On-load tap-changer VACUTAP VRC and VRE
|
|
- Ronald Nicholson
- 6 years ago
- Views:
Transcription
1 On-load tap-changer VACUTAP VRC and VRE Technical Data TD 246/03
2
3 Table of Contents Table of Contents 1 General / Technical data On-load tap-changer designations Summary of the technical data Step capacity diagram Step capacity diagram EAF/LF operation Rated insulation level Rated withstand voltages Rated withstand voltages of the internal insulation VR-rated withstand voltages - multiple coarse change-over selector Special designs Parallel jumpers for parallel connections On-load tap-changer combination VACUTAP VRC I/VRC II for delta connection On-load tap-changer VACUTAP VRC III 700 Y und VRC I 701/1001/1301 with multiple coarse change-over selector (up to max. of 5 coarse taps) Appendix Dimension drawings / connection diagrams Installation drawings NOTE These technical data are intended for the calculator and designer of the transformer. These type-specific data are only valid in connection with the information contained in the general section (TD 61) since this section contains important information on such subjects as potential connection of the tap winding, leakage inductance, current division, and so on. Changes may have been made to a product after going to press with this documentation. We expressly reserve the right to make changes to a product s technical data and design as well as changes to the scope of delivery. In all cases, the information submitted and agreements concluded during processing of the quotation and order in question shall be binding. Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformer manufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirements of the transformer are met. TD 246/03 3
4 1 General / Technical Data 1 General / Technical Data 1.1 On-load tap-changer designations Type Number of phases I um (in A) Number of configured sectors Applications U m (in kv) Tap selector size Number of max. operating positions without changeover selector Number of max. operating positions with change-over selector Mid-positions Change-over selector Tie-in measures VACUTAP VRC VACUTAP VRE 1 phase 2 phases 3 phases Example Exsample VRC III 700 Y - 72,5 / C W R VRC VRE I II III 400 VRC VRC 550 VRC,VRE 700 VRC,VRE 1000 VRC,VRE sector 1 2 sectors 2 3 sectors 3 3 sectors (Y) 0 For neutral connection only VRC,VRE VRC,VRE VRC,VRE VRC,VRE VRC,VRE VRC;VRE VRC;VRE VRC;VRE VRC;VRE Contacts mid-positions (without changeoverselector) 1 mid-position 3 mid-positions reversing change-over selector coarse change-over selector tie-in resistor potential switch potential switch with tie-in resistor Y B C D DE W G R S P - / - Basic connection diagram 4 TD 246/03
5 1 General / Technical Data 1.2 Summary of the technical data On-load tap-changer VRC III 400 Y VRC III 550 Y VRC III 700 Y VRC II 402 VRC II 552 VRC II 702 VRC I 401 VRC I 551 VRC I 701 VRC I 1001 VRC I 1301 VRE III 700 Y VRE I 701 VRE I 1001 VRE I 1301 No. of phases and application 3 1) 3 1) 3 1) ) Max. rated through-current I um (in A) Rated short-time withstand current (in ka) Rated short-circuit duration (in s) Rated peak withstand current (in ka) Max. rated step voltage U im (in V) 2) Step capacity (P StN ) (in kva) Rated frequency (in Hz) Operating positions Without change-over selector: max. of 18 3) With change-over selector: max. of 35 3) Note: 1) Neutral point 2) The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value. 3) For more operating positions, see section 2 Special designs. Oil compartment: Pressure-tight up to 0.3 bar permanent differential pressure (test pressure 0.6 bar), head and cover of the diverter switch oil compartment are vacuum-proof. Temperature The on-load tap-changer VACUTAP VR can be operated in the rated load range at temperatures of the range: surrounding oil between -25 and C and with overload up to 115 C according to IEC Dimensions: Weight, displacement volume, oil content of the diverter switch oil compartment are shown in the relevant dimension drawings. TD 246/03 5
