The power line carrier equipment will provide speech, telecontrol and teleprotection channels over 50 Hz, 132 KV transmission systems.
|
|
- Howard Jefferson
- 5 years ago
- Views:
Transcription
1 National Electric Power Company Telecommunication and Control Department Supply of Outdoor Coupling Equipments ( Line Traps and Coupling Filters ) Tender No. 8/2018 A) General NEPCO is extending the transmission system to integrate new 132 KV Over Head transmission Line substations (KFW, MAS, Masdar, Shoubak Wind, Safawi Solar). New 132 KV 50 Hz Over Head transmission Lines are constructed between: QAIA S/S KFW S/S, Madaba S/S KFW S/S, MAS S/S Hasa S/S, MAS S/S Tafilah Wind SS, Masder S/S Mowagger S/S, Shoubak Wind S/S Fujij S/S, Safawi Solar S/S - Solar S/S, as shown in Fig. 1, 2 and 3. NEPCO plans to utilize power line carrier equipment to provide a redundant path for the telecommunication services in case of failure of the existing Fiber Optics equipment (SDH, PDH). The power line carrier equipment will provide speech, telecontrol and teleprotection channels over 50 Hz, 132 KV transmission systems. These Tender calls for engineering, design, manufacturing, testing at factory, packing, and CIF Aqaba seaport or CIF QAIA airport delivery of outdoor coupling equipment comprising: coupling filters, coaxial cable and line traps as specified below:
2 1)Scope of Work: Supply of the following material to Aqaba seaport or QAIA: - 10 sets of HF coupling filters with phase-to-earth coupling sets of line traps. - (3000) meter of coaxial cable. 2) Method of coupling: The coupling units are required to cater for the phase to earth coupling which requires one line trap and one HF phase-to-earth coupling unit for each direction at each location, (See Fig 1, Fig 2, Fig 3, and Fig 4). B) Technical Specifications: 1- Line Traps: Rating voltage Rating current Coil inductance Blocking range Blocking resistance 132 KV 1250 A / 31.5 KA ( ) mh ( ) Hz 400 Ω for bundle conductors 600 Ω for single conductors Maximum weight Method of installation 170 KG Pedestal mounting The line traps shall be broad band tuned by use of a tuning device which shall be preferably arranged to permit interchange without removing the line trap, the tuning frequency range shall be ( ) KHz or better.
3 The blocking ranges shall be subject to approval of the engineer after the award of the Contract. The line trap shall have a protective device, which utilizes nonlinear resistor type arrestors, and the minimum discharge current shall be 10KA. The line trap shall be designed and equipped with Anti-corona rings and other necessary accessories to reduce corona discharge. The line traps shall be furnished with an adaptor plate to enable easy fixture on top of the CVTs. Tenderers shall submit type test reports or be expected to demonstrate that their line traps meet the tests recommended in IEC publication 353-line traps, with regard to temperature rise, short circuit current ratings, protective device, discharge current etc, and also the blocking capabilities of the line trap. All line traps shall be provided with non-metallic bird barriers. All line traps shall be provided with clearly visible rating plates which will include the following data:- a- Manufacturer s name. b- Type. c- Serial Number. d- Rated continuous current. e- Rated short time current with respect to time f- Rated coil inductance. g- Weight. Whilst the tuning device shall be similarly marked with the following details: a- Manufacturer s name. b- Type. c- Serial Number. d- Frequency band (s) etc, in Kilohertz. e- Rated protective level of the tuning device.
