PowerWorld Simulator GIC

Size: px
Start display at page:

Download "PowerWorld Simulator GIC"

Transcription

1 Tom Overbye PowerWorld Client Conference February 23, South First Street Champaign, Illinois (217)

2 Geomagnetic Disturbances (GMDs) Overview GMDs have the potential to severely disrupt operations of the electric grid by inducing quasi-dc geomagnetically induced currents (GICs) in the high voltage grid Until recently power engineers had few tools to help them assess the impact of GMDs on their system First integrated tool introduced by PowerWorld GMD assessment tools are now moving into the realm of power system planning and operations engineers Calculations are now implemented in power flow and transient stability GIC impact is certainly still an area of research, but tools are here Presentation presents PowerWorld implementation 2

3 GMD Background Solar corona mass ejections (CMEs) can cause changes in the earth s magnetic field (i.e., db/dt). These changes in turn produce a non-uniform electric field at the surface Changes in the magnetic flux are usually expressed in nt/minute; from a 60 Hz perspective they produce an almost dc electric field 1989 North America storm produced a change of 500 nt/minute, while a stronger storms, such as the ones in 1859 and 1921, could produce more than 5000 nt/minute variation Storm footprint can be continental in scale (much of USA) Image source: J. Kappenman, A Perfect Storm of Planetary Proportions, IEEE Spectrum, Feb 2012, page 29 3

4 July 2012 GMD Near Miss According to a July 2014 NASA press release, in July of 2012 there was a solar CME that barely missed the earth If it had hit the earth it would likely have caused the largest GMD that we have seen in the last 150 years There is still lots of uncertainly about how large a storm is reasonable to consider in electric utility planning Image Source: science.nasa.gov/science-news/science-at-nasa/2014/23jul_superstorm/ 4

5 Solar Cycles Sunspots follow an 11 year cycle, and have been observed for hundreds of years We're in solar cycle 24 (first numbered cycle was in 1755); minimum was in 2009, maximum in 2014/2015 Images from NASA 5

6 But Large CMEs Are Not Well Correlated with Sunspot Maximums The large 1921 storm occurred four years after the 1917 maximum 6

7 There would be a day or so warning but without specifics on the actual magnitude or location It could strike quickly (they move at millions of miles per hour) with rises times of less than a minute, rapidly covering a good chunk of the continent Early warning satellites at Lagrange points, 1 million miles out Reactive power loadings on hundreds of transformers could sky rocket, causing heating issues and potential large-scale voltage collapses Power system software like state estimation could fail Control room personnel would be overwhelmed The storm could last for days with varying intensity Waiting until it occurs to prepare might not be a good idea Impact of a Large GMD From an Operations Perspective 7

8 FERC and NERC Actions May 2013: FERC Order 779 issued to NERC to develop Operations Standards and Planning Standards November 2013: NERC files EOP-010-1, Geomagnetic Disturbance Operations Ongoing: NERC TPL Transmission System Planned Performance During Geomagnetic Disturbances May 20, 2014: Technical Conference Several requirements, including study of Benchmark GMD Event every 5 years NERC proposed a non-uniform field magnitude model that FERC has partially accepted (FERC has been seeking industry comments) FERC workshop next week (March 1, 2016) 8

9 Geomagnetically Induced Currents (GICs GMDs cause slowly varying electric fields Along length of a high voltage transmission line, electric fields can be modeled as a dc voltage source superimposed on the lines These voltage sources produce quasi-dc geomagnetically induced currents (GICs) that are superimposed on the ac (60 Hz) flows 9

10 Transformer Impacts of GICs The superimposed dc GICs can push transformers into saturation for part of the ac cycle This can cause large harmonics; in the positive sequence (e.g., power flow and transient stability) these harmonics can be represented by increased reactive power losses in the transformer Harmonics Images: Craig Stiegemeier and Ed Schweitzer, JASON Presentations, June

11 Overview of GMD Assessment The two key concerns from a big storm are 1) large-scale blackout due to voltage collapse, 2) permanent transformer damage due to overheating Image Source: 11

12 GMD Enhanced Power Analysis Software By integrating GIC calculations directly within power flow and transient stability engineers can see the impact of GICs on their systems, and consider mitigation options GIC calculations use many of the existing model parameters such as line resistance. Some non-standard values are also needed; either provided or estimated Substation grounding resistance transformer grounding configuration transformer coil resistance whether auto-transformer whether three-winding transformer, generator step-up transformer parameters 12

13 Geographic Information GMD-induced DC voltages depend on the storm strength and orientation and the latitude and longitude of the lines The electric field is integrated along the transmission line path The geo-coordinates of the terminal buses are sufficient for uniform field modeling Hence buses must be mapped to substations, and substations to their geo-coordinates Substation/geographic data can be supplied by PowerWorld for FERC 715 planning models Buses mapped to subs, latitude and longitude for substations 13

