Instruction Manual Ultrasonic Level Meter Model: NUS

Size: px
Start display at page:

Download "Instruction Manual Ultrasonic Level Meter Model: NUS"

Transcription

1 Instruction Manual Ultrasonic Level Meter Model: NUS KOBOLD Instruments Inc Parkway View Drive Pittsburgh PA Phone (412) Fax (412) Manual-NUS

2 Contents Contents General Specifications Mechanical Installation General Installation Standpipe Mounting Standard Mounting Configuration Electrical Connection Wiring Wiring Interconnection Wiring Diagram Operation Function Display Operation Setup Overview Measured Value and Status Display Quick Meter Setup for Normal Applications Linearization Current Output Adjustment Echo Quality Additional Input Possibilities Simulation and Function Test Interlocking Adjustment of the LED Display (when equipped) Errors and Warnings Diagnostics and Error Elimination Error Codes Dimensions Error Analysis V-H Setup Matrix Quick Meter Setup for Normal Applications: Overview...35 Manufactured and Marketed by: Kobold Instruments Inc Parkway View Drive Pittsburgh, PA Fax: Page 2

3 KOBOLD NUS Level Transmitter User Instructions CAUTION: For safety reasons, please read the cautionary information located at the end of the manual before attempting installation. These devices may only be installed, used and maintained by skilled personnel, who are familiar with this service manual and can observe applicable regulations regarding industrial safety and accident prevention. 1. General The KOBOLD NUS is intended for use in applications where level measurement is desired and the level data needs to be indicated locally and/or transmitted to a location remote from the level transmitter. The NUS may be equipped with a 4-digit, 7-segment red LED display for local level indication that may be scaled in the users desired engineering units. The NUS also contains a level transmitter that outputs a 4-20 ma, analog signal. This signal is proportional to the tank level measured by the instrument. The NUS is readily adjusted and scaled by the user via internally accessible buttons. The NUS sensor is made of PVDF. This highly chemical-resistant material allows the NUS to be used in many difficult industrial applications, especially in the chemical industry. The ultrasonic sensor emits ultrasonic pulses, which are reflected by the medium to be measured. These "echoes" are then received by the same sensor. The time taken by the ultrasonic pulses (to the material and back) is temperaturecompensated before measurement results are sent to the analog output and digital display. Page 3

4 2. Specifications Housing: Epoxy-Coated Aluminum, Polycarbonate Sensor and connection: PVDF Measuring range: Liquids: up to 23 (2 model) Liquids: up to 13 (1-1/2 model) Bulks: up to 15 (2 model) Bulks: up to 6 (1-1/2 model) Measuring accuracy: 0.25% of maximum range Resolution: +/ Deadband or block distance: 10 (1-1/2 model), 16 (2 model) Frequency: 50 khz / 70 khz Pulse frequency: 0.5 to 3 Hz (depending on electronics version) Radiation beam: 5.5 conical Min. delay time: approx. 5 s Output signal: 4 to 20 ma Load: max. 600 Ohm Process temperature: -40 to +176 F (-40 to 80 C) Ambient temperature: -4 to +140 F (-20 to 60 C) Max. operating pressure: 30 PSIG (3 bar Abs.) Protection class: NEMA 4X / IP 67 Construction: Combination sensor and electronics Process connection: 1½ MNPT, 2 MNPT Electrical connection: 1 m cable(s) with ½ conduit connection Power supply: 12 to 36 VDC (2-wire) 90 to 127 VAC, Hz. (4-wire) Display (when equipped): 4-digit, red LED Display, digit height: 0.3 (7.62 mm), programmable decimal point adjustment Display range: Page 4

5 3. Mechanical Installation 3.1. General Installation Install the unit to the tank with appropriately sized fittings. Take care not to place stresses on the electronics housing. Use an appropriately sized wrench and do not overtighten the sensor during installation (maximum torque: ft-lb.). Housing is not Rotatable! DO NOT apply force to the electronics housing! Max. Torque Ft-lb. Due to decaying behavior of the ultrasonic sensor, there is an area directly below the sensor face where no pulses can be received. This so-called "Deadband" is very important for the correct operation of the sensor. This distance must be taken into consideration during installation, as it is the minimum distance allowed between the sensor face and the maximum filling state. The deadband ranges are: 10 (1-1/2 model) or 16 (2 model) Mount the sensor sufficiently high enough so that even with maximum filling of the container, the deadband space is never entered. Media that enters the deadband space will cause a malfunction (See the following section on Standpipe Mounting ). Never mount two ultrasonic level-measuring devices in one container, because the two devices can impair each other's function. Do not mount the sensor at the center of container's cover. Always install the sensor perpendicular to the material surface. Avoid measurements through the fill stream. Page 5

6 3.2. Standpipe Mounting If the desired maximum media filling height will enter the deadband space, the sensor must be installed on a short standpipe to prevent improper operation. No material may be allowed to form on the pipe ends. The recommended dimensions of the short standpipe are approximate values, which you can vary slightly if required. Keep the standpipe height as short as possible. The inner side of end-piece must be smooth no edges, no welding seams. During operation, noise echoes (that may be generated by a short feed pipe for example) may be faded out with the function (fade out noise-echoes, see page 20). Standpipe diameter and height D min (in.) L max (in.) L D 3.3. Standard Mounting Configuration Mounting with 1-1/2 or 2 NPT Welded Sleeve Page 6

7 4. Electrical Connection 4.1. Wiring When utilizing the current output, use a shielded two-wire cable. For optimal electromagnetic compatibility, the shield of the cable should be grounded at the control room or at the nearest equipment ground point. The connection at the electronics housing uses a ½ conduit connection and an integral 1m cable for the 2-wire version, or a ½ conduit connection and two integral 1m cables for the 4-wire version Wiring Interconnection The ½ conduit connection allows for a wide range of cable terminations into a suitable junction box using flexible conduit, standard thinwall, or rigid conduit. A cable gland may be used on the 2-wire units where a flexible cable interconnection is permitted. PLEASE NOTE: The 2-wire units are 4-20mA loop-powered devices designed for use with an externally supplied VDC power source. The 4-wire units are for use with VAC, Hz power and provide an internal power source for the 4-20mA output signal. DO NOT CONNECT THE 4- WIRE UNIT TO AN EXTERNALLY POWERED CURRENT LOOP OR DAMAGE TO THE ELECTRONICS WILL OCCUR. Page 7

8 4.3. Wiring Diagram 2-wire 4-wire (2 cable) + - Brown (+) 24 VDC / 4-20 ma 2-wire Black (-) G 2 1 AC ~ (1) AC ~ (2) Ground Grn/Yel Brown (+) ma Black (-) Attention! In the event that the current output is not used, the output must be jumpered with a 250-ohm resistor to allow for display operation. Page 8

9 5. Operation The NUS Series offers a full range of user programmable functions and displays, such as: zero & span adjustment, sensor temperature, and echo quality. The programming features and display values are accessed via a programming matrix. This matrix has both a vertical (V) and horizontal (H) position that is shown on the function display. The instruction manual references these matrix positions in a VnHn format, where n = the vertical or horizontal matrix position. Example: V3H5 = 3 rd vertical matrix position and the 5 th horizontal matrix position. Navigation through the programming and status display matrix is performed via the function keys per section 5.2. The complete programming matrix is shown in: Section 9: V-H Setup Matrix. ATTENTION: Please review and familiarize yourself with the setup matrix information shown in Section 9 and the Quick Setup Adjustment shown in Section 5.5 and Section 10 before proceeding. Page 9

