FINDINGS AND REPAIR OF WESTINGHOUSE UTT AND McGRAW 550 TAP CHANGERS
|
|
- Timothy Chandler
- 5 years ago
- Views:
Transcription
1 FINDINGS AND REPAIR OF WESTINGHOUSE UTT AND McGRAW 550 TAP CHANGERS ABSTRACT Chad Tremaine, First Energy Corp. Goran Milojevic, DV Power Raka Levi, DV Power Toledo Edison had several issues with tap changers indicated by DGA results. Toledo Edison opened the tap changer looking for the source of the gasses, this eventually lead to performing a dynamic DC current test. The results of the tests indicated a problem with contacts and transfer switches. Resistance values were not consistent, while dynamic graphs showed significant ripples, which pointed to bad contacts. Following a detailed investigation of the UTT Westinghouse transfer switches, the laminates were found to be cracked and contact surfaces were worn to a significant degree. After the transfer switches were replaced, a retest was performed to verify the quality of the maintenance work. The McGraw 550 tap changer had an issue with the burned surface of stationary contacts, this was also detected through the dynamic test. INTRODUCTION FirstEnergy Corporation proudly serves 6 million customers in 10 different regulated companies across 6 states. In total we have 14,270 substations with 6,413 transformers providing reliable transmission and distribution services. Of those transformers only 2,014 transformers have an OLTC. FirstEnergy Corporations is focused on being a forward-thinking electric utility powered by a diverse team of employees committed to making customers lives brighter, the environment better, and our communities stronger. PROBLEM DESCRIPTION The Westinghouse tap changer model UTT had increasing DGA gas results, pointing to a problem with overheating in the tap changer compartment. Toledo Edison had the OLTC opened several times looking for the source of the gassing and the investigation was not conclusive. Toledo Edison decided to perform a dynamic test and try to pinpoint the cause of the increased dissolved gases. A continuous test and step by step tests were performed on all phases in April The McGraw tap changer model 550 had a history of high gas content. It operates about 10 times per day. Over the past year the ratio of Ethylene to Acetylene was very high in the order of Toledo Edison replaced the oil in February of 2016 and the gas sampling pointed to increased ratio Ethylene/Acetylene of 8.4 after only 30 days of operation. We have decided to perform the dynamic recording test also known as a DVtest, and in October of 2016 Toledo Edison preformed a complete battery of dynamic tests obtaining resistance values and dynamic graphs.
2 TAP CHANGERS The two types of On Load Tap Changers (OLTC) we are dealing in this paper are two different designs. One is an arcing tap switch the other with selector and transfer switch. Let us provide a brief description of various constructions. OLTC s can be divided by their construction into several groups: PLACEMENT: on-tank or in-tank ARRANGEMENT: diverter switch or selector switch SWITCHING PRINCIPLE: reactor or resistor As far as placement, most of USA s OLTCs are placed on-tank where a separate compartment is placed on the main transformer tank. A barrier separates the OLTC oil from the main tank oil. Both selector and switching elements are in the same oil. The in-tank design usually has a selector in the main tank oil while the diverter switch is in a separate sealed compartment placed inside the main tank, but with its own oil where it does not mix. Arrangement of the OLTC is based on several principles. Either the same contact performs the function of selecting the tap and switching the current, or there are separate contacts for each function. In the first case it is called an arcing tap switch or a selector switch, as it does both functions. The other arrangement has separate contacts where the selector only connects with the taps, while the diverter switch or a transfer switch performs all the current interruption and switching. The difference should be made between the selector switch and selector, as this terminology causes confusion. For that reason we will use the selector and arcing tap switch terms. There are modern vacuum type tap changers where a new term is introduced: the bypass switch. In that particular case all the switching is performed inside the vacuum bottle while the bypass switch opens and closes the circuit without current interruption and no arcing, further the selector is selecting the taps while disconnected by these bypass switches, thus not carrying any current and not arcing. The switching principle divides tap changers into two philosophical groups: resistor, fast tap changers, and reactor or slow tap changers. The principle of changing taps while the transformer is fully loaded was patented by Dr. Jansen in Today the principle is still applicable: make before break! The connection to the next tap should be made before the