Smith Meter AccuLoad III-N4

Size: px
Start display at page:

Download "Smith Meter AccuLoad III-N4"

Transcription

1 Issue/Rev. 0. (/) Electronic Preset Delivery System Smith Meter AccuLoad IIIN Installation Manual Bulletin MN0 The Most Trusted Name In Measurement

2 Caution The default or operating values used in this manual and in the program of the AccuLoad III are for factory testing only and should not be construed as default or operating values for your metering system. Each metering system is unique and each program parameter must be reviewed and programmed for that specific metering system application. Disclaimer FMC Technologies Measurement Solutions, Inc. hereby disclaims any and all responsibility for damages, including but not limited to consequential damages, arising out of or related to the inputting of incorrect or improper program or default values entered in connection with the AccuLoad III.

3 Receipt of Equipment When the equipment is received, the outside packing case should be checked immediately for any shipping damage. If the packing case has been damaged, the local carrier should be notified at once regarding his liability. Carefully remove the unit from its packing case and inspect for damaged or missing parts. If damage has occurred during shipment or parts are missing, a written report should be submitted to the Customer Service Department, FMC Technologies Measurement Solutions, Erie, PA. Prior to installation, the unit should be stored in its original packing case and protected from adverse weather conditions and abuse. Caution This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this Instruction Manual, may cause interference to radio communications. It has not been tested to comply with the limits for a Class A computing device pursuant to Subpart J of Part of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference. Warning These preset devices must be used with failsafe backup equipment to prevent accidental runaway delivery of product. Failure to provide backup equipment could result in personal injury, property loss and equipment damage. Warning On initial powerup of a new unit or after installation of a new computer board, there are several alarms that will be triggered which cannot be cleared until the AccuLoad is programmed. United States NIST Handbook UR... and UR... For compliance to United States NIST Handbook UR... and UR..., invoices printed using a mechanical numericonly printer (e.g., Smith Meter Load Printer) must contain in preprinted form, the following information: a. Volume corrected to 0 degrees F b. API/C of E c. Temperature d. Gross Volume Where the API/C of E, temperature, and gross volume may be handwritten on the ticket. Refer to Handbook, UR... and UR... for current requirements. i

4 Table of Contents Section I Introduction... Receipt of Equipment... Section II PreInstallation Considerations... Mechanical... Electrical... Important Note... Section III Installation... Mechanical... Electrical... Installing and Removing the Analog I/O Module... Input Frequency x... StartUp Procedure... Section IV Diagrams... Analog Module Settings (JP on EAAI)... Promass 0,, and... Wiring, 0mA and Vdc Inputs/Outputs... Digital Inputs... Wiring, Digital Inputs... Digital Outputs... Wiring, Digital Outputs... Optional AICB Board... Communications... Jumper Locations (see Figure AICB Board)... Section V Specifications... AccuLoad IIIN Specification... Accuracy... Weight... Electrical Inputs... Electrical Outputs... Environment... Approvals... Communications... Ethernet Communications Port... Specifications (AICB Board Optional) (Remote Mount... Specifications (Red and Green Indicating Light Units Optional)... Specifications (Stop Button Optional)... Section VI Related Publications... ii

5 Figures Figure. Analog Modules... Figure. Connector and Switches on PIB Board... Figure. AccuLoad IIIN ExplosionProof Dimensions... Figure. KDC Layout... Figure. EAAI Layout... Figure A. KDC/EAAI/PIB Boards...0 Figure. PIB Board...0 Figure a. Vdc Terminal Block Diagram (units built before January, 0)... Figure b. Vdc Terminal Block Diagram (units built after January, 0)... Figure. Wiring Diagram, Single Prime Meter... Figure. Wiring Diagram, Two Prime Meters... Figure 0. Wiring Diagram, Single PEXP Transmitter... Figure. UPT Wiring Single Pulse... Figure. UPT Wiring Dual Pulse... Figure. Wiring Diagram, Two PEXP Transmitters... Figure. Wiring Diagram, Single PPS Transmitter...0 Figure. Wiring Diagram, Two PPS Transmitters... Figure. Wiring Diagram, Turbine Meter with PA Preamps... Figure. Wiring Diagram, Two Turbine Meters with PA Preamps... Figure. Wiring Diagram, Transmitter with an Open Collector Output... Figure. Wiring Diagram, Promass and Dual Pulse... Figure 0. Wiring Diagram, Promass 0,, and Single Pulse... Figure. Wiring Diagram, Additive Meter... Figure. Resistance (RTD) Input (Single Meter Input)... Figure. Resistance (RTD) Input (Dual Meter Input)... Figure. 0mA Inputs (Active)...0 Figure. 0mA Inputs (Passive)...0 Figure. 0mA Outputs... Figure. Vdc Input... Figure. Vdc Output... Figure. DC Inputs... Figure 0. AC Inputs... Figure. DC Outputs... Figure. AC Outputs... Figure. EAAI/PIB Typical Single Meter Input Diagram... Figure. KDC Typical Diagram... Figure. KDC Pulse Output Diagram... Figure. EIA MultiDrop Communications... Figure. EIA MultiDrop Communications...0 Figure. Network Configuration for Multiple AccuLoads... Figure. Gate City EIA Communications... Figure 0. Gate City EIA (FourWire) Communication... Figure. EIA (FourWire) Additive Communication (Gate City BlendPack)... Figure. EIA (Four Wire) Additive Communication (Titan Pac)... Figure. EIA Coriolis Meter Communications... Figure. Optional AICB Board...0 Figure. AICB Jumper Locations... Figure. AICB Communications and DC Power... Figure. AICB Outputs... iii

6 Tables Table. Typical Wire Sizes... Table. Maximum Cable Length and Baud Rate (EIA)... Table. Maximum Cable Length and Baud Rate (EIA)... Table. Pulse Inputs... Table. Promass Modeling for Single Pulse Wiring... Table. Promass Modeling for Dual Pulse Wiring... Table. Wiring... Table. Digital Inputs... Table. Digital Outputs... Table 0. EIA Communications Port... Table. EIA Communications Port...0 iv

7 Section I Introduction This manual is to be used for the installation of the NEMA IV Division II Approved AccuLoad III Electronic Preset Controller. The manual will be divided into six sections: Introduction, PreInstallation Considerations, Installation, Diagrams, Specifications, and Related Publications. PreInstallation Considerations describes the areas that must be considered prior to the installation of the AccuLoad III. Installation describes the areas that have to be considered when installing the AccuLoad III. Diagrams covers dimensional outline drawings, wiring schematics, etc. Specifications describes the specifications of the AccuLoad IIIS Electronic Preset. Related Publications lists the literature that is associated with the NEMA IV Division II Approved AccuLoad III. Receipt of Equipment When the equipment is received, the outside packing case should be checked immediately for any shipping damage. If the packing case has been damaged, the local carrier should be notified at once regarding his liability. Carefully remove the unit from its packing case and inspect for damaged or missing parts. If damage has occurred during shipment or parts are missing, a written report should be submitted to the Customer Service Department, FMC Technologies Measurement Solutions, 0 Wagner Avenue, Erie, PA 0. Before installation, the unit should be stored in its original packing case and protected from adverse weather conditions and abuse. Issue/Rev. 0. (/) MN0 Page

8 Section II PreInstallation Considerations Mechanical In addition to the following, all previous warnings and cautions should be reviewed before installation.. A solid base (pedestal or shelf) should be used to support the AccuLoad III housing.. The location and the height of the AccuLoad III should be selected to permit easy viewing of the display and to provide convenient access to the keypad by all users.. Access for servicing the AccuLoad III is through the front cover. For ease of service and removal of parts the cover must swing open more than 0. The AccuLoad III is hinged on the left.. All wiring is through the conduit entrances located on the bottom of the NEMA IV housing. There are three." conduit entrances in the bottom of the housing.. A din rail is mounted in the upper section of the housing. The din rail has connectors to distribute the Vdc power to the transmitters mounted on the meters. The din rail also provides for up to 0 amp fused disconnect lever terminal blocks.. In warm climates, the AccuLoad III should be shaded from direct sunlight. The maximum external temperature of the AccuLoad III housing must not exceed 0 degrees F (0 degrees C) to ensure that the internal temperature limit is not exceeded. Electrical. All DC wiring must be routed into the AccuLoad III through the conduit entries located in the bottom of the housing. Do not route DC and AC wiring through the same conduit entry.. The DC signal wires must be multiconductor shielded cable of or 0 AWG minimum stranded copper. Note: The following recommendations are based on our knowledge of the electrical codes. The local electrical codes should be reviewed to ensure that these recommendations follow the local code. Also installation manuals of all the equipment being wired into the AccuLoad should be reviewed for transmission distances and wire recommendations. Table. Typical Wire Sizes Equipment Transmitters Temp. Probes Density & Pressure Transmitters EIA Communications EIA Communications Number and Gauge of Wire / Ga. / 0 Ga. Belden Number or Equivalent 0 / Ga. or 0 / Ga. / Ga. Table. Maximum Cable Length and Baud Rate (EIA) Baud Rate Feet Meters,00 0, ,00,000 0,00,000 0,00,000,0,00,000,0 Table. Maximum Cable Length and Baud Rate (EIA) Baud Rate Feet Meters,00,00,000,0 Note: For Ethernet communications refer to IEEE and IT rules and regulations regarding transmission distances when connecting to any hub, router, switch, etc. Page MN0 Issue/Rev. 0. (/)

