1 Tele- and Radio Research Institute WARSAW Mikroprocesor Unit for Protection, Measurements and Control MUPASZ COMPACT W01/W02/3W3 User Manual WARSAW 2005

2

3 MUPASZ COMPACT W01/W02/3.W3 User Manual The manufacturer reserves the right to alter the construction of the equipment and its performance without prior notice The Tele- and Radio Research Institute s The Research Centre for IT Systems and Hardware Applications Warszawa ul. Ratuszowa 11 tel/faks: (48-22) tel/faks: (48-22) energetyka@itr.org.pl mup_com_w01w023w3_en

4 MUPASZ COMPACT W01/W02/3.W3 User Manual

5 MUPASZ COMPACT W01/W02/3.W3 User Manual 1 Contents 1 General information Subject matter of the manual Purpose of the manual Functional features of the MUPASZ COMPACT W01/W02/3.W Technical parameters General ENVIRONMENTAL CONDITIONS INPUT CIRCUITS OUTPUT CIRCUITS REED CONTACT TYPE OUTPUT CIRCUIT OF MAGNETIC FLAG POWER ADAPTER ELECTRIC STRENGTH OF INSULATION CLASS OF PROTECTION CONNECTING TERMINALS REAL-TIME CLOCK DIMENSIONS OF THE DEVICE WEIGHT Accuracy of measurements Accuracy of measurements for tripping thresholds Disengagement of the breaker Protections (type, range) OVERLOAD PROTECTIONS nd stage independent overcurrent protection (I>) Inverse time overcurrent protection (I> zal) PROTECTION AGAINST PHASE TO PHASE SHORTS nd stage independent overcurrent protection (I>>) PROTECTIONS AGAINST SHORT-TO-EARTH FAULTS Overcurrent short-to-earth protection (I 0 >) Directional (angular) protection against short-to-earth faults (I 0 >k)* SPECIAL PROTECTIONS Technological protections 1, Technical characteristics of the unit MUPASZ COMPACT W01/W02/3.W Bay types Protections INTRODUCTION OVERLOAD PROTECTIONS nd stage independent overcurrent protection (I>) Reverse time overcurrent protection (I> zal) PROTECTION AGAINST PHASE TO PHASE SHORTS nd stage independent overcurrent protection (I>>) PROTECTIONS AGAINST EARTH FAULTS Overcurrent earth fault protection (I 0 >) Directional (angular) earth fault protection (I 0 > k) SPECIAL PROTECTIONS Technological protections 1, Measurements GENERAL REMARKS Circuit breaker control GENERAL REMARKS Warning alerts Operation Description of connections Front panel Programming Unit OPERATION OF THE PROGRAMMING UNIT...18 mup_com_w01w023w3_en

6 2 MUPASZ COMPACT W01/W02/3.W3 User Manual Introdution Programming Viewing of events by means of the programming module Output cancellation Readout of real-time clock and setting of clock Maintenance and service Transportation Storage Enclosure Tables of connectors Diagram for connection of the MUPASZ COMPACT W01/W02/3.W Dimensions of the MUPASZ COMPACT W01/W02/3.W Aktualizacja

7 MUPASZ COMPACT W01/W02/3.W3 User Manual 3 1 General information 1.1 Subject matter of the manual This User Manual is intended to describe technical construction and operation principles of the Microprocessor Unit for Protection, Measurements and Control MUPASZ COMPACT W01 i MUPASZ COMPACT W02. These devices differ from each other in functional features. The MUPASZ COMPACT 3.W3 additionally comprises announcements which warn users about to active second overload protection and second protection against short-toearth faults. The Manual comprises information about technical data and functional features. 1.2 Purpose of the manual MUPASZ COMPACT W01/W02/3.W3 is dedicated for protection in MV (Medium Voltage) outlet bays. 1.3 Functional features of the MUPASZ COMPACT W01/W02/3.W3 Operating current power supply; additional possibility of 24V DC power supply; Magnetic flag signalling tripping of the relay without the additional power supply; Polarized bi-stable output relays; Bi-stable inputs responding to closing external contacts; Possible programming of the unit also in the unpowered state; Battery operated Programming Unit; Clearing alarms by means of the Programming Unit or by pressing a key on the front panel the user may clear alarms which inform about protection tripping and active outputs; Implemented protections: - definite time and inverse time current overload; - phase overcurrent; - current ground fault; - directional current ground fault; - technological; Measurements: - 3 phase currents; - residual current; - residual voltage; Event recording the last protection tripping is; Indicators and signalling units; - alphanumeric display showing phase and residual currents I 1, I 2, I 0, - power on, - magnetic flag indicator showing tripping of any protection, mup_com_w01w023w3_en

8 4 MUPASZ COMPACT W01/W02/3.W3 User Manual 2 Technical parameters PN-EN 50263:2004 Electromagnetic compatibility (EMC) Product standard for measurnig relays and protection equipment PN-EN :2005 Electrical relays. Insulation coordination for measuring relays and protection equipment Requirements and tests. PN-EN 61293:2000 Parking of electrical equipment with ratings related to electrical supplysafety requirement. PN-EN 60529:2003 Degrees of protection provided by enclosures (IP Code) Requirements for protection devices Electrical relays. Measuring relays PN-EN :2000 and protection equipment Environmental testing Test A: Cold PN-IEC A1+A2:1996 /Ap1: C/16 h Test B: Dry heat PN-EN : C/16 h Test Cab: Damp heat, steady PN-EN :2002(U) +40 C; 95% rh /4days state Mechanical test Vibration test PN-EN :1999 Class 1 Schock and bump tests PN-EN :2000 Class 1 Seismic tests PN-EN :1999 PN-EN :1999/Ap1:2002 Electromagnetic compatibility Electrical relays PN-EN :2004 Class 1 Immunity Electrostatic discharge tests PN-EN :1999 4kV contact 8kV air Electomagnetic field immunity test PN-EN :2002 Level 3 10V/m Electrical fast transient/burst immunity test PN-EN :2003 (U) Class B Supply 2kV/5kHz ports in/out 2kV/5kHz Surge immunity test PN-EN :2003 (U) 4kV L-PE 4kV N-PE L-N 2kV Conducted disturbances induced PN-EN :2004 Level 3 by radio frequency fields 1 MHz burst disturbance tests PN-92/E Class III 2,5kV Emission Electromagnetic emission PN-EN :2002 Quasi peak medium Conduction f=0,15-0,5mhz <79dB <66dB f=0,5-30mhz <73dB <60dB Emission quasi peak f=30-230mhz < 40dB f= mhz <47dB Aktualizacja