14 Mapping Transformer GICs to Transformer Reactive Power Losses Transformer specific, and can vary widely depending upon the core type Single phase, shell, 3-legged, 5-legged Most significant with single phase designs Ideally information supplied by the transformer owner Currently support default values, a user specified linear mapping, or a piecewise linear mapping For large system studies default data is used when nothing else is available. Scaling value changes with core type Still debate in the industry with respect to the magnitude of damage GICs would cause in transformers (from slight aging to permanently destroyed) 14

15 Four Bus PowerWorld Example 150 volts I GIC,3Phase = = Ω ( ) amps or amps/phase Substation A with R=0.2 ohm Neutral = 18.7 Volts Bus 3 Substation B with R=0.2 ohm Neutral = Volts Bus 1 Bus 2 Bus 4 DC = 18.7 Volts DC = 28.1 Volts DC =-28.1 Volts DC =-18.7 Volts pu pu 765 kv Line pu pu 3 ohms Per Phase GIC/Phase = 31.2 Amps High Side = 0.3 ohms/ Phase GIC Input = Volts High Side of 0.3 ohms/ Phase GIC Losses = 52.6 Mvar GIC Losses = 52.5 Mvar slack The line and transformer resistance and current values are per phase so the total current is three times this value. Substation grounding values are total resistance. Brown arrows show GIC flow. 15

16 Specifying the Transformer Loss Values in Per Unit Previously K was specified as Mvars/amps Q loss = V pu KI GIC K is the loss factor, depends on core type, phases, etc. Q loss is in Mvars, I GIC is in Amps Since Q loss varies with V, this required an assumed nominal voltage (usually 500 kv) with the actual nominal voltage of each transformer used to scale the K values Q loss = V pu K V base,highkv 500 I GIC Disadvantages: Arbitrary assumed kv needed, K in Mvars/Amp cannot well model default piece-wise linear relationships that may exist for the three-leg transformers 16

17 Specifying Transformer Losses Scalars in Per Unit Current Approach: Representing the K values in per unit Using a base derived using the transformer s high side voltage Peak (or "crest") value Current base using the peak value used since this is a dc Sbase current base Ibase, highkv, peak = V 3 base, highkv Convert to per unit by dividing Q loss by S base,3ph V VpuK Q old loss = 500 S V I base base, highkv base, highkv 1000I 2 base, highkv, peak GIC K Q = V ( ) I = V ( K ) I = V K I K = 1.633K old loss, pu pu eff,pu pu old eff,pu pu new eff,pu new old 17

18 Specifying Transformer Losses Scalars in Per Unit Example: 345/138 kv transformer with I GIC = 100 amps and K = 1.5; use S base of 100 MVA Ibase, highkv, peak = = A I pu = = Q = = Q = Mvar loss, pu loss PowerWorld cases all use the new approach now 18

19 Four Bus Example: Input Data Next several slides demonstrate how GICs and their impacts can be calculated in an integrated fashion Earlier four bus system with an assumed electric field Substation coordinates need to be given to get line length In example Sub A is at 40N, 87W, Sub B is at 40N, 89W Line length is km (106.2 mile) 19

20 Four-Bus Inputs: Substations Key inputs are the grounding resistance and geo-location (latitude and longitude) 20 Latitude and longitude Grounding resistance = 0.2 Ω 20

21 Four-Bus Inputs: Transformers 21 Key inputs Coil resistance (DC ohms) Grounding configuration Autotransformer? (Yes/No) Core Type Most essential parameters; these determine the basic topology of the GIC network 21

22 Four-Bus Inputs: Transformers Manually Enter Coil Resistance Yes, User Set : user enters High Side Ohms per Phase and Medium Side Ohms per Phase No, Auto Default : values estimated XF Config High and XF Config Med: most common options are Gwye and Delta Is Autotransformer: Yes, No, or Unknown Core Type 22

23 Other Considerations Specifying a minimum voltage level to include in the analysis allows electric fields to be ignored on transmission lines below a cutoff kv GIC losses can be ignored on an area basis GIC input voltages can be ignored on an area basis 23

24 GIC Modeling Inputs Template MS Excel spreadsheet for data collection Does not require use of PowerWorld Simulator Contains transformer and substation GIC model inputs and allowable values in PowerWorld Simulator 24

25 Reactor Models Grounded shunt reactors can provide a GIC current path, similar to transformers Simulator GIC does not currently include reactors in the GIC circuit model, but it is possible to include a dummy transformer with an open-circuit secondary winding to approximate the affect for GIC modeling 25

26 Reactor Models Dummy Transformer as GIC Reactor Model: Delta Connected Secondary, Autotransformer = NO W ar Mvar Giant R 26

27 GMD Event Modeling After model inputs are assembled, the next step is to describe a GMD event Modern methods model GIC as DC voltage sources in transmission lines With pertinent parameters, GIC computation is a straightforward linear calculation 27

28 Other Considerations 28 Specifying a minimum voltage level to include in the analysis allows electric fields to be ignored on transmission lines below a cutoff kv GIC losses can be ignored on an area basis GIC input voltages can be ignored on an area basis 28

