Homepage > Products > Control units > VARYCONTROL > Control components > Type Easy. Type Easy

Size: px
Start display at page:

Download "Homepage > Products > Control units > VARYCONTROL > Control components > Type Easy. Type Easy"

Transcription

1 Homepage > Products > Control units > VARYCONTROL > Control components > Type Easy Type Easy QUICK AND EASY HANDLING Control components for VAV terminal units, to be mounted on the terminal unit for easy operation Simplified ordering and on-site assignment to rooms as selection is based on the nominal size of the duct Rapid volume flow rate setting without additional device Indicator light simplifies functional checking Proven technology of the Compact volume flow controllers Suitable for constant and variable volume flows as well as for V min / V max switching APPLICATION Application Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal units Dynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casing Suitable for different control tasks depending on how the input for the setpoint value signal is used The output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpoint

2 Override control by means of switches or relays Volume flow rate actual value is available as linear voltage signal Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow is passed through the transducer in order to measure the volume flow rate, please note: With heavy dust levels in the room, suitable extract air filters must be provided. If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used Application Electronic volume flow controllers of Type Easy are compact, all-in-one control devices for VAV terminal units Dynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casing Suitable for different control tasks depending on how the input for the setpoint value signal is used The output signals of the room temperature controller, central BMS, air quality controller or similar units control the volume flow rate setpoint Override control by means of switches or relays Volume flow rate actual value is available as linear voltage signal Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection. Since a partial volume flow is passed through the transducer in order to measure the volume flow rate, please note: With heavy dust levels in the room, suitable extract air filters must be provided. If the air is polluted with fluff or sticky particles, or if it contains aggressive media, Easy controllers cannot be used DESCRIPTION Construction LMV-D3AL-F for LVC 227V-024T for LVC LMV-D3A-F for TVR 227V-024T für TVR

3 227V-024T for TVJ, TVT SMV-D3A for TVT LMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA Operating modes Variable volume flow V V min max : minimum volume flow rate : maximum volume flow rate Constant value V min : constant volume flow rate V : 100 % max Signal voltage range 0 10 V DC Parts and characteristics Sensor for dynamic differential pressure measurements Mechanical stops for limiting the damper blade positions Actuators with overload protection Release button to allow for manual operation Construction LMV-D3AL-F for LVC 227V-024T for LVC LMV-D3A-F for TVR 227V-024T für TVR 227V-024T for TVJ, TVT SMV-D3A for TVT LMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA Operating modes

4 Variable volume flow V V min max : minimum volume flow rate : maximum volume flow rate Constant value V min : constant volume flow rate V : 100 % max Signal voltage range 0 10 V DC Parts and characteristics Sensor for dynamic differential pressure measurements Mechanical stops for limiting the damper blade positions Actuators with overload protection Release button to allow for manual operation TECHNICAL INFORMATION Function, Technical data, Order code, Produktbeziehungen FUNCTION Functional description VAV terminal units control the volume flow in a closed loop, i.e. measurement comparison control. The volume flow rate is determined by measuring the differential pressure (effective pressure). For this purpose the VAV terminal unit is fitted with a differential pressure sensor. The integral differental pressure transducer transforms the effective pressure into a voltage signal. The volume flow rate actual value is hence available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (V ). nom

5 The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switch contacts. Variable volume flow control results in a value between V and V. It is possible to override the room temperature control, e.g. by a complete shut-off of the duct. The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly. The volume flow rate parameters V and V can be set on potentiometers. min max Volume flow control The volume flow controller works independent of the duct pressure Differential pressure fluctuations do not result in permanent volume flow rate changes To prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move. The factory set volume flow rate parameters can be altered by the customer min max Functional description VAV terminal units control the volume flow in a closed loop, i.e. measurement comparison control. The volume flow rate is determined by measuring the differential pressure (effective pressure). For this purpose the VAV terminal unit is fitted with a differential pressure sensor. The integral differental pressure transducer transforms the effective pressure into a voltage signal. The volume flow rate actual value is hence available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (V ). nom The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switch contacts. Variable volume flow control results in a value between V and V. It is possible to override the room temperature control, e.g. by a complete shut-off of the duct. The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly. The volume flow rate parameters V and V can be set on potentiometers. min max Volume flow control The volume flow controller works independent of the duct pressure Differential pressure fluctuations do not result in permanent volume flow rate changes To prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move. The factory set volume flow rate parameters can be altered by the customer min max

6 Principe de fonctionnement Régulateurs Easy et Compact 1 Sonde de pression différentielle 2 Servomoteur 3 Régulateur de débit 4 Signal de valeur de consigne Régulateur Easy

7 1 Régulateur Easy 2 V max - Potentiomètre 3 V min - Potentiomètre 4 Voyant lumineux 5 Bouton-poussoir de service 6 Raccordements pour capteur de pression effective 7 Capot de protection 8 Axe de blocage Illustration : LMV-D3A-F

8 TECHNICAL DATA Easy controller LMV-D3AL-F Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC 10/+20 % Power rating (AC) 3.5 VA max. Power rating (DC) 2 W max. Running time for s Setpoint value signal input 0 10 V DC, R > 100 kω a Actual value signal output 0 10 V DC, 0.5 ma max. IEC protection class III (protective extra-low voltage) Protection level IP 20 EC conformity EMC to 2014/30/EU, low voltage to 2014/35/EU Easy controller 227V-024T

