Voltage Distortion & Power Quality Study Report for General Hospital Somewhere Valley, AK Background / Introduction

Size: px
Start display at page:

Download "Voltage Distortion & Power Quality Study Report for General Hospital Somewhere Valley, AK Background / Introduction"

Transcription

1 PowerCET Corporation 33 Scott Blvd., Bldg.. Unit 1 Santa Clara, CA 94 USA Voice: 48/ Fax: 48/ URL: consulting@powercet.com Study Report for General Hospital Somewhere Valley, AK Background / Introduction General Hospital has experience a series of problems associated with the electrical distribution when operating on emergency generator. The most troublesome condition is associated with UPS equipment located in the equipment rooms on multiple floors of the facility. The specific condition is the apparent inability of the UPS equipment to recognize the voltage as a viable source when operating on emergency generators resulting in a gradual discharge of the battery back-up and eventual failure of the connected electronic equipment if the utility source is not restored before the depletion of the battery supply. The problems experienced during generator testing are not limited to the above mentioned UPS equipment as there are reports of motor drives tripping-out as well. In an effort to identify the route cause and develop a mitigation strategy to correct the situation PowerCET Corporation was retained to conduct a thorough monitoring of the electrical distribution during a typical periodic generator test. The electrical environment associated with General Hospital s complex consisting of a total of four (4) automatic transfer switches (ATS) serving a variety of loads as well as two (2) active harmonic mitigation devices (aka, Harm Filter). Previous testing attempts, while providing some insight to the problem, were insufficient to provide a complete picture of this dynamic environment. The objective of the Study is to document the circuit conditions (specifically voltage distortion) during both normal and emergency generator operation. The information gathered can then be used to determine the appropriate mitigation of unsatisfactory conditions to allow for reliable operation of electrical/electronic equipment under all conditions. Methodology / Technical Approach PowerCET developed a comprehensive monitoring plan to document conditions of the facilities electrical distribution before, during and after a typical generator test. Figure 1 (below) is a simplified diagram of the normal and emergency electrical distribution associated with the facility. A total of ten (1) Dranetz power monitors were used and set to record both periodic (timed) readings as well as transient conditions. Dranetz PX / PG44 (or equivalent) monitors were programmed and installed at the locations shown in Figure 1 (above). The monitors were equipped with appropriate current probes for the application. In addition to distortion, energy and power quality information, the monitors were programmed to record a 12-cycle waveform sample of the voltage and current waveforms at the end of each power value period. Date: Revised /13/212 Page 1 of 21 Filename: Sample_Multiple_Monitor_Harmonic_Study.doc

2 Figure 1 Simplified electrical distribution with monitor locations. The monitoring equipment measures and records each cycle of the voltage and current along with the phase relationships. In addition to the measured parameters, voltage and current, the following calculated parameters are recorded. The monitor records the minimum, maximum and average value for each measured/calculated parameter. Distortion is measured over a 2ms window in compliance with appropriate IEC Standards. A summary of the Dranetz power monitor s measurement capabilities is contained in initial proposal. Date: Revised /13/212 Page 2 of 21

3 Table 1 (below) is a listing of the sequence of events associated with the early morning testing conducted on October 8, 21. Table 1 - Sequence of events testing activities - Transfer Harm Filter #1 Harm Filter #2 Transfer Active Harmonic Filter #1 Active Harmonic Filter #2 Power Monitor & Location Mntr Start Util to Gen OFF ON Gen to Util OFF On OFF 1 Generator HV :4:2 6::43 6:3:16 7::9 2 ATS #1 :14:9 6::2 6:31: 6:48:29 3 ATS #2 :16:29 6:4:2 6:3:16 6:48:29 4 ATS #3 (Xfmr Pri) :14:9 6:1:12 6:31:29 6:49:9 ATS #4 :17:29 6::41 6:33:33 6:48: /12 Xfmr Sdry :19:1 6:1:12 6:31:29 6:48:1 7 Harm Filter #1 :19:3 6:1:12 6:1: 6:26: 6:31:29 6:4: 6:4:3 6:48: 8 Harm Filter #2 :2:9 6:1:12 6:17:9 6:26:9 6:31:29 6:4:39 6:46:9 6:48:9 9 Pnl Bd Mntr #9 :26:28 6:1:12 6:31:29 6:3:8 1 Pnl Bd Mntr #1 :22:9 6:1:12 6:31:29 6:1:9 Mntr Key Findings and Recommendations The testing conducted on Wednesday, October 8, 21 revealed that while the voltage distortion is elevated when operating on emergency generators the level of voltage distortion (Vthd) under normal utility operation ranges from 3 to 8 and is contributing to equipment misoperation and stability issues. Table 2 (below) summarizes the average voltage and current distortion levels for utility and generator operation. Table 2 Power Monitor & Location Voltage thd fnd Current thd fnd Util Sply Gen Sply Util Sply Gen Sply 1 Generator HV n/a 4 n/a 17 2 ATS # ATS # ATS #3 (Xfmr Pri) ATS # Xfmr Sdry [1] Pnl Bd Mntr # Pnl Bd Mntr # [1] The B-phase has a preponderance of single-phase switch mode power supply load with a current thd above 1 and skews the average. Date: Revised /13/212 Page 3 of 21