29 Scaled Electric Field Modeling GICs are dependent upon the assumed electric field NERC approach is to use a scaled uniform direction electric field Field/voltage input is Electric-Field Magnitude (V/mile or V/km) Storm Direction (0 to 360 degrees) 29 All directions are a linear combination of the north and east directions α and β scaling factors (covered later) 29

30 Four Bus Case Eastward Field Below values show results with uniform 0.88 V/km eastward field With uniform field, voltage is path independent 0.88 V/km km = 150 V Ibase, highkv, peak (100 MVA Base) = = A QLoss,pu, GIC = = Mvar Substation A with R=0.2 ohm Substation B with R=0.2 ohm Neutral = 18.7 Volts Neutral = Volts Bus 3 Bus 1 Bus 2 Bus 4 DC = 18.7 Volts DC = 28.1 Volts DC =-28.1 Volts DC =-18.7 Volts pu pu 765 kv Line pu pu 3 ohms Per Phase GIC/Phase = 31.2 Amps High Side = 0.3 ohms/ Phase GIC Input = Volts High Side of 0.3 ohms/ Phase Losses GIC = 52.6 Mvar GIC Losses = 52.5 Mvar slack Values would be zero for a N-S field for this case 30

31 42 Bus Example System: No Electric Field 31

32 42 Bus Example System: 5 V/km Northward Electric Field 32

33 42 Bus Example System: 5 V/km Eastward Electric Field 33

34 Determining the Worst Direction For a uniform direction field, the worst direction can now be determined analytically This can be done for individual transformers, areas and the system as a whole This allows easy "worst case" analysis 34

35 Default WECC Example with Uniform Electric Field: 5 V/km Eastward Transmission Atlas Results: Mvar Losses: 21,408 Highest Losses: 21,847 Highest Dir.: 65 deg Lowest Losses: 17,619 Lowest Dir.: 156 deg But highest/lowest directions vary for areas (28 deg for BC Hydro) 35

36 NERC Proposed Benchmark GMD Event (TPL-007) Peak GMD electric field magnitude corresponding to reference value of 8 V/km at 60 degrees north geomagnetic latitude and for the reference Quebec earth model Apply scaling factors for local geomagnetic latitude and earth resistivity E = 8 α β (V/km) α = e (0.115 L) Geomagnetic latitude scalar β is an earth resistivity scalar that ranges from 0.21 to 1.17 in the US and Canada 36

37 Default WECC Example with Scaled Electric Field: 5 V/km Eastward Transmission Atlas Results (greatly reduced) Mvar Losses: 4303 Highest Losses: 4638 Highest Dir.: 57 deg Lowest Losses: 3751 Lowest Dir.: 145 deg 37

38 GMDs, GDVs and Sparklines ALBERTA B.C.HYDRO NORTHWEST FORTISBC IDAHO MONTANA WAPA U.M GMD results can be easily visualized using GDVs. This display uses sparklines to show the angular variation in the area GMD losses SIERRA 7.37 PACE WAPA R.M PG AND E PSCOLORADO NEVADA 38

39 Sierra Wauna Da y t o n Grays Harbor Energy Facility Covant a Sunset Longview O liv e W a y St. Marys Murryhil Por t Of W Monitor L e x in g t o n ashingt on St. Johns Alcoa River Road Cushm an Chehalis Paul Centralia Switching Station Swif t BlueLake Gr esham Troutdale H a p p y V a le y M ayf ield Fairmount South Bremerton Nor t heast Fr eder ickson ( PSPL) G le n o m Cowlitz Fals S im p s o n a Massachusetts White River ( PSPL) Berrydale Covington Sammamish Novelt y T h e D a le s P h Big Eddy J ohn Day Ph Cascade B ig lo w C a n y o n W in d Rock Cr eek Union Gap Pamona Heights W hit e Cr eek W ind Pr oj ect Kittitas Valey Wind Power Project A n d r e w Y o r k Out look RockyReach Douglas Wind Ridge Boar dm Sulphur an ( PGE) Colum bia W anapum P r ie s t R a p id s Horse Heaven Coyot e Spr ings M idway White Bluf f s Hermiston Power Project Cold Spr ings Bent on Lar son Sand Dunes P E C He a d wo r k s Franklin I c e Ha r bo r S t a t e lin e W in d P r o j e c t - W a s h in g t o n Lower Monumental Little Goose Ph Kettle Fals L o n g L a k e Shawnee Bel Beacon ( Spokane) U p r iv e r D a m N.Lewist on I. E. P a p e r Lo 12. GDV of Substation Neutral GICs Port Angeles East Omak Snohomish Bothell Sno-king Monroe Addy Kitsap Eastpine Chief Joseph Wells (DOPD) Grand Coulee Maple Talbot Valley O' Brien Tillamook Clatsop Aberdeen Satsop Beaver Allston Keeler Shelton J.D. Ross Olympia Napavine Mossyrock Tacoma Southwest Cowlitz Bonneville Vantage McNary Ashe A two color contour is used to show currents coming out of the ground (red) and into the ground Lower Granite Central Ferry (green) Ha Sacajawea Carlton Sherwood Pearl Carver Mcloughlin Slatt Chemawa Salem Bethel (PGE)

