Implementation of Automatic Under Voltage Load Shedding Program in Entergy System
|
|
- Brenda Norris
- 5 years ago
- Views:
Transcription
1 Implementation of Automatic Under Voltage Load Shedding Program in Entergy System Sharma Kolluri, IEEE Fellow Manager, Transmission Planning Entergy Services, Inc. Presentation at i-pcgrid Workshop San Francisco, CA March 26, 2014
2 What is Automatic UVLS Program? (Proposed NERC Definition) An automatic load shedding program consisting of distributed relays and controls used to mitigate the risk of Cascading, voltage instability, voltage collapse, or uncontrolled separation resulting from undervoltage conditions. Centrally-controlled UVLS is excluded because it is consistent with nature of SPSs.
3 New NERC UVLS Standard (Project ) NERC seeks to revise current UVLS standard based on FERC directive Modify PRC to require that integrated and coordinated approach be included in all protection systems SDT decided to consolidate the existing UVLS standards to create a single results based standard The proposed standard is currently posted for informal comments deadline April 16, 2014
4 Overview of Entergy System Over 15,000 miles of transmission lines in four states 1,550 substations 36,000 MW of connected generation 24,000 MW Entergyowned 12,000 MW merchantowned 28,000 MW of load
5 Background on Western Region Western Region load growth: ~ 5.1 % (in past) with high composition of air conditioning load Limited Generation resources: Two Lewis Creek units (260 MW, 150 MVAR each) With generation out of service, line outages can lead to potential voltage collapse - FIDVR A SCADA based UVLS program was commissioned to meet NERC requirements
6 FIDVR Event
7 Western Region One Line Grimes Crockett Lewis Creek Units China - Jacinto Oak Ridge - Tamina New Caney - Hickory
8 PV Curve for Western Region (generation and 230 kv line out) p.u Rivtrin Poco Goslin Cypress Conroe Pelican Road Frontier Dayton Rivtrin Conroe Poco Jacinto Cleveland Huntsville Goslin Lewis Creek Pelican Road Cypress Frontier Lewis Creek
9 Voltage Plot of Woodlands Area Buses 1.0 p.u. 0.9 p.u. Second Block Load Shed First Block Load Shed
10 Existing SCADA Based UVLS Program
11 SCADA Based Load Shed Logic Armed all time 4/8 buses <0.92 pu Drop load One or more Lewis Creek units inservice? OEL at Lewis Creek units 4/8 buses < 0.94 pu Time Delay 3 seconds Monitored Buses: Dayton Bulk 138kV Rivtrin 138kV Conroe 138kV Poco 138kV Jacinto 138kV Cleveland 138 kv Huntsville 138 kv Goslin 138 kv Load Blocks: Block 1: 120 MW Block 2: 100 MW Block 3: 60 MW Reset the Process for next LVSH block The above conditions need to be met for 3 scans to trigger load shedding
12 New Relay Based UVLS Program
13 Relay Based UVLS Program This program will replace existing SCADA based program Load shed decision is based on predicted time to recover above a preset voltage value instead of voltage magnitude SEL-451 relays will be installed at 4 selected 138 kv stations Relays monitor positive-sequence voltage on high side of 138 kv buses Program designed to drop a total of 200 MW load at the 4 stations
14 Program Overview Positive Sequence Voltage is sampled and saved once per cycle Program is enabled when the voltage is below 0.8 p.u. 5 consecutive slopes of voltage recovery (with 2, 4, 6, 8 and 10 cycles durations) is used for predicting voltage recovery time If all 5 consecutive recovery time predictions > predefined set time, Load shed is triggered If recovery time < setting time, no action is taken
15 UVLS Recovery Slope Calculation 1.05 pu 0.8 pu Relay Reset Actual Recovery Slope V2 pu V1 pu 0.3 pu 0.1 sec t1 sec t2 sec 2.1 sec 2 SEC 4.1 sec ARM RELAY 2 SEC TIMER DELAY RECOVER To 0.8 pu Within next 2 sec UV Detected
16 Neg seq block Logic Diagram Voltage in range Zero seq block Receive block from other relay Program Enable Transmits block to other relay Block low side fault Secondary voltage present
17 Voltage in range Logic Diagram(contd) Timer Trip count Preset recover voltage Preset time Clock, 1 pulse / cycle
18 Logic Diagram for Tripping Timer within per defined time range Trip Trip count = 5 Program Enable
19 Lab Simulations
20 Lab Setup
21 PSS/E Simulations Cases
22 Comtrade File
23 Relay Event Report V 1M ag RE Q_M A G V1Mag REQ_MAG TRP CNT V1 0.8 p.u. Trip count TRP CNT D igitals 0-5 PLT01 PSV59 Trip Program enable Relay 210 cycle Relay trip Cycles
24 Relay Event Report 65.0 V1Mag REQ_MAG V 1M ag RE Q_M A G V1 Relay trip 0.8 p.u Cycles
25 SUMMARY Relay based UVLS program is more appropriate for addressing FIDVR phenomena Faster when compared to SCADA based program More localized and independent More intelligent and flexible