6 1 General / Technical Data Step capacity diagram 1) kva Rated step voltage U i (V) VRC III 400Y VRC II 402'''' VRC I 401''' VRC III 550Y VRC II 552'''' VRC I 551''' 1500 kva VRE III 700Y VRE I 701 VRC III 700Y VRC II 702'''' VRC I 701''' VRE I 1001 VRC I 1001 VRE I 1301 VRC I Rated through-current I u (A) Fig. 1 Step capacities (rated step voltage U i, rated through-current I u ). Note: 1) When used for electrical arc furnace (EAF) and ladle furnace transformers (LF), refer to step capacity diagram chapter Step capacity diagram EAF/LF operation 2) kva 3500 Rated step voltage U i (V) VRC III 400Y VRC II 402'''' VRC I 401''' VRC III 550Y VRC II 552'''' VRC I 551''' VRC III 700Y VRC II 702'''' VRC I 701''' VRE I 701 VRE III 700Y 1750 kva VRE I kva VRC I kva VRE I 1301 VRC I Rated through-current I u (A) Fig. 2 Step capacities electrical arc furnace and ladle furnace operation (EAF/LF), rated step voltage U i, rated through-current I u. Note: 2) Please contact MR. 6 TD 246/03
7 1 General / Technical Data 1.3 Rated insulation level Rated insulation level On-load tap-changer 72.5 to 300 kv VRC I 401/551/701; VRC I 1001; VRC I 1301; VRC II 402/552/702; VRE I 701; VRE I 1001; VRE I to 245 kv VRC III 400/550/700 Y; VRE III 700 Y Highest voltage for equipment U m (in kv) 1) Rated lightning impulse with stand voltage (in kv, 1.2/50 μs) Rated switching impulse withstand voltage (in kv) Rated short-duration power frequency withstand voltage (in kv, 50 Hz, 1 min.) Note: 1) According to IEC , chapter 3.57: highest r.m.s. phase-to-phase voltage in a three-phase system for which a on-load tap-changer is designed with respect to its insulation. TD 246/03 7
8 1 General / Technical Data 1.4 Rated withstand voltages Rated withstand voltages of the internal insulation Fig. 2 shows diagrams of the voltage stress present on the tap winding of the three primary basic connections of three-pole on-load tap-changers and single-pole on-load tap-changers. When selecting the on-load tap-changer, a check must be made to determine whether the highest stress on the tap selector does not exceed the related rated withstand voltages. Without change-over selector With reversing change-over selector With coarse change-over selector in (+) position With coarse change-over selector in ( ) position CAUTION E Adhere to maximum rated lightning impulse withstand a0 = Between selected and preselected tapping on the diverter switch and tap selector voltage stress on a0 in mid-position. a1 = Between tap selector contacts of the winding of one tap position (connected or not connected) a = Between beginning and end of a tapped winding and also with coarse winding, between beginning and end of a coarse winding. Note for coarse tapping arrangement in (-) - position of the change-over selector: When stressed with impulse voltage, the permissible withstand voltage a must be adhered to between the end of a coarse tap winding connected with the K tap selector contact and the tap selector contact at the end of the tapped winding of the same phase b = Between the tap selector contacts of different phases and between change-over selector contacts of different phases, which are connected with the beginning/end of a tapped winding or with a tap selector contact f = Between diverter switch terminal and ground Additional for coarse tapping arrangement in (+) - position of the change-over selector: c1 = From one (-) - change-over selector contact to terminal of the same phase c2 = Between (-) - change-over selector contacts of different phases Fig. 2 Rated withstand voltages 8 TD 246/03
9 1 General / Technical Data Insulation Tap selector size B Tap selector size C Tap selector size D Tap selector size DE distances kv kv kv kv kv kv kv kv 1.2/50 μs 50 Hz 1.2/50 μs 50 Hz 1.2/50 μs 50 Hz 1.2/50 μs 50 Hz 1 min. 1 min. 1 min. 1 min. a0 Power frequency withstand voltage test (50 Hz/60 s): 20 kv 50 Hz 1 min; Response voltage at 1mA-leakage current: 44 kv 1.2/50 μs; 3 ka-residual voltage (= lightning impulse protection level): 70 kv 1.2/50 μs with ZnO On-load tap-changer VRC III 400 Y... VRE I 1301, rated withstand voltages of the interal on-load tap-changer insulation Note: a a b 1) c c 2 1) ) Insulation distance omitted for single-pole on-load tap-changers The admissible maximum operating voltage on the individual tap selector distances complies to half the value of the above mentioned rated short-duration power frequency withstand voltages. Without change-over selector With reversing change-over selector With coarse change-over selector Connection Tap selector size Connection Tap selector size Connection Tap selector size B/C/D/DE 10071W B/C/D/DE 10071G B/C/D/DE