KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB

Size: px
Start display at page:

Download "KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB"

Transcription

1 KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD Instruments Inc Parkway View Drive Pittsburgh PA Phone (412) Fax (412) Manual-NEO_5003-4_9-97

2 NEO Table Of Contents 1.0 General Specifications Installation Mechanical Installation Special Instructions for Mounting Near Tank Sidewall, Obstructions, and Turbulent Tanks Electrical Connections ma Transmitter Wiring Programming/Calibration Troubleshooting Maximum Application for the NEO Level Transmitter Loss of Acoustic Return Signal Factory Settings Changing the Display Units If the Transmitter Output Current is Always 4 ma or 20 ma Maintenance Arrival of Damaged Equipment List of Diagrams Diagram 2.1 Dimensions... 2 Diagram 3.1 Recess installation... 3 Diagram 3.2 Installation Precautions... 4 Diagram 3.3 Special NEO EchoKing Installation... 5 Diagram 4.1 NEO-5000 Wiring... 6 Diagram 4.2 Wiring the NEO to a 4-20 ma Control Loop... 7 Diagram 4.3 Wiring the NEO to a PLC... 7 Diagram 6.1 Echo Attenuation Graph Diagram 6.2 NEO Beam Cone Data... 11

3 NEO CAUTION: For safety reasons, please read the precautionary information Located at the end of this manual, before attempting installation 1.0 General The KOBOLD EchoKing level transmitter operates on the ultrasonic principle. An ultrasonic sound wave is pulsed eight times per second from the base of the transducer. The sound wave reflects against the process medium below and returns to the transducer. The microprocessor based electronics measure the time of flight between the sound generation and receipt, and translates this figure into the distance between the transmitter and process medium below. This design results in a high degree of accuracy with no requirement for contact with the fluid. 2.0 Specifications : 0.5 to 24.5 feet Accuracy: ± 0.25% of span (air) Resolution: 0.125" (3 mm) Pulse Frequency: 50 khz Pulse Rate: 8 pulses per second Dead Band: 6" from transducer face minimum Display Type: 4 segment LED Display Units: Selectable Inch or cm Calibration/programming: Push button Fail-safe diagnostics: Relay reverts to safe position Temperature rating: -4 to 140 F; (-20 to 60 C) Temp. compensation: Automatic over entire range Pressure rating: C., psi per C above 25 C. Fitting Size: 2 NPT Transducer material: Polyvinylidene Fluoride (PVDF)

4 NEO 2 Electrical Ratings: Enclosure rating: Enclosure material: Supply voltage: Current Consumption: Signal output: Output relay: Output relay ratings: NEMA 4X / IP65 Polypropylene VDC 200 ma Sourcing or sinking 4-20 ma Programmable for level alarm, pump-up/ pump-down or loss of signal alarm 250 VAC, 10 amp, 1/2 hp, SPDT Diagram 2.1 Dimensions KOB

5 3 NEO 3.0 Installation 3.1 Mechanical Installation Mounting the NEO properly is critical to operation. To install the NEO ultrasonic level transmitter in a system proceed as follows: If the NEO is installed such that the transducer face is recessed in a fitting or flange rather than flush with the tank lid, follow the criteria listed in Diagram 3.1 below. For a recess I.D. less than 3", do not recess the NEO more than 1 for best results. Diagram 3.1 Recess installation Recess I.D. (inches) Max. Depth (inches)

6 NEO The NEO level transmitter must be installed to avoid interference of the ultrasonic beam cone from the tank side wall. It must be installed such that the beam cone is not interfered by obstructions in the tank such as pipes, nozzles, ladders etc. The transmitter cannot be mounted at an angle (i.e. must be mounted perpendicular to the fluid surface). The NEO will not function in a vacuum. Diagram 3.2 illustrates these mounting precautions. Diagram 6.2 on page 11 gives the beam cone radius for various distances from the transducer face. Diagram 3.2 Installation Precautions Avoid Interference from tank side-wall Do not install at an angle Avoid interference from obstructions NEO will not operate in a vacuum

7 5 NEO 3.2 Special Instructions for Mounting near Tank Sidewall, Obstructions, and Turbulent Tanks When installing the NEO EchoKing level transmitter, every effort should be made to install the unit adhering to the precautions detailed in section 3.1.2, on page 4. In some installations where it is impossible to install away from the tank sidewall, away from obstructions or where the tank has a turbulent fluid surface it still may be possible to use the NEO level transmitter by attaching a two inch nominal I.D. pipe to the NEO transducer. The ultrasonic beam is then directed down the length of the pipe to the fluid surface and back to the transducer face. For this type of installation to work successfully, the following specific installation requirements must be met: The fluid cannot be a coating type media which will coat the inside of the pipe. If this occurs, the ultrasonic signal will be dispersed and the signal reflected off the fluid surface will not be strong enough to be detected by the NEO. The pipe used must be a single, continuous, straight length with no fittings, couplings or discontinuities except for the fitting which attaches the pipe to the 2 inch NPT fitting on the NEO transducer face. The pipe must extend into the tank the entire desired measuring length. A vent hole must be placed in the pipe. Both the vent hole and the two inch NPT fitting which attaches the pipe to the NEO must be placed within the six inch deadband which extends from the transducer face. If they extend beyond this deadband, they will interfere with the transmitted signal. Diagram 3.3 Illustrates this special installation. Diagram 3.3.Special NEO EchoKing Installation Pipe fitting and vent hole must be placed within 6 from the transducer face 6 Xducer deadband The pipe must be continuous and extend the entire tank measuring length

8 NEO Electrical Connections The NEO-5000 series level transmitter has both a 4-20 ma continuous level transmitter and SPDT relay. The SPDT relay can be programmed as a level alarm, as a pump-up/ pump-down control, to alarm when the transmitted ultrasonic signal return is lost, or to alarm when the 4-20 ma signal is lost. Diagram 4.1 shows the wiring color coding for the NEO. The NEO requires a VDC power with at least a 200 ma supply. Diagram 4.1 NEO-5000 Wiring ma Transmitter Wiring The NEO-5000 Series level transmitter has two different types of 4-20 ma transmitters. The Model NEO-5003 is a current sourcing 4-20 ma transmitter. This means that it has an internal power source for the 4-20 ma loop and requires no external D.C. power for the 4-20 ma current loop. It is for use with un-powered 4-20 ma loops and with PLCs which have no power source at their current inputs (current sinking inputs). The Model NEO-5004 is a current sinking 4-20 ma transmitter which requires an external power source in its 4-20 ma loop. It is for use with 4-20 ma loops in which has a power source in the loop and with PLCs which have a power source at their current inputs (current sourcing inputs). Diagram 4.2 shows wiring to a 4-20 ma loop. Diagram 4.3 shows wiring to PLCs.

9 7 NEO Diagram 4.2 Wiring the NEO to a 4-20 ma Control Loop Wiring to a Loop Indicator NEO-5004 Wiring to a Loop Indicator NEO-5003 Diagram 4.3 Wiring the NEO to a PLC Wiring to a PLC NEO-5003 Wiring to a PLC NEO-5004

10 NEO Programming/Calibration EchoKing Holding down the MENU key will scroll the display through its programming sequence. The display is lit only during the programming mode. It will automatically extinguish when programming is completed and the push-buttons are idle for 30 seconds. The following is a description of each item in the programming sequence: Program current settings: First determine the 4mA and 20 ma distances for the NEO. The 4mA setting is labeled EC4 and the 20 ma setting is labeled EC20. These settings represent the distance from the 4mA and 20 ma level to the bottom of the sensor. The EC4 value will be larger than the EC20 value. EC4: Hold the [MENU] key until EC4 appears in the display. Release the key and wait until a value appears. This value is the level that the NEO currently senses. If this is an acceptable 4 ma tank level, press [SET] to lock the value as the new EC4. If not, press either the [ ] or [ ] keys and the old setting for the EC4 will appear. From here, use the [ ] or [ ] keys to raise or lower the value to the correct measurement. Press the [SET] key to lock this value as the new EC4 value. EC20: Hold the [MENU] key until EC20 appears in the display. Release the key and wait until a value appears. This value is the level that the NEO currently senses. If this is an acceptable 20 ma tank level, press [SET] to lock the value as the new EC20. If not, press either the [ ] or [ ] keys and the old setting for the EC20 will appear. From here, use the [ ] or [of] keys to raise or lower the value to the correct measurement. Press the [SET] key to lock this value as the new EC20 value. RLAY: Only an indicator for the next two modes. The 10 amp relay is latched between the HSET and LSET points (for pump-up/pump-down as an example). To simply energize or de-energize the relay at a single level (as for a level alarm), HSET and LSET should be set to the same value. HSET & LSET: Sets the high point and low point for relay activation. Press [MENU] key until either HSET or LSET appears. Wait for the display to change to the current value and press either [ ] or [ ] to change the numeric value. The [SET] key does not need to be pressed to lock in the value. Repeat process for the other setting.