40 Power Flow Convergence Integrated GIC modeling can certainly impact power flow convergence since the GIC induced reactive power losses simultaneously adds potentially lots of vars Several techniques can help prevent divergence Just calculating the GICs without solving the power flow Not calculating GMD voltages for equivalent lines Gradually increasing the electric fields to avoid adding too much reactive power at one time Only calculating the GIC transformer reactive power losses for specified areas vars do not tend to travel far Freezing the transformer taps and switched shunt Solving in transient stability for an increasing GMD 40

41 GMD Calculations in Transient Stability GMD calculations are fully integrated into transient stability as well Input is a time-varying electric field Values are calculated and report then as time-varying We are working on extending this to EMP analysis 20.0 Mvar 319 MW 785 Mvar 312 MW 743 Mvar Substation Substation 3 Total GIC Losses Mvar 758 MW Mvar 6 Substation MW 318 Mvar 630 MW 1153 Mvar 630 MW 1153 Mvar 88% MW 59 Mvar 234 MW 88 Mvar 29 Substation Mvar 210 MW MW 54 Mvar MW 16 Mvar Mvar 176 MW 73 Mvar MW 29 Mvar Substation Mvar Substation MW 892 Mvar Mvar 47 MW 20.0 Mvar MW 254 MW 584 Mvar 584 Mvar Substation 1 31 MW 12 Mvar MW 127 Mvar 41

42 Questions? 42

Power System Impacts of Geomagnetic Disturbances

Power System Impacts of Geomagnetic Disturbances 1 Power System Impacts of Geomagnetic Disturbances Thomas J. Overbye Fox Family Professor of Electrical l and Computer Engineering i University of Illinois at Urbana Champaign overbye@illinois.edu September

More information

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd. Geomagnetic Disturbances IEEE PES Chicago Chapter Technical Presentation March 12, 2014 Alan Engelmann Transmission Planning ComEd GMD Background Solar Disturbances Impacts Monitoring Events 2 Solar Disturbances

More information

Grounding Resistance

Grounding Resistance Grounding Resistance Substation grounding resistance is the resistance in ohms between the substation neutral and earth ground (zeropotential reference) An actual fall of potential test is the best way

More information

The Engineering Problem. Calculating GIC Flow through the EHV System

The Engineering Problem. Calculating GIC Flow through the EHV System The Engineering Problem Calculating GIC Flow through the EHV System 1 Creating the GIC System Model Since the EHV system is a three-phase balanced network, it is only necessary to model a single-phase

More information

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System 21, rue d Artois, F-75008 PARIS C4-306 CIGRE 2014 http : //www.cigre.org Modeling and Evaluation of Geomagnetic Storms in the Electric Power System K. PATIL Siemens Power Technologies International, Siemens

More information

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA CIGRÉ-697 2015 CIGRÉ Canada Conference 21, rue d Artois, F-75008 PARIS http : //www.cigre.org Winnipeg, Manitoba, August 31-September 2, 2015 GIC Analysis using PSS E K.V. PATIL Siemens Power Technologies

More information

TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

TPL Transmission System Planned Performance for Geomagnetic Disturbance Events TPL-007-1 Transmission System Planned Performance for Geomagnetic Disturbance Events Stan Sliwa Transmission Planning RSCS Meeting May 18, 2017 www.pjm.com TPL-007-1 Purpose: Establish requirements for

More information

GMD Voltage Collapse Study

GMD Voltage Collapse Study GMD Voltage Collapse Study Terry Volkmann 2016 Fall Reliability Conference November 2, 2016 1 GMD Voltage Collapse Studies in Wisconsin and Maine Overview: Modeling shows GMD Voltage Collapse Issues: Power

More information

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765

More information

Integration of Geomagnetic Disturbance Modeling into the Power Flow: A Methodology for Large-Scale System Studies

Integration of Geomagnetic Disturbance Modeling into the Power Flow: A Methodology for Large-Scale System Studies Copyright 2012 IEEE. Reprinted, with permission from: Integration of Geomagnetic Disturbance Modeling into the Power Flow: A Methodology for Large-Scale System Studies Thomas J. Overbye, Trevor R. Hutchins,

More information

Case Study Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device

Case Study Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Case Study Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device

More information

GIC Calculations Using PSS E. Live Demonstration February 16, 2017

GIC Calculations Using PSS E. Live Demonstration February 16, 2017 GIC Calculations Using PSS E Live Demonstration February 16, 2017 usa.siemens.com/digitalgrid NERC TPL-007-1 GMD Vulnerability Assessment Process Source: NERC GMD Task Force Documents Page 2 How to run

More information

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation) Transformer Thermal Impact Assessment White Paper Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-1 Transmission System Planned Performance for Geomagnetic Disturbance Events Background On

More information

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Assessment of the Impact of GMD on the TVA 500 kv Grid & Power Transformers Part II:

More information

Evaluating Transformer Heating due to Geomagnetic Disturbances

Evaluating Transformer Heating due to Geomagnetic Disturbances Evaluating Transformer Heating due to Geomagnetic Disturbances Presented by: Brian Penny, American Transmission Company 53 rd Annual Minnesota Power Systems Conference November 7, 2017 atcllc.com Presentation

More information

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation) Transformer Thermal Impact Assessment White Paper (Draft) Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-1 Transmission System Planned Performance during Geomagnetic Disturbances Background

More information

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779. Transformer Thermal Impact Assessment White Paper Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-12 Transmission System Planned Performance for Geomagnetic Disturbance Events Background On

More information

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada 1 Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs Luis Marti Hydro One, Canada 2 GMD 101 Background. What is a GMD event. Effects on the power system

More information

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events Transformer Thermal Impact Assessment White Paper TPL-007-2 Transmission System Planned Performance for Geomagnetic Disturbance Events Background Proposed TPL-007-2 includes requirements for entities to

More information

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events Transformer Thermal Impact Assessment White Paper TPL-007-2 Transmission System Planned Performance for Geomagnetic Disturbance Events Background Proposed TPL 007 2 includes requirements for entities to

More information

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events Topic and abstract Geomagnetic disturbances Events associated with GMD have been known and studied in power systems since the 1960 s. Early events pre dating the AC power have been recorded to the 1850

More information

Vulnerability Assessment and Planning

Vulnerability Assessment and Planning Vulnerability Assessment and Planning Project 2013-03 (GMD Mitigation) Standard Drafting Team GMD Task Force In-person meeting March 18-19, 2014 Topics Application of the Benchmark GMD Event in System

More information

Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances

Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances Gary R. Hoffman, Advanced Power Technologies Sam Sambasivan, Consolidated Edison Vincenzo Panuccio, Consolidated

More information

PSERC Tutorial: High Altitude Electromagnetic Pulse (HEMP) Impacts on the Grid

PSERC Tutorial: High Altitude Electromagnetic Pulse (HEMP) Impacts on the Grid PSERC Tutorial: High Altitude Electromagnetic Pulse (HEMP) Impacts on the Grid Thomas J. Overbye University of Illinois at Urbana-Champaign overbye@illinois.edu June 8, 2016 This presentation is based

More information

concerning the risks to the electric power grid from geomagnetic storms,

concerning the risks to the electric power grid from geomagnetic storms, Description of document: Requested date: Released date: Posted date: Source of document: Idaho Public Utilities Commission (PUC) records concerning the risks to the electric power grid from geomagnetic

More information

Unofficial Comment Form Project Geomagnetic Disturbance Mitigation

Unofficial Comment Form Project Geomagnetic Disturbance Mitigation Project 2013-03 Geomagnetic Disturbance Mitigation Please DO NOT use this form for submitting comments. Please use the electronic form to submit comments on the Standard. The electronic comment form must

More information

GIC Distribution. Carlos David Fernández Barroso. Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University

GIC Distribution. Carlos David Fernández Barroso. Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University CODEN:LUTEDX/(TEIE-5328)/1-062/(2014) GIC Distribution Carlos David Fernández Barroso Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University Table of contents

More information

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC 1 A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC Ramsis Girgis, Kiran Vedante, and Gary Burden ABB Power Transformers Abstract: There has been

More information

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation

More information

Operational Experiences of an HV Transformer Neutral Blocking Device

Operational Experiences of an HV Transformer Neutral Blocking Device MIPSYCON NOVEMBER 7, 2017 Operational Experiences of an HV Transformer Neutral Blocking Device Fred R. Faxvog, Emprimus Michael B. Marz, American Transmission Co. SolidGround GIC Neutral Blocker Fully

More information

Effects of GIC on Power Transformers and Power Systems

Effects of GIC on Power Transformers and Power Systems Effects of GIC on Power Transformers and Power Systems Prepared by Dr. Ramsis Girgis and Kiran Vedante (USA) in the name of CIGRE SC A2 Background There has been some misconception in the electric power

More information

Geo-Magnetic Disturbance Analysis of HV and EHV Grids

Geo-Magnetic Disturbance Analysis of HV and EHV Grids Engineering Conferences International ECI Digital Archives Modeling, Simulation, And Optimization for the 21st Century Electric Power Grid Proceedings Fall 10-22-2012 Geo-Magnetic Disturbance Analysis

More information

GMD Impacts on Generators

GMD Impacts on Generators Walling Energy Systems Consulting, LLC GMD Impacts on Generators Reigh Walling 1 CME interacts with earth magnetic field Large solar flare - Coronal Mass Ejection (CME) Protons and electrons in solar wind

More information

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S ESA-SPACE WEATHER WORKSHOP The Netherlands 17. November, 2005 by J. Elovaara 1 Jarmo Elovaara Oct. 25, 2005 Content: 1. About the potential effects of GIC's