9 Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC ± 20 % Power rating (AC) 5 VA max. Power rating (DC) 3 W max. Running time for s Setpoint value signal input 0 10 V DC, R > 100 kω a Actual value signal output 0 10 V DC, 0.5 ma max. IEC protection class III (protective extra-low voltage) Protection level IP 20 EC conformity EMC according to 2014/30/EU Easy controllers LMV-D3A and LMV-D3A-F

10 Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC 10/+20 % Power rating (AC) 5 VA max. Power rating (DC) 2.5 W max. Running time for s Setpoint value signal input 0 10 V DC, R > 100 kω a Actual value signal output 0 10 V DC, 0.5 ma max. IEC protection class III (protective extra-low voltage) Protection level IP 20 EC conformity EMC according to 2014/30/EU Easy controller 227V-024T

11 Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC ± 20 % Power rating (AC) 5 VA max. Power rating (DC) 3 W max. Running time for s Setpoint value signal input 0 10 V DC, R > 100 kω a Actual value signal output 0 10 V DC, 0.5 ma max. IEC protection class III (protective extra-low voltage) Protection level IP 20 EC conformity EMC according to 2014/30/EU Easyregler 227V-024T

12 Versorgungsspannung (Wechselspannung) 24 V AC ± 20 %, 50/60 Hz Versorgungsspannung (Gleichspannung) 24 V DC ± 20 % Anschlussleistung (Wechselspannung) Max. 5 VA Anschlussleistung (Gleichspannung) Max. 3 W Laufzeit für s Eingang Sollwertsignal 0 10 V DC, R > 100 kω a Ausgang Istwertsignal 0 10 V DC, max. 0,5 ma Schutzklasse III (Schutzkleinspannung) Schutzgrad IP 20 EG-Konformität EMV nach 2014/30/EU Easy controller SMV-D3A

13 Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz Supply voltage (DC) 24 V DC 10/+20 % Power rating (AC) 6 VA max. Power rating (DC) 3 W max. Running time for s Setpoint value signal input 0 10 V DC, R > 100 kω a Actual value signal output 0 10 V DC, 0.5 ma max. IEC protection class III (protective extra-low voltage) Protection level IP 20 EC conformity EMC according to 2014/30/EU Variants, Product details VARIANTS

14 Part number Type Type of VAV terminal unit M466EU1 LMV-D3AL-F LVC M466EU2 227V-024T LVC M466ES1 LMV-D3A-F TVR M466DC3 227V-024T TVR A V-024T TVJ, TVT M466ES3 SMV-D3A TVT M466ES2 LMV-D3A TZ-Silenzio, TA-Silenzio, TVZ, TVA Régulateur Easy LMV-D3AL-F

15 Régulateur Easy 227V-024T Régulateur Easy LMV-D3A

16 Régulateur Easy 227V-024T

17 Régulateur Easy 227V-024T

18 Régulateur Easy SMV-D3A PRODUCT DETAILS The Easy principle The Easy principle Sélectionner la dimension nominale

19 Régler le débit La diode verte s'allume : c'est prêt! Electrical connection, Commissioning, Characteristics

20 ELECTRICAL CONNECTION Répartition du bornier 1, : terre 2 ~, +: tension électrique 24 V 3 w: signal de valeur de consigne 0 10 V DC 4 U: signal de valeur réelle 0 10 V DC INBETRIEBNAHME Commissioning Use the potentiometer to set the minimum or maximum volume flow rate on site Take the adjustment value from the volume flow rate scale (sticker on each VAV terminal unit) Comply with the volume flow rate control range, do not set a volume flow rate which is below the minimum flow rate Volume flow rate range of LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA: % Volume flow rate range of TVJ and TVT: % Once the VAV terminal unit has been installed and wired, and the volume flow rate has been set, the unit is ready for operation Remove the transparent cover of the Easy controller only temporarily for wiring and commissioning Commissioning Use the potentiometer to set the minimum or maximum volume flow rate on site Take the adjustment value from the volume flow rate scale (sticker on each VAV terminal unit) Comply with the volume flow rate control range, do not set a volume flow rate which is below the minimum flow rate Volume flow rate range of LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA: % Volume flow rate range of TVJ and TVT: % Once the VAV terminal unit has been installed and wired, and the volume flow rate has been set, the unit is ready for operation Remove the transparent cover of the Easy controller only temporarily for wiring and commissioning Échelle de réglage de débit pour TVR-Easy

21 Chaque unité terminale VAV porte un autocollant avec une échelle de réglage de débit afin de déterminer les paramétrages sur site (voir exemple : TVR-Easy, grandeur nominale 200). Les pourcentages se rapportent à la plage de réglage qui peut être utilisé. Régulation à débit variable Les débits requis doivent être réglés sur site. Si V est réglé plus haut que V, V est fourni en tant que débit constant, même en cas d'émission d'un signal de consigne. min max min Si V est réglé sur 0 %, le débit en résultant se situera entre la coupure et Vmax. Si le signal de consigne chute en min dessous de 0,5 V DC, le clapet de réglage se ferme (coupure). Régulation à débit constant Home Contact Imprint Delivery and payment terms Privacy Disclaimer TROX Austria GmbH

22 Homepage > Products > Control units > VARYCONTROL > Control components > Type Easy Le débit constant est défini avec le potentiomètre V. Dans ce cas, le réglage du potentiomètre V est sans importance. min max Variable de pilotage en provenance du système centralisé de gestion du bâtiment (GTB-GTC) Pour que le système centralisé de gestion du bâtiment pilote le débit, il faut régler le potentiomètre V potentiomètre V max sur 0 % et le sur 100 %. Si le signal de consigne chute en dessous de 0,5 V DC, le clapet de réglage se ferme (coupure). Étant donné que le signal de consigne peut ou ne peut pas être inférieure à 0,1 V DC, une régulation prioritaire est recommandée pour la fermeture. min Réglage usine Home Contact Imprint Delivery and payment terms Privacy Disclaimer TROX Austria GmbH

