ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA

Size: px
Start display at page:

Download "ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA"

Transcription

1

2 ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria

3 EA 675/15 ENG Contents 1. Basic characteristics Basic technical data Rated through current (Iu), rated step voltages (Ui), rated switching capacity (PstN) Electrical and mechanical endurance Insulation level Review of the different RS 9.3 / RS 9 types Main dimensions Number of steps and basic connection diagrams Appendices Overall dimension drawings of OLTCs Additional drawings of OLTCs RS 9.3/RS 9 driving shafts...13 Notes: 1) This technical data catalog is intended to be used by transformer designers as well as other technical personnel responsible for maintenance, diagnostics and operation of OLTCs. 2) HHI-Bulgaria reserves the right to make changes in the overall dimension drawings and connection diagrams without prior notice. Updated drawings are provided as part of the technical documentation received by the customer at the time of the product delivery; updated drawings can be provided also to potential customers on request. 3) The OLTC is manufactured according to the specific data in the order specification sheet filled in by the client. 4) HHI-Bulgaria is not responsible for the client s improper selection of an OLTC. 2

4 1. Basic characteristics The OLTCs of Hyundai Heavy Industries Co. Bulgaria (HHIB) meet the requirements of the IEC standard Basic technical data Table 1 RS 9.3 RS 9.3 RS 9.3 RS 9.3 RS 9.3 RS 9.3 RS 9.3 RS 9.3 RS 9.3 OLTC type ІІІ 200 ІІІ 400 ІІІ 630 І 200 І 400 І 630 І 800 І 1200 І 1600 Number of phases and application 3 in the neutral 1 phase at any point on the winding Maximum rated through current (А) Short circuit R.m.s. value (3 s duration) , , withstand current (ка) Peak value , , Maximum rated step voltage per phase (V) Rated step capacity (kva) Rated frequency (Hz) Highest voltage for equipment Um (kv, r.m.s.) 1) 41,5 72, Rated separate source AC withstand voltage, min duration (kv, r.m.s.) Insulation to earth Rated switching impulse withstand voltage (kv, 250/2500 µs) Rated lighting impulse withstand voltage (kv, 1,2/50 µs) Number of operating positions Without change-over selector max. of 18 With change-over selector max. of 35 Five tap selector sizes (K, L, M, N, Р) are available corresponding to the requirements of the Tap selector voltage stress across the regulating winding. The tap selector insulation level can be chosen independently from the maximum operating voltage to earth. Oil pressure in the diverter switch oil compartment Operating oil pressure up to 0,3x10 5 Pa (testing pressure 0,6x10 5 Pa). Vacuum-proof for drying. Siphon for draining the oil from the diverter switch oil vessel Drying Basic design left or right In vacuum furnace up to 110 C In kerosene vapour up to 125 C OLTC type RS 9.3 ІІІ 200/400/630 RS 9.3 І 200/400/630 RS 9.3 І 800/1200/1600 Tap selector sizes K L M N P K L M N P K L M N Р Weight in kg without chage-over selector (approx.) with chage-over selector Displacement volume in dm 3 (approx.) Oil filling quantity of the diverter switch oil compartment Vs in dm 3 (approx.) 41, ,5 kv kv kv kv kv ,5 kv ,5 kv kv kv kv kv ) In accordance with IEC , chapter 3.60 highest effective value for phase-to-phase voltage in a three-phase system for which an on-load tap-changer is designed with respect to its insulation. Notes: 1. RS 9 OLTCs are with elliptical upper flange. RS 9.3 OLTCs are with round upper flange. All the rest technical data are the same. 2. Minimum conservator volume due to the temperature expanse of the oil at temperature changes from -30ºC up to +100ºC is: ΔV = 0,1Vs + 5 (dm 3 ) 3. RS 9.3 OLTCs can operate with a rated load at oil temperature from -25ºC to +105ºC. 3

