Railway application RER670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES

Size: px
Start display at page:

Download "Railway application RER670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES"

Transcription

1 Railway application RER670 Version 2.2 IEC R E L I O N 670 SERIES

2

3 Document ID: 1MRK TEN Issued: June 2018 Revision: D Product version: 2.2 Copyright 2017 ABB. All rights reserved

4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license. This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit. ( This product includes cryptographic software written/developed by: Eric Young (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com). Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest ABB representative.

5 Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

6 Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Lowvoltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN for the EMC directive, and with the product standards EN and EN for the low voltage directive. The product is designed in accordance with the international standards of the IEC series.

7 Table of contents Table of contents Section 1 General...3 Definitions...3 Presumptions for Technical Data... 4 Section 2 Energizing quantities, rated values and limits... 5 Analog inputs...5 Auxiliary DC voltage... 7 Binary inputs and outputs... 7 Influencing factors Section 3 Type tests according to standards Section 4 Control...17 Section 5 Differential protection Section 6 Section 7 Impedance protection...25 Current protection...29 Section 8 Voltage protection Section 9 Frequency protection...45 Section 10 Secondary system supervision...47 Section 11 Scheme communication...51 Section 12 Logic...53 Section 13 Monitoring...55 Section 14 Metering Section 15 Station communication...65 Section 16 Remote communication...69 Section 17 Hardware...71 IED...71 Modules Electrical safety Connection system Section 18 Basic IED functions Railway application RER IEC 1

8 Table of contents Section 19 Inverse characteristics Railway application RER IEC

9 1MRK TEN D Section 1 General Section 1 General 1.1 Type test data GUID67C041E3DFD149E5B7C7C2FC1BBB777F v17 This document certifies that the product described below is in accordance with, and conforms to the data stated in this Type Test Certificate and corresponding data in the Product Guide. The product has been tested according to relevant parts of the standards stated below. Product/Type Product Guide User's Manuals Function Manufactured by Author/department Railway application IED Type RER670 v2.2 1MRK BEN 1MRK UEN 1MRK UEN 1MRK UEN 1MRK UEN 1MRK UEN Railway application ABB AB, Sweden Date of issue Approved by Standards Espen Mathisen TP/TD ABB AB Product Manager Joseph Menezes IEC 60255series, IEC 61000series, IEC 60068series, IEC 60529, IEC 60664, ANSI C37.90, ANSI C37.94, ANSI C37.99, ANSI C37.112, ANSI C63.4, SS , IEC 60870, IEC 60871, IEC 61588, IEC 61810, IEC 61850, IEEE C50.13, IEEE 421.3, ANSI C37.118, IEEE Definitions GUIDCA22C5BFEC6B4C96BEB4FBB68C63E0AF v1 Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment. Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements. Railway application RER IEC 3

10 Section 1 General 1MRK TEN D Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its intended functions according to the specified requirements. 1.3 Presumptions for Technical Data GUID1E949E38E04D4374A086912C25E9F93C v2 The technical data stated in this document are only valid under the following circumstances: 1. Main current transformers with 1 A or 2 A secondary rating are wired to the IED 1 A rated CT inputs. 2. Main current transformer with 5 A secondary rating are wired to the IED 5 A rated CT inputs. 3. CT and VT ratios in the IED are set in accordance with the associated main instrument transformers. 4. Parameter IBase used by the tested function is set equal to the rated CT primary current. 5. Parameter UBase used by the tested function is set equal to the rated primary phasetophase voltage. 6. Parameter SBase used by the tested function is set equal to: IBase UBase for 2Ph system. 7. The rated secondary quantities have the following values: Rated secondary phase current I r is either 1 A or 5 A depending on selected TRM. Rated secondary phasetophase voltage U r is within the range from 100 V to 120 V. Rated secondary power for twophase system S r = U r I r 8. For operate and reset time testing, the default setting values of the function are used if not explicitly stated otherwise. 9. During testing, signals with rated frequency have been injected if not explicitly stated otherwise. 4 Railway application RER IEC

11 1MRK TEN D Section 2 Energizing quantities, rated values and limits Section 2 Energizing quantities, rated values and limits IP v2 2.1 Analog inputs IP v1 M v11 Table 1: TRM Energizing quantities, rated values and limits for protection transformer (16.7 Hz) Description Frequency Rated frequency f r Value 16.7 Hz Operating range f r ± 10% Current inputs Rated current I r Operating range 1 or 5 A (030) x I r Thermal withstand 100 I r for 1 s *) 30 I r for 10 s 10 I r for 1 min 4 I r continuously Burden < 20 mva at I r = 1 A < 150 mva at I r = 5 A *) max. 350 A for 1 s when COMBITEST test switch is included. Voltage inputs **) Rated voltage U r Operating range Thermal withstand Burden 100 V V 300 V for 10 s 120 V continuously < 60 mva at 100 V **) all values for individual voltage inputs Note! All current and voltage data are specified as RMS values at rated frequency Railway application RER IEC 5

12 Section 2 Energizing quantities, rated values and limits 1MRK TEN D Table 2: TRM Energizing quantities, rated values and limits for protection transformer (50/60 Hz) Description Value Frequency Rated frequency f r 50 or 60 Hz Operating range f r ± 10% Current inputs Rated current I r Operating range 1 or 5 A (0100) x I r Thermal withstand 100 I r for 1 s *) 30 I r for 10 s 10 I r for 1 min 4 I r continuously Dynamic withstand Burden 250 I r one half wave < 20 mva at I r = 1 A < 150 mva at I r = 5 A *) max. 350 A for 1 s when COMBITEST test switch is included. Voltage inputs **) Rated voltage U r 110 or 220 V Operating range Thermal withstand Burden **) all values for individual voltage inputs V 450 V for 10 s 420 V continuously < 20 mva at 110 V < 80 mva at 220 V Note! All current and voltage data are specified as RMS values at rated frequency M63891 v5 Table 3: MIM ma input module Quantity: Rated value: Nominal range: Input resistance R in = 194 Ohm Input range Power consumption each ma board each ma input ±5, ±10, ±20 ma 05, 010, 020, 420 ma 2 W 0.1 W 6 Railway application RER IEC

13 1MRK TEN D Section 2 Energizing quantities, rated values and limits 2.2 Auxiliary DC voltage IP v3 M v9 Table 4: PSM Power supply module Quantity Rated value Nominal range Auxiliary DC voltage, EL (input) EL = (2460) V EL = (90250) V Power consumption 50 W typically Auxiliary DC power inrush < 10 A during 0.1 s Supply interruption bridging time < 50 ms EL ±20% EL ±20% 2.3 Binary inputs and outputs IP v1 M v8 Table 5: BIM Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs 16 DC voltage, RL Power consumption 24/30 V 48/60 V 110/125 V 220/250 V 24/30 V 48/60 V 110/125 V 220/250 V max W/input max. 0.1 W/input max. 0.2 W/input max. 0.4 W/input Counter input frequency 10 pulses/s max Balanced counter input frequency 40 pulses/s max Oscillating signal discriminator Debounce filter Binary input operate time (Debounce filter set to 0 ms) Blocking settable 1 40 Hz Release settable 1 30 Hz Settable 120 ms 3 ms RL ±20% RL ±20% RL ±20% RL ±20% Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. The stated operate time for functions include the operating time for the binary inputs and outputs. Railway application RER IEC 7

14 Section 2 Energizing quantities, rated values and limits 1MRK TEN D M v10 Table 6: IOM Binary input/output module Quantity Rated value Nominal range Binary inputs 8 DC voltage, RL Power consumption 24/30 V, 50 ma 48/60 V, 50 ma 110/125 V, 50 ma 220/250 V, 50 ma 220/250 V, 110 ma Counter input frequency Oscillating signal discriminator Debounce filter Binary input operate time (Debounce filter set to 0 ms) 24/30 V 48/60 V 110/125 V 220/250 V max W/input max. 0.1 W/input max. 0.2 W/input max. 0.4 W/input max. 0.5 W/input 10 pulses/s max Blocking settable 140 Hz Release settable 130 Hz Settable 120 ms 3 ms RL ±20% RL ±20% RL ±20% RL ±20% Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. The stated operate time for functions include the operating time for the binary inputs and outputs. M v9 Table 7: IOM Binary input/output module contact data (reference standard: IEC ) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs 10 2 Max system voltage 250 V AC, DC 250 V DC Test voltage across open contact, 1 min Current carrying capacity Per relay, continuous Per relay, 1 s Per process connector pin, continuous Making capacity at inductive load with L/R > 10 ms 1000 V rms 800 V DC 8 A 10 A 12 A 8 A 10 A 12 A 0.2 s 1.0 s Table continues on next page 30 A 10 A 0.4 A 0.4 A 8 Railway application RER IEC