23 Homepage > Products > Control units > VARYCONTROL > Control components > Type Easy À la livraison, les unités possèdent des réglages V min = 40 % et V max = 80 %. CHARACTERISTICS Caractéristiques du signal de valeur de consigne Home Contact Imprint Delivery and payment terms Privacy Disclaimer TROX Austria GmbH

24 Homepage > Products > Control units > VARYCONTROL > Control components > Type Easy TROX Austria GmbH Online-Services Service-Hotlines TROX Academy Your contact partner Online fault report Sales Austria and technical consulting Contact Lichtblaustraße Wien, Austria Telefon Fax trox@trox.at Home Contact Imprint Delivery and payment terms Privacy Disclaimer TROX Austria GmbH

TVB-2 INSTRUCTION SHEET. Test Verification Box

TVB-2 INSTRUCTION SHEET. Test Verification Box TVB- INSTRUCTION SHEET Test Verification Box V.07.08 DECLARATION OF CONFORMITY Manufacturer: Address: Product Name: Model Number: Associated Research, Inc. 3860 W. Laurel Dr. Lake Forest, IL 60045, USA

More information

FD470 RAILWAY RELAY, 2 PDT-DB-DM, 3 AMP / 72VDC RELAIS FERROVIAIRE, 2 R (DC)+ 2 T (DE)/ 3 A / 72VCC

FD470 RAILWAY RELAY, 2 PDT-DB-DM, 3 AMP / 72VDC RELAIS FERROVIAIRE, 2 R (DC)+ 2 T (DE)/ 3 A / 72VCC Polarized, non-latching hermetically sealed relay Relais hermétique monostable polarisé Contact arrangement Combinaison des contacts Coil supply Alimentation bobine Qualified or in accordance with Qualifié

More information

Brief description. Type overview

Brief description. Type overview echnical data sheet VAV-Compact KNX A pressure sensor, digital VAV controller and damper actuator all in one, providing a VAV-Compact solution with a communications capability for pressureindependent VAV

More information

12V 7Ah 3.15A AC V +12V DC. Paxton Net2 plus 12V DC 12V DC EXIT /100 Ethernet. INPUT AC V 50 / 60 Hz 1.2A OUTPUT DC 13.

12V 7Ah 3.15A AC V +12V DC. Paxton Net2 plus 12V DC 12V DC EXIT /100 Ethernet. INPUT AC V 50 / 60 Hz 1.2A OUTPUT DC 13. Paxton ins-0006 3 4 - + +V DC V V V V V - 4V Clock/D V Clock/D V DC V DC 0 00 0/00 Ethernet Paxton Net plus I RS485 CAT5 TX RX V INPUT AC 00-4 50 / 60 Hz.A OUTPUT DC 3.8V A AC 00-4 V 7Ah 3.5A - +V DC +

More information

AM 441 S-DIAS Analog Mixed Module ±10 V

AM 441 S-DIAS Analog Mixed Module ±10 V AM 441 S-DIAS Analog Mixed Module ±10 V Date of creation: 03.10.2013 Version date: 18.10.2017 Article number: 20-017-441-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax:

More information

Polycom VoxBox Bluetooth/USB Speakerphone

Polycom VoxBox Bluetooth/USB Speakerphone SETUP SHEET Polycom VoxBox Bluetooth/USB Speakerphone 1725-49004-001C Package Contents Micro USB Cable 1.21 m 4 ft Carrying Case Security USB Cable 3 m 10 ft L-Wrench Optional Accessories Security USB

More information

INSTALLATION MANUAL Model 1923 Load Cells Certified for Explosion Safety na Non-Sparking

INSTALLATION MANUAL Model 1923 Load Cells Certified for Explosion Safety na Non-Sparking INSTALLATION MANUAL Model 1923 Load Cells Certified for Explosion Safety na Non-Sparking 15-165EX 1923 Rev I Page 1 of 7 REVISION REQUIRES NOTIFICATION CERTIFICATION BODY Change Record: DATE Revision Page

More information

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

Technical data. Safety notes.  T3-LR24A-SR en v Subject to changes 1 / 2 echnical data sheet LR4A-SR Modulating rotary actuator for and -way control ball valves orque Nm Nominal voltage AC/DC 4 V Control: Modulating DC... V Position feedback: DC... V echnical data Safety notes

More information

Have Elisha and Emily ever delivered food? No, they haven t. They have never delivered food. But Emily has already delivered newspapers.

Have Elisha and Emily ever delivered food? No, they haven t. They have never delivered food. But Emily has already delivered newspapers. Lesson 1 Has Matt ever cooked? Yes, he has. He has already cooked. Have Elisha and Emily ever delivered food? No, they haven t. They have never delivered food. But Emily has already delivered newspapers.