connection from the previous tap position is open (broken). During this period of time when both taps are connected to the transformer output, we have a portion of the regulating winding shorted. To minimize the short circuit current through this portion of the transformer, winding resistors are used in the resistor types, and a reactor or a preventive autotransformer (PA) for reactor types. One benefit of reactor construction is possibility to operate indefinitely in the bridging position, while the resistor tap changer slides through this state within few milliseconds. TAP CHANGERS IN QUESTION Both of the tap changers we will be dealing with in this paper are of reactor type, and both are mounted in the on-tank construction. The difference is that the McGraw 550 is an arcing tap switch design, while the Westinghouse UTT is a selector with transfer switches. Also, the McGraw has two stationary contacts per tap, while the Westinghouse unit has one fixed contact per tap. Two principles of motion are applied here: with one set of contacts per tap the one single moving arm with two separate contacts connect the taps. On the contrary, with two fixed contacts per tap, there are two moving arms that move alternatively controlled by a Geneva gear. All this is of big importance for analysis of the DVtest graphs that will be explained in the next section. We will concentrate in this paper on reactor type tap changers only, and will not deal with the resistor types as this was explained in other presentations [1,2]. 2 of 15
3 DYNAMIC RECORDING MEASUREMENT (DRM) This test method, also incorrectly known as a dynamic resistance measurement (same DRM acronym) is an off-line, non-destructive test in which a DC current is injected through the winding and tap changer as it moves through all tap positions. Results from the current signatures recorded with high sampling rate of 10 khz are examined and compared against previous tests or similar unit test results. This test may be used to detect tap changer problems such as slow transition time, mechanical or contact problems, and open circuits, among many others. The advantage of this method, also known as a DVtest is an advanced algorithm incorporated to allow testing and evaluation of tap changers connected through a series transformer [5]. The simplest application would be performing a continuous recording. A DC current of Amps is injected through the winding from the bushing through the tap changer to the neutral bushing. Connection is identical to a winding resistance measurement. The current measurement is recorded continuously with high resolution as the tap changer moves through all tap positions. Motor current is also monitored and recorded during the test, and this signature is very useful for the mechanism and motor control diagnostics. Typical DRM Graph of a Reactor Tap Changer Going Through 2 Positions Figure 1 The DRM current trace in the graph of Figure 1 shows key points of the tap changer operation identified by the sudden current change we call ripples. These ripples should be consistent and clean straight lines without bouncing marks. Length of ripples depends on the transition: is it bridging to non-bridging or reverse, and if the tap changer is moving from position 16L to 16R or in the opposite direction. Figure 1 shows that the ripple of bridging to non bridging transition is longer while the other ripple is shorter in length, due to the different switching phenomena with inclusion in one, or shorting the PA in the other case. The initial small ripple is a current change due to the start of the contact motion. The third ripple on the graph of a single transition is the moment when the moving contact is connecting with the next tap. As the graph shows, bridging to non-bridging and non-bridging to bridging transitions are similar but not identical. The next procedure is a little more complex and it is known as a step-by-step test. The resistance readings and the transition graphs are recorded alternately as the tap changes from one position to the next. The plot in Figure 1 shows the current signature, the recording is for a specified period of time (usually 10 seconds) once a tap change is detected. The next step is a measurement of the winding resistance at the new tap position. The recording picks-up again after the user is satisfied that the current has again reached stabilization and the winding resistance is measured and recorded. The black vertical dashed line in Figure 1 is where the recording ends and resumes after the unspecified period of time during which current re- 3 of 15