9 MUPASZ COMPACT W01/W02/3.W3 User Manual GENERAL ENVIRONMENTAL CONDITIONS Ambient temperature Storage temperature Max. relative humidity C C no condensation or water, formation of hoar, frosting nor icing INPUT CIRCUITS Power supply current circuits 1A 50Hz Secondary rated current of the suppying transformer I nz Rated frequency Current-carrying capacity: - long term 2I nz - short time (1 s) 20I nz Power consumption 10VA/phase at I = I nz Electric current circuits for protecting against phase-to-phase shorts Rated current I n Primary rated current of the current transformer I n Rated frequency current-carrying capacity: - long term 2I n 5A A, every 1A 50Hz - short time (1 s) 20I n Power consumption of the electric current inputs <1VA/phase at I = I n Electric current circuit for protecting against fault-to-earth events Rated current I 0n : 1A Ferranti transformer transformation ratio 120 current-carrying capacity: - long term 5I 0n - short time (1 s) 20I 0n Power consumption of electric current inputs <1VA/phase at I = I 0n Phase to-phase voltge citcuits with U 0 Rated voltage U 0n 100V Voltage carrying capacity: - long term 2U 0n Power consumption <0,5VA at U = U 0n Two-state (binary) inputs Controlling current 2..10mA permissible length of wire do 100m (0,75mm 2 ) mup_com_w01w023w3_en

10 6 MUPASZ COMPACT W01/W02/3.W3 User Manual Current transformers Recommended TRANSFORMEX current relays: TypE PP-15W 200/ 5/ 1 or 600/ 5/ 1 Core I: S2n= 1VA, class 10P, ALF 20 measuring Core II: S2n= 10VA, class 1, FS 2 supplying OUTPUT CIRCUITS REED CONTACT TYPE Two-state (binary) outputs - reed contact type Output relays: - switched power 2kVA/ 8A/ 380V AC 150W/ 250V DC OUTPUT CIRCUIT OF MAGNETIC FLAG Tripping energy 0,1J Output voltage 10V POWER ADAPTER With operation current external voltage power consumption with external voltage 0,2I n (one phase) 24V DC (18..36V DC) 2W ELECTRIC STRENGTH OF INSULATION Alternating voltage 2kV/ 50Hz/ 60s lub 3kVDC/ 60s Surge voltage 4kV/ 1,2µs/ 50µs resistance of insulation przy 500V >100MΩ CLASS OF PROTECTION From the front panel with protected socket for the Programming Unit From the connectors IP 54 IP 20 (IP 30 with connectors) CONNECTING TERMINALS Connecting terminals WAGO Cross-section of connecting wires 0,08..2,50mm mm Aktualizacja

11 MUPASZ COMPACT W01/W02/3.W3 User Manual REAL-TIME CLOCK accuracy better than 1 minute per month Note: Before putting the unit in operation set the real time clock and correct its setting regularly (see p ) DIMENSIONS OF THE DEVICE Width: Height: Depth: 195mm 150mm 103mm WEIGHT Weight ca.2,5kg 2.2 Accuracy of measurements current 2,5% voltage 2,5% 2.3 Accuracy of measurements for tripping thresholds phase overcurrent protections 3% earth fault protections 3% Note: Accuracy is specified with respect to the measured value, provided for the measured parameter should fall within the limits from 0.2 to 2 times of its rated value. 2.4 Disengagement of the breaker Time to operating 1,2s Note: for operation current supply 0,2I n one phase mup_com_w01w023w3_en

12 8 MUPASZ COMPACT W01/W02/3.W3 User Manual 2.5 Protections (type, range) OVERLOAD PROTECTIONS ND stage independent overcurrent protection (I>) Parameter Range Remarks Activity active/ inactive Action disengagement not to set Tripping current I 0,2..2I n, with the step 0,01I n Delay time T 0..5s, with the step 100ms Own response time t ms not to set Operation time T + t Inverse time overcurrent protection (I> zal) Parameter Range Remarks Activity inactive/ active Action disengagement not to set Tripping current I 0,2..2I n, with the step 0,01I n Delay time T 0..5s, with the step 100ms result of formula Own response time t ms not to set Operation time T + t Curve Very inverse not to set PROTECTION AGAINST PHASE TO PHASE SHORTS ND stage independent overcurrent protection (I>>) Parameter Range Remarks Activity active not to set Action disengagement not to set Tripping current I 2..20I n, with the step 0,1I n Delay time T 0..2s, with the step 100ms Own response time t ms not to set Operation time T + t PROTECTIONS AGAINST SHORT-TO-EARTH FAULTS Overcurrent short-to-earth protection (I 0 >) Parameter Range Remarks Activity inactive/ active Action disengagement not to set Tripping current I 0,2..2I 0n, with the step 0,1I 0n Delay time T 0..5s, with the step 100 ms Own response time t ms not to set Operation time T + t Aktualizacja