11 9 NEO SAF1/SAF2: The 10 amp relay inside the NEO can be used in a fail-safe design for your system. When [SAF1] is set, the relay will de-energize when the acoustic return signal is LOST. When [SAF2] is set, the relay will energize when the 4-20 ma signal is LOST. Response times will vary according to the setting of the NEO ([FAST] or [SLOW] modes). FAST/SLOW: [FAST] is the standard in which the NEO operates. [SLOW] is designed to dampen out turbulence in tanks. In the [FAST] mode, the NEO will average 8 responses per second and update every second. In the [SLOW] mode, the NEO will average over the preceding 10 seconds. When used with [SAFI] or [SAF2], the time for the relay to switch over is 30 seconds for the [FAST] mode, and 2.5 minutes for the [SLOW] mode. ALIN: Indicates that the unit is in the Alignment Mode. Display will show the return signal strength in db's. Used as an indicator for mechanical alignment of the NEO and/or to indicate signal attenuation. Typical readings range between 0 and 50 db's. For optimum alignment, first energize the unit and receive a valid return signal. Then select the ALIN mode and adjust the NEO until the display is maximized. ON/OFF: Used to toggle alignment [ON] or [OFF] with the [Set] key. The ALIN mode must be turned [OFF] when alignment is completed. This mode will not automatically default back to [LEVL]. TANK: Used as an indication for [TANK]. TANK sets the maximum tank depth that the NEO will recognize. It will filter out any returns greater than the tank value. This feature is useful for eliminating false readings in tanks which have irregular shaped bottoms or obstructions near the bottom of the tank. When the signal does exceed the tank value, the tank value will be displayed and transmitted. Use the next setting to change the TANK value. (value): Use the [ ] and [ ] buttons to change the current TANK value and press [SET] to enter the value. The NEO will limit the displayed and transmitted level to this distance. The maximum distance is 300 inches.

12 NEO Troubleshooting 6.1 Maximum Application for the NEO Level Transmitter The maximum range of the NEO is 24.5 feet at 110 db. Yet a number of factors can reduce the overall quality of signal return and shorten the accurate range of the transmitter. To determine the maximum application range of the product, follow the example signal return formula against the echo attenuation graph below. Diagram 6.1 Echo Attenuation Graph

13 11 NEO 6.2 Loss of Acoustic Return Signal A reading of LOST in the display of the NEO indicates the NEO is not receiving a valid return signal. In addition to a LOST appearing on the NEO display, the transmitter output will freeze at the last value where a valid acoustic return was received regardless of changes in tank level. If LOST appears, please check for: Interference such as the side wall, ladders, seams, rungs or pipes within the NEO's beam cone. The beam cone data is listed in Diagram 6.2 below. Proper installation such that the NEO is installed level and free from interference from the installation fitting. Sufficient power being supplied to the NEO. The NEO requires 14 to 36 VDC power with a minimum supply of 200 ma. Proper programming of the TANK function. For best results, set the TANK function as the distance from the bottom of the tank to the transmitter. When the acoustic return is again recognized by the NEO. The LOST display will clear and the transmitter will resume normal function. Diagram 6.2 NEO Beam Cone Data (feet) Radius (inches) (feet) Radius (inches)

14 NEO Factory Settings The NEO sensor is preset at the factory. When powering up the sensor the first time, the factory settings will be active. If at any time in you need to return to these settings, remove power from the sensor and wait 10 seconds. Press the [Set] and [Menu] buttons simultaneously while powering up the sensor. Table 6.1 Factory Calibration Default Values LEVL Inches SAF1/2 SAF1 EC 4 8 F/S FAST EC ALIN N/A RLAY N/A OFF OFF HSET 5 TANK N/A LSET 288 value Changing the Display Units The NEO comes preset to measure in inches. To change the unit to display centimeters, remove power to the unit and wait 10 seconds. Press [ ] and [Set] simultaneously while powering up the sensor. The NEO will now read in centimeters. To return to inches, remove power and wait 10 seconds. Press [ ] and [Set] simultaneously while powering up the sensor. 6.5 If the Transmitter Output Current is Always 4 ma or 20 ma If the output of the NEO is always reading 4mA or 20 ma, check the EC 4 and EC 20 input values for the NEO. The display of the NEO reads to the 1/10 of an inch or cm. A display of 1234 is 123.4" and not 1234". 7.0 Maintenance The Series NEO level transmitter is an electronic device with no moving parts. It has a totally digital electronic design which means that there is minimal calibration drift. These features make the NEO virtually maintenance free. If a coating of process media should form on the sensor face the unit should be removed from the system and the sensor face cleaned. 8.0 Arrival of Damaged Equipment Your instrument was inspected prior to shipment and found to be defect-free. If damage is visible on the unit, we advise that you carefully inspect the packing in which it was delivered. If damage is visible, notify your local carrier at once. The carrier is liable for a replacement under these circumstances. If your claim is refused, please contact KOBOLD Instruments.

15 13 NEO CAUTION PLEASE READ THE FOLLOWING WARNINGS BEFORE ATTEMPTING INSTALLATION OF YOUR NEW DEVICE. FAILURE TO HEED THE INFORMATION HEREIN MAY RESULT IN EQUIPMENT FAILURE AND POSSIBLE SUBSEQUENT PERSONAL INJURY.

16 NEO 14 User's Responsibility for Safety: KOBOLD manufactures a wide range of process sensors and technologies. While each of these technologies are designed to operate in a wide variety of applications, it is the user's responsibility to select a technology that is appropriate for the application, to install it properly, to perform tests of the installed system, and to maintain all components. The failure to do so could result in property damage or serious injury. Proper Installation and Handling: Use a proper sealant with all installations. Never overtighten the transmitter within the fitting. Always check for leaks prior to system start-up. Wiring and Electrical: A supply voltage of VDC is used to power the NEO transmitter. The sensor systems should never exceed a maximum of 36 VDC. Electrical wiring of the sensor should be performed in accordance with all applicable national, state, and local codes. Temperature and Pressure: The NEO is designed for use in application temperatures from -20 C (-4 F) to 60 C (140 F), and for use at pressures up to C, psi per C above 25 C. Operation outside these limitations will cause damage to the unit. Material Compatibility: The NEO is made of two materials. The enclosure is of Polypropylene (PP) and the transducer is made of Polyvinylidene Fluoride (PVDF). Make sure that the model which you have selected is chemically compatible with the application liquids. While the transmitter housing is liquid resistant when installed properly, it is not designed to be immersed. It should be mounted in such a way that it does not normally come into contact with fluid. Flammable, Explosive and Hazardous Applications: The NEO level transmitter system is not an explosion-proof design. It should not be used in applications where an explosion-proof design is required. Make a Fail-Safe System: Design a fail-safe system that accommodates the possibility of transmitter or power failure. In critical applications, KOBOLD recommends the use of redundant backup systems and alarms in addition to the primary system.