B/C/D/DE 10081W B/C/D/DE 10081G B/C/D/DE B/C/D/DE 10091W B/C/D/DE 10091G B/C/D/DE B/C/D/DE 12101W B/C/D/DE 12101G B/C/D/DE B/C/D/DE 12111W B/C 12111G B/C B/C/D/DE 14111W D/DE 14111G D/DE B/C/D/DE 14121W B/C 14121G B/C B/C/D/DE 14131W B/C 14131G B/C B/C/D/DE 16121W D/DE 16121G D/DE B/C/D/DE 16131W D/DE 16131G D/DE B/C/D/DE 16141W B/C/D/DE 16141G B/C/D/DE B/C/D/DE 16151W B/C 16151G B/C B/C/D/DE 18151W D/DE 18151G D/DE B/C/D/DE 18161W B/C 18161G B/C B/C/D/DE 18171W B/C 18171G B/C B/C/D/DE 10191W B/C/D/DE 10191G B/C/D/DE B/C 12231W B/C/D/DE 12231G B/C/D/DE B/C 14271W B/C/D/DE 14271G B/C/D/DE 16311W B/C/D/DE 16311G B/C/D/DE 18351W B/C/D/DE 18351G B/C/D/DE Available connections (also available as 3 W, 3 G) TD 246/03 9
10 1 General / Technical Data VR-rated withstand voltages - multiple coarse change-over selector E a0 = Between selected and preselected tapping on the diverter switch and tap selector a1 = Between tap selector contacts of the winding of a tap position (connected or not connected) a = Between beginning and end of a tapped winding and also between the connected K contact and any points of the tapped winding of the same phase b = Between the tap selector contacts of different phases and between the connected K contact of one phase and any points of the tapped winding of another phase c1 = Between any coarse tappings of one phase to the diverter switch terminal of the same phase c2 = Between identically-named, unconnected coarse tappings of different phases d1 = Between connected and adjacent coarse tap contacts in one phase. d2 = Between unconnected, adjacent coarse tap contacts in one phase d3 = Between beginning and end of all coarse taps of one phase f = Between diverter switch terminal and ground Insulation Tap selector size B Tap selector size C distances a 0 kv kv kv kv 1.2/50 μs 50 Hz 1.2/50 μs 50 Hz 1 min. 1 min. Power frequency withstand voltage test (50 Hz/60 s): 20 kv 50 Hz 1 min; Response voltage at 1 ma-leakage current: 44 kv 1.2/50 μs; 3 ka-residual voltage (= lightning impulse protection level): 70 kv 1.2/50 μs with ZnO a a b 1) c c2 1) d d d On-load tap-changer VACUTAP VRC with multiple coarse change-over selector, rated withstand voltages of the internal on-load tap-changer insulation Note: 1) Insulation distance omitted for single-pole on-load tap-changers The admissible maximum operating voltage on the individual tap selector distances complies to half the value of the above mentioned rated short-duration power frequency withstand voltages. 10 TD 246/03
11 2 Special designs 2 Special designs 2.1 Parallel jumpers for parallel connections Current division on the connection terminals of 2 tap selector planes only for on-load tap-changers VACUTAP VR I 1001 and of 3 tap selector planes only for on-load tap-changers VACUTAP VR I 1301, see appenidix, drawing Parallel jumpers on the tap selector terminals are then mandatory when the tap winding was wound in two or more branches and each of these branch taps is connected to the terminals of the tap selector. This measure reliably prevents the following. a) Introduction of circulating currents into the current paths of tap selector and diverter switch b) Arcing on movable tap selector contact bridges due to commutation c) Overvoltage between adjacent tap selector terminals connected in parallel 2.2 On-load tap-changer combination VACUTAP VRC I/VRC II for delta connection The VRC II 402 on-load tap-changer can also be used with the single-phase on-load tap-changer VRC I 401 as a two-column on-load tap-changer combination VRC I 401/VRC II 402 for adjusting the voltage of transformer windings in a delta connection (similar to VRC I 551 / VRC II 552 and VRC I 701 / VRC II 702). The tap windings should correspond to those in fig. 3. Fig. 3 On-load tap-changer combination VRC I 401 / VRC II 402 (a VRC I 401, b VRC II 402) for delta connection. KHW On-load tap-changer VACUTAP VRC III 700 Y and VRC I 701/1001/1301 with multiple coarse change-over selector (up to max. of 5 coarse taps) Extremely fine voltage adjustment requires a great number of operating positions which sometimes may only be implemented with a multiple coarse tapping arrangement. For instance, 107 operating positions can be obtained by using a coarse 5-tap winding and a tapped winding with 18 tappings. The multiple coarse change-over selector is attached to both sides of the tap selector. The on-load tap-changers are available (on request) for U m = 72.5 up to max. 300 kv and for 2 to 5 coarse taps (tap selector sizes B and C) or 2 and 3 coarse taps (tap selector size D). TD 246/03 11