4 2- HF Coupling Units: Working bandwidth Tuning range KHz KHz Line side impedance range: Phase-earth coupling Phase-phase coupling Equipment side impedance Composite loss within tuning range Line and equipment side return loss over the tuning range Average continuous power Minimum peak envelope power withstand at 100KHz Isolation transformer voltage(primary/secondary) Impulse test voltage on each phase filter ohms ohms 75ohms =<2dB =>14dB 200W =<1000W 10KV,1minute 10KV Drain coil current carrying capacity Continuous current at 50/50Hz 1 A 0.2 second current =<50A Earthing switch Rated current 300A continuously 1 second current 16KA Surge arrestor sparkover voltage Surge arrestor rated voltage 1KV 660v
5 Earth switch interlock with door Distortion and intermodulation yes/no =<80dB below P.E.P The filters are to be suitable for outdoor use in a hot dusty climate and are to have weatherproof door seals together with breather holes to avoid condensation, the units must have an external earthing switch which should preferably be interlocked with the box door/lid such that the latter cannot be opened unless the earth switch is closed to earth the device. The earthing switch should be connected directly to the substation earth. The units must have an air surge arrestors and for higher security a gas surge arrestor connected between the isolating transformer equipment side terminals. The purpose of the last surge arrestor being to protect the PLC equipment. The earth switch shall be located outside the box of the coupling device. The coupling units should permit parallel coupling of two power line carrier terminals which use adjacent frequency-bands, in order to avoid interferences between them due to the increased number of channels transmitted on the same physical medium. The coupling units should also permit to connect power line carrier terminal to two phases of the power line in order to improve the reliability of transmission. When inter circuit coupling is employed it shall be possible to earth either of the coupling filters and maintain carrier transmission on a phase to earth basis using the other filter. The coupling device shall meet in full the safety and protection requirements of the IEC recommendation for such devices (IEC publication 481- Coupling devices for power line carrier systems). The device shall be fitted with a rating plate clearly defining, but not limited to the following data: a- Manufacturer s name. b- Type. c- Serial Number.
6 d- Peak envelope power. e- Available bandwidth or working range. Tenderers shall be expected to demonstrate that their equipment complies with the following tests: The coupling Filters detailed above shall be mounted on the CVT or CC lattice pedestals. 3- Coaxial Cable: - The coaxial cable shall have a characteristic impedance of 75 ohms unbalanced and have low attenuation in the frequency band (40-500) KHz ( the attenuation shall not be more than 0.5db/100m ) and shall be PVC covered, steel wire armored with a further outer sheath of PVC or PE. - The coaxial cable must be RG-11 type.
1.0 mh, 3150 A LINE TRAP
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 1.0 mh, 3150 A LINE TRAP GETCO/E/TS-400KV WT 0904/R0, Dt: 09.01.2012
More informationTitle: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric
More informationAdvanced Test Equipment Rentals ATEC (2832) Lightning Surge Simulator LSS-F02.
Lightning Surge Simulator Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) LSS-F02 www.noiseken.com Conforming to IEC61000-4-5 ed2 Standard LSS-F02 series A simulator
More informationData Isolation Cards. 2-Wire HDSL/56KBS Isolation Card P Wire HDSL/56KBS Isolation Card P30050
Data Isolation Cards 2-Wire HDSL/56KBS Isolation Card P30076 4-Wire HDSL/56KBS Isolation Card P30050 Printed in USA 12/11 T0331 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 System
More informationWIRELESS INSULATOR POLLUTION MONITORING SYSTEM
SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power
More informationEC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s
EC 200 EC200 - Rev. 3-23.06.11 Characteristic impedance 50 ± 2 Material copper wire Nominal capacity (pf/m) 80.5 Construction - Relative propagation velocity (%) 83 Diameter (mm) 1.05 Inductance (µh/m)
More informationSPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS
-1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification
More informationLightning Surge Simulator LSS-F03 series
Lightning Surge Simulator LSS-F03 series Compliant with IEC61000-4-5 Edition 3 requirements Lightning Surge Simulator LSS-F03 series Feature "Output voltage 15kV, current 7500A" which can conduct breakdown
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationTECHNICAL DESCRIPTION
TECHNICAL DESCRIPTION A.M. BROADCAST TRANSMITTER SENDER AM 3000 SS June 2001-1- Rev. B TRANSMITTER CHARACTERISTICS 1. BASIC OFFER The basic offer includes: One AM3000SS A.M. Medium Wave Solid State Broadcast
More informationHands On Relay School 2017
Hands On Relay School 2017 RFL Electronics Inc. www.rflelect.com PLC Teleprotection 2 Application of TPS PLC IEEE Std 643 2004 The PLC uses the Power lines to transmit and receive signals from station
More informationVHF LAND MOBILE SERVICE
RFS21 December 1991 (Issue 1) SPECIFICATION FOR RADIO APPARATUS: VHF LAND MOBILE SERVICE USING AMPLITUDE MODULATION WITH 12.5 khz CARRIER FREQUENCY SEPARATION Communications Division Ministry of Commerce
More informationSWT 3000 Teleprotection technical data siemens.com
Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable
More informationSUPPLY OF CARRIER PROTECTION COUPLER TYPE NSD-50
(I) GENERAL : Indoor PLCC Equipments are required for important 400KV, 220KV and 132KV Sub/station for Speech, Data Transmission, Protection and Teleprinter Links. (II) GENERAL REQUIREMENT : The equipments
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationAll the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.