26 Questions?
Fault Induced Delayed Voltage Recovery (FIDVR) Advisory
Fault Induced Delayed Voltage Recovery (FIDVR) Advisory NERC Synchronized Measurement Subcommittee (SMS) NASPI Engineering Analysis Task Team (EATT) July 2015 Why the Advisory? The goal of this advisory
More informationStudy on the Improvement of the Special Protection Scheme (SPS) in the Korean power system
Study on the Improvement of the Special Protection Scheme (SPS) in the Korean power system Jeonghoon Shin, Suchul Nam, Seungtae Cha, Jaegul Lee, Taekyun Kim, Junyoen Kim, Taeok Kim, Hwachang Song Abstract--This
More informationReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria
ReliabilityFirst Regional Criteria 1 Disturbance Monitoring and Reporting Criteria 1 A ReliabilityFirst Board of Directors approved good utility practice document which are not reliability standards. ReliabilityFirst
More informationTexas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event
Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event
More informationPRC Disturbance Monitoring and Reporting Requirements
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationNVESTIGATIONS OF RECENT BLACK-
DIGITAL VISION outs indicate that the root cause of almost all major power system disturbances is voltage collapse rather than the underfrequency conditions prevalent in the blackouts of the 1960s and
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationPRC Compliance Using Bitronics 70 Series Recorders
PRC-002-2 Compliance Using Bitronics 70 Series Recorders Introduction The North American Electric Reliability Council (NERC) has defined standards for disturbance monitoring and reporting requirements
More informationRemedial Action Scheme Definition Development
Remedial Action Scheme Definition Development Background and Frequently Asked Questions Project 2010-05.2 Special Protection Systems June 2014 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA
More informationRemedial Action Scheme Definition Development Background and Frequently Asked Questions
Remedial Action Scheme Definition Development Background and Frequently Asked Questions Project 2010-05.2 Special Protection Systems October 2014 1 3353 Peachtree Road NE Suite 600, North Tower Atlanta,
More informationVOLTAGE STABILITY OF THE NORDIC TEST SYSTEM
1 VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM Thierry Van Cutsem Department of Electrical and Computer Engineering University of Liège, Belgium Modified version of a presentation at the IEEE PES General
More informationNPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements
NPCC Regional Reliability Reference Directory # 12 Under frequency Load Shedding Program Requirements Task Force on System Studies Revision Review Record: June 26 th, 2009 March 3 rd, 2010 Adopted by the
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationMay 30, Errata to Implementation Plan for the Revised Definition of Remedial Action Scheme Docket No. RM15-13-_
May 30, 2018 VIA ELECTRONIC FILING Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C. 20426 RE: Errata to for the Revised Definition of Remedial Action
More informationFinal ballot January BOT adoption February 2015
Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and
More informationMassive Transient Stability Based Cascading Analysis and On-line Identification of Critical Cascades
1 Massive Transient Stability Based Cascading Analysis and On-line Identification of Critical Cascades Paper Number: 16PESGM2419 Marianna Vaiman, V&R Energy marvaiman@vrenergy.com 2016 IEEE PES General
More informationNORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE)
COORDONNATEUR DE LA FIABILITÉ Direction Contrôle des mouvements d énergie Demande R-3944-2015 NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE) Original : 2016-10-14 HQCMÉ-10, Document 2 (En liasse) Standard
More informationSetting and Verification of Generation Protection to Meet NERC Reliability Standards
1 Setting and Verification of Generation Protection to Meet NERC Reliability Standards Xiangmin Gao, Tom Ernst Douglas Rust, GE Energy Connections Dandsco LLC. Abstract NERC has recently published several
More informationVoltage Stability Assessment at the EMS
Voltage Stability Assessment at the EMS Jay Giri i-pcgrid San Francisco, March 26 th, 2013 GRID EMS Overview DSA Integration Load Load (area) meas. Forecast SCADA AGC Division Load & Loss Status & Analog