12 3 Appendix 3 Appendix 3.1 Dimension drawings / connection diagrams On-load tap-changer VACUTAP VRC, VRE, survey of types _1-4 Page On-load tap-changer VACUTAP VR, basic connection diagrams, designation of tap selector terminal contacts according to MR standard _1/2 Page 18/19 On-load tap-changer VACUTAP VRC III 400/550/700 Y, connection diagram 10191W Page 20 On-load tap-changer VACUTAP VRE III 700 Y, connection diagram 10193W Page 21 On-load tap-changer VACUTAP VRC III 400/550/700 Y - 0/W/G, dimension drawing Page 22 On-load tap-changer VACUTAP VRE III 700 Y - 0/W/G, dimension drawing Page 23 On-load tap-changer VACUTAP VRC II 402/552/702-0/W/G, dimension drawing Page 24 On-load tap-changer VACUTAP VRC I 401/551/701-0/W/G, dimension drawing Page 25 On-load tap-changer VACUTAP VRE I 701-0/W/G, dimension drawing Page 26 On-load tap-changer VACUTAP VRC I /W/G, dimension drawing Page 27 On-load tap-changer VACUTAP VRE I /W/G, dimension drawing Page 28 On-load tap-changer VACUTAP VRC I /W/G, dimension drawing Page 29 On-load tap-changer VACUTAP VRE I /W/G, dimension drawing Page 30 On-load tap-changer VACUTAP VRC/VRE connecting leads 3W, 1G, 3G, dimension drawing Page 31 On-load tap-changer VACUTAP VRC III 700 Y, with multiple coarse change-over selector, dimension drawing Page 32 On-load tap-changer VACUTAP VRC I 701, with multiple coarse change-over selector, dimension drawing Page 33 On-load tap-changer VACUTAP VRC I 1001, with multiple coarse change-over selector, dimension drawing Page 34 On-load tap-changer VACUTAP VRC I 1301, with multiple coarse change-over selector, dimension drawing Page TD 246/03
13 3 Appendix 3.2 Installation drawings On-load tap-changer VACUTAP VRC und VRE, installation drawing _1/2 Page 36/37 On-load tap-changer VACUTAP VR, on-load tap-changer head Page 38 On-load tap-changer VACUTAP VR, on-load tap-changer head with flange for pressure-relief device Page 39 On-load tap-changer VACUTAP VR, special design for bell-type tank Page 40 On-load tap-changer VACUTAP VRC und VRE, contact arrangement on the tap selector, no. of contacts per plane Seite 41 On-load tap-changer VACUTAP VRC I 1001/1301, VRE I 1001/1301, jumpers for the parallel connection of tap selector terminals Page 42 On-load tap-changer VACUTAP VR, installation position of tap selector terminals Page 43 On-load tap-changer VACUTAP VRC III 400/550/700 Y, VRE III 700 Y, arrangement of tap selector terminals Seite 44 On-load tap-changer VACUTAP VRC I 401/551/701, VRE I 701, arrangement of tap selector terminals Page 45 On-load tap-changer VACUTAP VRC I 1001, VRE I 1001, arrangement of tap selector terminals Page 46 On-load tap-changer VACUTAP VRC I 1301, VRE I 1301, arrangement of tap selector terminals Seite 47 On-load tap-changer VACUTAP VR, versions of the on-load tap-changer head, swivelling range and drive direction of the gear unit Page 48 On-load tap-changer VACUTAP VR, versions of the on-load tap-changer head, swivelling range and drive direction of the gear unit Seite 49 On-load tap-changer VACUTAP VR, horizontal drive shaft Seite 50 On-load tap-changer VACUTAP VRC and VRE, design: VRC III, VRE III, tie-in resistors with or without potential switch Seite 51 On-load tap-changer VACUTAP VRC, design: VRC II, tie-in resistors with or without potential switch Page 52 On-load tap-changer VACUTAP VRC and VRE, design: VRC I, VRE I, tie-in resistors with or without potential switch Page 53 On-load tap-changer VACUTAP VRC and VRE, tie-in resistor cylinder with potential switch without tie-in resistors Page 54 TD 246/03 13
14 E_1 On-load tap-changer VACUTAP VRC, VRE Survey of types 14 TD 246/03
15 E_2 On-load tap-changer VACUTAP VRC, VRE Survey of types TD 246/03 15
16 E_3 On-load tap-changer VACUTAP VRC, VRE Survey of types 16 TD 246/03
17 E_4 On-load tap-changer VACUTAP VRC, VRE Survey of types TD 246/03 17
18 E_1 On-load tap-changer VACUTAP VR Basic connection diagrams Designation of tap selector terminal contacts according to MR standard 18 TD 246/03
19 E_2 On-load tap-changer VACUTAP VR Basic connection diagrams Designation of tap selector terminal contacts according to MR standard TD 246/03 19