4 stabilizes. The DRM data collected should serve as a benchmark for future tests, as signatures are very repeatable. Winding resistance of all tap positions can be plotted as well, this shows a characteristic pattern of values alternating (bridging to non bridging) and changing direction following a neutral position, as it is a case with plus minus regulation. As most OLTC in the USA have 33 positions, the middle or neutral one is the position 17 (or in case 16R to 16L, the neutral is marked N). The graph below in Figure 2 shows a sample of winding resistance values for all three phases Ran [mω] Rbn [mω] Rcn [mω] Winding Resistance Values for All Tap Positions Figure 2 Several typical problems were found using this DVtest method and reported at various presentations. Contact coking is a very common problem in hot oil-copper or even silver contact-plating environments, detected by small ripples in the trace [3]. The mechanism is also a problematic assembly of this component - the only moving part under voltage in a power transformer. DVtest has shown several defects in the mechanism or motor control [4] of OLTC by analysis of motor current trace in conjunction with the test current DRM trace. FIRST ENERGY TAP CHANGER CASES DIAGNOSED USING DRM CASE 1 Westinghouse Type UTT Tap Changer Clyde Substation averages 7.18 MVA over a 12 month span to part of the city of Clyde, Ohio. TR #1 is rated for 14 MVA and tested regularly by the use of a DGA test. The OLTC type UTT is manufactured by Westinghouse, a reactor type tap changer with transfer switches that arc in oil. The results of the DGA pointed to overheating contacts. Investigation included lowering the oil, opening the LTC and visually inspecting the tap changer. The DRM test was performed at 25A, testing each tap on each phase of TR #1. The graphs of winding resistance measured, and dynamic trace of phase A are given in the graphs of Figures3, 4 and 5 below. 4 of 15
5 Winding Resistance of All 3 Phases Figure 3 As it can be observed from the results plotted in the graph of Figure 3, certain contacts measured higher resistance in the order of 3% above the expected values for that particular tap position. Phase A DRM Trace Figure 4 In Figure 4 shown above is of a continuous test recorded from phase A. The arrows are pointing to the ripples that were not what a clean and proper transition ripple should be. The Figure 5 below zooms into the transition and ripple shapes. 5 of 15
6 The 6 Transitions: 3 B>NB and 3 NB>B Figure 5 We have used the overlay functionality of the DV Win software to compare graphs in Figure 5 of transitions associated with the same contacts. Although these tap positions are different, they use the same contacts as in one case the regulating winding is added and in the other it is subtracted from the secondary winding, to provide for the double number of tap positions. It can be observed that the graphs are almost identical, which is expected as the contacts leave the characteristic fingerprint each time they switch the test current. Following the repair, when the transfer switches and stationary contacts were replaced, attached are a few photographs showing the issue of the worn out parts. Moving Transfer Switch Contacts Comparison Figure 6 6 of 15
7 Moving Transfer Switch Contacts Comparison Figure 7 The photos of Figures 6 and 7, show worn out contacts of the moving parts. The difference is clear when compared to the new contact. Stationary Transfer Switch Comparison Figure 8 7 of 15
8 Broken Down Laminates Figure 9 The photos of Figures 8 and 9, show a delaminated transfer switch fixed parts old and new. The gap difference is noticeable due to laminates breaking down. Stationary Transfer Switch and Movable Contact (Old) Figure 10 8 of 15
9 Stationary Transfer Switch and Movable Contact (New) Figure 11 The photos of Figures 10 and 11, show the difference between the old stationary and movable contacts compared to the new stationary and movable contacts. The gaps between the two contacts caused arcing which lead to the increase in gassing in the LTC tank. Through testing it could be determined what was wrong before opening the LTC which saved time and effort. A retest was performed to confirm the repair was successful. The trace of the graph is now smooth and when compared to the trace from before the difference is clear. Figure 12 shows two DRM graphs overlaid of the same phase, the smooth one taken after the repair. It is obvious that the trace before the repair with all the undesired ripples, points to a bad condition of contacts that operate on all transitions where these are the transfer switch contacts. Comparing DRM Traces Before and After Repair Figure 12 9 of 15
