CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

Size: px
Start display at page:

Download "CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter"

Transcription

1 Installation Instructions CD-Pxx-00-0 Issue Date February 4, 006 CD-Pxx-00-0 Series Duct Mount CO Transmitter Application Requirements FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. Canadian Compliance Statement This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Installation IMPORTANT: The CD-Pxx-00-0 Series transmitters are intended to provide input to equipment under normal operating conditions. Where failure or malfunction of the transmitter could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of, or protect against, failure or malfunction of the transmitter must be incorporated into and maintained as part of the control system. Parts Included The duct mount CO transmitter is shipped assembled. It consists of three main parts: base and Printed Circuit Board (PCB), cover, and mounting flange with four screws (for probe depth adjustment). A conduit adaptor is also included. Mounting Location Considerations When selecting a location for the transmitter, note the following: The transmitter is designed for duct mounting in any position. The probe is best mounted in the return airstream. The device should penetrate the duct by a minimum of 3.0 in. (76. mm) to ensure the sensing part of the element is fully in the airstream. The transmitter should be placed in an area free of condensation. The transmitter is duct mounted using a flange. The mounting flange adjusts the distance between the probe and the inner duct wall. Fasten the mounting flange with the four screws as follows: 1. Loosen the probe retention screw, and separate the flange from the assembled unit.. Drill a hole 7/8 to 1 in. ( to 5 mm) diameter in the duct for the transmitter s probe. 3. Using the mounting flange as a template centered on the hole, drill four 1/8 in. (3.18 mm) holes for the mounting screws positioned as in Figure (4) 0.87 () 006 Johnson Controls, Inc. 1 Part No , Rev. A Center Hole 1.65 (4) Figure 1: Mounting Holes on the Flange Dimensions in. (mm) 4. Fasten the mounting flange onto the duct using the four screws provided. 5. Insert the probe a minimum of 3.0 in. (76. mm), and tighten the probe retention screw on the mounting flange.

2 Wiring Power Supply Requirements The transmitter requires a 4 AC/DC, Class power supply maintaining voltages of 18 to 30 DC or 0 to 30 AC. Although the power input includes a halfwave rectifier, using a DC supply is recommended to avoid excessive current peaks (current consumption: peak, 170 ma; average, 85 ma). 4 AC Power Supply Connections When more than one transmitter is connected to one 4 AC transformer, a common loop is formed at the controller, and the risk of a short circuit increases. All commons must be at the same potential. Note: To avoid a short circuit, isolate the 4 power supply by providing a separate transformer for each transmitter as shown in Figure. 4 AC Supply 4 AC Supply Output CO Transmitter Signals Controller ma or + - CO Transmitter ma or 0 Shared Common Line Figure : Connecting Separate AC Supplies (Recommended) If several transmitters share one transformer, the phase ( ) must always be the same at each transmitter to maintain polarity and avoid a short circuit via a shared common line at the controller, as shown in Figure 3. 4 AC Supply Supply Output CO Transmitter Signals Controller + ma or - 0 CO Transmitter + - ma or 0 Shared Common Line Connecting the Conduit Adaptor 1. Align the nut with the opening inside the enclosure, and hold it in place.. Insert the adaptor body into the transmitter conduit opening. 3. Manually tighten the adaptor into the nut, turning in a Clockwise (CW) direction (see Figure 4). Nut Adaptor Body Adaptor Figure 4: Inserting the Conduit Adaptor IMPORTANT: Do not overtighten the conduit adaptor to prevent damage or displacement of the PCB. 4. Insert the wires through the conduit adaptor body opening. 5. Tighten the adaptor onto the adaptor body by turning the adaptor in a CW direction. Wiring the PCB To wire the PCB s input and output connections: 1. Open the transmitter cover.. Insert the wire carefully through the conduit adapter and then strip 1/4 in. (6.35 mm) of the wire insulation to prepare the wire for connection to the terminal block. 3. Connect the 4 supply between the positive ( ) and negative () terminals as shown in Figure 5. Figure 3: Connecting One AC Supply to Several Transmitters (Not Recommended) CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions

3 X6 0/4mA X7 ma 0 + Wiring the Relay Model CD-PR is shipped with a relay module. To wire the relay, refer to Figure 6, and attach the relay wires to the relay PCB s two screw terminals. Screw Terminals SERIAL COM X5 X3 Figure 5: Transmitter PCB 7 10 Configuring the Output The transmitter is capable of generating either voltage or current output. To select, refer to Figure 5, and: 1. Connect the common wire to Terminal 0.. Connect the other wire to: Terminal (for voltage output) Terminal ma (for current output) and configure the pins marked 0/4mA as follows: - 4 to 0 ma: connect the jumper so that it shorts the pins (default) - 0 to 0 ma: disconnect (do not discard) the jumper 3. If the unit has an optional relay accessory, follow the procedure described in the Wiring the Relay section and then reposition the cover. Connect to X5 Connect to X3 Figure 6: Relay PCB The relay has two setpoint values: the On level and the Off level. These provide hysteresis and desired control function. The On level must be higher than the Off level. When CO concentration is increasing, the relay closes at the On level, and the relay opens when concentration is reduced to the Off level. Note: The default relay setpoints are 1,000 ppm On and 950 ppm Off. Change these settings by entering new values using the Relay Setpoint Software ACC-CD-S. Setup and Adjustments Commissioning Johnson Controls Carbon Dioxide (CO ) transmitters come from the factory calibrated for the following: output signal (0 to 10) proportional to CO concentration (0 to,000 parts per million [ppm]) altitude range of 0 to 1,969 ft (0 to 600m) above sea level without compensation default relay output trigger point of 1,000 ppm CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions 3