More information

Impact of Solar Storms on the Swiss Transmission Network

Impact of Solar Storms on the Swiss Transmission Network Impact of Solar Storms on the Swiss Transmission Network Research Center for Energy Networks - ETH Zurich Giovanni Beccuti Impact of Solar Storms on the Swiss Transmission Network 1/25 Contents 1 Introduction

More information

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to

More information

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference July 17, 2014

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference July 17, 2014 TPL-007-1 Project 2013-03 Geomagnetic Disturbance Mitigation Technical Conference July 17, 2014 Administrative Meeting Space Safety Information Presentations available on the project page: http://www.nerc.com/pa/stand/pages/geomagnetic-disturbance-

More information

Power Grid Sensitivity Analysis of Geomagnetically Induced Currents

Power Grid Sensitivity Analysis of Geomagnetically Induced Currents IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 4, NOVEMBER 2013 4821 Power Grid Sensitivity Analysis of Geomagnetically Induced Currents Thomas J. Overbye, Fellow, IEEE, Komal S. Shetye, Member, IEEE,

More information

2012 Grid of the Future Symposium. Geomagnetic Disturbance Impacts and AEP GIC/Harmonics Monitoring System

2012 Grid of the Future Symposium. Geomagnetic Disturbance Impacts and AEP GIC/Harmonics Monitoring System 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Geomagnetic Disturbance Impacts and AEP GIC/Harmonics Monitoring System Q. QIU, J. FLEEMAN

More information

Model, Monitor & Mitigate Geomagnetically Induced Currents

Model, Monitor & Mitigate Geomagnetically Induced Currents Model, Monitor & Mitigate Geomagnetically Induced Currents Jeff Fleeman, American Electric Power CIGRE Grid of the Future Boston, MA October 22, 2013 CWG/9416P Page 1 Solar Storm Impacts Coronal mass ejections

More information

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in Docket No. RM15 11 on June 28, 2016.

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in Docket No. RM15 11 on June 28, 2016. Screening Criterion for Transformer Thermal Impact Assessment White Paper TPL-007-2 Transmission System Planned Performance for Geomagnetic Disturbance Events Summary Proposed TPL 007 2 includes requirements

More information

Deployment and Initial Experience with Oscillation Detection Application at Bonneville Power Administration

Deployment and Initial Experience with Oscillation Detection Application at Bonneville Power Administration Deployment and Initial Experience with Oscillation Detection Application at Bonneville Power Administration Dmitry Kosterev, Ashley Donahoo, Nick Leitschuh BPA Jeff Dagle, Frank Tuffner PNNL Dan Trudnowski

More information

Magnetohydrodynamic Electromagnetic Pulse Assessment of the Continental U.S. Electric Grid

Magnetohydrodynamic Electromagnetic Pulse Assessment of the Continental U.S. Electric Grid Magnetohydrodynamic Electromagnetic Pulse Assessment of the Continental U.S. Electric Grid Geomagnetically Induced Current and Transformer Thermal Analysis 3002009001 Magnetohydrodynamic Electromagnetic

More information

Application Guide. Computing Geomagnetically-Induced Current in the Bulk-Power System. December 2013

Application Guide. Computing Geomagnetically-Induced Current in the Bulk-Power System. December 2013 Application Guide Computing Geomagnetically-Induced Current in the Bulk-Power System December 2013 1 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 Table of Contents Table of Contents...

More information

GIC Neutral Blocking System Prototype to Production

GIC Neutral Blocking System Prototype to Production IEEE Meeting in Augusta, Maine GIC Neutral Blocking System Prototype to Production July 22, 2015 SolidGround TM Installed in Wisconsin Dr. Arnold Vitols, ABB Sr. Scientist and Dr. Fred Faxvog, Sr. Research

More information

Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation

Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation Meta-R-322 Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation John Kappenman Metatech Corporation 358 S. Fairview Ave., Suite E

More information

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference May 20, 2014

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference May 20, 2014 TPL-007-1 Project 2013-03 Geomagnetic Disturbance Mitigation Technical Conference May 20, 2014 Administrative Internet passcode: 3htw0br3wt1s (label located on desk) Presentations available on the project

More information

Transformer Technology Seminar GIC Capability of Power Transformers

Transformer Technology Seminar GIC Capability of Power Transformers Pomona CA, May 24-25, 2016 Transformer Technology Seminar GIC Capability of Power Transformers Siemens AG Transformers siemens.com/answers Geo-magnetic Induced Current GIC resistant Transformers page 2

More information

Solar Storm Probabilities Grid Contingencies Harmonic Relay Settings

Solar Storm Probabilities Grid Contingencies Harmonic Relay Settings Presentation to NERC GMD Meeting March 18 th 19 th, 2014 SolidGround TM Transformer Neutral Blocking System Solar Storm Probabilities Grid Contingencies Harmonic Relay Settings Agenda US Power Usage and