10 5.1. Function Display By removing the back cover, the internal electronics of the transducer become accessible. An LCD Display is provided for adjustments and visual display of functions. During operational disturbances, the electronics differentiate between an error and a warning. (Compare also: Section 6, Errors and Warnings ) 2- wire Electronics detects an error The bargraph is flashing within the display The current output assumes the user selected fault value of: 3.8mA, 22mA, or hold last value An error-code in V9H0 is displayed Electronics detects a warning The device continues to measure An error-code in V9H0 is displayed 4- wire Electronics detects a error The red LED next to function display flashes The bargraph is flashing within the display The current output assumes the user selected fault value of: 3.8mA, 22mA, or hold last value An error-code in V9H0 is displayed Electronics detects a warning The red LED next to function display lights up The device continues to measure An error-code in V9H0 is displayed Page 10

11 5.2. Operation The electronics are adjusted while viewing a 10 x 10 LCD matrix. In simplest case, adjustment is carried out only via three matrix fields. Display elements Parameter VH-Position Bargraph display -Display: Flow or Echo Quality -Flashes with disturbance The matrix field is shown under the letters VH. The appropriate parameter is displayed to the left. The bargraph flashes in case of error and displays the current or the quality of echo. Table 5.1 Function of Keys Keys Function Selection of matrix fields and Inputting Parameter or and Confirmation of input or Selection of vertical matrix position Selection of horizontal matrix position Return to V0H0 Activates the selected matrix position. Digit is flashing. Increases the displayed parameter Decreases the displayed parameter Resets the recent input value to the original value, if it is not confirmed with V or H key yet. Accepts the currently displayed parameter and moves to the next matrix position Matrix interlocking / unlocking (see also Section 5.11) and and Matrix interlocking, 9999 appears in V9H9 Matrix unlocking, 333 appears in V9H9 Page 11

12 5.3. Setup Overview Alignment Linearization no yes Volume measure in linear container Semi-automatic linearization thru >Liters out< Manual input of a linearization curve Special case: Cylindrical Horiz. tank Adjust current output analog digital Echo-quality Time-delay Noise-echo fade out First echo factor Simulation 5.4. Measured Value and Status Display Matrix field Table 5.2 Measured Value and Status Information Measured value display Display Matrix field Status display Display V0H0 Tank % full based on programmed span V9H0 Current error code V0H8 V0H9 Distance from sensor face to medium in user s units (ft/m) Bargraph shows echo quality Height of medium from empty point (V0H1) in user s units (ft/m) Bargraph shows echo quality V9H1 V9H2 Last error code Sensor and electronics identifier V9H8 Output current value in ma V9H3 Unit and software identifier V3H5 Temperature in Degrees C V3H2 Echo quality (1-10) Page 12

13 5.5. Quick Meter Setup for Normal Applications Table 5.3 Quick Meter Setup Step VH Input Text 1 V9H5 333 Reset to default factory parameters 2 V8H2 (0 / 1) User s desired measurement unit 0: meters (default) 1: feet 3 V0H1 E (m/ ft) Empty distance in user s units (actual value), 4mA setpoint 4 V0H2 F (m/ ft) Net distance medium will move to achieve a full tank in user s units (= empty distance - full distance), 20mA setpoint 5 V0H3 0 4 Application type (see below)! V0H3: Application type 0: Normal setting for most liquid applications (default) Full = 20 ma 1: Fast response setting. Empty = 4mA 2: Liquid applications for tanks with a domed cover. 3: Bulk materials with grain size > 5/32 (4mm) 4: Conveyer allocation Reset With a Reset, most adjustments for the device are canceled and the default factory settings apply. The following parameters do not change to factory default: All inputs for Linearization (V2H0 V2H3) the tag number (VAH0) and the measuring units (V8H2) Page 13

14 Attention: V8H2 Measuring Units The measuring units are not changed by a Reset. It may only be changed manually. If the measuring units are changed later, all of the changed following inputs must be repeated. Measurement Display: V0H0: Filling height in % V0H8: Distance in m / ft V0H9: Filling height in m / ft Please Note! All following inputs (linearization, current output and fixed target fadeout) must be entered in the user s selected measuring unit. NOTE: THE FEATURES INDICATED IN THE FOLLOWING SECTIONS (SECTIONS 5.6 THROUGH 5.10) ARE SPECIAL FEATURES AND ARE NECESSARY ONLY FOR SPECIAL TANK CONFIGURATIONS AND / OR APPLICATIONS WITH UNIQUE OPERATING CONDITIONS Linearization Input of a Linearization Curve The input of the linearization curve must take place in the user s selected measuring units. Prior to entering a linearization curve, it is recommended that the linearization table is cleared to eliminate previously entered points with: V2H0 = 4. A linearization curve can consist of maximum of 11 points. The linearization points must always be entered such that the volume units increase for each linearization point as the tank level rises. Activate the linearization curve after inputting all value pairs with V2H0 = 1. If desired, the points of linearization curve may be modified individually by simply entering a new value pair. The corrected curve must also increase in volume from the previous point. Page 14

15 Adjustment of Current Output After linearization, the output current follows the linearization curve to provide an accurate volume measurement. Note: Errors and Warnings in V9H0 During the input of a linearization curve, the current output is subjected to an error and the unit stops measuring any further. The following linearization related errorindications may appear. E605: Display during the input of linearization curve. This error-indication disappears if the linearization curve is activated. E602: The linearization curve is not indicating a continuously rising volume level. In V2H1, the number of the last entered correct value pair appears automatically. Enter the new value in the next line of the table in V2H2 and V2H3. E604: The linearization curve consists of less than two value pairs. Supplement your inputs with additional value pairs. Measurement display after linearization: V0H0: Display in user-defined units V0H8: Distance in m / ft V0H9: Filling height in m / ft Four Possibilities " Volume measurement with linear relation; filling state-volume: V2H0 = 5 BD Filling ht. Full=V 100% e.g.2000 l Empty Volume The Tank Full volume is input at V2H5. A linear level / volume relationship is assumed at all other points. Note! The volume in V2H5 is automatically assigned to the filling height at the tank full point. Page 15

16 Table 5.4 Volume Measurement with Linear Relation # VH Input Text 1 V2H0 4 H Delete 2 V2H0 5 H Linear 3 V2H5 e.g H Volume (Full Scale) V 100% (e.g l) # Inputting a Linearization Table for a Container through Volume Addition 4 m BD Filling ht. Full e.g l Empty The container is filled or emptied in a controlled manner, measuring the volume added at each linearization point. The known total volume is entered at each point. The level is automatically registered. Table 5.5 Linearization Through Volume Addition # VH Inputs Text 1 V2H0 4 H Delete 2 V2H0 3 H Measuring contents in liters 3 V2H1 7 H Line number 4 V2H2 e.g m H Level 5 V2H3 e.g l H Volume input 6 V2H1 6 H Line number After entering all values V2H0 1 H Activate table Page 16

17 $ Manual Input of a Linearization Table BD Full 0.4 m Empty e.g. 100 l For a linearization curve, a maximum of 11 pairs of level and volume can be entered. Table 5.6 Manual Input of a Linearization Table # VH Input Text 1 V2H0 4 H Delete 2 V2H0 2 H Manually 3 V2H1 1 H Line No. 4 V2H2 e.g m H Level input 5 V2H3 e.g l H Volume input 6 V2H1 2 H Line No. After inputting all value pairs V2H0 1 H Activate table % Special Case: Horizontally Mounted Cylindrical Tank Using the following example, with the diameter = 1, the linearization curve for any cylindrical and horizontally mounted tank, can be calculated. 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% BD V level % = V total V % 100 Page 17

18 Table 5.7 Line No. V2H1 Horizontally Mounted Cylindrical Tank Level V2H2 Volume V2H3 % User's value % User's value Current Output Adjustment Instructions for current output: The current output (zero and span) may be adjusted to a percentage of the empty and full distances entered previously in V0H1 and V0H2 (see Table 5.3). The current output may be inverted (if desired), so that the value in V0H5 is larger than value in V0H6. That means on increasing measured values, the current signal decreases. Integration time (V0H4): The integration time causes damping of current output and thus a delayed measured value on LCD Display. With a turbulent liquid, a stable display can be achieved by means of the integration time (0-255 sec) Output behavior on error (V0H7) 4- wire 2- wire 10 % 2.4 ma 3.8 ma +110 % 22 ma 22 ma 4 ma Threshold: This threshold ensures that the current value will not fall short of 4 ma during operation. Page 18

