. CAREAY is a trade mark of Power Factor Ay The MF4 indicate mains loss when the derivative of frequency or frequency deviation exceeds the adjustable set value. The device has three output relays: over frequency (and df/dt >), under frequency (and df/dt <) and frequency window relay. Technical specification General data: Power consumption Auxiliary voltage or MF4x 3. W max 24 VDC 7..4 VDC Output signals : indication: pulse output: The amplitude of output pulse equals the auxiliary voltage and it is square shaped. The polarity of measurement voltage is not indicated. Measurement voltage isolation 3.5 kv Programming protocol: MODBUS RTU * Programming device: PC, PC PCprogram CCRMF4 Mechanical properties [u] 24 u in ( t) out( t) Operational temperature C Size h x w x d 75xx t. [t] Case, polycarbonate IP2 Fixing DINbar Figure. Measured voltage and frequency pulse Wire connectors max 4 mm 2 output Input signals : Rated voltage Auxiliary voltage Current ma Measurement input: Output impedance Ω Input impedance min. 44 kω Voltage loss see. Figure 2 Voltage 3mV.. 5V RMS Output voltage as a function of current.2.. z 98 Voltage max. continuous 4 V RMS 96 Voltage max. s V RMS Uaux= 24 VDC Generatorand mains circuit breaker position: Optical isolation kv Input type (IEC 32) Type (sinking) Maximum current ma at rated voltage (24 VDC) 3 ma OFFstate current max 24 µα Output U% Uaux= 4 VDC Output current I[A] Figure 2. pulse output voltage

2 MF4 CAREAY is a trade mark of Power Factor Ay indication: current output: Current 4..2 ma Allowed load...5 Ω No galvanic isolation type: MF4xn isolation kv MF4xi no current output MF4xw Serial communication: MODBUS RTU ED indicators: Yellow Red Green Connection examples RS485 5VDC (no parity, 2 stop) serial communication supervisory on power on /operational Figure 3 represents the connection of MF4 relay in system where startup and shutdown procedures of asynchronous generator is controlled by PC. Startup, connection to grid: See figure 3. When the MF4 is powered for at least 5 ms, and the initsignal is pulsed (min ms, pulse length adjustable) f<, f> relays are set to grid normal position. When the turbine inlet valve is opened the MF4 measures the rotational speed of Supervisory output: Open collectortype conducting state current 5 ma max the generator. When synchronous speed is achieved the output relay closes contact between pins 6 and 8. This contact can be used directly to close the open state voltage..3 V DC generator circuit breaker or can be used as as input for the controlling PC. This then control the generator Relay outputs: circuit breaker. The supervision of the grid fre quency begins when generator circuit breaker (GCB) Maximum operational voltage 25 VAC / 3 VDC and mains circuit breaker (MSB) have been closed Maximum current 5 A continuous (auxiliary contacts are open) for the adjustable time Isolation 2 kv delay of ms min. If, because of the loss of mains situation, the grid frequency exceeds the set value or the rate of the frequency exceeds its set value the contact of relay 2 or relay 3 ( f< tai f>) opens. This switches the voltage of from the under voltage release of GCB opening the main circuit. The contacts of voltage relay can be connected to this same protection circuit. When the grid is restored, the relays 2 and 3 can be set again to grid normal position with the init input signal in order to start the new startup procedure. If shunt release is used instead of the under voltage release, the relays 2 and 3 should be connected in parallel. If there is no need for the rotational speed information the measurement input pins 29 and 3 of MF4 can be connected in phase conductors between MCB and GCB. In that case, mainsloss protection of the whole plant can be done using one MF4 protection relay.

3 MF4 CAREAY is a trade mark of Power Factor Ay Figure 3. Example connection of MF4 protection relay.

4 MF4 Init Init Delay Setup Delay CAREAY is a trade mark of Power Factor Ay Relay trip (f >, df/dt) INPUTS Inhibit Inhibit 2 Supervisory Output OUTPUTS Supervisory ed f >, df/dt Relay Flashing led MONITORING f<, df/dt Relay f >, df/dt Monitoring f<, df/dt Monitoring Time Figure 4. Timing diagram of the MF4 relay activation. Init Init Delay AND Activate Relays Inihibit NOT AND Setup Delay Inihibit 2 NOT Activate Monitoring Figure 5. Block diagram of the relay activation for the supervisory (monitoring).