4 Altitude Compensation The sensors are calibrated for an altitude of 984 ft (300m) above sea level and are intended for applications within the range of 0 to 1,969 ft (0 to 600m) without compensation. For altitudes above 1,969 ft (600m) where optimum accuracy of the CO concentration measurement is essential, modify the Building Automation System (BAS) controller s Analog Input (AI) high range to compensate for sensor placement at other than the standard calibration altitude. Note: For altitude compensation, only adjust the AI high range. The AI low range should remain at zero. To do this, reset the,000 ppm value using the controller s Compensation Factor (CF) shown in Figure 7 or Figure 8 as follows: Corrected alue = CF x,000 For example, if the sensor is situated at an altitude of 3,000 ft (914.4m) above sea level, CF, from either Figure 7 or Figure 8, is The new value is calculated as follows: Corrected alue = (1.10)(,000 ppm) =,00 ppm CF ,000,000 3,000 4,000 6,000 7,000 Altitude (Feet) 1.30 Figure 7: Altitude Compensation in Feet Above Sea Level CF ,000 1,00 1,400 1,600 1,800,000,00 Altitude (Meters) Figure 8: Altitude Compensation in Meters Above Sea Level 4 CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions

5 Troubleshooting General The transmitter is not field repairable. In the event the unit is not functioning properly, use the following checklist to identify the symptoms and determine a solution. 1. erify that the unit is mounted properly and the appropriate output jumper is selected.. erify that all wiring is correct. 3. erify that the power supply voltage level is 0 to 30 AC or 18 to 30 DC. Note: The diagnostic Light-Emitting Diodes (LEDs) shown in the lower right-hand corner of Figure 5 indicate operational status: 7 lights up if the self-diagnostics procedure detects an abnormality. 10 pulses to indicate that the device is operational. If the transmitter will not operate after completing these steps, replace the unit. Testing the Relay Module To confirm that the relay is operating correctly, perform the following procedure: IMPORTANT: To expose the sensing portion of the probe, loosen the probe retention screw, and remove the probe from the duct. After testing is complete, reinstall the probe, and tighten the probe retention screw. 5. Determine whether the contacts are open or closed. If the contacts are closed, the relay is functioning properly, and no further testing is necessary. If the contacts are open, increase the CO concentration by exhaling near the probe, looking for a change in the resistance value. If no change is noted, confirm that the CO concentration has been raised above the trip point. - Check the transmitter output signal with a voltmeter to make sure the signal has risen above the 1,000 ppm relay trip point. - If the output signal has not reached the trip point, it may be necessary to further increase the CO concentration. If the contacts are open after exceeding the trip point, replace the unit with the appropriate module, and restart this procedure. 6. Disconnect power to the transmitter. 7. Disconnect the multimeter from the relay terminals. 8. Reconnect the wires to the relay screw terminal. 9. Reconnect power to the transmitter. 10. Reposition the cover. 1. Temporarily shut off power to the unit.. Temporarily remove wires connected to the relay screw terminal. 3. Connect a multimeter to the relay terminals. 4. Read the resistance level to determine whether the contacts are open or closed. If the contacts are closed, replace the unit with the appropriate relay module, and restart this procedure. If the contacts are open, apply power to the transmitter. CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions 5

6 Technical Data Product CD-Pxx-00-0 Series Duct Mount CO Transmitter Measuring Range 0 to,000 ppm CO Accuracy at 77 F (5 C) Non-Linearity Temperature Dependence of Output Long-Term Stability Response Time (0 to 63%) Operating Temperature Range Storage Temperature Range Humidity Range Transmitter Output Signal < ±[30 ppm CO +.0% of reading] (includes manufacturing deviation and drift). All accuracy specifications reflect testing the transmitters using high-grade, certified gases. Transmitters are intended for an altitude range of 0 to 1,969 ft (0 to 600 m) above sea level without compensation. < 0.5% of Full Scale < 0.056% of Full Scale/F (< 0.1% of Full Scale/C ) < ±5.0% of Full Scale/5 Years 1 Minute 3 to 113 F (-5 to 45 C) -4 to 158 F (-0 to 70 C) 0 to 85% RH (non-condensing) CO Jumper Selectable: 0 to 0 ma or 4 to 0 ma or 0 to 10 DC (Default) Maximum Output Current: 5 ma; Maximum Output : 1.5 Relay Output (Optional) Maximum 30, 0.5A, Class Recommended External Current Output: Maximum 500 ohms Load Resistance Load Output: Minimum 1,000 ohms Load Resistance Power Supply Range 0 to 30 AC (18 to 30 DC), Class Power Consumption Warm-up Time Air Flow Range Duct Probe Material Housing Material Dimensions (H x W x D) Shipping Weight Agency Listings <.5 W Average, 4.1 A < 5 Minutes 0 to 7,500 ft/minute (0 to,86 m/minute) Duct Probe Meets Plenum Rating Requirements of UL 1995, Heating and Cooling Equipment ABS Plastic 3-5/3 x 3-3/16 x 8 in. (80 x 81 x 04 mm) 0.3 lb (140g) UL Listed, CCN XAPX (US) and XAPX7 (Canada); EMC Directive (CE Mark), 89/336/EEC; FCC and DOC Compliant The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 43 Milwaukee, WI 5301 Printed in U.S.A 6 CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions

Installation Instructions

Installation Instructions CD-W00-x0-1 Series Wall Mount CO 2 Transmitters Installation Instructions CD-W00-00-1, CD-W00-N0-1 Part No. 24-9601-94, Rev. E Issued August 14, 2014 North American Emissions Compliance United States This

More information

HLC-1000 High-limit Humidity Control

HLC-1000 High-limit Humidity Control FANs 216, 1628.3 Product/Technical Bulletin HLC-1000 Issue Date 1197 HLC-1000 High-limit Humidity Control The HLC-1000 is designed to limit duct humidity by comparing a controller s request for humidification

More information

WRZ-RMT10K-0 Wireless Remote Temperature Transmitter

WRZ-RMT10K-0 Wireless Remote Temperature Transmitter WRZ-RMT10K-0 Wireless Remote Temperature Transmitter Product Bulletin WRZ-RMT10K-0, TE-6361A-1, TE-6361V-2, TE-636GV-2, TE-636S-1 The WRZ-RMT10K-0 Wireless Remote Temperature Transmitter is designed to

More information

Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output

Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output www.cometsystem.com Instruction Manual T5140 T5141 T5145 Programmable transmitter of CO2 concentration with 4-20 ma output T5240 T5241 T5245 Programmable transmitter of CO2 concentration with 0-10 V output

More information

TE-6300P Series Temperature Sensors

TE-6300P Series Temperature Sensors TE-6300P Series Temperature Sensors Installation Instructions TE-63xxP-1 Part No. 24-4034-107, Rev. M Issued April 30, 2014 Supersedes August 26, 2013 Applications To meet plenum rating where Underwriters

More information

GE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor

GE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor clear mode enter clear mode enter GE Sensing Introduction The GE Telaire Vaporstat 900 sensor measures in applications in the range of 0 to 0 F dew point. The sensor package is designed for wall mounting.

More information

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection.

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection. Carbon Dioxide - User Manual 1 Intended Use 2 Functional Description 2.1 Control Mode 2.2 Sensor 3 Installation 3.1 Mounting instructions 3.2 Installation 4 Electrical Connection 4.1 Instruction 5 Commissioning

More information

TS-9100 Electronic Sensors and Transducers. Features and Benefits. G Wide range of enclosures and signal outputs

TS-9100 Electronic Sensors and Transducers. Features and Benefits. G Wide range of enclosures and signal outputs European Electronic Controls Catalogue Catalogue Section A Product Bulletin TS-9100 Issue Date 09 2000 TS-9100 Electronic Sensors and Transducers I ntroduction The TS-9100 series of electronic temperature

More information

User Manual. PolyGard AT-2000 V3. Infrared Refrigerant Gas Transmitter Serial No. AT March, 2009

User Manual. PolyGard AT-2000 V3. Infrared Refrigerant Gas Transmitter Serial No. AT March, 2009 PolyGard AT-2000 V3 Infrared Refrigerant Gas Transmitter Serial No. AT-2000 User Manual March, 2009 February 16, 2016 Revision Specifications subject to change without notice. USA 160216 Page 2 of 13 1

More information

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL Mid-West Instrument BULLETIN NO. ELEC-IM140/11A Replaces ELEC-IM140-141/09A ELECTRICAL Gauges with switches have one or two SPST or SPDT hermetically sealed adjustable set point reed switch assemblies.

More information

WPR400 Wireless Portable Reader

WPR400 Wireless Portable Reader P516-098 WPR400 Wireless Portable Reader User guide Para el idioma español, navegue hacia www.schlage.com/support. Pour la portion française, veuillez consulter le site www.schlage.com/support. Contents

More information

SER8300 Series Terminal Equipment Controller with Optional PIR sensor Installation Guide

SER8300 Series Terminal Equipment Controller with Optional PIR sensor Installation Guide Room Controllers Terminal Equipment Controller with Optional PIR sensor Installation Guide Commercial and Hotel/Lodging HVAC Fan Coil Applications 1 CONTENTS Installation 2 Location 2 Installation 2 Terminal,

More information

QPM Series Indoor Air Quality Duct Sensors

QPM Series Indoor Air Quality Duct Sensors Document No. CE1N1962 QPM Series Indoor Air Quality Duct Sensors Description The QPM Series Room Carbon Dioxide (CO 2 ) and Air Quality Duct Sensors are designed for applications where precise, stable

More information

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3 CHAPTER MAINTENANCE AND 6 TROUBLESHOOTING In This Chapter... Maintenance and Inspection.................6 2 Monthly Inspection:..................................6 2 Annual Inspection....................................6