4 ATS #2 (Monitor #3) Nominal Current 1A/phase ATS #2 (Monitor #3) has approximately 1A/phase of load, most of which is 6-pulse motor drives with dominant th and 7 th harmonic distortion. These drives are associated with the larger environmental loads in the building. A survey of the equipment by facilities staff indicates that all drives are equipped with 3 or impedance line reactors (inductors). Normal Utility Power Source Discussion Figure 2 (below) shows the voltage, current and distortion plots for monitoring Monitor Location #3, ATS # Timeplot 2 22 Transfer to Generator Transfer back to Utility 2 A Vrms B Vrms C Vrms A Irms B Irms C Irms A VThd B VThd C VThd A IThd B IThd C IThd :2 :3 :4 : 6: 6:1 6:2 6:3 6:4 6: Figure 2 Vthd and Ithd time plots of ATS #2 (Monitor #3). Under normal, utility operation the Vthd is in the 7 to 8 range and increase to between 9 and 1 when operating on the generator supply. This increase in Vthd is the result of the higher (about 3) source impedance presented by the generators to the distribution system. Industry practices attempt to operate facilities in the 3 to Vthd range for Utility operation and expect an increase when switching to the emergency generator supply. Figure 3 (below) shows the voltage and current waveforms during normal utility source operation just prior to the generator test conducted on October 1th. The current waveforms are typical of 6-pulse rectified loads with line-reactors installed. Comparing the current waveform with the associated voltage waveform it is obvious that the distortion of the voltage is the result of the load current interacting with the source impedances. Figure 4 (below) is the phase-to-phase 48V waveforms associated with the phase-to-neutral waveforms shown in Figure 3. The 48V waveform is actually what the load is seeing and has distortion near the zero-crossing point on the sine wave which, if severe enough, can cause timing errors of the drives and drop-out. The amount of distortion present in this environment is dependent on the power source and the characteristics of the loads operation at any given time. Date: Revised /13/212 Page 4 of 21

5 Event Details/Waveforms A V B V C V -1-2 A I B I C I :4:9.8 9/8/21 :4:9.86 :4:9.87 :4:9.88 :4:9.89 :4:9.9 Figure 3 Monitor #3 (ATS #2), utility source, voltage (phase-to-neutral) and current waveforms showing typical 6-pulse current waveforms. Figure 4 Monitor #3 (ATS #2), utility source, voltage (phase-to-phase) waveform showing distortion near zero crossing which can result in motor drive drop-out. Figure (below) shows the Discrete Fourier Transform (DFT) plot for the voltage and current waveforms from Figure 3 (above). The vertical bars represent the level of the various frequency content of the waveform. The dominant harmonic frequencies for 6-pulse loads is represented by the formula 6n 1 and results in the series: th, 7 th, 11 th, 13 th, etc. The purpose of the DFT plot is to provide information relative to the frequency and magnitude of the distorting signal that requires mitigation. Further analysis of the waveform data is contained in Figure 6 (below) which is the DFT plot of the power (Watts) associated with the signals in Figure 3 (above). In this case the DFT graph shows a positive and negative plot area. The positive/negative plots indicate the direction of harmonic energy flow. In Figure 6 the th and 7 th harmonic values are negative indicating that harmonic energy is flowing from the loads i.e., the loads are generating the harmonic current. Date: Revised /13/212 Page of 21

6 H2 H3 H4 H H6 H7 H8 H9 H1 A VHarm B VHarm C VHarm H2 H2 H3 H4 H H6 H7 H8 H9 H1 H2 A VHarm B VHarm C VHarm AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND DC Figure Monitor #3 (ATS #2), utility source, voltage and current DFT plot H2 H3 H4 H H6 H7 H8 H9 H1 H2 A PHarm B PHarm C PHarm Figure 6 Monitor #3 (ATS #2), utility source, DFT of Watts illustrating harmonic energy (negative) flow from the load. Dominant harmonic is th (3Hz). Emergency Generator Power Source Operation The following series of Figures, 7 through 1, are basically the same as previously discussed except the power source has been transferred to the emergency generators. Figure 7 (below) shows the voltage (line-to-neutral) and current waveforms for the ATS #2 (Monitor #3) operating on the generator supply. Note the increase in voltage distortion and the prominent multiple zero-crossings which typically cause drives to trip-off as they can not synchronize properly. [Note: It was reported that a number of drives had trip-off during the early morning testing on October 1th.] Figure 8 (below) shows the corresponding line-to-line voltage from Figure 7 and has the same zerocrossing problems discussed above. Date: Revised /13/212 Page 6 of 21

7 Event Details/Waveforms Zero Crossing Errors A V B V C V -1-2 A I B I C I 6:33:29.8 9/8/21 6:33: :33: :33: :33: :33:29.9 Figure 7 Monitor #3 (ATS #2), generator source, voltage (phase-to-neutral) and current waveforms showing distortion and multiple zero-crossing errors. Figure 8 Monitor #3 (ATS #2), generator source, voltage (line-to-line) showing distortion and multiple zero-crossings. Figures 9 and 1 (below) are DFT plots of the voltage and current waveform while operating on the emergency generator supply. As was the case when operating on the utility supply the dominant frequencies are, as expected, the th, 7 th, 11 th, 13 th, etc. The Vthd increased about 2 to a 1 level and the current, Ithd, actually decreased slightly. This is a typical situation in that the load interacting with higher source impedance of the generator can result in lower Ithd and higher Vthd. Date: Revised /13/212 Page 7 of 21

8 H2 H3 H4 H H6 H7 H8 H9 H1 A IHarm B IHarm C IHarm H2 2.. H2 H3 H4 H H6 H7 H8 H9 H1 H2 A VHarm B VHarm C VHarm AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND DC Figure 9 Monitor #3 (ATS #2), generator source, voltage and current DFT plot. W H2 H3 H4 H H6 H7 H8 H9 H1 H2 A PHarm B PHarm C PHarm Figure 1 -- Monitor #3 (ATS #2), generator source, DFT of Watts illustrating harmonic energy (negative) flow from the load. Dominant harmonic is th (3Hz). RECOMMENDATION: The 1A/phase load associated with the ATS #2 is causing significant voltage distortion on the 48Vac emergency bus distribution. Best practices recommend a Vthd level of around 3, with an upper action limit of. In the case of this facility the nominal Vthd is running 8. The th (3Hz) harmonic is the major contributor to the problems being experienced with equipment operation on the emergency 48V bus for the facility. The following are some possible mitigation activities that have a good possibility of improving equipment operation and overall system reliability. 1. Change out the existing 3 impedance line reactors for impedance reactors provided the drives can tolerate the higher circuit losses. The increased impedance will results in higher circuit losses and will attenuate the associated harmonics. There is an energy penalty in that the circuit IR losses will increase slightly. [TCI, Trans-Coil International, would be a good supplier for these types of products.] Date: Revised /13/212 Page 8 of 21