10 CASE 2 McGraw 550 tap changer Maumee Substation averages MVA over a 12 month span to part of the city of Maumee, Ohio. TR #1 is rated for 28 MVA. The OLTC on this transformer operates about 10 times per day, this transformer is also tested regularly by the use of a DGA test. Laboratory DGA results are presented in the table 1 below, only a portion of the data is shown: the ratio of ethylene to acetylene, and the total heat generated gas. The oil from the OLTC was replaced in February and the data associated with the sampling on February the 3rd 2016 shows no data for the C2H4/C2H2 ratio, as the tap changer did not operate in the new oil before sampling. Table 1 Laboratory Analysis of Gasses from the Tap Changer Gas analysis C2H4/C2H2 ratio Total heat gas The OLTC type 550 is manufactured by McGraw Edison, it is a reactor type, with an arcing tap switch, and double stationary contacts. The DRM test was performed at a 20A test current. Both the test current and motor current were recorded. The graph of phase B (X2) is shown in the Figure 13. Phase B DRM Graph Recorded in Continuous Mode Figure 13 During the step by step testing method, a measurement of winding resistance on each of 33 taps for all three phases are recorded and these values are represented in the Figure of 15
11 Winding Resistance Values of All Three Phases in All 33 Positions Figure 14 The phase C graph showed an interesting discrepancy at transitions associated with positions 9 to 10 and 28 to 29 both associated with the same fixed tap changer contact number 6. This is shown in the Figure 15, the arrows point to the two outstanding ripples. Phase C DRM Graph with Suspicious Ripples Figure 15 Three distinctions were observed in this graph associated with transitions of contact 6. A zoomed in view of these transitions is shown in the Figure 16: 1. Current is lower on that tap indicating higher resistance 2. The ripple is longer than others 3. There is a small peak when moving starts again 11 of 15
12 Comparison of Two Transitions at the Same Contact Figure 16 Analysis of the graph points to a problem with this particular fixed contact as the other transitions are consistent, where this would eliminate a possible moving contact problem. It was decided to look into contact 6 further by removing the oil and opening the LTC. Upon opening the LTC the stationary contacts on 6 showed sever arcing along with arcing to the movable contacts. This is shown in Figure 17 and 18 below. Burned Contacts on Stationary and Movable Contacts Figure of 15
13 Burned Stationary Contacts Figure 18 The contacts were removed and replaced with new contacts both on the stationary and movable contacts. Below in Figure 19 and 20 the difference between the burned contacts and new contacts is shown. Stationary Contact Comparison as Replaced from the OLTC Figure of 15
14 Movable Contact Comparison as Replaced from the OLTC Figure 20 There was no time to run a retest due to the need for the transformer to be put back in service. The latest DGA results show improved results after maintenance was complete. CONCLUSION This is a very useful test for OLTC diagnostics as it does not require opening the tap changer, which involves draining the oil and long term delays. This allows us the advantage of knowing the source of problem which allows us the possibility of bringing replacement parts before the OLTC is opened for repair and knowing where to look for a troublesome part once the tap changer is open. REFERENCES [1] Kellie Robinson, BPA, Steve Larson, Snohomish County PUD, Marcos Ferreira, Reinhausen Manufacturing, Results from Experiences of Performing Dynamic resistance Measurements on Resistance and Reactance LTC Types, Doble Client Conference, Boston 2012 [2] R. Levi, M. Ferreira, Dynamic Resistance Measurement Applied to On-Load Tap-Changers, Weidmann Annual Transformer Conference, Las Vegas, 2011 [3] G. Andersson, R. Levi, E. Osmanbasic, Dynamic tap changer testing, reactors and reactance, CIRED, 22nd International Conference on Electricity Distribution Stockholm, June 2013, Paper [4] R.Levi, G. Milojevic, From the AMforum Knowledge-base: Case studies of OLTC problems detected by DVtest, TechCon Training Track presentation, Sacramento CA, February 2015 [5] R. Levi, V. Mrdic, Advanced Dynamic Testing of Substation Apparatus, TechCon Albuquerque, NM, USA, of 15
15 BIOGRAPHY Chad Tremaine, EE, is a commissioning engineer and substation maintenance engineer at FirstEnergy Corp., USA. He has been employed by FirstEnergy Corp. since December 2015 Goran Milojevic, MSEE, is an application engineer at DV Power, Sweden, working as a technical support engineer for North America and Western Europe. After receiving his MSc, he worked as a product manager for the high-current transformer testing instruments, including the TWA40D, the most advanced threephase winding ohmmeter in the market. He is a member of the AMforum On-Load Tap Changer Dynamic Resistance Measurement working group. He has led a DRM research project in cooperation with ESBI, Ireland. Raka Levi, Dr.Eng., is an application expert at DV-Power Sweden. He has 30 years of asset performance and condition assessment experience, specializing in apparatus testing, monitoring and diagnostics. During his career, Dr. Levi has provided consulting service to utility clients in Europe and USA in the field of diagnostic testing, and investigations as a part of comprehensive substation condition assessment programs. Seven years ago he started within the AMforum organization a working group on DRM test methodology for tap changers. For 20 years he has been running committees that assemble asset managers and operations specialists of major European utilities, organizing conferences in Europe, TC Universities in USA, and TC Colleges in Asia. He has written over 25 technical papers on the subject of electrical testing, transformers, OLTCs, and breaker diagnostics and condition monitoring. His education includes Ph.D. in the field of HV diagnostics for circuit breakers and Diploma of electrical engineering, both at the U. of Belgrade, and ME in electric power from the RPI, New York. 15 of 15