19 Errors and Warnings in V9H0 E620: The current output is outside of the adjusted range (smaller than 3.8 ma, greater than 20.5 ma). Check the setting and the adjustments of the current output Two possibilities of the adjustment 1. Current output: linear The current varies from 4 to 20mA as level changes. Table 5.8 Current Output Adjustment (Linear) # VH Inputs Text 1 V8H1 e.g. 0 H Current output 0: linear 4 20 ma 1: linear 4 20 ma with 4 ma threshold 2 V0H5 e.g. 10 % H Level for 4 ma 3 V0H6 z. B. 90 % H Level for 20 ma 4 V0H4 e.g. 20 s H Integration time 5 V0H7 e.g. 1 H Output on disturbance 0: 10 % 1:+ 110 % 2: HOLD (retain last measured value) Filling ht. BD V0H6 90% 4 ma V0H5 10% 20 ma Page 19

20 2. Current Output: Digital The current value of 4 and 20 ma (or 8 and 16 ma) for switching and automatic level. Table 5.9 Current Output Adjustment (Digital) # VH Input Text 1 V8H1 e.g. 2 H Current output 2: digital 4/ 20 ma 3: digital 8/ 16 ma 2 V0H5 e.g. 10 % H Switch point min. 4 or 8 ma 3 V0H6 e.g. 90 % H Switch point max. 20 or 16 ma 4 V0H4 z. B. 10 s H Integration time 5 V0H7 e.g. 1 H Output on error: 0: 10 % 1: +110 % 2: HOLD (retain last measured value) Filling ht. BD V0H6 90% V0H5 10% 4 ma 20 ma 8 ma 16 ma Page 20

21 5.8. Echo Quality The echo quality of ultrasonic signal is given out in V3H2 in steps from 1 10 and displayed in matrix fields V0H8 and V0H9 via a bargraph display. Bad echo quality through: Steam, dust, high temperature, foam, larger measuring distance, etc. No impairment of the echo with smooth liquid surface: Place the sensor Use the echo quality display (via bargraph) during mounting process, in order to find the correct mounting location. Fixed mountings, which look too far into the detection range of the sensor, reflect the echo. If an unwanted signal is detected e.g. during mounting, another location can be selected or the noise-echo may be suppressed. Page 21

22 Noise Echo Suppression The noise echo suppression feature is useful if, instead of the actual level, obstructions inside the container are detected. Up to three, noise echo signals can be suppressed. The suppression should be attempted when the tank is empty or as near empty as possible. Echo Step 1 Step m max. 3 Noise-echo 3 m Good echo Distance Table 5.10 # VH Input Text 1 V0H8 Indicates the distance to the false echo. Wait until a stable value is displayed. 2 V3H0 e.g H Known distance of the medium's surface level (e.g. 3 m) Note for 2- wire: Wait for approx. 40 s 3 V0H8 Meas. distance approx. 3 m? YES Fixed target is faded out NO Repeat procedure Page 22

23 5.9. Additional Input Possibilities Temperature The current temperature at the sensor is shown in V3H5. Temperature upper-limit Exceeding of the upper temperature limit of 80 C will be indicated in field V3H5 by storing the value above 80 C Echo loss - delay time The input of a delay time in V8H3 delays an alarm due to short term echo loss (e.g. by foam). For normal level measurements, the delay time should not be selected smaller than 30 s. # VH Input Text 1 V8H3 e.g. 80 H The measuring point reacts only after 80 s on the echo loss and switches the alarm E 641. Factory setting: 60 s Selectable: s Page 23

24 Actual Level: A false level reading in V0H9 (e.g. through temperature changes or material stratification) can be corrected by inputting the actual level in V3H1. The input of an actual level automatically corrects the alignment First echo factor In containers with strongly rounded off covers (arched covers) double echoes may the generated, which result in the display of a much lower level. By setting the first echo factor to»maximum«, double echoes can be switched off. # VH Input Text 1 V3H4 2 H First echo factor maximum Simulation and Function Test Simulation offers the possibility to simulate and test the functions of the unit. Error and Warning in V9H0 E613: Display during the duration of simulation. After termination of the simulation, return to the normal measuring operation. Simulation off: V9H6: 0 In case of a power failure, the device returns automatically into normal measuring operation! Table 5.11 Simulation and Function Test Height Simulation # VH Input Text 1 V9H6 1 H Simulation height 2 V9H7 e.g H Simulated height (e.g. 2 m) 3 V9H8 V0H0 Display current (also appears on bargraph) Display height or level or volume 4 V9H6 0 H Simulation off Current Simulation # VH Input Text 1 V9H6 3 H Simulation current 2 V9H7 e.g. 14 H Simulated current (e.g. 14 ma) 3 V9H8 Display current (also appears on bargraph) 4 V9H6 0 H Simulation off Page 24

25 Volume Simulation # VH Inputs Text 1 V9H6 2 H Simulation of Volume 2 V9H7 e.g H Simulated Volume (e.g. 100 l) 3 V9H8 V0H0 Display current (also appears on bargraph) Display volume (if no linearization curve is entered, volume corresponds to filling level.) 4 V9H6 0 H Simulation off Interlocking After inputting all the parameters, the matrix can be locked. " Interlocking the matrix by entering a three-digit code number of any value other than 333 in V9H9: # VH Input Text 1 V9H9 e.g. 332 H Interlock 2 In V9H9 appears 332. All matrix fields other than V9H9 are blocked. Unlocking the matrix by entering the value 333 in V9H9: # VH Input Text 1 V9H9 333 H Unlock 2 In V9H9 appears 333. The blocking of matrix fields is removed. Page 25

26 # Interlocking via the keypad P = Protect - + V H F = Free - + V H Note! By interlocking via the keypad, the programming through the keypad or display is blocked. Matrix positions can be displayed but cannot be accessed. Removal of blocking is possible only through the keypad. Page 26

27 5.12. Adjustment of the LED Display (when equipped) Note! Before the adjustment of the LED display, the analog output must be adjusted first. In case of subsequent programming modifications that would affect the output signal, it is likely that the display would need to be readjusted. If the current output is not used, the output must be jumpered with a 250-ohm resistor to allow for display operation. Loosen and remove the four cross-slotted screws then remove the display cover plate. Key 1 Key 2 Key 1: Key 2: Keys 1+2 : Downward and selection of Menu Upward and selection of Menu Enter menu selection for adjustment or quit adjustment mode Decimal point Press key 2 until: " dp " is displayed. Press key 1+2: Enter menu for adjustment: " " Press key 2 or 1: for up and down: " " Press key 1+2: Quit adjustment mode and return to Menu " dp " Zero point (value to be displayed at 4 ma) Press key 2 until: " ZP 4 " is displayed. Press key 1+2: Enter menu for adjustment; " 0.00 e.g.: (0.0 Liters) Press key 2 or 1: for up and down Press key 1+2: Quit the adjustment mode and return to Menu " ZP 4 " End point (value to be displayed at 20 ma) Press key 2 until: " EP20 is displayed. Press key 1+2: Enter menu for adjustment: " 0.00 " Press key 2 or 1: for up and down: " " e.g.: (60 Liters) Press key 1+2: Quit the adjustment mode and return to Menu "EP20" Page 27