1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationCoaxial Cable Protection
Coaxial Cable Protection 1485-005 Technical Note Coaxial Cable Protection Coaxial Cable Protection Why is coaxial cable protection needed? Skin effect is a physical phenomenon that relates to the limited
More informationmblc-10, mblw-10 Block Up Converter User Manual
mblc-10, mblw-10 Block Up Converter User Manual mblc -10 User Manual Contacting Belcom The following information is provided for your use. Please feel free to contact us at Belcom Microwaves Ltd. Address:
More informationCapacitive voltage transformers
Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550
More informationEMC TEST REPORT 2G-2S.0.3.FC-BOX. METEL s.r.o., Žižkův Kopec 617, Česká Skalice. Measured Date Type Version DPS SN
EMC TEST REPORT METEL s.r.o., Žižkův Kopec 617, 55203 Česká Skalice 2G-2S.0.3.FC-BOX - 1 - Immunity Testing - Electrostatic Contact Discharge Test No. 1: EN61000-4-2 ed.2 Device Used: SRG200LC Description
More information4. CAPACITIVE VOLTAGE TRANSFORMERS AND COUPLING CAPACITORS Oil-paper insulation
4. CPCITIVE VOLTGE TRNSFORMERS ND COUPLING CPCITORS 420 kv Capacitive voltage transformers. Fingrid, Visulahti (Finland). 34 Instrument transformers High voltage INTRODUCTION Capacitive voltage transformers
More informationUBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS
More informationSchlöder GmbH - EMC Test and Measurement Systems Model #
Schlöder GmbH - EMC Test and Measurement Systems Model # Product Description IEC / EN 61000-4 - 2 ESD SESD 216 ESD generator 10 kv CON / 16,5 kv AIR acc. to IEC 61000-4-2, 150 pf / 330 ohm SESD 230 ESD
More information1. SYSTEM DESCRIPTION NON - DIRECTIONAL RADIO BEACON TRANSMITTER (NDB) JTM-30C
Documentation Rev.Date Rev. Document no. 1. SYSTEM DESCRIPTION NON - DIRECTIONAL RADIO BEACON TRANSMITTER (NDB) JTM-30C 1. SYSTEM DESCRIPTION... 2 1.1 OVERALL SYSTEM DESCRIPTION... 2 1.2 BASIC MODULES...
More information11-SDMS-03 REV. 02 SPECIFICATIONS FOR
11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice
More informationINSTALLATION MANUAL. CTA-30RK-550 Rack Mount Distribution Amplifier
INSTALLATION MANUAL CTA-30RK-550 Rack Mount Distribution Amplifier 1 PACKAGE CONTENTS This package contains: One CTA-30RK-550 Rack Mount Distribution Amplifier One CTA-30RK-550 instruction manual PRODUCT
More informationSecondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.
Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the
More informationSOCIETY OF CABLE TELECOMMUNICATIONS ENGINEERS INC
SOCIETY OF CABLE TELECOMMUNICATIONS ENGINEERS INC ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 151 2008 Mechanical, Electrical, and Environmental Requirements
More informationTRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS
1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8
More informationUtility Communications Teleprotection Equipment TPT-200
Utility Communications Teleprotection Equipment TPT-200 5C Communications Inc. All rights reserved Teleprotection is designed to transfer protection commands coming, in most cases, from distance protection
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV
More informationTelecommunication Wiring Questions
Telecommunication Wiring Questions 1. is the process of modifying a carrier frequency in rhythm to the audio frequency. A, Modulation B. Amplitude C. Change of phase D. Interference 2. is the property
More informationHigh Voltage Engineering
High Voltage Engineering Course Code: EE 2316 Prof. Dr. Magdi M. El-Saadawi www.saadawi1.net E-mail : saadawi1@gmail.com www.facebook.com/magdi.saadawi 1 Contents Chapter 1 Introduction to High Voltage
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationPower Quality. Case Study. Conrad Bottu Laborelec January 2008
Case Study Electromagnetic compatibility (EMC) study Breakdown of low voltage electronic equipment in a 25 kv substation Conrad Bottu Laborelec January 2008 Power Quality Power Quality 1 Introduction Description
More informationIntroduction EMC. Filter parameters. Definition of EMC / EMI. X-Capacitor. Sources of EMI. Coupling mechanism. Y-Capacitor.
Introduction to EMC Schurter has over 75 years experience in the electronics and electrical industries, developing and manufacturing components that ensure a clean and safe supply of power. Schurter provides
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More informationI P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and
More informationCAPACITOR VOLTAGE TRANSFORMER
CAPACITOR VOLTAGE TRANSFORMER March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What
More informationVOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)
TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part
More informationcommunication networks Power Line Carrier Communication. Design and Engineering.
communication networks Power Line Carrier Communication. Design and Engineering. 2 3 An existing PLC network represents a considerable investment made over many years. In spite of the growing significance
More informationDevice Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.
/9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala
More informationI P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary
More information6. Internal lightning protection
6. Internal lightning protection 6.1 Equipotential bonding for metal installations Equipotential bonding according to IEC 60364-4- 41 and IEC 60364-5-54 Equipotential bonding is required for all newly
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationINTERNATIONAL TELECOMMUNICATION UNION. SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Digital terminal equipments General
INTERNATIONAL TELECOMMUNICATION UNION ITU-T G.703 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (11/2001) SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Digital terminal equipments
More informationPOWER LINE CARRIER UCC 2021
POWER LINE CARRIER SPECIAL FEATURES UCC 2021 Flexibility for upgrade of existing PLC networks (100% compatible with existing PA and Line Interface modules of Analog GE PLC equipments) Interconnection between
More informationCentral Electronics Model 600L Linear Amplifier
INTRODUCTION This manual has been reproduced by James Lawrence, NA5RC, a 600L owner. Text no longer applicable such as insurance claim with the carrier has been deleted. Some capitalization and grammar
More informationTECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This
More informationTechnical Equipment Specification
STATE OF CALIFORNIA Office of the State Chief Information Officer Public Safety Communications Division Technical Equipment Specification Equipment Type: Transmitter/Receiver Mobile Relay/Base/Control
More informationDS2000ICLA. Specification highlights Symbol Unit Min Typ Max. Features. Applications: 1 ppm linearity. MPS for particles accelerators.
Ultra-stable, high precision (ppm class) fluxgate technology DS Series current transducer for non-intrusive, isolated DC and AC current measurement up to 3000A Features ppm linearity 0 ppm offset Current
More informationCOUPLING / DECOUPLING NETWORK (CDN) CDN AF TYPE, CDN CAN
IEC / EN 61000-4-6 specifies the design and performance of a range of coupling / decoupling networks (CDNs). Each CDN is specific to the of cable and the intended signal carried on the cable. Teseq offers
More informationProposal of double voltage transmission line pulse generator using four coaxial cables
Proposal of double voltage transmission line pulse generator using four coaxial cables Hitoshi Kijima, Koji Ochi Abstract In order to carry out the simulation of an electrical noise, a pulse generator
More informationTelegärtner Mobile Radio Base Station Components.