5 MF4 OVER FREQUENCY TRIPPING DIAGRAM CAREAY is a trade mark of Power Factor Ay OFimit if x >, y = y else, y = x y Counter AND Over Relay TripDelay OFMWindow Figure 6. Block diagram of the over frequency trip. UNDER FREQUENCY TRIPPING DIAGRAM UFimit if x >, y = y else, y = x y Counter AND Under Relay TripDelay OFMWindow Figure 7. Block diagram of the under frequency trip. MAINSOSS DETECTION Derivate of Derivate imit if x >, y = y else, y = x y Counter Over / Under Relay OFM / UFM Window Figure 8. Block diagram of df/dt tripping. Rpm meter output 4..2 ma Models MF4xn ja MF4xi The output current signal relates to measured frequency. The current signal can be read with PC or with 4..2mA panel meter. The output signal relates to the rotational speed of an asynchronous generator when generator is not connected to grid. The scaling of the output is programmable. Obs: The frequency information can also be obtained from the pulse output (connector 26, pulse/z) with a tachometer (counter).

6 MF4 CAREAY is a trade mark of Power Factor Ay Relay settings with MODBUS RTUbus All operational parameters of MF4 can be changed with CCRMF4 program. The program is delivered with the device and can also be downloaded at. If the computer do not include the RS485 port (normal PC), the RS485/RS232converter is required in addition to the connection cable delivered with MF4. A suitable converter is for example SIEMENS PCPPIcable (6ES7 93BFXA). MF4 can be connected to MODBUSRTU as slave, if master uses two stopbits without parity check. The MODBUS registers of MF4 that are needed in order to change principal operaationl parameters are presented in Table. The registers are described in detail in appendix. olding Register Parameter DeviceID InitDelay 2 SetupDelay 3 TripDelay 4 RPMFMin 5 RPMFMax 6 RPMWindow 7 OFimit 8 OFMimit 9 OFMWindow OFMDerivateimit UFimit 2 UFMimit 3 UFMWindow 4 UFMDerivateimit 5 PWMOffset 6 PWMConstant 7 BaudRate 8 Parity 9 Flags Input Register Parameter 2 Derivate Coil Register Parameter RPMRelay OFMRelay 2 UFMRelay 3 OKOutput 4 Powered 5 Activeed 6 WEEPROM 7 Testbit The default factory address for MF4 is and baud rate 96. Attention! The MF4 has to be connected into the low impedance input such as between phase conductors or motor terminals. When the inputs of the devices are as open circuit the MF4 easily measures the frequency of interfering magnetic field that is generally 5 z. Special Models MF4 is a versatile relay. Almost all device parameters may be modified and customized by programming. The special models may be delivered with extra price. CAREAY is trademark of Power Factor Ay.

7 MF4 Appendix CAREAY is trademark of Power Factor Ay ODING REGISTER All the register values and addresses are 6 bit DeviceID: The Modbus address of MF4 device. The address is used to indentify the device connected to field bus. The slave devuce address value may be in the range of 28. The address is reserved for the master. The default factory setting for the device is. InitDelay: The minumum time delay that init signal has to be active in order to activate the relays of MF4. The delay value is represented in holding register as tens of milliseconds. The value may be in the range of The default value is, which represents time delay second. Setup Delay: The time delay that is required after the activation of relays and deactivation of inhibit signals when the MF4 goes to the supervisory state and starts the monitoring of distribution network frequency. The delay value is represented as tens of milliseconds. The value may be in the range of The default value is, which represents time delay second. Trip Delay: The time delay that affects the functionality of both frequency relays. If the over or underfrequency in detected, the MF4 waits trip delay again. If the same crossing of frequency limit is detected again, the relay will be tripped. The value may be in the range of The default value is, which represents time delay second. RPMFMin: The lower frequency of frequency window relay. The default value is 49 z. The frequency is calculated with equation: 6 5 z value =, () 4 f where f is frequency. RPMFMax: The upper frequency of frequency window relay. The default frequency value is 5 z. The value is calculated using equation. RPMWindow The length of window, which defines how many subsequent frequency limit crossings is required to activate the RPM relay. The default value is 4. OFimit: The tripping limit of over frequencymainsloss relay. The value is calculated using equation. The default frequency value is 5.3 z.

8 MF4 Appendix CAREAY is trademark of Power Factor Ay OFMimit: The upper frequency after which the supervising of frequency starts. The value is calculated using equation. The default value is 5. z. OFMWindow: The length of window, which defines how many subsequent crossings of over frequency or derivate limits is required in order to determine that frequency or derivate limit is crossed. Only positive derivate values are calculated. The default value is 4. OFMDerivateimit: The frequency derivate limit for over frequencymains loss relay. The default derivate value is 5 z/s. The value may be calculated using equation: df value = *. (2) dt UFimit: The under frequency limit for the under frequencymains loss relay. The frequency is calculated using equation. The default value is 49.7 z. UFMimit: The upper frequency limit for under the frequencymains loss relay. At the lower frequencies, the relays starts monitoring distribution network frequency. UFMWindow: The length of window, which defines how many subsequent crossings of under frequency or derivate limits is required in order to determine that frequency or derivate limit is crossed. Only negative derivate values are calculated. The default value is 4. UFMDerivateimit: The setting for under frequency mains loss relay. The default absolute value is 5 z/s. The register values are determined using equation 2. PWMOffset: The offsett coefficient for current output. The value is set such that at frequency z, the output current is 4 ma. The default value is 29. PWMConstant: The coefficient that determines the scale of current output. The default value is 4. Using it the current scale 42 ma corresponds the frequency scale z. BaudRate: The baud rate of Modbus protocol. The possible rates are 96, 92, 288 and 336. The default value is 96. Parity: The used parity in serial communications: no parity, odd parity, 2 even parity. Currenly only setting: no parity is used. In this case, the number of stop bits is two.