17 WARRANTY, SERVICE & REPAIR If for some reason your product must be returned for factory service, contact KOBOLD, or your KOBOLD distributor to receive a material return authorization number first, and provide them with the following information: 1. Part number, serial number 2. Name and telephone number of a person who can answer questions related to the product and its application 3. Return shipping address 4. Brief description of the symptom 5. Brief description of the application KOBOLD Ultrasonic Level Transmitter Model NEO-5001 Owner s Manual A KOBOLD customer service representative will issue a return authorization. Once you have received a return authorization, ship the product prepaid in its original packing to: KOBOLD INSTRUMENTS INC Parkway View Drive Pittsburgh, PA Please include any related symptom and application information with your product. This information enables our service technicians to process your repair order as quickly as possible. NRTL/C Version Part # LU /98 WARRANTY KOBOLD warrants to the original purchaser of its products that such products will be free from defects in material and workmanship under normal use and service for a period which is equal to the shorter of one year from the date of purchase of such products. This warranty covers only those components of the products which are non-moving and not subject to normal wear. Moreover, products which are modified or altered, and electrical cables which are cut to length during installation are not covered by this warranty. KOBOLD s obligation under this warranty is solely and exclusively limited to the repair or replacement, at KOBOLD s option, of the products (or components thereof) which KOBOLD s examination proves to its satisfaction to be defective. KOBOLD SHALL HAVE NO OBLIGA- TION FOR CONSEQUENTIAL DAMAGES TO PERSONAL OR REAL PROPERTY, OR FOR INJURY TO ANY PERSON. This warranty does not apply to products which have been subject to electrical or chemical damage due to improper use, accident, negligence, abuse or misuse. Abuse shall be assumed when indicated by electrical damage to relays, reed switches or other components. The warranty does not apply to products which are damaged during shipment back to KOBOLD s factory or designated service center or are returned without the original casing on the products. Moreover, this warranty becomes immediately null and void if anyone other than service personnel authorized by KOBOLD attempts to repair the defective products. Products which are thought to be defective must be shipped prepaid and insured to KOBOLD s factory or a designated service center (the identity and address of which will be provided upon request) within 30 days of the discovery of the defect. Such defective products must be accompanied by proof of the date of purchase. THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS WARRANTY. This warranty and the obligations and liabilities of KOBOLD under it are exclusive and instead of, and the original purchaser hereby waives, all other remedies, warranties, guarantees or liabilities, express or implied. EX- CLUDED FROM THIS WARRANTY IS THE IMPLIED WARRANTY OF FITNESS OF THE PRODUCTS FOR A PARTICULAR PURPOSE OR USE AND THE IMPLIED WARRANTY OF MERCHANT ABIL- ITY OF THE PRODUCTS. This warranty may not be extended, altered or varied except by a written instrument signed by a duly-authorized officer of KOBOLD, Inc. If KOBOLD level transmitters or switches are used for process control where failure of the transmitter or switch could result in personal injury or property damage, an independent means such as a redundant KOBOLD point level switch should be used. Where KOBOLD level transmitters or switches are used as a part of a pressure vessel or pipe, care should be taken to independently protect against personal injury or property damage should the KOBOLD sensor fail or be mishandled. Contact KOBOLD or your local distributor for additional information.

18 SAFETY PRECAUTIONS Step Two About this Manual: PLEASE READ THE ENTIRE MANUAL PRIOR TO INSTALLING OR USING THIS PRODUCT. This manual includes information on all versions of the continuous ultrasonic level transmitter from KOBOLD; model NEO-50_1 and NEO-50_1-IS. Please refer to the part number located on the sensor label to verify the exact model which you have purchased. User s Responsibility for Safety: KOBOLD manufactures a wide range of liquid level sensors and technologies. While each of these technologies are designed to operate in a wide variety of applications, it is the user s responsibility to select a technology that is appropriate for the application, install it properly, perform tests of the installed system, and maintain all components. The failure to do so could result in property damage or serious injury. Proper Installation and Handling: Use a proper sealant with all installations. Never overtighten the transmitter within the fitting. Always check for leaks prior to system start-up. Wiring and Electrical: A supply voltage of VDC is used to power the NEO-50_1 transmitter and a supply voltage of VDC is used to power the NEO-50_1-IS. The sensor systems should never exceed a maximum of 36 VDC for the NEO-50_1 and 32 VDC for the NEO-50_1-IS. Electrical wiring of the sensor should be performed in accordance with all applicable national, state, and local codes. Temperature and Pressure: The NEO-50_1 is designed for use in application temperatures from -40 C (-40 F) to 60 C (140 F), and for use at pressures up to C, psi per C above 25 C. Material Compatibility: The continuous ultrasonic level transmitter, NEO-50_1, is made of two materials. The enclosure is of Polypropylene (PP) and the transducer is made of Polyvinylidene Fluoride (PVDF). Make sure that the model which you have selected is chemically compatible with the application liquids. While the transmitter housing is liquid-resistant when installed properly, it is not designed to be immersed. It should be mounted in such a way that it does not normally come into contact with fluid. Flammable, Explosive and Hazardous Applications: Only the NEO-50_1-IS is rated for use in hazardous locations. Refer to the Certificate of Compliance for all applicable intrinsically safe ratings and entity parameters for the NEO-50_1-IS. Refer to the National Electric Code (NEC) for all applicable installation requirements in hazardous locations. DO NOT USE THE NEO- 50_1 GENERAL PURPOSE TRANSMITTER IN HAZARD- OUS LOCATIONS. Make a Fail-Safe System: Design a fail-safe system that accommodates the possibility of transmitter or power failure. In critical applications, KOBOLD recommends the use of redundant backup systems and alarms in addition to the primary system. Warning The NEO-50_1 is a loop powered device. The load should never exceed 900 Ohms. NEO-50_1-IS must be installed in accordance with drawing LU20CD rev B (see steps) for safe operation in a hazardous area. When installing the NEO-50_1, never tighten the transmitter from the body. Always use the wrench flat located above the threads. DEFINITION Step Three EC4 EC20 20 ma 4 ma EC4: The 4 ma setting for the NEO-50_1. The EC4 is the distance from the bottom of the NEO- 50_1 to the 4 ma set point. This setting is measured in either inches or centimeters on the display. The EC4 setting is typically greater that the EC20 setting. EC20: The 20 ma setting for the NEO-50_1. The EC20 is the distance from the bottom of the NEO- 50_1 to the 20 ma set point. This setting is measured in either inches or centimeters on the display. SAF1/SAF2/SAF3: Fail-Safe setting for the NEO-50_1. Use the SAF_ settings to determine a fail-safe mode for the current signal. When [SAF1] is set, the current will increase to 22 ma if the signal becomes LOST. When [SAF2] is set, the current will decrease to 4 ma if the signal becomes LOST. When [SAF3] is set, the current will remain constant if the signal becomes LOST. FAST/SLOW: Setting for echo averaging on the NEO-50_1. [FAST] is the typical setting for the NEO-50_1 to operate. [SLOW] is designed to help dampen out effects caused by severe turbulence. In the [FAST] mode, the NEO-50_1 will average 2 signal responses per second and update every second. In the [SLOW] mode, the NEO-50_1 will average signal returns over the preceding 10 seconds. When used with [SAF 1/2/3], the time for the current to default is 30 seconds for [FAST] mode and 2.5 minutes for [SLOW] mode. ALIN: Indicates that the unit is in the Alignment mode. Display will show the return signal strength in db's. Used as an indicator for mechanical alignment of the NEO-50_1 and/or signal attenuation. Typical readings range between 2 and 60 db's. For optimum alignment, first energize the unit and receive a valid return signal. Then select the ALIN mode and adjust the NEO-50_1 until the display value is maximized. ON/OFF: Actual setting for ALIN mode. The ALIN mode must be turned [OFF] when alignment is completed. This mode will not automatically default back to [LEVL]. MAXR: Used as an indication for [MAXR] or maximum range. The MAXR sets the maximum tank height and will filter out all returns greater than this value. (value): Actual MAXR setting. The maximum distance is inches. MINR: Used as an indication for [MINR] or the minimum range. The MINR value is the deadband closest to the transducer face where no signal will be generated. The MINR sets the minimum distance between the liquid and the transducer. (value): Actual MINR setting. The minimum distance is 6.0 inches. MINR MAXR

19 PROGRAMMING Step Four EC4: 1. Hold [MENU] key until EC4 appears in display. 2. Release [MENU] key and wait until a value appears. This value is the current measured level value. 3. If this is acceptable, press [SET] to lock the value as the new EC4 set point. If not, press either the [ ] or [ ] keys once and the old setting for the EC4 will appear. 4. From here, use the [ ] or [ ] keys to raise or lower the value to the desired value. 5. Press the [SET] key to enter this value as the new EC4 set point. WIRING Step Five The NEO-50_1 requires VDC power with at least 25 ma supply in order to operate. 1. Wiring to a Two-Wire Loop Indicator (Model NEO-50_1): (+) (-) Echotouch TM Ultrasonic Level Transmitter DC Power Supply VDC EC20: 1. Hold [MENU] key until EC20 appears in display. 2. Release [MENU] key and wait until a value appears. This value is the current measured level value. 3. If this is acceptable, press [SET] to lock the value as the new EC20 set point. If not, press either the [ ] or [ ] keys once and the old setting for the EC4 will appear. 4. From here, use the [ ] or [ ] keys to raise or lower the value to the desired value. 5. Press the [SET] key to enter this value as the new EC20 set point. SAF1/SAF2/SAF3: 1. Hold [MENU] key until SAF1, SAF2 or SAF3 appears in the display. 2. Release [MENU] key and hold [SET] key to toggle between SAF1, SAF2 and SAF3. 3. When desired setting is reached, release [SET] key. The last displayed setting will be locked into memory. To change, start again at step 1. SET MENU 2. Wiring to a PLC (NEO-50_1): (+) (-) Echotouch TM Ultrasonic Level Transmitter SET MENU DC Power Supply VDC A Typical PLC 250Ω FAST/SLOW: 1. Hold [MENU] key until FAST or SLOW appears in the display. 2. Release [MENU] key and hold [SET] key to toggle between FAST and SLOW. 3. When desired setting is reached, release [SET] key. The last displayed setting will be locked into memory. To change, start again at step 1. ALIN: 1. Hold [MENU] key until ALIN appears in the display. 2. Continue to hold [MENU] key until OFF appears in the display. 3. Release [MENU] key and hold [SET] key to toggle from OFF to ON. 4. Release [SET] key. The NEO-50_1 is now in ALIN mode. 5. To exit ALIN mode, repeat steps 1-4 changing from ON to OFF. MAXR: 1. Hold [MENU] key until MAXR appears in the display. 2. Continue to hold [MENU] key until a value appears in the display. This value is the current MAXR setting. 3. If this is acceptable, press [SET] to lock the value as the MAXR setting. If not, use the [ ] or [ ] keys to raise or lower the value to the desired setting. 4. Press the [SET] key to enter this value as the new MAXR setting. MINR: 1. Hold [MENU] key until MINR appears in the display. 2. Continue to hold [MENU] key until a value appears in the display. This value is the current MINR setting. 3. If this is acceptable, press [SET] to lock the value as the MINR setting. If not, use the [ ] or [ ] keys to raise or lower the value to the desired value. 4. Press the [SET] key to enter this value as the new MINR setting.