9 Section II PreInstallation Considerations All AC wiring must be routed into the AccuLoad III through the conduit entries located in the bottom of the housing. Connectors are sized for a maximum of gauge wire. Consult the local electrical codes for the minimum AC wire size required for your application. Do not route AC and DC wiring through the same conduit entry. AC wiring must use AC wiring ducts.. All AC wiring should be stranded copper and must comply with federal, state and local codes and specifications.. Two separate AC circuits must be provided from the breaker panel. One circuit will supply isolated power to the AccuLoad III electronics (instrument power). The second circuit will supply power to the external devices.. For proper operation the AccuLoad III must be earth grounded. The grounding point should be as close to the unit as possible. To ensure proper earth ground, the following conditions must be met: a) The resistance between the earth ground terminal in the AccuLoad III and the grounding point must not exceed Ω b) The proper grounding point is a ½" to ¾" diameter copper stake that extends into the water table. Where this is not practical, a ground plane may be used; Note: Electrical conduit, piping, and structural steel are not considered proper grounding points for equipment using electronics. c) No other devices, except AccuLoad IIIs and ancillary equipment such as load printers, should be connected to any point in the grounding circuit.. If external relay permissives are used in series with AccuLoad III relays, an RC network must be placed in parallel with the permissive to prevent a false turnon of the AccuLoad III relays. Recommended RC network = 0. UF capacitor and a 0 Ω resistor (Electrocube part number RG 0 ).. Interposing relays must be installed between the pump controller, alarming device, and the AccuLoad III permissive sense relays. Important Electrical Safety Installation Notes Input and output wiring must be in accordance with Class I, Division wiring methods and in accordance with the authority having jurisdiction. This equipment is suitable for use in Class I, Div., Groups C and D or nonhazardous locations only. WARNING Explosion Hazard substitution of components may impair suitability for Class I, Div.. WARNING Explosion Hazard do not disconnect equipment unless power has been switched off or the area is known to be nonhazardous. WARNING EXPLOSION HAZARD. DO NOT REMOVE OR REPLACE FUSE UNLESS POWER HAS BEEN DISCONNECTED OR THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS OF FLAMMABLE GASES OR VAPORS. The enduse installation must include a switch, suitable for the location where it is installed, so that power can be removed for replacement of fuse. Issue/Rev. 0. (/) MN0 Page

10 Section III Installation Mechanical See Preinstallation Considerations. Electrical. AC circuits must be isolated from DC circuits and brought into the unit through their respective conduit openings.. All signal and DC wiring should be connected before connecting AC wiring.. Be sure that all connections on the terminal blocks are tight.. All shields must be connected as follows: (a),,, or on terminal block TB on the EAAI board; (b) and on terminal block TB on the KDC board; or (c) of P on Vdc distribution block.. All exposed shields must be properly insulated to prevent short circuits to other terminals or to the chassis. The shield at the device (e.g., temperature device, transmitter, etc.) must be cut back to the insulation and taped off. All shields should be continuous. If splices are required, they must be soldered and properly insulated.. If other communicating devices are used with the AccuLoad III, refer to the manual for that unit for shielding information. Shields for other communicating equipment should not be terminated in the AccuLoad III.. Sufficient slack should be provided for the wiring in the AccuLoad III to permit easy removal of the boards. Installing and Removing the Analog I/O Module Caution: Turn off the power at the unit prior to installing or removing the Analog I/O Module. Failure to do so will damage modules. Care should be taken when installing or removing the Analog I/O modules so as not to damage the board or the module. To install the module, line up the alignment pins with the socket and push down on the module. Once it is seated, screw in the mounting screw until tight. Do not overtighten the screw. To remove the modules from the board, loosen the mounting screw and pull up on the module. Figure. Analog Modules Page MN0 Issue/Rev. 0. (/)

11 Section III Installation Input Frequency x If the application requires a pulse rate that is higher than the meter is capable of putting out, the AccuLoad III can multiply the incoming pulses times two. This option is activated by switches located on the PIB board. The PIB board is located on the EAAI board. 0 Figure. Connector and Switches on PIB Board ON OFF StartUp Procedure. Verify that wiring has been completed. Once it is complete, power can be applied to the unit.. The displays should light, indicating that the AccuLoad is ready for startup.. The AccuLoad can be programmed either through the keypad or using a PC and the AccuMate programming tool. Comm port # on each board set is initialized at the factory to match the communication settings of the AccuMate.. All loading arms on the communication line must be set up with a unique address.. Program the AccuLoad III.. Once the programming has been completed and tested, the AccuLoad III is ready for operation.. Record the programming of the AccuLoad III for future reference. The default setting from the factory is times. The switch is closed (ON). To multiply the incoming pulses times, push the switch of the incoming pulse channel to the open (OFF) position. The switches are located on the PIB boards, as shown in Figure above. The PIB board that is located on the EAAI board is for pulse inputs through. Note: The switches correspond to the pulse input channels (i.e., Meter Pulse In # is equal to Switch #, meter pulse in # is equal to switch #). Issue/Rev. 0. (/) MN0 Page

12 Section IV Diagrams Figure. AccuLoad IIIN ExplosionProof Dimensions Page MN0 Issue/Rev. 0. (/)

13 Section IV Diagrams Figure. KDC Layout Configurable jumper locations and switch locations are heavily circled on the diagram above. For more information on S, see page. It is important to note that all but one of these jumpers, J, are factory defaults and should not be configured by the user. The proper settings are provided below so if one of these is accidentally changed, it can be returned to its original position. J is the jumper used to zero the passcodes. Jumpers are configured using the plugs that fit over the jumper prongs. A jumper with no prongs plugged, or with one prong plugged, is OUT. A jumper with both prongs plugged is IN. Note: Should Program Mode be inaccessible after changing PROMs, or if the operator loses or forgets the access code, set J to OUT, then power up. In Out Out 0 Out In Out Out In Out Out In Out 0 In In In In*** Out Out In Out Out **** Note: For units shipped prior to October 00: J must be in the in position for Optrex Model DMF00N. For units shipped after October 00: J must be in the out position for Model MTG0 displays Issue/Rev. 0. (/) MN0 Page

14 TB TB TB Section IV Diagrams An pin DIP switch, S, will be available for upgrading firmware (SW) and for setting the IP address (SW and SW). This switch is only used when the AccuLoad is equipped with the KDC.net (Ethernet capability and flash memory) using firmware rev..0 or higher. The switch will be utilized as follows: SW force firmware upgrade (powers up the bootloader; waiting for firmware upgrade message is displayed) SW SW OFF OFF use programmed IP address ON OFF use..0. OFF ON use ON ON use DHCP Note: To power up the bootloader, toggle SW to the on position and cycle power. AccuMate.net can also be used to do this (see AccuMate.net manual). The bootloader will then allow the firmware to be upgraded. CN F AM AM AM AM AM AM TP TP TP C J0 GND TP J C TP SMITH METER EAAI 00 SERIES J C C J J C D U JP J J U SSR SSR SSR SSR SSR SSR SSR SSR SSR SSR0 SSR F L L GND ACIM ACIM ACIM ACIM ACIM TB TB TB TB Figure. EAAI Layout The userconfigurable jumper on the EAAI board is indicated by a circle and arrow in the diagram above. See the table on the following page for an explanation of analog module settings. This jumper has been configured for the modules that were shipped with the unit. Changes should only be made if different modules are added or deleted. Modules must be installed with inputs first, followed by outputs. Page MN0 Issue/Rev. 0. (/)

15 Analog Module Settings (JP on EAAI) Section IV Diagrams Inputs, 0 Outputs Inputs, Outputs Inputs, Output Input, Outputs Inputs, Outputs 0 Inputs, Outputs Inputs, Outputs Issue/Rev. 0. (/) MN0 Page

16 AM # Section IV Diagrams TB TB 0 TB 0 TX RX RTS CTS COM TX TX RX RX COM N.C. N.C. In # DC In # DC COM # In # DC Pulse Out # Out # DC Out # DC Out # DC Pulse Out # KDC COM # COM # VDC In TX RX COM TX TX RX RX COM TX TX RX RX COM Gnd Gnd Prewired at the factory TB TB TB TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD SIG SIG RTD SIG SIG SIG SIG SIG SIG FT FT FT FT FT FT RTD RTD FT FT0 TX RX Gnd N.C. In # DC In # DC In # DC VDC Out DC Gnd AM # AM # AM # AM # AM # AM # PT Com # 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure a. KDC/EAAI/PIB Boards Figure. PIB Board Page 0 MN0 Issue/Rev. 0. (/)