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

DP2500 DP0100 DP0250 Differential Pressure Transmitter

DP2500 DP0100 DP0250 Differential Pressure Transmitter PB_DPT_03 2010 DP2500 DP0100 DP0250 Differential Pressure Transmitter The DP Low Differential Pressure Transmitter series is an accurate and cost competitive solution for measuring low pressures of air

More information

Instruction Manual Model Upconverter

Instruction Manual Model Upconverter Instruction Manual Model 2006-01 Upconverter October 2013, Rev. B IF IN RF OUT Data, drawings, and other material contained herein are proprietary to Cross Technologies, Inc., but may be reproduced or

More information

DP2500 DP0100 DP0250 Differential Pressure Transmitter

DP2500 DP0100 DP0250 Differential Pressure Transmitter PB_DP_03 2011 DP2500 DP0100 DP0250 Differential Pressure Transmitter The DP Low Differential Pressure Transmitter series is an accurate and cost competitive solution for measuring low pressures of air

More information

RSMFX-2R MULTIFUNCTIONAL

RSMFX-2R MULTIFUNCTIONAL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

Wireless Room Temperature and Humidity Transmitter (Units without Temperature Setpoint or Override) Installation and Operating Instructions

Wireless Room Temperature and Humidity Transmitter (Units without Temperature Setpoint or Override) Installation and Operating Instructions Wireless Temperature and Humidity Overview and Indentification The Wireless Temperature and Humidity measures the room temperature and Relative Humidity and transmits the data at 418MHz or 433MHz RF to

More information

Worldwide Manufacturer of Gas Detection Solutions. Transmitter EC 23. Operation Manual

Worldwide Manufacturer of Gas Detection Solutions. Transmitter EC 23. Operation Manual Worldwide Manufacturer of Gas Detection Solutions Transmitter EC 23 Operation Manual Table of Contents For Your Safety...4 General Description...4 Electrical Connections...5 Zero Point Adjustment...5

More information

OSMAC RDR Low-voltage Retrofit Kit

OSMAC RDR Low-voltage Retrofit Kit OSMAC RDR Low-voltage Retrofit Kit Part Number RDR0160LVN0 User s Guide Installation of the RDR (Radio Data Receiver) low-voltage unit will enable you to remotely operate your existing Vari-Time 4000 satellite

More information

CSD Series Current Devices Solid Core with Relay

CSD Series Current Devices Solid Core with Relay CSD Series Current Devices Solid Core with Installation Instructions CSD-SA1E1-1 CSD-SA1E2-1 Part No. 24-10345-26, Rev. F Issued March 31, 2014 Supersedes April 5, 2013 Applications The Current Switch

More information

VENTI-LIGHT VLD. Ventilatie Indicator G e b r u i k e r s h a n d l e i d i n g. Ampèrestraat NL-1446 TR PURMEREND

VENTI-LIGHT VLD. Ventilatie Indicator G e b r u i k e r s h a n d l e i d i n g. Ampèrestraat NL-1446 TR PURMEREND VENTI-LIGHT VLD Ventilatie Indicator G e b r u i k e r s h a n d l e i d i n g mpèrestraat 35-37 NL-446 TR PURMEREND Postbus 783 NL-440 T PURMEREND T (+3) 099 630 60 F (+3) 099 630 6 E info@atal.nl I www.atal.nl

More information

- Wiring Brochure Universal Reset Module 423

- Wiring Brochure Universal Reset Module 423 - Wiring Brochure Universal Reset Module 423 W 423 03/09 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

12V Victor 888 User Manual

12V Victor 888 User Manual The Victor speed controllers are specifically engineered for robotic applications. The high current capacity, low voltage drop, and peak surge capacity make the Victor ideal for drive systems while its

More information

Wireless 900 MHz Receiver

Wireless 900 MHz Receiver Overview and Identification The 900 MHz unit receives a repeated or re-transmitted RF signal from one or more wireless temperature or humidity transmitters. The signal from the transmitter (418 MHz) is

More information

Instruction Manual Model Upconverter

Instruction Manual Model Upconverter Instruction Manual Model 2006-02 Upconverter October 2013, Rev. B IF IN RF OUT Data, drawings, and other material contained herein are proprietary to Cross Technologies, Inc., but may be reproduced or

More information

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity

More information

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the

More information

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions Overview and Identification The BAPI-Stat 4 X-Combo () Room Unit features 4 output channels and optional local indication of temperature and humidity. Additional options include Temperature Setpoint, Humidity

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC.