15 1MRK TEN D Section 2 Energizing quantities, rated values and limits Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Making capacity at resistive load 0.2 s 1.0 s 30 A 10 A V/0.4 A V/0.4 A V/0.2 A V/0.1 A Breaking capacity for AC, cos φ > V/8.0 A 250 V/8.0 A Breaking capacity for DC with L/R < 40 ms 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A Maximum capacitive load 10 nf Operating time < 6 ms <= 1 ms Maximum 72 outputs may be activated simultaneously with influencing factors within nominal range. After 6 ms an additional 24 outputs may be activated. The activation time for the 96 outputs must not exceed 200 ms. 48 outputs can be activated during 1 s. Continued activation is possible with respect to current consumption but after 5 minutes the temperature rise will adversely affect the hardware life. Maximum two relays per BOM/IOM/SOM should be activated continuously due to power dissipation. The stated operate time for functions include the operating time for the binary inputs and outputs. M v9 Table 8: IOM with MOV and IOM 220/250 V, 110mA contact data (reference standard: IEC ) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs IOM: 10 IOM: 2 Max system voltage 250 V AC, DC 250 V DC Test voltage across open contact, 1 min 250 V rms 250 V rms Current carrying capacity Per relay, continuous Per relay, 1 s Per process connector pin, continuous Making capacity at inductive loadwith L/R > 10 ms 0.2 s 1.0 s Table continues on next page 8 A 10 A 12 A 30 A 10 A 8 A 10 A 12 A 0.4 A 0.4 A Railway application RER IEC 9

16 Section 2 Energizing quantities, rated values and limits 1MRK TEN D Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Making capacity at resistive load 0.2 s 1.0 s Breaking capacity for AC, cos j > 0.4 Breaking capacity for DC with L/R < 40 ms 30 A 10 A V/0.4 A V/0.4 A V/0.2 A V/0.1 A 250 V/8.0 A 250 V/8.0 A 48 V/1 A 110 V/0.4 A 220 V/0.2 A 250 V/0.15 A Maximum capacitive load 10 nf 48 V/1 A 110 V/0.4 A 220 V/0.2 A 250 V/0.15 A Operating time < 6 ms <= 1 ms Maximum 72 outputs may be activated simultaneously with influencing factors within nominal range. After 6 ms an additional 24 outputs may be activated. The activation time for the 96 outputs must not exceed 200 ms. 48 outputs can be activated during 1 s. Continued activation is possible with respect to current consumption but after 5 minutes the temperature rise will adversely affect the hardware life. Maximum two relays per BOM/IOM/SOM should be activated continuously due to power dissipation. The stated operate time for functions include the operating time for the binary inputs and outputs. SEMOD v8 Table 9: SOM Static Output Module (reference standard: IEC ): Static binary outputs Function of quantity Static binary output trip Rated voltage 4860 VDC VDC Number of outputs 6 6 Impedance open state ~300 kω ~810 kω Test voltage across open contact, 1 min Current carrying capacity: No galvanic separation Continuous 5 A 5 A 1.0 s 10 A 10 A Making capacity at capacitive load with the maximum capacitance of 0.2 μf : 0.2 s 30 A 30 A Table continues on next page No galvanic separation 10 Railway application RER IEC

17 1MRK TEN D Section 2 Energizing quantities, rated values and limits Function of quantity Static binary output trip 1.0 s 10 A 10 A Breaking capacity for DC with L/R 40 ms 48 V/1 A 110 V/0.4 A 60 V/0.75 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A Operating time < 1 ms < 1 ms Table 10: SOM Static Output module data (reference standard: IEC ): Electromechanical relay outputs Function of quantity Max system voltage Trip and signal relays 250 V AC/DC Number of outputs 6 Test voltage across open contact, 1 min 1000 V rms Current carrying capacity: Continuous 8 A 1.0 s 10 A Making capacity at capacitive load with the maximum capacitance of 0.2 μf: 0.2 s 30 A 1.0 s 10 A Breaking capacity for DC with L/R 40 ms 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A Operating time < 6 ms Maximum 72 outputs may be activated simultaneously with influencing factors within nominal range. After 6 ms an additional 24 outputs may be activated. The activation time for the 96 outputs must not exceed 200 ms. 48 outputs can be activated during 1 s. Continued activation is possible with respect to current consumption but after 5 minutes the temperature rise will adversely affect the hardware life. Maximum two relays per BOM/IOM/SOM should be activated continuously due to power dissipation. The stated operate time for functions include the operating time for the binary inputs and outputs. Railway application RER IEC 11

18 Section 2 Energizing quantities, rated values and limits 1MRK TEN D M v9 Table 11: BOM Binary output module contact data (reference standard: IEC ) Function or quantity Binary outputs 24 Max system voltage Test voltage across open contact, 1 min Current carrying capacity Per relay, continuous Per relay, 1 s Per process connector pin, continuous Making capacity at inductive load with L/R > 10 ms 0.2 s 1.0 s Breaking capacity for AC, cos j > 0.4 Breaking capacity for DC with L/R < 40 ms Operating time Trip and Signal relays 250 V AC, DC 1000 V rms 8 A 10 A 12 A 30 A 10 A 250 V/8.0 A 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A < 6 ms Maximum 72 outputs may be activated simultaneously with influencing factors within nominal range. After 6 ms an additional 24 outputs may be activated. The activation time for the 96 outputs must not exceed 200 ms. 48 outputs can be activated during 1 s. Continued activation is possible with respect to current consumption but after 5 minutes the temperature rise will adversely affect the hardware life. Maximum two relays per BOM/IOM/SOM should be activated continuously due to power dissipation. The stated operate time for functions include the operating time for the binary inputs and outputs. 2.4 Influencing factors IP v1 M v16 Table 12: Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, operate value Relative humidity Operative range +20±5 C 25 C to +55 C 0.02%/ C 4575% 095% 1090% Storage temperature 40 C to +70 C 12 Railway application RER IEC

19 1MRK TEN D Section 2 Energizing quantities, rated values and limits Table 13: Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal range Influence Ripple, in DC auxiliary voltage Operative range Auxiliary voltage dependence, operate value max. 2% Full wave rectified 15% of EL 0.01%/% ±20% of EL 0.01%/% Interrupted auxiliary DC voltage 2460 V DC ± 20% V DC Interruption ±20% interval 0 50 ms No restart 0 s Correct behaviour at power down Restart time < 300 s Table 14: Frequency influence (reference standard: IEC ) (16.7 Hz) Dependence on Within nominal range Influence Frequency dependence, operate value Frequency dependence for two step overvoltage protection Frequency dependence for two step undervoltage protection Frequency dependence for transformer energizing function Harmonic frequency dependence (20% content) Harmonic frequency dependence for restricted earth fault protection Harmonic frequency dependence for distance protection (10% content) Harmonic frequency dependence for tank overcurrent protection (5% content) f r ±5.0% for 16.7 Hz f r ±5.0% for 16.7 Hz f r ±5.0% for 16.7 Hz f r ±5.0% for 16.7 Hz ±2.0%/Hz ±3.0%/Hz ±5.0%/Hz ±3.0%/Hz 2 nd, 3 rd and 5 th harmonic of f r ±2.0% 2 nd, 3 rd and 5 th harmonic of f r ±3.0% 2 nd, 3 rd and 5 th harmonic of f r ±5.0% 2 nd, 3 rd and 5 th harmonic of f r ±6.0% Railway application RER IEC 13

20 Section 2 Energizing quantities, rated values and limits 1MRK TEN D Table 15: Frequency influence (reference standard: IEC ) (50/60 Hz) Dependence on Within nominal range Influence Frequency dependence, operate value Frequency dependence for two step overvoltage protection Frequency dependence for two step undervoltage protection Frequency dependence for transformer energizing function Harmonic frequency dependence (20% content) Harmonic frequency dependence for restricted earth fault protection Harmonic frequency dependence for distance protection (10% content) Harmonic frequency dependence for tank overcurrent protection (5% content) f r ±5.0% f r ±5.0% f r ±5.0% f r ±5.0% ±1.0%/Hz ±1.0%/Hz ±2.0%/Hz 2 nd, 3 rd and 5 th harmonic of f r ±2.0% 2 nd, 3 rd and 5 th harmonic of f r ±3.0% 2 nd, 3 rd and 5 th harmonic of f r ±5.0% 2 nd, 3 rd and 5 th harmonic of f r ±6.0% 14 Railway application RER IEC