More informationSystem Operating Limit Definition and Exceedance Clarification
System Operating Limit Definition and Exceedance Clarification The NERC-defined term System Operating Limit (SOL) is used extensively in the NERC Reliability Standards; however, there is much confusion
More informationWECC CMPLDW Phase 2 Study update. LMTF April 18 th, 2017 Atlanta, GA
WECC CMPLDW Phase 2 Study update LMTF April 18 th, 2017 Atlanta, GA Background CMPLDW load model phase 1 has been in approved WECC cases since 2013, it s the best available model to capture system oscillations,
More informationSeptember 19, Errata to Implementation Plan for the Revised Definition of Remedial Action Scheme
!! September 19, 2017 VIA ELECTRONIC FILING Veronique Dubois Régie de l'énergie Tour de la Bourse 800, Place Victoria Bureau 255 Montréal, Québec H4Z 1A2 RE: Errata to for the Revised Definition of Remedial
More informationGeomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.
Geomagnetic Disturbances IEEE PES Chicago Chapter Technical Presentation March 12, 2014 Alan Engelmann Transmission Planning ComEd GMD Background Solar Disturbances Impacts Monitoring Events 2 Solar Disturbances
More informationMidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above
MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above March 13, 2018 Issued by: Dehn Stevens, Director System Planning and Services 1.0 SCOPE This document defines the criteria
More informationRecently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.
December 7 th, 2010 NPCC Full Member Committee; Please find attached a draft revised NPCC Regional Reliability Directory #12 Underfrequency Load Shedding Program Requirements and a draft revised NPCC UFLS
More informationECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability
ECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability Spring 2016 Instructor: Kai Sun 1 Content Basic concepts Voltage collapse and Saddle-node bifurcation P-V curve and V-Q curve Causes
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-1 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the Board of Trustees. Description
More informationUnit Auxiliary Transformer (UAT) Relay Loadability Report
Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC
More informationNERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1
NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,
More information1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report
1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report Rich Bauer Associate Director Reliability Risk Management / Event Analysis Mid C Seminar July 19, 2017 Western Interconnection
More informationSYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011
SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More informationReal Time Stability Analysis at Peak Reliability. Slaven Kincic, Hongming Zhang JSIS May 2017, SLC
Real Time Stability Analysis at Peak Reliability Slaven Kincic, Hongming Zhang JSIS May 2017, SLC Overview: Overview of Peak s DSA Application; o Set up o User Cases Transient Stability Criteria; TSAT
More informationLow Frequency Demand Disconnection Summary
Low Frequency Demand Disconnection Summary This article assesses the suitability of current low frequency protection on the network as more distributed generation is connected to WPD s network. DSOF June
More informationUPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS
UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS 1 B. RAMESH, 2 K. P. VITTAL Student Member, IEEE, EEE Department, National Institute of Technology Karnataka,
More informationFault Locating at Pacific Gas and Electric Company
Fault Locating at Pacific Gas and Electric Company i-pcgrid 2015 Scott Hayes Relay Targets were the earliest fault location devices. Light Beam Oscillographs and later Digital Fault Recorders Microprocessor
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationIndustry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017
Industry Webinar Reactive Power Planning NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Webinar Topics Reliability Guideline on Reactive Power Planning Webinar Topics Fundamentals of
More informationAt generating sites with 1200MW or greater of installed generating capacity.