Telegärtner Mobile Radio Base Station Components www.telegaertner.com Mobile Radio Base Station Components Components: Connectors EMP Protectors Jumper Cables Adaptors Tools and Accessories 2011 Telegärtner
More information700 Series AC Dielectric Test Sets
700 Series AC Dielectric Test Sets AC Test Systems HAEFELY HIPOTRONICS standard line of AC Test Systems is designed to perform high voltage AC tests on electrical apparatus in accordance with IEC60, IEEE
More informationResistive capacitive voltage divider
Resistive capacitive voltage divider Outdoor operation Oil insulated ROF 72 550 kv General description Resistive capacitive voltage dividers type ROF (RC divider) are used in high voltage networks within
More informationTECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)
TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +
More informationReactors for filtering
NEW ZEALAND WWW.LPINZ.CO.NZ Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:info@LPINZ.co.nz Web: www.lpinz.co.nz Reactors
More informationKu-Band. Reliable Designed and built to survive in extremely adverse environmental conditions. Operates in ambient temperatures up to 60 C.
200W Outdoor TWT Amplifier for Satellite Communications The T02UO-2G 200 Watt TWT Power Amplifier higher efficiency in an environmentally sealed compact package designed for outdoor operation Less Prime
More informationSTA3318 Series StellarMini TM 180 W, Ku-Band Antenna Mount TWTA
STA3318 Series StellarMini TM 180 W, Ku-Band Antenna Mount TWTA The STA3318 range of Ku-Band TWT amplifiers from e2v technologies provide over 150 W of output power in a compact, lightweight, rugged, weatherproof,
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules
More information5/1.0 kw AM Transmitter
5/1.0 kw AM Transmitter Collins' 820E /F -1 series of broadcast transmitters is one of the most extensively transistorized series of transmitters available in the 5 -kw to 10 -kw power range. The series
More information8792 Power Tube. Linear Beam Power Amplifier Tube
8792 Power Tube Linear Beam Power Amplifier Tube 1000 Watts Peak Sync Output in VHF Translator Service 265 Watt Average-Noise-Power Output with White Noise Loading 300 Watt Power Output in UHF-Linear Telephony
More informationFatima Michael college of Engineering and Technology
Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric
More information7P Series - Surge Protection Device (SPD) Features 7P P P
Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationDS200ID-CD100. Specification highlights Symbol Unit Min Typ Max. Features. Applications: Linearity error maximum 2 ppm. MPS for particles accelerators
Ultra-stable, high precision (ppm class) fluxgate technology DS Series current transducer for non-intrusive, isolated DC and AC current measurement up to 370A Features Linearity error maximum 2 ppm 100
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More informationR-F Skewed Hybrids. Type H1SB and H1SB-R. & R-F Balanced Hybrids Type H1R, H3X and Type H1RB, H3XB and Type H1RB-40. System Manual CH44 VER03
R-F Skewed Hybrids Type H1SB and H1SB-R & R-F Balanced Hybrids Type H1R, H3X and Type H1RB, H3XB and Type H1RB-40 System Manual CH44 VER03 (Replaces CH44-VER02) AMETEK Power Instruments 4050 NW 121st Avenue
More informationPHYSICAL/ELECTRICAL CHARACTERISTICS OF HIERARCHICAL DIGITAL INTERFACES. (Geneva, 1972; further amended)
5i Recommendation G.703 PHYSICAL/ELECTRICAL CHARACTERISTICS OF HIERARCHICAL DIGITAL INTERFACES (Geneva, 1972; further amended) The CCITT, considering that interface specifications are necessary to enable
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Data Sheet Pim 31 Passive Intermodulation Analyzer 2 x 20W Taking performance to a new peak PIM 31 - Passive Intermodulation
More informationTechnical Specification
LARGEST RANGE OF IMPULSE TESTERS UP TO 100KV/100KA Technical Specification E-MIG1203CWG revised: 22. June 2003 1 MIG Tester Type MIG1203CWG 1 MIG Tester Type MIG1203CWG 1 1.1 Introduction 1 2 General 2
More informationCP6A. 6 Band Trap Vertical 75-6m
CP6A 6 Band Trap Vertical 75-6m Instruction Sheet The CP6A is a multi-band trap-vertical antenna for HF bands, covering the 75*, 40, 20, 15, 10m & 6m amateur bands. Made from heavy duty aluminum, the CP6A