5 EA 675/15 ENG 1.2. Rated through current (Iu), rated step voltages (Ui), rated switching capacity (PstN) Table 2 shows the maximum values of Iu, the corresponding step voltage Ui and the rated step capacity PstN. Table 2: Maximum rated through current (Ium), rated step voltages (Ui), rated step capacity (PstN) OLTC RS 9.3 III RS 9.3 I Ium (A) Ui (V) PstN (kva) The rated through current Iu and its corresponding rated step voltage Ui are determined by the curve of the rated step capacity (Fig. 1, 2). Fig. 1: Step capacities (rated through current Iu [A]; rated step voltages Ui [V]) Fig. 2: Step capacities (rated through current Iu [A]; rated step voltages Ui [V]) 4

6 In case of overexcitation of the transformer, the maximum step voltage can be increased with 10% under the condition that the step capacity is limited to its rated value. The specific commutation regimes are clarified in the technical data catalog for all HHIB OLTCs Electrical and mechanical endurance The electrical edurance of the diverter switch arcing contacts depends on many factors, connected with the operating conditions. The number of operations until inspection and contact replacement, obtained experimentally at maximum rated through current, relevant step voltage and cosφ = 1 is given in table 3. OLTC RS 9.3 ІІІ 200 A RS 9.3 ІІІ 400 A Table 3: Electrical and mechanical endurance RS 9.3 ІІІ 630 A RS 9.3 І 800 A RS 9.3 І 1200 A RS 9.3 І 1600 A Number of switching operations till inspection 1) Number of switching operations till replacement of contacts Mechanical endurance number of switching operations 1) or in operation for maximum: 200 A 5 years; 400 A 3 years and for 630, 800, 1200 and 1600 A 2 years. Detailed information about the number of switching operations till inspection for the different tap changers is given in the RS 9.3/RSV 9.3 Installation and Operation Manual Insulation level The insulation level of the OLTC is determined by a number of withstand voltage values. The rated withstand voltage values to earth are given in Table 1. These voltages are determined by national and international standards. The internal insulation is dimensioned depending on the voltages defined by the transformer winding taps to the different parts of the selector, change-over selector and the diverter switch. Fig. 3 shows the main connection diagrams and the typical insulation distances to them. The withstand voltage values from the different insulation distances are given in Table 4. For a correct OLTC selection, these voltage values should correspond to the voltage values that occur during the lightning impulse test, the induced voltage test and the power frequency voltage test of the transformer. The least favorable position of the OLTC should be taken into account. The insulation to earth and the tap selector insulation size are not mutually connected and can be selected in accordance with the specific requirements. 5

7 EA 675/15 ENG RS 9.3 III 200/400/630 OLTCs WITHOUT CHANGE-OVER SELECTOR WITH REVERSE CHANGE-OVER SELECTOR WITH COARSE CHANGE-OVER SELECTOR RS 9.3 I 200/400/630/800/1200/1600 OLTCs WITHOUT CHANGE-OVER SELECTOR WITH REVERSE CHANGE-OVER SELECTOR WITH COARSE CHANGE-OVER SELECTOR Fig. 3: Insulation distances of the transformer windings Insulation distances Rated withstand voltages (kv) Table 4: Rated withstand voltages Tap selector size K Tap selector size L Tap selector size M Tap selector size N Tap selector size P 1,2/50 μs 50 Hz 1 min 1,2/50 μs 50 Hz 1 min 1,2/50 μs 50 Hz 1 min 1,2/50 μs 50 Hz 1 min 1,2/50 μs 50 Hz 1 min a b b c c d

8 2. Review of the RS 9.3 / RS 9 types 2.1. Main dimensions 1) WITHOUT CHANGE-OVER SELECTOR WITH REVERSE CHANGE-OVER SELECTOR WITH COARSE CHANGE-OVER SELECTOR Fig. 4: RS 9.3 ІІІ Table 5: RS 9.3 ІІІ Selector insulation size Um K L M N P h d h d h d h d h d 41,5kV kv kv kv kv Fig. 5: RS 9.3 І Table 6: RS 9.3 І Selector insulation size Um K L M N P h d h d h d h d h d 41,5kV kv kv kv kv Um Fig. 6: RS 9.3 ІI + RS 9.3 I Table 7: RS 9.3 IІ + RS 9.3 I Selector insulation size K L M N P h 1 h 2 d h 1 h 2 d h 1 h 2 d h 1 h 2 d h 1 h 2 d 41,5kV kv kv kv kv ) For the rest of the dimensions see appendices 7

