DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO
|
|
- Rudolf Parsons
- 6 years ago
- Views:
Transcription
1 PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 % 4 MAX. RAINFALL PER DAY 5 LOCATION OF INSTALLATION INDOOR 6 SITE ENVIRONMENT TROPICALIZED, MARINE, WITH PRESENCE OF CORROSIVE FUMES B SYSTEM PARTICULARS 1 PRIMARY SYSTEM LIGHTING - DRY TYPE 1.1 VOLTAGE kv ± 10% 1.2 FREQUENCY 50 Hz ± 5 % 1.3 COMBINED VOLTAGE & FREQUENCY ± 10 % VARIATION 1.4 NO. OF PHASES / WIRE 3 PHASE / 3 WIRE 1.5 SYSTEM GROUNDING Solidly Grounded 1.6 FAULT LEVEL 50 ka 3 PH SYMM 2 SECONDARY SYSTEM 2.1 VOLTAGE kv 2.2 NO. OF PHASES / WIRE 3 PHASE / 4 WIRE 2.3 SYSTEM GROUNDING SOLIDLY GROUNDED C TECHNICAL PARTICULARS 1 RATING * 2 NO. OF PHASES THREE 3 NO LOAD VOLTAGE RATIO : / kv PRIMARY/SECONDARY /ANY 4 VECTOR GROUP Dyn11 5 % IMPEDANCE : * 6 TYPE OF COOLING ANAN X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 1 OF 8
2 PART - A : SPECIFIC REQUIREMENTS ( CONTD...) C TECHNICAL PARTICULARS ( CONTD..) 7 INSULATION LEVEL a ) FOR IMPULSE TEST (KVP) b ) FOR POWER FREQUENCY HV : - KV, LV : - KV HV : 3 KV, LV : 3 KV WITHSTAND (RMS) 8 TEMPERATURE RISE : a ) WINDING 90 C ABOVE AMBINET TEMPERATURE OF 45 C b ) OIL NOT APPLICABLE 9 ADDITIONAL OUTDOOR BUSHING FOR NEUTRAL EARTHING : a ) FOR PRIMARY b ) FOR SECONDARY c ) EARTH CONDUCTOR SIZE NOT REQUIRED REQUIRED 75 X 10 G.I EARTH STRIP 10 TAP CHANGER : HV SIDE OFF LOAD 11 RANGE OF TAPS / STEPS : +/- 2.5 % IN STEPS OF 2.5 % 12 ON LOAD TAP CHANGER : AUTO & MANUAL NOT APPLICABLE 13 PROTECTIVE BUSHING CT'S : 13.1 HV. SIDE : RATIO : NA ACCURACY CLASS : NA BURDEN : NA 13.2 LV. SIDE : RATIO : NA ACCURACY CLASS : NA BURDEN : NA 13.3 NEUTRAL SIDE: RATIO : NA ACCURACY CLASS : NA BURDEN : NA 14 MOUNTING OF CT's HV. SIDE : NA LV. SIDE : NA NEUTRAL : NA D CONSTRUCTION 1 TERMINAL BOX ARRANGEMENT ; HV & LV OPPOSITE 2 PRIMARY TERMINAL TYPE CABLE BOX WITH DISCONNECTING CHAMBER 2.1 CABLE / CONDUCTOR SIZE : * 3 SECONDARY TERMINAL TYPE CABLE BOX WITH DISCONNECTING CHAMBER FOR 3.1 CABLE / CONDUCTOR / BUS BAR SIZE : * 4 RADIATORS NA 5 PAINTING : EPOXY PAINT SHADE NO. 632 AS PER IS : 5 6 FITTINGS & ACCESSORIES AS PER STD. SPECIFICATION. :44LK5100ESS-04 X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 2 OF 8
3 7 BIDIRECTIONAL RAILWHEEL / ROLLER RAIL WHEEL E PERFORMANCE PARTICULARS AS SPECIFIED ELSEWHERE IN FEED DOCUMENT F DRAWING, DATA & TEST AS SPECIFIED ELSEWHERE IN FEED DOCUMENT CERTIICATES G INSPECTION & TESTING AS PER INSPECTION TEST PLAN ATTACHED ELSEWHERE. H NOTES & ADDITIONAL REQUIREMENTS: 1) INSULATION SHALL BE CLASS H WITH TEMPERATURE RISE LIMITED TO CLASS F. * - BOILER VENDOR TO SPECIFY X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 3 OF 8
4 PART - B : PERFORMANCE PARTICULARS. THE PARTICULARS MARKED WITH ASTERISK ( * ) SHALL BE GUARANTEED, SUBJECT TO THE TOLERANCE SPECIFIED IN IS REF. 44LK5100ESS 004 UNIT 1 NAME OF THE MANUFACTURER. 