13 MUPASZ COMPACT W01/W02/3.W3 User Manual Directional (angular) protection against short-to-earth faults (I 0 >k)* Parameter Range Remarks Activity inactive/ active Action disengagement not to set Tripping current I 0,2..2I 0n, with the step 0,1I 0n result of formula Delay time T 0..5s, with the step 100ms Own response time t ms not to set Operation time T + t α- angle of maximum sensitivity 0..90, with the step 1 * for U 0 > 0,2 U 0n SPECIAL PROTECTIONS Technological protections 1, 2 Parameter Range Remarks Activity inactive/ active Action disengagement not to set Delay time T 0s not to set mup_com_w01w023w3_en

14 10 MUPASZ COMPACT W01/W02/3.W3 User Manual 3 Technical characteristics of the unit MUPASZ COMPACT W01/W02/3.W3 3.1 Bay types MUPASZ COMPACT W01/W02/3.W3 may be used in MV outlet bays. 3.2 Protections INTRODUCTION Every individual protecting facility, available with the unit, needs to be activated (except I>>, always active). Activation is carried out by means of the Programming Unit. Unless detailed specification of the protection states otherwise, one of the following events may occur as a consequence of protection tripping: switching the bay off, i.e. disengagement of the circuit breaker (after switching off by the protection it is not possible to re-close the breaker before the magnetic flag is cancelled). The information about tripping of the protection is recorded into the event log (the last event). The principle of protection s operation is described in the following example: The setting values of the current overload protection I>: I = 1 I n, T = 1 s. Breaking of the circuit will take place if the set value of 1 I n is exceeded over the set period of 1 s OVERLOAD PROTECTIONS Note: In the MUPASZ COMPACT 3.W3 only one overload protection may be active: either the time constant or the reverse time one. If a second overload protection is to be activated the operator must confirm deactivation of the first one before ND stage independent overcurrent protection (I>) It is an overcurrent-type protection; its adjustable duration time does not depend on the electric current value Reverse time overcurrent protection (I> zal) It is an overcurrent-type protection with a time dependent (very inverse). current characteristics. Variation of electric current that flows through the protected line affects the tripping time of the protection. Therefore the time-delay interval depends on the value of the level of exceeding of the threshold limit. In case when the value of the electric current remains constant the time can be calculated by means of the following formula: where: I - electric current during tripping; T 10, I r - adjustable parameters; α=1, β=9 T = T I I r 10 α β 1 Aktualizacja

15 MUPASZ COMPACT W01/W02/3.W3 User Manual 11 To better understand the setting procedure the diagram below contains families of characteristic curves for the protection I > zal t[s] The time vs. current characteristic curve for the overcurrent dependent protection Charakterystyka prądowo-czasowa zabezpieczenia nadprądowego zależnego α =1 β = T10=5s 1 T10=2s T10=1s T10=0.5s 0.1 T10=0.2s T10=0.1s _I 20 I r PROTECTION AGAINST PHASE TO PHASE SHORTS ND stage independent overcurrent protection (I>>) It is an overcurrent-type protection; its adjustable duration time does not depend on the electric current value. The protection is always active PROTECTIONS AGAINST EARTH FAULTS Note: The Ferranti transformer transformation ratio is assumed 120 and the secondary residual current I 0n (rated residual) is assumed 1 A. Both these parameters are constant and are not editable. Note: In the MUPASZ COMPACT 3.W3 it is possible to activate only one ground fault protection: either the overcurrent earth fault or the directional the overcurrent earth fault. If a second earth fault protection is to be activated the operator must confirm deactivation of the first one before Overcurrent earth fault protection (I 0 >) It is an independent overcurrent-type protection with time delay. It is tripped by neutral current I 0 from Ferranti transformer. mup_com_w01w023w3_en

16 12 MUPASZ COMPACT W01/W02/3.W3 User Manual Directional (angular) earth fault protection (I 0 > k) It is the zero-current protection (either for reactive or active current) with time delay. The start-up current is calculated by the formula: I = I m /cos(φ 0 +α) where: I m - electric current of maximum sensitivity (setting); φ 0 - phase angle between U 0 i I 0 ; α - setting for the angle. However, for reliable tripping of the protection it is required that the zero voltage U 0 would be not less than 15% U N. If the phase angle for the protection is set to zero, the protection can be tripped for the actual phase distance between voltages and currents within the 1 st and 4 th quadrant of the co-ordinates. It the preset angle is different than zero tripping is also possible for the 3 rd quadrant. The forthcoming diagram of current vs. phase characteristic curve for the angular protection against short-to-earth faults can be useful to facilitate the setting procedure. On the phase plane and for two preset values of the phase angle α = 0 and α = 90 o the diagram exhibits areas where the protection is applicable or not. Diagram Charakterystyka of current vs. phase prądowo-fazowa characteristic zabezpieczenia curve for the angular protection against kątowego short-to-earth ziemnozwarciowego faults for(dla the phase α=0): angle α = 0 I r I m φ 0 Aktualizacja

17 MUPASZ COMPACT W01/W02/3.W3 User Manual 13 α = 0 ο Non-tripping area Im 5 I max 1 st quadrant Tripping area 2 st quadrant γ =78,46 o I 0 I max U 0 Re 3 st quadrant γ =78,46 o - 5 I max 4 st quadrant α = 90 o Im 2 st quadrant Non-tripping area 1 st quadrant - 5 I max 5 I max Re U 0 I max I 0 3 st quadrant 4 st quadrant γ =78,46 o γ =78,46 o Tripping area mup_com_w01w023w3_en