21 1MRK TEN D Section 3 Type tests according to standards Section 3 Type tests according to standards IP v1 M v14 Table 16: Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 100 khz slow damped oscillatory wave immunity test Ring wave immunity test, 100 khz Electrostatic discharge Direct application Indirect application Electrostatic discharge Direct application Indirect application Fast transient disturbance Surge immunity test Power frequency immunity test Conducted common mode immunity test Power frequency magnetic field test Pulse magnetic field immunity test Damped oscillatory magnetic field test Radiated electromagnetic field disturbance 2.5 kv IEC kv IEC , Level 3 24 kv IEC , Level 4 15 kv air discharge 8 kv contact discharge 8 kv contact discharge 15 kv air discharge 8 kv contact discharge 8 kv contact discharge 4 kv 2 kv, SFP galvanic RJ45 2 kv, MIM mainputs 24 kv, 1.2/50ms high energy 12 kv, BOM and IRF outputs IEC IEC , Level 4 IEEE/ANSI C IEC , Zone A IEC , Zone B IEC , Zone A IEC , Zone B V, 50 Hz IEC , Zone A 303 V, Hz IEC , Level A/m, 3 s 100 A/m, cont. IEC , Level A/m IEC , Level A/m IEC , Level 5 20 V/m MHz GHz 10 V/m, GHz IEC IEEE/ANSI C EN Radiated emission MHz IEC MHz IEEE/ANSI C63.4, FCC Conducted emission MHz IEC Railway application RER IEC 15

22 Section 3 Type tests according to standards 1MRK TEN D Table 17: Insulation Test Type test values Reference standard Dielectric test Impulse voltage test Insulation resistance 2.0 kv AC, 1 min. 1.0 kv AC, 1 min.: SFP galvanic RJ45 X.21LDCM 5 kv, 1.2/50ms, 0.5 J 1 kv, 1.2/50 ms 0.5 J: SFP galvanic RJ45 X.21LDCM > 100 MW at 500 VDC IEC ANSI C37.90 IEEE , Environment A Table 18: Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at 25 C IEC Cold storage test Test Ab for 16 h at 40 C IEC Dry heat operation test Test Bd for 16 h at +70 C IEC Dry heat storage test Test Bb for 16 h at +85 C IEC Change of temperature test Damp heat test, steady state Test Nb for 5 cycles at 25 C to +70 C Test Ca for 10 days at +40 C and humidity 93% Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 C and humidity 93 to 95% (1 cycle = 24 hours) IEC IEC IEC Table 19: CE compliance Test According to Electromagnetic compatibility (EMC) EN Low voltage (LVD) EN Table 20: Mechanical tests Test Type test values Reference standards Vibration response test Vibration endurance test Class II: Rack mount Class I: Flush and wall mount IEC Class I: Rack, flush and wall mount IEC Shock response test Class I: Rack, flush and wall mount IEC Shock withstand test Class I: Rack, flush and wall mount IEC Bump test Class I: Rack, flush and wall mount IEC Seismic test Class II: Rack mount Class I: Flush and wall mount IEC Railway application RER IEC

23 1MRK TEN D Section 4 Control Section 4 Control M v15 Table 21: Synchronizing, synchrocheck and energizing check SESRSYN (16.7 Hz) Phase shift, j line j bus (180 to 180) degrees Voltage high limit for synchronizing and synchrocheck Frequency difference limit between bus and line for synchrocheck Phase angle difference limit between bus and line for synchrocheck Voltage difference limit between bus and line for synchronizing and synchrocheck Time delay output for synchrocheck when angle difference between bus and line jumps from PhaseDiff + 2 degrees to PhaseDiff 2 degrees Frequency difference minimum limit for synchronizing Frequency difference maximum limit for synchronizing Maximum allowed frequency rate of change Maximum closing angle between bus and line for synchronizing Breaker closing pulse duration tmaxsynch, which resets synchronizing function if no close has been made before set time Minimum time to accept synchronizing conditions Voltage high limit for energizing check Voltage low limit for energizing check ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r ( ) Hz ±5 mhz ( ) degrees ±2.0 degrees ( ) p.u ±0.5% of U r ( ) ±0.2% or ±70 ms whichever is ( ) Hz ±5 mhz ( ) Hz ±5 mhz ( ) Hz/s ±5% or ±10.0 mhz/s whichever is ( ) degrees ±2.0 degrees ( ) s ±0.2% or ±15 ms whichever is ( ) s ±0.2% or ±70 ms whichever is ( ) s ±0.2% or ±70 ms whichever is ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r ( )% of UBase ±0.5% of U r Table continues on next page Railway application RER IEC 17

24 Section 4 Control 1MRK TEN D Maximum voltage for energizing ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r Time delay for energizing check when voltage jumps from 0 to 90% of Urated ( ) s ±0.2% or ±125 ms whichever is Operate time for synchrocheck function when angle difference between bus and line jumps from PhaseDiff + 2 degrees to PhaseDiff 2 degrees Operate time for energizing function when voltage jumps from 0 to 90% of Urated Min. = 35 ms Max. = 65 ms Min. = 100 ms Max. = 125 ms Table 22: Synchronizing, synchrocheck and energizing check SESRSYN (50/60 Hz) Phase shift, j line j bus (180 to 180) degrees Voltage high limit for synchronizing and synchrocheck Frequency difference limit between bus and line for synchrocheck Phase angle difference limit between bus and line for synchrocheck Voltage difference limit between bus and line for synchronizing and synchrocheck Time delay output for synchrocheck when angle difference between bus and line jumps from PhaseDiff + 2 degrees to PhaseDiff 2 degrees Frequency difference minimum limit for synchronizing Frequency difference maximum limit for synchronizing Maximum allowed frequency rate of change Maximum closing angle between bus and line for synchronizing Breaker closing pulse duration Table continues on next page ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r ( ) Hz ±5 mhz ( ) degrees ±2.0 degrees ( ) p.u ±0.5% of U r ( ) s ±0.2% or ±35 ms whichever is ( ) Hz ±5 mhz ( ) Hz ±5 mhz ( ) Hz/s ±5% or ±10.0 mhz/s whichever is ( ) degrees ±2.0 degrees ( ) s ±0.2% or ±15 ms whichever is 18 Railway application RER IEC

25 1MRK TEN D Section 4 Control tmaxsynch, which resets synchronizing function if no close has been made before set time Minimum time to accept synchronizing conditions Voltage high limit for energizing check ( ) s ±0.2% or ±35 ms whichever is ( ) s ±0.2% or ±35 ms whichever is ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r Voltage low limit for energizing check Maximum voltage for energizing Time delay for energizing check when voltage jumps from 0 to 90% of Urated ( )% of UBase ±0.5% of U r ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r ( ) s ±0.2% or ±100 ms whichever is Operate time for synchrocheck function when angle difference between bus and line jumps from PhaseDiff + 2 degrees to PhaseDiff 2 degrees Operate time for energizing function when voltage jumps from 0 to 90% of Urated Min. = 15 ms Max. = 30 ms Min. = 70 ms Max. = 90 ms M v13 Table 23: Autorecloser SMBRREC (16.7/50/60 Hz) Dead time: shot 1 "t1 Dead time: shot 1 "t1_hs Dead time: shot 2 t2 shot 3 t3 shot 4 t4 shot 5 t5 Minimum time that circuit breaker must be closed before new sequence is allowed tcbclosedmin Maximum allowed start pulse duration tlongstartinh Circuit breaker closing pulse duration tpulse ( ) s ±0.2% or ±20 ms whichever is ( ) s ±0.2% or ±20 ms whichever is ( ) s ±0.2% or ±20 ms whichever is ( ) s ±0.2% or ±20 ms whichever is ( ) s ±0.2% or ±10 ms whichever is ( ) s ±0.2% or ±10 ms whichever is Reclaim time treclaim ( ) s ±0.2% or ±10 ms whichever is Reset time for reclosing inhibit tinhibit Table continues on next page ( ) s ±0.2% or ±20 ms whichever is Railway application RER IEC 19