Dynamic Testing for On Load Tap Changer Condition Assessment
4th International Colloquium "Transformer Research and Asset Management TUTORIAL Dynamic Testing for On Load Tap Changer Condition Assessment Dr. Raka Levi, AMforum Abstract The tutorial covers different
More informationReactor-type tap changers testing. Dynamic resistance measurement for on load tap changers
EVENTS DIAGNOSIS DVtest or dynamic resistance measurement is a diagnostic technique used in detecting on load tap changer operational problems ABSTRACT This paper discusses DVtest or Dynamic Resistance
More informationTap Changer Condition Assessment Using Dynamic Resistance Measurement
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Tap
More informationRegional Technical Seminar
Regional Technical Seminar LOAD TAP CHANGERS (LTCS) DESIGN, OPERATION, AND MAINTENANCE CONSIDERATIONS SPX Dallas Facility Damon Jones General Manager SPX Transformer Solutions Components Group Cell: 214-422-8979
More informationTesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis
feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.
More informationTWA Series Three-Phase Winding Ohmmeters & Tap Changer & Winding Analyzers
TWA Series Three-Phase Winding Ohmmeters & Tap Changer & Winding Analyzers Resistance measurement of all tap positions in all six windings performed in a single test True three-phase on-load tap changer
More informationLoad Tap Changers for Power Transformers
Load Tap Changers for Power Transformers Dr. Dieter Dohnal / Maschinenfabrik Reinhausen GmbH Dipl. Ing. Bernhard Kurth / Reinhausen Manufacturing Inc. Load Tap Changers for Power Transformers Content Basic
More informationThree-Phase Transformer Demagnetizer DEM60
Three-Phase Transformer Demagnetizer DEM60 Fully automatic demagnetization Demagnetization currents 5 ma 60 A DC Automatic discharging circuit Lightweight 13,1 kg High DC Current Source for Automatic Transformers
More informationOMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates
OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationPomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations
More information24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD
A NEW GENERATION VOLTAGE REGULATION DISTRIBUTION TRANSFORMER WITH AN ON LOAD TAP CHANGER FOR POWER QUALITY IMPROVEMENT IN THE ELECTRICAL DISTRIBUTION SYSTEMS Sudheer MOKKAPATY Jens WEISS Frank SCHALOW
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationOperational Management of Grid Transformers An Experience of POWERGRID
Operational Management of Grid Transformers An Experience of POWERGRID 1.0 Introduction P.N. Dixit, GM; S. Victor, AGM; V.K. Bhaskar, CM; Gunjan Agrawal, Manager Operation Services Department Power Grid
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60214-2 First edition 2004-10 Tap-changers Part 2: Application guide Reference number IEC 60214-2:2004(E) Publication numbering As from 1 January 1997 all IEC publications are
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationNew PCS Task Force Evaluate the need for an OLTC Diagnostic Field Testing Guide
New PCS Task Force Evaluate the need for an OLTC Diagnostic Field Testing Guide ---------------------------------------------------------------- Chair: Marcos Ferreira Vice Chair: Raka Levi Secretary:
More informationEffective maintenance test techniques for power transformers
Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure
More informationThe measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms
Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited
More informationEffective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa
More informationAcoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.
Acoustic Emission in power transformers 1 More expensive equipment in the substation Many years of operation First indication of a problem: Dissolved Gases Begin investigation to determine the origin of
More informationImportance of Transformer Demagnetization
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance
More informationTap Changer Analyzer & Winding Ohmmeter RMO-TT
Tap Changer Analyzer & Winding Ohmmeter RMO-TT On-load tap changer dynamic resistance measurement Three resistance measurement channels Four temperature measurement channels Vibration measurement Automatic
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationABB Power Products Service
Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?