More informationExtract from the online catalog
Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation at http://www.download.phoenixcontact.com. The
More informationRGCoaxials RG, low noise and sub-miniature coaxials
RGCoaxials RG, low noise and sub-miniature coaxials RG Coaxials Contents Page Introduction and contents Comparison of coaxial and triaxial cable types RG (LS0H) FR, LS, ZH, RAD Low smoke, zero halogen
More informationMESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head
More informationStandard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables
Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240
More informationMEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KOKM Cable current instrument transformers Instruction for Installation, use and maintenance 2 KOKM CABLE CURRENT INSTRUMENT TRANSFORMERS INSTRUCTION FOR INSTALLATION, USE AND MAINTENANCE
More informationIMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES
IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES Thomas Steiner HIGHVOLT Prüftechnik Dresden GmbH Lifecycle of utilities time schedule utilities Tests during life cycle of utilities
More informationCorona noise on the 400 kv overhead power line - measurements and computer modeling
Corona noise on the 400 kv overhead power line - measurements and computer modeling A. MUJČIĆ, N.SULJANOVIĆ, M. ZAJC, J.F. TASIČ University of Ljubljana, Faculty of Electrical Engineering, Digital Signal
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationOutdoor Installation 2: Lightning Protection and Grounding
Outdoor Installation 2: Lightning Protection and Grounding Training materials for wireless trainers This one hour talk covers lightning protection, grounding techniques and problems, and electrolytic incompatibility.
More informationZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR
ZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR The flexibility of the Zucchini MS range during planning and installation makes it ideal for frequently changing requirements in small to medium sized commercial
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationLightning Strikes. Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS
Lightning Strikes Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS ARRL CT State Technical Coordinator The Power of Lightning What is a Ground? Design
More informationPOTENTIAL TRANSFORMER
POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More informationSTUDIO TO TRANSMITTER LINKING SYSTEM
RFS37 May 1995 (Issue 1) SPECIFICATION FOR RADIO LINKING SYSTEM: STUDIO TO TRANSMITTER LINKING SYSTEM USING ANGLE MODULATION WITH CARRIER FREQUENCY SEPARATION BETWEEN 75 AND 500 khz Communications Division
More informationCP6 6 Band Trap Vertical 80-6m
CP6 6 Band Trap Vertical 80-6m Instruction Sheet The CP6 is a multi-band trap-vertical antenna for HF bands, covering the 80*, 40, 20, 15, 10m & 6m amateur bands. Made from heavy duty aluminum, the CP6
More informationSingle Line Diagram of Substations
Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission lines are
More informationLIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED
LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More informationHigh Performance Current Transducer IT 200-S ULTRASTAB = A. ε L
High Performance Current Transducer IT 200-S ULTRASTAB For the electronic measurement of currents: DC, AC, pulsed..., with galvanic isolation between the primary circuit and the secondary circuit. I PM
More informationOverview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.
Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential
More informationHVDC High Voltage Direct Current
HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the
More informationCOMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS
006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR
More informationGENERAL TECHNICAL SPECIFICATION (Turnkey Work)
GENERAL TECHNICAL SPECIFICATION (Turnkey Work) March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,
More information