9 2. Employ phase shifting, zigzag transformers (3 angular displacement), on some of the drives to cancel out th and 7 th harmonic currents. The advantage of the phase shifting is that it is a passive harmonic filter and does not present the problem of cross-talk or interaction between other system distribution components that conventional harmonic filter might. [There are a number of suppliers of this equipment: Hammond Power Solutions, Inc.; Mirus International Inc.; SquareD (Schneider Electric).] 3. Employ a single point harmonic filter on the load side of the ATS #2 (Monitor #3) to mitigate the th and 7 th harmonics. This solution would require some engineering and the equipment can be rather large depending on the level of harmonic current. If space in the electrical equipment room is not available it may be possible to roof mount such a unit. The major advantage of this is a single point solution. It may be possible to re-configure the existing active harmonic filters to work on the 48Vac bus this possibility might be worth checking out. [There are a number of harmonic filter suppliers and generally they have a good engineering/application support.] ATS #3 (Monitors #4, #6-1) UPS Charging Problem On Gen Source The load side of the ATS #3 (see Figure 1) connects to a 48-28/12Vac step-down distribution transformer that distributes 28/12Vac power to a series of equipment rooms on each floor. Part of the load in each of the rooms is a UPS, 4.2kW (.2kVA). The UPS is connected as a 28Vac single-phase device and has input power factor correction. Several of the USP installations have experienced problems during the periodic generator testing in that the rectifier (input power supply) will not recognize the emergency generator as a valid power source. In an apparent effort to mitigate the USP situation two active harmonic filters were installed on the 28Vac distribution bus associated with the secondary of the step-down transformer discussed above. Figures 11 and 12 (below) show the current and voltage waveforms for the UPS equipment when powered from the utility source and generator source respectively. The UPS s power supply is power factor corrected which means it tries to follow the voltage waveform. If the voltage is distorted then the corresponding current waveform will be distorted. Figure 11 UPS input voltage and current waveforms utility source Date: Revised /13/212 Page 9 of 21

10 Figure UPS input voltage and current waveforms generator source The active harmonic filter is also a voltage following device which means there are we have the two devices trying to compensate for the distortion. The result is generally an unsatisfactory condition. During the testing activities on October 1th several of the UPS s failed to come on-line when transferred to generator. As an experiment the active harmonic filters were turned off, Figure 13 (below), and the current hunting from the UPS equipment stopped and the UPS equipment came on-line and started charging the batteries. It appears from this experiment that the increase in voltage distortion when operating with the generators as the power source results in an unstable condition in which, at least some of the UPS s, can not accept the voltage signal. Disabling the active harmonic filter equipment allows the UPS equipment to return to normal operation. Observations of the active harmonic filter equipment under normal operating conditions does not reveal any significant benefit from operation of the equipment (harmonic filters) in this application. Figure 13 Harmonic Filter current time plots versus UPS current plot documenting UPS power supply stability when Harmonic Filters are OFF. RECOMMENDATION: Install kva transformers on the input power to the UPS equipment. This will buffer the power factor corrected supply from the source and result in improved performance. Do NOT install any type of active regulating device in series with this type of application. Date: Revised /13/212 Page 1 of 21

11 RECOMMENDATION: From the testing results the active harmonic filter equipment is not improving the operating environment for the UPS equipment and should be removed from this application. During emergency generator operation the equipment actually interferes with the reliable operation of the UPS equipment. RECOMMENDATION: If the active harmonic filter equipment can be reconfigured for a 48Vac application then there may be a good application associated with the ATS #2 harmonic mitigation. This possibility certainly should be investigated as the equipment is in close proximity to the load side of the ATS #2. Figure 14 (below) is a record of the voltage and current waveforms on the secondary of the ATS #3 stepdown transformer secondary. There is a significant level of 18Hz neutral return current from the singlephase rectified (computer) loads served by this transformer. There does not appear to be significant distortion associated with the loading of the transformer. The B-phase loading appears to have a high level of non-power factor corrected loads, but the load imbalance calculations are within acceptable limits maximum unbalance is 14 with an average of 7 during the monitoring period. Event Details/Waveforms A V B V C V A I B I C I D I :29:4.3 :29:4.3 :29:4.4 :29:4.4 Figure 14 Monitor #6, generator source, voltage and current waveforms on secondary of ATS #3 step-down transformer. Figure 1 and 16 (below) summarize the distortion associated with the secondary of the step-down transformer. The voltage distortion appears to be associated with the general distortion caused by the large harmonic ATS #2 load and Figure 16 showing the harmonic energy flow indicates that this circuit is an acceptor of harmonics. Date: Revised /13/212 Page 11 of 21

12 H2 H3 H4 H H6 H7 H8 H9 H1 A VHarm B VHarm C VHarm H H2 H3 H4 H H6 H7 H8 H9 H1 AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND DC A IHarm B IHarm C IHarm H2 Figure 1 Monitor #6 (ATS #3, transformer secondary) generator source, voltage and current DFT plots H2 H3 H4 H H6 H7 H8 H9 H1 A PHarm B PHarm C PHarm H2 Figure 16 Monitor #6 (ATS #3, transformer secondary), generator source, DFT of Watts illustrating harmonic energy (positive) flow to the load. Dominant harmonics are th, 11 th and 13 th. RECOMMENDATION: Once harmonic mitigation has been implemented on the ATS #2 loads the ATS #3 loads should be reevaluated with respect to distortion and loading. Date: Revised /13/212 Page 12 of 21