28 Damping Press key 2 until: " FILt " is displayed. Press key 1+2: Enter menu for adjustment: " 0.3 " (min. = 0.3 sec.; max. = 20.0 sec.) Press key 2 or 1: for up and down: " 1.5 " (1.5 sec.) Press key 1+2: Quit the adjustment mode and return to Menu " FILt " Range Exceeded (indication if below 4 ma or above 20 ma) Indicates " HI " if the upper limit or " LO " if the lower limit is exceeded Press key B until: " HILO " is displayed. Press key 1+2: Enter menu for adjustment: " off " = indication inactive Press key 2 or 1: for up and down: " on " = indication active Press key 1+2: Quit the adjustment mode and return to Menu " HILO " Indication: " HI "= Current exceeds the upper limit of the measuring range (I > 20 ma), " LO "= Current is below the lower limit of the measuring range (I < 4 ma) Caution: When the "HILO" indication is inactive, exceeding the upper limit of the display range ( ) results in the error code "Er06" being displayed Return to Measuring Mode Depending upon the selected menu point, press Key 1 or 2 from one to eight times. Page 28

29 6. Errors and Warnings 6.1. Diagnostics and Error Elimination The electronics differentiate between an error and warning during operation. 2-wire: Electronics detect an error bargraph flashes within the digital display current output takes the selected value ( 10 % = 3.8 ma, +110 %, HOLD) an error-code in V9H0 is given out Electronics detect a warning unit continues to measure an error-code in V9H0 is given out 4-wire: Electronics detect an error red LED lights up bargraph flashes within the digital display current output takes the selected value ( 10 % = 2.4 ma, +110 %, HOLD) an error-code in V9H0 is given out Electronics detect a warning red LED flashes unit continues to measure an error-code in V9H0 is given out Page 29

30 6.2. Error Codes Code Type Cause and Elimination E 101 Error Checksum error EEPROM/ FRAM call Kobold E 102 Warning Checksum error EEPROM/ FRAM call Kobold E 103 Warning Initialization begins. If error persists, initialization cannot be started. E 106 Error Download in progress Wait, until the process is complete. E 110 E 121 Error Execute Reset. If error persists, electronic device error call Kobold E 116 Error Error during Download Press Reset, or start a new Download with corrected data. E 125 Error Sensor failure Check sensor connection. If error persists, call Kobold E 261 Error Error in temperature sensor (interruption) call Kobold E 501 Error Sensor electronics stops detection call Kobold E 602 Warning Linearization curve does not rise continuously Check with manual linearization curve. Does the volume increase with the filling height? E 604 Warning Linearization curve consists of less than 2 points Check manual linearization curve and provide with additional points. E 605 Error Linearization table not available appears during input of linearization curve. Activate all points after inputting linearization curve. E 613 Warning Simulation On After running simulation, switch to normal measuring operation. Simulation Off: V9H6: 0 E 620 Warning Current out of nominal range Check alignment and adjustments of current output. E 641 Error No echo to be evaluated Short time echo loss e.g. due to foam or during start up. Check alignment and operating voltage. If the error persists, call Kobold E 661 Warning Temperature on sensor too high (more than 80 C) Check Measuring conditions. Page 30

31 7. Dimensions Page 31

32 8. Error Analysis Error Analog output Possible cause Remedy Measured value jumps sporadically on constant level and turbulent liquid surface or if the stirring fans run. 20 ma Signal is affected by turbulent liquid surface or stirring fans? Increase the Integration time While stirring fans are within measuring range, check sensor position. expected occurs Relocate the sensor. Choose application parameter 0 or 2 in V0H3 4 ma t With constant level, the measured value jumps to a lower value or remains too low constantly. 20 ma Multiple echoes? Choose application parameter 2 in V0H3 Choose larger first echo factor 1 or 2 in V3H4 expected occurs 4 ma t Page 32

33 Error Analog output Possible causes Remedy Digit-segment flashes Measured value in V0H0 too low Reaction of current output depends upon adjustment in V0H7 V0H7= 0 10 % 2.4 ma or 3.8 ma V0H7= % 22 ma V0H7= 2 HOLD last value is retained D m/ft (V0H8) 20 ma expected Error code in V9H0 E641 in V9H0 Echo too weak or foam on surface Distance D in V0H8 too large? Which error code? Proceeding further depends on error code. Check sensor position. Adjust the sensor mounting position. Multiple echoes? Gas-accumulation over surface. Check sensor position. Adjust the sensor mounting position. Linearization wrong? Enter a new linearization curve. occurs Measured value in V0H0 too large D m/ft (V0H8) 4 ma t 20 ma occurs Current output wrong? Distance D in V0H8 too small? Check values in V0H5 and V0H6 and possibly input new values. Noisy installation in measuring range. Check standpipe dimensions. Check sensor position. Adjust the sensor mounting position. Select parameter 0 or 2 in V0H3. Execute false echo fade out. expected Linearization wrong? Enter a new linearization curve. 4 ma t Current output wrong? Check values in V0H5 and V0H6 and possibly input new values. Page 33

34 9. V-H Setup Matrix NUS H0 H1 H2 H3 H4 H5 H6 H7 H8 H9 Basicsettings V0 Meas. value User's unit Adjustment»Empty«m/ft Adjustment»Full«m/ft Application 0: Liquid 1: Quick change 2: Arched cover 3: Rough solids 4: Conveyer belt. Integration time s Default: 3 s Seconds Value for 4 ma Default: 0 % Switching point for 4 ma 8 ma Value for 20 ma Default: 100 % Switching point for 20 ma 16 ma Current output with error 0: 10 % 2- wire.: 3.8 ma 4- wire.: 2.4 ma 1: +110 % 2: HOLD Meas. distance Bargraph = Echo-quality m/ft Filling height Bargraph = Echo-quality m/ft V1 Linearization V2 Linearization 0: Height 1: Tab. Activate 2: manual input 3: volumetric 4: delete 5: linear Linearizationtable line No. Linearizationtable Filling height m/ft Linearization - table Volume User's unit Volume full-scale value Default: User's unit Extended settings V3 False echo fade out Default: Actual level: Default: Echo-quality 0 10 First echo factor 0: none 1: middle 2: max. Temperature C V4 V7 Op. Param. V8 Current output 0: linear 4 20mA 1: linear with 4mA threshold 2: digit. 4/ 20mA 3: digit. 8/ 16mA m/ ft Switch-over 0: m 1: ft Echo-loss time-delay s Default: 60 s Seconds Service/ Simulate V9 Error status current error Error status last recovered error Sensor / electronics detection Unit and Software detection Reset 333 Simulation 0: Current 1: Height 2: Volume 3: Current Simulation value Current output Lock values Locked <>333 unlocked = 333 Display field Input field Factory-set values in bold font Page 34

35 10. Quick Meter Setup for Normal Applications: Overview Reset 1. Reset unit V9H5 Input: Measuring unit V8H2 Input: 0: m 1: ft 3. Align Empty V0H1 Input: E (m/ ft) 4. Align Full V0H2 Input: F (m/ ft) 5. Application V0H3 Input: (0 4) O: Liquid 1: Quick level-change 2: Dome cover 3: Bulk solids 4: Conveyer-belt allowance Page 35

36 This page intentionally left blank. Page 36

37 CAUTION PLEASE READ THE FOLLOWING WARNINGS BEFORE ATTEMPTING INSTALLATION OF YOUR NEW DEVICE. FAILURE TO HEED THE INFORMATION HEREIN MAY RESULT IN EQUIPMENT FAILURE AND POSSIBLE SUBSEQUENT PERSONAL INJURY. Page 37