2 TRANSFORMER DESIGNATION 3 QUANTITY NOS. 4 INSTALLATION 5 RATED KVA AS PER IS KVA 6 CONTINUOUS MAXIMUM RATING FOR SITE CONDITIONS SPECIFIED IN PART - A KVA 7 ( * ) NO LOAD VOLTAGE RATIO 8 VECTOR GROUP REFERENCE 9 ( * ) NO LOAD LOSSES AT RATED VOLTAGE * KW 10 ( * ) LOAD LOSSES AT RATED CURRENT, 75 C * KW 11 RESISTANCE VOLTAGE (AT RATED KVA,75 C & 50 Hz) % 12 REACTANCE VOLTAGE (AT RATED KVA,75 C & 50 Hz) % 13 ( * ) IMPEDANCE VOLTAGE ( AT RATED KVA, 75 C & 50 Hz. ) * % 14 RESISTANCE OF WINDINGS, AT 75 C a ) H.V. PER PHASE b ) L.V. PER PHASE OHMS OHMS 15 WINDING INSULATION 16 ZERO PHASE SEQUENCE IMPEDANCE ( ESTIMATED ) % 17 EFFICIENCY ( AT 75 C ) AT FULL LOAD a ) 1.0 P.F % b ) 0.8 P.F. (LAG) % 18 EFFICIENCY ( AT 75 C ) AT 75 % OF FULL LOAD a ) 1.0 P.F % b ) 0.8 P.F. (LAG) % 19 EFFICIENCY ( AT 75 C ) AT 50 % OF FULL LOAD a ) 1.0 P.F % b ) 0.8 P.F. (LAG) % 20 LOAD AT WHICH MAX. EFFICIENCY SHALL OCCUR % FULL LOAD 21 MAXIMUM EFFICIENCY : % X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 4 OF 8
5 PART - B : PERFORMANCE PARTICULARS. ( CONTD... ) 22 PERCENTAGE REGULATION AT FULL LOAD : a ) 1.0 P.F. % b ) 0.8 P.F. ( LAG ) % 23 EXCITING CURRENT REFERRED TO PRIMARY, 50 Hz. : a ) 90 % RATED VOLTAGE b ) 100 % RATED VOLTAGE ( NO LOAD CURRENT ) c ) 110 % RATED VOLTAGE AMPS. AMPS. AMPS. 24 POWER FACTOR OF EXCITING CURRENT AT RATED VOLTAGE AND 50 Hz. : 25 TAPPING ON H.V. WINDING a) TYPE OF TAP CHANGER b) TAPPING RANGE WITH STEPS 26 TERMINAL CONNECTION a) TERMINAL BOX ARRANGEMENT ; HV & LV b) PRIMARY TERMINAL TYPE c) CABLE / CONDUCTOR SIZE : d) SECONDARY TERMINAL TYPE e) CABLE / CONDUCTOR / BUS BAR SIZE : f) BUS DUCT TAKE OFF 27 RADIATORS 28 TERMINAL BUSHINGS a) VOLTAGE CLASS b) RATED CURRENT c) IMPULSE WITHSTAND VOLTAGE d) POWER FREQUENCY WITHSTAND VOLTAGE e) CLAREANCE IN AIR f) PHASE TO PHASE g) PHASE TO EARTH h) MINIMUM CREEPAGE/ PROTECTIVE CREEPAGE DISTANCE 29 BUSHING CTs REQUIRED 30 DRY TYPE, CAST RESIN CTs LOATED IN CABLE BOX REQUIRED 31 CT DETAILS a) NUMBER OF CTs REQUIRED b) APPLICATION OF CTs c) NUMBER OF CORES e) CT RATIO f) CLASS OF ACCURACY g) BURDEN h) PARAMETERS FOR Vk, Imag, Rct AND Vct AS PER DATA SHEET X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 5 OF 8
6 PART - B : PERFORMANCE PARTICULARS. ( CONTD... ) 32 MAGNETISING INRUSH CURRENT ( PEAK ) UNDER WORSE CONDITIONS OF RESIDUAL MAGNETISM & INSTANT OF SWITCHING : KA. 33 SYMMETRICAL SHORT-CIRCUIT CURRENT (ASSUME INFINITE SOURCE ) : KA. 34 TIME OF WITHSTAND WITHOUT INJURY UNDER MAX. SYMM. SHORT CIRCUIT CONDITION : SECS. 35 THERMAL TIME CONSTANT : HRS. 36 MAX. FLUX DENSITY IN CORE AT RATED K.LINES / VOLTAGE : CM ² 37 CURRENT DENSITY AT RATED LOAD : a ) H.V. WINDING A / MM ² b ) L.V. WINDING A / MM ² 38 TYPE OF WINDING : HIGH VOLTAGE : LOW VOLTAGE : 39 MATERIAL FOR WINDING 40 INSULATION CLASS 41 IMPULSE LEVELS WITH 1.2/50 MICRO-SECOND WAVE FORM : a ) HIGH VOLTAGE. b ) LOW VOLTAGE. KV. KV. 42 POWER FREQUENCY WITHSTAND VOLTAGE a ) HIGH VOLTAGE. b ) LOW VOLTAGE. KV. KV. 43 TYPE OF COOLING. 44 MAXIMUM TEMPERATURE RISE ABOVE AMBIENT TEMP TOP OIL BY THERMOMETER a) FOR ONAN TYPE COOLING b) FOR ONAF TYPE COOLING c) FOR ONWF TYPE COOLING d) FOR OFWF TYPE COOLING 44.2 WINDING BY RESISTANCE METHOD a) FOR ONAN TYPE COOLING b) FOR ONAF TYPE COOLING c) FOR ONWF TYPE COOLING d) FOR OFWF TYPE COOLING 45 COOLING FANS a) NUMBER OF FANS REQUIRED b) RATING OF EACH FAN c) MIN NUMBER OF FANS TO BE IN OPERATION AT FULL LOAD d) WINDING TEMPERATURE AT WHICH FORCED COOLING IS INITIATED X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 6 OF 8