More information

Differential pressure sensors

Differential pressure sensors 1 912 1912P02 QBM64/ 1912P01 QBM63/ Differential pressure sensors for air and non-aggressive gases, with a diaphragm sensing element QBM63/ QBM64/ With choice of pressure-linear or extracting-the-root

More information

ELECTRONIC THERMOSTAT: T920

ELECTRONIC THERMOSTAT: T920 μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with

More information

ANALOG INPUT/OUTPUT MODULES SPECIFICATIONS* Input resistance. From ± 10 mveff to ± 50 Veff (see ranges) AC input ZIN = 100 KΩ

ANALOG INPUT/OUTPUT MODULES SPECIFICATIONS* Input resistance. From ± 10 mveff to ± 50 Veff (see ranges) AC input ZIN = 100 KΩ ACM ANALOG INPUT/OUTPUT MODULES Analog Input/Output: - Modules - Voltage - Potentiometer - Current - RTDs and thermocouples - Strain gage - Accelerometer - ICP Freq => Voltage - RMS => DC - Etc. Plug and

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control modulating Conversion of sensor signals Communication via KNX (S-Mode)

More information

PL 221 S-DIAS Pixel LED Module

PL 221 S-DIAS Pixel LED Module PL 221 S-DIAS Pixel LED Module Date of creation: 13.03.2018 Version date: 16.05.2018 Article number: 20-018-221-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/6274/4321-18

More information

Vannes à commande manuelle manually actuated valves

Vannes à commande manuelle manually actuated valves Vannes à commande manuelle Vannes 3/2-5/2-5/3 avec raccord G1/8 -G1/4 3/2-5/2-5/3 spool valves with G1/8 -G1/4 threaded ports Installation dans toutes les positions Installation in any position Large gamme

More information

Pser G uide oduct Manual

Pser G uide oduct Manual ADC-T2000 Hub User Product Guide Manual Hub Product Manual 1 Set Up Required Standard home router with active Internet connection Z-Wave devices to be installed Indicator Lights White Flashing: no internet

More information

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC echnical data sheet SMA-PC Parameterisable damper actuator for adjusting air dampers in ventilation and air-conditioning systems in buildings Air damper size up to approx. m orque 0 Nm Nominal voltage

More information

VAV Rectangular Terminal Units

VAV Rectangular Terminal Units RSVQ VAV Rectangular Terminal Units RSVQ Variable Air Volume (VAV) HVAC systems are the best solution to guarantee high levels of comfort and energy effi ciency in civil and industrial applications VAV

More information

Rotary gear motor series AG8...

Rotary gear motor series AG8... Rotary gear motor series AG8... The electric actuator belonging to AG8 series is designed to operate gas valves and air dampers in ventilation and air conditioning systems. The compact design and universal

More information

DATA SHEET Selectable AC transducer TAS-311DG

DATA SHEET Selectable AC transducer TAS-311DG DATA SHEET Selectable AC transducer Measuring on AC networks Class 0.5 (IEC688) measurement Supply/measur. voltage up to 690 V Easy configuration via PC interface possible DEIF A/S Frisenborgvej 33 DK-7800

More information

Huba Control FEINE MESSIDEEN FÜR DRUCK UND STRÖMUNG FOR FINE PRESSURE AND FLOW MEASUREMENT LA FINESSE DES MESURES DE PRESSION ET DE DEBIT

Huba Control FEINE MESSIDEEN FÜR DRUCK UND STRÖMUNG FOR FINE PRESSURE AND FLOW MEASUREMENT LA FINESSE DES MESURES DE PRESSION ET DE DEBIT 694 Relativ- und Differenz-Drucktransmitter Relative and differential pressure transmitter Transmetteur de pression relative et différentielle 0.5 +0.5 mbar / 0 1 50 mbar Huba Control FEINE MESSIDEEN FÜR

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet LMA-MF-P Multifunctional damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx.

More information

Power consumption In operation At rest For wire sizing. 150 s / C Sound power level Motor. Emergency setting function 61 db (A)

Power consumption In operation At rest For wire sizing. 150 s / C Sound power level Motor. Emergency setting function 61 db (A) echnical Data sheets GRK4A-SR-5 Modulating SuperCap rotary actuator with emergency setting function and extended functionalities for butterfly valves and ball valves with mounting flange ISO 511-F05 orque

More information

StreetSounds STS-170-MMST Mobile Master. User Guide

StreetSounds STS-170-MMST Mobile Master. User Guide StreetSounds STS-170-MMST Mobile Master User Guide V1.4 June 3, 2018 1 CONTENTS 1 Introduction... 3 1.1 Mobi Front Panel... 3 1.2 Mobi Rear Panel... 4 1.3 Operating the Mobi... 4 2 FCC Statements... 6

More information

Technical data. Parameterisable damper actuator in the

Technical data. Parameterisable damper actuator in the echnical data sheet Parameterisable damper actuator in the IP66 protective housing for or adjusting ad usting air dampers in industrial plants and in technical building installations For air dampers up

More information

User Manual. Z01-A19NAE26- Wireless LED Bulb Z02-Hub Sengled Hub. LED + Smart Control

User Manual. Z01-A19NAE26- Wireless LED Bulb Z02-Hub Sengled Hub. LED + Smart Control User Manual Z01-A19NAE26- Wireless LED Bulb Z02-Hub Sengled Hub LED + Smart Control EN System Features: Control Element lighting from anywhere at anytime Schedule scenes based on timing, brightness and

More information

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing echnical data sheet Rotary actuator LR4A Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage AC/DC 4 V Control: Open/close or -point echnical data Electrical data Nominal voltage

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-KNX Communicative rotary actuator for ball valves Nominal torque 5 Nm Nominal voltage AC/DC 24 V Conversion of sensor signals echnical data Electrical data Nominal voltage AC/DC

More information

Image. Installation VAV-Universal Retrofit-Set. General Information. Safety notes