9 MF4 Appendix CAREAY is trademark of Power Factor Ay Flags: The flags that affect functionality of relay. The value set MF4 into autoinit mode. INPUT REGISTER All the register values and addresses are 6 bit : The highest 6 bits of 32 bit counter value representing the measured frequency. : The lowest 6 bis of 32 bit counter representing the measured frequency. The counter value may be converted to frequency using equation: f 5 = 4 6 z ( ). (3) Derivate: The measured frequency derivate INPUTS All Inputs are single bits Init: The init input. It is used to initialize the under frequencymains loss and over frequency mains loss relays. The intialization has to be performed after every tripping. The duration of initialization pulse has to be at minimum the initialization delay. After that the pulse has to be deactivated. Inhibit & 2: The inhibits prevent the frequencymains loss and over frequency mains loss relays to go into the supervisory state. When both inhibit signals are deactivated, the MF4 will enter into the supervisory state after the setup delay. COIS All coils are single bit outputs RPMRelay: The state of frequency window relay. The relay is active, when the measured frequency is inside the set frequency window limits. OFMRelay: The status of over frequency mains loss relay. The coil is active, when the relay is in supervisory state.

10 MF4 Appendix CAREAY is trademark of Power Factor Ay UFMRelay: The status of under frequency mains loss relay. The coil is active, when the relay is in supervisory state. OKOutput: The status of MF4. The status is high when the both relays are active and in supervisory state. Powered: Power switched on and microprosessor in operational state Activeed: The status of MF4. The status is high when the both relays are active and in supervisory state. WEEPROM: When activated, the contents of holding register are save into the EEPROM memory. Correspondingly, in the powerup the device parameters are read from the EEPROM. TestBit: When activated, the relays and outputs of the MF4 can be controlled through Modbus. The initialisation of the MF4 restored the device into the normal state.

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA

More information

Digital Panel Meters DC/AC Current and Voltage Indicator/Controller Type LDM40

Digital Panel Meters DC/AC Current and Voltage Indicator/Controller Type LDM40 Digital Panel Meters Current and Voltage Indicator/Controller Type LDM40 Multi-input instrument 4-DGT LED 0.1% RDG basic accuracy TRMS AC current and voltage measurements AC/DC current measurements: selectable

More information

Brushless DC Motor Controller Specification Assemblies 025F0248

Brushless DC Motor Controller Specification Assemblies 025F0248 Brushless DC Motor Controller Specification Assemblies 025F0248 600A1099 Rev. B April 4 th, 2014 Revision History EC Date Description Rev EC54318 09/03/13 Initial Release A EC58093 04/04/14 Added cap discharge

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate True RMS AC Voltage & Current Meter with 1 Cycle Update at 50/60 Hz Features True AC or AC plus DC RMS measurement with crest factor of 3.0 at FS Fast response: reading

More information

Multi-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5

Multi-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5 Multi-channel DC power digital isolation transducer manual CE-AD81-34MN3-0.5 1 Overview The main function of this product is to centralized measurement convert multi-channel standard DC transmission signal

More information

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current

More information

ENA33LCD. Power line analyzer. User and service manual. Obrezija 5 SI-1411 Izlake

ENA33LCD. Power line analyzer. User and service manual.   Obrezija 5 SI-1411 Izlake ENA33LCD Power line analyzer User and service manual version 2.9 (FW version 6.8 and newer) ETI, d.o.o. Obrezija 5 SI-1411 Izlake www.etigroup.eu/products-services 1. Front control panel and terminal plate

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

Position Indicator model MFC-300/IP. Technical Manual. Licht

Position Indicator model MFC-300/IP. Technical Manual. Licht Position Indicator model MFC-300/IP Technical Manual Licht Contents 1 Introduction 2 2 Front panel indication 3 3 Error indication 4 4 Manual commands 5 5 Configuration 6 5.1 Parameter reset 6 6 Programmable

More information

Selection guide. Communication accessories. Communication accessory selection guide. Characteristics

Selection guide. Communication accessories. Communication accessory selection guide. Characteristics Communication accessories Selection guide There are 2 types of Sepam communication accessories: b communication interfaces, which are essential for connecting Sepam to the communication network b converters