7 PART - B : PERFORMANCE PARTICULARS. ( CONTD... ) e) TRANSFORMER DERATING FACTOR AFTER FAILURE OF - ONE COOLING FAN - TWO COOLING FANS - ALL COOLING FANS 46 TOTAL WEIGHT WITH OIL & ACCESSORIES. KG. 47 VOLUME OF OIL FOR COMPLETE FILLING LITRES 48 APPROXIMATE OVERALL DIMENSIONS ( L x W x H ) MM. 49 SIZE ( L x W x H ) & WT. OF LARGEST SHIPPING SECTION MM. & KG 51 CLERANCE a) MINIMUM CLERANCE HEIGHT FOR LIFTING CORE AND MM WINDING FROM TANK b) FREE SPACE REQUIRED AT THE TOP FOR REMOVAL MM OF ACCESSORIES INCLUDING BUSHING 52 WHEELS a) PLAIN ROLLERS / FLANGED WHEELS b) MOVEMENT UNIDIRECTIONAL / BIDIRECTIONAL c) GUAGE d) QUANTITY 53 ENCLOSURE FOR MARSHALLING BOX, COOLING CONTROL CABINET, OLTC PANEL ETC 54 VACUUM WITHSTAND CAPABILITY a) MAIN TANK b) RADIATORS 55 DETAILS OF FITTINGS & ACCESSORIES. a) RATING & DIAGRAM PLATE PROVIDED / NOT PROVIDED / NOT APPLICABLE b) DIAL TYPE MAGNETIC OIL LEVEL GUAGE WITH LOW PROVIDED / NOT PROVIDED / NOT APPLICABLE LEVEL ALARM CONTACTS C) SILICA GEL BREATHER WITH A SEAL & CONNECTING PROVIDED / NOT PROVIDED / NOT APPLICABLE PIPE, IN A TRANSPARENT ENCLOSURE d) CONSERVATOR WITH FILLING HOLE, CAP AND DRAIN PROVIDED / NOT PROVIDED / NOT APPLICABLE VALVE & ISOLATING VALVE FOR CONSERVATOR e) EXPLOSION VENT WITH DIAPHRAGM EQUILISING PIPE PROVIDED / NOT PROVIDED / NOT APPLICABLE f) PLAIN OIL LEVEL INDICATOR WITH MINIMUM MARKING PROVIDED / NOT PROVIDED / NOT APPLICABLE g) DOUBLE FLOAT BUCHHOLZ RELAY PROVIDED / NOT PROVIDED / NOT APPLICABLE h) DIAL TYPE THERMOMETER FOR OIL TEMPERATURE PROVIDED / NOT PROVIDED / NOT APPLICABLE WITH ALARM AND TRIP CONTACTS i) MARSHALLING BOX PROVIDED / NOT PROVIDED / NOT APPLICABLE j) OIL SAMPLING VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE k) TOP OIL FILTER VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE l) BOTTOM FILTER VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE m) DRAIN VALVE WITH PLUG PROVIDED / NOT PROVIDED / NOT APPLICABLE n) PRESSURE RELEIF VALVE PROVIDED / NOT PROVIDED / NOT APPLICABLE p) INSPECTION COVER PROVIDED / NOT PROVIDED / NOT APPLICABLE q) THERMOMETER POCKET (FOR TOP OIL TEMP) PROVIDED / NOT PROVIDED / NOT APPLICABLE X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 7 OF 8
8 PART - B : PERFORMANCE PARTICULARS. ( CONTD... ) r) BI DIRECTIONAL ROLLERS PROVIDED / NOT PROVIDED / NOT APPLICABLE s) DRAW EYES PROVIDED / NOT PROVIDED / NOT APPLICABLE t) LIFTING LUGS PROVIDED / NOT PROVIDED / NOT APPLICABLE u) JACKING PADS PROVIDED / NOT PROVIDED / NOT APPLICABLE w) AIR RELEASE VENT PROVIDED / NOT PROVIDED / NOT APPLICABLE x) TWO EARTHING TERMINALS PROVIDED / NOT PROVIDED / NOT APPLICABLE y) IMAGE COIL CT FOR WINDING TEMP WITH DIAL TYPE PROVIDED / NOT PROVIDED / NOT APPLICABLE THERMOMETER I NOTES & ADDITIONAL REQUIREMENTS 1) DRY TYPE TRANSFORMERS SHALL BE PROVIDED WITH CLASS H INSULATION WITH TEMPERATURE RISE LIMITED TO CLASS F. X:\STD\FORMS\E04-004A_Rev0 REV. 0 PAGE : 8 OF 8
TECHNICAL SPECIFICATION FOR POWER TRANSFORMER
TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL
More informationsave energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers
save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED
More informationProlific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2
Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationPRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS
PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer
More informationPUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT
PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT SPECIFICATION SS-25 / 14 POWER TRANSFORMERS 150/15.75-21kV, 40/50 MVA WITH AUTOMATIC LOAD-RATIO CONTROL CONNECTION
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules
More informationIntroduction. Centrado leading-edge transformer. Introduction
Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationPURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS
PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More informationSOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)
E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationCOMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS
006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationDISTRIBUTION TRANSFORMER 11 / kv
Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The
More informationSPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.
SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. 1. SCOPE: This specification covers design, manufacture, testing and supply of 6.64/10.12 KV 24/15.7, 30/19.7
More informationSECTION VI TECHNICAL SCHEDULES
SECTION VI TECHNICAL SCHEDULES Kenya Power and Lighting Company VI 4.3 - i Contract A36B TECHNICAL SCHEDULES 1 PREAMBLE...1 TECHNICAL SCHEDULES SUBSTATIONS...2 SCHEDULE VI-1a TECHNICAL GUARANTEES, OUTDOOR
More information51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without
More information51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS
SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationEARTHING TRANSFORMER
EARTHING TRANSFORMER December 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationAPDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL
PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationArild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems
Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -
More informationDISTRIBUTION TRANSFORMERS
DISTRIBUTION TRANSFORMERS OIL IMMERSED up to 6 MVA www.alfanar.com Contents 1 - General Information 4 2 - Applications 10 3 - Product Portfolio 11 4 - Product Breakdown 12 5 - Transformer Classifications
More informationDISTRIBUTION TRANSFORMER kv
ELECTRICITY COMMISSION PLANNING AND STUDY DEP BAGHDAD, REPUBLIC OF IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER kv REVISION YEAR 2001 DISTRIBUTION TRANSFORMERS 1- SCOPE OF THE TENDER : Tenderer
More informationGE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class
GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial
More informationWESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)
WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices
More informationTECHNICAL DESCRIPTION ND-387. THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. December 2017 TECHNICAL DESCRIPTION ND-387 THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1 I. SCOPE The scope of the present description
More informationElectrical Description
History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced
More informationGeneral Electricity Company of Libya
GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company
More informationUBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS
More informationOIL-IMMERSED ARC-SUPPRESSION COILS
ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department
More informationMechanical Design. Brian Brinson Mechanical Design Manager.