9 EA 675/15 ENG 2.2. Number of steps and basic connection diagrams Fig. 7, 7a and 7b show the basic connection diagrams where the selector contacts are designations according to the overall dimension drawings. Fig. 7: Basic connection diagrams 8

10 Fig. 7a: Basic connection diagrams 9

11 EA 675/15 ENG Fig. 7b: Basic connection diagrams 10

12 Fig. 8: Basic connection diagram W Fig. 9: Basic connection diagram W 11

13 EA 675/15 ENG Fig. 10: Basic connection diagram G Fig. 11: Basic connection diagram G 12

14 3. Appendices 3.1. Overall dimension drawings of OLTCs RS 9 III 200/400/ RS 9 II 200/400/ RS 9 I 200/400/ RS 9.3 III 200/400/ RS 9.3 II 200/400/ RS 9.3 I 200/400/ RS 9.3 I 800/ RS 9.3 I /P 1083 RS 9.3 I RS 9.3 III 200/400/630/P 1085 RS 9.3 II 200/400/630/P 1086 RS 9.3 I 200/400/630/P 1087 OLTSs with pressure relief device and tie-in resistors 310Q OLTCs RS 9.3/RSV 9.3 flange s configuration Additional drawings of OLTCs RS 9.3/RS 9 III 10, 12, 14 arrangement of tap selector terminals 374 RS 9.3/RS 9 III 16, 18 arrangement of tap selector terminals 375 RS 9.3/RS 9 I 10, 12, 14 arrangement of tap selector terminals 376 RS 9.3/RS 9 I 16, 18 arrangement of tap selector terminals OLTCs type RS9 and RS9.3 driving shafts arrangement RS 9 driving shafts arrangement 209 RS 9.3 driving shafts arrangement

15 ON LOAD TAP CHANGERS RS 9 III 200/400/

16 ON LOAD TAP CHANGERS RS 9 II 200/400/

17 ON LOAD TAP CHANGERS RS 9 I 200/400/

18 ON LOAD TAP CHANGERS RS 9.3 III 200/400/

19 ON LOAD TAP CHANGERS RS 9.3 II 200/400/

20 ON LOAD TAP CHANGERS RS 9.3 I 200/400/

21 ON LOAD TAP CHANGERS RS 9.3 I 800/

22 ON LOAD TAP CHANGERS RS 9.3 I 1200 P 1083

23 ON LOAD TAP CHANGERS RS 9.3 I

24 ON LOAD TAP CHANGERS RS 9.3 III 200/400/630 P 1085

25 ON LOAD TAP CHANGERS RS 9.3 II 200/400/630 P 1086

26 ON LOAD TAP CHANGERS RS 9.3 I 200/400/630 P 1087

27 ON LOAD TAP CHANGER RS 9/RS 9.3/RSV 9.3a WITH PRESSURE RELIEF DEVICE AND TIE-IN RESISTORS 310Q

28 ON LOAD TAP CHANGERS RS 9.3/RSV 9.3/RS 7.3/RSV

29 OLTC RS 9.3/RS 9 III 10, 12, 14 ARRANGEMENT OF TAP SELECTOR TERMINALS 374

30 OLTC RS 9.3/RS 9 III 16, 18 ARRANGEMENT OF TAP SELECTOR TERMINALS 375

31 OLTC RS 9.3/RS 9 I 10, 12, 14 ARRANGEMENT OF TAP SELECTOR TERMINALS 376

32 OLTC RS 9.3/RS 9 I 16, 18 ARRANGEMENT OF TAP SELECTOR TERMINALS 377

33 ON LOAD TAP CHANGER RS 9 DRIVING SHAFTS ARRANGEMENT 209 Sheet 1/2

34 ON LOAD TAP CHANGER RS 9 DRIVING SHAFTS ARRANGEMENT 209 Sheet 2/2

35 ON LOAD TAP CHANGER RS 9.3/RSV 9.3 DRIVING SHAFTS ARRANGEMENT Sheet 1/2

36 ON LOAD TAP CHANGER RS 9.3/RSV 9.3 DRIVING SHAFTS ARRANGEMENT Sheet 2/2

37

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017-2 EA 710. /1 EN Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current