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC. INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC. MANUAL PART NUMBER 180-0036 ORIGINAL: 1-17-83 REVISION: B (8-26-86) NOT TO BE CHANGED WITHOUT MSHA

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading-edge microprocessor-based circuitry has nonvolatile memory. The display

More information

AMM-1022 Digital Multimeter USER`S MANUAL

AMM-1022 Digital Multimeter USER`S MANUAL Digital Multimeter USER`S MANUAL www.tmatlantic.com CONTENTS 1. SAFETY INFORMATION.3 2. DESCRIPTION..6 3. SPECIFICATIONS.8 4. OPERATING INSTRUCTION..11 4.1 Voltage measurement...11 4.2 Current measurement

More information

WATTNODE Pulse Output Installation and Operation Manual

WATTNODE Pulse Output Installation and Operation Manual WATTNODE Pulse Output Installation and Operation Manual Continental Control Systems http://www.ccontrolsys.com Rev 1.20dUL Information in this document is subject to change without notice. No part of this

More information

SAFETY WARNINGS AND GUIDELINES INTRODUCTION

SAFETY WARNINGS AND GUIDELINES INTRODUCTION SAFETY WARNINGS AND GUIDELINES Turn off and unplug all equipment prior to making electrical connections, including speaker wire connections. Reduce the volume level prior to making any change to the audio

More information

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5 LIST OF CONTENTS Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5 Section 2, Calibration Calculations... 7 Calibration Procedure... 8 Section

More information

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.

More information

Technical Instructions Document No EA GQD June 23, OpenAir

Technical Instructions Document No EA GQD June 23, OpenAir OpenAir Spring Return, 20 lb-in (2 Nm), Rotary GQD Series, Electronic Damper Actuators Technical Instructions Document No. 155-760 EA GQD Description Features Application The OpenAir GQD Series direct-coupled

More information

IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION INSTALLATI INSTRUCTIS Model: RB-G-K10 IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIS BEFORE BEGINNING INSTALLATI The Miller Edge RBand Monitored Gate Edge Transmitter/Receiver system is intended to provide

More information

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED. READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION.

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED. READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION. INSTALLATI INSTRUCTIS Model: RB-G-K10 IMPORTANT: THIS DEVICE MUST BE PROFESSIALLY INSTALLED. READ AND UNDERSTAND ALL INSTRUCTIS BEFORE BEGINNING INSTALLATI. The Miller Edge RBand Monitored Gate Edge Transmitter/Receiver

More information

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS INSTALATION, OPERATION & MAINTENANCE MANUAL FOR PA-1001A Series SIGNAL CONDITIONER & CONVERTORS PA1001A 7/02 Page 1 of 11 SIGNAL CONDITIONER & CONVERTERS PA1001A Series INTRODUCTION: The PA1001A series

More information

NEO CAR AUDIO. Neo AUXiN AUX INPUT INTERFACE. Instruction Manual

NEO CAR AUDIO. Neo AUXiN AUX INPUT INTERFACE. Instruction Manual NEO CAR AUDIO Neo AUXiN AUX INPUT INTERFACE Instruction Manual IMPORTANT NOTE Neo AUXiN Dip switch positions MUST be set BEFORE any other step is taken. Otherwise, the kit will not operate properly. See

More information

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K O P E R A T I N G I N S T R U C T I O N S WEL-200 TM W I R E L E S S E D G E L I N K 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales Inquiries: salessupport@emxinc.com

More information

SCC-FV01 Frequency Input Module

SCC-FV01 Frequency Input Module USER GUIDE SCC-FV01 Frequency Input Module Conventions The SCC-FV01 frequency input module is a frequency-to-voltage converter designed to measure signals from frequency-generating sensors and other periodic

More information

DM-45 Digital Multimeter

DM-45 Digital Multimeter INSTRUCTION MANUAL DM-45 Digital Multimeter Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Description The Greenlee DM-45 Digital

More information

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION INSTALLATI INSTRUCTIS Models: RB-G-K10, RB-TX10 IMPORTANT: THIS DEVICE MUST BE PROFESSIALLY INSTALLED READ AND UNDERSTAND ALL INSTRUCTIS BEFORE BEGINNING INSTALLATI The Miller Edge RBand Monitored Gate

More information

SAFETY WARNINGS AND GUIDELINES

SAFETY WARNINGS AND GUIDELINES SAFETY WARNINGS AND GUIDELINES Turn off and unplug all equipment prior to making electrical connections, including speaker wire connections. Reduce the volume level prior to making any change to the audio

More information

MODEL AT-10 ANALOG TRANSMITTER

MODEL AT-10 ANALOG TRANSMITTER MODEL AT-10 ANALOG TRANSMITTER INSTALLATION & OPERATING MANUAL Industrial Weighing Systems 9 Richmond Street Picton, Ontario K0K 2T0 Phone: 613-921-0397 Fax: 613-476-5293 Web: www.iwsystems.ca info@iwsystems.ca

More information

RM24100A. *Maximum transmit power output levels and local radio frequency regulator bodies must be obeyed in the country of operation.