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

Ocean Controls KT-5221 Modbus IO Module

Ocean Controls KT-5221 Modbus IO Module Ocean Controls Modbus IO Module 8 Relay Outputs 4 Opto-Isolated Inputs 2 Analog Inputs (10 bit) 1 PWM Output (10 bit) 4 Input Counters Connections via Pluggable Screw Terminals 0-5V or 0-20mA Analog Inputs,

More information

Data Acquisition Modules/ Distributed IO Modules

Data Acquisition Modules/ Distributed IO Modules User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332

More information

MULTIFUNCTION GRAPHICAL UNIT MGU 800

MULTIFUNCTION GRAPHICAL UNIT MGU 800 MULTIFUNCTION GRAPHICAL UNIT MGU 800 For display, recording and evaluation of process instruments signals (level, temperature, pressure, etc.) 3.5" TFT display, multi-language menu Variety of possible

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information

PLA 33. Power line analyzer. User and service manual. version 2.4

PLA 33. Power line analyzer. User and service manual. version 2.4 PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0

More information

PLC-K506 Series FEATURES DESCRIPTION FEATURES

PLC-K506 Series FEATURES DESCRIPTION FEATURES FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate With Up to 32 Devices DESCRIPTION

More information

Chapter 1. Chapter 2. STS Setup. Chapter 3. Decoder. Chapter 4. ICC Setup. Appendix A - B -

Chapter 1. Chapter 2. STS Setup. Chapter 3. Decoder. Chapter 4. ICC Setup. Appendix A - B - 1 Mottech 2 Wire AC Decoder Owner s Manual 2 Contents Chapter 1 Chapter 2 Chapter 3 Chapter 4 - - - - Install and wire the "254 2W" module STS Setup Decoder Programming and Setup ICC Setup Appendix A -

More information

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide 14/11/2006 V10 P.O.Box 24 Stanfield 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com

More information

WIRELESS MODBUS GATEWAY WGW410

WIRELESS MODBUS GATEWAY WGW410 WIRELESS MODBUS GATEWAY WGW410 The Tekon Wireless Modbus Gateway WGW410 is specifically designed to meet the most rigorous requirements of operation in the industrial process environments. Due to their

More information

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide 12/03/2012 V11.0 P.O.Box 164 Seven Hills 1730 NSW AUSTRALIA Tel: +61 2 96248376 Fax: +61 2 9620 8709 Email: proconel@proconel.com Web: www.proconel.com

More information

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Data Bulletin 0613IB1201 06/2012 Retain for future use. 0613IB1201 Modbus Communications System for Micrologic A, P, and H

More information

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418 Measuring Transducer MT4xx series Programmable AC Current Transducer MT418 o RMS AC current or frequency measurements o Current auto range measurements up to 12 A o Frequency measurement range 16 400 Hz

More information

PRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter

PRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter Telephone : 44 (0) 1245 428500 PRELIMIARY DATA SHEET RIF400 Series easywire Single and Three Phase Multifunction Energy Meter DI 96 panel mounted 330mV Input from easywire CTs (or /1A and /5A current transformer

More information

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate with up to 32 devices DESCRIPTION

More information

GS1 Parameter Summary Detailed Parameter Listings...4 9

GS1 Parameter Summary Detailed Parameter Listings...4 9 CHAPTER AC DRIVE 4 PARAMETERS Contents of this Chapter... GS1 Parameter Summary...............................4 2 Detailed Parameter Listings..............................4 9 Motor Parameters.........................................4

More information

current transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart

current transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart NK Technologies ADC series signal converters use sensor outputs (4 0 ma, 0 5 and 0 10 VDC) and convert these to digital RS485 outputs. The CTC series accept either 5 A secondary current from Analog to

More information

EM-72 Electricity Meters for Current Transformers

EM-72 Electricity Meters for Current Transformers Product sheet MT8.18 Meter EM72 EM-72 Electricity Meters for Current Transformers EM72 electricty meters have been designed for panel mounting to monitor electricity consumption and the quality of the

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide NTG MULTIFUNCTON GENERATOR PROTECTION RELAY 1 NTG Digital protection relay that integrates a number of functions required r for the protection of generators. It is used in power stations from gas, steam,

More information

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A

More information

Know your energy. Modbus Register Map EB etactica Power Bar

Know your energy. Modbus Register Map EB etactica Power Bar Know your energy Modbus Register Map EB etactica Power Bar Revision history Version Action Author Date 1.0 Initial document KP 25.08.2013 1.1 Document review, description and register update GP 26.08.2013

More information

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw isma-b-w0202 isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw www.gc5.com 1. Introduction... 4 2. Safety rules... 4 3. Technical specifications... 5 4. Dimension... 6 5. LED Indication...