More informationRecognizing if a Tap Changer Has Multiple Nominal Positions
Application Note Recognizing if a Tap Changer Has Multiple Nominal Positions The middle position of a tap changer is usually called a nominal or neutral position. Normally, transformer nominal voltage
More informationREPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD.
REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD. (DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/2015-16/Mgr(T)O&M-E-2/22
More informationOn-Load Tap Changer Type M
On-Load Tap Changer Type M OLTC type model M III 500 Y, U m = 123 Kv, 500A, ± 9 steps The type M On Load tap changers are used to vary the ratio of oil-immersed transformers under load.in general they
More informationTap Changer Analyzer & Winding Ohmmeter RMO-TT
Tap Changer Analyzer & Winding Ohmmeter RMO-TT On-load tap changer dynamic resistance measurement Three resistance measurement channels Up to six temperature measurement channels Automatic resistance/temperature
More informationTap Changer Analyzer & Winding Ohmmeter RMO60TT
Tap Changer Analyzer & Winding Ohmmeter RMO60TT On-load tap changer dynamic resistance measurement Three resistance measurement channels Three temperature measurement channels Automatic resistance/temperature
More informationCase Studies of Electric Power Equipment Diagnostics Using Acoustic Emission
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission Oswaldo G. SANTOS FILHO 1, Sergio L. ZAGHETTO
More informationVibro-Acoustic Testing Applied on Tap Changers and Circuit Breakers
Vibro-Acoustic Testing Applied on Tap Changers and Circuit Breakers By Fouad Brikci, Ph.D. Page 1 of 28 Page 2 of 28 VIBRO-ACOUSTIC TESTING APPLIED TO TAP CHANGERS AND CIRCUIT BREAKERS Fouad Brikci, Ph.D.
More informationDEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER
DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER JESSE M LOPEZ CPS ENERGY USA EMILIO MORALES CRUZ QUALITROL USA SUMMARY Power transformers are essential
More informationPrimary Test Manager (PTM) Testing and management software for primary assets
Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear
More informationMethod for Static and Dynamic Resistance Measurements of HV Circuit Breaker
Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker Zoran Stanisic Megger Sweden AB Stockholm, Sweden Zoran.Stanisic@megger.com Abstract S/DRM testing methods usually use long,
More informationAdvanced Diagnostic Testing Services. Provides detailed and reliable results
Advanced Diagnostic Testing Services Provides detailed and reliable results Advanced Diagnostic Testing Services from the world s leading manufacturer of power transformers ABB leadership begins with our
More informationTap Changer Analyzer & Winding Ohmmeter RMO-TD Series
Tap Changer Analyzer & Winding Ohmmeter RMO-TD Series On-load tap changer dynamic resistance measurement Three resistance measurement channels One temperature measurement channel Automatic resistance measurement
More information1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide
1ZSC000562-AAJ en, Rev. 1 Vacuum on-load tap-changers, type VUBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationThe Weidmann Conference The Aging of America s Transformers
The Weidmann Conference 2006 The Aging of America s Transformers by Jon L. Giesecke, Director, (610) 518-1615 jlgassociatesllc@yahoo.com How Old is Old? The aging of the electrical infrastructure in the
More informationPOWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
POWER TRANSFORMER Failure Analysis & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Electricity is high-grade energy. Working
More informationTap Changer Analyzer & Winding Ohmmeter RMO60TD
Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels
More informationPDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics
PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics CASE STUDY 1 (Doble Client Conference 2011, ACCA committee meeting) Dissolved Gas Analysis (DGA)
More informationVACUTAP VVS COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS.
COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS. WWW.REINHAUSEN.COM 2 TAILORED FOR GRID APPLICATIONS. The vacuum on-load tap-changer was developed and optimized for operation in transformers up to approximately
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationAutotransformer Condition Monitoring Systems
Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following
More informationHands-On Transformer Testing and Maintenance
Hands-On Course Description This Hands-On course will teach you how to prioritize your transformer maintenance strategy, stretch your maintenance budget and at the same time maximize the life and condition
More informationPower Transformer Products & Services INCREASED PERFORMANCE & UPTIME
Power Transformer Products & Services INCREASED PERFORMANCE & UPTIME Grand Eagle Your Single Source for Transformer Support Others claim to provide total transformer services and support. Grand Eagle delivers
More informationSAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.