26 Section 4 Control 1MRK TEN D Maximum wait time for fulfilled synchrocheck conditions tsync Delay time before indicating successful reclosing tsuccessful Maximum wait time for circuit breaker closing before indicating unsuccessful tunsuccl ( ) s ±0.2% or ±25 ms whichever is ( ) s ±0.2% or ±20 ms whichever is ( ) s ±0.2% or ±25 ms whichever is SEMOD v14 Table 24: Tap changer mechanism TCMYLTC/TCLYLTC (16.7/50/60 Hz) Tap position for lowest and highest voltage ma for lowest and highest voltage tap position (1 63) ( ) ma Type of code conversion BIN, BCD, GRAY, SINGLE, ma Time after position change before the value is accepted tstable (1 60) s ±0.2% or ±210 ms whichever is GUIDFF6E48CB9A4B4A06AC3409A352783FA1 v5 Table 25: Transformer energization control XENCPOW (16.7 Hz) Operate level for voltage high limit ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r Operate level for voltage low limit ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r Target accuracy Closing at voltage peak ±3 ms 20 Railway application RER IEC

27 1MRK TEN D Section 5 Differential protection Section 5 Differential protection M v20 Table 26: Restricted earthfault protection, low impedance REFPDIF (16.7 Hz) Operating characteristic Adaptable ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 94% Minimum pickup, IdMin ( )% of IBase ±1.0% of I r Relay operate angle (6090) degrees ±2.0 degrees Operate time, trip at 0 to 2 x IdMin Reset time, trip at 2 x IdMin to 0 Operate time, trip at 0 to 10 x IdMin Reset time, trip at 10 x IdMin to 0 Second harmonic blocking Min. = 45 ms Max. = 65 ms Min. = 35 ms Max. = 55 ms Min. = 35 ms Max. = 55 ms Min. = 35 ms Max. = 55 ms 60.0% of fundamental (fixed value) ±2.0% of I r Note: Fundamental magnitude = 100% of I r Table 27: Restricted earthfault protection, low impedance REFPDIF (50/60 Hz) Operating characteristic Adaptable ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 94% Minimum pickup, IdMin ( )% of IBase ±1.0% of I r Relay operate angle (6090) degrees ±2.0 degrees Operate time, trip at 0 to 2 x IdMin Reset time, trip at 2 x IdMin to 0 Operate time, trip at 0 to 10 x IdMin Reset time, trip at 10 x IdMin to 0 Second harmonic blocking Min. = 25 ms Max. = 35 ms Min. = 15 ms Max. = 25 ms Min. = 20 ms Max. = 30 ms Min. = 15 ms Max. = 30 ms 60.0% of fundamental (fixed value) ±2.0% of I r Note: Fundamental magnitude = 100% of I r Railway application RER IEC 21

28 Section 5 Differential protection 1MRK TEN D GUID18E8FFF307264DBFA3EF20C273EB2161 v5 Table 28: Transformer differential protection T1PPDIF (16.7 Hz) Operating characteristic Adaptable ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 94% Unrestrained differential current limit, IdUnre ( )% of IBase ±1.0% of I r at I I r ±1.0% of I at I>I r Minimum pickup, IdMin ( )% of IBase ±1.0% of I r Differential current alarm level, IdAlarm ( )% of IBase ±1.0% of I r Independent time delay for alarm at 0 to 2 x IdAlarm Second harmonic blocking Fifth harmonic blocking ( )s ( )% of fundamental differential current ( )% of fundamental differential current ±0.2% or ±55 ms whichever is ±2.0% of I r Note: fundamental magnitude = 100% of I r ±10.0% of I r Note: fundamental magnitude = 100% of I r Operate time at 0 to 2 x IdMin, restrained function Reset time at 2 x IdMin to 0, restrained function Operate time at 0 to 2 x IdUnre, unrestrained function Reset time at 2 x IdUnre to 0, unrestrained function Min. = 60 ms Max. = 75 ms Min. = 35 ms Max. = 50 ms Min. = 35 ms Max. = 50 ms Min. = 35 ms Max. = 50 ms Critical impulse time 25 ms typically at 0 to 2 x Id Impulse margin line 35 ms typically Table 29: Transformer differential protection T1PPDIF (50/60 Hz) Operating characteristic Adaptable ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 94% Unrestrained differential current limit, IdUnre ( )% of IBase ±1.0% of I r at I I r ±1.0% of I at I>I r Minimum pickup, IdMin ( )% of IBase ±1.0% of I r Differential current alarm level, IdAlarm ( )% of IBase ±1.0% of I r Independent time delay for alarm at 0 to 2 x IdAlarm Second harmonic blocking Fifth harmonic blocking Table continues on next page ( )s ( )% of fundamental differential current ( )% of fundamental differential current ±0.2% or ±25 ms whichever is ±1.0% of I r Note: fundamental magnitude = 100% of I r ±5.0% of I r Note: fundamental magnitude = 100% of I r 22 Railway application RER IEC

29 1MRK TEN D Section 5 Differential protection Operate time at 0 to 2 x IdMin, restrained function Reset time at 2 x IdMin to 0, restrained function Operate time at 0 to 2 x IdUnre, unrestrained function Reset time at 2 x IdUnre to 0, unrestrained function Min. = 25 ms Max. = 40 ms Min. = 10 ms Max. = 25 ms Min. = 10 ms Max. = 25 ms Min. = 10 ms Max. = 25 ms Critical impulse time 10 ms typically at 0 to 2 x Id Impulse margin line 15 ms typically Railway application RER IEC 23

30 24

31 1MRK TEN D Section 6 Impedance protection Section 6 Impedance protection M v12 Table 30: Automatic switch onto fault logic ZCVPSOF (16.7 Hz) Parameter Range or value Accuracy Operate voltage, detection of dead line Operate current, detection of dead line (1 100)% of UBase (1 100)% of IBase ±0.5% of U r ±1.0% of I r Time delay for UI detection ( ) s ±0.2% or ±50 ms whichever is Delay time for activation of dead line detection ( ) s ±0.2% or ±25 ms whichever is Dropoff delay time of switch onto fault function ( ) s ±0.2% or ±35 ms whichever is Table 31: Automatic switch onto fault logic ZCVPSOF (50/60 Hz) Parameter Range or value Accuracy Operate voltage, detection of dead line Operate current, detection of dead line (1 100)% of UBase (1 100)% of IBase ±0.5% of U r ±1.0% of I r Time delay for UI detection ( ) s ±0.2% or ±20 ms whichever is Delay time for activation of dead line detection ( ) s ±0.2% or ±20 ms whichever is Dropoff delay time of switch onto fault function ( ) s ±0.2% or ±30 ms whichever is GUIDE8104D F5589F9A74B14BFE6FE v7 Table 32: Underimpedance protection for generators and transformers ZGTPDIS (16.7 Hz) Number of zones 3 Minimum operate current (10150)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Positive sequence impedance Fault resistance ( ) Ω/phase ( ) Ω/phase ±5.0% of the set impedance Conditions: Voltage range: (0.11.1) x U r Current range: (0.512) x I r Angle: at 0 deg and 85 deg Reset ratio 105% typically Table continues on next page Railway application RER IEC 25

32 Section 6 Impedance protection 1MRK TEN D Operate time at 2 x Zreach to 0.8 x Zreach Reset time at 0.8 x Zreach to 2 x Zreach Definite time delay Min. = 80 ms Max. = 105 ms Min. = 70 ms Max. = 90 ms ( ) s ±0.2% or ±110 ms whichever is Table 33: Underimpedance protection for generators and transformers ZGTPDIS (50/60 Hz) Number of zones 3 Minimum operate current (10150)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Positive sequence impedance Fault resistance ( ) Ω/phase ( ) Ω/phase ±2.0% of the set impedance Conditions: Voltage range: (0.11.1) x U r Current range: (0.512) x I r Angle: at 0 deg and 85 deg Reset ratio 105% typically Operate time at 2 x Zreach to 0.8 x Zreach Reset time at 0.8 x Zreach to 2 x Zreach Definite time delay Min. = 25 ms Max. = 40 ms Min. = 60 ms Max. = 75 ms ( ) s ±0.2% or ±45 ms whichever is GUID919B5CCEE B50B8CE4A6B62AE v5 Table 34: Distance protection zone, quadrilateral characteristic ZRWPDIS (16.7 Hz) Parameter Range or value Accuracy System Earthing Compensated earthed Solidly earthed High Impedance earthed Number of zones Max. 6 with selectable direction Operate level for minimum residual current Minimum operate current, PhE and PhPh Table continues on next page (1080)% of IBase ±1.0% of I r (1080)% of IBase ±1.0% of I r 26 Railway application RER IEC