20 WIRING II Step Six The NEO-50_1-IS requires VDC power with at least 25 ma supply in order to operate. The follow provides an overview of wiring the NEO-50_1-IS to various devices. Please note that a barrier must be installed between the NEO-50_1-IS and the device and the barrier must be located within the nonhazardous location. 1. Hazardous System Diagram INSTALLATION Step Seven Mounting the NEO-50_1 is critical to the successful operation of the transmitter. Avoid the following parameters: Avoid interference from side of tank Do not install NEO-50_1 at an angle NON-HAZARDOUS LOCATION HAZARDOUS LOCATION Class I, Div I, Groups A, B, C & D Class II, Div I, Groups E, F & G Class III, Div I Supply Any Approved I.S. Barrier Vdc 32.0 V Isc 130 ma Ca 0 µf La 0 µh Model LU20 Ultrasonic Level Transmitter Vmax = 32.0 V Imax = 130 ma Ci 0 µf Li 0 µh Avoid interference from obstructions in tank NEO-50_1 will not operate in vacuum Control drawing for the LU20-50X1-IS NEO-50_1-IS ultrasonic level transmitter approved under the entity concept as an I.S. apparatus Control Drawing: LU20CD Rev. B* Wiring to a Two-Wire Loop Indicator VACUUM Wiring to a PLC NON-HAZARDOUS LOCATION DC Power Supply VDC Any Approved I.S. Barrier Vdc 32.0 V Isc 130 ma Ca 0 µf La 0 µh + - HAZARDOUS LOCATION Model LU20 Ultrasonic Level Transmitter Vmax = 32.0 V Imax = 130 ma Ci 0 µf Li 0 µh MINR Minimum (MINR) Setting If installing the NEO-50_1 in a flange or any device which recesses the bottom of the transmitter, use the MINR setting. The minimum value for the MINR setting is the distance from the bottom of the transmitter to the end of the flange. Never set MINR to less than 6.0 inches. Typical PLC 250Ω A NON-HAZARDOUS LOCATION DC Power Supply VDC Any Approved I.S. Barrier Vdc 32.0 V Isc 130 ma Ca 0 µf La 0 µh + - HAZARDOUS LOCATION Model LU20 Ultrasonic Level Transmitter Vmax = 32.0 V Imax = 130 ma Ci 0 µf Li 0 µh Maximum Application The maximum range of NEO-50_1 is 18 feet at 110 db. Under less than ideal conditions, a number of factors can reduce the overall quality of signal return and shorten the accurate range of the transmitter. To determine the maximum application range of the product, follow the signal return formula against the echo attenuation graph below. Echo Attenuation Graph 50 ALIGN READING (db) TYPICAL CURVE 10 db ABSORPTION EXAMPLE: OPTIMIZE ALIGNMENT 1: Distance from transducer = 40" 2: Highest possible ALIN = 28dB (under ideal conditions) Adjust mechanical alignment of unit to maximize displayed ALIN value PREDICT MAXIMUM RANGE USING ALIGN VALUE 3: If the actual ALIN = 18dB at D = 40" 4: Maximum = 138" db ABSORPTION DISTANCE FROM FACE OF TRANSDUCER (inches)

21 INSTALLATION II Step Eight Factory Settings: The NEO-50_1 is preset at the factory. When powering up the transmitter the first time, the factory settings will be active. If at any time in you need to return to these settings, remove power from the NEO-50_1 and wait 10 seconds. Press the [Set] and [Menu] buttons simultaneously while powering up the transmitter. EC 4 EC20 SAF1/2/3 Fast/Slow ALIN Factory Calibration 216" (548.4 cm) 8" (20.3 cm) SAF1 FAST N/A OFF MAXR value MINR value OFF N/A 216" (548.4 cm) N/A 6" (15.2 cm) Changing Display Units: The NEO-50_1 comes preset to measure in inches. To change the unit to display centimeters, remove power to the NEO-50_1 and wait 10 seconds. Press [ ] and [Set] simultaneously while powering up the transmitter. The NEO-50_1 will now read in centimeters. To return to inches, remove power and wait 10 seconds. Press [ ] and [Set] simultaneously while powering up the transmitter. Beam Cone Data Radius (Feet) (Inches) 1' 2.6" 2' 4.2" 3' 5.7" 4' 7.3" 5' 8.9" 6' 10.5" 7' 12.1" 8' 13.6" 9' 15.2" Depth Radius (Feet) (Inches) 10' 16.8" 11' 18.4" 12' 20.0" 13' 21.5" 14' 23.1" 15' 24.7" 16' 26.3" 17' 27.8" 18' 29.4" TROUBLESHOOTING Step Nine LOST Signal: A reading of LOST in the display of the NEO-50_1 indicates the transmitter is not receiving a valid return signal. If LOST appears, please check the following troubleshooting items: 1. Beam cone interference such as the side wall, ladders, seams, rungs or pipes within the NEO-50_1's beam cone. 2. Proper installation such that the NEO-50_1 is installed level and free from interference from the installation fitting or flange. 3. Sufficient power being supplied to the NEO-50_1. The NEO-50_1 requires VDC power with a minimum supply of 25 ma. The NEO-50_1-IS requires VDC power with a minimum supply of 25 ma. 4. Proper programming of the MAXR or MINR function. For best results, set the MAXR function as the distance from the bottom of the tank to the bottom of the transmitter. Also set the MINR distance above the highest level in the tank. Do not set the MINR to less than 6 inches. 5. Make sure that the transmitter is not installed at an angle. Even a 5 degree offset can reduce the signal return strength greatly. Other Hints: Current must change with changes in level. Example: For the illustration below, as level increases, the current output will increase and as the level decreases, the current output will decrease. If the output of the NEO-50_1 is always reading 4 ma or 20 ma, check the input values for the NEO-50_1. EC20 Radius 20 ma EC4 4 ma