A. Introduction 1. 2. Number: 3. Purpose: To provide FRCC requirements for installation of Disturbance Monitoring Equipment (DME) and reporting of Disturbance data to facilitate analyses of events and
More informationResponse of Grid Interconnected Solar PV inverters to Transmission System Faults
Response of Grid Interconnected Solar PV inverters to Transmission System Faults David Piper, P.E. Operations Planning & Analysis SCE Grid Control Center July 18, 2017 1 OVERVIEW 1. Overview of the event
More informationHarmonizing the Changing Resource Mix Keeping the Grid Together
Harmonizing the Changing Resource Mix Keeping the Grid Together Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 30, 2017 NERC-IEEE Memorandum of Understanding
More informationSmart Wires. Distributed Series Reactance for Grid Power Flow Control. IEEE PES Chapter Meeting - Jackson, MS August 8, 2012
Smart Wires Distributed Series Reactance for Grid Power Flow Control IEEE PES Chapter Meeting - Jackson, MS August 8, 2012 Jerry Melcher Director Program Management Smart Wires Inc. 2 Agenda Technology
More informationArizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan
Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Mark Hackney October 5-8, 2009 Amman, Jordan Energy Control Center Layout 2 Energy Control
More informationWind and Solar (PV) Sub harmonic Interactions with Power Systems
I PCGRID Workshop - 2017 Wind and Solar (PV) Sub harmonic Interactions with Power Systems Dr. Krish Narendra Chief Technology Officer ERLPhase Protection, Automation, Control & Smart Grid ERLPhase Power
More informationInverter-Based Resource Disturbance Analysis
Inverter-Based Resource Disturbance Analysis Key Findings and Recommendations Informational Webinar February 15, 2018 August 16, 2016 Blue Cut Fire Disturbance Key Findings and Recommendations 2 Western
More informationWIND FARM Flexible AC Transmission Systems
WIND FARM Flexible AC Transmission Systems WIND ENERGY AND GRID INTEGRATION Madrid 24-25 January 2006 Jacques COURAULT Assumption: Wind farm is with Fixed Speed Induction Generator (FSIG) SUMMARY 1/ Wind
More informationHighgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES
Highgate Converter Overview Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Abstract Introduction to HVDC Background on Highgate Operation and Control schemes of Highgate 22 Why
More informationNERC Protection Coordination Webinar Series June 30, Dr. Murty V.V.S. Yalla
Power Plant and Transmission System Protection ti Coordination Loss-of-Field (40) and Out-of of-step Protection (78) NERC Protection Coordination Webinar Series June 30, 2010 Dr. Murty V.V.S. Yalla Disclaimer
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0 DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationNERC Protection Coordination Webinar Series June 23, Phil Tatro
Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection NERC Protection Coordination Webinar Series
More informationGMD Voltage Collapse Study
GMD Voltage Collapse Study Terry Volkmann 2016 Fall Reliability Conference November 2, 2016 1 GMD Voltage Collapse Studies in Wisconsin and Maine Overview: Modeling shows GMD Voltage Collapse Issues: Power
More informationA Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors
A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors Dinesh Rangana Gurusinghe Yaojie Cai Athula D. Rajapakse International Synchrophasor Symposium March 25,
More informationError Correction and Hidden Failure Detection in Centralized Substation Protection
Error Correction and Hidden Failure Detection in Centralized Substation Protection Sakis Meliopoulos*, George Cokkinides*, Paul Myrda** and E. Farantatos** * Georgia Institute of Technology, Atlanta, Georgia
More informationIndustry Webinar Draft Standard
Industry Webinar Draft Standard Project 2010-13.2 Phase 2 of Relay Loadability: Generation PRC-025-1 Generator Relay Loadability December 13, 2012 Agenda Welcome, Introductions and Administrative NERC
More informationSDG&E Transmission Synchrophasor Project Update
SDG&E Transmission Synchrophasor Project Update Joint Synchronized Information Subcommittee (JSIS) Meeting Tariq Rahman, May 22-25, 2017 2006 San Diego Gas & Electric Company. All copyright and trademark
More information900 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report
900 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report Southern California Event: October 9, 2017 Joint NERC and WECC Staff Report February 2018 NERC Report Title Report Date
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee
More informationPower Plant and Transmission System Protection Coordination
Technical Reference Document Power Plant and Transmission System Protection Coordination NERC System Protection and Control Subcommittee Revision 1 July 2010 Table of Contents 1. Introduction... 1 1.1.
More informationPOWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER
POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,
More informationFault Location Using Sparse Wide Area Measurements
319 Study Committee B5 Colloquium October 19-24, 2009 Jeju Island, Korea Fault Location Using Sparse Wide Area Measurements KEZUNOVIC, M., DUTTA, P. (Texas A & M University, USA) Summary Transmission line
More informationReducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationFACILITIES STUDY PID 211 INTERCONNECTION LEWIS CREEK 138 KV
TRANSMISSION LINE & SUBSTATION PROJECTS COMPANY:ETI CUSTOMER: PID 211 FACILITIES STUDY EJO # F4PPTX0018 PID 211 INTERCONNECTION LEWIS CREEK 138 KV Revision: 1 Rev Issue Prepared Description of Revision
More informationMonitoring Voltage Stability using Real Time Dynamics Monitoring System
Monitoring Voltage Stability using Real Time Dynamics Monitoring System ipcgrid Meeting Voltage Stability Panel Session San Francisco March 26, 2013 Bharat Bhargava Electric Power Group. Built upon GRID-3P
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationSYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES. A.G. Phadke
SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES A.G. Phadke Lecture outline: Evolution of PMUs Standards Development of Phasor Measurement Units Phasor Estimation Off-nominal frequency phasors Comtrade Synchrophasor
More informationSynchrophasors and the Smarter Grid
Synchrophasors and the Smarter Grid Synchrophasor A synchrophasor is a phasor measurement with respect to an absolute time reference. With this measurement we can determine the absolute phase relationship
More informationLoss of Solar Resources during Transmission Disturbances due to Inverter Settings II
Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II Informational Webinar on Level 2 NERC Alert Ryan Quint, Senior Manager, Advanced Analytics and Modeling Rich Bauer,
More informationRELIABILITY: Our Advantages, Challenges, and Opportunities
RELIABILITY: Our Advantages, Challenges, and Opportunities NERC Reliability Leadership Summit March 21, 2017 Edmund O. Schweitzer, III Ph.D. President, Schweitzer Engineering Laboratories, Inc. Copyright
More informationReal-time Decentralized Voltage Stability Monitoring and Protection against Voltage Collapse
Real-time Decentralized Voltage Stability Monitoring and Protection against Voltage Collapse Costas Vournas National Technical University of Athens vournas@power.ece.ntua.gr 1 Outline Introduction to Voltage
More informationMinnesota Power Systems Conference 2015 Improving System Protection Reliability and Security
Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Steve Turner Senior Application Engineer Beckwith Electric Company Introduction Summarize conclusions from NERC
More informationDUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning
DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation
More informationEndorsed Assignments from ERS Framework
ERSTF Completion Endorsed Assignments from ERS Framework Ref Number Title ERS Recommendatio n Ongoing Responsibility 1 Synch Inertia at Interconnection Level Measure 2 Initial Frequency Deviation Measure
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationPower Quality Monitoring: Key Component of Comprehensive Power System Monitoring
1 Power Quality Monitoring: Key Component of Comprehensive Power System Monitoring Daniel Sabin, P.E., M.Eng., IEEE Fellow Principal Engineer & Software Architect Boston, Massachusetts, USA dsabin@electrotek.com
More informationPredicting Voltage Abnormality Using Power System Dynamics
University of New Orleans ScholarWorks@UNO University of New Orleans Theses and Dissertations Dissertations and Theses Fall 12-20-2013 Predicting Voltage Abnormality Using Power System Dynamics Nagendrakumar
More informationTransmission Interconnection Requirements for Inverter-Based Generation
Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationNERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series
More information(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in