Keep Powering On SAMPLE Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs. Overheating, arcing, partial discharge, and other active or slow-evolving
More informationMR PUBLICATION. On-Load Tap-Changers for Power Transformers A Technical Digest
On-Load Tap-Changers for Power Transformers A Technical Digest Abstract Introduction On-Load Tap-Changers (OLTCs) are one of the indispensable components for the regulation of power transformers used
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer
More information1ZSE en, Rev. 6. On-load tap-changers, type UBB Technical guide
1ZSE 5492-106 en, Rev. 6 On-load tap-changers, type UBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationTechnical guide. Type VRLTC load tap changer
Technical guide Type VRLTC load tap changer Table of contents General information... 2 Electrical characteristics... 3 Type tests... 4 Switching sequence... 5 Tank characteristics... 7 Terminal board...
More informationUse of On and Offline Oil Analysis on the ESB, Distribution and Generation Networks
Reliability Ireland Conference 2016, Grand Hotel Malahide, 12-13 April 2016, Dublin, Ireland. Use of On and Offline Oil Analysis on the ESB, Distribution and Generation Networks J. Carpenter*, ESB International,
More informationWinding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer
Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Lightweight 9,5 kg Test current 5 ma 40 A DC Measuring range 0,1-2 k Two voltage sense channels Extremely quick measurement Rapid automatic
More informationWinding Ohmmeter & Tap Changer Test Set RMO10TW
Winding Ohmmeter & Tap Changer Test Set RMO10TW Lightweight - only 7,5 kg Test current 5 ma 10 A DC Measuring range 0,1 µω - 2 kω Two voltage sense channels Extremely quick measurement Automatic discharge
More informationTap Changer Analyzer & Winding Ohmmeter RMO25TD
Tap Changer Analyzer & Winding Ohmmeter RMO25TD Test current 5 ma 25 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 9,5 kg Measuring range 0,1-2 k Two voltage sense channels
More informationTRANSFORMER SERVICES OUR KNOWLEDGE. YOUR EXPERTS.
TRANSFORMER SERVICES OUR KNOWLEDGE. YOUR EXPERTS. WWW.REINHAUSEN.COM Diagnostics Consulting Service TRANSFORMER LIFECYCLE PARTNER Modernization TRANSFORMER SERVICES 2 MAXIMUM AVAILABILITY. IDEALLY PLANNED.
More informationTap Changer Analyzer & Winding Ohmmeter RMO60TD
Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationSCOPE TRM 25 TRM 25+ Transformer Winding Resistance Meter. The most advanced Transformer Winding Resistance Meter injects up to 25A DC...
SCOPE TRM 25 TRM 25+ Transformer Winding Resistance Meter The most advanced Transformer Winding Resistance Meter injects up to 25A DC......TRM 25 The Product TRM 25 / TRM 25+ : Advanced Transformer Winding
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationRegional Technical Seminar TAP CHANGERS
Regional Technical Seminar TAP CHANGERS SPX Transformer Solutions, Inc. September 4, 2018 De-Energized and Load Tap Changers Jason Varnell Lead Design Engineer jason.varnell@spx.com SPX Transformer Solutions,
More informationDemagnetization of Power Transformers Following a DC Resistance Testing
Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.
More informationON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA
ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017 EA 782/15 ENG Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current (Iu),
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationPower Transformer Condition Assessment Based on Standard Diagnosis
Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer
More informationPololu Dual G2 High-Power Motor Driver for Raspberry Pi
Pololu Dual G2 High-Power Motor Driver for Raspberry Pi 24v14 /POLOLU 3752 18v18 /POLOLU 3750 18v22 /POLOLU 3754 This add-on board makes it easy to control two highpower DC motors with a Raspberry Pi.