13 Harmonic Acceptors The following circuits all appear to accepting harmonic energy from the facility at this time. The voltage distortion and to a certain extent the current distortion for these circuits are, in large part, triggered by the general voltage distortion from the ATS #2 (Monitor #3) location. The following circuits (monitor locations) are documented in this section: ATS #1 [Monitor #2] ATS #4 [Monitor #] 12.47kV [Monitor #1] ATS #1 (Monitor #2) Distortion and Harmonic Energy Flow The ATS #1 (Monitor #2) at this time appears to be one of the circuits accepting harmonic energy from the facility. The general Vthd level is in the 7 range and rises to around 9 during generator operation Figure 17. The nominal loading of 1A/phase should not be a significant distortion source, but it will depend on the exact mix of loads. p y[ ] A Vrms B Vrms C Vrms A Irms B Irms C Irms A VThd B VThd C VThd A IThd B IThd C IThd :2 :3 :4 : 6: 6:1 6:2 6:3 6:4 6: Figure 17 ATS #1 [Monitor #2] voltage, current and distortion time plots. The waveform record from utility source, Figure 18 (below), show the moderate distortion level for the voltage and a more significant distortion characteristic for the current waveform. The current waveform may have more to do with the individual loads reaction to the existing voltage distortion. The harmonic analysis contained in the DFT plots, Figures 19 and 2, indicates that the harmonic energy is flowing to the load as opposed to being created by the load. Figures (below) document the ATS #1 circuit performance with the generators as the power source. As expected the distortion increases and harmonic energy is still flowing toward the loads. RECOMMENDATION: Loading associated with the ATS #1 should be inventoried and evaluated with respect to harmonic contribution. Date: Revised /13/212 Page 13 of 21

14 A V B V C V -1 A I B I C I :43:9.8 :43:9.8 :43:9.9 :43:9.9 :44:. Figure 18 ATS #1 [Monitor #2] voltage and current waveforms utility source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A VHarm B VHarm C VHarm H2 H3 H4 H H6 H7 H8 H9 H1 H2 A IHarm B IHarm C IHarm AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND DC Figure 19 ATS #1 [Monitor #2] voltage and current DFT plots utility source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A PHarm B PHarm C PHarm Figure 2 ATS #1 [Monitor #2] Watts DFT plot utility source. Date: Revised /13/212 Page 14 of 21

15 A V B V C V A I B I C I 6:2:29.8 6:2:29.8 6:2:29.9 6:2:29.9 6:2:3. Figure 21 ATS #1 [Monitor #2] voltage and current waveforms generator source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A VHarm B VHarm C VHarm H2 H3 H4 H H6 H7 H8 H9 H1 H2 A IHarm B IHarm C IHarm AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND DC Figure 22 ATS #1 [Monitor #2] voltage and current DFT plots generator source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A PHarm B PHarm C PHarm Figure 23 ATS #1 [Monitor #2] Watts DFT plot generator source. Date: Revised /13/212 Page 1 of 21

16 ATS #4 (Monitor #) Distortion and Harmonic Energy Flow ATS #4 (Monitor #) at this time is another of the circuits accepting harmonic energy from the facility. The general Vthd level is in the 1 range and rises to around 2 during generator operation Figure 24. The nature of the load, ATS #4, makes it difficult to assign a nominal load value as the cycling of the equipment results in substantial variations in current levels. There were no reported problems during the test period, but the significant increase in voltage distortion makes this circuit a candidate for additional monitoring/study under both nominal and generator operation. Timeplot Elevator ATS [Monitor #] A Vrms B Vrms C Vrms A VRss B VRss C VRss A Irms B Irms C Irms 1 1 A IRss B IRss C IRss :2 :3 :4 : 6: 6:1 6:2 6:3 6:4 6: Figure 24 ATS #4 [Monitor #] voltage, current and distortion time plots. The waveform record from utility source, Figure 2 (below), show the moderate distortion level for the voltage and current waveforms. The harmonic analysis contained in the DFT plots, Figures 26 and 27, indicates that the harmonic energy is flowing to the load as opposed to being created by the load. This could be misleading as the start/stop operation of the elevators is difficult to characterize. Figures 28-3 (below) document the ATS #4 circuit performance with the generators as the power source. As expected the distortion increases and harmonic energy is still flowing toward the loads. RECOMMENDATION: Loading associated with the ATS #4 should be studied in more detail to document inrush (start-up) conditions under both normal and emergency operations. Now that there is some baseline information it will be much easier to set meaningful thresholds to capture the necessary information. Date: Revised /13/212 Page 16 of 21

17 A V B V C V D V -1 A I B I C I :42:29.8 :42:29.8 :42:29.9 :42:29.9 :42:3. Figure 2 ATS #4 [Monitor #] voltage and current waveforms utility source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A VHarm B VHarm C VHarm H2 H3 H4 H H6 H7 H8 H9 H1 H2 A IHarm B IHarm C IHarm AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND DC Figure 26 ATS #4 [Monitor #] voltage and current DFT plots utility source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A PHarm B PHarm C PHarm Figure 27 ATS #4 [Monitor #] Watts DFT plot utility source. Date: Revised /13/212 Page 17 of 21

18 A V B V C V -1 A I B I C I 6:23:9.8 9/8/21 6:23:9.8 6:23:9.9 6:23:9.9 6:24:. Figure 28 ATS #4 [Monitor #] voltage and current waveforms generator source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A VHarm B VHarm C VHarm H2 H3 H4 H H6 H7 H8 H9 H1 H2 A IHarm B IHarm C IHarm AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND DC Figure 29 ATS #4 [Monitor #] voltage and current DFT plots generator source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A PHarm B PHarm C PHarm Figure 3 ATS #4 [Monitor #] Watts DFT plot generator source. Date: Revised /13/212 Page 18 of 21