33 1MRK TEN D Section 6 Impedance protection Parameter Range or value Accuracy Positive sequence impedance reach, PhE and PhPh loop Positive sequence reactance reach, PhE and PhPh loop Fault resistance, PhE and PhPh Load encroachment criteria: Load resistance, forward and reverse Safety load impedance angle Dynamic overreach ( ) Ω IEC ±5.0% static accuracy ( ) Ω ( ) Ω ( ) Ω (570) deg < 5% at 55 degrees Short line 5 < SIR < 50 and Long line 0.2 < SIR < 10 Reset ratio for impedance 105% typically Operate time Starting element, Zone16 Reset time at 0.2 to 2 x Zreach Definite time delay PhE and Ph Ph operation ±3.0 degrees static angular accuracy Conditions: Voltage range: (0.11.1) x U r Current range: (0.212) x I r Angle: at 0 degrees and 85 degrees < 50 ms typically IEC Min. = 50 ms Max. = 100 ms ( ) s ±0.2% or ±50 ms whichever is Table 35: Distance protection zone, quadrilateral characteristic ZRWPDIS (50/60 Hz) Parameter Range or value Accuracy System Earthing Compensated earthed Solidly earthed High Impedance earthed Number of zones Max. 6 with selectable direction Operate level for minimum residual current Minimum operate current, PhE and PhPh Positive sequence impedance reach, PhE and PhPh loop Positive sequence reactance reach, PhE and PhPh loop Fault resistance, PhE and PhPh Load encroachment criteria: Load resistance, forward and reverse Safety load impedance angle Dynamic overreach (1080)% of IBase ±1.5% of I r (1080)% of IBase ±1.5% of I r ( ) Ω IEC ±2.0% static accuracy ( ) Ω ( ) Ω ( ) Ω (570) deg < 5% at 55 degrees Short line 5 < SIR < 50 and Long line 0.2 < SIR < 10 Reset ratio for impedance 105% typically Operate time for starting element, Zone16 Reset time at 0.2 to 2 x Zreach Definite time delay PhE and Ph Ph operation ±2.0 degrees static angular accuracy Conditions: Voltage range: (0.11.1) x U r Current range: (0.212) x I r Angle: at 0 degrees and 85 degrees < 30 ms typically IEC Min. = 35 ms Max. = 65 ms ( ) s ±0.2% or ±30 ms whichever is Railway application RER IEC 27

34 Section 6 Impedance protection 1MRK TEN D GUIDB0283D4E2D7D43BB964C289D76C5F718 v2 Table 36: Catenary distance protection ZRCPDIS (16.7 Hz) Number of zones Max. 5 with selectable direction Minimum operate current (1080)% of IBase ± 1.0% of I r Reactance reach in forward and reverse direction Fault resistance in forward and reverse direction Load encroachment criteria: Load resistance, forward and reverse safety load impedance angle ( ) Ω IEC ±5.0% static accuracy ( ) Ω ( ) Ω (570) deg. Reset ratio for impedance 105% typically ±3.0 degrees static angular accuracy Conditions: Voltage range: (0.11.1) x U r Current range: (0.212) x I r Angle: at 0 degrees and 85 degrees Operate time Zone 15 < 50 ms IEC Reset time at 0.2 x Z reach to 2 x Z reach Min. = 50 ms Max. = 100 ms Definite time delay ( ) s ±0.2% or ±50 ms whichever is Table 37: Catenary distance protection ZRCPDIS (50/60 Hz) Number of zones Max. 5 with selectable direction Minimum operate current (1080)% of IBase ± 1.0% of I r Reactance reach in forward and reverse direction Fault resistance in forward and reverse direction Load encroachment criteria: Load resistance, forward and reverse safety load impedance angle ( ) Ω IEC ±2.0% static accuracy ( ) Ω ( ) Ω (570) deg. Reset ratio for impedance 105% typically ±2.0 degrees static angular accuracy Conditions: Voltage range: (0.11.1) x U r Current range: (0.212) x I r Angle: at 0 degrees and 85 degrees Operate time Zone 15 < 30 ms IEC Reset time at 0.2 x Z reach to 2 x Z reach Min. = 35 ms Max. = 65 ms Definite time delay ( ) s ±0.2% or ±30 ms whichever is 28 Railway application RER IEC

35 1MRK TEN D Section 7 Current protection Section 7 Current protection M v13 Table 38: Instantaneous phase overcurrent protection PHPIOC (16.7 Hz) Operate current ( )% of lbase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% at ( )% of IBase Operate time at 0 to 2 x I set Reset time at 2 x I set to 0 Min. = 40 ms Max. = 50 ms Min. = 45 ms Max. = 65 ms Critical impulse time 35 ms typically at 0 to 2 x I set Operate time at 0 to 10 x I set Reset time at 10 x I set to 0 Min. = 10 ms Max. = 20 ms Min. = 80 ms Max. = 100 ms Critical impulse time 7 ms typically at 0 to 10 x I set Dynamic overreach < 5% at t = 100 ms Table 39: Instantaneous phase overcurrent protection PHPIOC (50/60 Hz) Operate current ( )% of lbase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% at ( )% of IBase Operate time at 0 to 2 x I set Reset time at 2 x I set to 0 Min. = 15 ms Max. = 25 ms Min. = 15 ms Max. = 25 ms Critical impulse time 10 ms typically at 0 to 2 x I set Operate time at 0 to 10 x I set Reset time at 10 x I set to 0 Min. = 5 ms Max. = 15 ms Min. = 25 ms Max. = 40 ms Critical impulse time 2 ms typically at 0 to 10 x I set Dynamic overreach < 5% at t = 100 ms Railway application RER IEC 29

36 Section 7 Current protection 1MRK TEN D M v21 Table 40: Directional phase overcurrent protection, two steps D2PTOC (16.7 Hz) Measuring current input Measuring voltage input phase1, phase2, PosSeq, MaxPh, phase1phase2 phase1, phase2, PosSeq, phase1phase2 Operate current, step 12 (5 1200)% of lbase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% Independent time delay at 0 to 2 x I set, step 12 Operate time, start at 0 to 2 x I set Reset time, start at 2 x I set to 0 Voltage level where voltage memory takes over ( ) s ±0.2% or ±50 ms whichever is Min. = 35 ms Max. = 45 ms Min. = 20 ms Max. = 50 ms ( )% of UBase ±0.5% of U r Second harmonic blocking ( )% of fundamental ±2.0% of I r Note: fundamental magnitude = 100% of I r Directional function Settable: Nondirectional Forward Reverse Relay characteristic angle (45 to +135) degrees ±2.0 degrees Relay operate angle (5 to 90 ) degrees ±2.0 degrees Critical impulse time Impulse margin time Minimum operate current for IEC curves, step1 25 ms typically at 0 to 2 x I set 35 ms typically (5 1000)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Minimum operate time for IEC curves, step1 ( ) s ±0.2% or ±20 ms whichever is IEC Inverse time characteristics, step 1 Settable: IEC Normal Inverse IEC Very Inverse IEC Extremely Inverse RI type See table 143 and table Railway application RER IEC

37 1MRK TEN D Section 7 Current protection Table 41: Directional phase overcurrent protection, two steps D2PTOC (50/60 Hz) Measuring current input Measuring voltage input phase1, phase2, PosSeq, MaxPh, phase1phase2 phase1, phase2, PosSeq, phase1phase2 Operate current, step 12 (5 1200)% of lbase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% Independent time delay at 0 to 2 x I set, step 12 Operate time, start at 0 to 2 x I set Reset time, start at 2 x I set to 0 Voltage level where voltage memory takes over ( ) s ±0.2% or ±25 ms whichever is Min. = 15 ms Max. = 25 ms Min. = 10 ms Max. = 20 ms ( )% of UBase ±0.5% of U r Second harmonic blocking ( )% of fundamental ±2.0% of I r Note: fundamental magnitude = 100% of I r Directional function Settable: Nondirectional Forward Reverse Relay characteristic angle (45 to +135) degrees ±2.0 degrees Relay operate angle (5 to 90 ) degrees ±2.0 degrees Critical impulse time Impulse margin time Minimum operate current for IEC curves, step1 10 ms typically at 0 to 2 x I set 15 ms typically (5 1000)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Minimum operate time for IEC curves, step1 ( ) s ±0.2% or ±20 ms whichever is IEC Inverse time characteristics, step 1 Settable: IEC Normal Inverse IEC Very Inverse IEC Extremely Inverse RI type See table 144 and table 146 Railway application RER IEC 31