More information

ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA

ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017 EA 782/15 ENG Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current (Iu),

More information

On-Load Tap Changer Type M

On-Load Tap Changer Type M On-Load Tap Changer Type M OLTC type model M III 500 Y, U m = 123 Kv, 500A, ± 9 steps The type M On Load tap changers are used to vary the ratio of oil-immersed transformers under load.in general they

More information

On-load tap-changer VACUTAP VRD, VRF, VRG

On-load tap-changer VACUTAP VRD, VRF, VRG www.reinhausen.com On-load tap-changer VACUTAP VRD, VRF, VRG Technical Data TD 237/02 Table of Contents Table of Contents 1 General / Technical data... 3 1.1 On-load tap-changer designations... 3 1.2 Summary

More information

On-load tap-changer VACUTAP VRC and VRE

On-load tap-changer VACUTAP VRC and VRE www.reinhausen.com On-load tap-changer VACUTAP VRC and VRE Technical Data TD 246/03 Table of Contents Table of Contents 1 General / Technical data... 4 1.1 On-load tap-changer designations... 4 1.2 Summary

More information

TECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER

TECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER TECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. CONTENT 1. General 2 2. Technical specifications 2 3. Model explanation 4 4. Terms and definitions

More information

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER HM0.154.1901 SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. General 1. General 3 2. Technical specifications 4 3. Type explanation 5 4. Terms and definitions

More information

VACUTAP VR On-Load Tap-Changer for Regulating Transformers

VACUTAP VR On-Load Tap-Changer for Regulating Transformers www.reinhausen.com VACUTAP VR On-Load Tap-Changer for Regulating Transformers Types and variants of VACUTAP VRC, VRE / OILTAP M, RM U m 72.5...245 kv U m 72.5...300 kv VRC VRE U im : 3300 V U im : 4000

More information

VACUTAP VVS COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS.

VACUTAP VVS COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS. COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS. WWW.REINHAUSEN.COM 2 TAILORED FOR GRID APPLICATIONS. The vacuum on-load tap-changer was developed and optimized for operation in transformers up to approximately

More information

TAP CHANGER SELECTING MANUAL TECHNICAL DATA

TAP CHANGER SELECTING MANUAL TECHNICAL DATA TECHNICAL DATA HM0.154.000 SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. General 1. General requirement for tap changer selecting 2 2. Attention for tap changer mounting 10 3. Tap changer accessories 10 4.

More information

TECHNICAL DATA TYPE SHZV VACUUM ON-LOAD TAP CHANGER FOR OIL-IMMERSED TRANSFORMER

TECHNICAL DATA TYPE SHZV VACUUM ON-LOAD TAP CHANGER FOR OIL-IMMERSED TRANSFORMER TECHNICL DT TYPE SHZV VCUUM N-LD TP CHNGER FR IL-IMMERSED TRNSFRMER HM0.154.3901-02.06/2018 SHZV(cylinder tap selector) SHZV(cage tap selector) SHNGHI HUMING PWER EQUIPMENT C., LTD. General 1. General

More information

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations

More information

1ZSE en, Rev. 6. On-load tap-changers, type UBB Technical guide

1ZSE en, Rev. 6. On-load tap-changers, type UBB Technical guide 1ZSE 5492-106 en, Rev. 6 On-load tap-changers, type UBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide

1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide 1ZSC000562-AAJ en, Rev. 1 Vacuum on-load tap-changers, type VUBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 25876 Safat 13119 Kuwait Contact: Mr Atul Madhukar Vaidya Tel: +965 1822600 Fax: +965 24761963 E-Mail: factory@ahleiasg.com Website:

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses BS884 Fuses 6x27, 2X6x27, 250 VAC Extremely high breaking capacity fuses: protection of power semiconductors as per IEC standard 60269.1 and 4 250 V voltage COMPLYING WITH IEC gr class (s from 50 to 50

More information

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site

More information

1ZSC AAW en, Rev. 2. On-load tap-changers, type UC Technical guide

1ZSC AAW en, Rev. 2. On-load tap-changers, type UC Technical guide 1ZSC000562-AAW en, Rev. 2 On-load tap-changers, type UC Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD A NEW GENERATION VOLTAGE REGULATION DISTRIBUTION TRANSFORMER WITH AN ON LOAD TAP CHANGER FOR POWER QUALITY IMPROVEMENT IN THE ELECTRICAL DISTRIBUTION SYSTEMS Sudheer MOKKAPATY Jens WEISS Frank SCHALOW

More information

VACUTAP VR THE ALL-AROUND ON-LOAD TAP-CHANGER. TRANSFORMER CONTROL

VACUTAP VR THE ALL-AROUND ON-LOAD TAP-CHANGER. TRANSFORMER CONTROL VACUTAP VR THE ALL-AROUND ON-LOAD TAP-CHANGER. TRANSFORMER CONTROL VACUTAP VR. VACUTAP VR I HD VACUTAP VR PROFIT FROM LOW TOTAL COST OF OWNERSHIP. 2 With the introduction of vacuum technology in on-load

More information

1ZSE en, Rev. 9. On-load tap-changers, type UC and VUC Technical guide

1ZSE en, Rev. 9. On-load tap-changers, type UC and VUC Technical guide 1ZSE 5492-105 en, Rev. 9 On-load tap-changers, type UC and VUC Technical guide The manufacturer Hereby declares that The products Manufacturer s declaration ABB AB Components SE-771 80 LUDVIKA Sweden comply

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...

More information

About us. Vision. To lead our field in innovation, quality and customer service.

About us. Vision. To lead our field in innovation, quality and customer service. a Index 1 2 4 6 7 8 13 About us Low voltage switchgear & bus duct Medium voltage switchgear & bus duct UKAS ACCREDITATION ASTA RECOGNITION Distribution and Power transformers OUR TEAM About us Vision To

More information

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch. Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137 ITEM Power factor (tanδ) & Capacitance Measurement Dry 1-minute Power frequency with partial discharge measurement CAN/CSA C88.1-96 IEEE C57.19.00/01 IEC 60137 Requirement Requirement Requirement Clause

More information

On-load tap-changers, type UC and VUC Technical guide

On-load tap-changers, type UC and VUC Technical guide 1ZSE 5492-105 en, Rev. 7 On-load tap-changers, type UC and VUC Technical guide The manufacturer Hereby declares that The products Manufacturer s declaration ABB AB Components SE-771 80 LUDVIKA Sweden comply

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

Electrical Description

Electrical Description History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced

More information

HVR. Lead Wire Length (H, mm)

HVR. Lead Wire Length (H, mm) High Resistor Features Special conductive film withstands high voltage d L H D working voltage far over that of generalpurpose resistors Suitable for applications such as TV s, high voltage power supply,

More information

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION February 2017 SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

More information

TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS

TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS INFORMATION ABOUT THE SAFE OPERATION OF VOLTAGE TRANSFORMERS OPERATION CONDITIONS FOR POTENTIAL TRANSFORMERS 1. When

More information

POWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

POWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E POWER TRANSFORMER Failure Analysis & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Electricity is high-grade energy. Working

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY) E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

Introduction. Centrado leading-edge transformer. Introduction

Introduction. Centrado leading-edge transformer. Introduction Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

TRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting

TRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting TRANSFORMER OPERATIONAL Principles, Selection & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Power and distribution transformers