18 14 MUPASZ COMPACT W01/W02/3.W3 User Manual SPECIAL PROTECTIONS Technological protections 1, 2 Technological protections react on double-state signal and are activated by shorting of the external contact connected to the technological protections input (contacts 3,4 or 5,6). After the protections activation, breaker switch opens. 3.3 Measurements GENERAL REMARKS The device MUPASZ COMPACT W01/W02/3.W3 is equipped with hardware and software facilities that perform fast measurements for the purpose of protection. Selected measured values can be presented on-line on the display of the device that is placed on its front panel. In the mode of measurements the following information is displayed: - symbolic denomination of the measured parameter; - value; - unit. The displayed values refer to the primary side of the measuring transformers. Display shows results of the measurements of the phase currents I 1, I 2, I 3. The measurement cycle takes 1 second. That is why the content of the display is automatically refreshed within the same period. Please refer to par PROGRAMMING UNIT for detailed instructions how to use the Programming Unit. 3.4 Circuit breaker control GENERAL REMARKS The circuit breaker that is installed in each bay of the switchgear can be controlled by the MUPASZ COMPACT W01/W02/3.W3 through magnetic tripping device after tripping of a protections (e.g. disengagement during a fault). Breaker switch opening impulse is supplied three times in a second. It is to increase the reliability of breaker switch activation. 3.5 Warning alerts For signalling purposes the MUPASZ COMPACT W01/W02/3.W3 device is equipped with signal lamps 24V POMOCNICZE and magnetic memory status indicator on the front panel. During suppling with external voltage diode 24V POMOCNICZE is lit. Status indicator ZABEZPIECZNIE is lit (yellow) after tripping of a protection. Aktualizacja

19 MUPASZ COMPACT W01/W02/3.W3 User Manual 15 4 Operation 4.1 Description of connections Designation of individual connectors as well as analog inputs and outputs is shown in the diagram for connetions (p.5.2). Specification of connectors is included in Tables 1 and 2 (p.5.1) 4.2 Front panel MUPASZ COMPACT W01/W02/3.W3 front panel contains: - text display 2-lines 16-characters; - 24 V DC external power supply signal lamp; - yellow magnetic flag, activated with one of the protections; - flag and double-state output cancellation button (activated with the power supply); - Programming Unit plug-in socket. Display shows current measurement results I 1, I 2 i I 3. mup_com_w01w023w3_en

20 16 MUPASZ COMPACT W01/W02/3.W3 User Manual After supplying the power, display shows the following: and after a short period of time: Value of indicated currents I 1, I 2 i I 3 will change depending on their actual value. After protection activation, front panel signal flag will change from black to yellow. Protection type can be verified using Programming Unit s REJESTRATOR function. After plugging-in the Urogramming Unit to the PROGRAMATOR socket (located at the unit s front panel) the display will change: Aktualizacja

21 MUPASZ COMPACT W01/W02/3.W3 User Manual Programming Unit The Programming Unit is powered using 4 AA 1,5V batteries, or AA NiCd or NiMH rechargeable batteries. To check the battery power level press the BAT button located at the Programming Unit. After pressing the BAT button, a diode located near the button will light and the display will activate, indicating that the batteries are charged enough to use the Programming Unit. If the diode does not light, the batteries shall be replaced. Caution: It is possible that the battery power level check will show that the batteries are charged, but the programming unit does not operate or the unit restarts all the time. In this case it is also necessary to replace the batteries. All the parameters of protections are stored in the built-in memory unit of the MUPASZ COMPACT W01/W02/3.W3 device. The parameters can be modified by an authorized person only. Prior to carry out any of the operations mentioned above the programming module plug must be inserted into the socket marked as PROGRAMATOR ( Programming Unit ) on the front panel of the MUPASZ COMPACT W01/W02/3.W3 unit. mup_com_w01w023w3_en

22 18 MUPASZ COMPACT W01/W02/3.W3 User Manual OPERATION OF THE PROGRAMMING UNIT Introdution MUPASZ COMPACT W01/W02/3.W3 unit may realize required protections. In order to configure the MUPASZ COMPACT W01/W02/3.W3 protections it is necessary to program the unit. Programming is performed using an external Programming Unit. The Programming Unit is connected to the MUPASZ COMPACT W01/W02/3.W3 through a dedicated socket located at the front panel. Initial programming shall be fully performed prior to activation of the switching station and may be performed outside the switching station. Programming MUPASZ COMPACT W01/W02/3.W3 does not require power supply. During further operation, settings of MUPASZ COMPACT W01/W02/3.W3 may be readjusted to meet the current operational requirements with closed breaker switch. Those changes shall be performed with caution to prevent random breaker switch activation. It is recommended to activate/deactivate protections with the breaker switch opened. Programming process does not hold back normal operation of the MUPASZ COMPACT W01/W02/3.W3. Programmable values: initial current measuring transformer nominal value; protections settings: - tripping values, - delay values, - activity / inactivity; system clock Programming Programming of the MUPASZ COMPACT W01/W02/3.W3 includes setting parameters for the following configuration parameters: Date and time Ranges of measured I n configuration of protectins year (4 digits), month, day, hour, minute A, with the step of 1A - Activity; - Delay time; - Tripping current. Using Programming Unit s tree is easy and subordinated to the following general rules: - using 1..9 keys you can enter the further tree level; - using WYCOFANIE key you can enter the previous tree level; - new data are entered at the cursor s position as a number from the proper range. After plugging-in the Programming Unit s plug into the front panel dedicated socket, display will show the first part of the main menu tree. Aktualizacja

23 MUPASZ COMPACT W01/W02/3.W3 User Manual 19 Display shows 4 lines. It is a general rule. If there are more than 4 items in the menu (as shown above) it is indicated by the arrow symbol or. Press the key on the programming unit to move to the 5 th item (5-NOMINAŁY). Use key to scroll the display upwards. If there are only 4 menu items as for instance in the protection parameters menu (as shown below), to enter the further menu tree level it is necessary to press numerical key corresponding to the item. You can cancel your choice by pressing WYCOFANIE key. To cancel edited parameter changes, it is required to finish the edition process, press the ZATWIERDZENIE button and press WYCOFANIE while the display shows ZAT- WIERDZIĆ DANE?. The edited parameter shall not be stored. Example To change the current fault protection activation delay time value T, which is always active, press 1-ZABEZPIECZENIA in the main menu. Display will show as follows: mup_com_w01w023w3_en