Mechanical Design Brian Brinson Mechanical Design Manager brian.brinson@spx.com September 26, 2018 Agenda 1. Design Process 2. Pre-Approval Drawings Bid Drawings Preliminary Drawings 3. Approval Package
More informationMGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide
MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888
More informationPomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations
More informationIndustrial Applications
Industrial Applications Transformers for Industrial Applications Tamini has always produced industrial transformers of high quality and reliability, designed to satisfy the most diverse and complex technical
More informationTMC Transformers TMC
TMC Product & Technology Presentation Cast Resin Transformer (CRT) History Cast resin transformers first appeared in Germany during the 1960s. This new style of dry type transformer was developed with
More informationCOMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3
CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationSECTION TRANSFORMERS
SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section
More information50-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------
More informationNEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :
NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE
More informationDistribution and Power Transformers
Distribution and Power Transformers The data provided in this document is accurate at time of going to press. As standards, specifications and designs are subject to change, please ask for confirmation
More informationCompany Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers
Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5 Relating to 11kV Distribution Transformers Policy Summary This specification covers the requirements for Distribution Transformers from 16kVA single
More informationTitle: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric
More informationSPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION February 2017 SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER
More informationPOTENTIAL TRANSFORMER
POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More informationCast resin transformers HARMONY TM
Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety
More informationOn-Load Tap Changer Type M
On-Load Tap Changer Type M OLTC type model M III 500 Y, U m = 123 Kv, 500A, ± 9 steps The type M On Load tap changers are used to vary the ratio of oil-immersed transformers under load.in general they
More informationTransformers Contents Page
Transformers Contents Page Introduction... / Product Range... / Electrical Design... / Transformer Loss Evaluation... / Mechanical Design... / Connection Systems... / Accessories and Protective Devices...
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationArc Suppression Coils
Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty
More informationNo. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS
College of Agriculture, Maharana Pratap University of Agriculture & Technology, Bhilwara-311001 (Rajasthan) Phone: 01482-246118 (O), Email: coabhilwara@gmail.com, No. COA/BHL/2018/293 Dated: 07.06.2018
More informationTransformer Fault Categories
Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)
More informationWorking Group Members
POWER TRANSFORMER - STANDARDISATION MANUAL 6 Chapter - 7 Design Review Working Group Members Mr. M. Vijayakumaran ALSTOM Ltd Mr. S. K. Negi Mr. Y. V. Joshi GETCO GETCO 6 POWER TRANSFORMER - STANDARDISATION
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationBasic principles and operation of a transformer
Basic principles and operation of a transformer Seminar paper for course Distribution and industrial networks Andrea Ljubljanac Mentor: professor Grega Bizjak Ljubljana, March 2018 TABLE OF CONTENTS 1
More informationOil-immersed Transformers
Oil-immersed Transformers Manual for Installation, Operation and Maintenance UNITRAFO Electric AB, Askims Industriväg 1A, 436 34 Askim, tel +46-31-68 56 20, fax +46-31-68 58 11 ENGLISH 1 / 13 ENGLISH Technical
More informationPS REV NO: 01 PAGE : 2 OF 22
PAGE : 2 OF 22 1.0 INTRODUCTION Bharat Heavy Electricals Limited (BHEL), Electronics Division, Bangalore is setting up a 10 MW Solar PV Grid-connected power plant for its customer BEL at O.F.BOL, Badmal,
More informationSECTION : 8.0. Guaranteed Technical Particulars
SECTION : 8.0 Guaranteed Technical of "Design, Supply, Erection, Installation, Testing and Commissioning 33/11KV AIS Substation on Turnkey Basis Under Power Distribution System Development Project, Rajshahi
More informationThe NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:
Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More information1 SCOPE & INTENT OF SPECIFICATION
1 SCOPE & INTENT OF SPECIFICATION Welspun Solar UP Private Limited. is setting up a 5 MW Solar PV Power Plant in state of Rajasthan at Village Deh, Tehsil Kolayat, District Bikaner 4.5MVA Inverter Transformer
More informationReport on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)
Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated
More informationSCHEDULE-VII TECHNICAL SPECIFICATIONS. Specification No
SCHEDULE-VII TECHNICAL SPECIFICATIONS Specification No. 01410116 11KV/415V, 400 kva, 630 kva, 1000 kva and 1600 kva, SINGLE RATIO, ONAN TYPE DISTRIBUTION TRANSFORMERS Notice for revision of specification
More informationSPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers
SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.