A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-3 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability
More informationTransmission Availability Data System Definitions
Table of Contents Transmission Availability Data System Definitions February 1, 2018 1 of 31 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com Table of Contents
More informationModeling of Distributed Generation under Next Generation Interconnection Requirements. Anna Edwards. A thesis. Submitted in partial fulfillment of the
Modeling of Distributed Generation under Next Generation Interconnection Requirements Anna Edwards A thesis Submitted in partial fulfillment of the requirements for the degree of: Master of Science in
More informationUTILIZING MICROPROCESSOR BASED RELAYS AS PREDICTIVE TOOLS TO MITIGATE VOLTAGE INSTABILITY PROBLEMS THAT STEM FROM
UTILIZING MICROPROCESSOR BASED RELAYS AS PREDICTIVE TOOLS TO MITIGATE VOLTAGE INSTABILITY PROBLEMS THAT STEM FROM THE FAST VOLTAGE COLLAPSE AND DELAYED VOLTAGE RECOVERY PHENOMENA Except where reference
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationUnit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition
Unit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition NERC System Protection and Control Subcommittee March 2016 NERC Report Title Report Date I Table
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationMicro-synchrophasors (µpmus) in Electric Power Distribution Systems 5/29/15 SF PES Chapter Workshop
Micro-synchrophasors (µpmus) in Electric Power Distribution Systems 5/29/15 SF PES Chapter Workshop Dr. Alexandra (Sascha) von Meier Co-Director, Electric Grid Research, California Institute for Energy
More informationPRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1
PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities
More informationMHD-EMP (E3) Assessment of the US Power Grid GIC and Transformer Thermal Assessment
MHD-EMP (E3) Assessment of the US Power Grid GIC and Transformer Thermal Assessment NERC Joint OC-PC Webinar July 25, 2017 Randy Horton, Ph.D., P.E. Senior Program Manager High-altitude Electromagnetic
More informationPMU-based Voltage Instability Detection through Linear Regression
PMU-based Voltage Instability Detection through Linear Regression Rujiroj Leelaruji and Prof. Luigi Vanfretti Smart Transmission Systems Lab. Electric Power Systems Department KTH Royal Institute of Technology,
More informationProject System Operating Limits Drafting Team Meeting Notes
Notes Tuesday, February 23, 2016 8:30 AM 5:00 PM Wednesday, February 24, 2016 8:30 AM 5:00 PM Thursday, February 25, 2016 8:30 AM 12:00 PM WECC office 155 North 400 West Salt Lake City, Utah 84103 ReadyTalk
More informationImplementation of Revised IEEE Standard 1547
MAY 31, 2017 HOLYOKE, MASSACHUSETTS Implementation of Revised IEEE Standard 1547 Presentation to ISO-TO Operations Committee David Forrest Key Points As New England adds significant amounts of Distributed
More informationMeasurement tools at heart of Smart Grid need calibration to ensure reliability
Measurement tools at heart of Smart Grid need calibration to ensure reliability Smart grid; PMU calibration position 1 The North American interconnections, or electric transmission grids, operate as a
More informationUNDER VOLTAGE LOAD SHEDDING FOR CONTINGENCY ANALYSIS TO OPTIMIZE POWER LOSS AND VOLTAGE STABILITY MARGIN
UNDER VOLTAGE LOAD SHEDDING FOR CONTINGENCY ANALYSIS TO OPTIMIZE POWER LOSS AND VOLTAGE STABILITY MARGIN Shiwani Rai 1, Yogendra Kumar 2 and Ganga Agnihotri 3 Department of Electrical engineering Engineering,
More informationLine Impedance Estimation Using SCADA Data
Line Impedance Estimation Using SCADA Data Presenter: Ramiro Da Corte - Power System Engineer Prepared by: James Shen - Principal Engineer, AESO Nov. 5, 214 Background AESO is responsible for grid reliability
More informationMeeting Notes Project Remedial Action Schemes Standard Drafting Team January 19-22, :00 p.m. 5:00 p.m. PT
Meeting Notes Project 2010-05.3 Remedial Action Schemes Standard Drafting Team January 19-22, 2015 8:00 p.m. 5:00 p.m. PT Southern California Edison Pomona, CA Administrative Introductions and chair remarks
More information