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

EE059: Transformer Operation, Maintenance, Diagnosis & Testing

EE059: Transformer Operation, Maintenance, Diagnosis & Testing EE059: Transformer Operation, Maintenance, Diagnosis & Testing EE059 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: Power and distribution transformers are essential devices in electricity

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established

More information

INTERPLANT STANDARD - STEEL INDUSTRY CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS

INTERPLANT STANDARD - STEEL INDUSTRY CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS INTERPLANT STANDARD - STEEL INDUSTRY IPSS CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS Corresponding IS does not exist IPSS:1-04-035-08 0. FOREWORD 0.1 This Inter

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Technical guide. Type VRLTC load tap changer

Technical guide. Type VRLTC load tap changer Technical guide Type VRLTC load tap changer Table of contents General information... 2 Electrical characteristics... 3 Type tests... 4 Switching sequence... 5 Tank characteristics... 7 Terminal board...

More information

HOW TO SAFE GUARD THE TRANSFORMER..???

HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various

More information

TECHNICAL DESCRIPTION ND-387. THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1

TECHNICAL DESCRIPTION ND-387. THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1 HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. December 2017 TECHNICAL DESCRIPTION ND-387 THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1 I. SCOPE The scope of the present description

More information

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published

More information

Regional Technical Seminar

Regional Technical Seminar Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979

More information

Hands-On Transformer Testing and Maintenance

Hands-On Transformer Testing and Maintenance Hands-On Course Description This Hands-On course will teach you how to prioritize your transformer maintenance strategy, stretch your maintenance budget and at the same time maximize the life and condition

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

Technical guide. Type VRLTC load tap changer

Technical guide. Type VRLTC load tap changer Technical guide Type VRLTC load tap changer Table of contents 2 General information 4 Switching sequences 6 Tank characteristics 6 Terminal board 7 Tap selector 7 Stationary contacts 7 Reversing switch

More information

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT SPECIFICATION SS-25 / 14 POWER TRANSFORMERS 150/15.75-21kV, 40/50 MVA WITH AUTOMATIC LOAD-RATIO CONTROL CONNECTION

More information

Load Tap Changers for Power Transformers

Load Tap Changers for Power Transformers Load Tap Changers for Power Transformers Dr. Dieter Dohnal / Maschinenfabrik Reinhausen GmbH Dipl. Ing. Bernhard Kurth / Reinhausen Manufacturing Inc. Load Tap Changers for Power Transformers Content Basic

More information

TEST REPORT. Table Of Contents

TEST REPORT. Table Of Contents Table Of Contents Page 2 of 15 Voltage Ratio...3 Winding Resistance...4 No Load Losses...5 Load Losses...6 Efficiency...7 Regulation...8 Applied Voltage...9 Induced Voltage... 10 Insulation Resistance...

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1 Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

Phase Shifter Application Workshop. Siemens Energy, Inc.

Phase Shifter Application Workshop. Siemens Energy, Inc. Phase Shifter Application Workshop Siemens Energy, Inc. PJM Power Pool, March, 2015 siemens.com/energy Phase Shifter Application Workshop Phase Shifting Transformers Principles, Design Aspects and Operation

More information

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...

More information

ABB Power Technologies

ABB Power Technologies ABB Power Technologies Info. No. 1ZSC000498-AAN en From/Date Order data sheet explanations for tap-changer type UZ Scope This product information gives some more explanations to the order data sheet for

More information

Magnetization System of Magnetically Controlled Shunt Reactors

Magnetization System of Magnetically Controlled Shunt Reactors Magnetization System of Magnetically Controlled Shunt Reactors Leonid Kontorovych, Technical Director of ZTR PJSC, PH.D. in Engineering Sciences; Igor Shyrokov, head of the department of reactors control

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

Transformer condition assessment with an integrated test van

Transformer condition assessment with an integrated test van Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

CAST RESIN DRY TRANSFORMER

CAST RESIN DRY TRANSFORMER CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,

More information

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

High-Voltage Capacitive Compensation Unit for Transformer and Shunt Reactor Testing, Type HVCC