More information

PredictiveGrid. GMD/GIC detection explorations via PMU s

PredictiveGrid. GMD/GIC detection explorations via PMU s PredictiveGrid GMD/GIC detection explorations via PMU s 1 2 the data Provider Sensor Notes Data Rate USGS magnetometers 3 locations: Virginia, Colorado, and Washington 1 Hz Body Level One SCADA transformers

More information

Impact of transformer saturation from GIC on power system voltage regulation

Impact of transformer saturation from GIC on power system voltage regulation Impact of transformer saturation from GIC on power system voltage regulation L. Gérin-Lajoie, S. Guillon, J. Mahseredjian, O. Saad Abstract - Geomagnetically induced currents (GICs) affect power systems

More information

Grid Impact of Neutral Blocking for GIC Protection:

Grid Impact of Neutral Blocking for GIC Protection: Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

POWER TRANSFORMERS: Saturation Compensation Modeling, Simulation, and Experiments

POWER TRANSFORMERS: Saturation Compensation Modeling, Simulation, and Experiments POWER TRANSFORMERS: Saturation Compensation Modeling, Simulation, and Experiments John Thomas, Dr. David Cope Engineering Matters, Inc. 375 Elliot Street, Suite 130K Newton, MA 02464 www.engineeringmatters.com

More information

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in RM15-11 on June 28,

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in RM15-11 on June 28, Screening Criterion for Transformer Thermal Impact Assessment Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-12 Transmission System Planned Performance for Geomagnetic Disturbance Events

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Space Weather Impact on the Scandinavian Interconnected Power Transmission System

Space Weather Impact on the Scandinavian Interconnected Power Transmission System Space Weather Impact on the Scandinavian Interconnected Power Transmission System Roberta Piccinelli and Elisabeth Krausmann 2015 Report EUR 27571 EN European Commission Joint Research Centre Institute

More information

Geomagnetic Disturbance Planning Guide

Geomagnetic Disturbance Planning Guide Geomagnetic Disturbance Planning Guide December 2013 1 of 20 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 Table of Contents Table of Contents... ii Preface... iii Chapter 1 Introduction...

More information

DIRECT CURRENT COMPENSATION FIELD EXPERIENCE UNDER SERVICE CONDITIONS

DIRECT CURRENT COMPENSATION FIELD EXPERIENCE UNDER SERVICE CONDITIONS Journal of Energy VOLUME 63 2014 journal homepage: http://journalofenergy.com/ Helfried Passath Siemens AG Österreich Transformers Weiz helfried.passath@siemens.com Peter Hamberger Siemens AG Österreich

More information

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report 1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report Rich Bauer Associate Director Reliability Risk Management / Event Analysis Mid C Seminar July 19, 2017 Western Interconnection

More information

The Robust Electrical Grid? Richard L. Garwin 1 Christie Place Unit 402W Scarsdale, NY URL:

The Robust Electrical Grid? Richard L. Garwin 1 Christie Place Unit 402W Scarsdale, NY URL: The Robust Electrical Grid? Discussion for the Rotary Club meeting Moscato Restaurant, Scarsdale, NY January 19, 2016 Richard L. Garwin 1 Christie Place Unit 402W Scarsdale, NY 10583 RLG2@us.ibm.com URL:

More information

Geomagnetic Disturbances: Impact on Power System Components

Geomagnetic Disturbances: Impact on Power System Components Geomagnetic Disturbances: Impact on Power System Components Sakis Meliopoulos Georgia Power Distinguished Professor School of Electrical and Computer Engineering Georgia Institute of Technology tlanta,

More information

Spring 2000 EE361: MIDTERM EXAM 1

Spring 2000 EE361: MIDTERM EXAM 1 NAME: STUDENT NUMBER: Spring 2000 EE361: MIDTERM EXAM 1 This exam is open book and closed notes. Assume f=60 hz and use the constant µ o =4π 10-7 wherever necessary. Be sure to show all work clearly. 1.

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Real Time Stability Analysis at Peak Reliability. Slaven Kincic, Hongming Zhang JSIS May 2017, SLC

Real Time Stability Analysis at Peak Reliability. Slaven Kincic, Hongming Zhang JSIS May 2017, SLC Real Time Stability Analysis at Peak Reliability Slaven Kincic, Hongming Zhang JSIS May 2017, SLC Overview: Overview of Peak s DSA Application; o Set up o User Cases Transient Stability Criteria; TSAT

More information

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1 Screening Criterion for Transformer Thermal Impact Assessment Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-1 Transmission System Planned Performance for Geomagnetic Disturbance Events Summary

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

MHD-EMP (E3) Assessment of the US Power Grid GIC and Transformer Thermal Assessment

MHD-EMP (E3) Assessment of the US Power Grid GIC and Transformer Thermal Assessment MHD-EMP (E3) Assessment of the US Power Grid GIC and Transformer Thermal Assessment NERC Joint OC-PC Webinar July 25, 2017 Randy Horton, Ph.D., P.E. Senior Program Manager High-altitude Electromagnetic

More information

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1 Screening Criterion for Transformer Thermal Impact Assessment Project 213-3 (Geomagnetic Disturbance Mitigation) TPL-7-1 Transmission System Planned Performance for Geomagnetic Disturbance vents Summary

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

Investigation of Geomagnetic Induced Current Effects on Power Transformer

Investigation of Geomagnetic Induced Current Effects on Power Transformer International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Investigation of Geomagnetic Induced Current Effects on Power Transformer Roshni.R.Jethani 1, Dr.Harikumar Naidu 2,

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

MITIGATING GEOMAGNETIC INDUCED CURRENTS USING SURGE ARRESTERS. Alberto Ramirez Orquin Vanessa Ramirez Resilient Grids, LLC.