24 20 MUPASZ COMPACT W01/W02/3.W3 User Manual Pressing the programming unit s 1 1-I>> key will result in displaying tripping current and required delay time T edition window. The cursor indicates the edited parameter (that can be changed or not) which can be confirmed with ZATWIERDZENIE button. To leave the tripping current value unchanged and to move to the delay time T value press ZATWIERDZENIE button on the programming unit. Cursor indicates the next parameter. Enter the required delay time T value (including decimal period and decimal fraction value) and press the ZATWIERDZENIE button. When the ZATWIERDZIEĆ DANE? is displayed, pressing ZATWIERDZENIE or WYCOFANIE will cause confirmation or cancellation of the edited value respectively Viewing of events by means of the programming module To read the latest event registered by the MUPASZ unit, press 2 2-REJESTRATOR button in the main menu tree. The display will show event date and information window. The demonstration register window shows the following: Aktualizacja

25 MUPASZ COMPACT W01/W02/3.W3 User Manual Output cancellation To cancel the magnetic flag signal on the front panel, press 3 3-KASOWANIE WYJ. key. The output relay contact will be opened Readout of real-time clock and setting of clock To read the system clock, enter 4-ZEGAREK window and press 1 1-ODCZYT key on the programming unit. To change/set the system clock, enter 4-ZEGAREK window and press 1 2- NASTAWA key on the programming unit. The display shows the following edition window. After setting the year (ROK) value, the display shows month (MIESIAC), day (DZIEN), hour (GODZINA) and START successively. To set the new clock values confirm the START. Edition and confirmation of the clock values is similar to the protection parameters edition. Confirmation will result in setting the new clock values. 4.4 Maintenance and service MUPASZ COMPACT W01/W02/3.W3 does not require any special maintenance, whereas service and inspection may only be carried out by the manufacturer. 4.5 Transportation MUPASZ COMPACT W01/W02/3.W3 may be transported if protected against mechanical damages. 4.6 Storage MUPASZ COMPACT W01/W02/3.W3 may be stored at temperatures C mup_com_w01w023w3_en

26 22 MUPASZ COMPACT W01/W02/3.W3 User Manual 5 Enclosure 5.1 Tables of connectors TABLE 1. Connector GN1 (grey). Contours of alternating current and voltage No of contact Designation 1 zero-sequence voltage 3U0 (m) 2 zero-sequence voltage 3U0 (n) 3 zero-sequence electric current 3I0 (k from the Ferranti transformer) 4 zero-sequence electric current 3I0 (l from the Ferranti transformer) 5 electric current for the phase l3 (l) measurement 6 electric current for the phase l3 (k) measurement 7 electric current for the phase l3 (l) supply* 8 electric current for the phase l3 (k) supply * 9 electric current for the phase l2 (l) measurement 10 electric current for the phase l2 (k) measurement 11 electric current for the phase l2 (l) supply * 12 electric current for the phase l2 (k) supply * 13 electric current for the phase l1 (l) measurement 14 electric current for the phase l1 (k) measurement 15 electric current for the phase l1 (l) supply * 16 electric current for the phase l1 (k) supply * * When the supplying is 24VDC only then connecting of supply input is not necessary. TABLE 2. Connector GN2 (orange). Power supply, Two-state (binary) inputs and outputs, Breaker control. No of contact Designation 1 supply (minus) 2 supply (plus) 3 Temperature input (technological protection 1) 4 Temperature input (technological protection 1) 5 Input of the fire alarm input (technological protection 2) 6 Input of the fire alarm input (technological protection 2) Trip coil (plus) 14 Trip coil (minus) Output 1 active from overcurrent and technological protectin 18 Output 1 active from overcurrent and technological protectin 19 Output 2 active from technological protectin 20 Output 2 active from technological protectin TABELA 3. The way of operation contact output No of output Action of the technological Action of the overcurrent protection protection Out1 excited excited Out2 excited Not excited Aktualizacja

27 MUPASZ COMPACT W01/W02/3.W3 User Manual Diagram for connection of the MUPASZ COMPACT W01/W02/3.W3 mup_com_w01w023w3_en

28 24 MUPASZ COMPACT W01/W02/3.W3 User Manual 5.3 Dimensions of the MUPASZ COMPACT W01/W02/3.W3 Aktualizacja

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

SPECIFICATION FOR OVERCURRENT RELAYS

SPECIFICATION FOR OVERCURRENT RELAYS SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM]

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM] Feature Suit for LV/ HV voltage system Compact design with all real-time measurement Consist of basic unit and optional modules 10 years back-up of integrated energy data Large LCD, high brightness High

More information

Zelio Control Measurement Relays

Zelio Control Measurement Relays Selection Guide Application Voltage control Current control Functions 3-phase Single-phase and d.c. Integrated current transformer - Overvoltage and between phases - Overvoltage and between phases and

More information

PART NUMBERING SYSTEM

PART NUMBERING SYSTEM Plug-In Timer 11 pins Multifunction or monofunction Compact body for space saving Wide time range (from 0.5 seconds to 10 days delay) Universal power supply (12-240 Vz) 1 or 2 relay outputs (SPDT / Changeover)

More information

PART NUMBERING SYSTEM

PART NUMBERING SYSTEM Plug-In Timer pins Multifunction or monofunction Compact body for space saving Wide time range (from 0. seconds to 0 days delay) niversal power supply (-0 Vz) or relay outputs (SPDT / Changeover) Protective