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

Programmable AC Voltage Transducer MT416

Programmable AC Voltage Transducer MT416 Programmable AC Voltage Transducer MT416 RMS AC voltage or frequency measurements Voltage auto measurements up to 600 V L-N Frequency measurement 16 400 Hz AC or universal wide auiliary power 24 300 Vdc,

More information

Product type designation. General information. Hardware product version 01. Firmware version V2.6. Engineering with. update.

Product type designation. General information. Hardware product version 01. Firmware version V2.6. Engineering with. update. 6ES7313-6CF03-0AB0 SIMATIC S7-300, CPU 313C-2DP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 64 KBYTE WORKING MEMORY, FRONT CONNECTOR

More information

Programmable AC Current Transducer MT418

Programmable AC Current Transducer MT418 Programmable AC Current Transducer MT418 RMS AC current measurements Current auto range measurements up to 12 A Frequency measurement range 16 400 Hz AC or universal wide auiliary power supply range 24

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

DUCATI INSTRUMENTS COMPARISON TABLE

DUCATI INSTRUMENTS COMPARISON TABLE DUCATI INSTRUMENTS COMPARISON TABLE DUCA47 DUCA47-7 DUCA47-7-SP -96 P P 6 module DIN rail mounting instrument 7x7 panel mounting instrument 96x96 panel mounting instrument Low internal depth High-contrast

More information

Model FLSC-C3-XX. DC Powered Microprocessor Controlled Transmitter

Model FLSC-C3-XX. DC Powered Microprocessor Controlled Transmitter Model FLSC-C3-XX DC Powered Microprocessor Controlled Transmitter CONTENTS. Introduction----------------------------------------------------------------- 2 2. Specifications ---------------------------------------------------------------

More information

METERSUK. SmartLink D Y N A M i T E. EM415 MOD Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION. Single Phase Metering

METERSUK. SmartLink D Y N A M i T E. EM415 MOD Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION. Single Phase Metering METERSUK LTD s a l e s @ m e t e r s. c o. u k 0 1 5 2 4 5 5 5 9 2 9 Series Smart Energy Meter KEY FEATURES Single Phase Metering Single phase metering 4 din modules, Standard DIN rail Format (DIN43880)

More information

GCS20K. Conductivity Switch FEATURES

GCS20K. Conductivity Switch FEATURES Conductivity Switch FEATURES l 100V / 1A OPEN DRAIN OUTPUT WITH REVERSE POLARITY PROTECTION l RESOLUTION: BETTER THAN 2 ua l THE WHOLE SWITCH IS BUILT-IN THE HEAD - IT IS JUST THE PROBE AND A THIN CABLE

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Direct connection up to 65 A (WSx10x) Connection with current transformer (WSx30x) Industrial or meters

More information

APPA 300 Series. The Most User-Friendly High Performance Multimeter

APPA 300 Series. The Most User-Friendly High Performance Multimeter APPA 300 Series The Most User-Friendly High Performance Multimeter Throw Away the Manual... So Easy, So Simple Straight Forward... For basic application, simply to operate these keys... "LIGHT" "BAR" "DIGIT"

More information

SPAF 340 C Frequency Relay

SPAF 340 C Frequency Relay SPAF 0 C Frequency Relay User s manual and Technical description U n = 00V/0V/5V/0V 5 U f f < > < > df dt IRF SPAF 0 C 80...65 V ~ 8...80 V U aux OPERATION INDICATORS U U U SPCF D5 0 Stage Start Stage

More information

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00 NetBiter I/O Extender 4RO 6RTD 8DIO DAIO User Manual Revision 1.00 IntelliCom Innovation AB Linjegatan 3D SE302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 18 21 99 email info@intellicom.se www

More information

PRELIMINARY DATA SHEET. RI-F300 Series. easywire Single and Three Phase Multifunction Energy Meter (MID Certified) MID

PRELIMINARY DATA SHEET. RI-F300 Series. easywire Single and Three Phase Multifunction Energy Meter (MID Certified) MID RIF300 Series easywire Single and Three Phase Multifunction Energy Meter (MID Certified) DI 96 panel mounted 330mV Input from easywire CTs (or /1A and /5A current transformer input with TASSCTEWA module)

More information

TECHNICAL DATASHEET #TDAX Universal Input, Single Output Valve Controller CAN (SAE J1939)

TECHNICAL DATASHEET #TDAX Universal Input, Single Output Valve Controller CAN (SAE J1939) Features: TECHNICAL DATASHEET #TDAX021610 Universal Input, Single Output Valve Controller CAN (SAE J1939) 1 universal signal input (voltage, current, resistive, PWM, frequency or digital) 1 output: proportional