17 Section IV Diagrams Product Meters (Rev. 0.0 and above firmware) Input # Input # Input # Input # Input # Input # Single Pulse Meter #A Meter #A Meter #A Meter #A Meter #A Meter #A Dual Pulse N/A N/A N/A N/A N/A N/A Dual/Integrity N/A N/A N/A N/A N/A N/A Product Meters (Rev. 0.0 and above firmware) Input # Input # Input # Input # Input # Input # Single Pulse Meter #A Meter #A Meter #A Meter #A Meter #A Injector/Dens. Dual Pulse N/A N/A N/A N/A N/A N/A Dual/Integrity N/A N/A N/A N/A N/A N/A Product Meters (Rev. 0.0 and above firmware) Input # Input # Input # Input # Input # Input # Single Pulse Meter #A Meter #A Meter #A Meter #A Injector/Dens. Injector/Dens. Dual Pulse N/A N/A N/A N/A N/A N/A Dual/Integrity N/A N/A N/A N/A N/A N/A Product Meters Input # Input # Input # Input # Input # Input # Single Pulse Meter #A Meter #A Meter #A Injector/Dens. Injector/Dens. Injector/Dens. Dual Pulse Meter #A Meter #B Meter #A Meter #A Meter #B Meter #B Dual/Integrity N/A N/A N/A N/A N/A N/A Product Meters Input # Input # Input # Input # Input # Input # Single Pulse Meter #A Meter #A Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Dual Pulse Meter #A Meter #B Injector/Dens. Meter #A Meter #B Injector/Dens. Dual/Integrity Meter #A Meter #B Meter #A Bar Meter #A Meter #B Meter #A Bar Product Meter Input # Input # Input # Input # Input # Input # Single Pulse Meter #A Reserved Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Dual Pulse Meter #A Meter #B Reserved Injector/Dens. Injector/Dens. Injector/Dens. Dual/Integrity Meter #A Meter #B Meter #A Bar Injector/Dens. Injector/Dens. Injector/Dens. Table. Pulse Inputs \Note: When using dual pulse and not the A Bar inputs for transmitter security, the pulse inputs for the A Bar assignment will be not used. Issue/Rev. 0. (/) MN0 Page

18 Section IV Diagrams Product Meters with Flow Controlled Additive Input # Input # Input # Input # Input # Input # Dual Pulse Meter #A Meter #B FC Inj #A Meter #A Meter #B FC Inj # B Dual/Integrity N/A N/A N/A N/A N/A N/A Product Meter with Flow Controlled Additive Input # Input # Input # Input # Input # Input # Dual Pulse Meter #A Meter #B Injector/Dens. FC Inj A FC Inj B Injector/Dens. Dual/Integrity Meter #A Meter #B Meter # Bar FC Inj A FC Inj B FC Inj Bar Product Meter with Flow Controlled Additive Input # Input # Input # Input # Input # Input # Dual Pulse Meter #A Meter #B Injector/Dens. FC Inj A FC Inj B Injector/Dens. Dual/Integrity Meter #A Meter #B Meter # Bar FC Inj A FC Inj B FC Inj Bar Page MN0 Issue/Rev. 0. (/)

19 Section IV Diagrams Figure a. Vdc Terminal Block Diagram (units built before January, 0) Prewired at Factory VDC GND VDC Field Wiring VDC Terminal Block One of Each Set of Boards GND Figure b. Vdc Terminal Block Diagram (units built after January, 0) Issue/Rev. 0. (/) MN0 Page

20 Section IV Diagrams Prime White Yellow Red Black Note: Yellow wire only connected when dual pulse input required. To TB 0,, or To TB,, or TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # PT TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Single Prime Meter Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Prime Wire Codes: Black: Common Red: Input Power White: Signal A Yellow: Signal B Page MN0 Issue/Rev. 0. (/)

21 Section IV Diagrams Prime Meter White Yellow Red Black Prime Meter White Yellow Red Black Note: Yellow wire only connected when dual pulse input required. To TB 0,, or To TB,, or To TB 0,, or To TB,, or TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Two Prime Meters Note: Drawing is shown with dual meters and each meter being shown wired as a dual pulse input. When not using the dual pulse input meter # should be wired to Pulse Input # using white and black inputs from the transmitter. Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Prime Wire Codes: Black: Common Red: Input Power White: Signal A Yellow: Signal B Issue/Rev. 0. (/) MN0 Page

22 Section IV Diagrams PEXP Tranmitter Black Red White To TB 0,, or To TB,, or TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure 0. Wiring Diagram, Single PEXP Transmitter Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. PEXP Wire Codes: Black: Signal Red: Input Power White: Common Page MN0 Issue/Rev. 0. (/)

23 Section IV Diagrams UPT Transmitter 0 To TB 0,, or To TB,, or UPT Transmitter 0 To TB 0,, or To TB,, or UPT Transmitter 0 To TB 0,, or To TB,, or TB 0 TB 0 PT EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # 0 Pulse In # TB TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out N.C. DC Gnd PIB Board S ON On = X OFF = X L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. UPT Wiring Single Pulse Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. UPT Terminal Connections: : Electronics Ground : Input Power : Signal B Output : B _ Output : Signal A Output : A _ Output : Shield : Verification Pulse Output : Inverted Verification Pulse Output 0: Not Used Issue/Rev. 0. (/) MN0 Page

24 Section IV Diagrams UPT Transmitter 0 To TB 0,, or To TB,, or UPT Transmitter 0 To TB 0,, or To TB,, or UPT Transmitter 0 To TB 0,, or To TB,, or EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) TB TB TB 0 PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # TB TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out N.C. DC Gnd PIB Board S ON On = X OFF = X L L Gnd TB Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) 0 TB 0 Figure. UPT Wiring Dual Pulse Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. UPT Terminal Connections: : Electronics Ground : Input Power : Signal B Output : B _ Output : Signal A Output : A _ Output : Shield : Verification Pulse Output : Inverted Verification Pulse Output 0: Not Used Page MN0 Issue/Rev. 0. (/)

25 Section IV Diagrams PEXP Transmitter Meter # Black Red White PEXP Transmitter Meter # Black Red White To TB 0,, or To TB,, or To TB 0,, or To TB,, or TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Two PEXP Transmitters Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. PEXP Wire Codes: Black: Signal Red: Input Power White: Common Issue/Rev. 0. (/) MN0 Page

26 Section IV Diagrams PPS Transmitter TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Single PPS Transmitter Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. PPST Terminal Connections : Common : Input Power : Signal B Output : B _ Output : Signal A Output : A _ Output Page 0 MN0 Issue/Rev. 0. (/)

27 Section IV Diagrams PPS Transmitter Meter # PPS Transmitter Meter # To TB 0,, or To TB,, or To TB 0,, or To TB,, or TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Two PPS Transmitters Note: Drawing is shown with dual meters and each meter being shown wired as a dual pulse input. When not using the dual pulse input meter # should be wired to Pulse Input # using connections and on the transmitter. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. PPST Terminal Connections : Common : Input Power : Signal B Output : B _ Output : Signal A Output : A _ Output Issue/Rev. 0. (/) MN0 Page

28 Section IV Diagrams Turbine Meter PA Preamps Note: Two Preamps only connected when dual pulse input is required. To TB,, or To TB 0,, or To TB,, or To TB 0,, or TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Turbine Meter with PA Preamps Note: For a singlepulse input, use upper PA and AccuLoad III Pulse Input #. Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. PA Terminal Connections : Common : Signal Output : Input Power Page MN0 Issue/Rev. 0. (/)

29 Section IV Diagrams Turbine Meter PA Preamps Meter # Preamp # Preamp # Turbine Meter PA Preamps Meter # Preamp # Preamp # To TB,, or To TB 0,, or To TB,, or To TB 0,, or To TB,, or To TB 0,, or To TB,, or To TB 0,, or Note: Two Preamps only connected when dual pulse input is required. TB TB TB RTD SIG SIG RTD RTD SIG SIG RTD RTD 0 SIG SIG RTD SIG SIG SIG SIG SIG SIG 0 FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Two Turbine Meters with PA Preamps Note: Drawing is shown with dual meters and each meter being shown wired as a dual pulse input. When not using the dual pulse input the single preamp on meter # should be wired to Pulse Input # using white and black inputs from the transmitter. Also the second preamp on meter number is not used. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. PA Terminal Connections (Preamp #) : Common : Signal A Output : Input Power PA Terminal Connections (Preamp #) : Common : Signal B Output : Input Power Issue/Rev. 0. (/) MN0 Page

30 Section IV Diagrams Open Collector Output TB TB TB 0 0 RTD SIG SIG RTD RTD SIG SIG RTD RTD SIG SIG RTD SIG SIG SIG SIG SIG SIG FT FT FT FT FT FT FT FT FT FT0 AM # AM # AM # AM # AM # AM # TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. PIB Board L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Transmitter with an Open Collector Output Caution: For clarity, shields are not shown. Connect,,, or to Terminal Block. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair Page MN0 Issue/Rev. 0. (/)