Image. Installation VAV-Universal Retrofit-Set. General Information. Safety notes VAV-Universal Retrofit-Set VRD-RE-SET VAV-Universal Retrofit Set for utilisation of existing VAV devices made by various manufacturers. VRD-RE-SET for air velocity up to m/s. Image Suitable only for round

More information

DQ-58 C78 QUESTION RÉPONSE. Date : 7 février 2007

DQ-58 C78 QUESTION RÉPONSE. Date : 7 février 2007 DQ-58 C78 Date : 7 février 2007 QUESTION Dans un avis daté du 24 janvier 2007, Ressources naturelles Canada signale à la commission que «toutes les questions d ordre sismique soulevées par Ressources naturelles

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet GM4A-SR-P Modulating damper actuator for operating air control dampers in ventilation and airconditioning systems for building services installations For air dampers up to approx. 8

More information

PowerView Remote Control Guide

PowerView Remote Control Guide FRONT: OPEN Group 3 Group 4 Group 2 Group 5 LEFT ARROW Sends the middle rail DOWN on Top-Down/Bottom-Up or Duolite products Group 1 Group 6 RIGHT ARROW Sends the middle rail UP on Top-Down/Bottom-Up or

More information

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke s 4 501 ACVATIX Electromotoric actuators for valves SAX.. with a 20 mm stroke SAX31.. Operating voltage AC 230 V, 3-position control signal Operating voltage AC/DC 24 V, control signal DC 0 10 V, 4 20

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LM24A-KNX Communicative damper actuator for adjusting dampers in technical building installations Nominal torque 5 Nm Nominal voltage AC/DC 24 V Conversion of sensor signals echnical

More information

ENERGY SAVINGS WITH VARIABLE SPEED DRIVES ABSTRACT. K M Pauwels. Energy auditor, Laborelec, Industrial Applications, Belgium

ENERGY SAVINGS WITH VARIABLE SPEED DRIVES ABSTRACT. K M Pauwels. Energy auditor, Laborelec, Industrial Applications, Belgium ENERGY SAVINGS WITH VARIABLE SPEED DRIVES ABSTRACT K M Pauwels Energy auditor, Laborelec, Industrial Applications, Belgium This paper focuses on the economic benefits that can be obtained by replacing

More information

Electronic Emission Notices

Electronic Emission Notices Electronic Emission Notices - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - The following information refers to the Lenovo Active pen. Federal

More information

XtremeRange 5. Model: XR5. Compliance Sheet

XtremeRange 5. Model: XR5. Compliance Sheet XtremeRange 5 Model: XR5 Compliance Sheet Modular Usage The carrier-class, 802.11a-based, 5 GHz radio module (model: XR5) is specifically designed for mesh, bridging, and infrastructure applications requiring

More information

Regulatory Compliance Statement

Regulatory Compliance Statement Regulatory Compliance Statement EU Declaration of Conformity The declaration of conformity may be consulted at www.kobo.com/userguides SAR Limits The exposure standard for wireless devices employs a unit

More information

Functional data Factory settings Variable Settings

Functional data Factory settings Variable Settings echnical data sheet Rotary actuator RF-MF(-O) Multifunctional rotary actuator with emergency control for and 3 way control ball valve orque Nm Nominal voltage AC/DC V Control: Modulating DC... V or variable

More information

Mid-Power Expansion Unit (MxU) Quick Installation Sheet

Mid-Power Expansion Unit (MxU) Quick Installation Sheet Mid-Power Expansion Unit (MxU) Quick Installation Sheet CMA-597-AEN GENERAL INFORMATION 1. THE MxU supports the 2.5 GHz TDD band and is installed in conjunction with the mid-power remote unit (MRU) (ordered

More information

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque echnical data sheet GK4A- Communicative SuperCap rotary actuator with emergency setting function and extended functionalities for adjusting air dampers in ventilation and air-conditioning systems for building

More information

FCC Certification Notice: IC Certification

FCC Certification Notice: IC Certification Users Manual VP4450 FCC Certification This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2)

More information

Technical data. Safety notes

Technical data. Safety notes echnical data sheet M3A-F Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. m orque 5 m ominal

More information

..-MF /..-MP /..-MFT(2) /..-MOD /..LON..-MF /..-MP /..-MFT(2) /..-MOD /..LON

..-MF /..-MP /..-MFT(2) /..-MOD /..LON..-MF /..-MP /..-MFT(2) /..-MOD /..LON Product information ZTH-GEN Service-Tool for parameterisable and communicative Belimo actuators and VAV controllers. Connection via service socket on the device or MP/ connection. Information Belimo Automation

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GR24A--R Communicative Retrofit rotary actuator for rotary valves and butterfly valves Nominal torque 40 Nm Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Position

More information

VAV solutions for comfort applications

VAV solutions for comfort applications Product information VAV solutions for comfort applications Table of contents Product range overview volumetric flow and section pressure control 2 Technical data sheet Brief description 3 Type overview

More information

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke s 4 501 ACVATIX Electromotoric actuators for valves SAX.. with a 20 mm stroke SAX31.. Operating voltage AC 230 V, 3-position control signal SAX61.. Operating voltage AC/DC 24 V, control signal DC 0 10

More information

NRT 105: Electronic fan-coil controller, equiflex

NRT 105: Electronic fan-coil controller, equiflex Product data sheet 4.04 R 105: Electronic fan-coil controller, equiflex How energy efficiency is improved ECO Meter for displaying the current energy consumption and digital input for the change-over between

More information

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16 MZ Servomotor for butterfly valves VF, VFH delta-elektrogas.com EE157-01/16 MZ Servomotor Contents Description.... 2 Features........ 2 Functioning and application..... 3 Technical specifications......