19 Generator 12.47kV (Monitor #1) Distortion and Harmonic Energy Flow The Generator 12.47kV (Monitor #1) accepts th and 7 th harmonic energy from the loads. The general Vthd level is slightly under 4. Figure 31. It will be interesting to reevaluate the current distortion after mitigation of the ATS #2 1A of harmonic load A-B Vrms B-C Vrms C-A Vrms A Irms B Irms C Irms A-B VThd B-C VThd C-A VThd A IThd B IThd C IThd 6:2 6:1 6:1 6:2 6:3 6:3 Figure kV Generator Supply [Monitor #1] voltage, current and distortion time plots. The waveform record from utility source, Figure 32 (below), shows moderate distortion levels for the voltage and current waveforms. The harmonic analysis contained in the DFT plots, Figures 33 and 34, indicates that the harmonic energy is flowing to the load as opposed to being created by the load A-B V B-C V C-A V - -1 A I B I C I 6::29.8 6::29.8 6::29.9 6::29.9 6::3. Figure kV Generator Supply [Monitor #1] voltage and current waveforms generator source. Date: Revised /13/212 Page 19 of 21

20 H2 H3 H4 H H6 H7 H8 H9 H1 A IHarm B IHarm C IHarm H2 H2 H3 H4 H H6 H7 H8 H9 H1 H2 A VHarm B VHarm C VHarm AV BV CV DV A-BV B-CV C-AV AI BI CI DI RMS FND N/A N/A N/A DC Figure kV Generator Supply [Monitor #1] voltage and current DFT plots generator source H2 H3 H4 H H6 H7 H8 H9 H1 H2 A PHarm B PHarm C PHarm Summary Figure kV Generator Supply [Monitor #1] Watts DFT plot generator source. It is surprising how well thing operate in view of the level of distortion under normal operating conditions. As a general rule of thumb we try to maintain Vthd to less than and expect some increase when switching to generator operations with the corresponding higher source impedance. In the case of General Hospital the nominal Vthd on the 48V bus is about 8 and increases, as expected during operation on the emergency supply. The major contributor to the distortion levels is the ATS #2 loads that typically appear to run about 1A/phase at 48Vac. All drives were verified to have either 3 or line reactors installed with, obviously, is insufficient to control the th and 7 th harmonics associated with 6-pulse loads. There may be additional load issues, but they will be difficult to identify as they would be masked by the size of the ATS #2 load and associated harmonics. Date: Revised /13/212 Page 2 of 21

21 The mitigation of the harmonics, especially the th (3Hz) harmonic, associated with the ATS #2 loads should be the first priority. A number of possible solutions are available to address these issues which are discussed in more detail in the earlier sections of this report. Specifically Replace 3 line reactors with (assuming the drives can tolerate the higher losses) Install phase-shifting transformers on selected drives to cancel harmonic currents. Replace (or supplement) existing line-reactors with harmonic filters NOT RECOMMENDED. This solution would require very careful management of the installation and probably constant tweaking to prevent interaction between filters. Install a single point solution, active filter, on the load side of the ATS #2. Size/space can be an issue with this equipment; it all depends on the amount of harmonic current being mitigated. Please understand that reducing the Vthd from 8 to 4 would probably resolve most, if not all, of this type of problem and improve performance and reliability. The other issue investigated in the activity is the performance of the UPS equipment. The problem has been the unreliable operation of the equipment when on the emergency generator power source. Specifically the UPS input power module does not always recognize the generator as a viable power source and under extended runtime the back-up battery supply is depleted. In a previous effort to resolve the UPS performance problem a set of active harmonic filters were installed. Unfortunately, these are not an appropriate solution for this type of problem. The UPS equipment has a power factor corrected input power supply which is a voltage following device the current tracks the input voltage signal. The active harmonic filter is also a voltage following device two similar devices in series seldom works. During the testing, while operating on the generator supply, the active harmonic filter equipment was turned-off the UPS equipment returned to normal operation with the active harmonic filters off. Recommend discontinuing use of the active harmonic filter equipment for this application. General Hospital is a large complex facility and some type of on-going monitoring capability should be implemented on the key distribution locations. This will allow for tracking of conditions over time and with the proper analysis can result in identifying unsatisfactory conditions before they become catastrophic. In addition with permanent monitoring should a problem occur much better information is available to facilities personnel to help them determine the appropriate course of action. Prepared by: Bruce Lonie President, PowerCET Corporation Disclaimer The information contained in this document is provided for educational purposes only as an example on how to incorporate power monitoring data and other observations into a report format. It is not intended to provide consulting advice for any specific problem or situation. This is a copyrighted document and intended for individual use and should not be reproduced or distributed in any form without specific written permission from PowerCET Corporation. Date: Revised /13/212 Page 21 of 21

Sample Consulting Report ATS Transfer Testing with Chiller s Operational Data Center One

Sample Consulting Report ATS Transfer Testing with Chiller s Operational Data Center One PowerCET Corporation 335 Scott Blvd., Bldg. 55. Unit 1 Santa Clara, CA 9554 USA Voice: 48/988-1346 Fax: 48/988-4869 URL: http://www.powercet.com E-mail: consulting@powercet.com Background Sample Consulting

More information

Consulting Report Breaker Trip / Fuse Blowing Investigation MCC / Blower Motors

Consulting Report Breaker Trip / Fuse Blowing Investigation MCC / Blower Motors PowerCET Corporation 3350 Scott Blvd., Bldg. 55. Unit 1 Santa Clara, CA 95054 USA Voice: 408/988-1346 Fax: 408/988-4869 URL: http://www.powercet.com E-mail: consulting@powercet.com Introduction / Background