31 Promass 0,, and Coriolis Meters Section IV Diagrams When connecting the Promass (does not apply to the Promass 0 or models) to an AccuLoad, it is important that the Line Monitoring function on the Promass be disabled. This is because the pulse input circuitry of the AccuLoad requires the input pulse off voltage to be less than one volt (and the on voltage to be greater than volts). If the Line Monitoring on the Promass is enabled, the off voltage of the pulses will be greater than one volt and therefore will not be counted by the AccuLoad. There are three jumpers on each of the frequency output submodules on the I/O board that enable/disable the Line Monitoring function. The factory default is to enable Line Monitoring. Follow the steps from section.. of the Proline Promass Operating Instruction Bulletin MN0M0 to enable/disable this function. Transmitter/Sensor Modeling Terminal Terminal 0XXX XXXXXXXXXXXXA 0XXX XXXXXXXXXXXXD 0XXX XXXXXXXXXXXXS 0XXX XXXXXXXXXXXXT 0XXX XXXXXXXXXXXX XXX XXXXXXXXXXXXA XXX XXXXXXXXXXXXB XXX XXXXXXXXXXXXS XXX XXXXXXXXXXXXT XXX XXXXXXXXXXXXC XXX XXXXXXXXXXXXD XXX XXXXXXXXXXXXN XXX XXXXXXXXXXXXP XXX XXXXXXXXXXXX XXX XXXXXXXXXXXX XXX XXXXXXXXXXXX XXX XXXXXXXXXXXXS XXX XXXXXXXXXXXXT XXX XXXXXXXXXXXXN XXX XXXXXXXXXXXXD XXX XXXXXXXXXXXX Table. Promass Modeling for Single Pulse Wiring Transmitter/Sensor Modeling Terminal Terminal XXX XXXXXXXXXXXXM,, XXX XXXXXXXXXXXXM,, XXX XXXXXXXXXXXX,, Table. Promass Modeling for Dual Pulse Wiring Note: In dual pulse mode, Output (/) leads Output (/) when flowing in the forward direction. Issue/Rev. 0. (/) MN0 Page

32 Section IV Diagrams To TB,, or Promass Meter To TB,, or Promass Meter To TB,, or Promass Meter TB 0 TB 0 PT 0 EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # TB TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PIB Board S ON On = X OFF = X L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure. Wiring Diagram, Promass and Dual Pulse Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair Promass Wire Codes: Terminal : Output Terminal : Output Terminal : Output Terminal : Output Note: The pulse input circuitry has. kω of current limiting resistance builtin so that an external pullup resistor is not required when an open collector output device is connected as shown. Page MN0 Issue/Rev. 0. (/)

33 Section IV Diagrams To TB,, or Promass Meter / / To TB,, or Promass Meter / / To TB,, or Promass Meter / / TB 0 TB 0 PT 0 Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # Pulse In # EAAI Notice: Before returning EAAI board to factory for service remove all analog modules, AC Input and Output Modules and PIB Board. Reinstall all modules into their respective locations on the EAAI replacement board. WARNING: CMOS Circuitry. Use grounded facility when handling. TB TX Com # RX Gnd In # DC In # DC In # DC 0 VDC Out DC Gnd N.C. PIB Board S ON On = X OFF = X L L Gnd TB AC in Com In # (AC) In # (AC) In # (AC) In #0 (AC) In # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) Out #0 (AC) Out # (AC) Out # (AC) Out # (AC) Out # (AC) TB TB 0 TB 0 Figure 0. Wiring Diagram, Promass 0,, and Single Pulse Caution: For clarity, shields not shown. Connect Shields to,,, or of Terminal Block. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. Promass Wire Codes: Terminal /: Terminal /: Note: The pulse input circuitry has.kω of current limiting resistance builtin so that an external pullup resistor is not required when an open collector output device is connected as shown. Issue/Rev. 0. (/) MN0 Page

34 Section IV Diagrams Figure. Wiring Diagram, Additive Meter Caution: For clarity, shields are not shown. Connect shields to,,, or of Terminal Block. Note: If only one additive meter is used, it must be wired into Pulse In # when using the ALS firmware. Note: The volt power for the transmitters can be wired through the terminal block located at the top of the enclosure. Note: Wiring between transmitter and AccuLoad should be done using a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair. The additive meters and frequency densitometer can be wired into Pulse Inputs,, or if so programmed in the unit. They are not limited to Input (densitometer) or Inputs and (metered injectors). Page MN0 Issue/Rev. 0. (/)

35 Section IV Diagrams Figure. Resistance (RTD) Input (Single Meter Input) Note: The following positions are available on Terminal Block for RTD input: (), (), (), (), (), (). Figure. Resistance (RTD) Input (Dual Meter Input) Note: If using two twisted pairs of wires, RTD and RTD should be wired with one twisted pair. Sig and Sig should be wired with another twisted pair. Used for temperature input from a platinum RTD. This input requires a fourwire connection to a platinum sensor with the following specification: Degrees Celsius Ω/ Ω /Deg. C., DIN 0, BS0, or IPTS Temperature Coefficient. Issue/Rev. 0. (/) MN0 Page

36 Section IV Diagrams The RTD X and RTD X provide a voltage source to the RTD and high precision resistance. The current through the RTD and Precision Resistor are equal. SIG X and SIG X comprise a very high resistance voltmeter circuit, and therefore, draw no significant current from the RTD circuit. The second voltmeter circuit (VM) measures the voltage across a very precise 0.0% resistor with a fixed value. Since the current through the RTD and the resistor is the same, the RTD resistance is the ratio of the two measured voltages (VM/VM) multiplied by a constant. Wiring resistance of the conductors on the terminals RTD X and RTD X do not lead to an error due to the high input resistance of the voltmeter, and extremely low current through these wires. Wiring resistance to conductors on terminals SIG X and SIG X have no effect, since any small change to current flow for which the constant current source does not make up is reflected by the voltage measured by voltmeter VM. Although the conductors do not have to be balanced resistancewise, as in threewire circuits, two twisted pairs should be used, as shown, to take advantage of the voltmeters large amount of common mode rejection. Figure. 0mA Inputs (Active) Figure. 0mA Inputs (Passive) The 0mA inputs are isolated from the processor and main power and can be programmed for the function required by the application. The analog inputs are also scalable through the I/O Configuration Menu of the unit. The resolution of the input is bits or one part in,. The inputs should be wired with shielded twisted pairs of wires of to gauge. Page 0 MN0 Issue/Rev. 0. (/)

37 Section IV Diagrams Figure. 0mA Outputs The 0mA outputs are isolated from the processor and main power and can be programmed for the function required by the application. The analog outputs are also scalable through the I/O Configuration Menu of the unit. The resolution of the output is bits or one part in,. The outputs should be wired with shielded twisted pairs of wires of to gauge. Figure. Vdc Input The Vdc inputs are isolated from the processor and main power and can be programmed for the function required by the application. The inputs are scalable through the I/O Configuration Menu of the unit. The resolution of the input is bits or one part in,. The inputs should be wired with shielded twisted pairs of wires of to gauge. Issue/Rev. 0. (/) MN0 Page

38 Section IV Diagrams Figure. Vdc Output The Vdc outputs are isolated from the processor and main power and can be programmed for the function required by the application. The outputs are also scaleable through the I/O Configuration Menu of the unit. The resolution of the output is bits or one part in,. The outputs should be wired with shielded twisted pairs of wires of to 0 gauge. Wiring, 0mA and Vdc Inputs/Outputs Module Number Connection Terminal Number Board Terminal Block AM # EAAI TB AM # EAAI TB AM # Shield,,, or EAAI TB AM # EAAI TB AM # EAAI TB AM # Shield,,, or EAAI TB AM # 0 EAAI TB AM # EAAI TB AM # Shield,,, or EAAI TB AM # EAAI TB AM # EAAI TB AM # Shield,,, or EAAI TB AM # EAAI TB AM # EAAI TB AM # Shield,,, or EAAI TB AM # EAAI TB AM # EAAI TB AM # Shield,,, or EAAI TB Table. Wiring Page MN0 Issue/Rev. 0. (/)

39 Section IV Diagrams Digital Inputs The AccuLoad III is capable of providing six DC digital inputs and five AC digital inputs. The inputs can be programmed as to function through the configuration directory. Figure. DC Inputs Figure 0. AC Inputs Issue/Rev. 0. (/) MN0 Page

40 Section IV Diagrams Wiring, Digital Inputs Inputs # Voltage Type Board Terminal Block Terminal Input () 0 EAAI TB EAAI TB Shield,,, or EAAI TB EAAI TB EAAI TB Shield,,, or EAAI TB EAAI TB EAAI TB Shield,,, or EAAI TB 0 EAAI TB EAAI TB Table. Digital Inputs Digital Outputs The AccuLoad III is capable of providing six DC digital inputs and five AC digital inputs. The inputs can be programmed as to function through the configuration directory. Figure. DC Outputs Page MN0 Issue/Rev. 0. (/)

41 Section IV Diagrams Figure. AC Outputs Wiring, Digital Outputs Outputs # Voltage Type Board Terminal Block Terminal Output () Connections Common () DC KDC TB DC KDC TB DC KDC TB AC EAAI TB AC EAAI TB AC EAAI TB AC EAAI TB AC EAAI TB 0 AC EAAI TB 0 AC EAAI TB AC EAAI TB AC EAAI TB AC EAAI TB AC EAAI TB 0 Table. Digital Outputs Issue/Rev. 0. (/) MN0 Page