More information

Position Indicator with/without Limit Values

Position Indicator with/without Limit Values .1 Position Indicator with/without Limit Values Large, 6-digit, 14 mm high LED display Prescaler 2 variable limit values Eeasy direct selection by 2 function keys Rrelay output with two change-over contacts

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of telemetry modules provide remote monitoring

More information

IP1 Datasheet PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES DESCRIPTION CONNECTOR DETAILS

IP1 Datasheet PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES DESCRIPTION CONNECTOR DETAILS PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES 1 PWM Output (3.3V) 0 Hz 1 khz Single Channel 3.3V 12-bit ADC input for voltage sensing Optional automated PWM adjustment based on input voltage for standalone

More information

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming Energy Management Type WM14 DI version Protection degree (front): IP40 2 digital outputs 16 freely configurable alarms with OR/AD logic linkable with up to 2 digital outputs RS422/485 serial output (MODBUS-RTU),

More information

Transducing electrical quantities Iskra MIS d.d. Measuring Transducers. Features

Transducing electrical quantities Iskra MIS d.d. Measuring Transducers. Features Measuring Transducers Transducing electrical quantities Iskra MIS d.d. Measuring Transducers Features AC, DC POWER SYSTEM MEASUREMENT MICROPROCESSOR CONTROL HOUSING FOR DIN RAIL MOUNTING IN COMPLIANCE

More information

DMTME-96 2CSG133030R4022 M DMTME-I Operation and assembly instructions 2CSG163030R4022 M CSG445001D0202

DMTME-96 2CSG133030R4022 M DMTME-I Operation and assembly instructions 2CSG163030R4022 M CSG445001D0202 DMTME-96 2CSG133030R4022 M204675 DMTME-I-485-96 2CSG163030R4022 M204685 2CSG445001D0202 GB Operation and assembly instructions DMTME-96: three-phase multimeter for panel mounting, used also in singlephase

More information

Protection components

Protection components Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &

More information

DIGITAL SYNCHRONIZING UNIT KS3.2 SERVICE MANUAL. 144 x 144 x 77 mm C E R T I F I E D

DIGITAL SYNCHRONIZING UNIT KS3.2 SERVICE MANUAL. 144 x 144 x 77 mm C E R T I F I E D DIGITAL SYNCHRONIZING UNIT KS3.2 C E R T I F I E D 144 x 144 x 77 mm SERVICE MANUAL 1 CONTENTS 1. APPLICATION... 3 2. DELIVERY SPECIFICATION... 3 3. BASIC SAFETY REQUIREMENTS AND USER S SAFETY... 4 4.

More information

Excellent low-cost Process & Temperature Controllers

Excellent low-cost Process & Temperature Controllers C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200

More information

Communicative heating controller

Communicative heating controller UC100 Communicative heating controller Summary UC100 is a communicative room heating controller with one PWM output for control of a radiator or electrical heater. It can work autonomously, or in connection

More information

Energy Management Modular Power Analyzers Type WM2-96

Energy Management Modular Power Analyzers Type WM2-96 ISE, Inc. - 10100 Royalton Rd. - Cleveland, OH 44133 USA Energy Management Modular Power Analyzers Type WM2-96 - Tel: (440) 237-3200 - Fax: (440) 237-1744 - http://instserv.com Class 1 Modular power analyzer

More information

N30P DIGITAL PANEL METER

N30P DIGITAL PANEL METER N30P DIGITAL PANEL METER Features: NEW Measurement of single-phase network parameters: voltage, current, active, reactive and apparent power, cosj, tgj, j, frequency, active, reactive and apparent energy,

More information

High Performance Process & Temperature Controllers

High Performance Process & Temperature Controllers C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal

More information

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER AC DRIVE PARAMETERS. In This Chapter... CHAPTER AC DRIVE 4 PARAMETERS In This Chapter... GS2 Parameter Summary....................4 2 Detailed Parameter Listings.................4 11 Motor Parameters........................4 11 Ramp Parameters.........................4

More information

N1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES

N1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION N1040i is a quite versatile process indicator. With a wide list of input types - thermocouples, thermo-resistance, voltage and current the N1040i

More information

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW MicroManager Torque Mode CTCW/Loadcell Control Instruction Manual MM3000-CTCW Table of Contents 1. General Description... 5 2. Specifications... 5 2.1 Electrical... 5 2.2 Physical... 6 3. Installation...