RM24100A. *Maximum transmit power output levels and local radio frequency regulator bodies must be obeyed in the country of operation. RM24100A 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE 802.15.4 compliant) Operating Manual English 1.02 Introduction The RM24100A radio modem acts as a wireless serial cable replacement and

More information

DU3 Ultrasonic Vehicle Detector

DU3 Ultrasonic Vehicle Detector DU3 Ultrasonic Vehicle Detector INSTALLATION/MAINTENANCE INSTRUCTIONS The DU3 is a vehicle detector unit with selfcontained electronics, designed for use with a drive-thru timer system. It should be installed

More information

Installation and Operation Manual MSI. Multi-Sensor Interface Hub. Interface Module for all Sensors Network and Wireless CAUTION

Installation and Operation Manual MSI. Multi-Sensor Interface Hub. Interface Module for all Sensors Network and Wireless CAUTION Installation and Operation Manual MSI Multi-Sensor Interface Hub Interface Module for all Sensors Network and Wireless CAUTION This equipment complies with the limits for a Class B digital device, pursuant

More information

ANT400 OPTIONAL REMOTE ANTENNA MODULE

ANT400 OPTIONAL REMOTE ANTENNA MODULE P516-099 ANT400 OPTIONAL REMOTE ANTENNA MODULE INSTRUCTIONS FOR ANT400-REM-I/O, ANT400-REM-I/O+6dB, ANT400-REM-CEILING, ANT400-REM-HALL Para el idioma español, navegue hacia www.schlage.com/support. Pour

More information

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL Confirm contents of package: 1 sensor, 1 cable, 1 wide lens (default), 1 narrow lens, mounting template, User s Guide. Install the sensor at the desired

More information

Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL This manual covers installation, setup, operation and troubleshooting. Read carefully before attempting to install, operate or

More information

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806 Series 500 Analog Transmitters by Data Industrial Data Industrial Owner s Manual Data Industrial 2/95 PN 72806 Table of Contents Introduction... 1 4-20 ma Loop Supply Requirements... 2 Installation...

More information

USER'S MANUAL DMR-6700

USER'S MANUAL DMR-6700 USER'S MANUAL Multimeter True RMS DMR-6700 CIRCUIT-TEST ELECTRONICS www.circuittest.com Introduction This meter measures AC/DC Voltage, AC/DC Current, Resistance, Capacitance, Frequency (electrical & electronic),

More information

User Manual. PolyGard ADTD Infrared Carbon Dioxide Transmitter Serial No. SM03_00X. October, 2011

User Manual. PolyGard ADTD Infrared Carbon Dioxide Transmitter Serial No. SM03_00X. October, 2011 PolyGard Infrared Carbon Dioxide Transmitter Serial No. SM0_00X User Manual October, 0 GAADTD6_E_0 Page Intended Use... Functional Description.... Control Mode.... Sensor... Installation.... Mounting Instructions....

More information

Contents. Instruction Leaflet IL E Effective March HMi VU Series Instruction Leaflet. Description... Page. Preface...

Contents. Instruction Leaflet IL E Effective March HMi VU Series Instruction Leaflet. Description... Page. Preface... Instruction Leaflet IL04801003E Effective March 2013 HMi VU Series Instruction Leaflet Contents Description... Page Preface... 1 Safety Precautions... 1 Installation... 3 Wiring... 4 asic Inspection...

More information

USER MANUAL. WBP314P71 active power transducer. (3-phase 4-wired)

USER MANUAL. WBP314P71 active power transducer. (3-phase 4-wired) 2 WBP314P1 Active power transducer Safety claim The information in the safety claim of the equipment documentation is intended to ensure that equipment is properly installed in order to maintain it in

More information

IS7705. Installation & Operation Manual AUDIO INTEGRATION KIT. TranzIt LINK

IS7705. Installation & Operation Manual AUDIO INTEGRATION KIT. TranzIt LINK GET CONNECTED Installation & Operation Manual AUDIO INTEGRATION KIT IS7705 Note to Readers, The information contained within the following documentation is subject to change without notice. Features discussed

More information

INSTALLATION AND OPERATING INSTRUCTIONS MODEL SIVF. KB Part No Signal Isolator for KBVF Controls. See Page 1 Pending

INSTALLATION AND OPERATING INSTRUCTIONS MODEL SIVF. KB Part No Signal Isolator for KBVF Controls. See Page 1 Pending INSTALLATION AND OPERATING INSTRUCTIONS MODEL SIVF KB Part No. 9474 Signal Isolator for KBVF Controls See Page 1 Pending See Safety Warning on Page 1 The information contained in this manual is intended

More information

Electronic Controls For general purpose and multi stages controls. Features and Benefits

Electronic Controls For general purpose and multi stages controls. Features and Benefits Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin MS1/4 Electronic Controls For general purpose and multi stages controls Introduction This range of versatile controls is intended for

More information

12 24 VAC/VDC ±10% (inhibited when voltage is applied) min. pulse width duration = 50 ms. Normal mode or Background Analysis mode

12 24 VAC/VDC ±10% (inhibited when voltage is applied) min. pulse width duration = 50 ms. Normal mode or Background Analysis mode DESCRIPTION SUPERSCAN-T Door-Mounted, Presence Sensor for Automatic, Pedestrian Doors SuperScan-T sensors are intended to be used with pedestrian, swing door systems. ENGLISH 1 1. Lens. Master circuit

More information

2- and 4-port Transceivers Piercing, N-type, and BNC

2- and 4-port Transceivers Piercing, N-type, and BNC $0.00 June 1992 LE050 LE051 LE052 LE053 LE063 LE064 2- and 4-port Transceivers Piercing, N-type, and BNC ETHERNET / IEEE 802.3 10MBPS 4-PORT TRANSCEIVER (MAU) POWER REQUIREMENT 11V - 16V, 500mA SQE TEST