42 Section IV Diagrams Figure. EAAI/PIB Typical Single Meter Input Diagram Note:. If external relay permissives are used in Series with AccuLoad III relays, an RC network may need to be placed in parallel with the permissive to prevent a false turn on of the AccuLoad III relays. Recommended RC network = 0.µF capacitor and a 0 ohm resistor (electrocube part number RG 0). Any device shown outside of the AccuLoad III housing is to be supplied by the customer.. Additive injector feedback switches are supplied by the injector manufacturers. (Example: Piston Switches on the GatePak Systems.) Page MN0 Issue/Rev. 0. (/)

43 Section IV Diagrams Figure. KDC Typical Diagram Issue/Rev. 0. (/) MN0 Page

44 Section IV Diagrams Figure. KDC Pulse Output Diagram Page MN0 Issue/Rev. 0. (/)

45 Section IV Diagrams Figure. EIA MultiDrop Communications The figure shows the typical wiring scheme for multidrop communications between a communications device and multiple AccuLoad IIIs. Refer to the table below for pin numbers on each of the EIA communication ports. Note that the shield is to be terminated at the communication device. Comm Port Tx Rx Common Board Terminal Block KDC TB KDC TB EAAI TB Table 0. EIA Communication Ports Note: Communications Port and can be either EIA or EIA. Issue/Rev. 0. (/) MN0 Page

46 Section IV Diagrams Figure. EIA MultiDrop Communications The figure shows the typical wiring scheme for multidrop communications between a communications device and multiple AccuLoad IIIs. Refer to the table below for pin numbers on each of the EIA communication ports. Note that the shield is to be terminated at the communication device. Comm Port Tx Tx Rx Rx Board Terminal Block KDC KDC TB KDC KDC TB EAAI KDC TB Table. EIA Communication Ports Note: Communications Port and can be either EIA or EIA. Page 0 MN0 Issue/Rev. 0. (/)

47 Section IV Diagrams Figure. Network configuration for multiple AccuLoads connected via a hub then linked directly to the automation system and LAN. Refer to the standards IEEE 0.X states for wiring and using Ethernet connectivity rules and regulations. Utilize standard IT practices and protocol when connecting several AccuLoads to any type of hub, router, or switching device. There are various different unique network configurations and the responsibility of each type of network is left to the network administrator. Distances, transmission time, etc. will all follow the standard IEEE spec rating. If there are any questions regarding installation of multiple AccuLoads over Ethernet communications, please consult the factory. Employ the standard CAT Cable, used for connecting an AccuLoad to any router, switch, or hub. Note: If the AccuLoad is being connected directly to a PC, then a crossover CAT cable is needed (for instance, to connect directly to AccuMate.net). Issue/Rev. 0. (/) MN0 Page

48 Section IV Diagrams Figure. Gate City EIA Communications Page MN0 Issue/Rev. 0. (/)

49 Section IV Diagrams Figure 0. Gate City EIA (TwoWire) Communications Issue/Rev. 0. (/) MN0 Page

50 Section IV Diagrams Figure. EIA (FourWire) Additive Communication (Gate City BlendPak) Page MN0 Issue/Rev. 0. (/)

51 Section IV Diagrams Figure. EIA (FourWire) Additive Communication (Titan Pac) Issue/Rev. 0. (/) MN0 Page

52 Section IV Diagrams Figure. Promass Coriolis Meter Communications Programming Parameter AccuLoad III Promass Baud Rate Parity /No Parity/ Stop bits No Parity, stop bits Modbus Endian Big Byte order 0 Sequence Number Address Mass Meter Type Promass Timeout 0 Transmission Mode Reply Delay RTU 0 ms Page MN0 Issue/Rev. 0. (/)

53 Section IV Diagrams Optional AICB Board Metered Additive Pulses # and # are wired into the PIB Board on the EAAI board. Metered Additives through are wired to the AICB board. Connections are shown in the table below. Meter Pulses Injector # Terminal Block Voltage Signal Common TB TB TB, TB (TB) (TB) (TB) TB TB TB 0 TB 0 TB TB TB 0 Additive Pumps # and # are wired to the programmed terminals on the EAAI board. Additive Pumps through are wired per the following table. Additive Pumps Additive Pump # Terminal V Terminal Block 0 TB TB TB TB TB 0 TB TB 0 TB TB TB Issue/Rev. 0. (/) MN0 Page

54 Section IV Diagrams Additive Solenoids Additive Solenoid # Terminal V Terminal Block TB TB TB TB TB TB TB 0 TB TB TB Communications (AICB Board) Metered Additive Pulses # and # are wired into the PIB Board on the EAAI board. Metered Additives through are wired to the AICB board. Connections are shown in the table below. Communications Type Function Terminal Jumpers AICB Board AICB Board CN CN EIA TX TB () EIA RX TB () EIA Com TB () EIA RX TB () EIA RX TB () EIA TX TB () EIA TX TB () Out Out In Out Out Out Out Out In In Page MN0 Issue/Rev. 0. (/)

55 Section IV Diagrams Jumper Locations (see Figure ) AICB Board Communications Designation Jumpers Description CN V V Out CN V V Out CN V V Out Communications Address Baud Rate Communications CN In Address 00, Out Address 00* CN In 00 Baud, Out.K Baud CN Last Unit Only (Termination of Communications with AccuLoad) In Communications, Out Communications Address Baud Rate Communications CN In EIA, Out EIA CN In EIA, Out EIA Note: Jumpers CN and CN for factory use only. Issue/Rev. 0. (/) MN0 Page

56 Section IV Diagrams TB TB 0 TB 0 TB TB V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN # Signal Common V Out DC IN #0 Signal Common RS (Rx ) RS (RX )/RS (Rx) RS (Tx ) RS (Tx )/RS (Tx) VDC Common AICB Board AC L Input To Out Out 0 N/C N/C Out Out Out Out Out Out Out Out Out Out 0 Out Out Out Out Out Out Out Out Out Out 0 AC L Input To Out Out 0 TB TB 0 TB 0 TB Figure. Optional AICB Board Page 0 MN0 Issue/Rev. 0. (/)

57 Section IV Diagrams Jumpers CN Jumpers CN Jumpers CN Figure. AICB Jumper Locations Issue/Rev. 0. (/) MN0 Page

Electronic Preset Delivery System Smith Meter microload.net. Installation Manual. Bulletin MN06150 Issue/Rev 0.6 (8/15)

Electronic Preset Delivery System Smith Meter microload.net. Installation Manual. Bulletin MN06150 Issue/Rev 0.6 (8/15) Electronic Preset Delivery System Smith Meter microload.net Installation Manual Bulletin MN06150 Issue/Rev 0.6 (8/15) Caution The default or operating values used in this manual and in the program of the

More information

Smith Meter AccuLoad III VLR Simulator for AccuLoad III. Installation / Operation Manual. Bulletin MN06116 Issue/Rev 0.3 (10/13)

Smith Meter AccuLoad III VLR Simulator for AccuLoad III. Installation / Operation Manual. Bulletin MN06116 Issue/Rev 0.3 (10/13) Smith Meter AccuLoad III VLR Simulator for AccuLoad III Installation / Operation Manual Bulletin MN06116 Issue/Rev 0.3 (10/13) Caution The default or operating values used in this manual and in the program

More information

Electronic Preset Delivery System Smith Meter microflow.net Liquid. Installation Manual. Bulletin MNFL001 Issue/Rev 0.3 (10/15)

Electronic Preset Delivery System Smith Meter microflow.net Liquid. Installation Manual. Bulletin MNFL001 Issue/Rev 0.3 (10/15) Electronic Preset Delivery System Smith Meter microflow.net Liquid Installation Manual Bulletin MNFL001 Issue/Rev 0.3 (10/15) Caution The default or operating values used in this manual and in the program

More information

Smith Meter microload.net

Smith Meter microload.net Electronic Preset Delivery System Issue/Rev. 0.5 (2/13) Smith Meter microload.net Installation Bulletin MN06150 The Most Trusted Name In Measurement Caution The default or operating values used in this

More information

Electronic Preset Delivery System. AccuLoad II TM. Installation. The Most Trusted Name In Measurement

Electronic Preset Delivery System. AccuLoad II TM. Installation. The Most Trusted Name In Measurement Electronic Preset Delivery System AccuLoad II TM Issue/Rev. 0.8 (8/95) Installation Bulletin MN06037 The Most Trusted Name In Measurement Section 1 - General J4 J5 J3, J6, J7 and J8 J1 J2 Figure

More information

INSTALLATION INSTRUCTIONS FOR THE CLIKCARD COMMERCIAL RECEIVER (NARROW BAND)

INSTALLATION INSTRUCTIONS FOR THE CLIKCARD COMMERCIAL RECEIVER (NARROW BAND) Doc. 6001200 Rev. B INSTALLATION INSTRUCTIONS FOR THE CLIKCARD COMMERCIAL RECEIVER (NARROW BAND) TABLE OF CONTENTS TABLE OF CONTENTS...1 INSTALLATION FOR INFINITY AND PROCARD...3 PULLING CABLE... 3 MOUNTING

More information

M2 Antenna Systems, Inc. Model No: S3 Sequencer. Operating Instructions

M2 Antenna Systems, Inc. Model No: S3 Sequencer. Operating Instructions WARRANTY ADDENDUM TROUBLESHOOTING INSTALLATION OVERVIEW M2 Antenna Systems, Inc. Model No: S3 Sequencer Operating Instructions PLEASE READ BEFORE USE AND SAVE M2 Antenna Systems, Inc. 4402 N. Selland Ave.