22 SPECIFICATIONS Step One : 0.5 to 18 feet (15 cm to 5.4 m) Accuracy: ± 0.25% of span in air Resolution: (3 mm) Frequency: 50 khz Pulse rate: 2 pulses per second Beam width: 8 conical Deadband: 0.5' (15 cm) minimum Blocking distance: 0.5 to 18 feet (15 cm to 5.4 m) Display type: 4 segment LCD Display units: Inch (cm) Memory: Non-volatile Supply voltage: GP: VDC IS: VDC Max loop resistance GP: VDC (see below) IS: VDC (see below) Signal output: GP: 4-20 ma, VDC (see below) IS: 4-20 ma, VDC (see below) Signal invert: 4-20 ma / 20-4 ma Calibration: Push button Fail-safe diagnostics: Reverts to 4 ma, 22 ma or remains constant Temperature rating: F: -40º to 140º C: -40º to 60º (see below) Temp. compensation: Automatic over entire range Pressure rating: 30 psi (2 25 C., psi (.113 bar) per C. above 25 C. (see below) Enclosure rating: NEMA 4X (IP65) Enclosure material: Polypropylene (PP), U.L. 94VO Transducer material: Polyvinylidene Fluoride (PVDF) Mounting threads: 2 NPT (2" G) Mounting gasket: Viton (2") metric only Conduit connection: 1/2" NPT (1/2" BSP) CE Compliance: EN immunity EN emission CSA Certificate: LR *GP = General Purpose IS = Intrinsically Safe Operating Pressure (psi) Max. Series Resistance (Ohms) Ambient Sensor Temperature ( C) Temperature/Pressure Derating 35 Unacceptable Acceptable Maximum Temperature/Voltage Derating Continuous 20 ma Curve (LU20-50X1) (NEO-50_1) 100 Unacceptable Acceptable Operating Voltage (VDC) Flowline Kobold 4 or 20 ma LU20-50X1 (NEO-50_1) Electrical Loading Limits 1, Temperature ( C) Unacceptable Acceptable Supply Volyage (VDC) Max. Series Resistance (Ohms) Ambient Sensor Temperature ( C) Maximum Maximum Temperature/Voltage Temperature/Voltage Derating Derating Continuous ma ma Curve Curve (LU20-50X1-IS) (NEO-50_1-IS) 100 Unacceptable Acceptable Operating Voltage (VDC) Flowline Kobold 4 or or ma LU20-50X1-IS (NEO-50_1-IS) Electrical Loading Limits 1, Unacceptable (+) (-) Technology An ultrasonic sound wave is pulsed two times per second from the base of the transducer. The sound wave reflects against the process medium below and returns to the transducer. The microprocessor based electronics measure the time of flight between the sound generation and receipt, and translates this figure into the distance between the transmitter and process medium below. Acceptable Echotouch TM Ultrasonic Level Transmitter Supply Volyage (VDC) LEVEL, EC4, EC20, SAF1/SAF2/SAF3, FAST/SLOW, ALIN, OFF/ON, TANK, (value) SET MENU Holding down the [MENU] key will scroll the display in the following sequence. 6.3" (159 mm) Dimensions 4.9" (124 mm) 3.6" (92 mm) 1.3" (32 mm) Intrinsically Safe Control Drawing LU20CD NON-HAZARDOUS LOCATION Supply Any Approved I.S. Barrier Vdc 32.0 V Isc 130 ma Ca 0 µf La 0 µh Model LU20 Ultrasonic Level Transmitter Vmax = 32.0 V Imax = 130 ma Ci 0 µf Li 0 µh Control drawing for the LU20-50X1-IS NEO-50_1-IS ultrasonic level transmitter approved under the entity concept as an I.S. apparatus Control Drawing: LU20CD Rev. B* LR NRTL/C Intrinsically Safe/ Securite Intrinseque Exia For use in Hazardous Locations: Class I, Groups A, B, C & D Class II, Groups E, F & G Class III Temperature Code: T3C Intrinsically Safe when used with an approved I.S. barrier. Entity Parameters Vmax = 32.0 VDC Imax = 130 ma Ci = 0 µf Li = 0 µh Warning: Suitable for for Class I, I, Groups A, A, B, B, C & D; Class II, II, Groups E, E, F F & & G; G; Class III, T3C; III, T3C; when when used used with an with approved an approved I.S. I.S. barrier. Substitution of of components may may impair impair intrinsic intrinsic safety safety NEO-50_1-IS LU20-50X1-IS requirements for Intrinsically Safe requirements operation for Intrinsically Safe operation. 2.8" (71 mm) HAZARDOUS LOCATION Class I, Div I, Groups A, B, C & D Class II, Div I, Groups E, F & G Class III, Div I Part # Description Thread NEO-5001 General Purpose 2" NPT NEO-5061 General Purpose 2" G NEO-5001-IS Intrinsically Safe 2" NPT NEO-5061-IS Intrinsically Safe 2" G

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 Manual-NEO_5003-4_1-17

More information

Ultrasonic Level Transmitter Model LU20 Owner s Manual

Ultrasonic Level Transmitter Model LU20 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 15 Humbolt Street Los Alamitos, CA 972. If for

More information

Ultrasonic Level Transmitter Model LU30 Owner s Manual

Ultrasonic Level Transmitter Model LU30 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720. If

More information

Ricochet Alphasonic Level Transmitter Model LA15 Owner s Manual

Ricochet Alphasonic Level Transmitter Model LA15 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720. If

More information

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 500 Humbolt Street Los Alamitos, CA 9. If for

More information

MiniMe 2-Wire Ultrasonic Level Transmitter Model LU12/LU13/LU14 Owner s Manual

MiniMe 2-Wire Ultrasonic Level Transmitter Model LU12/LU13/LU14 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows: www.flowline.com. On-line Warranty Registration

More information

MiniMe Two-Wire Ultrasonic Level Transmitter Model LU11/12/13/14 Owner s Manual

MiniMe Two-Wire Ultrasonic Level Transmitter Model LU11/12/13/14 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows: www.flowline.com On-line Warranty Registration

More information

EchoSonic II Manual 09 JUL 08 Revision A

EchoSonic II Manual 09 JUL 08 Revision A EchoSonic II Manual 09 JUL 08 Revision A Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598-3015 Fax: (562) 431-8507 www.flowline.com 09 JUL 09 EchoSonic II 1 of 26 2 of 26 EchoSonic

More information

EchoNet Wireless Level Transmitter Model LN20 Owner s Manual

EchoNet Wireless Level Transmitter Model LN20 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720. If

More information

LPU-2127 User Manual

LPU-2127 User Manual LPU-2127 User Manual Doc #9004169 Rev A1, 04/15 Table of Contents Introduction... iii Warranty and Warranty Restrictions... iv Chapter 1: Specifications and Options... 1 Dimensions...1 Specifications...

More information

EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure

EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure QS300480 Rev B 2013 Flowline, Inc. All Rights Reserved Made in USA 10500 Humbolt Street, Los Alamitos, CA

More information

EchoSwitch Multi-Point Ultrasonic Level Switch Model LU71/72/73/75 Owner s Manual

EchoSwitch Multi-Point Ultrasonic Level Switch Model LU71/72/73/75 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows: www.flowline.com On-line Warranty Registration

More information

EchoSonic Two-Wire Ultrasonic Level Transmitter Model LU05/11/12/13 Owner s Manual

EchoSonic Two-Wire Ultrasonic Level Transmitter Model LU05/11/12/13 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows: www.flowline.com On-line Warranty Registration

More information

EchoSonic II Ultrasonic Level Transmitter LU27 Series Quick Start NEMA 4X Enclosure

EchoSonic II Ultrasonic Level Transmitter LU27 Series Quick Start NEMA 4X Enclosure EchoSonic II Ultrasonic Level Transmitter LU27 Series Quick Start NEMA 4X Enclosure QS300116 Rev C 2013 Flowline, Inc. All Rights Reserved Made in USA 10500 Humbolt Street, Los Alamitos, CA 90720 USA Tel:

More information

EchoSonic II Manual. LU23-0, LU27-0, LU28-0, LU29-0, LU23-1, LU27-1, LU28-1, LU29-1 Series

EchoSonic II Manual. LU23-0, LU27-0, LU28-0, LU29-0, LU23-1, LU27-1, LU28-1, LU29-1 Series EchoSonic II Manual LU23-0, LU27-0, LU28-0, LU29-0, LU23-1, LU27-1, LU28-1, LU29-1 Series Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598-3015 Fax: (562) 431-8507 www.flowline.com

More information

2-wire level transmitter

2-wire level transmitter Badger Meter Europa GmbH 2-wire level transmitter Model L2xx INSTALLATION AND OPERATION MANUAL July 2002 Version UF-L2xx-07/02-e Contents Contents Page 1. Installation 1 1.1 Mounting the instrument 1 1.2

More information

Ultrasonic level transmitter, non-contact

Ultrasonic level transmitter, non-contact Ultrasonic level transmitter, non-contact Type 8175 can be combined with... Compact, remote versions for level measurement up to 10 m Multi language menu control Interference echo filter Automatic calibration:

More information

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806 Series 500 Analog Transmitters by Data Industrial Data Industrial Owner s Manual Data Industrial 2/95 PN 72806 Table of Contents Introduction... 1 4-20 ma Loop Supply Requirements... 2 Installation...