38 This page intentionally left blank. Page 38

39 User's Responsibility for Safety: KOBOLD manufactures a wide range of process sensors and technologies. While each of these technologies are designed to operate in a wide variety of applications, it is the user's responsibility to select a technology that is appropriate for the application, to install it properly, to perform tests of the installed system, and to maintain all components. The failure to do so could result in property damage or serious injury. Wiring and Electrical: Section 2.0, Specifications and Section 4.0, Electrical Connections, provide the voltage and current limitations and the wiring for the various sensor types. The sensor electrical ratings should never be exceeded. Electrical wiring of the sensor should be performed in accordance with all applicable national, state and local codes. Operating Temperature: Section 2.0, Specifications, provides the operating temperature limits for each model. Operation outside these limitations will cause damage to the unit and can potentially cause personal injury. Material Compatibility: Section 2.0, Specifications, provides the materials of construction for the display/controller. Make sure that the model that you have selected is chemically compatible with its operating environment. While the meter is both liquid and spray resistant when installed properly, it is not designed to be immersed. Flammable, Explosive and Hazardous Applications: The NUS series is not an intrinsically safe or explosion-proof design. They should not be used in installations in which an intrinsically safe or explosion-proof design is required. Make a Fail-safe System: Design a fail-safe system that accommodates the possibility of device or power failure. In critical applications, KOBOLD recommends the use of redundant backup systems and alarms in addition to the primary system. Page 39

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 Manual-NEO_5003-4_1-17

More information

prosonic T FMU230, FMU231

prosonic T FMU230, FMU231 Technical Information prosonic T FMU230, FMU231 Ultrasonic Level Measurement Compact transmitters for non-contact level measurement of fluids and coarse bulk materials Application The compact transmitters

More information

LPU-2127 User Manual

LPU-2127 User Manual LPU-2127 User Manual Doc #9004169 Rev A1, 04/15 Table of Contents Introduction... iii Warranty and Warranty Restrictions... iv Chapter 1: Specifications and Options... 1 Dimensions...1 Specifications...

More information

NUS-4. Ultrasonic Level Transmitter. for Liquids and Solids

NUS-4. Ultrasonic Level Transmitter. for Liquids and Solids Ultrasonic Level Transmitter for Liquids and Solids measuring monitoring analyzing 4 Measuring Ranges: Liquids: Up to 25 meters (80 feet) Solids: Up to 10 meters (32 feet) Accuracy: ± 0.2 % of Reading

More information

MP Series Radar Transmitter Installation & Operation Manual

MP Series Radar Transmitter Installation & Operation Manual IOM MP Series Radar Transmitter Installation & Operation Manual MP Series Radar Transmitter Installation & Operation Manual CONTENTS I. HANDLING AND STORAGE... 1 Inspection and Handling Disposal and Recycling

More information

LST100 Ultrasonic level transmitter for upstream oil and gas

LST100 Ultrasonic level transmitter for upstream oil and gas Data sheet DS/LST100-EN LST100 Ultrasonic level transmitter for upstream oil and gas Accurately track and measure the most expensive consumable on your site chemicals. Measurement made easy Features Keep

More information

Ultrasonic level transmitter, non-contact

Ultrasonic level transmitter, non-contact Ultrasonic level transmitter, non-contact Type 8175 can be combined with... Compact, remote versions for level measurement up to 10 m Multi language menu control Interference echo filter Automatic calibration:

More information

LST400 Ultrasonic level / open channel flow transmitter

LST400 Ultrasonic level / open channel flow transmitter Data sheet DS/LST400 EN Rev.C LST400 Ultrasonic level / open channel flow transmitter Measurement made easy Reduced installation cost Easy access terminations Integrated echo display makes for easy troubleshooting

More information

EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure

EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure QS300480 Rev B 2013 Flowline, Inc. All Rights Reserved Made in USA 10500 Humbolt Street, Los Alamitos, CA

More information

Specification DataFile

Specification DataFile DATUM U & U Ultrasonic Level System Specification DataFile 6-digit backlit l.c.d. and bargraph clear display of measured level Echo Processing using 'DATEM' software true level measurement, overcoming

More information

EchoSonic II Ultrasonic Level Transmitter LU27 Series Quick Start NEMA 4X Enclosure

EchoSonic II Ultrasonic Level Transmitter LU27 Series Quick Start NEMA 4X Enclosure EchoSonic II Ultrasonic Level Transmitter LU27 Series Quick Start NEMA 4X Enclosure QS300116 Rev C 2013 Flowline, Inc. All Rights Reserved Made in USA 10500 Humbolt Street, Los Alamitos, CA 90720 USA Tel:

More information

Ricochet Alphasonic Level Transmitter Model LA15 Owner s Manual

Ricochet Alphasonic Level Transmitter Model LA15 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720. If

More information

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 500 Humbolt Street Los Alamitos, CA 9. If for

More information

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter ABB MEASUREMENT & ANALYTICS DATA SHEET Ultrasonic level LST400 Open channel flow transmitter 2 ULTRASONIC LEVEL LST400 / OPEN CHANNEL FLOW TRANSMITTER DS/LST400 EN REV. D Measurement made easy Reduced

More information

Level Measurement. GDSL Series. Ultrasonic Level Sensor

Level Measurement. GDSL Series. Ultrasonic Level Sensor Level Measurement GDSL Series Ultrasonic Level Sensor Contact Person: (Mr.) Mason. DING +86 153 9807 6422 / +86 158 2936 4223 mason.ding@tosilon.com www.tosilon.com Principle Ultrasonic pulses generated

More information

MK372/Ultrasonic Sensor System. Installation & Setting up Instructions. Comprising. MK372 Indicator/Controller Ultrasonic Transmitter

MK372/Ultrasonic Sensor System. Installation & Setting up Instructions. Comprising. MK372 Indicator/Controller Ultrasonic Transmitter MK372/Ultrasonic Sensor System Installation & Setting up Instructions Comprising MK372 Indicator/Controller Ultrasonic Transmitter 1 Contents page Page 1.0 Overview 3 2.0 General Specification MK372 4

More information

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 Manual-NEO_5003-4_9-97

More information

U Series Non-Contact Ultrasonic Transmitter

U Series Non-Contact Ultrasonic Transmitter U Series Non-Contact Ultrasonic Transmitter Form 1035 This new SOR Ultrasonic Transmitter is a proven solution offering more flexibility and reliability than similar transmitters. With unique features,

More information

RCM DIRECT READING FLOWMETER

RCM DIRECT READING FLOWMETER RCM DIRECT READING FLOWMETER Flow Pressure Level Temperature measurement monitoring control Special Features Compact Design Easy to Install For Horizontal or Vertical Pipes Rugged Construction Accuracy:

More information

Electro-Magnetic Flowmeters COPA-XE

Electro-Magnetic Flowmeters COPA-XE Data Sheet Electro-Magnetic Flowmeters COPA-XE 10DX4311 Flowmeter system utilizes a smart microprocessor converter System accuracy of ± 0.5% of rate Field configurable via integral pushbuttons, eliminates

More information

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual THE HIGH PERFORMANCE COMPANY Series 70 Hold 1 sec. Hold 1 sec. FOR MORE INFORMATION ON THIS PRODUCT AND OTHER BRAY PRODUCTS PLEASE VISIT OUR WEBSITE www.bray.com Table of Contents 1. Definition of Terms.........................................2

More information

Ultrasonic Level Transducer Type: MPUL06 Article No.: ca. 122

Ultrasonic Level Transducer Type: MPUL06 Article No.: ca. 122 Type: Article No.: 0067720.006 Dimensions ø95 PG7 45.25 16 101 ca. 122 ø53 NPS 2" Figure 1: Ultrasonic Level Transducer Description and application The MPULxx is an ultrasonic transducer used for determining

More information

2-wire level transmitter

2-wire level transmitter Badger Meter Europa GmbH 2-wire level transmitter Model L2xx INSTALLATION AND OPERATION MANUAL July 2002 Version UF-L2xx-07/02-e Contents Contents Page 1. Installation 1 1.1 Mounting the instrument 1 1.2

More information

EchoSonic II Manual. LU23-0, LU27-0, LU28-0, LU29-0, LU23-1, LU27-1, LU28-1, LU29-1 Series

EchoSonic II Manual. LU23-0, LU27-0, LU28-0, LU29-0, LU23-1, LU27-1, LU28-1, LU29-1 Series EchoSonic II Manual LU23-0, LU27-0, LU28-0, LU29-0, LU23-1, LU27-1, LU28-1, LU29-1 Series Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598-3015 Fax: (562) 431-8507 www.flowline.com

More information

Level Transmitter / Controller / Indicator. 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance.