More information

SAX..P. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

SAX..P. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke s 4 509 ACVATIX Electromotoric actuators for valves SAX..P with a 20 mm stroke SAX31P.. Operating voltage AC 230 V, 3-position control signal SAX61P.. Operating voltage AC/DC 24 V, control signal DC 0

More information

CB TEST CERTIFICATE. Uninterruptible Power Supply. Additional Information on page 2 BK500...

CB TEST CERTIFICATE. Uninterruptible Power Supply. Additional Information on page 2 BK500... Ref. Certif. No. NO49720 IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR ELECTRICAL EQUIPMENT (IECEE) CB SCHEME SYSTEME CEI D ACCEPTATION MUTUELLE DE CERTIFICATS D ESSAIS DES EQUIPEMENTS ELECTRIQUES

More information

Technical data sheet. Technical data. Safety notes

Technical data sheet. Technical data. Safety notes echnical data sheet LM4A-F Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. m orque 5 Nm Nominal

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet SM4A-SR-P Modulating damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. 4 m orque

More information

StreamStick by NAV-TV is a USB-powered, HI-FI Bluetooth 4.0 audio streaming module for automotive and home use. Make ANY stereo (equipped with AUX

StreamStick by NAV-TV is a USB-powered, HI-FI Bluetooth 4.0 audio streaming module for automotive and home use. Make ANY stereo (equipped with AUX StreamStick by NAV-TV is a USB-powered, HI-FI Bluetooth 4.0 audio streaming module for automotive and home use. Make ANY stereo (equipped with AUX input) a Bluetooth-audio receiver! Using the StreamStick

More information

Electronic Air / Fuel Ratio Control System

Electronic Air / Fuel Ratio Control System 7 871 ISO 9001 Electronic Air / Fuel Ratio Control System RVW20... Electronic control unit - for use with modulating single- and dual-fuel burners - with extended functionality for mechanical air / fuel

More information

Jeu Find your best friend! Niveau Lieu Classroom Vocabulaire Classe! Grammaire Durée >15min Compétence Expression orale Matériel Doc

Jeu Find your best friend! Niveau Lieu Classroom Vocabulaire Classe! Grammaire Durée >15min Compétence Expression orale Matériel Doc www.timsbox.net - Jeux gratuits pour apprendre et pratiquer l anglais PRINCIPE DU JEU Jeu Find your best friend! Niveau Lieu Classroom Vocabulaire Classe! Grammaire Durée >15min Compétence Expression orale

More information

DCH-G020 mydlink Connected Home Hub

DCH-G020 mydlink Connected Home Hub DCH-G020 mydlink Connected Home Hub User s Manual Version 01.0 Oct. 15 th, 2014 Manual Page 1 10/16/2014 1. PRODUCT DESCRIPTION The DCH-G020 is a Connected Home Z-Wave Gateway used to control a variety

More information

Volumetric flow controller

Volumetric flow controller Volumetric flow controller VRAR Leakage air flow with control damper closed according to DIN EN 1751, up to class 3 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74-980 - 0 Fax

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet MC4A-SR-F Modulating damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx..4 m orque

More information

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2 echnical data sheet Rotary actuator LRA Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage AC... 4 V Control: Open/close or -point echnical data Electrical data Nominal voltage

More information

ECM S10 Partition Sensor Setup Guide

ECM S10 Partition Sensor Setup Guide Product Category EC Partition ensor etup uide EC is a pollution degree product with a rated impulse voltage of V. Construction of Control is defined as Independently ounted. The purpose of the control

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet SMA--P Multifunctional damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. m orque

More information

Supplementary questionnaire on the 2011 Population and Housing Census BELGIUM

Supplementary questionnaire on the 2011 Population and Housing Census BELGIUM Supplementary questionnaire on the 2011 Population and Housing Census BELGIUM Supplementary questionnaire on the 2011 Population and Housing Census Fields marked with are mandatory. INTRODUCTION As agreed

More information

Technical Information Nivector FTC968, FTC968Z

Technical Information Nivector FTC968, FTC968Z TI0007F/00/EN/7.6 7494 Products Solutions Services Technical Information Nivector FTC968, FTC968Z Capacitance Point level switch for powder and fine-grained bulk solids Application The Nivector is a small-sized

More information

ControlNet Modular Repeater Medium Distance Fiber Module

ControlNet Modular Repeater Medium Distance Fiber Module Installation Instructions ControlNet Modular Repeater Medium Distance Fiber Module Cat. Nos. 9904-RPFM Use this document as a guide when you install a ControlNet repeater fiber module for medium distances.

More information

Pumping of clear unfilled liquids in housing, agricultural and industrial sectors.