More information

Echotel Model 910 Ultrasonic Level Switch

Echotel Model 910 Ultrasonic Level Switch Echotel Model 910 Ultrasonic Level Switch D E S C R I P T I O N Echotel Model 910 Level Switches utilize ultrasonic contact technology for measuring level in clean liquid applications. The dual conduit

More information

Echotel Model 961 Ultrasonic Level Switches for Hygienic Applications

Echotel Model 961 Ultrasonic Level Switches for Hygienic Applications Echotel Model 961 Ultrasonic Level Switches for Hygienic Applications D E S C R I P T I O N Echotel Model 961 Ultrasonic Level Switches use pulsed signal technology for superior performance in difficult

More information

Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow

Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow DESCRIPTION Echotel Model 338 is a two-wire, loop-powered noncontact transmitter for liquid level,

More information

Non-Submersible Industrial Pressure Transducer

Non-Submersible Industrial Pressure Transducer Non-Submersible Industrial Pressure Transducer KPSI Transducers Series 27, 28, 30 FEATURES Custom Pressure Ranges up to 2000 (13,790 kpa) Accuracy to ±0.10% FS Analog Outputs of 4-20 ma or VDC Welded 316

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading-edge microprocessor-based circuitry has nonvolatile memory. The display

More information

Symprobe RF Capacitance Level Transmitter Model LP75 Owner s Manual

Symprobe RF Capacitance Level Transmitter Model LP75 Owner s Manual Warranty, Service and Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: FLOWLINE Inc. 1000 Humbolt Street Los Alamitos, CA 90720 If

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 151 Graham Road P.O. Box 9010 College Station, TX 77842-9010 T: 800-876-1172 Int l: (979) 690-5560, Fax: (979) 690-0440 E-mail : globalw@globalw.com Radar Level Transmitters

More information

Instruction Manual Ultrasonic Level Meter Model: NUS

Instruction Manual Ultrasonic Level Meter Model: NUS Instruction Manual Ultrasonic Level Meter Model: NUS KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com Manual-NUS-8-13-02 Contents

More information

Mini Receiver. Off Peak System Control. Operation & Installation Guide for Power Line Carrier WARRANTY. (Applicable to Software Version

Mini Receiver. Off Peak System Control. Operation & Installation Guide for Power Line Carrier WARRANTY. (Applicable to Software Version MR9 WARRANTY Steffes Corporation ( Steffes ) warrants that the Steffes Power Line Carrier Mini Receiver is free from defects in materials and workmanship under normal use and service. Steffes obligation

More information

AUTOMATION. Operator s Manual. IRU-2xx4/3xx4 Series. Rev. A2, 11/08 Doc

AUTOMATION. Operator s Manual. IRU-2xx4/3xx4 Series. Rev. A2, 11/08 Doc AUTOMATION P R O D U C T S G R O U P, I N C. Operator s Manual IRU-2xx4/3xx4 Series Rev. A2, 11/08 Doc. 9002673 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com IRU-2xx4/3xx4

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading edge microprocessor-based circuitry has nonvolatile memory. The display

More information

THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC)

THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC) THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC) Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic, single-point level controller

More information

Echotel Model 910 Ultrasonic Level Switch

Echotel Model 910 Ultrasonic Level Switch Echotel Model 910 Ultrasonic Level Switch D E S C R I P T I O N Echotel Model 910 Level Switches utilize ultrasonic contact technology for measuring level in clean liquid applications. The dual conduit

More information

Echotel Trident 91S/92S Ultrasonic Level Switches

Echotel Trident 91S/92S Ultrasonic Level Switches Echotel Trident 91S/92S Ultrasonic Level Switches D E S C R I P T I O N The Trident 91S/92S detects single or dual point level in a wide variety of liquid applications. It is available with either an ma

More information

LT3000 ULTRASONIC LEVEL TRANSMITTER

LT3000 ULTRASONIC LEVEL TRANSMITTER LT3000 ULTRASONIC LEVEL TRANSMITTER Owner s Manual Specifications Installation Calibration Troubleshooting Warranty Drawings Distributed By: iprocessmart.com 14262 Doolittle Drive San Leandro, CA 94577

More information

User s Guide Instructions for Installation and Operation

User s Guide Instructions for Installation and Operation User s Guide Instructions for Installation and Operation 2.4 GHZ SPREAD SPECTRUM REMOTE CONTROLS Keyfob Transmitters Models KTX24SS1 KTXW24SS3 KTX24SS2 KTX24SS3 Wall Mount Models NTX24SS1 NTX24SS2 Remote

More information

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER

Model 5100F. Advanced Test Equipment Rentals ATEC (2832) OWNER S MANUAL RF POWER AMPLIFIER Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OWNER S MANUAL Model 5100F RF POWER AMPLIFIER 0.8 2.5 GHz, 25 Watts Ophir RF 5300 Beethoven Street Los Angeles, CA 90066

More information

Broadband Step-Up Transformer. User Manual

Broadband Step-Up Transformer. User Manual Broadband Step-Up Transformer User Manual 990-1930 09/2004 Introduction Introduction About this unit The APC Step-Up Transformer provides 220 V power from 60 VAC Broadband cable systems. Safety Electrical

More information

Symprobe RF Capacitance Level Transmitter Model LP75 Owner s Manual

Symprobe RF Capacitance Level Transmitter Model LP75 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 1000 Humbolt Street Los Alamitos, CA 90720. If

More information

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents KENCO ENGINEERING COMPANY P.O. BOX 470426, TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 http://www.kenco-eng.com e-mail: info@kenco-eng.com KENCO Loop Powered Magnetostrictive Transmitter

More information

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL Mid-West Instrument BULLETIN NO. ELEC-IM140/11A Replaces ELEC-IM140-141/09A ELECTRICAL Gauges with switches have one or two SPST or SPDT hermetically sealed adjustable set point reed switch assemblies.

More information

Level Transmitter / Controller / Indicator. 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance.

Level Transmitter / Controller / Indicator. 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance. Level Transmitter / Controller / Indicator 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance. 2.1 NEW Class 1, Division 1 Hazardous Areas Approved

More information

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K O P E R A T I N G I N S T R U C T I O N S WEL-200 TM W I R E L E S S E D G E L I N K 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales Inquiries: salessupport@emxinc.com

More information

LST100 Ultrasonic level transmitter for upstream oil and gas

LST100 Ultrasonic level transmitter for upstream oil and gas Data sheet DS/LST100-EN LST100 Ultrasonic level transmitter for upstream oil and gas Accurately track and measure the most expensive consumable on your site chemicals. Measurement made easy Features Keep

More information

Table of Contents. Safety Notices

Table of Contents. Safety Notices IM0081 2018-01 Table of Contents Product Overview... 3 Principle of Operation... 3 Closed-Loop Servo Control with the FC-24 Controller... 4 Adjustments... 5 LED Status Indicators... 6 Installation...7

More information

LR10, LR15, LR20, LR25 & LR30 Series Manual

LR10, LR15, LR20, LR25 & LR30 Series Manual Radar Liquid Level Transmitter LR10, LR15, LR20, LR25 & LR30 Series Manual Flowline, Inc. 10500 Humbolt Street, Los Alamitos, CA 90720 p 562.598.3015 f 562.431.8507 w flowline.com MN301700 Rev B1 Introduction

More information

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA Mobrey Ultrasonic Product Data Sheet February 215 IP245, Rev EA MSP422, MSP4RH, and MSP9GH Level Transmitters Non-contacting measurement with no moving parts Integral LCD and push-buttons as standard for

More information

CSIS CAPACITANCE TRANSMITTER. Intrinsically-Safe Continuous Output Level Transmitter INSTALLATION AND OPERATIONS MANUAL

CSIS CAPACITANCE TRANSMITTER. Intrinsically-Safe Continuous Output Level Transmitter INSTALLATION AND OPERATIONS MANUAL CSIS CAPACITANCE TRANSMITTER INSTALLATION AND OPERATIONS MANUAL Intrinsically-Safe Continuous Output Level Transmitter READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information on the CSIS

More information

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Gain Electronic Co. Ltd. Table Of Contents Safety Considerations ------------------------------------------------------------2

More information

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter ABB MEASUREMENT & ANALYTICS DATA SHEET Ultrasonic level LST400 Open channel flow transmitter 2 ULTRASONIC LEVEL LST400 / OPEN CHANNEL FLOW TRANSMITTER DS/LST400 EN REV. D Measurement made easy Reduced

More information

AUTOMATION. Operator s Manual. DCR-1005 and DCR Rev. A4, 10/08 Doc

AUTOMATION. Operator s Manual. DCR-1005 and DCR Rev. A4, 10/08 Doc AUTOMATION P R O D U C T S G R O U P, I N C. Operator s Manual DCR-1005 and DCR-1006 Rev. A4, 10/08 Doc. 9002664 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com

More information

GT-1050A 2 GHz to 50 GHz Microwave Power Amplifier

GT-1050A 2 GHz to 50 GHz Microwave Power Amplifier Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Giga-tronics GT-1050A Microwave Power Amplifier GT-1050A 2 GHz to 50 GHz Microwave Power Amplifier Operation Manual