MITIGATING GEOMAGNETIC INDUCED CURRENTS USING SURGE ARRESTERS. Alberto Ramirez Orquin Vanessa Ramirez Resilient Grids, LLC. MITIGATING GEOMAGNETIC INDUCED CURRENTS USING SURGE ARRESTERS Alberto Ramirez Orquin Vanessa Ramirez Resilient Grids, LLC. September, 2015 General Introducing a simple, cost-effective, means to deal with

More information

PAPER-II (Subjective)

PAPER-II (Subjective) PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 07 December 2016 ISSN (online): 2349-6010 A Novel Method to Analyse the Effects of Geomagnetic Induced Current

More information

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network Dietrich Bonmann, ABB AG Bad Honnef, March 15, 2016 Impact of GIC on transformers and the transmission network Impact of GIC on transformers and the transmission network : From GIC to black-out Main network

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies T.G. Martinich, M. Nagpal, A. Bimbhra Abstract-- Technological advancements in high-power

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

University of Cape Town

University of Cape Town GEOMAGNETICALLY INDUCED CURRENTS (GIC) IN LARGE POWER SYSTEMS INCLUDING TRANSFORMER TIME RESPONSE THESIS BY: DAVID TEMITOPE OLUWASEHUN OYEDOKUN DEPARTMENT OF ELECTRICAL ENGINEERING University of Cape Town

More information

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling 2, rue d Artois, F-758 PARIS B4-7 CIGRE 28 http : //www.cigre.org A cost effective hybrid HVDC transmission system with high performance in DC line fault handling Mats Andersson, Xiaobo ang and ing-jiang

More information

Hydro One GMD Preparedness Plan for Cycle 24

Hydro One GMD Preparedness Plan for Cycle 24 Hydro One GMD Preparedness Plan for Cycle 24 Presented to: Critical Infrastructure Protection and Space Weather Workshop March 28-29, 2012, Ottawa, Ontario, Canada L. Marti Hydro One Networks Inc. 483

More information

ECEN 615 Methods of Electric Power Systems Analysis Lecture 8: Advanced Power Flow

ECEN 615 Methods of Electric Power Systems Analysis Lecture 8: Advanced Power Flow ECEN 615 Methods of Electric Power Systems nalysis Lecture 8: dvanced Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas &M University overbye@tamu.edu nnouncements Read Chapter

More information

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009 Lab 1 Objectives In this lab, our objective is to simulate a simple single machine infinite bus configuration using the PowerWorld Simulator software. We design a local generator system (a synchronous

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1 Screening Criterion for Transformer Thermal Impact Assessment Project 213-3 (Geomagnetic Disturbance Mitigation) TPL-7-1 Transmission System Planned Performance for Geomagnetic Disturbance vents Summary

More information

Disturbances. Their Impact on the Power Grid. By the IEEE Power & Energy Society Technical Council Task Force on

Disturbances. Their Impact on the Power Grid. By the IEEE Power & Energy Society Technical Council Task Force on By the IEEE Power & Energy Society Technical Council Task Force on Geomagnetic Disturbances nasa/sdo/aia Geomagnetic Disturbances Their Impact on the Power Grid Digital Object Identifier 1.119/MPE.213.2256651

More information

Pinhook 500kV Transformer Neutral CT Saturation

Pinhook 500kV Transformer Neutral CT Saturation Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization

More information

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Steve Turner Senior Application Engineer Beckwith Electric Company Introduction Summarize conclusions from NERC

More information

DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS

DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS Cigré Session, Paris, Paper 36-26 August 22 DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS J. Koen *, C.T. Gaunt University of Cape Town, South Africa 1. INTRODUCTION

More information

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved. Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Effect of Geomagnetically Induced Currents on Protection Systems

Effect of Geomagnetically Induced Currents on Protection Systems Effect of Geomagnetically Induced Currents on Protection Systems Sture Lindahl 2004-01-23 Industrial Electrical Engineering and Automation sture.lindahl@iea.lth.se Effect of GIC on Protective Relays Activity

More information

Solving old problems with new technology: How to monitor and measure GIC and OPD currents

Solving old problems with new technology: How to monitor and measure GIC and OPD currents Solving old problems with new technology: How to monitor and measure GIC and OPD currents Marcelo Zapella (GE Grid Solutions), Lucas Oliveira (GE Grid Solutions), Rich Hunt (GE Grid Solutions), Dylan Stewart

More information