38 Section 7 Current protection 1MRK TEN D M v9 Table 42: Instantaneous residual overcurrent protection EFRWPIOC (16.7 Hz) Operate current (51200)% of lbase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% at ( )% of lbase Operate time at 0 to 2 x I set Reset time at 2 x I set to 0 Min. = 40 ms Max. = 50 ms Min. = 45 ms Max. = 65 ms Critical impulse time 35 ms typically at 0 to 2 x I set Operate time at 0 to 10 x I set Reset time at 10 x I set to 0 Min. = 15 ms Max. = 20 ms Min. = 80 ms Max. = 100 ms Critical impulse time 10 ms typically at 0 to 10 x I set Dynamic overreach < 5% at t = 100 ms Table 43: Instantaneous residual overcurrent protection EFRWPIOC (50/60 Hz) Operate current (51200)% of lbase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% at ( )% of lbase Operate time at 0 to 2 x I set Reset time at 2 x I set to 0 Min. = 15 ms Max. = 25 ms Min. = 15 ms Max. = 25 ms Critical impulse time 10 ms typically at 0 to 2 x I set Operate time at 0 to 10 x I set Reset time at 10 x I set to 0 Min. = 5 ms Max. = 15 ms Min. = 25 ms Max. = 40 ms Critical impulse time 2 ms typically at 0 to 10 x I set Dynamic overreach < 5% at t = 100 ms M v17 Table 44: Directional residual overcurrent protection, two steps EF2PTOC (16.7 Hz) Operate current, nondirectional, step 12 (11200)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% at (101200)% of IBase Relay characteristic angle (RCA) (45 to 135) degrees ±2.0 degrees Table continues on next page 32 Railway application RER IEC

39 1MRK TEN D Section 7 Current protection Operate current for directional release (5 500)% of IBase For RCA ±60 degrees: ±2.5% of I r at I I r ±2.5% of I at I > I r Independent time delay at 0 to 2 x I set, nondirectional, step 12 Independent time delay at 0 to 2 x I dir, directional operation in forward direction ( ) s ±0.2% or ±50 ms whichever is ( ) s ±0.2% or ±50 ms whichever is Second harmonic blocking (10100)% of fundamental ±2.0% of I r Note: fundamental magnitude = 100% of I r Minimum polarizing voltage (1100)% of UBase ±0.5% of U r Operate time, start at 0 to 2 x I set Reset time, start at 2 x I set to 0 Operate time, start at 0 to 10 x I set Reset time, start at 10 x I set to 0 Minimum operate residual current for inverse curves, nondirectional, step 1 Min. = 35 ms Max. = 50 ms Min. = 30 ms Max. = 50 ms Min. = 10 ms Max. = 25 ms Min. = 45 ms Max. = 65 ms (1 1000)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Minimum operate time for inverse curves, nondirectional, step 1 Inverse time characteristics, nondirectional, step 1 ( ) s ±0.2% or ±20ms whichever is Settable: IEC Normal inverse IEC Very inverse IEC Extremely inverse RI type Critical impulse time 25 ms typically at 0 to 2 x I set Impulse margin time 35 ms typically See Table 143 and Table 145 Table 45: Directional residual overcurrent protection, two steps EF2PTOC (50/60 Hz) Operate current, nondirectional, step 12 (11200)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Reset ratio > 95% at (101200)% of IBase Relay characteristic angle (RCA) (45 to 135) degrees ±2.0 degrees Operate current for directional release (5 500)% of IBase For RCA ±60 degrees: ±2.5% of I r at I I r ±2.5% of I at I > I r Independent time delay at 0 to 2 x I set, nondirectional, step 12 Table continues on next page ( ) s ±0.2% or ±25 ms whichever is Railway application RER IEC 33

40 Section 7 Current protection 1MRK TEN D Independent time delay at 0 to 2 x I dir, directional operation in forward direction ( ) s ±0.2% or ±25 ms whichever is Second harmonic blocking (10100)% of fundamental ±2.0% of I r Note: fundamental magnitude = 100% of I r Minimum polarizing voltage (1100)% of UBase ±0.5% of U r Operate time, start at 0 to 2 x I set Reset time, start at 2 x I set to 0 Operate time, start at 0 to 10 x I set Reset time, start at 10 x I set to 0 Minimum operate residual current for inverse curves, nondirectional, step 1 Min. = 10 ms Max. = 25 ms Min. = 10 ms Max. = 25ms Min. = 5 ms Max. = 15 ms Min. = 15 ms Max. = 30 ms (1 1000)% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Minimum operate time for inverse curves, nondirectional, step 1 Inverse time characteristics, nondirectional, step 1 ( ) s ±0.2% or ±20ms whichever is Settable: IEC Normal inverse IEC Very inverse IEC Extremely inverse RI type Critical impulse time 10 ms typically at 0 to 2 x I set Impulse margin time 15 ms typically See Table 144 and Table 146 SEMOD v16 Table 46: Sensitive directional residual overcurrent and power protection SDEPSDE (16.7 Hz) Operate level for 2I 0 cosj directional residual overcurrent ( )% of IBase ±1.5% of I r at I I r ±1.5% of I at I > I r Operate level for 2I 0 2U 0 cosj directional residual power Operate level for 2I 0 and j residual overcurrent ( )% of SBase ±1.5% of S r at S S r ±1.5% of S at S > S r ( )% of IBase ±1.0% of I r at I r ±1.0% of I at I > I r Operate level for nondirectional overcurrent ( )% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r Operate level for nondirectional residual overvoltage Residual release current for all directional modes Residual release voltage for all directional modes ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r ( )% of IBase ±1.0% of I r at I I r ±1.0% of I at I > I r ( )% of UBase ±0.5% of U r at U U r ±0.5% of U at U > U r Table continues on next page 34 Railway application RER IEC

R E L I O N 670 SERIES Line distance protection REL670 Version 2.2 ANSI Type test certificate

R E L I O N 670 SERIES Line distance protection REL670 Version 2.2 ANSI Type test certificate R E L I O N 670 SERIES Line distance protection REL670 Version 2.2 ANSI Document ID: 1MRK 506 372TUS Issued: September 2018 Revision: E Product version: 2.2 Copyright 2017 ABB. All rights reserved Copyright

More information

Relion 670 series. Generator protection REG IEC Type test certificate

Relion 670 series. Generator protection REG IEC Type test certificate Relion 670 series Generator protection REG670 2.0 IEC Document ID: 1MRK502054TEN Issued: July 2016 Revision: B Product version: 2.0 Copyright 2014 ABB. All rights reserved Copyright This document and

More information

Line distance protection REL670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES

Line distance protection REL670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES Line distance protection REL670 Version 2.2 IEC R E L I O N 670 SERIES Document ID: 1MRK 506 372TEN Issued: October 2017 Revision: A Product version: 2.2.1 Copyright 2017 ABB. All rights reserved Copyright

More information

Bay control REC670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES

Bay control REC670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES Bay control REC670 Version 2.2 IEC R E L I O N 670 SERIES Document ID: 1MRK 511 404TEN Issued: October 2017 Revision: A Product version: 2.2.1 Copyright 2017 ABB. All rights reserved Copyright This document

More information

R E L I O N 670 SERIES Phasor measurement unit RES670 Version 2.2 ANSI Type test certificate

R E L I O N 670 SERIES Phasor measurement unit RES670 Version 2.2 ANSI Type test certificate R E L I O N 670 SERIES Phasor measurement unit RES670 Version 2.2 ANSI Document ID: 1MRK 511 410TUS Issued: September 2018 Revision: E Product version: 2.2 Copyright 2017 ABB. All rights reserved Copyright

More information

Phasor measurement unit RES670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES

Phasor measurement unit RES670 Version 2.2 IEC Type test certificate R E L I O N 670 SERIES Phasor measurement unit RES670 Version 2.2 IEC R E L I O N 670 SERIES Document ID: 1MRK 511 410TEN Issued: September 2018 Revision: E Product version: 2.2 Copyright 2017 ABB. All rights reserved Copyright