More information

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Effective Harmonic Mitigation with Active Filters

Effective Harmonic Mitigation with Active Filters Advancing Power Quality White Paper Effective Harmonic Mitigation with Active Filters Written by: Ian Wallace Variable Speed Drive with no Harmonic Mitigation Industry standard variable speed drives, with

More information

7/15/2002 PP.AFD.08 1 of 28

7/15/2002 PP.AFD.08 1 of 28 Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy

More information

Technical Paper. Harmonic Distortion in Data Centers

Technical Paper. Harmonic Distortion in Data Centers Technical Paper Harmonic in Data Centers Written By: Ian Wallace Summary Power quality and power reliability are critical to data center operation. As strides have been made to improve energy efficiency

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Harmonic Distortion Levels Measured at The Enmax Substations

Harmonic Distortion Levels Measured at The Enmax Substations Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

Complimentary Reference Material

Complimentary Reference Material Complimentary Reference Material This PDF has been made available as a complimentary service for you to assist in evaluating this model for your testing requirements. TMG offers a wide range of test equipment

More information

Active Harmonic Filter (AF3)

Active Harmonic Filter (AF3) Active Harmonic Filter (AF3) Active Harmonic Filter Improving the Efficiency and Life of System by use of Digital Active Power Conditioner HARMONICS 50 Hz, fundamental 100 Hz, 2nd Harmonic 150 Hz, 3rd

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

Agilent 6800 Series AC Power Source/Analyzer

Agilent 6800 Series AC Power Source/Analyzer Agilent 6800 Series AC Power Source/Analyzer Product Note Using the Agilent Technologies 6800 Series AC Power Source/Analyzers for Generation and Measurement Applications: Simulating AC Line Sub-Cycle

More information

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern

More information

How Harmonics have led to 6 Power Factor Misconceptions

How Harmonics have led to 6 Power Factor Misconceptions Harmonic and Energy Saving Solutions How Harmonics have led to 6 Power Factor Misconceptions Tony Hoevenaars, P.Eng. Power Factor Misconceptions 1. Low power factor is normally caused by electric motors

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

How adjustable speed drives affect power distribution

How adjustable speed drives affect power distribution How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually

More information

SHUNT ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER 75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines

OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines by Judith M. Russell Consulting Electrical Engineer PowerLines Introduction Power Quality has historically been quantified in terms of voltage. Metering equipment measures RMS voltage level, voltage sags

More information

Harmonic Requirements

Harmonic Requirements Chapter 1 Harmonic Requirements 1.1 INTRODUCTION Placing limits upon the effects that nonlinear loads may produce on users of electric power requires definition of system and equipment parameters. The

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion Harmonic Solutions Clean Power Drive Solution to Harmonic Distortion UTILITY GRID UTILITY SWITCH YARD IN THE FACILITY IEEE-519 POINT OF COMMON COUPLING POWER PLANT GENERATION TRANSMISSION MEDIUM VOLTAGE

More information

Reliable Power Meters Multipoint Power Recorder

Reliable Power Meters Multipoint Power Recorder Reliable Power Meters Multipoint Power Recorder High-speed capability for permanent installation Technical Data What is Full Disclosure Technology? Full Disclosure Technology is built into all Fluke and

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Understanding Input Harmonics and Techniques to Mitigate Them

Understanding Input Harmonics and Techniques to Mitigate Them Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations

More information

Fluke MDA-510 and MDA-550 Motor Drive Analyzer

Fluke MDA-510 and MDA-550 Motor Drive Analyzer TECHNICAL DATA Fluke MDA-510 and MDA-550 Motor Drive Analyzer Simplify complex motor-drive troubleshooting with guided test setups and automated drive measurements that provide reliable, repeatable test

More information

APPLICATION GUIDE. Harmonics in HVAC applications

APPLICATION GUIDE. Harmonics in HVAC applications APPLICATION GUIDE Harmonics in HVAC applications Table of contents 4 Harmonics in general and why we should care 4 Introduction 4 Basics of harmonics 5 Causes of harmonic distortion 5 Problems caused

More information

ZENER ELECTRIC PTY LTD

ZENER ELECTRIC PTY LTD ACN 00 595 428 APPLICATION NOTE: IM 0002 Revision -, June 996 Effective: 24/06/96 Topic: Mains Harmonic Disturbance and Variable Speed AC-Drives Introduction Most common industrial variable speed drives

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

The increase in the application

The increase in the application Harmonic mitigation for AC variable frequency pump drives Pump applications increasingly use AC variable speed drives. However, their operation introduces harmonic distortion of voltage supplies, which

More information

Transmission Line Models Part 1

Transmission Line Models Part 1 Transmission Line Models Part 1 Unlike the electric machines studied so far, transmission lines are characterized by their distributed parameters: distributed resistance, inductance, and capacitance. The

More information

AC Power Instructor Notes

AC Power Instructor Notes Chapter 7: AC Power Instructor Notes Chapter 7 surveys important aspects of electric power. Coverage of Chapter 7 can take place immediately following Chapter 4, or as part of a later course on energy

More information

CHAPTER 4 HARMONICS AND POWER FACTOR

CHAPTER 4 HARMONICS AND POWER FACTOR 4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried

More information

NJWA - Harmonics and Drives Proper System Design

NJWA - Harmonics and Drives Proper System Design Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives

More information

ABB n.v. Power Quality Products, October 2014

ABB n.v. Power Quality Products, October 2014 ABB n.v. Power Quality Products, October 2014 Power Quality Harmonic Basics Problems and solutions March 19, 2015 Slide 1 828m high 160 floors in total Total 113 PQF in this tower, 12000A PQFS 45M IP30