More information

HITEK POWER XR KW X-RAY POWER SUPPLY MODULE

HITEK POWER XR KW X-RAY POWER SUPPLY MODULE HITEK POWER XR1000 1 KW X-RAY POWER SUPPLY MODULE Component power supply for industrial x-ray systems, elemental analysis equipment, x-ray diffraction spectrometers, and materials process monitoring applications

More information

Integra 1560 and 1580 Digital Transducer Systems

Integra 1560 and 1580 Digital Transducer Systems Integra 1560 and 1580 multi function transducers provide high accuracy

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

SPTO 1D2. Control module SPAC 3 C. User s manual and Technical description. U aux V _ V _. f n SPTO 1D2. I n = 1 / 5 A( I o)

SPTO 1D2. Control module SPAC 3 C. User s manual and Technical description. U aux V _ V _. f n SPTO 1D2. I n = 1 / 5 A( I o) SPTO 1D2 Control module User s manual and Technical description f n = 50 60 Hz I n = 1 / 5 A ( I ) I n = 1 / 5 A( I o) SPAC 3 C 2 5 IRF O I TEST INTERLOCK GAS PRESSURE MOTOR VOLTAGE STEP R L U aux 80...

More information

RS485 AMR Interface E350 User Manual

RS485 AMR Interface E350 User Manual Page 1 from 6 General Upgradable for future communication needs: flexible remote communication modules without breaking approval seal. The new series of modules for domestic use puts promises into practice,

More information

TECHNICAL DATASHEET #TDAX022420

TECHNICAL DATASHEET #TDAX022420 TECHNICAL DATASHEET TDAX022420 Four Inputs, Two Outputs Universal Valve Controller 2 Universal Signal Inputs, Magnetic Pick Up Sensor, or Encoder Inputs 2-3A High Side, Low Side or Half-bridge Outputs

More information

Absolute multi-turn hollow shaft encoder BOMH Dignalizer SSI

Absolute multi-turn hollow shaft encoder BOMH Dignalizer SSI features high resolution multi-turn encoder up to - 8 bit single-turn - 8 bit multi-turn interface programmable permanent self-test reference point programmable general data voltage supply 5 VDC (05C)

More information

USER MANUAL Z-8TC. Via Germania, Z.I. CAMIN PADOVA ITALY. Via Svizzera, Z.I. CAMIN PADOVA ITALY

USER MANUAL Z-8TC. Via Germania, Z.I. CAMIN PADOVA ITALY. Via Svizzera, Z.I. CAMIN PADOVA ITALY USER MANUAL Z-8TC SENECA s.r.l. Via Germania, 34 35127 Z.I. CAMIN PADOVA ITALY Via Svizzera, 17 35127 Z.I. CAMIN PADOVA ITALY Tel. +39.049.8705355 8705359 Fax. +39.049.8706287 Web site: www.seneca.it Technical

More information

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Čapkova 22 678 01 Blansko tel.: +420 516 416942, 419995 fax: +420 516 416963 R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Display module is designed for measuring the resistance, the signal from the

More information

B850 Boiler House Energy Monitor

B850 Boiler House Energy Monitor Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES AS440 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y697 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals.

ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals. 1 Definition ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals. 2 Operating Principle An electronic circuit

More information

ES-777-MV-P2_A1 03/01/10

ES-777-MV-P2_A1 03/01/10 ENGINEERING SPECIFICATION SYMCOM MODEL 777-MV-P2 Electronic Overload Relay PART 1 GENERAL 1.1 REFERENCES A. UL 508 Industrial Control Equipment Underwriters Laboratories B. IEC 60947 Low Voltage Switchgear

More information

Device/PLC Connection Manuals

Device/PLC Connection Manuals Device/PLC Connection Manuals About the Device/PLC Connection Manuals Prior to reading these manuals and setting up your device, be sure to read the "Important: Prior to reading the Device/PLC Connection

More information

I-7088, I-7088D, M-7088 and M-7088D User Manual

I-7088, I-7088D, M-7088 and M-7088D User Manual I-7088, I-7088D, M-7088 and M-7088D User Manual I-7000 New Features 1. Internal Self Tuner 2. Multiple Baud Rates 3. Multiple Data Formats 4. Internal Dual WatchDog 5. True Distributed Control 6. High

More information

Energy Management Modular Smart Power Transducer Type SPT-90

Energy Management Modular Smart Power Transducer Type SPT-90 Energy Management Modular Smart Power Transducer Type SPT-90 Class 0.5 (current/voltage) 16-bit µp-based modular smart power transducer Measurements of: W, Wavg, VA, VAr, PF, Wh, VAh, VArh, Amax (among

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

CoolEx User Manual 2008 XDIMAX LTD. Revision 1.0

CoolEx User Manual 2008 XDIMAX LTD. Revision 1.0 CoolEx User Manual Revision 1.0 2 CoolEx User Manual Table of Contents Foreword 0 Part I Overview 3 Part II Configuration and Setup 4 1 Terminals Layout... 4 2 Modbus Address... Switch 4 Part III Functional

More information

DIN Rail Kilowatt Hour Energy Meters

DIN Rail Kilowatt Hour Energy Meters DIN Rail Kilowatt Hour Energy Meters Single Phase DIN Rail Kilowatt Hour Energy Meters DRK-1PPO-240 Single Phase 230V - 15A Direct Connected, Pulse Output This innovative two DIN module kilowatt hour energy

More information

Energy Management. Type WM14-96 Basic Version. Product Description. How to order WM14-96 AV5 3 D PGX. Type Selection. Input specifications.