More information

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring The first Real-Time Protection and Automation platform that can be adapted to a wide variety of applications. While

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Instantaneous Overcurrent Relay

Instantaneous Overcurrent Relay Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type

More information

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics 9ROWDJHUHVWUDLQWRYHUFXUUHQW UHOD\DQGSURWHFWLRQ DVVHPEOLHV 5;,6.+DQG 5$,6. 509 033-BEN Page 1 Issued: September 2001 Changed since: June 1999 Data subject to change without notice (SE970171) (SE970896)

More information

METRAClip87 and 88 Clamp Multimeters

METRAClip87 and 88 Clamp Multimeters 3-349-795-03 1/7.14 Current and frequency measurement via clamp meter: METRAClip87: 1500 A AC TRMS and 1500 A DC METRAClip88: 2000 A AC TRMS and 3000 A DC Multimeter functions via connector sockets: V

More information

Test Specification for Type Approval

Test Specification for Type Approval A2 (1991) (Rev.1 1993) (Rev.2 1997) (Rev. 2.1 July 1999) (Rev.3 May 2001) (Corr.1 July 2003) (Rev.4 May 2004) (Rev.5 Dec 2006) (Rev.6 Oct 2014) Test Specification for Type Approval.1 General This Test

More information

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual

More information

PowerPact H-, J-, and L-Frame Circuit Breakers General Information. Vibration. Electromagnetic disturbances. Tropicalization

PowerPact H-, J-, and L-Frame Circuit Breakers General Information. Vibration. Electromagnetic disturbances. Tropicalization General Information Vibration PowerPact H-, J-, and L-frame devices resist mechanical vibration. Tests are carried out in compliance with standard UL 489 SA and SB for the levels required by merchant-marine

More information

Power supply CP-D 24/4.2 Primary switch mode power supply

Power supply CP-D 24/4.2 Primary switch mode power supply Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution

More information

C series Product brief

C series Product brief Product brief Key applications Landlord sub-metering Object metering Meter performance Direct connected up to 0 ctive energy Low power consumption larm function Pulse output Installation Small size - 1

More information

CP-T range Product group picture

CP-T range Product group picture Product group picture /1 ABB Catalog Electronic Products and Relays 1/1 2CDC 110 00 C09 Table of contents CP-T range Product group picture /1 Table of contents /2 Benefits and advantages / Ordering details

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

Utility Communications Teleprotection Equipment TPT-200

Utility Communications Teleprotection Equipment TPT-200 Utility Communications Teleprotection Equipment TPT-200 5C Communications Inc. All rights reserved Teleprotection is designed to transfer protection commands coming, in most cases, from distance protection

More information

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L High Performance Current Transducer IT 200-S ULTRASTAB For the electronic measurement of currents: DC, AC, pulsed..., with galvanic isolation between the primary circuit and the secondary circuit. I PM

More information

Power Meter Series PM3200 Functions and characteristics

Power Meter Series PM3200 Functions and characteristics Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact size and DIN rail mounting, the PM3200 allows mains and feeders monitoring

More information

COMPACT SIZE HIGH PRECISION TIMERS VARIOUS OUTPUT & OPERATION MODE TYPES. UL File No.: E CSA File No.: LR39291

COMPACT SIZE HIGH PRECISION TIMERS VARIOUS OUTPUT & OPERATION MODE TYPES. UL File No.: E CSA File No.: LR39291 COMP SIZE HIGH PRECISI IMERS VARIOUS OUPU & OPERAI MODE YPES SDX (one) SDX imers Features UL File No.: E22222 CSA File No.: LR3929 3 operation modes added for fuller lineup Now, operation modes include

More information

Product Specification sheet

Product Specification sheet INPUT MINIMUM RATED MAXIMUM Input Voltage 90V AC 100 240V AC 264V AC Input Frequency 47 Hz 50 / 60 Hz 63 Hz Input Current * 350mA Inrush Current **

More information

Power supply CP-E 24/2.5

Power supply CP-E 24/2.5 2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment

More information

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM

More information

Energy Management Energy Meter Type EM21 72R Retro-Fit

Energy Management Energy Meter Type EM21 72R Retro-Fit Energy Management Energy Meter Type EM21 72R Retro-Fit Including 3 miniature split-core current sensors 10mm (90A), 16mm (150A) and 24mm (250A) diameter holes Class A (kwh) according to EN50470-3 Class

More information

XP2-R Power and Reverse Power Relay

XP2-R Power and Reverse Power Relay XP2-R Power and Reverse Power Relay Manual XP2-R (Revision C) Woodward Manual XP2-RE Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

Harmonic restraint earth fault or single-phase overcurrent protection

Harmonic restraint earth fault or single-phase overcurrent protection Harmonic restraint earth fault or single-phase overcurrent protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970885) Features Sensitive earth fault protection

More information

e 2 TANGO-50 Short-Circuit Detector K Data Sheet

e 2 TANGO-50 Short-Circuit Detector K Data Sheet e 2 TANGO-50 Short-Circuit Detector K-31.2.1 Data Sheet We Create Ideas With Power! e 2 TANGO-50 short-circuit detector is a product of ELEKTROMETAL ENERGETYKA SA developed by our engineers with extensive

More information

Power supply CP-E 24/20.0

Power supply CP-E 24/20.0 2CDC 271 027 F0008 a OUTPUT L+, L+, L, L-: terminals output b INPUT L, N, PE: terminals input c 13-14: terminals - signalling contact d OUTPUT OK: green LED output voltage OK e OUTPUT LOW: red LED output

More information

Power supply CP-D 12/2.1

Power supply CP-D 12/2.1 2CDC 271 025 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 12 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 2.1 A Rated output power