More information

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual USL300 SNOW DEPTH SENSOR Revision 1.1.2 User Manual 1 Table of Contents 1. Introduction... 3 2. Operation... 3 2.1. Electrostatic Transducer... 4 2.2. SL300 Analog Board... 4 2.3. SL300 Digital Circuit

More information

FLOW SWITCH 600 Series Velocity Flow Sensor. Instruction Manual

FLOW SWITCH 600 Series Velocity Flow Sensor. Instruction Manual SWITCH 600 Series Velocity Flow Sensor Instruction Manual Ultrasonic Velocity Sensor using Doppler Technology Model: FS-600 Manual Release Date: November, 2009 ECHO Process Instrumentation, Inc. CONTENTS

More information

Indoor Contact Input Photosensor

Indoor Contact Input Photosensor General Information Indoor Contact Input Photosensor INSTALLATION SHEET Model# PPS-4 The Indoor Contact Input Photosensor (PPS-4) can be used with any Greengate lighting controller and may also be used

More information

MK372/Ultrasonic Sensor System. Installation & Setting up Instructions. Comprising. MK372 Indicator/Controller Ultrasonic Transmitter

MK372/Ultrasonic Sensor System. Installation & Setting up Instructions. Comprising. MK372 Indicator/Controller Ultrasonic Transmitter MK372/Ultrasonic Sensor System Installation & Setting up Instructions Comprising MK372 Indicator/Controller Ultrasonic Transmitter 1 Contents page Page 1.0 Overview 3 2.0 General Specification MK372 4

More information

2001A. 200KHz Function Generator Instruction Manual. 99 Washington Street Melrose, MA Phone Toll Free

2001A. 200KHz Function Generator Instruction Manual. 99 Washington Street Melrose, MA Phone Toll Free 2001A 200KHz Function Generator Instruction Manual 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com WARRANTY Global Specialties

More information

Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches

Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches Kotron Sentinel Models 8, 8 and 84 RF Point Level Switches D E S C R I P T I O N The Sentinel is a powerful multi-point level switch. The microprocessor-based circuitry has non-volatile memory, to protect

More information

Echotel Model 911/921 Ultrasonic Level Switches

Echotel Model 911/921 Ultrasonic Level Switches Echotel Model 911/921 Ultrasonic Level Switches D E S C R I P T I O N Echotel Model 911/921 ultrasonic level switches sense the presence or absence of liquids in a transducer gap by utilizing continuous

More information

POWER TRACE TM TASCO, INC.

POWER TRACE TM TASCO, INC. POWER TRACE TM Instruction Manual PTL610 TASCO, INC. HOW YOUR POWER TRACE TM OPERATES The Power Trace TM is composed of two primary components: the Receiver and the Transmitter. When the Transmitter is

More information

LST400 Ultrasonic level / open channel flow transmitter

LST400 Ultrasonic level / open channel flow transmitter Data sheet DS/LST400 EN Rev.C LST400 Ultrasonic level / open channel flow transmitter Measurement made easy Reduced installation cost Easy access terminations Integrated echo display makes for easy troubleshooting

More information

MODEL 8080PR3 Released on 11th Mar 2013

MODEL 8080PR3  Released on 11th Mar 2013 MODEL 8080R3 Released on 11 th Mar 2013 DUAL CHANNEL TEMERATURE INDICATOR WITH ALARMS 8080R3 DESCRITION The IME 8080R3 is a micro-controller based Digital Dual-channel Indicator with two relay outputs

More information

INSTRUCTION MANUAL LKG 601 Electrical Safety Analyzer

INSTRUCTION MANUAL LKG 601 Electrical Safety Analyzer INSTRUCTION MANUAL LKG 601 Electrical Safety Analyzer 110 Toledo Street Farmingdale, NY 11735 USA http://www.netech.org 510-USER-Manual Rev3 10/29/2007 Dear User, We appreciate your purchase of the LKG

More information

Princo MagneLevel Model LML

Princo MagneLevel Model LML Instrumentation designed with the user in mind Instruction Manual Princo MagneLevel Model LML Two-Wire Magnetic Coupled Level Transmitter 11 Nov 05 PRINCO INSTRUMENTS INC., 1020 INDUSTRIAL BLVD., SOUTHAMPTON,

More information

Solitel Vibrating Rod Level Switch

Solitel Vibrating Rod Level Switch Solitel Vibrating Rod Level Switch D E S C R I P T I O N Solitel Vibrating Rod Level Switches provide reliable level detection of powders and bulk solids. This compact, integral switch is suitable for

More information

PDB4. Four Channel Passive Direct Box USER'S GUIDE

PDB4. Four Channel Passive Direct Box USER'S GUIDE PDB4 Four Channel Passive Direct Box USER'S GUIDE IMPORTANT SAFETY INSTRUCTIONS - READ FIRST This symbol, wherever it appears, alerts you to important operating and maintenance instructions in the accompanying

More information

GT Series Grooving Tool

GT Series Grooving Tool GT Series Grooving Tool Tube & Pipe Cleaners Tube Testers Tube Plugs Tube Removal Tube Installation Operating and Maintenance Instructions www.elliott-tool.com TABLE OF CONTENTS Introduction... 4 Safety

More information

RPS /02 Effective for models with serial numbers beginning with "G".

RPS /02 Effective for models with serial numbers beginning with G. Instruction Sheet B2000 Cyclone Bender RPS-0097 0/02 Effective for models with serial numbers beginning with "G". IMPORTANT RECEIVING INSTRUCTIONS Visually inspect all components for shipping damage. If

More information

MP Series Radar Transmitter Installation & Operation Manual

MP Series Radar Transmitter Installation & Operation Manual IOM MP Series Radar Transmitter Installation & Operation Manual MP Series Radar Transmitter Installation & Operation Manual CONTENTS I. HANDLING AND STORAGE... 1 Inspection and Handling Disposal and Recycling

More information

f i r e - p a r t s. c o m

f i r e - p a r t s. c o m Model: CON 1001-1 INSTALLATION AND OPERATING INSTRUCTIONS SINGLE-FUNCTION WIRELESS REMOTE CONTROL SYSTEM FOR OPERATING VALVES WITH ON/OFF LATCHING SOLENOIDS IF YOU CANNOT READ OR UNDERSTAND THESE INSTALLATION

More information

Solitel Vibrating Rod Level Switch

Solitel Vibrating Rod Level Switch Solitel Vibrating Rod Level Switch DESCRIPTION Solitel Vibrating Rod Level Switches provide reliable level detection of powders and bulk solids. This compact, integral switch is suitable for high or low

More information

Radio Remote Controls Manual K Series

Radio Remote Controls Manual K Series Radio Remote Controls Manual K Series PN 52764 2010.12.20 Rev. 2 K Series radio control manual 1 Conductix Incorporated The technical data and images which appear in this manual are for informational purposes

More information

CS02 CAPACITANCE TRANSMITTER. Continuous Output Transmitter with Advanced Features INSTALLATION AND OPERATIONS MANUAL

CS02 CAPACITANCE TRANSMITTER. Continuous Output Transmitter with Advanced Features INSTALLATION AND OPERATIONS MANUAL CS02 CAPACITANCE TRANSMITTER INSTALLATION AND OPERATIONS MANUAL Continuous Output Transmitter with Advanced Features WWW.SOLUTIONSWITHINNOVATION.COM 60 GREAT HILL ROAD NAUGATUCK, CT 06770 TEL: 203-729-6434

More information

Echotel Models 344/345 Ultrasonic Non-Contact Transmitters for Level, Volume, or Open Channel Flow

Echotel Models 344/345 Ultrasonic Non-Contact Transmitters for Level, Volume, or Open Channel Flow Echotel Models 344/345 Ultrasonic Non-Contact Transmitters for Level, Volume, or Open Channel Flow D E S C R I P T I O N Echotel Models 344 and 345 are full-featured, ultrasonic non-contact transmitters

More information

9 PIECE TUNGSTEN CARBIDE HOLE SAW KIT. Model 90721

9 PIECE TUNGSTEN CARBIDE HOLE SAW KIT. Model 90721 9 PIECE TUNGSTEN CARBIDE HOLE SAW KIT Model 90721 Set up And Operating Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ

More information

CT-2 and CT-3 Channel Taggers OPERATION MANUAL

CT-2 and CT-3 Channel Taggers OPERATION MANUAL CT-2 and CT-3 Channel Taggers OPERATION MANUAL Trilithic Company Profile Trilithic is a privately held manufacturer founded in 1986 as an engineering and assembly company that built and designed customer-directed