Pumping of clear unfilled liquids in housing, agricultural and industrial sectors. operating limits Flow rates up to : 98 m 3 /h Head up to : Max. discharge pressure : Max. suction pressure : Temperature range : 25 m CE 16 et 25 bar 1 bar - 15 to +12 C* Max. ambient temperature : + 4

More information

Thanks for choosing Phyn

Thanks for choosing Phyn Homeowner guide Thanks for choosing Phyn We sincerely appreciate you bringing Phyn into your home, and promise to be a good houseguest. Phyn is a smart water assistant that starts to learn about your plumbing

More information

i500 Inverter i510-cabinet Use in UL approved systems hp Mounting and switch-on instructions

i500 Inverter i510-cabinet Use in UL approved systems hp Mounting and switch-on instructions i500 Inverter i510-cabinet 0.33... 3 hp Mounting and switch-on instructions Use in UL approved systems This page intentionally left blank! Contents Contents 1 General information 4 1.1 Read first, then

More information

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0.35 % FSO. Nominal pressure

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0.35 % FSO. Nominal pressure DMP 4 Industrial Pressure Transmitter Without Media Isolation accuracy according to IEC 60770: 0.5 % FSO Nominal pressure from 0... 0 mbar up to 0... 000 mbar Product characteristics excellent linearity

More information

WRZ-SST-120 Wireless Sensing System Tool

WRZ-SST-120 Wireless Sensing System Tool WRZ-SST-120 Wireless Sensing System Tool WRZ-SST-120 24-10563- 55, Rev. C (barcode for factory use only) Part No. 24-10563-55, Rev. C Issued March 2017 Applications The WRZ-SST-120 Wireless Sensing System

More information

STREETSOUNDS STS-170-FMST USER GUIDE V1.0. Fixed Master STS-170-FMST. User Guide V1.1 August 25,2018

STREETSOUNDS STS-170-FMST USER GUIDE V1.0. Fixed Master STS-170-FMST. User Guide V1.1 August 25,2018 Fixed Master STS-170-FMST User Guide V1.1 August 25,2018 1 1 TABLE OF CONTENTS 2 Introduction... 3 3 Outdoor Unit (ODU)... 3 4 Indoor Unit (IDU)... 4 5 Optonal High Gain Antenna Assembly... 5 6 Pole Mount...

More information

J IPC IGBT power converter

J IPC IGBT power converter M. K. JUCHHEIM GmbH & Co Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 60 03-0 Fax: +49 661 60 03-6 07 E-mail: mail@jumo.net Internet: www.jumo.net

More information

Technical data. T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC

Technical data.  T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC echnical data sheet SMASR Modulating damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. 4 m orque Nm

More information

VIBRATION AND TEMPERATURE SENSOR (FY01) USER GUIDE (For FCC/IC Certification) Version: 0.7

VIBRATION AND TEMPERATURE SENSOR (FY01) USER GUIDE (For FCC/IC Certification) Version: 0.7 VIBRATION AND TEMPERATURE SENSOR (FY01) USER GUIDE (For FCC/IC Certification) Version: 0.7 TABLE OF CONTENTS 1. OVERVIEW... 4 1.1 Features... 4 1.2 Applications... 4 2. GETTING STARTED... 4 3. VIBRATION

More information

CURTAIN RAIL FITTING INSTRUCTIONS NOTICE D INSTALLATION DU RAIL DE DOUCHE ENGLISH FRANÇAIS

CURTAIN RAIL FITTING INSTRUCTIONS NOTICE D INSTALLATION DU RAIL DE DOUCHE ENGLISH FRANÇAIS CURTAIN RAIL FITTING INSTRUCTIONS NOTICE D INSTALLATION DU RAIL DE DOUCHE ENGLISH FRANÇAIS English Evolution Grab Rails Fitting Instructions PARTS LIST Mount s that may be required: Tape measure Pencil

More information

SAX.. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

SAX.. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke s 4 501 ACVATIX Electromotoric actuators for valves SAX.. with a 20 mm stroke SAX31.. Operating voltage AC 230 V, 3-position control signal SAX61.. Operating voltage AC/DC 24 V, control signal DC 0 10

More information

Power consumption Operation At rest Wire sizing

Power consumption Operation At rest Wire sizing echnical data sheet NM24P-SR Modulating Robustline damper actuator for operating air dampers in industrial plants and in the technical building installations For air dampers up to approx..6 m 2 orque 8

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GK24G-MF Parameterisable SuperCap damper actuator with emergency control function and extended functionalities in the IP66 protective housing for adjusting dampers in technical building

More information

Universal Controller

Universal Controller 7 863 Universal Controller POLYGYR RWF32... ISO 9001 RWF32... with casing ARG61.01 The RWF32... is a universal digital boiler temperature / pressure controller designed for use in oil- and / or gas-fired

More information

AMPLIFICADORES MULTIBANDA MULTIBAND AMPLIFIERS AMPLIFICATEURS MULTIBANDE SERIE 904 SERIES

AMPLIFICADORES MULTIBANDA MULTIBAND AMPLIFIERS AMPLIFICATEURS MULTIBANDE SERIE 904 SERIES AMPLIFICADORES MULTIBANDA MULTIBAND AMPLIFIERS AMPLIFICATEURS MULTIBANDE SERIE 904 SERIES CÓDIGO-CODE-CODE MODELO-MODEL-MODELE Número de entradas/salidas Number of inputs/outputs Nombre d'entrées/sorties

More information

VALE U S E R G U I D E

VALE U S E R G U I D E VALE USER GUIDE GET TO KNOW YOUR BRAVEN VOLUME UP/DOWN (SHORT PRESS) MICROHPONE ON / OFF TALK (SHORT PRESS) ROUTER CONNECTION MODE (PRESS & HOLD) FAST VOLUME UP/DOWN (PRESS & HOLD) LIGHT RING WHITE: VOLUME

More information

SINEAX U 553 Transducer for AC Voltage

SINEAX U 553 Transducer for AC Voltage With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U 55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load

More information

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation Vmax low-n: Vmax for low-noise operation