20 On-load tap-changer VACUTAP VRC III 400/550/700 Y-10191W Connection diagram 20 TD 246/03
21 On-load tap-changer VACUTAP VRE III 700 Y-10193W Connection diagram TD 246/03 21
22 E On-load tap-changer VACUTAP VRC III 400/550/700 Y 0/W/G Dimension drawing 22 TD 246/03
23 E On-load tap-changer VACUTAP VRE III 700 Y 0/W/G Dimension drawing TD 246/03 23
24 E On-load tap-changer VACUTAP VRC II 402/552/702 0/W/G Dimension drawing 24 TD 246/03
25 E On-load tap-changer VACUTAP VRC I 401/551/701 0/W/G Dimension drawing TD 246/03 25
26 E On-load tap-changer VACUTAP VRE I 701 0/W/G Dimension drawing 26 TD 246/03
27 E On-load tap-changer VACUTAP VRC I /W/G Dimension drawing TD 246/03 27
28 E On-load tap-changer VACUTAP VRE I /W/G Dimension drawing 28 TD 246/03
29 E On-load tap-changer VACUTAP VRC I /W/G Dimension drawing TD 246/03 29
30 E On-load tap-changer VACUTAP VRE I /W/G Dimension drawing 30 TD 246/03
31 E On-load tap-changer VACUTAP VRC/VRE Connecting leads 3W, 1G, 3G Dimension drawing TD 246/03 31
32 E On-load tap-changer VACUTAP VRC III 700 Y with multiple coarse change-over selector Dimension drawing 32 TD 246/03
33 E On-load tap-changer VACUTAP VRC I 701 with multiple coarse change-over selector Dimension drawing TD 246/03 33
34 E On-load tap-changer VACUTAP VRC I 1001 with multiple coarse change-over selector Dimension drawing 34 TD 246/03
35 E On-load tap-changer VACUTAP VRC I 1301 with multiple coarse change-over selector Dimension drawing TD 246/03 35
36 E_1 On-load tap-changer VACUTAP VRC and VRE Installation drawing 36 TD 246/03
37 E_2 On-load tap-changer VACUTAP VRC and VRE Installation drawing TD 246/03 37
38 E On-load tap-changer VACUTAP VR On-load tap-changer head 38 TD 246/03
39 E On-load tap-changer VACUTAP VR On-load tap-changer head with flange for pressure-relief device TD 246/03 39
40 E On-load tap-changer VACUTAP VR Special design for bell-type tank 40 TD 246/03
41 E On-load tap-changer VACUTAP VRC and VRE Contact arrangement on the tap selector No. of contacts per plane TD 246/03 41
42 E On-load tap-changer VACUTAP VRC I 1001/1301 VRE I 1001/1301 Jumpers for the parallel connection of tap selector terminals 42 TD 246/03
43 E On-load tap-changer VACUTAP VR Installation position of tap selector terminals TD 246/03 43
44 E On-load tap-changer VACUTAP VRC III 400/550/700 Y VRE III 700 Y Arrangement of tap selector terminals 44 TD 246/03
45 E On-load tap-changer VACUTAP VRC I 401/551/701 VRE I 701 Arrangement of tap selector terminals TD 246/03 45
46 E On-load tap-changer VACUTAP VRC I 1001 VRE I 1001 Arrangement of tap selector terminals 46 TD 246/03
47 E On-load tap-changer VACUTAP VRC I 1301 VRE I 1301 Arrangement of tap selector terminals TD 246/03 47
48 E On-load tap-changer VACUTAP VR Versions of the on-load tap-changer head Swivelling range and drive direction of the gear unit 48 TD 246/03
49 E On-load tap-changer VACUTAP VR Versions of the on-load tap-changer head Swivelling range and drive direction of the gear unit TD 246/03 49
50 E On-load tap-changer VACUTAP VR Horizontal drive shaft 50 TD 246/03
51 E On-load tap-changer VACUTAP VRC and VRE Design: VRC III, VRE III Tie-in resistors with or without potential switch TD 246/03 51
52 E On-load tap-changer VACUTAP VRC Design: VRC II Tie-in resistors with or without potential switch 52 TD 246/03
53 E On-load tap-changer VACUTAP VRC and VRE Design: VRC I, VRE I Tie-in resistors with or without potential switch TD 246/03 53
54 E On-load tap-changer VACUTAP VRC and VRE Tie-in resistor cylinder with potential switch without tie-in resistors 54 TD 246/03
55
56 Maschinenfabrik Reinhausen GmbH Phone Falkensteinstrasse 8 Fax Regensburg, Germany sales@reinhausen.com TD 246/03 en 0208/500 F Printed in Germany
On-load tap-changer VACUTAP VRD, VRF, VRG
www.reinhausen.com On-load tap-changer VACUTAP VRD, VRF, VRG Technical Data TD 237/02 Table of Contents Table of Contents 1 General / Technical data... 3 1.1 On-load tap-changer designations... 3 1.2 Summary
More informationVACUTAP VR On-Load Tap-Changer for Regulating Transformers
www.reinhausen.com VACUTAP VR On-Load Tap-Changer for Regulating Transformers Types and variants of VACUTAP VRC, VRE / OILTAP M, RM U m 72.5...245 kv U m 72.5...300 kv VRC VRE U im : 3300 V U im : 4000
More informationVACUTAP VVS COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS.
COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS. WWW.REINHAUSEN.COM 2 TAILORED FOR GRID APPLICATIONS. The vacuum on-load tap-changer was developed and optimized for operation in transformers up to approximately
More informationON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA
ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017 EA 782/15 ENG Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current (Iu),
More informationON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA
ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017-2 EA 710. /1 EN Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current
More informationVACUTAP VR THE ALL-AROUND ON-LOAD TAP-CHANGER. TRANSFORMER CONTROL
VACUTAP VR THE ALL-AROUND ON-LOAD TAP-CHANGER. TRANSFORMER CONTROL VACUTAP VR. VACUTAP VR I HD VACUTAP VR PROFIT FROM LOW TOTAL COST OF OWNERSHIP. 2 With the introduction of vacuum technology in on-load
More informationON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA
ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria EA 675/15 ENG Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current (Iu),
More informationOn-Load Tap Changer Type M
On-Load Tap Changer Type M OLTC type model M III 500 Y, U m = 123 Kv, 500A, ± 9 steps The type M On Load tap changers are used to vary the ratio of oil-immersed transformers under load.in general they
More informationTECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER
TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER HM0.154.1901 SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. General 1. General 3 2. Technical specifications 4 3. Type explanation 5 4. Terms and definitions
More informationTECHNICAL DATA TYPE SHZV VACUUM ON-LOAD TAP CHANGER FOR OIL-IMMERSED TRANSFORMER
TECHNICL DT TYPE SHZV VCUUM N-LD TP CHNGER FR IL-IMMERSED TRNSFRMER HM0.154.3901-02.06/2018 SHZV(cylinder tap selector) SHZV(cage tap selector) SHNGHI HUMING PWER EQUIPMENT C., LTD. General 1. General
More informationTECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER
TECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. CONTENT 1. General 2 2. Technical specifications 2 3. Model explanation 4 4. Terms and definitions
More informationTAP CHANGER SELECTING MANUAL TECHNICAL DATA
TECHNICAL DATA HM0.154.000 SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. General 1. General requirement for tap changer selecting 2 2. Attention for tap changer mounting 10 3. Tap changer accessories 10 4.
More information1ZSE en, Rev. 6. On-load tap-changers, type UBB Technical guide
1ZSE 5492-106 en, Rev. 6 On-load tap-changers, type UBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide
1ZSC000562-AAJ en, Rev. 1 Vacuum on-load tap-changers, type VUBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationLoad Tap Changers for Power Transformers
Load Tap Changers for Power Transformers Dr. Dieter Dohnal / Maschinenfabrik Reinhausen GmbH Dipl. Ing. Bernhard Kurth / Reinhausen Manufacturing Inc. Load Tap Changers for Power Transformers Content Basic
More information1ZSC AAW en, Rev. 2. On-load tap-changers, type UC Technical guide
1ZSC000562-AAW en, Rev. 2 On-load tap-changers, type UC Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationMR PUBLICATION. On-Load Tap-Changers for Power Transformers A Technical Digest
On-Load Tap-Changers for Power Transformers A Technical Digest Abstract Introduction On-Load Tap-Changers (OLTCs) are one of the indispensable components for the regulation of power transformers used
More informationPRODUCTS AND SOLUTIONS FOR A SMOOTH POWER SUPPLy. TRANSFORMER CONTROL
PRODUCTS AND SOLUTIONS FOR A SMOOTH POWER SUPPLy. TRANSFORMER CONTROL REGULATING TRANSFORMERS MR A RELIABLE PARTNER. GUARANTEED. We at MR have been writing our success story for more than 140 years. As
More information1ZSE en, Rev. 9. On-load tap-changers, type UC and VUC Technical guide
1ZSE 5492-105 en, Rev. 9 On-load tap-changers, type UC and VUC Technical guide The manufacturer Hereby declares that The products Manufacturer s declaration ABB AB Components SE-771 80 LUDVIKA Sweden comply
More informationOn-load tap-changers, type UC and VUC Technical guide
1ZSE 5492-105 en, Rev. 7 On-load tap-changers, type UC and VUC Technical guide The manufacturer Hereby declares that The products Manufacturer s declaration ABB AB Components SE-771 80 LUDVIKA Sweden comply
More information24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD
A NEW GENERATION VOLTAGE REGULATION DISTRIBUTION TRANSFORMER WITH AN ON LOAD TAP CHANGER FOR POWER QUALITY IMPROVEMENT IN THE ELECTRICAL DISTRIBUTION SYSTEMS Sudheer MOKKAPATY Jens WEISS Frank SCHALOW
More informationRegional Technical Seminar
Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979
More informationPomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations
More informationPRODUCTS & ACCESSORIES FOR DISTRIBUTION TRANSFORMERS.
PRODUCTS & ACCESSORIES FOR DISTRIBUTION TRANSFORMERS. WWW.REINHAUSEN.COM DISTRIBUTION TRANSFORMER ONLY THE BEST FOR YOUR DISTRIBUTION TRANSFORMER (DT). Switching, insulating, measuring and protecting.
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationAMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS
AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published
More informationAll the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.