More information

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents Data sheet Current monitoring relays CM-SRS.2 for single-phase AC/DC currents For the monitoring of currents in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact

More information

8V General information. 2 Order data 8V

8V General information. 2 Order data 8V 8V05.00-8V05.00- General information Modular mechanical design using plug-in modules Integrated line filter Integrated braking resistor All connections are made using plug-in connectors Integrated electronic

More information

SAMSUNG ELECTRO-MECHANICS CO., LTD

SAMSUNG ELECTRO-MECHANICS CO., LTD Model Name : Features : ㅡ Suitable for LED lighting application ㅡ UL8750, UL1310 Class 2 ㅡ For use in Dry and Damp Location ㅡ Full-protection provided: OCP/OVP/OTP/SCP ㅡ 0-10V Dimming Control ㅡ IP67 ㅡ

More information

PD30CNB25xxPS. Photoelectrics, Background suppression reflective - PointSpot. Main features. Main functions. Description

PD30CNB25xxPS. Photoelectrics, Background suppression reflective - PointSpot. Main features. Main functions. Description Photoelectrics, Background suppression reflective - PointSpot Main features Miniature sensor range The visible red PointSpot light makes alignment very easy Range: 250 mm Sensitivity adjustment by potentiometer

More information

ZBRRA Programmable receiver - 2 relays V AC/ DC - 2 pusbuttons - 6 LEDs

ZBRRA Programmable receiver - 2 relays V AC/ DC - 2 pusbuttons - 6 LEDs Characteristics Programmable receiver - 2 relays - 24..240 V AC/ DC - 2 pusbuttons - 6 LEDs Product availability : Stock - Normally stocked in distribution facility Price* : 410.00 USD Main Range of product

More information

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks. 2CDC 251 054 F0t08 CM-MPN.52 2CDC 251 055 F0t08 CM-MPN.62 2CDC 251 056 F0t08 CM-MPN.72 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage

More information

Flexible AC current probes

Flexible AC current probes Flexible AC current probes Making use of the principle of Rogowski coils, the MiniFLEX models are flexible sensors offering a wide dynamic range for measuring AC intensities and viewing high-speed current

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

INSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13

INSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13 INSTALLATION MANUAL Model: Smart Analyzer Manufacturer: Smart Impulse Power meter with consumption breakdown by use 03/12/13 Table of contents Table of contents... 2 1. Introduction... 3 2. Installation

More information

Power supply CP-D 24/1.3

Power supply CP-D 24/1.3 2CDC 271 027 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 24 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 1.3 A Rated output power

More information

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-T 48/20.0 Primary switch mode power supply Data sheet Power supply CP-T 48/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

SWT 3000 Teleprotection technical data siemens.com

SWT 3000 Teleprotection technical data siemens.com Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel

More information

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK (RXLK_2H.tif) RALK.psd Features Micro-processor based time-overexcitation relay with continuous settings for

More information

LED Driver Compact dimming

LED Driver Compact dimming Driver LCAI 35W 3mA 900mA ECO C flat ECO series Product description Dimmable built-in LED Driver for LED Constant current LED Driver Output current adjustable between 3 900 ma Max. output power 35 W Nominal

More information

Power supply CP-T 48/5.0 Primary switch mode power supply

Power supply CP-T 48/5.0 Primary switch mode power supply Data sheet Power supply CP-T 48/5.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

Power supply CP-T 24/20.0 Primary switch mode power supply

Power supply CP-T 24/20.0 Primary switch mode power supply Data sheet Power supply CP-T 24/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Energy Management Energy Meter GM3T E GM3T-RS485 E

Energy Management Energy Meter GM3T E GM3T-RS485 E Energy Management Energy Meter GM3T E09 814 96 GM3T-RS485 E09 816 65 Certified according to MID Directive Product Description Three-phase energy meter with removable front LCD display unit. The same unit

More information

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks. 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 2CDC 251 050 F0t08 CM-MPS.31 2CDC 251 051 F0t08 CM-MPS.41 R/T: yellow LED - relay status, timing F1: red LED - fault message F2: red LED - fault

More information

Smart Power Relay E I...

Smart Power Relay E I... Smart Power Relay E-48-8I... Description The Smart Power Relay E-48-8I.- is a remotely controllable electronic load disconnecting relay with three functions in a single unit: l electronic relay l electronic

More information

SERIE E N. The E N series clamps use Hall-effect technology for the measurement of AC and DC currents from several milliamps to over 100 A.

SERIE E N. The E N series clamps use Hall-effect technology for the measurement of AC and DC currents from several milliamps to over 100 A. Pinces Current ampèremetriques clamps for AC/DC pour current courant AC SERIE E N The E N series clamps use Hall-effect technology for the measurement of AC and DC currents from several milliamps to over

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

Power supply CP-E 24/0.75

Power supply CP-E 24/0.75 2CDC 271 016 F0t06 a OUTPUT L+, L : terminals output b INPUT L, N, PE: terminals input c LOW: red LED output voltage too low d OK: green LED output voltage OK e OUTPUT Adjust: rotary potentiometer output

More information

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Complementary Contacts material Control type [Us] rated supply voltage Voltage range Main Range of product Product or component

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications. Current Transducer IT 605-S ULTRASTAB I PN = 600 A For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Features Wide operating temperature

More information

PHOENIX CONTACT - 09/2009

PHOENIX CONTACT - 09/2009 Electronic miniature circuit-breaker CLIPLINE Data sheet 03906_en_0 PHOENIX CONTACT - 09/2009 Description The EC-E... electronic miniature circuit-breaker selectively protects all 24 V DC load circuits

More information

MK-S (New Models) General-purpose Relays. New Super MK Relays. Models with Latching Lever Added to the Series. Features. Model Number Structure