More information

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 5, SEPTEMBER 2001 603 A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

More information

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,

More information

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar. Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate

More information

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

POWER QUALITY MONITORING - PLANT INVESTIGATIONS Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it

More information

VFDs and Harmonics in HVAC Applications

VFDs and Harmonics in HVAC Applications VFDs and Harmonics in HVAC Applications Larry Gardner Product Marketing Manager Yaskawa America, Inc. Jeff Grant Senior Sales Engineer LONG Building Technologies October 20, 2016 2016 Yaskawa America,

More information

Tuningintobetter power quality

Tuningintobetter power quality Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign

More information

PROGRAMMABLE AC POWER SOURCE MODEL 6500 SERIES MODEL 6500 SERIES. Programmable AC Power Source. Key Features:

PROGRAMMABLE AC POWER SOURCE MODEL 6500 SERIES MODEL 6500 SERIES. Programmable AC Power Source. Key Features: Programmable AC Power Source MODEL 6500 SERIES Key Features: PROGRAMMABLE AC POWER SOURCE MODEL 6500 SERIES The global AC power testing requirements demand more sophisticated AC Power Source that is capable

More information

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation UPEC21 31st Aug - 3rd Sept 21 Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation H. M. Zubi IET and IEEE member hz224@bath.ac.uk R. W. Dunn IEEE member E-mail r.w.dunn@bath.ac.uk

More information

Dynamic Generation of DC Displacement AN 13

Dynamic Generation of DC Displacement AN 13 Dynamic Generation of DC Displacement AN 13 Application Note to the R&D SYSTEM Nonlinearities inherent in the transducer produce a DC component in the voice coil displacement by rectifying the AC signal.

More information

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA ATCO Electric Hangingstone Substation HARMONIC STUDY Prepared By Pierre Archambault, PEng Power Survey International Inc. 8025 Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA Rev.: 6 March 2007 TABLE OF

More information

Do Capacitor Switching Transients Still Cause Problems?

Do Capacitor Switching Transients Still Cause Problems? Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution

More information

ETSI EN V1.2.1 ( )

ETSI EN V1.2.1 ( ) EN 300 132-3 V1.2.1 (2003-08) European Standard (Telecommunications series) Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified

More information

Application Note. Applicable Product: AC Drives

Application Note. Applicable Product: AC Drives Application Note Application Note Guidelines For The Use Of 400-600 Volt AC Drives In Medium Voltage Applications Applicable Product: AC Drives 4kV Step-down Transformer AC Drive 400-600V Output Filter

More information

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND

More information

Harmonic Filters for Single Phase Equipment

Harmonic Filters for Single Phase Equipment POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,

More information

Fluke 40/41 Power Harmonics Analysers

Fluke 40/41 Power Harmonics Analysers Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power

More information

Reducing Total Harmonic Distortion with Variable Frequency Drives

Reducing Total Harmonic Distortion with Variable Frequency Drives Reducing Total Harmonic Distortion with Variable Frequency Drives Low Harmonic Technology in Optidrive Eco Overview Overview Both AC line chokes and DC link chokes have historically been used with Variable

More information

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS. MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC

More information

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter)

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter) Exercise 2 Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter) EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the singlephase grid-tied inverter. DISCUSSION OUTLINE

More information

Drives 101 Lesson 5. Power Input Terminology for a VFD

Drives 101 Lesson 5. Power Input Terminology for a VFD Drives 101 Lesson 5 Power Input Terminology for a VFD This lesson covers the terminology associated with the incoming power to a Variable Frequency Drive (VFD) and the efforts to protect both the VFD and

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

Presents. Harmonics Years

Presents. Harmonics Years Presents Harmonics What is a Harmonic? A harmonic is the term used for current flow on your facilities power system at frequencies other than 60Hertz. Harmonic Problems Include: Harmonic Problems

More information

Motors and drives. Module B- Introduction to input measurements

Motors and drives. Module B- Introduction to input measurements Motors and drives Module B- Introduction to input measurements Introduction to input measurements There are a number of locations where input measurements may be made Which is the most important location

More information

Energy Explorer PROFESSIONAL POWER & HARMONICS ANALYSER

Energy Explorer PROFESSIONAL POWER & HARMONICS ANALYSER 1 Energy Explorer PORTABLE POWER ANALYSERS DESCRIPTION PROFESSIONAL POWER & HARMONICS ANALYSER ENERGY EXPLORER is an advanced Power Analyser, designed for use by electricians, plant engineers and energy

More information

Active Vibration Isolation of an Unbalanced Machine Tool Spindle

Active Vibration Isolation of an Unbalanced Machine Tool Spindle Active Vibration Isolation of an Unbalanced Machine Tool Spindle David. J. Hopkins, Paul Geraghty Lawrence Livermore National Laboratory 7000 East Ave, MS/L-792, Livermore, CA. 94550 Abstract Proper configurations

More information

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 1, JANUARY/FEBRUARY 2002 131 New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications Sewan Choi,

More information

Harmonic Mitigating Transformer - Technical Guide

Harmonic Mitigating Transformer - Technical Guide Harmonic Mitigating - Technical Guide HARMONY Series s HARMONY-1 www.mirusinternational.com Benefits: Prevent voltage flat-topping while reducing energy costs. Reduce voltage distortion caused by harmonic

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

SIMPLE RULES FOR SOLVING POWER QUALITY MYSTERIES

SIMPLE RULES FOR SOLVING POWER QUALITY MYSTERIES SIMPLE RULES FOR SOLVING POWER QUALITY MYSTERIES Prepared for the Conference on Protecting Electrical Networks and Quality of Supply Heathrow, UK, 22-23 January 1997 Prepared by, Richard P. Bingham Dranetz

More information

Power Factor. Power Factor Correction.