Level Transmitter / Controller / Indicator. 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance. Level Transmitter / Controller / Indicator 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance. 2.1 NEW Class 1, Division 1 Hazardous Areas Approved

More information

EchoSonic II Manual 09 JUL 08 Revision A

EchoSonic II Manual 09 JUL 08 Revision A EchoSonic II Manual 09 JUL 08 Revision A Flowline Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598-3015 Fax: (562) 431-8507 www.flowline.com 09 JUL 09 EchoSonic II 1 of 26 2 of 26 EchoSonic

More information

MiniMe Two-Wire Ultrasonic Level Transmitter Model LU11/12/13/14 Owner s Manual

MiniMe Two-Wire Ultrasonic Level Transmitter Model LU11/12/13/14 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows: www.flowline.com On-line Warranty Registration

More information

LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide

LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide M-5578/0516 M-5578/0516 Section TABLE OF CONTENTS 1 Introduction... 1 2 Quick Guide on Getting Started... 2 Mounting the LVTX-10 Series

More information

TEK-F LEX 4100A. Guided Wave Radar Level Transmitter. LEVEL. Technology Solutions

TEK-F LEX 4100A. Guided Wave Radar Level Transmitter.   LEVEL. Technology Solutions Technology Solutions TEK-F LEX 4100A Guided Wave Radar Level Transmitter LEVEL www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction Featuring TDR (Time Domain

More information

Digital flow transmitter for continuous flow measurement

Digital flow transmitter for continuous flow measurement Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:

More information

PhD Inline Vortex. Performance Specifications Accuracy. Operating Specifications

PhD Inline Vortex. Performance Specifications Accuracy. Operating Specifications Description The Vortex PhD vortex shedding flowmeter measures process fluid flow by detecting the frequency at which vortices are shed from an obstruction in the process fluid line (the bluff body). A

More information

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual 1800 Series Attachable Loop-Powered Digital Indicators Operating Manual 1010 West Bagley Road, Berea, Ohio 44017 P 440.243.0888 F 440.243.3472 www.noshok.com Index 1 INTRODUCTION 3 2 SAFETY REGULATIONS

More information

Description of Instrument Functions. Prosonic T FMU30. Ultrasonic Level Measurement BA00388F/00/EN/

Description of Instrument Functions. Prosonic T FMU30. Ultrasonic Level Measurement BA00388F/00/EN/ Description of Instrument Functions Prosonic T FMU30 Ultrasonic Level Measurement BA00388F/00/EN/14.14 71244274 Short instructions Short instructions KA290F/00/A2/12.09 71106912 000 measured value Group

More information

OPTIWAVE 5200 C/F Quick Start

OPTIWAVE 5200 C/F Quick Start OPTIWAVE 5200 C/F Quick Start 2-wire / 10 GHz Radar (FMCW) Level Meter for distance, level, volume, flow and reflection measurement of liquids, pastes and slurries KROHNE CONTENTS OPTIWAVE 5200 C/F 1 Safety

More information

MiniMe 2-Wire Ultrasonic Level Transmitter Model LU12/LU13/LU14 Owner s Manual

MiniMe 2-Wire Ultrasonic Level Transmitter Model LU12/LU13/LU14 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows: www.flowline.com. On-line Warranty Registration

More information

LT3000 ULTRASONIC LEVEL TRANSMITTER

LT3000 ULTRASONIC LEVEL TRANSMITTER LT3000 ULTRASONIC LEVEL TRANSMITTER Owner s Manual Specifications Installation Calibration Troubleshooting Warranty Drawings Distributed By: iprocessmart.com 14262 Doolittle Drive San Leandro, CA 94577

More information

937CU-DIFRQ_1 Installation Instructions. Universal Frequency Converter

937CU-DIFRQ_1 Installation Instructions. Universal Frequency Converter 937CU-DIFRQ_1 Installation Instructions Universal Frequency Converter Bul. 937C Universal Frequency Converter Installation Instructions Symbols Used Warning Attention This symbol warns of possible danger.

More information

THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC)

THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC) THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC) Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic, single-point level controller

More information

USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER. Rev04009 USER MANUAL DEI MODEL USFT-CS

USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER. Rev04009 USER MANUAL DEI MODEL USFT-CS Rev04009 USER MANUAL DEI MODEL USFT-CS USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER The Model USFT-CS is an ultrasonic transit time flow meter designed to accurately and reliably report the flow

More information

Model Sono-Trak Transit Time

Model Sono-Trak Transit Time Model Sono-Trak Transit Time Ultrasonic Flow Meter Engineered for performance excellence, the Sono-Trak Transit Time ultrasonic meter combines non-invasive, bi-directional measurement with advanced ultrasonic

More information

Ultrasonic Level Transmitter Model LU20 Owner s Manual

Ultrasonic Level Transmitter Model LU20 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, fill out the enclosed warranty card and return it immediately to: Flowline Inc. 15 Humbolt Street Los Alamitos, CA 972. If for

More information

Ult r a s o n i c le v e l me t e r s ULM 70

Ult r a s o n i c le v e l me t e r s ULM 70 preliminary data průmyslová elektronika Ult r a s o n i c le v e l me t e r s ULM 70 For continuous non-contact level measurement Suited to level measurement of various liquid and bulk-solid materials

More information

Ultrasonic Transmitter

Ultrasonic Transmitter Ultrasonic Transmitter Instrucciones Generales General Instructions Table of Contents Page Topic 2...Quick Start Installation Guide 4...Safety/Protection 5...Typical Mounting Guidelines 6...Mounting -

More information

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA Mobrey Ultrasonic Product Data Sheet February 215 IP245, Rev EA MSP422, MSP4RH, and MSP9GH Level Transmitters Non-contacting measurement with no moving parts Integral LCD and push-buttons as standard for

More information

Instruction Manual ABM HART Gateway Software. Instruction Manual Revision A.1

Instruction Manual ABM HART Gateway Software. Instruction Manual Revision A.1 Instruction Manual ABM HART Gateway Software Instruction Manual Revision A.1 Table of Contents Section 1: Getting Started... 3 1.1 Setup Procedure... 3 1.2 Quick Setup Guide for Ultrasonic Sensors... 11

More information

Ultrasonic level meters ULM 70

Ultrasonic level meters ULM 70 průmyslová elektronika Ultrasonic level meters ULM 70 For continuous level measurement of liquids (even if polluted), mash and paste materials in open or closed vessels, sumps, open channels, drains, etc.

More information

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity

More information

Ultrasonic Level Sensor LUC-M** with HART/4 ma ma and PROFIBUS PA

Ultrasonic Level Sensor LUC-M** with HART/4 ma ma and PROFIBUS PA BA 240O/98/en/01.10 52027993 185572 01/10 01 Ultrasonic Level Sensor LUC-M** with HART/4 ma... 20 ma and PROFIBUS PA Description of instrument functions LUC-M10 LUC-M40 LUC-M20 LUC-M30 Valid as of software

More information

IT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual

IT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual IT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual OVERVIEW IT6810 IT6811 The Model IT6810/IT6811/IT6812 Impact Transmitter uses new technology to measure impact severity on reciprocating machinery.