MK-S (New Models) General-purpose Relays. New Super MK Relays. Models with Latching Lever Added to the Series. Features. Model Number Structure General-purpose Relays MK-S (New Models) CSM_MK-S_DS_E 1 New Super MK Relays. Latching Lever Added to the Series. Same mounting and internal wiring as the previous Super MK Relays Built-in mechanical indicator

More information

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC DATASHEET - ETR4-51-A Timing relay, star-delta, 50 ms, 1W, 3-60s, 24-240VAC/DC Part no. ETR4-51-A Catalog No. 031884 Eaton Catalog No. XTTR6A60S51B EL-Nummer 0004133308 (Norway) Delivery program Product

More information

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

DSR120 Series. xxx Series. 120 Watts.   AC-DC Power Supplies. Models & Ratings. Mechanical Details 120 Watts xxx Series Ultra Slim Design - 32 mm 150% Peak Load for 3 seconds Ambient Operation from -25 C to +70 C Full Load at 60 C (24V/48V) High Efficiency - Up to 92% Volt-Free Contact for OK Selectable

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

satech SynchroStar GPS 200 Series

satech SynchroStar GPS 200 Series satech SynchroStar GPS 200 Series KEY BENEFITS Designed with high quality oscillator OCXO the device is characterized by superior frequency stability and improved holdover performance that allows maintaining

More information

79/26 Series III Multimeter

79/26 Series III Multimeter 79/26 Series III Multimeter Instruction Sheet W Read First: Safety Information Never use the meter if the meter or test leads look damaged. Be sure the test leads and switch are in the correct position

More information

CP-T range Benefits and advantages

CP-T range Benefits and advantages Benefits and advantages Characteristics Rated output voltages V, V DC Output voltage adjustable via front-face rotary potentiometer OUTPUT Adjust Rated output currents 5 A, 10 A, A, A Rated output powers

More information

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications. Current Transducer IT 700-SB ULTRASTAB I PM = 700 A For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Features ± 10 V voltage output

More information

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC Features DIN-Rail 2 and 3-phase operation Input voltage range: 320 575VAC Output trim range: 22.5 29.5VDC High electrical strength; high reliability Permanent overload and short-circuit protection Parallel

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O Product data sheet Characteristics RE22R2MMU Multifunction Timer Relay - 24VDC/24..240 V AC - 2 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output

More information

Solid-state Timer H3DS

Solid-state Timer H3DS Solid-state Timer H3DS DIN Track Mounted, Standard 17.5-mm Width Timer Range A wide AC/DC power supply range (24 to 230 VAC/ 24 to 48 VDC) reduces the number of timer models kept in stock. (24 to 230 VAC/VDC

More information

Contents H3CR. DIN 48 x 48-mm Multifunctional Timer Series. Broad Line-up of H3CR Series H3CR-A. Solid-state Timer. Common to ALL Timers

Contents H3CR. DIN 48 x 48-mm Multifunctional Timer Series. Broad Line-up of H3CR Series H3CR-A. Solid-state Timer. Common to ALL Timers Solid-state Timer H3CR DIN 48 x 48-mm Multifunctional Timer Series Conforms to EN61812-1 and EN60664-1 (VDE0110) 4 kv/2 for Low Voltage, and EMC Directives. Approved by UL and CSA. Lloyds/NK approvals.

More information

Protection components

Protection components Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &

More information

LED Driver Compact dimming

LED Driver Compact dimming Driver LCAI 35W 350mA 900mA ECO C ECO series Product description Dimmable built-in LED Driver for LED Constant current LED Driver Output current adjustable between 350 900 ma Max. output power 35 W Nominal

More information

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1 INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 02/2010 MODELS 201A-AU 201-575-AU II_201A-AU_B1 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605)

More information

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

Power supply CP-T 24/10.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply Data sheet Power supply CP-T 24/10.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Time over/underfrequency relay with protection assemblies

Time over/underfrequency relay with protection assemblies Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features

More information

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 24/40.0 Primary switch mode power supply Data sheet Power supply CP-T 24/40.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,

More information

Energy Management Energy Meter GM3D

Energy Management Energy Meter GM3D Energy Management Energy Meter Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Accuracy ±0.5 RDG (current/voltage) Energy meter Instantaneous variables readout: 3 DGT Energies

More information

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External

More information

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49 TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument True RMS measurement User-friendly programing Four different types for optimal specification RS485 interface For 3- or 4-wire connection Compact

More information

Solid-state Timer H3CR. DIN 48 x 48-mm Multifunctional Timer Series. Broad Line-up of H3CR Series H3CR-A

Solid-state Timer H3CR. DIN 48 x 48-mm Multifunctional Timer Series. Broad Line-up of H3CR Series H3CR-A Solid-state Timer H3CR DIN 48 x 48-mm Multifunctional Timer Series Conforms to EN61812-1 and EN60664-1 (VDE0110) 4 kv/2. Conforms to EMC standards (EN50081-2 and EN50082-2). Approved by UL and CSA. Lloyds/NK

More information

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics off-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal

More information

METRAClip85 and 86 Clamp Multimeters

METRAClip85 and 86 Clamp Multimeters 3-349-794-03 1/8.14 Current and frequency measurement via clamp meter: 600 A AC TRMS and 900 A DC (automatic or manual switching) Multimeter functions via connector sockets: V (AC TRMS and DC) up to 1000

More information

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications. Current Transducer IT 700-S ULTRASTAB I PM = 700 A For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Features Closed loop (compensated)

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

Electronic timer CT-SDS.22

Electronic timer CT-SDS.22 CDC 0 F0t07 Features Rated control supply voltage 8 V DC, 0 V AC Single function timer with star delta change over One device includes 7 time ranges (0.0 s 0 min) n/o contacts LEDs for status indication

More information

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA

More information