Energy Management. Type WM14-96 Basic Version. Product Description. How to order WM14-96 AV5 3 D PGX. Type Selection. Input specifications. Energy Management Power Analyzer Type WM-96 Basic Version Optional dual pulse output Alarms (visual only) V, An Optional galvanically insulated measuring inputs Product Description 3-phase power analyzer

More information

AC 01.2 Modbus TCP/IP

AC 01.2 Modbus TCP/IP General information Actuator controls AC 01.2 for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR.2 type range with interface. Features and functions Power

More information

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use Wireless New Products... New Solutions The range of telemetry modules provide remote monitoring and control by radio or twisted-pair wire, over short or long distances. Transducer signals connected at

More information

maxon document number:

maxon document number: maxon document number: 791272-04 1 Table of contents... 2 2 Table of figures... 3 3 Introduction... 4 4 How to use this guide... 4 5 Safety Instructions... 5 6 Performance Data... 6 6.1 Motor data... 6

More information

P/N: AX TECHNICAL DATASHEET #TDAX Single Input, Dual Output Valve Controller 1 Universal Input, +5V reference CAN (SAE J1939)

P/N: AX TECHNICAL DATASHEET #TDAX Single Input, Dual Output Valve Controller 1 Universal Input, +5V reference CAN (SAE J1939) TECHNICAL DATASHEET #TDAX022000 Single Input, Dual Output Valve Controller 1 Universal Input, +5V reference (SAE J1939) Features: 1 universal signal input 2 proportional or on/off outputs up to 3 A User

More information

BATCHMATE 1500 Batch Control Computer Technical Bulletin

BATCHMATE 1500 Batch Control Computer Technical Bulletin TS-5(C) BATCHMATE 5 Batch Control Computer Technical Bulletin DESCRIPTION The BATCHMATE features an 8 digit.55-in. alphanumeric LED display. The pulse input model will accept up to 2, pulses per second

More information

FM COUNTER MODULE

FM COUNTER MODULE FM 450-1 COUNTER MODULE Function The module off-loads the CPU by: Direct connection of one incremental encoder per channel Direct connection for gate signals (light barrier, etc.) using integrated digital

More information

Ranges >500 mm: L10 = ±0.10 % f.s. L02 = ±0.02 % f.s. Ranges 500 mm: L10 = ±0.5 mm L02MM = ±0.2 mm Repeatability ±3 µm

Ranges >500 mm: L10 = ±0.10 % f.s. L02 = ±0.02 % f.s. Ranges 500 mm: L10 = ±0.5 mm L02MM = ±0.2 mm Repeatability ±3 µm Flat Profile Housing with Analog POSICHRON position sensor Only 12 mm height and 36 mm width Protection class IP64 Measurement range 0... 100 to 0... 5750 mm Absolute position measurement Ultra flat profile

More information

Universal measuring transducer

Universal measuring transducer Universal measuring transducer EM4000 Compact housing High accuracy Full galvanic separation MODbus (RS232/RS485) 3 Analogue + 1 Pulse output Direct voltagemeasurement up to 690V 48 hour service EXW ELEQ

More information

SUPPLY NETWORK ANALYZER CVM-96 SERIES

SUPPLY NETWORK ANALYZER CVM-96 SERIES SUPPLY NETWORK ANALYZER CVM-96 SERIES (Power Demand) INSTRUCTION MANUAL ( M 981 326 / 00B - GB) (c) CIRCUTOR S.A. ----- Supply network analyzer CVM-96 ------ User's manual --- Page No. 1 CVM-96 SUPPLY

More information

PLUS WGW420 WIRELESS GATEWAY 868MHz

PLUS WGW420 WIRELESS GATEWAY 868MHz PLUS WGW420 WIRELESS GATEWAY 868MHz REF.: PA164510210 An easy-to-use system that allows wireless reception and transmission of any process variables that could be transformed into an analogue signal. PLUS

More information

2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES

2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES 2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES Medium-voltage rack-mount power supplies Page 2 The MV2000 series high-performance, medium output

More information

Installation and Operating Instructions

Installation and Operating Instructions Energy Division Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Our commitment. Your advantage. Contents Page 1 Introduction 4 1.1 Measurement Capabilities 5 1.2

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 469 FREQUENTLY ASKED QUESTIONS 1 Can not communicate through the front port RS232 Check the following settings Communication port on your computer ( com1, com2 com3 etc ) Parity settings must match between

More information