High-Voltage Capacitive Compensation Unit for Transformer and Shunt Reactor Testing, Type HVCC HIGHVOLT Prüftechnik Dresden GmbH Marie-Curie-Straße 1 1139 Dresden, Germany Phone +49 351 8425-7 Fax +49 351 8425-679 E-mail sales@highvolt.de Website www.highvolt.de Data Sheet 8.81-1/1 High-Voltage

More information

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60214-2 First edition 2004-10 Tap-changers Part 2: Application guide Reference number IEC 60214-2:2004(E) Publication numbering As from 1 January 1997 all IEC publications are

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

SECTION VI TECHNICAL SCHEDULES

SECTION VI TECHNICAL SCHEDULES SECTION VI TECHNICAL SCHEDULES Kenya Power and Lighting Company VI 4.3 - i Contract A36B TECHNICAL SCHEDULES 1 PREAMBLE...1 TECHNICAL SCHEDULES SUBSTATIONS...2 SCHEDULE VI-1a TECHNICAL GUARANTEES, OUTDOOR

More information

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s Designed for Partial Discharge Analyzers (PDA s) monitoring rotating machinery or other medium-voltage equipment from 1 to 35 kvac RMS at power-line frequencies of 10 Hz to 1 khz, Mica Capacitor Type 297

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

Transformer differential protection

Transformer differential protection Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or

More information

Efacec work every day to anticipate solutions for a sustainable world in the new energy era.

Efacec work every day to anticipate solutions for a sustainable world in the new energy era. Transformers Efacec is the largest industrial portuguese company of the electric and electromechanical sector developing high technology products, solutions and systems used every day by millions of people

More information

TRAFO ELECTRIC P. LTD.

TRAFO ELECTRIC P. LTD. TRAFO ELECTRIC P. LTD. About Us Trafo Electric P. Ltd. started manufacturing Power & Distribution Transformers in 1974. Originally known as J B Electricals, the unit s entire production was for BSES( Bombay

More information

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description: OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description: VTOP 2(1) X Dry Insulated voltage transformer (VT) There are two designs of this voltage transformers: - VTOP 1-X single phase, dry insulated

More information

MODERN POWER TRANSFORMER PRACTICE BIBLIOGRAPHY

MODERN POWER TRANSFORMER PRACTICE BIBLIOGRAPHY 354 BIBLIOGRAPHY MODERN POWER TRANSFORMER PRACTICE Bolton, D. J., Electrical Engineering Economics, Chapman and Hall, London, 2nd edn (1936) Brownsey, C. M., 'The Problem of Noise with Particular Reference

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses Main characteristics Recognized 650 to 300VAC / 63 to 2800A. Exceptionally low I 2 T, Watt losses. Non-magnetic construction, highly reliable low voltage. Indicator system. Conformity to UL, CSA investigated,

More information

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc. Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

SPAE 010, 011 High Impedance Protection Relay

SPAE 010, 011 High Impedance Protection Relay SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n

More information

Insulation Level and Test Technology of. 1000kV Power Transformer

Insulation Level and Test Technology of. 1000kV Power Transformer Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC

More information

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2 Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II

More information

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

Three-Phase Transformer Test Systems

Three-Phase Transformer Test Systems Three-Phase Transformer Test Systems PHENIX TECHNOLOGIES R Testing Applications Models Available Perform tests on utility distribution and power transformers in accordance with IEC 60076 and ANSI / IEEE

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

Metal Film Precision Resistor. Features

Metal Film Precision Resistor. Features Features -Excellent overall stability -Tight tolerance down to ±0.1% -Extremely low TCR down to ±10 PPM/ C -High power rating up to 1 Watts Applications -Telecommunication -Medical Equipment Construction

More information

Metal Film Precision Resistor. Features

Metal Film Precision Resistor. Features Features -Excellent overall stability -Tight tolerance down to ±0.1% -Extremely low TCR down to ±10 PPM/ C -High power rating up to 1 Watts Applications -Telecommunication -Medical Equipment Construction

More information