1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred
More informationInsulation Co-ordination For HVDC Station
Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating
More informationComparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137
ITEM Power factor (tanδ) & Capacitance Measurement Dry 1-minute Power frequency with partial discharge measurement CAN/CSA C88.1-96 IEEE C57.19.00/01 IEC 60137 Requirement Requirement Requirement Clause
More informationSemiconductor (AC) fuses
Main characteristics Recognized 650 to 300VAC / 63 to 2800A. Exceptionally low I 2 T, Watt losses. Non-magnetic construction, highly reliable low voltage. Indicator system. Conformity to UL, CSA investigated,
More informationVoltage Regulator TAPCON 230 basic. Quick reference guide /02
Voltage Regulator TAPCON 230 basic Quick reference guide 2117248/02 2012 All rights reserved by Maschinenfabrik Reinhausen Copying and distribution of this document and the utilization and communication
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationRegional Technical Seminar TAP CHANGERS
Regional Technical Seminar TAP CHANGERS SPX Transformer Solutions, Inc. September 4, 2018 De-Energized and Load Tap Changers Jason Varnell Lead Design Engineer jason.varnell@spx.com SPX Transformer Solutions,
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationTechnical guide. Type VRLTC load tap changer
Technical guide Type VRLTC load tap changer Table of contents 2 General information 4 Switching sequences 6 Tank characteristics 6 Terminal board 7 Tap selector 7 Stationary contacts 7 Reversing switch
More information7P Series - Surge Protection Device (SPD) Features 7P P P
Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to
More informationTECHNICAL INFORMATION
Single-Phase Low Voltage Dry- Type Transformers 5-400 kva Three-Phase Low Voltage Dry- Type Transformers 7.5-1000 kva TECHNICAL INFORMATION TABLE OF CONTENTS Introduction...3 Technical Explanations...4
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 25876 Safat 13119 Kuwait Contact: Mr Atul Madhukar Vaidya Tel: +965 1822600 Fax: +965 24761963 E-Mail: factory@ahleiasg.com Website:
More informationOIL-IMMERSED ARC-SUPPRESSION COILS
ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department
More informationDocuments and Addresses
Report No.: 14-041-MS Sheet: 2 Documents and Addresses Accreditation The Prüffeld der Schaltwerke, Berlin has been approved by the DAkkS (German accreditation body) according to EN ISO/IEC 17025 for tests
More informationTechnical guide. Type VRLTC load tap changer
Technical guide Type VRLTC load tap changer Table of contents General information... 2 Electrical characteristics... 3 Type tests... 4 Switching sequence... 5 Tank characteristics... 7 Terminal board...
More informationTechnical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL
Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-66 Version 6.6 Table of Contents SMA Solar Technology AG Table of
More informationS. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)
S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical
More informationINTERNATIONAL STANDARD
NTERNATONAL STANDARD EC 60214-1 Edition 2.0 2014-05 colour inside Tap-changers Part 1: Performance requirements and test methods EC 60214-1:2014-05(en) THS PUBLCATON S COPYRGHT PROTECTED Copyright 2014
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules
More informationService by MR. Safety ex Works
www.reinhausen.com Service by MR. Safety ex Works Checkups are fine. Our service is better One thing is for sure: When you buy an on-load tap-changer from MR, you get the tech - nically mature and sophisticated
More informationR Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data
Distribution Transformers Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections R201-90-2 Reference Data CONTENTS POPULAR DlSTRIBUTlON TRANSFORMER AND CIRCUIT VOLTAGES... 1 2400-Volt Systems
More informationTechnical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL
Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-65 Version 6.5 Table of Contents SMA Solar Technology AG Table of
More informationSERIES K: PROTECTION AGAINST INTERFERENCE
International Telecommunication Union ITU-T K.45 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (04/2008) SERIES K: PROTECTION AGAINST INTERFERENCE Resistibility of telecommunication equipment installed
More informationLiquid-Filled Transformers
Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationMEDIUM VOLTAGE PRODUCT. TJP 7.x Indoor voltage transformers
MEDIUM VOLTGE PRODUCT TJP 7.x Indoor voltage transformers 2 TJP 7.X INDOOR VOLTGE TRNSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning impulse test voltage
More informationKeywords: Power Transformer, On-load Tap Changer, AVR, Low Voltage Variation, Change Positions, OLTC Control.
www.semargroup.org, www.ijsetr.com ISSN 2319-8885 Vol.03,Issue.11 June-2014, Pages:2487-2493 Advance OLTC Control for Improving Power System Voltage Stability NWE NWE SOE 1, KYAW SAN LWIN 2 1 Dept of Electrical
More informationTechnical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope
Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site
More informationReactor and inductor are names used interchangeably for this circuit device.