More information

How to install your ecobee Switch+

How to install your ecobee Switch+ How to install your ecobee Switch+ Warning Installing this product involves handling high voltage wiring. Each step of the enclosed instructions must be followed carefully. To avoid fire, personal injury,

More information

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual IM-LZSA500-3 January 2008 Revision H Table of Contents LZS-A500-3 Power Supply 1) Safety and Recommended Practices 2 1.1 General

More information

MS2030 CAT III 600 V A V AUTO RS232

MS2030 CAT III 600 V A V AUTO RS232 MS2030 AC Digital Clamp Meter User s Manual CAT III 600 V AUTO RS232 A V CONTENTS 1.Introduction...1 2.Safety Information...1 2.1 Precautions...1 2.2 Safety Symbols...3 3. Description...4 3.1 Front Panel...4

More information

TAG5000 WIRELESS PHASER. Instruction Manual HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS U.S.A.

TAG5000 WIRELESS PHASER. Instruction Manual HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS U.S.A. TAG5000 WIRELESS PHASER Instruction Manual TM HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS 60085 U.S.A. PHONE 847.473.4980 FAX 847.473.4981 website: www.hdelectriccompany.com DESCRIPTION

More information

TE-7700 Series Radio Frequency (RF) Wireless Room Temperature Sensing System

TE-7700 Series Radio Frequency (RF) Wireless Room Temperature Sensing System Submittal Bulletin TE-7700 Series Issue Date July 10, 2003 TE-7700 Series Radio Frequency (RF) Wireless Room Temperature Sensing System The TE-7700 Series RF Wireless Room Temperature Sensing System consists

More information

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure New Product News Measuring & Monitoring Relays K8AK/K8DS Series DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays Compact 22.5 mm and 17.5 mm housings Resistant to high-frequency

More information

PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D

PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D T8211D 1 1. SAFETY INFORMATION BE EXTREMELY CAREFUL IN THE USE OF THIS METER. Improper use of this device can result in electric shock or destroy of

More information

Disclaimers. Important Notice

Disclaimers. Important Notice Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means,

More information

OVEN INDUSTRIES, INC. Model 5C7-362

OVEN INDUSTRIES, INC. Model 5C7-362 OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-362 THERMOELECTRIC MODULE TEMPERATURE CONTROLLER TABLE OF CONTENTS Features... 1 Description... 2 Block Diagram... 3 RS232 Communications Connections...

More information

Document # Rev. C October, GEMINI EXPRESS MULTIPLEXER User s Guide

Document # Rev. C October, GEMINI EXPRESS MULTIPLEXER User s Guide Document # 400-2601-01 Rev. C October, 2002 GEMINI EXPRESS MULTIPLEXER User s Guide TABLE OF CONTENTS SAFETY 3 Federal Communications Commission (FCC) Statement 3 Classification of LED Transmitter Device

More information

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 500 Humbolt Street Los Alamitos, CA 9. If for

More information

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting FANs 216, 121 Technical Bulletin R48 Issue Date 0695 Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting Table of Contents Mounting... 1 Output Control... 2 Wiring...

More information

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors H765A, H765A, H766A, H766A Series 000 Humidity/Temperature Sensors WALL-MOUNT MODELS INSTALLATI INSTRUCTIS APPLICATI The H765A, H766A, H765A and H766A Wall-Mount Humidity/Temperature Sensors are universal

More information

Milliamp Calibrator. Model 434. General description. Calibrate with laboratory accuracy. All 4 to 20 ma loop functions

Milliamp Calibrator. Model 434. General description. Calibrate with laboratory accuracy. All 4 to 20 ma loop functions Milliamp Calibrator Model 434 General description Calibrate Loop Instruments Calibrate and troubleshoot all the signals in a standard 4 to 20 milliamp process control loop with Altek s Model 434 Milliamp

More information

GETTING STARTED GUIDE NI AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous

GETTING STARTED GUIDE NI AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous GETTING STARTED GUIDE NI 9228 8 AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous This document explains how to connect to the NI 9228. Note Before you begin, complete the software and hardware installation procedures

More information

Subject: P0052 Bed Locator Installation Instructions

Subject: P0052 Bed Locator Installation Instructions Subject: P0052 Bed Locator Installation Instructions Tools required: Standard drill 1/4" diameter drill bit Phillips head screwdriver Screwdriver 5/16" hex nut driver Tape measure 4' (122 cm) level Power

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 Barometric Pressure: WE100 Solar Radiation: WE300 Wind Speed: WE550 Wind

More information

Isolated RTD Modules Product Specifications and Installation Data

Isolated RTD Modules Product Specifications and Installation Data Isolated RTD Modules Product Specifications and Installation Data 1 DESCRIPTION The Horner APG Isolated Resistance Temperature Detector (RTD) Input Modules allow RTD temperature sensors to be directly

More information

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5 New Information Electric Current! Danger to Life! Only skilled or instructed persons may carry out the following operations. Variable Speed Micro Drives for Machinery Applications () VSxxx0_, VSxxx2x4_,

More information

RM24100D. Introduction. Features. 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE compliant) Operating Manual English 1.