More information

PACSystems* RX3i. Isolated RTD Input Module, 8 Channels, IC695ALG508-CA. Module Features. GFK-2501C November 2012

PACSystems* RX3i. Isolated RTD Input Module, 8 Channels, IC695ALG508-CA. Module Features. GFK-2501C November 2012 November 2012 PACSystems* RX3i Isolated RTD Input Module, 8 Channels, IC695ALG508-CA Isolated RTD Input module IC695ALG508 provides eight isolated differential RTD input channels. Each channel can be individually

More information

MODEL , MODEL 310SAO, AND MODEL 310-ALT

MODEL , MODEL 310SAO, AND MODEL 310-ALT MODEL -0, MODEL SAO, AND MODEL -ALT VOLUME CALL AudioMaster MODEL -0 VOLTS: / VDC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A. WARNING: DISCONNECT POWER BEFORE REMOVING COVER TALK TM LISTEN 0A0

More information

GE Fanuc IC695ALG312. Rx3i PacSystem

GE Fanuc IC695ALG312. Rx3i PacSystem GE Fanuc IC695ALG312 http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/ic695alg312 Rx3i PacSystem GE IP Isolated Thermocouple Input module 12 INPUTS 919-535-3180 sales@pdfsupply.com June 2008

More information

AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH

AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH INSTRUCTION MANUAL PLEASE READ THIS MANUAL BEFORE OPERATING THIS EQUIPMENT! 116 Willow Road Starkville, MS 39759 USA 662-323-8211 Version 3B Printed in U.S.A.

More information

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS INSTALATION, OPERATION & MAINTENANCE MANUAL FOR PA-1001A Series SIGNAL CONDITIONER & CONVERTORS PA1001A 7/02 Page 1 of 11 SIGNAL CONDITIONER & CONVERTERS PA1001A Series INTRODUCTION: The PA1001A series

More information

Data Acquisition Modules/ Distributed IO Modules

Data Acquisition Modules/ Distributed IO Modules User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332

More information

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter Installation Instructions CD-Pxx-00-0 Issue Date February 4, 006 CD-Pxx-00-0 Series Duct Mount CO Transmitter Application Requirements FCC Compliance Statement This equipment has been tested and found

More information

Smith Meter AccuLoad. Electronic Preset Delivery System. Tank Proving Guide. Bulletin MN Issue/Rev. 0.1 (7/10)

Smith Meter AccuLoad. Electronic Preset Delivery System. Tank Proving Guide. Bulletin MN Issue/Rev. 0.1 (7/10) Electronic Preset Delivery System Smith Meter AccuLoad Tank Proving Guide Issue/Rev 01 (7/10) Bulletin MN06146 The Most Trusted Name In Measurement Caution The default or operating values used in this

More information

Model FLSC-C3-XX. DC Powered Microprocessor Controlled Transmitter

Model FLSC-C3-XX. DC Powered Microprocessor Controlled Transmitter Model FLSC-C3-XX DC Powered Microprocessor Controlled Transmitter CONTENTS. Introduction----------------------------------------------------------------- 2 2. Specifications ---------------------------------------------------------------

More information

VersaMax* Analog Input, 16-Bit RTD Module

VersaMax* Analog Input, 16-Bit RTD Module Product Description The Analog Input RTD Module is an intelligent module that accepts input signals from up to four RTD input devices and provides input data with 16 bits of resolution. OK ANALOG INPUT

More information

Explosion Proof Page/Talk Paging Amplifier

Explosion Proof Page/Talk Paging Amplifier Industrial Communications Worldwide Explosion Proof Page/Talk Paging Amplifier Installation & Operation 7552-10 th Street. N.E. Calgary Alberta, Canada T2E W1 Ph: 403.25.3100 \ email:info@guardiantelecom.com

More information

INSTRUCTIONS YASKAWA. Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference.

INSTRUCTIONS YASKAWA. Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference. YASKAWA DUAL ENCODER (PG) FEEDBACK CARD (PG-Z) INSTRUCTIONS Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference. Package Contents:

More information

5570M Series Intercom Installation and Operation Guide

5570M Series Intercom Installation and Operation Guide 5570M Series Intercom Installation and Operation Guide Isolated balanced/unbalanced lines Audio signals for the 5570M are transmitted over a wire pair using balanced line technology. An isolation transformer,

More information

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the

More information

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K O P E R A T I N G I N S T R U C T I O N S WEL-200 TM W I R E L E S S E D G E L I N K 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales Inquiries: salessupport@emxinc.com

More information

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit Service Instructions The Conductor Controls Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit Table of Contents General Section Page Safety Instructions.. 4 Introduction 5 Inspection and Long-Term

More information

P700-WLS ioprox Receiver

P700-WLS ioprox Receiver Installation Manual DN1628-1611 Pre-Installation Notes Copyright 2016 Tyco International Ltd. and its Respective Companies. All Rights Reserved. All specifications were current as of publication date and

More information

The SCB-68 is a shielded board with 68 screw terminals for easy connection to National Instruments 68-pin products.

The SCB-68 is a shielded board with 68 screw terminals for easy connection to National Instruments 68-pin products. NATIONAL INSTRUMENTS The Software is the Instrument SCB-68 68-Pin Shielded Connector Block Installation Guide Part Number 320745-01 This guide describes how to connect and use the SCB-68 68-pin shielded

More information

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual TM M723 Rev. C Model 1050 Strain Gage Transmitter Installation, Operation and Maintenance Manual Table of Contents General... 1 Installation... 1 Specifications... 1 Wiring... 2 Setup and Operation...

More information

Installation and user s guide H A. NCi-5 non-contact tool setting interface

Installation and user s guide H A. NCi-5 non-contact tool setting interface Installation and user s guide H-5259-8500-05-A NCi-5 non-contact tool setting interface 1 English Installation and user s guide NCi-5 non-contact tool setting interface This page is intentionally left

More information

IB6 Series Solid-State Isolation Relay

IB6 Series Solid-State Isolation Relay IB6 Series Solid-State Isolation Relay Installation & Operation Manual TRANSDATA, INC. 2560 TARPLEY ROAD CARROLLTON, TEXAS 75006 TEL (972) 418-7717 FAX (972) 418-7774 Website: www.transdatainc.com E-mail:

More information

K-Factor Scaler F5140 and Programming Kit F5141 Installation & Operating Instructions

K-Factor Scaler F5140 and Programming Kit F5141 Installation & Operating Instructions F5140 and Programming Kit F5141 8635 Washington Avenue Racine, WI 53406 USA Tel: 800-433-5263 or 262-639-6770 Fax: 800-245-3569 or 262-639-2267 E-Mail: flo-techsales@racinefed.com www.flo-tech.com TABLE

More information

IOM. Model 1050 Strain Gage Transmitter Installation & Operation Manual. (Cage Code #1MU21)

IOM. Model 1050 Strain Gage Transmitter Installation & Operation Manual. (Cage Code #1MU21) IOM Model 1050 Strain Gage Transmitter Installation & Operation Manual (Cage Code #1MU21) Model 1050 Strain Gage Transmitter Installation & Operation Manual CONTENTS I. GENERAL...1 II. INSTALLATION...2

More information

This Errata Sheet contains corrections or changes made after the publication of this manual.

This Errata Sheet contains corrections or changes made after the publication of this manual. Errata Sheet This Errata Sheet contains corrections or changes made after the publication of this manual. Product Family: DL4 Date: September 12, 218 Manual Number D4-ANLG-M Revision and Date th Ed., Rev.

More information

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00 NetBiter I/O Extender 4RO 6RTD 8DIO DAIO User Manual Revision 1.00 IntelliCom Innovation AB Linjegatan 3D SE302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 18 21 99 email info@intellicom.se www

More information

+GF+ SIGNET Temperature Transmitter Instructions

+GF+ SIGNET Temperature Transmitter Instructions GF SIGNET 80- Temperature Transmitter Instructions ENGLISH -80.090- B-/00 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal

More information

B850 Boiler House Energy Monitor

B850 Boiler House Energy Monitor Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

P700WLS IoProx Receiver

P700WLS IoProx Receiver Installation Manual Warning! This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

Programmable K-Factor Scaler B and Programming Software Kit B

Programmable K-Factor Scaler B and Programming Software Kit B Programmable K-Factor Scaler B220-885 and Programming Software Kit B220-900 INSTALLATION & INSTRUCTION MANUAL 8635 Washington Avenue Racine, Wisconsin 53406 Toll Free: 800.235.1638 Phone: 262.639.6770

More information

Model 1791 VHF Radio User's Manual

Model 1791 VHF Radio User's Manual Model 79 VHF Radio User's Manual ALL WEATHER INC 65 NATIONAL DRIVE SACRAMENTO, CA 95834 WWW.ALWEATHERINC.COM 79 VHF RADIO USER'S MANUAL CONTENTS INTRODUCTION... Description... Transmitter Module... Power

More information

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

IC800SSD Hardware Manual Pub 348R5. for models. A publication of

IC800SSD Hardware Manual Pub 348R5. for models. A publication of IC800SSD Hardware Manual Pub 348R5 for models IC800SSD104S1A IC800SSD104RS1A IC800SSD107S1A IC800SSD107RS1A IC800SSD407RS1A IC800SSD216S1A IC800SSD216RS1A IC800SSD420RS1A IC800SSD228S1A IC800SSD228RS1A

More information

Wiring Instructions for 10, 16 & 20 Function, 92 & 93 Series, FET Receivers.