More information

INSTRUCTION MANUAL INF Fax: (503)

INSTRUCTION MANUAL INF Fax: (503) INSTRUCTION MANUAL INF151 1-800-547-5740 Fax: (503) 643-6322 www.ueiautomotive.com email: info@ueitest.com Introduction Congratulations on your purchase of the INF151 infrared thermometer. Like all UEi

More information

Explosion Proof Page/Talk Paging Amplifier

Explosion Proof Page/Talk Paging Amplifier Industrial Communications Worldwide Explosion Proof Page/Talk Paging Amplifier Installation & Operation 7552-10 th Street. N.E. Calgary Alberta, Canada T2E W1 Ph: 403.25.3100 \ email:info@guardiantelecom.com

More information

User Manual. Smart-UPS On-Line. Uninterruptible Power Supply. Isolation Transformer Models: SURT001 and SURT002

User Manual. Smart-UPS On-Line. Uninterruptible Power Supply. Isolation Transformer Models: SURT001 and SURT002 User Manual Smart-UPS On-Line Uninterruptible Power Supply Isolation Transformer Models: SURT001 and SURT002 Isolation and Step-Down Transformer Models: SURT003 and SURT004 General Information Important

More information

BC145 SIGNAL ISOLATOR BOARD

BC145 SIGNAL ISOLATOR BOARD BC145 SIGNAL ISOLATOR BOARD 4/17 Installation & Operating Manual MN1373 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com to download

More information

Smart-UPS RT. Isolation Transformer Models: SURT001 and SURT002 Isolation and Step-Down Transformer Models: SURT003 and SURT004.

Smart-UPS RT. Isolation Transformer Models: SURT001 and SURT002 Isolation and Step-Down Transformer Models: SURT003 and SURT004. Smart-UPS RT Isolation Transformer Models: SURT001 and SURT002 Isolation and Step-Down Transformer Models: SURT003 and SURT004 User Manual 990-1673A, English, 11/2003 General Information General Information

More information

Rosemount 753R Remote Web Based Monitoring Indicator

Rosemount 753R Remote Web Based Monitoring Indicator Rosemount 753R Remote Web Based Monitoring Indicator Product Discontinued February 2010 Start Overview Rosemount 753R with Integral 3051S Pressure Transmitter Rosemount 753R with Remote Mounted HART Transmitter

More information

ULT-MVP O P E R A T I N G I N S T R U C T I O N S ULTRALOOP V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128

ULT-MVP O P E R A T I N G I N S T R U C T I O N S ULTRALOOP V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128 ULT-MVP ULTRALOOP O P E R A T I N G I N S T R U C T I O N S V E HI C L E L O O P DETECTOR 4564 Johnston Parkway, Cleveland, Ohio 44128 P. 800 426 9912 F. 216 518 9884 Sales Inquiries: salessupport@emxinc.com

More information

TABLE OF CONTENTS WARRANTY

TABLE OF CONTENTS WARRANTY DM4000 CONTROL SERIES CONTROLS Instruction Manual Field Programmable Digital Tachometer for Rate and Time P.O. Box 10 5000 W. 106th Street Zionsville, Indiana 46077 Phone (317) 873-5211 Fax (317) 873-1105

More information

TIA-952 Optical/Electrical Converter. Operating Instructions

TIA-952 Optical/Electrical Converter. Operating Instructions TIA-952 Optical/Electrical Converter Operating Instructions Terahertz Technologies Inc.169 Clear Road Oriskany NY 13424 (315) 736-3642 FAX (315) 736-4078 E-mail sales@terahertztechnologies.com 2/2012 Contents

More information

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009 User s Guide Publication number 34134-90001 April 2009 For Safety information, Warranties, Regulatory information, and publishing information, see the pages at the back of this book. Copyright Agilent

More information

Model 9305 Fast Preamplifier Operating and Service Manual

Model 9305 Fast Preamplifier Operating and Service Manual Model 9305 Fast Preamplifier Operating and Service Manual This manual applies to instruments marked Rev 03" on rear panel. Printed in U.S.A. ORTEC Part No.605540 1202 Manual Revision B Advanced Measurement

More information

Mid-West. Instrument. Model 142 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL

Mid-West. Instrument. Model 142 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL Mid-West Instrument Model 142 Electrical Installation and Operating Instructions BULLETIN NO. ELEC. IM142/14A Supersedes ELEC. IM142/10A ELECTRICAL Gauges with switches have one or two SPST or SPDT hermetically

More information

Level Lance Model 5100

Level Lance Model 5100 Sales Manual Section 100 Product Specification Model 5100 Level Lance Model 5100 GENERAL DESCRIPTION The Robertshaw Model 5100 Level-Lance is a microprocessor based, advanced technology On-Off level detection

More information

Kotron Model 82 CE RF Level Transmitter

Kotron Model 82 CE RF Level Transmitter Kotron Model 82 CE RF Level Transmitter DESCRIPTION The Kotron Model 82 RF Capacitance transmitter is one of the most cost effective level transmitters available today. Compact in size, it employs state-of-the-art

More information

HP 86290B RF PLUG-IN GHz HEWLETT PACKARD

HP 86290B RF PLUG-IN GHz HEWLETT PACKARD OPERATING AND SERVICE MANUAL. HP 86290B RF PLUG-IN 2.0-18.6 GHz HEWLETT PACKARD COPYRIGHT AND DISCLAIMER NOTICE Copyright - Agilent Technologies, Inc. Reproduced with the permission of Agilent Technologies

More information

Instruction Sheet REB SERIES. Rotating Sliding Base REB18

Instruction Sheet REB SERIES. Rotating Sliding Base REB18 Instruction Sheet REB SERIES Rotating Sliding Base REB14 REB18 THANK YOU Thank you for purchasing the REB Series Rotating Sliding Base. Please read these instructions thoroughly before installing this

More information

Echotel Model 355 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow

Echotel Model 355 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow Echotel Model 355 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow D E S C R I P T I O N Echotel Model 355 is a two-wire, loop-powered, noncontact ultrasonic transmitter

More information

Radar Level Measurement micropilot FMR 130 for stilling wells

Radar Level Measurement micropilot FMR 130 for stilling wells Technical Information TI 258F/24/ae Radar Level Measurement micropilot FMR 130 for stilling wells Smart transmitter for non-contact measurement in metallic by-pass pipes and stilling wells Suitable for

More information

Overboard Recovery Communications Apparatus (ORCA ) RX-102 Receiver User s Manual

Overboard Recovery Communications Apparatus (ORCA ) RX-102 Receiver User s Manual Overboard Recovery Communications Apparatus (ORCA ) RX-102 Receiver User s Manual This page intentionally left blank 3 For technical support, contact BriarTek at 703-548-7892 or through our website at

More information

The transducer component converts the measured signal and displays the actual value.

The transducer component converts the measured signal and displays the actual value. Digital inductive conductivity transmitter System Integration Provides low Total Cost of Ownership PEEK/PPA version for CIP applications TEACH IN and SIMULATION Function Approval PVDF Version PEEK Version

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MEMFLO MFT2 2-WIRE FLOW TRANSMITTER (877) 356-5463 (p) 330-331-7331 (f) 330-331-7172 www.flo-corp.com 2017 FLO-CORP REVA 1116 1 DESCRIPTION Please read carefully! No liability can

More information

Using the USB Output Port to Charge a Device

Using the USB Output Port to Charge a Device Table of Contents ----------------------------------- 2 Features ----------------------------------------------- 3 Controls and Functions ---------------------------------- 4 ER210 Power Sources -----------------------------------

More information

Operating Instructions for Pressure Sensor with Ceramic Sensor Element. Model: SEN-9601

Operating Instructions for Pressure Sensor with Ceramic Sensor Element. Model: SEN-9601 Operating Instructions for Pressure Sensor with Ceramic Sensor Element Model: SEN-9601 We don t accept warranty and liability claims neither upon this publication nor in case of improper treatment of the

More information

WORLD-BEAM QS30 Adjustable-Field Sensors

WORLD-BEAM QS30 Adjustable-Field Sensors with Background Suppression Midsize sensors featuring extended range and background suppression mode Features Bipolar discrete outputs, PNP and NPN 128 element photo receiver for superior performance on

More information

Owner s Manual & Safety Instructions

Owner s Manual & Safety Instructions Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s

More information

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER SAFE INSTALLATION MANUAL (FM APPROVAL) -WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe/explosion-proof) MODEL B6U/B6U-B BEFORE USE... SAFETY PRECAUTIONS This manual describes

More information