More informationINTERNATIONAL STANDARD
NTERNATONAL STANDARD EC 60214-1 Edition 2.0 2014-05 colour inside Tap-changers Part 1: Performance requirements and test methods EC 60214-1:2014-05(en) THS PUBLCATON S COPYRGHT PROTECTED Copyright 2014
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationThe InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.
The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency
More informationRESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS
RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)
More informationON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA
ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017-2 EA 710. /1 EN Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current
More informationTechnical guide. Type VRLTC load tap changer
Technical guide Type VRLTC load tap changer Table of contents 2 General information 4 Switching sequences 6 Tank characteristics 6 Terminal board 7 Tap selector 7 Stationary contacts 7 Reversing switch
More informationFIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.
Regional Technical Seminar FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Field Electrical Testing Applications Key Purposes of Field Electrical Testing: Receiving inspection Acceptance testing/commissioning
More informationReport on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)
Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated
More informationUnderstanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion
More informationSoftware System for Finding the Incipient Faults in Power Transformers
Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 21 25 Sep $3,750 Dubai, UAE In any of the 5 star
More informationON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA
ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria EA 675/15 ENG Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current (Iu),
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationLife Cycle Management of Station Equipment & Apparatus Interest Group (LCMSEA) Getting Started with an Asset Management Program (Continued)
Life Cycle Management of Station Equipment & Apparatus Interest Group (LCMSEA) Getting Started with an Asset Management Program (Continued) Projects sorted and classified as: 1. Overarching AM Program
More informationChapter 7 Conclusion 7.1 General
Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due
More informationCondition-based maintenance of power transformers Complete three-phase system Turns Ratio: Recovery Voltage: Winding Resistance:
ETP SYSTEM Condition-based maintenance of power transformers The predictive and condition based maintenance is nowadays accepted as the most efficient solution to guarantee the proper operation of critical
More informationProblems connected with Commissioning of Power Transformers
Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.
More informationThree-Phase Winding Ohmmeter TWA25K
Three-Phase Winding Ohmmeter TWA25K Resistance measurement of all tap positions in all six windings performed in a single test Test currents 5 ma 25 A Extremely quick measurement, single-step cable setup
More informationB3-102 THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV SUBSTATIONS
21, rue d'artois, F-75008 Paris http://www.cigre.org B3-102 Session 2004 CIGRÉ THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV
More informationMots clés Power Transformer, Condition Assessment, On-line Monitoring Internet. Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM T&D, Germany
Benefit of sensors for on-line monitoring systems for power transformers Mots clés Power Transformer, Condition Assessment, On-line Monitoring Internet Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM
More informationMonitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers
in cooperation with Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers BZ-MS/1 pazifik power Complete Transformer Monitoring System (TMS) ZVCM-1001 Bushing Monitoring
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and
More informationCASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division
CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION - S K Mishra & S K Das NHPC Ltd O&M Division 1 PRESENTATION COVERS Introduction DESCRIPTION OF EVENTS INITIAL RESPONSE DETAILED INSPECTION
More informationProduct Catalog 2014
Product Catalog 2014 About DV Power Smart test devices for reliable electric power systems The company was founded in 2000 by the group of engineers with an extensive experience in the power electronics
More informationINTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER
Volume: 03 Issue: 07 July16 www.irjet.net p-issn: 2395-0072 INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER Sameer S. Patel 1, 1 Student, Electrical Dept, Rajasthan Institute
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationSURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company
SURGE ARRESTERS AND TESTING Keith Hill Doble Engineering Company Surge arresters are often overlooked when performing Power Factor tests on transformers, breakers and other apparatus in a substation. Often
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More informationPower Transformers Basics
Power Transformers Basics Transformer Basic Objective Introduce Basic Transformer Theory as it Relates to Diagnostics Provide a Better Understanding of the Diagnostic Test Environment Identify Important
More informationDIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS
DFFERENTAL PROTECTON METHODOLOGY FOR ARBTRARY THREE-PHASE POWER TRANSFORMERS Z. Gaji ABB AB-SA Products, Sweden; zoran.gajic@se.abb.com Keywords: power transformer, phase shifting transformer, converter
More informationTRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING
Training Title TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING Training Duration 5 days Training Date Transformer Operational Principles, Selection & Troubleshooting 5 15 19 Nov $4,250
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More information