Power Factor. Power Factor Correction. Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively

More information

POWER QUALITY THAILAND LTD SINCE 1986

POWER QUALITY THAILAND LTD SINCE 1986 POWER QUALITY THAILAND LTD SINCE 1986 PQ TEST EQUIPMENT (198 S TO 215) BMI Power Quality recorders ($2,) BMI Energy recorders ($8,) BMI Line viewers (with oscilloscope) ($2) Dranetz 66 (1975) 626 (198

More information

HARMONIC MITIGATIONCASE STUDY

HARMONIC MITIGATIONCASE STUDY HARMONIC MITIGATIONCASE STUDY CNCE AND NCE INSTALLATION AT BROADCASTING STUDIO Concerned about video noise detected on some of its studio equipment, E! Entertainment Television (ETV), commissioned a study

More information

ECET Modern Power

ECET Modern Power ECET 273000 Modern Power Course Instructors Course Philosophy This course is an introduction to a wide range of electrical energy systems technologies. Topics include fundamentals of energy conversion,

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis By ALL-TEST Pro, LLC & EMA Inc. Industry s use of Motor Drives for AC motors continues to grow and the Pulse-Width

More information

PQ Monitoring Standards

PQ Monitoring Standards Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality

More information

Power Quality, Earthing And Bonding Oct $4,250 Dubai, UAE. In any of the 5 star hotels. The exact venue will be informed once finalized.

Power Quality, Earthing And Bonding Oct $4,250 Dubai, UAE. In any of the 5 star hotels. The exact venue will be informed once finalized. Training Title POWER QUALITY, EARTHING AND BONDING Training Duration 5 days Training Date Power Quality, Earthing And Bonding 5 04 08 Oct $4,250 Dubai, UAE In any of the 5 star hotels. The exact venue

More information

Harmonic Filtering in Variable Speed Drives

Harmonic Filtering in Variable Speed Drives Harmonic Filtering in Variable Speed Drives Luca Dalessandro, Xiaoya Tan, Andrzej Pietkiewicz, Martin Wüthrich, Norbert Häberle Schaffner EMV AG, Nordstrasse 11, 4542 Luterbach, Switzerland luca.dalessandro@schaffner.com

More information

Harmonics, its Mitigation & Result of Case study of Spinning Mill

Harmonics, its Mitigation & Result of Case study of Spinning Mill International Journal of Innovative Research in Engineering & Management (IJIREM) ISSN: 2350-0557, Volume-2, Issue-4, July 2015, its Mitigation & of Case of Spinning Mill Yogesh Subhash Shimpi M. Tech

More information

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists 3,900 116,000 120M Open access books available International authors and editors Downloads Our

More information

UNBALANCED CURRENT BASED TARRIF

UNBALANCED CURRENT BASED TARRIF UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage &current unbalance are serious power quality problems with

More information

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1 Module 5 DC to AC Converters Version 2 EE IIT, Kharagpur 1 Lesson 37 Sine PWM and its Realization Version 2 EE IIT, Kharagpur 2 After completion of this lesson, the reader shall be able to: 1. Explain

More information

Alternator winding pitch and power system design

Alternator winding pitch and power system design Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering

More information

TEST REPORT IEC Uninterruptible power systems Part 3: Method of specifying the performance and test requirements

TEST REPORT IEC Uninterruptible power systems Part 3: Method of specifying the performance and test requirements Test Report issued under the responsibility of: TEST REORT IEC 62040-3 Uninterruptible power systems art 3: Method of specifying the performance and test requirements Report reference No...: 11-EL-0026.06

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Abstract: A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Vijay Bendre, Prof. Pat Bodger, Dr. Alan Wood. Department of Electrical and Computer Engineering, The University of

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

Harmonics Elimination Using Shunt Active Filter

Harmonics Elimination Using Shunt Active Filter Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 7 1 Today Sags and short interruptions Some Homework 2 pointers

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Final Exam Fall 2018

Final Exam Fall 2018 Due date: 14 December Page 1 of 6 Instructions: This is a take-home exam. It is considered open-book, and open-notes. The use of Mathcad, Matlab, Excel, and similar software is encouraged where it is appropriate.

More information

Please use the Q & A utility to ask us any questions concerning the material being presented.

Please use the Q & A utility to ask us any questions concerning the material being presented. Meet Our Team Webinar Notes Please use the Q & A utility to ask us any questions concerning the material being presented. You can find a recording of this webinar and presentation on our Video Library

More information

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT Shyam V. Alaspure 1, Snehal G. Vinchurkar 2, Swapnil D. Raut 1 Electronics & Telecommunication 2 Electronics & Power 3 Computer 1 Lecturer, G.H. Raisoni Polytechnic

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Alternators Reactance for Nonlinear Loads

Alternators Reactance for Nonlinear Loads Alternators Reactance for Nonlinear Loads Allen Windhorn. P.E. 26 July, 2013 Introduction Widespread invocation of IEEE Std 519 on systems powered by generators, together with increased use of equipment

More information

Tech Byte 16: The Truths About Transformers Part 2

Tech Byte 16: The Truths About Transformers Part 2 In The Truths About Transformers Part 1, the discussion focused on the reality that not all transformers are created equal. Today, more than ever, there is a need to look at every transformer application

More information

Electric Power Quality: Voltage Sags Momentary Interruptions

Electric Power Quality: Voltage Sags Momentary Interruptions Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage

More information

Harmonic Analysis and Its Mitigation Using Different Passive Filters

Harmonic Analysis and Its Mitigation Using Different Passive Filters Harmonic Analysis and Its Mitigation Using Different Passive Filters Ashlin Gloria Reginald 1, K J Thomas 2 1 PG Scholar, Amal Jyothi College of Engineering, Kanjirapally Kottayam, India ashlingloriar@gmail.com

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information