Wiring Instructions for 10, 16 & 20 Function, 92 & 93 Series, FET Receivers. Wiring Instructions for 10, 16 & 20 Function, 92 & 93 Series, FET Receivers. 92220.02E 1 1. The Receiver is designed to carry a maximum of 15 Amps. That is, for example,15 Amps through one output or 5

More information

B850 Boiler House Energy Monitor

B850 Boiler House Energy Monitor Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault CCE-32 1.09 Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault Index 1. General description... 5 2. Applications... 5 3. Installation... 5 4. Connections...

More information

ITP16. Temperature indicator. User guide

ITP16. Temperature indicator. User guide ITP16 Temperature indicator User guide ITP16_2018.05_0280_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany Tel.: +49 (0) 511

More information

Instruction Manual T-800 Series Current Transmitter. Model T-800L Model T-800LT Model T-800TT

Instruction Manual T-800 Series Current Transmitter. Model T-800L Model T-800LT Model T-800TT Instruction Manual T-800 Series Current Transmitter Model T-800L Model T-800LT Model T-800TT M323 Rev G1 September 10, 2009 JOWA USA, Inc. 59 Porter Road Littleton, MA 01460-1431 USA Telephone: 978-486

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

IF30. User's manual. Description. Table of contents IF30

IF30. User's manual. Description. Table of contents IF30 User's manual IF30 Description IF30 is an encoder interface unit designed to convert the output signals delivered by so-called sine-cosine-encoders and similar measuring systems (devices which deliver

More information

Radio Control Installation and Operating Instructions System 4

Radio Control Installation and Operating Instructions System 4 Radio Control Installation and Operating Instructions System 4 P.O. Box 403, One Cedar Parkway, Jackson, WI 53037 Phone: 800-628-1909 Fax: 262-677-2058 Revision: April 19, 2012 Contents Introduction 3

More information

CONTROL MICROSYSTEMS SCADAWave Radio Transceiver. Hardware Manual

CONTROL MICROSYSTEMS SCADAWave Radio Transceiver. Hardware Manual 5908 SCADAWave Radio Transceiver Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical

More information

DISCRETE INPUT MODULE, 16 points

DISCRETE INPUT MODULE, 16 points INSTRUCTION MANUAL DISCRETE INPUT MODULE, points (Modbus) RM-DA MODEL RM-DA BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.

More information

SLC 500 RTD/Resistance Input Module

SLC 500 RTD/Resistance Input Module Installation Instructions SLC 500 RTD/Resistance Input Module (Catalog Number 1746-NR8) Inside page Important User Information... 2 For More Information... 3 Hazardous Location Considerations... 4 Environnements

More information

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

ITP14. Universal process indicator. User guide

ITP14. Universal process indicator. User guide ITP14 Universal process indicator User guide ITP14_2018.05_0279_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany Tel.: +49 (0)

More information

This product is for use in a dry, indoor environment only. This product is not to be installed near water, liquid, or flammable materials.

This product is for use in a dry, indoor environment only. This product is not to be installed near water, liquid, or flammable materials. The equipment described in this manual contains high voltage. Always disconnect power to the equipment before installing, disconnecting, or servicing the product. This product is for use in a dry, indoor

More information

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents KENCO ENGINEERING COMPANY P.O. BOX 470426, TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 http://www.kenco-eng.com e-mail: info@kenco-eng.com KENCO Loop Powered Magnetostrictive Transmitter

More information

Trusted Power Distribution Unit MCB 24 Vdc

Trusted Power Distribution Unit MCB 24 Vdc PD-T8292 Trusted Trusted Power Distribution Unit MCB 24 Vdc Product Overview The dual 5-channel Trusted Power Distribution Unit Miniature Circuit Breaker (MCB) 24 V is designed for N+1 or 100 % redundant

More information

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3 CHAPTER INSTALLATION 2 AND WIRING Contents of this Chapter... Ambient Conditions..............................2 2 Storage Conditions...............................2 2 Installation.....................................2

More information

Installation guide 970 SmartRadar ATi

Installation guide 970 SmartRadar ATi Installation guide 970 SmartRadar ATi July 2008 Part no. 4416.717 Rev. 3 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywell.com Website

More information

MODEL KBWD-15 Pulse Width Modulated (PWM)

MODEL KBWD-15 Pulse Width Modulated (PWM) MODEL KBWD-15 Pulse Width Modulated (PWM) DC MOTOR SPEED CONTROL WHISPER DRIVE INSTALLATION AND OPERATING INSTRUCTIONS See Safety Warning on Page 1 and Application Note Warning on Page 2 The information

More information

Installation/Operation Manual

Installation/Operation Manual Installation/Operation Manual USM GEN2 Universal Sensor Module Form USM GEN2 IOM 9/15 1 1.0 DESCRIPTION 1.1 The USM GEN2 reduces on-skid conduit and tubing runs by bringing the process information into

More information

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL Mid-West Instrument BULLETIN NO. ELEC-IM140/11A Replaces ELEC-IM140-141/09A ELECTRICAL Gauges with switches have one or two SPST or SPDT hermetically sealed adjustable set point reed switch assemblies.

More information

Digital Lighting Systems, Inc.

Digital Lighting Systems, Inc. PD408-AN0-277 ANALOG 0-0 V 0-0V analog control 4 Channel x 2250 W Dimmer & Switch Packs 220/240/277 Volts operation PD408-AN0-277 4 circuit Analog -0V 4 x 8 A. Dimmer pack Serial Number Digital Lighting

More information

SCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD

SCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD Modular Wireless I/O System User Manual Version V. for BENTEK SYSTEMS LTD #, 0 Ave S.E. Calgary, AB, Canada TB 0L Ph:(0) Fax:(0) email: sales@scadalink.com web: The is a Modular Wireless I/O System that

More information

Model 4800 O P E R AT I O N M A N U A L L O A D C E L L S U M M I N G T R A N S M I T T E R

Model 4800 O P E R AT I O N M A N U A L L O A D C E L L S U M M I N G T R A N S M I T T E R O P E R AT I O N M A N U A L Model 4800 L O A D C E L L S U M M I N G T R A N S M I T T E R CALEX Manufacturing Company, Inc. Concord, California 94520 Ph: 925/687-4411 800/542-3355 Fax: 925/687-3333 http://www.calex.com

More information

NEO CAR AUDIO. Neo AUXiN AUX INPUT INTERFACE. Instruction Manual

NEO CAR AUDIO. Neo AUXiN AUX INPUT INTERFACE. Instruction Manual NEO CAR AUDIO Neo AUXiN AUX INPUT INTERFACE Instruction Manual IMPORTANT NOTE Neo AUXiN Dip switch positions MUST be set BEFORE any other step is taken. Otherwise, the kit will not operate properly. See

More information

Installation guide 971 SmartRadar LTi

Installation guide 971 SmartRadar LTi Installation guide 971 SmartRadar LTi March 2009 Part no. 4416.715 Revision 3 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywellenraf.nl

More information

USB-TEMP and TC Series USB-Based Temperature Measurement Devices

USB-TEMP and TC Series USB-Based Temperature Measurement Devices USB-Based Temperature Measurement Devices Features Temperature and voltage measurement USB devices Thermocouple, RTD, thermistor, or semiconductor sensor measurements Eight analog inputs Up to ±10 V inputs*

More information

F4-08RTD 8-Channel RTD Input

F4-08RTD 8-Channel RTD Input F-8RTD 8-Channel RTD 92 F8RTD 8-Channel RTD Module Specifications The F8RTD 8 Differential Channel RTD module provides several features and benefits. It provides eight RTD input channels with 16-bit resolution.