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation Vmax low-n: Vmax for low-noise operation echnical data sheet EP..R-R6+BAC Characterised control valve with sensor-operated flow control, 6-way, Internal thread, PN 16 (EPIV) Nominal voltage AC/DC 24 V Control modulating, communicative wo sequences

More information

MOVADO.COM/SMARTSUPPORT

MOVADO.COM/SMARTSUPPORT LANGUAGES ENGLISH... 3 FRANÇAIS... 4 ESPAÑOL... 5 REGULATORY INFORMATION... 6 MOVADO CONNECT POWERED BY ANDROID WEAR DOWNLOAD THE APP & GET STARTED AT MOVADO.COM/SMARTSUPPORT 3 MOVADO CONNECT POWERED BY

More information

AI 043 S-DIAS Analog Input Module

AI 043 S-DIAS Analog Input Module AI 043 S-DIAS Analog Input Module Date of creation: 04.06.2014 Version date: 18.10.2017 Article number: 20-009-043-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/6274/4321-18

More information

Technical data. Safety notes. Power consumption In operation At rest For wire sizing

Technical data. Safety notes. Power consumption In operation At rest For wire sizing echnical data sheet Damper actuator NM4A-SR-P Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air control dampers up

More information

DECO TRACKS. collection collection

DECO TRACKS. collection collection DECO TRACKS collection collection Stylish decorative tracks have become very popular in recent times. The option of the wave effect given to the curtain as well as the possibility of manual or corded use,

More information

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable echnical data sheet S--MF- Multifunctional rotary actuator for butterfly valves orque 00 Nm Nominal volta e V Control: ontrol configurable confi urable Position feedback: configurable Auxiliary u iliary

More information

Sylvain Guillaumet Composer, Interpreter, Teacher

Sylvain Guillaumet Composer, Interpreter, Teacher Sylvain Guilumet Composer, Interpreter, Teacher rance, Châteauroux About the artist Musician, composer and author, he multipes the musical experiences, both in the interpretation of the writing Today,

More information

Activate Your xfi Pods from the Xfinity xfi Mobile App

Activate Your xfi Pods from the Xfinity xfi Mobile App Activate Your xfi Pods from the Xfinity xfi Mobile App This document provides step-by-step instructions on how you can activate your xfi Pods using the Xfinity xfi app for mobile devices. If you have additional

More information

Roll Rite Automated Tarp System Remote Control Owner s Guide

Roll Rite Automated Tarp System Remote Control Owner s Guide Roll Rite Automated Tarp System Remote Control Owner s Guide On behalf of Roll Rite, we wish to thank you for your purchase of our Automated Tarp Systems Our Mission Roll Rite designs and manufactures

More information

ihealth Wireless Body Analysis Scale OWNER S MANUAL

ihealth Wireless Body Analysis Scale OWNER S MANUAL ihealth Wireless Body Analysis Scale OWNER S MANUAL TABLE OF CONTENTS INTENDED USE... 2 IMPORTANT NOTE FOR USERS... 2 CONTRAINDICATION... 2 OFFLINE MEMORY... 3 SPECIFICATIONS... 3 GENERAL SAFETY AND PRECAUTIONS...

More information

DS600048C-CL. 48" Sliding Linear Shower Door. 1174~1199mm (46-3/16"~47-3/16")

DS600048C-CL. 48 Sliding Linear Shower Door. 1174~1199mm (46-3/16~47-3/16) DS000C-CL " Sliding Linear Shower Door 0mm(-/") ~99mm (-/"~-/") Dimension of shower door: (~99) x 0mm(H) / (-/"~-/") x -/"(H) Profile adjustment: +mm/" Rev. April,0 DS0000C-CL 0" Sliding Linear Shower

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LH24A-00 Communicative linear actuator adjusting dampers and slide valves in technical building installations Air damper size up to approx. m² Actuating force 50 N Nominal voltage AC/DC

More information

RFC1000. Wireless Transceiver for the RFOT, Therm A lert and RF2000A data loggers. Product User Guide

RFC1000. Wireless Transceiver for the RFOT, Therm A lert and RF2000A data loggers. Product User Guide RFC1000 Wireless Transceiver for the RFOT, Therm A lert and RF2000A data loggers Product User Guide Product User Guide Table of Contents Product Overview... 3 Software Installation... 4 Activating & Deploying

More information

Overview of types. Technical data

Overview of types. Technical data echnical data sheet SHA-.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control dampers

More information

Lenovo regulatory notice for wireless adapters

Lenovo regulatory notice for wireless adapters Lenovo regulatory notice for wireless adapters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - This manual contains regulatory information for the following Lenovo products:

More information

INSTALLATION MANUAL ES-SUB-WIRELESS-KIT ES-SUB-WIRELESS-RCVR

INSTALLATION MANUAL ES-SUB-WIRELESS-KIT ES-SUB-WIRELESS-RCVR INSTALLATION MANUAL ES-SUB-WIRELESS-KIT ES-SUB-WIRELESS-RCVR FCC STATEMENT This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC

More information

DATA SHEET AC current single function transducer TAC-311DG/TAC-321DG

DATA SHEET AC current single function transducer TAC-311DG/TAC-321DG DATA SHEET AC current single function transducer TAC-311DG/TAC-321DG Compact design, 55 x 75 mm Easily accessible terminals Accuracy class 0.5 35 mm DIN rail or base mounting DEIF A/S Frisenborgvej 33

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet Communicative damper actuator for adjusting dampers in technical building installations Air damper size up to approx. m² Nominal torque 5 Nm Nominal voltage AC/DC 24 V Control Modulating

More information