More information

Relion 670 series. Transformer protection RET IEC Type test certificate

Relion 670 series. Transformer protection RET IEC Type test certificate Relion 670 series Transformer protection RET670 2.0 IEC Document ID: 1MRK504141TEN Issued: July 2016 Revision: B Product version: 2.0 Copyright 2014 ABB. All rights reserved Copyright This document and

More information

Relion 670 series. Generator protection REG670 Type test certificate

Relion 670 series. Generator protection REG670 Type test certificate Relion 670 series Generator protection REG670 Document ID: 1MRK502031-TEN Issued: February 2015 Revision: C Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and parts

More information

Relion 670 series. Line differential protection RED670 ANSI Type test certificate

Relion 670 series. Line differential protection RED670 ANSI Type test certificate Relion 670 series Line differential protection RED670 ANSI Document ID: 1MRK505226-TUS Issued: February 2015 Revision: C Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document

More information

Relion 670 series. Line differential protection RED670 Type test certificate

Relion 670 series. Line differential protection RED670 Type test certificate Relion 670 series Line differential protection RED670 Document ID: 1MRK505226-TEN Issued: February 2015 Revision: D Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document

More information

Relion 670 series. Transformer protection RET670 ANSI Type test certificate

Relion 670 series. Transformer protection RET670 ANSI Type test certificate Relion 670 series Transformer protection RET670 ANSI Document ID: 1MRK504117-TUS Issued: February 2015 Revision: C Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document

More information

Line distance protection REL650 Version 2.2 Type test certificate

Line distance protection REL650 Version 2.2 Type test certificate RELION 650 SERIES Line distance protection REL650 Version 2.2 Document ID: 1MRK 506 384TEN Issued: October 2017 Revision: A Product version: 2.2.1 Copyright 2017 ABB. All rights reserved Copyright This

More information

Relion 670 series. Phasor measurement unit RES670 Type test certificate

Relion 670 series. Phasor measurement unit RES670 Type test certificate Relion 670 series Phasor measurement unit RES670 Document ID: 1MRK511254-TEN Issued: February 2015 Revision: B Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and

More information

Breaker protection REQ650 Version 2.2 Type test certificate

Breaker protection REQ650 Version 2.2 Type test certificate RELION 650 SERIES Breaker protection REQ650 Version 2.2 Document ID: 1MRK 505 386TEN Issued: October 2017 Revision: A Product version: 2.2.1 Copyright 2017 ABB. All rights reserved Copyright This document

More information

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Harmonic restraint earth fault or single-phase overcurrent protection

Harmonic restraint earth fault or single-phase overcurrent protection Harmonic restraint earth fault or single-phase overcurrent protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970885) Features Sensitive earth fault protection

More information

Busbar protection REB650 Version 2.2 Type test certificate

Busbar protection REB650 Version 2.2 Type test certificate RELION 650 SERIES Busbar protection REB650 Version 2.2 Document ID: 1MRK 505 391TEN Issued: March 2018 Revision: B Product version: 2.2 Copyright 2017 ABB. All rights reserved Copyright This document

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

Relion 670 series. Bay control REC670 ANSI Type test certificate

Relion 670 series. Bay control REC670 ANSI Type test certificate Relion 670 series Bay control REC670 ANSI Document ID: 1MRK511231-TUS Issued: February 2015 Revision: C Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and parts thereof

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

Compact current relay and protection assemblies RXHL 401 and RAHL 401

Compact current relay and protection assemblies RXHL 401 and RAHL 401 Compact current relay and protection assemblies RXHL 401 and RAHL 401 (xx00000120.tif) Features Three phase compact current relay for: Phase overcurrent protection, three stages Earth-fault overcurrent

More information

Transformer differential protection

Transformer differential protection Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or

More information

Time over/underfrequency relay with protection assemblies

Time over/underfrequency relay with protection assemblies Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features

More information

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK (RXLK_2H.tif) RALK.psd Features Micro-processor based time-overexcitation relay with continuous settings for

More information

Relion 670 series. Phasor measurement unit RES IEC Type test certificate

Relion 670 series. Phasor measurement unit RES IEC Type test certificate Relion 670 series Phasor measurement unit RES670 2.0 IEC Document ID: 1MRK511319TEN Issued: July 2016 Revision: B Product version: 2.0 Copyright 2014 ABB. All rights reserved Copyright This document and

More information

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual Relion 605 series Relion 605 series Relion 605 series Self-Powered Feeder Protection REJ603 Application manual Document ID: 1MDU07206-YN 6 2 4 This document and parts thereof must not be reproduced or

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

Modular multifunction generator protection

Modular multifunction generator protection Modular multifunction generator Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970186) Features is a modular generator that enables selection of the desired in

More information

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics 9ROWDJHUHVWUDLQWRYHUFXUUHQW UHOD\DQGSURWHFWLRQ DVVHPEOLHV 5;,6.+DQG 5$,6. 509 033-BEN Page 1 Issued: September 2001 Changed since: June 1999 Data subject to change without notice (SE970171) (SE970896)

More information

User s manual and Technical description. Self-Powered Feeder Protection REJ603

User s manual and Technical description. Self-Powered Feeder Protection REJ603 and Technical description Self-Powered Feeder Protection 2 Document ID: Issued: 18.02.2008 Revision: A Product version:1.0 Copyright 2008 ABB. All rights reserved 3 Copyright This document and parts thereof

More information

Time-overcurrent relays and protection assemblies

Time-overcurrent relays and protection assemblies Time-overcurrent relays and protection Page 1 509 002-BEN Issued January 2004 Revision: A Data subject to change without notice (SE970134) (SE970150) Features RXIDK 2H relay and Single-, two-, three-phase

More information

Relion 670 series. Busbar protection REB670 ANSI Type test certificate

Relion 670 series. Busbar protection REB670 ANSI Type test certificate Relion 670 series Busbar protection REB670 ANSI Document ID: 1MRK505212-TUS Issued: February 2015 Revision: D Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and parts

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Time relay RXKA 1. (xx jpg) RXKA 1

Time relay RXKA 1. (xx jpg) RXKA 1 Time relay RXKA 1 (xx02000674.jpg) RXKA 1 Features For protection, control, signal and industrial applications On-delay and Off-delay functions Continuous and pulse output functions Setting range 0.1-320

More information

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM

More information

SPECIFICATION FOR OVERCURRENT RELAYS

SPECIFICATION FOR OVERCURRENT RELAYS SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24 Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24 RXIK 1 (RXIK_1.tif) RXEEB 1 (RXEEB_1.tif) RXIB 24 (RXIB_24.tif) Features RXIK low current relay, 50-60 Hz and dc High sensitivity 0,5-2

More information

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring The first Real-Time Protection and Automation platform that can be adapted to a wide variety of applications. While

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Instantaneous Overcurrent Relay

Instantaneous Overcurrent Relay Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

presentation contents application advantages

presentation contents application advantages presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is

More information

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Complementary Contacts material Control type [Us] rated supply voltage Voltage range Main Range of product Product or component

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Procontrol P14 89AS30R0100 Module and Application Description Analog Signal Multiplier

Procontrol P14 89AS30R0100 Module and Application Description Analog Signal Multiplier Procontrol P14 89AS30R0100 Module and Application Description Analog Signal Multiplier Procontrol P14 89AS30R0100 Analog Signal Multiplier NOTICE TRADEMARKS This document contains information about one

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics off-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal

More information

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

ASHIDA Numerical OC/EF Protection Relay

ASHIDA Numerical OC/EF Protection Relay ASHIDA Numerical OC/EF Protection Relay Features: 4 Element (3 Phase + EF) over current IDMT with instant trip. Back - lit LCD display for settings. Display of fault current. / Load current. Selection

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

IRIG-B Interface (De-modulated) External clock synchronization signal IRIG format B00X

IRIG-B Interface (De-modulated) External clock synchronization signal IRIG format B00X P847B&C Technical Data Sheet INTERFACES IRIG-B (De-modulated) Use Standard Connector Cable type Isolation Input signal Input impedance at dc Accuracy IRIG-B Interface (De-modulated) External clock synchronization

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

Features. Regulated Converters. RAC01-C RAC02-C 1-2 Watt Single Output RAC0_- C. AC/DC Converter

Features. Regulated Converters. RAC01-C RAC02-C 1-2 Watt Single Output RAC0_- C. AC/DC Converter Features Regulated Converters Description Compact low profile AC-DC power supply mw no load power consumption Class II power supply with kvac isolation Universal input voltage range (~VAC) Low output ripple/noise

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O Product data sheet Characteristics RE22R2MMU Multifunction Timer Relay - 24VDC/24..240 V AC - 2 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output

More information

Features. Regulated Converter. RAC02-SE/277 2 Watt Single Output RAC02- SE/277. AC/DC Converter

Features. Regulated Converter. RAC02-SE/277 2 Watt Single Output RAC02- SE/277. AC/DC Converter Features Regulated Converter Description 5mW max. no load power consumption Efficiency up to 76% Isolated output kvac / min SCP, OVP protection Wide operating temperature range: -4 C to +85 C Universal

More information

Line protection REL 100

Line protection REL 100 Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970130) Features Simultaneous phase-phase and phaseearth loop impedance measurement, with individual numerical measuring

More information

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable

More information

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER Customer : REV. 0 Page 1/16 Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INRUMENTRANSFORMER CVS - 24 - G - Revision Prepared Description Checked by Rev. Date by 0 13/06/16 First issue E.