More information

incorrect use or handling that exceeds normal operating limits.

incorrect use or handling that exceeds normal operating limits. User s Manual Wall mount unit for projectors Model name HAS-WM06 Thank you for purchasing a wall mount unit specially designed for Hitachi projectors. Be sure to read this manual and the User s Manual

More information

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication

More information

AUTOMATION. Operator s Manual. DCR-1005 and DCR Rev. A4, 10/08 Doc

AUTOMATION. Operator s Manual. DCR-1005 and DCR Rev. A4, 10/08 Doc AUTOMATION P R O D U C T S G R O U P, I N C. Operator s Manual DCR-1005 and DCR-1006 Rev. A4, 10/08 Doc. 9002664 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com

More information

Rosemount 5408 and 5408:SIS Level Transmitters

Rosemount 5408 and 5408:SIS Level Transmitters Quick Start Guide 00825-0100-4408, Rev AD March 2018 Rosemount 5408 and 5408:SIS Level Transmitters Cone Antenna Quick Start Guide March 2018 1 About this guide This Quick Start Guide provides basic guidelines

More information

Explosion Proof Page/Talk Paging Amplifier

Explosion Proof Page/Talk Paging Amplifier Industrial Communications Worldwide Explosion Proof Page/Talk Paging Amplifier Installation & Operation 7552-10 th Street. N.E. Calgary Alberta, Canada T2E W1 Ph: 403.25.3100 \ email:info@guardiantelecom.com

More information

LR10, LR15, LR20, LR25 & LR30 Series Manual

LR10, LR15, LR20, LR25 & LR30 Series Manual Radar Liquid Level Transmitter LR10, LR15, LR20, LR25 & LR30 Series Manual Flowline, Inc. 10500 Humbolt Street, Los Alamitos, CA 90720 p 562.598.3015 f 562.431.8507 w flowline.com MN301700 Rev B1 Introduction

More information

6GHz Intelligent Radar Level Meter Product Manual. Model:KRD520 SERIES

6GHz Intelligent Radar Level Meter Product Manual. Model:KRD520 SERIES 6GHz Intelligent Radar Level Meter Product Manual Model:KRD520 SERIES Directory 1 Product Overview...1 2 Product Introduction...2 3 The Installation Requirements...4 4 The Electrical Connection...6 5 Instrument

More information

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual USL300 SNOW DEPTH SENSOR Revision 1.1.2 User Manual 1 Table of Contents 1. Introduction... 3 2. Operation... 3 2.1. Electrostatic Transducer... 4 2.2. SL300 Analog Board... 4 2.3. SL300 Digital Circuit

More information

Operating instructions Electronic level sensor LK / / 2008

Operating instructions Electronic level sensor LK / / 2008 Operating instructions Electronic level sensor LK31 UK 704046 / 00 01 / 2008 Contents Safety instructions...2 Menu structure...3 Controls and indicating elements...4 Function and features...5 Functional

More information

UltraFlo UFDD ULTRASONIC CLAMP-ON FLOW METER

UltraFlo UFDD ULTRASONIC CLAMP-ON FLOW METER UltraFlo UFDD ULTRASONIC CLAMP-ON FLOW METER DESCRIPTION The UltraFlo UFDD Clamp-On Ultrasonic Flow Meter is the ideal flow meter with accurate, easy-to-use, easy-to-install digital doppler technology.

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 151 Graham Road P.O. Box 9010 College Station, TX 77842-9010 T: 800-876-1172 Int l: (979) 690-5560, Fax: (979) 690-0440 E-mail : globalw@globalw.com Radar Level Transmitters

More information

Operating Instructions

Operating Instructions CMYX Color mark sensor Operating Instructions CAUTIONS AND WARNINGS SET-UP DISTANCE ADJUSTMENT: As a general rule, the sensor should be fixed at a 15 to 20 angle from directly perpendicular to the target

More information

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MEMFLO MFT2 2-WIRE FLOW TRANSMITTER (877) 356-5463 (p) 330-331-7331 (f) 330-331-7172 www.flo-corp.com 2017 FLO-CORP REVA 1116 1 DESCRIPTION Please read carefully! No liability can

More information

User Manual Laser distance sensor. series OWLE. Welotec GmbH Zum Hagenbach Laer Manual_OWLE _EN 1/20

User Manual Laser distance sensor. series OWLE. Welotec GmbH Zum Hagenbach Laer  Manual_OWLE _EN 1/20 User Manual Laser distance sensor series OWLE 1/20 English 1 General notes... 3 2 Functional principle... 4 3 Mounting instructions... 4 4 Application hints... 9 5 Teaching the OWLE...11 6 Technical data...17

More information

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use Wireless New Products... New Solutions The range of telemetry modules provide remote monitoring and control by radio or twisted-pair wire, over short or long distances. Transducer signals connected at

More information

+GF+ SIGNET Temperature Transmitter Instructions

+GF+ SIGNET Temperature Transmitter Instructions GF SIGNET 80- Temperature Transmitter Instructions ENGLISH -80.090- B-/00 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal

More information

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2 Calibration Instruction Manual Emerson 475 Field Communicator Manual Revision FC.2 ABM 2 Wire Radar with HART ABM Sensor Technologies Inc 2013, all rights reserved. Emerson is a registered trademark of

More information

6.9 Jump frequency - Avoiding frequency resonance

6.9 Jump frequency - Avoiding frequency resonance E581595.9 Jump frequency - Avoiding frequency resonance : Jump frequency : Jumping width Function Resonance due to the natural frequency of the mechanical system can be avoided by jumping the resonant

More information

BATCHMATE 1500 Batch Control Computer Technical Bulletin

BATCHMATE 1500 Batch Control Computer Technical Bulletin TS-5(C) BATCHMATE 5 Batch Control Computer Technical Bulletin DESCRIPTION The BATCHMATE features an 8 digit.55-in. alphanumeric LED display. The pulse input model will accept up to 2, pulses per second

More information

Radar Level Measurement micropilot FMR 130 for stilling wells

Radar Level Measurement micropilot FMR 130 for stilling wells Technical Information TI 258F/24/ae Radar Level Measurement micropilot FMR 130 for stilling wells Smart transmitter for non-contact measurement in metallic by-pass pipes and stilling wells Suitable for

More information

1000TR. Instructions

1000TR. Instructions 1000TR ph Instructions CONTENTS 1. INTRODUCTION... 2 1.1 COMMON INTRODUCTION... 2 1.2 PARTS & ACCESSORIES... 2 2. INSTALLATION... 3 2.1 CASING... 3 2.2 MOUNTING... 3 2.3 ELECTRICAL INSTALLATION... 3 2.3.1

More information

EIB/KNX Switch Actuators. User manual

EIB/KNX Switch Actuators. User manual EIB/KNX Switch Actuators User manual IT KNT 004 IT KNT 012 Tel.: +34943627988 E-mail: knx@dinuy.com Web: www.dinuy.com Contents 1. Introduction --------------------------------------------------------------------------------------------------------------

More information

MHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data

MHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data Technical documentation Table of content Page 2: Page 3: Page 4: Page 5: Page 6: Page 7: Page 8: Characteristics - applications - technical data Technical data - input quantity - output quantity Electrical

More information

ULTRASONIC LEVEL INDICATOR

ULTRASONIC LEVEL INDICATOR ULTRASONIC LEVEL INDICATOR REFLEX/SCANFLEX MULTIFLEX MINIFLEX LR MICROFLEX-C TYPICAL NON-CONTACT LEVEL METER! OUTSTANDING SOFWARE MAKES HIGHLY STABLE AND RELIABLE. A WIDE RANGE OF S FROM SOLIDS TOLIQUIDS,

More information

PROXIMITY SENSOR TERMINOLOGY

PROXIMITY SENSOR TERMINOLOGY Never use this desk reference for installation or operation of equipment. Refer to manual for installation and operation instructions. The following descriptions refer to the European standard EN 60947-5-2.