Recommended Design Criteria for Air-Cooled Reactor for Line and Track Circuits Revised 2015 (7 Pages) A. Purpose This Manual Part recommends design criteria for an air-cooled reactor for line and track
More informationSemiconductor (AC) fuses
BS884 Fuses 6x27, 2X6x27, 250 VAC Extremely high breaking capacity fuses: protection of power semiconductors as per IEC standard 60269.1 and 4 250 V voltage COMPLYING WITH IEC gr class (s from 50 to 50
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following
More informationCONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationIGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards
APPROVED IGS Iranian Gas Standards Contactors. Fax:(9821)-8131-5679 --. /012 34-52673892 :;395- 8? /@A7 B;CD /E FGH 34-52673892I2
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationMEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers
MEDIUM VOLTAGE PRODUCT TJP 6.1, TJP 6.2 Indoor voltage transformers 2 TJP 6.1, TJP 6.2 INDOOR VOLTAGE TRANSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning
More informationTransformers connected via a cable Overvoltage protection
A P P L I C AT I O N N OT E 2. 1 Transformers connected via a cable Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage
More informationSERIES K: PROTECTION AGAINST INTERFERENCE
International Telecommunication Union ITU-T K.21 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (04/2008) SERIES K: PROTECTION AGAINST INTERFERENCE Resistibility of telecommunication equipment installed
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationInsulation Level and Test Technology of. 1000kV Power Transformer
Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC
More informationMEDIUM VOLTAGE PRODUCT. TJP 5.x Indoor voltage transformers
MEDIUM VOLTAGE PRODUCT TJP 5.x Indoor voltage transformers 2 TJP 5.X INDOOR VOLTAGE TRANSFORMERS 01 Voltage transformer TJP 5.1 and TJP 5.2 with suitable fuses Parameters Highest voltage for equipment
More informationSPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS
-1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More information3. COMBINED TRANSFORMERS Oil-paper insulation
3. COMBINED TRANSFORMERS Oil-paper insulation 123 kv Combined transformers. 26 Instrument transformers High voltage INTRODUCTION Combined instrument transformers contain a current transformer and an inductive
More informationSPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION February 2017 SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and
More informationTRANSFORMER SERVICES OUR KNOWLEDGE. YOUR EXPERTS.
TRANSFORMER SERVICES OUR KNOWLEDGE. YOUR EXPERTS. WWW.REINHAUSEN.COM Diagnostics Consulting Service TRANSFORMER LIFECYCLE PARTNER Modernization TRANSFORMER SERVICES 2 MAXIMUM AVAILABILITY. IDEALLY PLANNED.
More informationLOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY. This instruction of a general nature and does not relate to specific standards.
LTI-G2 LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY This instruction of a general nature and does not relate to specific standards. It provides additional information ensuring a suitable degree
More informationISOLATING TRANSFORMERS FOR TLC PLANTS
ISOLATING TRANSFORMERS FOR TLC PLANTS Isolating transformers for TLC plants The power supply of telecommunication plants and FM/TV relay stations has always entailed numerous problems and specific needs
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationVacuum Interrupters for Medium Voltage
for Medium Voltage Reliable, Maintenance-Free and Environmentally Friendly Today, vacuum as an arc extinguishing medium provides the most cost-effective solution for medium-voltage circuit-breakers. Siemens
More informationPRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS
PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationCommissioning Manual Distribution Transformers - Three-phase Oil Filled
1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...
More informationI -limiter The world s fastest switching device
I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection
More informationINTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE
INTERNTIONL TELECOMMUNICTION UNION TELECOMMUNICTION STNDRDIZTION SECTOR OF ITU K.21 (10/2000) SERIES K: PROTECTION GINST INTERFERENCE Resistibility of telecommunication equipment installed in customer
More information10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units
BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells
More informationShunt Reactor Switching
Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented
More informationABB Power Technologies
ABB Power Technologies Info. No. 1ZSC000498-AAN en From/Date Order data sheet explanations for tap-changer type UZ Scope This product information gives some more explanations to the order data sheet for
More informationMEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly
MEDIUM VOLTAGE PRODUCT PARAMETERS GUIDE How to specify the indoor instrument transformers correctly The range of electric values in the power supply systems is very extensive. This is why it is necessary
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV
More informationSiemens AG New portfolio for reliable personnel, material and fire protection
s Siemens AG 2016 SENTRON 5SV9 Compact RCBOs New portfolio for reliable personnel, material and fire protection Reliable personnel/ investment protection This combination of residual current operated circuit
More informationTransformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018
Transformer Testing & Maintenance Fundamentals 1 AVO Training Institute, Inc. 2018 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the
More informationSERIES K: PROTECTION AGAINST INTERFERENCE
International Telecommunication Union ITU-T K.21 TELECOMMUNICTION STNDRDIZTION SECTOR OF ITU (11/2011) SERIES K: PROTECTION GINST INTERFERENCE Resistibility of telecommunication equipment installed in
More informationCOMPACT LED DRIVERS. ComfortLine Selectable Current (LEDset) ComfortLine SELECTABLE CURRENT LEDset ,
COMPACT LED DRIVERS ComfortLine SELECTABLE CURRENT LEDset 186650, 186664 Typical Applications Built-in in compact luminaires for Shop lighting Downlights ComfortLine with selectable current SELECTABLE
More informationUNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationTRANSFORMERS FOR GIS APPLICATIONS VOLTAGE VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS
VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS INFORMATION ABOUT THE SAFE OPERATION OF VOLTAGE TRANSFORMERS OPERATION CONDITIONS FOR POTENTIAL TRANSFORMERS 1. When
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer LF 1010-S/SPA5 I P N = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationTS RES - OUTSTANDING ISSUES
TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationIntroduction EMC. Filter parameters. Definition of EMC / EMI. X-Capacitor. Sources of EMI. Coupling mechanism. Y-Capacitor.
Introduction to EMC Schurter has over 75 years experience in the electronics and electrical industries, developing and manufacturing components that ensure a clean and safe supply of power. Schurter provides
More information