More information

PART NUMBERING SYSTEM

PART NUMBERING SYSTEM Plug-In Timer pins Multifunction or monofunction Compact body for space saving Wide time range (from 0. seconds to 0 days delay) niversal power supply (-0 Vz) or relay outputs (SPDT / Changeover) Protective

More information

CP-T range Product group picture

CP-T range Product group picture Product group picture /1 ABB Catalog Electronic Products and Relays 1/1 2CDC 110 00 C09 Table of contents CP-T range Product group picture /1 Table of contents /2 Benefits and advantages / Ordering details

More information

Protection components

Protection components Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &

More information

Features. Regulated Converter RAC05- SK/C14. RAC 5 Watt Single Output RAC05-3.3SK/C14. AC/DC Converter

Features. Regulated Converter RAC05- SK/C14. RAC 5 Watt Single Output RAC05-3.3SK/C14. AC/DC Converter Features Regulated Converter Unique, patent-pending design Isolated power supply with integrated mains filter Packaged inside of line filter case Safe, touchable DC outputs Easy installation Worldwide

More information

Features. Regulated Converter. RAC04-C/277 4 Watt Single and Dual Output RAC04- C/277 -_. AC/DC Converter

Features. Regulated Converter. RAC04-C/277 4 Watt Single and Dual Output RAC04- C/277 -_. AC/DC Converter Features Regulated Converter Description mw max. no load power consumption High efficiency up to 79% Isolated Output 3.75kVAC / 1 minute SCP, OVP protection Wide operating temperature range: -4 C to +

More information

PART NUMBERING SYSTEM

PART NUMBERING SYSTEM Plug-In Timer 11 pins Multifunction or monofunction Compact body for space saving Wide time range (from 0.5 seconds to 10 days delay) Universal power supply (12-240 Vz) 1 or 2 relay outputs (SPDT / Changeover)

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

SWT 3000 Teleprotection technical data siemens.com

SWT 3000 Teleprotection technical data siemens.com Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable

More information

SPAE 010, 011 High Impedance Protection Relay

SPAE 010, 011 High Impedance Protection Relay SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n

More information

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC Characteristics time delay relay 10 functions - 1 s..100 h - 12..240 V AC/DC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay

More information

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC Characteristics time delay relay 10 functions - 1 s..100 h - 12..240 V AC/DC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay

More information

z8801 Local Oscillator PXI

z8801 Local Oscillator PXI TECHNICAL SPECIFICATIONS z8801 Local Oscillator PXI 2014 LitePoint, A Teradyne Company. All rights reserved. Port Descriptions Front Panel Label Type Description REF OUT SMA Backplane reference clock output

More information

DOBLE F6150SV TECHNICAL SPECIFICATIONS

DOBLE F6150SV TECHNICAL SPECIFICATIONS DOBLE F6150SV TECHNICAL SPECIFICATIONS The F6150sv line of System Simulators is designed for simulation tests on relay and protection schemes. There are four distinct models for your specific testing needs.

More information

This annex is valid from: to Replaces annex dated: Locations where activities are performed under accreditation

This annex is valid from: to Replaces annex dated: Locations where activities are performed under accreditation Annex to declaration accreditation (scope accreditation) Locations where activities are performed under accreditation Location Abbreviation/ location code Head Location Vijzelmolenlaan 5 & 7 3447 GX oerden

More information

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

DSA150 Series. xxx Series. 150 Watts.   AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125. 15 Watts xxx Series Ultra Slim Design 15% Peak Load for 3 seconds Ambient Operation from -1 C to +7 C High Efficiency Selectable Overload Characteristic Selectable Remote Inhibit or Enable 3 Year Warranty

More information

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents Data sheet Current monitoring relays CM-SRS.2 for single-phase AC/DC currents For the monitoring of currents in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact

More information

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C) XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by

More information

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

DSR120 Series. xxx Series. 120 Watts.   AC-DC Power Supplies. Models & Ratings. Mechanical Details 120 Watts xxx Series Ultra Slim Design - 32 mm 150% Peak Load for 3 seconds Ambient Operation from -25 C to +70 C Full Load at 60 C (24V/48V) High Efficiency - Up to 92% Volt-Free Contact for OK Selectable

More information

TSX Series. Modicon Manuals. Presented by: Modicon PLC. Schneider Electric Quantum Modicon Gould Gettys

TSX Series. Modicon Manuals. Presented by: Modicon PLC. Schneider Electric Quantum Modicon Gould Gettys TSX Series Modicon Manuals Presented by: Modicon PLC Schneider Electric Quantum Modicon Gould Gettys For Product Needs: Email: sales@modiconplc.com Call: 1-800-691-8511 Fax: 919-415-1614 ModiconPLC.com

More information

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Product availability : Stock - Normally stocked in distribution facility Price* : 42.90 USD Main Range of product Product or component

More information

RE11RMMU time delay relay 10 functions - 1 s..100 h V AC - 1 OC

RE11RMMU time delay relay 10 functions - 1 s..100 h V AC - 1 OC Product data sheet Characteristics RE11RMMU time delay relay 10 functions - 1 s..100 h - 24..240 V AC - 1 OC Complementary Contacts material Width pitch dimension Control type Voltage range Connections

More information

Features. Regulated Converter. RAC02-SE/277/W 2 Watt Single Output. RAC02- SE/277/W Wired. AC/DC Converter

Features. Regulated Converter. RAC02-SE/277/W 2 Watt Single Output. RAC02- SE/277/W Wired. AC/DC Converter Features Regulated Converter Description 35mW max. no load power consumption Efficiency up to 76% Isolated output 3kVAC / 1 minute SCP, OVP protection Wide operating temperature range: -4 C to +85 C Universal

More information

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC Characteristics time delay relay 10 functions - 1 s..100 h - 12..240 V AC/DC - 1 OC Product availability : Stock - Normally stocked in distribution facility Price* : 75.00 USD Main Range of product Product

More information

Capacitor protection relay

Capacitor protection relay Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent

More information

18V 35V 65V 40A 60A 1.5W 1.2W ms 40ms. 20ms 20ms

18V 35V 65V 40A 60A 1.5W 1.2W ms 40ms. 20ms 20ms Features DIN Rail Description Universal AC Input (85264VAC) Protections: SCP, OVP, OLP, OTP DC OK Indicator LED with Relay Contacts 5% (8W) peak load capacity Builtin active PFC,PF>,95 High effciency up

More information

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer

More information

CLP0205 Open Frame Power Supply Vac input; 5Vdc output; 200W Output Power; 0.25A stdby

CLP0205 Open Frame Power Supply Vac input; 5Vdc output; 200W Output Power; 0.25A stdby ; 12Vout @ 0.25A stdby Applications Industrial equipment LED Signage Telecommunications equipment Description Features Compact size 50.8mm x 101.6mm x 36.1mm (2in x 4in x 1.4in) with density of 18W/in

More information

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique Protection and control Sepam range Sepam 0 LA Self-powering protection Merlin Gerin Square D Telemecanique presentation contents page presentation protection functional and connection schemes other connection

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor

More information

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation Location(s) where activities are performed under accreditation Head Office Vijzelmolenlaan 5 & 7 3447 GX oerden The Netherlands Location Abbreviation/ location code Vijzelmolenlaan 5 & 7 3447 GX oerden

More information