RM24100D. Introduction. Features. 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE compliant) Operating Manual English 1. RM24100D 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE 802.15.4 compliant) Operating Manual English 1.09 Introduction The RM24100D radio modem acts as a wireless serial cable replacement and

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading edge microprocessor-based circuitry has nonvolatile memory. The display

More information

OPTITEMP TT 20 Technical Datasheet

OPTITEMP TT 20 Technical Datasheet OPTITEMP TT 20 Technical Datasheet Analog PC-programmable two-wire transmitters for Pt100 Efficient PC-configuration without recalibration Very stable output Very fast response time The documentation is

More information

MS8211 DIGITAL MULTIMETER INSTRUCTION MANUAL

MS8211 DIGITAL MULTIMETER INSTRUCTION MANUAL MS8211 DIGITAL MULTIMETER INSTRUCTION MANUAL Ω CONTENTS CONTENTS 1. SAFETY INFORM...1 4.4 Range Transform...10 1.1 Preliminary...1 4.5 Auto Power Off...10 1.2 During use...2 4.6 Preparation For Measurement...11

More information

USERS GUIDE MATRIX P/N SINGLE DIGITAL INDUCTIVE LOOP SENSOR

USERS GUIDE MATRIX P/N SINGLE DIGITAL INDUCTIVE LOOP SENSOR USERS GUIDE MATRIX P/N 17500001 SINGLE DIGITAL INDUCTIVE LOOP SENSOR APPLICATIONS The MATRIX Digital Inductive Loop Detector is the ideal solution for parking barrier control, motorized gates and doors,

More information

TECHNICAL DATASHEET #TD1400AX PWM Controlled Solenoid Driver (DIN rail mount) P/N: PWMC-DR-2A, PWMC-DR-1.2A

TECHNICAL DATASHEET #TD1400AX PWM Controlled Solenoid Driver (DIN rail mount) P/N: PWMC-DR-2A, PWMC-DR-1.2A TECHNICAL DATASHEET #TD1400AX PWM Controlled Solenoid Driver (DIN rail mount) P/N: PWMC-DR-2A, PWMC-DR-1.2A Description: The PWM Controlled Solenoid Driver supplies a proportional solenoid with current

More information

Stand Alone Rudder Angle Indicator System

Stand Alone Rudder Angle Indicator System ComNav Marine Ltd. Phone: 604-207-1600 #15-13511 Crestwood Place Fax: 604-207-8008 Richmond, BC E-mail: sales@comnav.com Canada V6V 2G1 Web: www.comnavmarine.com Stand Alone Rudder Angle Indicator System

More information

LUDLUM MODEL 182 RADON FLASK COUNTER. June 2011 Serial Number PR and Succeeding Serial Numbers

LUDLUM MODEL 182 RADON FLASK COUNTER. June 2011 Serial Number PR and Succeeding Serial Numbers LUDLUM MODEL 182 RADON FLASK COUNTER June 2011 Serial Number PR206794 and Succeeding Serial Numbers LUDLUM MODEL 182 RADON FLASK COUNTER June 2011 Serial Number PR206794 and Succeeding Serial Numbers LUDLUM

More information

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series OpenAir GQD Series Spring Return, 20 lb-in (2 Nm), Rotary Electronic Damper Actuators Technical Instructions Document No. 155-760 EA GQD Description Features Application The OpenAir GQD Series direct-coupled

More information

1. SAFETY INFORMATION.1 2. DESCRIPTION SPECIFICATIONS.6 4. OPERATING INSTRUCTION Voltage measurement Current measurement 10

1. SAFETY INFORMATION.1 2. DESCRIPTION SPECIFICATIONS.6 4. OPERATING INSTRUCTION Voltage measurement Current measurement 10 CONTENTS 1. SAFETY INFORMATION.1 2. DESCRIPTION..4 3. SPECIFICATIONS.6 4. OPERATING INSTRUCTION..9 4.1 Voltage measurement...10 4.2 Current measurement 10 4.3 Resistance measurement...12 4.4 Diode test.12

More information

Model Number Structure

Model Number Structure Single-phase Voltage Relay CSM DS_E_3_1 Ideal for voltage monitoring for industrial facilities and equipment. Monitor for overvoltages or undervoltages. Manual resetting and automatically resetting supported

More information

SCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD

SCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD Modular Wireless I/O System User Manual Version V. for BENTEK SYSTEMS LTD #, 0 Ave S.E. Calgary, AB, Canada TB 0L Ph:(0) Fax:(0) email: sales@scadalink.com web: The is a Modular Wireless I/O System that

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 151 Graham Road P.O. Box 9010 College Station, TX 77842-9010 T: 800-876-1172 Int l: (979) 690-5560, Fax: (979) 690-0440 E-mail : globalw@globalw.com Radar Level Transmitters

More information

YES 12 Charging Wall Cabinet for Mini-laptops

YES 12 Charging Wall Cabinet for Mini-laptops Built with Anthro-DNA Owner's Manual for YES 12 Charging Wall Cabinet for Mini-laptops Part # YESMLCGMPW Components at a Glance 7 1 9 8 2 4 5 11 6 10 3 Front of Cabinet (closed) 1. Locking front door to

More information