More information

CX105 Conductivity/Resistivity Transmitter

CX105 Conductivity/Resistivity Transmitter CX105 Conductivity/Resistivity Transmitter User Manual REV A.15 Sensorex Corporation, USA 11751 Markon Drive Garden Grove, CA. 92841 U.S.A. www.sensorex.com IMPORTANT SAFETY INFORMATION Please read and

More information

DREXELBROOK. IMPULSE Series Guided Wave Radar (TDR) for Total Level and Volumetric Measurements. Easy to install, Easy to use. Dependable performance

DREXELBROOK. IMPULSE Series Guided Wave Radar (TDR) for Total Level and Volumetric Measurements. Easy to install, Easy to use. Dependable performance DREXELBROOK A Leader In Level Measurement Solutions IMPULSE Series Guided Wave Radar (TDR) for Total Level and Volumetric Measurements TDR Level Measurement Easy to install, Easy to use TDR Level Measurement

More information

ITP14. Universal process indicator. User guide

ITP14. Universal process indicator. User guide ITP14 Universal process indicator User guide ITP14_2018.05_0279_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany Tel.: +49 (0)

More information

Electromagnetic Flow Transmitter

Electromagnetic Flow Transmitter Electromagnetic Flow Transmitter Sensor in solid state technology Working as a transmitter and/or as an On/Off controller Automatic-calibration of full scale: Teach-In Clean in place (CIP) Type can be

More information

Digital conductivity transmitter

Digital conductivity transmitter Digital conductivity transmitter Compact version with integrated conductivity electrodes Remote version with seperated transmitter for short (15 ft.) or long (1500 ft.) distance Commissioning is easy due

More information

Non-Submersible Industrial Pressure Transducer

Non-Submersible Industrial Pressure Transducer Non-Submersible Industrial Pressure Transducer KPSI Transducers Series 27, 28, 30 FEATURES Custom Pressure Ranges up to 2000 (13,790 kpa) Accuracy to ±0.10% FS Analog Outputs of 4-20 ma or VDC Welded 316

More information

QL50 Luminescence Sensor

QL50 Luminescence Sensor Compact, self-contained luminescence sensor LISTED US Compact, self-contained design Features Senses luminescent marks, even on luminescent backgrounds and on reflective surfaces, such as ceramic, metal,

More information

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents KENCO ENGINEERING COMPANY P.O. BOX 470426, TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 http://www.kenco-eng.com e-mail: info@kenco-eng.com KENCO Loop Powered Magnetostrictive Transmitter

More information

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog

More information

USER MANUAL. Laser Distance Meter MODELS DT40M, DT60M, and DT100M

USER MANUAL. Laser Distance Meter MODELS DT40M, DT60M, and DT100M USER MANUAL Laser Distance Meter MODELS DT40M, DT60M, and DT100M Contents Introduction... 3 Safety Instructions... 3 Descriptions... 4 Measurement Preparation... 6 Programming Menu... 8 Distance Measurements...

More information

AUTOMATION. Operator s Manual. IRU-2xx4/3xx4 Series. Rev. A2, 11/08 Doc

AUTOMATION. Operator s Manual. IRU-2xx4/3xx4 Series. Rev. A2, 11/08 Doc AUTOMATION P R O D U C T S G R O U P, I N C. Operator s Manual IRU-2xx4/3xx4 Series Rev. A2, 11/08 Doc. 9002673 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com IRU-2xx4/3xx4

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading-edge microprocessor-based circuitry has nonvolatile memory. The display

More information

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic,

More information

Operating Instructions. MaxxFlow HTC Measurement of Bulk Solids for High Flow Rates

Operating Instructions. MaxxFlow HTC Measurement of Bulk Solids for High Flow Rates EN MaxxFlow HT Measurement of Bulk Solids for High Flow Rates ONTENTS Page 1. System Overview...................................................................... 3 2. Function..........................................................................

More information

GENERAL PURPOSE INDICATOR LOOP POWERED WITH VERY LARGE DIGITS DATASHEET F090 - GENERAL PURPOSE INDICATOR

GENERAL PURPOSE INDICATOR LOOP POWERED WITH VERY LARGE DIGITS DATASHEET F090 - GENERAL PURPOSE INDICATOR GENERAL PURPOSE INDICATOR LOOP POWERED WITH VERY LARGE DIGITS DATASHEET F090 - GENERAL PURPOSE INDICATOR Features Universal loop powered indicator. Very large 26mm (1 ) high digits. Displays the actual

More information

Operating Instructions. Indication and adjustment module PLICSCOM

Operating Instructions. Indication and adjustment module PLICSCOM Operating Instructions Indication and adjustment module PLICSCOM 8888 Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6

More information

USER MANUAL MODEL CSLFC ULTRASONIC FLOW TRANSMITTER. Rev USER MANUAL CLARK SONIC MODEL CSLFC

USER MANUAL MODEL CSLFC ULTRASONIC FLOW TRANSMITTER. Rev USER MANUAL CLARK SONIC MODEL CSLFC Rev 092012 USER MANUAL CLARK SONIC MODEL CSLFC USER MANUAL MODEL CSLFC ULTRASONIC FLOW TRANSMITTER The Model CSLFC is an ultrasonic transit time flow meter designed to accurately and reliably report the

More information

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output Digital Inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

USER MANUAL MODEL USFT-B ULTRASONIC FLOW TRANSMITTER. Rev USER MANUAL DEI MODEL USFT-B

USER MANUAL MODEL USFT-B ULTRASONIC FLOW TRANSMITTER. Rev USER MANUAL DEI MODEL USFT-B Rev012008 USER MANUAL DEI MODEL USFT-B USER MANUAL MODEL USFT-B ULTRASONIC FLOW TRANSMITTER The Model USFT-B is an ultrasonic transit time flow meter designed to accurately and reliably report the flow

More information

Quick Start Guide LIQ-QSG-226, Rev F June Rosemount 226. Toroidal Conductivity Sensors

Quick Start Guide LIQ-QSG-226, Rev F June Rosemount 226. Toroidal Conductivity Sensors Quick Start Guide LIQ-QSG-226, Rev F June 2017 Rosemount 226 Toroidal Conductivity Sensors Safety Information WARNING! HIGH PRESSURE AND TEMPERATURE HAZARD Before removing the senosr, reduce the process

More information

Level Measurement Continuous level measurement Radar transmitters

Level Measurement Continuous level measurement Radar transmitters Overview Configuration Mounting on a nozzle is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of solids and liquids in storage vessels including extreme levels of dust and high

More information

d = c 10/20/2017 Level Measurement Transmitters Applying Level Measurement p C T 273K Ultrasonic The Principle Time of Flight (TOF)

d = c 10/20/2017 Level Measurement Transmitters Applying Level Measurement p C T 273K Ultrasonic The Principle Time of Flight (TOF) Products Solutions Services Level Measurement Transmitters Applying Level Measurement Ultrasonic FDU95 FDU93 FDU92 FDU91 FDU90 Slide 1 Slide 2 The Principle Time of Flight (TOF) Emission of ultrasound

More information

XT Technical Documentation. The magnetostrictive level sensor. Edition: Version: 1 Article no.:

XT Technical Documentation. The magnetostrictive level sensor. Edition: Version: 1 Article no.: Technical Documentation The magnetostrictive level sensor Edition: 11-2010 Version: 1 Article no.: 233571 Gems Sensors & Controls One Cowles Rd Plainville CT Telephone 800-378-1600 Page 2/19 Table of contents

More information

Kotron Sentinel Model 804 RF Level Transmitter

Kotron Sentinel Model 804 RF Level Transmitter Kotron Sentinel Model 804 RF Level Transmitter D E S C R I P T I O N The Sentinel is a unique, powerful level transmitter. The leading edge microprocessor-based circuitry has nonvolatile memory. The display

More information

INTRODUCING SOME GREAT NEW PRODUCTS FROM OUR DWYER INSTRUMENTS RANGE:

INTRODUCING SOME GREAT NEW PRODUCTS FROM OUR DWYER INSTRUMENTS RANGE: Unit 1 / 14 Biscayne Way Jandakot WA 6104 P.O. Box 3232, Success WA 6964 Tel: (08) 9414 7666 Fax: (08) 9414 7677 Email: dg@dginstruments.com.au Website: www.dginstruments.com.au A.B.N: 59 113 005 959 DATE:

More information