More information

Effective: June, 2000 EX-1821 Satellite Display Unit Receiver Installation Manual Models: 4643-*-* 4644-*-9 Since 1937

Effective: June, 2000 EX-1821 Satellite Display Unit Receiver Installation Manual Models: 4643-*-* 4644-*-9 Since 1937 Effective: June, 2000 LevelPRO Satellite Display Unit Receiver Installation Manual Models: 4643-*-* 4644-*-9 Since 1937 The information contained in this manual was accurate at the time of release. Specifications

More information

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009 User s Guide Publication number 34134-90001 April 2009 For Safety information, Warranties, Regulatory information, and publishing information, see the pages at the back of this book. Copyright Agilent

More information

K-FACTOR SCALER B & B

K-FACTOR SCALER B & B K-FACTOR SCALER B220-880 & B220-881 INSTALLATION & INSTRUCTION MANUAL 8635 Washington Ave. Racine, Wisconsin 53406 Technical Toll-Free: 877.722.4631 Sales Toll-Free: 800.235.1638 Phone: 262.639.6770 Fax:

More information

AH71, AH72, and AH73 FM Approved Humidity Transmitter Assemblies Installation and Operating Instructions

AH71, AH72, and AH73 FM Approved Humidity Transmitter Assemblies Installation and Operating Instructions AH71, AH72, and AH73 FM Approved Humidity Transmitter Assemblies Installation and Operating Instructions Tel: 763. 571.3121 Fax: 763. 571.0927 www.minco.com Description Models AH71, AH72, and AH73 are

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading-edge microprocessor-based circuitry has nonvolatile memory. The display

More information

Nocturne+ E INSTRUCTIONS CAUTION. Motor Operated Exterior Projection Screen. 1¾ (45mm) END CAP. Wall Mounting Bracket. Wall Mounting Bracket

Nocturne+ E INSTRUCTIONS CAUTION. Motor Operated Exterior Projection Screen. 1¾ (45mm) END CAP. Wall Mounting Bracket. Wall Mounting Bracket Motor Operated Exterior Projection Screen Wall ing Bracket INSTRUCTIONS INSTALLATION & OPERATION CAUTION Wall ing Bracket 1. Inspect all boxes to make sure you have received the proper screen and parts.

More information

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions Overview and Identification The BAPI-Stat 4 X-Combo () Room Unit features 4 output channels and optional local indication of temperature and humidity. Additional options include Temperature Setpoint, Humidity

More information

INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668)

INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668) INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668) Use with Models KBDA-24D, 27D, 29, 45, 48 See Safety Warning, on page 4. RoHS The information contained in this

More information

8 Input/8 Output AC Block I/O Module

8 Input/8 Output AC Block I/O Module 8 Input/8 Output AC Module Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air flow through the block module.

More information

ProHelp Systems MIU 10X/98 WIRING / INSTALLATION INSTRUCTIONS

ProHelp Systems MIU 10X/98 WIRING / INSTALLATION INSTRUCTIONS ProHelp Systems MIU 10X/98 WIRING / INSTALLATI INSTRUCTIS 2 MIU-10X /5XS SETUP AND CFIGURATI MIU-10X Configuration and Diagnostics Screen Upon boot-up the MIU-10X first runs a self-diagnosis routine to

More information

Eaton Electrical Predictive Diagnostics ELECTRICAL. InsulGard TM. StartUp Guideline for Switchgears EEPD, 2012, Version 1.1

Eaton Electrical Predictive Diagnostics ELECTRICAL. InsulGard TM. StartUp Guideline for Switchgears EEPD, 2012, Version 1.1 Eaton Electrical Predictive Diagnostics ELECTRICAL InsulGard TM StartUp Guideline for Switchgears EEPD, 2012, 2015 Version 1.1 September 2015 EATON ELECTRICAL 2 Predictive Diagnostics TABLE OF CONTENTS

More information

CL900. True RMS 1000V 2000A 60MΩ ENGLISH. INSTRUCTION MANUAL 2000A Digital Clamp Meter. Measurement Technology

CL900. True RMS 1000V 2000A 60MΩ ENGLISH. INSTRUCTION MANUAL 2000A Digital Clamp Meter. Measurement Technology ENGLISH INSTRUCTION MANUAL 2000A Digital Clamp Meter True RMS Measurement Technology NON-CONTACT VOLTAGE TESTING INRUSH CURRENT LOW IMPEDANCE DATA HOLD RANGE HOLD AUDIBLE CONTINUITY DIODE TEST CAPACITANCE

More information

USING RS-232 to RS-485 CONVERTERS (With RS-232, RS-422 and RS-485 devices)

USING RS-232 to RS-485 CONVERTERS (With RS-232, RS-422 and RS-485 devices) ICS DataCom Application Note USING RS- to RS- CONVERTERS (With RS-, RS- and RS- devices) INTRODUCTION Table RS-/RS- Logic Levels This application note provides information about using ICSDataCom's RS-

More information

FST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL

FST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL FST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL 20020628 CONTENTS DESCRIPTION... 3 OPERATION... 4 Power Supply...4 Output Range...4 Temperature Operating Range and Temperature Limits...4

More information

Analog Module D1-15P User Manual

Analog Module D1-15P User Manual D1-15P Manual Analog Module D1-15P User Manual Sielco Elettronica Srl Edison Street 209 20019 Settimo Milanese (MI) - Italy http://www.sielcoelettronica.com info @ sielcoelettronica.com Tel 02 48916252

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 151 Graham Road P.O. Box 9010 College Station, TX 77842-9010 T: 800-876-1172 Int l: (979) 690-5560, Fax: (979) 690-0440 E-mail : globalw@globalw.com Radar Level Transmitters

More information

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL Table of Contents TITLE PAGE 1. GENERAL INSTRUCTIONS 1 1.1 Precaution safety measures 1 1.1.1 Preliminary 1 1.1.2 During use 2 1.1.3 Symbols

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading edge microprocessor-based circuitry has nonvolatile memory. The display

More information

F2A3X Frequency to Analog Converter Module

F2A3X Frequency to Analog Converter Module the professional s choice F2A3X Frequency to Analog Converter Module Instruction Manual MONARCH INSTRUMENT 15 Columbia Drive Amherst, NH 03031 USA Phone: (603) 883-3390 Fax: (603) 886-3300 E-mail: support@monarchinstrument.com

More information

Electronic Circuit Protector ESX10-T

Electronic Circuit Protector ESX10-T Electronic Circuit Protector ESX0-T Description Electronic circuit protector type ESX0-T is designed to ensure selective disconnection of systems. power supplies, which are widely used in industry today,

More information

Installation guide 873 SmartRadar Control Unit & Antenna Unit

Installation guide 873 SmartRadar Control Unit & Antenna Unit Installation guide 873 SmartRadar Control Unit & Antenna Unit Rev. 7 January 2006 Part no. 4416.569 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : info@enraf.nl

More information

Wireless Interface RAD-ISM-900-SET-BD-BUS Two-way (point-to-point) Monitoring and Control with Expandable I/O Options User Manual

Wireless Interface RAD-ISM-900-SET-BD-BUS Two-way (point-to-point) Monitoring and Control with Expandable I/O Options User Manual Wireless Interface RAD-ISM-900-SET-BD-BUS Two-way (point-to-point) Monitoring and Control with Expandable I/O Options User Manual ) ) ) ) ) ) ) ) ) ) ) ) Notice: These devices must be wired in accordance

More information

RK Hydrogen Transmitter Operator s Manual

RK Hydrogen Transmitter Operator s Manual 65-2451RK Hydrogen Transmitter Operator s Manual Part Number: 71-0133RK Revision: C Released: 5/17/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

User Manual. Data Acquisition Modules/ Distributed IO Modules

User Manual. Data Acquisition Modules/ Distributed IO Modules User Manual Data Acquisition Modules/ Distributed IO Modules UMIOE Rev 5.0, 10/2009 COPYRIGHT NOTICE This manual is a publication of Brainchild Electronics Co.. Ltd. and is provided for use by its customers

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Model RFT9709 Transmitter Instruction Manual

Model RFT9709 Transmitter Instruction Manual Model RFT9709 Transmitter Instruction Manual March 1999 Model RFT9709 Transmitter Instruction Manual For technical assistance, phone the Micro Motion Customer Service Department: In the U.S.A., phone

More information

MODEL AT-10 ANALOG TRANSMITTER

MODEL AT-10 ANALOG TRANSMITTER MODEL AT-10 ANALOG TRANSMITTER INSTALLATION & OPERATING MANUAL Industrial Weighing Systems 9 Richmond Street Picton, Ontario K0K 2T0 Phone: 613-921-0397 Fax: 613-476-5293 Web: www.iwsystems.ca info@iwsystems.ca

More information

VXI-TB CHANNEL ISOTHERMAL TERMINAL BLOCK

VXI-TB CHANNEL ISOTHERMAL TERMINAL BLOCK VXI-TB-1303 32-CHANNEL ISOTHERMAL TERMINAL BLOCK Introduction This guide describes how to install and use the VXI-TB-1303 terminal block with a VXI-SC submodule. The VXI-TB-1303 terminal block is a shielded

More information

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5 SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5 Phone: (905) 564-0801 Fax: (905) 564-0806 www.telecor.com E:\T2-108\T2-M108-ABC\T2-M108-B.doc/AD

More information

1-830 SERIES DISPLACEMENT TRANSMITTER

1-830 SERIES DISPLACEMENT TRANSMITTER 1-830 SERIES DISPLACEMENT TRANSMITTER Operation & Maintenance Manual 746 Arrow Grand Circle Covina, CA 91722 United States of America Tel: (626) 938-0200 Fax: (626) 938-0202 Internet: http://www.cecvp.com

More information

Model 7000 Low Noise Differential Preamplifier

Model 7000 Low Noise Differential Preamplifier Model 7000 Low Noise Differential Preamplifier Operating Manual Service and Warranty Krohn-Hite Instruments are designed and manufactured in accordance with sound engineering practices and should give

More information

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4.

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4. An American Control Electronics Brand PCM4 SERIES PCM4 USER MANUAL www.minarikdrives.com Dear Valued Consumer: Congratulations on your purchase of the PCM4 Series isolation card. This User Manual was created

More information