More information500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor
500 kva Dry-type Isolation Transformer - 13200V-Delta to 208Y/120V 3PH - NEMA 1/Indoor Part #: MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Page: 1 The MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Dry-type Isolation
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationMODERN POWER TRANSFORMER PRACTICE BIBLIOGRAPHY
354 BIBLIOGRAPHY MODERN POWER TRANSFORMER PRACTICE Bolton, D. J., Electrical Engineering Economics, Chapman and Hall, London, 2nd edn (1936) Brownsey, C. M., 'The Problem of Noise with Particular Reference
More informationEE059: Transformer Operation, Maintenance, Diagnosis & Testing
EE059: Transformer Operation, Maintenance, Diagnosis & Testing EE059 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: Power and distribution transformers are essential devices in electricity
More informationNeutral Earthing. For permanent or temporary neutral earthing in HV systems
Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection
More informationK Factor Power Transformers
Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business
More informationOUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:
OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description: VTOP 2(1) X Dry Insulated voltage transformer (VT) There are two designs of this voltage transformers: - VTOP 1-X single phase, dry insulated
More informationTechnical Specifications
Page 1 of 14 INSTITUTE FOR PLASMA RESEARCH Technical Specifications Design/engineering, manufacture, inspection, testing at vendor s site, delivery at site of resin cast dry type Cast Resin Transformer
More informationSYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR
SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY () SPECIFICATIONS FOR 20/0.4 KV DISTRIBUTION TRANSFORMER OPEN TERMINAL BUSHINGS AND HERMETICALLY SEALED
More informationMESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationLiquid-Filled Transformers
Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of
More informationTECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This
More informationELETTROMECCANICA. Since english OIL IMMERSED DISTRIBUTION TRANSFORMERS
ELETTROMECCANICA P I O S S A S C O Since 1962 english OIL IMMERSED DISTRIBUTION TRANSFORMERS ELETTROMECCANICA PIOSSASCO was created from the transformation of Elettromeccanica Luparia established in the
More informationMaharashtra State Electricity Distribution Co. Ltd.
Maharashtra State Electricity Distribution Co. Ltd. SPEC. NO. STORES:MSC-II/ conventional power Trf/ 2011 SPECIFICATION FOR 5 MVA and 10 MVA 33/11 kv, 33/22 kv & 22/11 kv POWER TRANSFORMERS FOR VARIOUS
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationCommissioning Manual Distribution Transformers - Three-phase Oil Filled
1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...
More informationSingle-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL
Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with
More information(
(www.xatianhong.com) Introduction to XATH Xi'an Tianhong Electric Co., Ltd. (XATH) is a solely state-owned enterprise, set up by China Shipbuilding Industry Corporation (CSIC). It is one of the largest
More informationOIL TRANSFORMER HV/LV
Rev.02 - Pag. 1/23 Installation, use and maintenance Manual OIL TRANSFORMER Rev.02 - Pag. 2/23 TABLE OF CONTENTS 1 INTRODUCTION... 4 1.1 Reference standard... 4 1.2 Electromagnetic compatibility... 4 1.3
More informationCEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant
CEYLON ELECTRICITY BOARD SRI LANKA GREEN POWER DEVELOPMENT AND ENERGY EFFICIENCY IMPROVEMENT INVESTMENT PROGRAMME (TRANCHE 2) PACKAGE 2: LOT A MANNAR NADUKUDA TRANSMISSION DEVELOPMENT (ADB LOAN NO: 47037-SRI)
More informationPower Transformers. TS of Power Transformer 1 1 SCOPE
1 Power Transformers 1 SCOPE 1.1 This Specification provides for design, engineering, manufacture, assembly, stage inspection, final inspection and testing before dispatch, packing and delivery at destination
More informationPROBLEMS on Transformers
PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary
More informationTECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C
TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil
More informationCompact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED
Dial : (033)2677-5835 & 2667-8358 Tele Fax : (033)2667-8358 Manufacturer of Dry Type Transformers E-mail : unimag111@gmail.com Office & Factory : 26/5, Sarat Chatterjee Road, Howrah 711 104, West Bengal,
More information