those activities and considerations associated with the design, installation and

Size: px
Start display at page:

Download "those activities and considerations associated with the design, installation and"

Transcription

1 : Low Voltage Switchboards d Purpose And Design Guidelines : This standard details those activities and considerations associated with the design, installation and maintenance of.

2 Index: Document History 1. Introduction 1.1 Purpose 1.2 Management Responsibility 2. References 2.1 International and National Standards 3. Glossary of Terms and Definitions 4. Construction 4.1 General 4.2 Electricity Supply 4.3 Discrimination 4.4 Forms of Separation 4.5 Ingress Protection 4.6 Impact Protection 4.7 Pollution Degree 4.8 Busbars 4.9 Outgoing Circuits 4.10 Cable Chambers 4.11 Earthing 4.12 Low Smoke Zero Halogen 4.13 Installation of LV cables 4.14 Labelling and Numbering Systems 4.15 Enclosure Numbering and Labelling 4.16 Electromagnetic Compatibility (EMC) 4.17 Electrolytic Action 5. Components 5.1 Air Circuit Breakers (ACB) 6. Interlocking 6.1 Non Paralleled Supplies 6.2 Paralleled Supplies 7. Fault Rating 8. Diversity 9. Spare Capacity 10. Power Factor Correction 10.1 Power Factor Correction 11. Inspection & Testing 11.1 Manufactures Type Tests 11.2 Particular Board Test 11.3 Energisation 12. Documentation 12.1 Electrical Drawings 12.2 Engineering Drawings 12.3 Device Parameters 12.4 Operation & Maintenance Manuals 12.5 Manuals 13. Component Table 13.1 General components Appendix Attachments 1. Attachment??? Revision: 2 Feb 2012 Noel Corry Page 2 of 27

3 Document History Date Revision Number Revision History Written By: Verified By: Approved By: 04/01/11 1 Text communicating changes and reasons for change (note changes in body text of document must be highlighted) Noel Corry Alain Polycarpe Noel Corry 07/02/12 2 Revised for rev 2. Revised text in Yellow Noel Corry Alain Polycarpe Noel Corry 1. Introduction This standard supplements national, international standards and legal requirements. It does not overrule these and where any conflict exists, national, international standards and legal requirements take precedence. This standard relates to the design, manufacture and works testing of Low Voltage main switchboards and sub distribution boards for supply to CCE Inc. This standard is not intended to be restrictive. Alternate means will be considered. However, proposals that do not address these basic requirements, as a minimum, are not likely to be acceptable. The proposed alternative, clearly indicating any advantages shall be submitted to the CCE responsible person. The written acceptance, of a proposed alternative, by CCE shall be obtained before any work is carried out. The requirements for packing, delivery, off loading, temporary storage and installation will be included in the specific contract documentation. 1.1 Purpose This standard details those activities and considerations associated with the design, installation and maintenance of Low Voltage Switchboards. This standard applies to the supply of the relevant equipment wherever installed on premises controlled by CCE in Belgium, the Netherlands, Norway, Sweden, Great Britain and Continental France. 1.2 Management Responsibility Standard Owner Procedure fulfilled by Managers locally accountable and responsible for: ESC Central Manager Electrical & Automation Manager -Noel Corry Engineering Manager Revision: 2 Feb 2012 Noel Corry Page 3 of 27

4 2. References The following documents contain provisions which, through reference in this text, constitute provisions of this Low Voltage Switchboard standard. 2.1 International and National Standards As this standard is for use in several countries the EN reference is used rather that a particular county version i.e. EN rather than BS EN Where national variations exist in standards the CCE responsible person shall decide which applies to a specific contract. Reference EN :2007 IEC :2007 EN :2007 EN :2006 EN EN :2009 EN 62262:2002 Title Low voltage fuses. General requirements. Insulation coordination for equipment within low-voltage systems Principles, requirements and tests Low-Voltage Switchgear and Control gear Specification for low-voltage switchgear and control gear. Circuit-breakers Specification for low-voltage switchgear and control gear. Switches, disconnectors, switch-disconnectors and fuse-combination units Low-Voltage Switchgear and Control gear Assemblies Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code) 3. Glossary of Terms and Definitions As used in this standard: Abbreviation or Term ASTA Association of Short-circuit Testing Authorities Definition Circuit Breaker (CB) A mechanical switching device, capable of making, carrying, and breaking currents under normal circuit conditions, and also making, carrying for a specified time and breaking currents under specified abnormal circuit conditions such as those of short circuit. Contactor A mechanical switching device having only one position of rest, carrying and breaking currents under normal circuit conditions including operating overload conditions. Revision: 2 Feb 2012 Noel Corry Page 4 of 27

5 Control gear (Also see switchgear) Disconnector A general term covering switching devices and their combination with associated control, measuring, protective and regulating equipment, also assemblies of such devices and equipment with associated interconnections, accessories, enclosures and supporting structures. A mechanical switching device that provides, in the open position, an isolating distance in accordance with the specified requirements. Extra Low Voltage (ELV) Fuse Switch High Voltage (HV) IDMT Insulator Lambar LED Low Voltage (LV) Main Board Main LV Switchgear Voltage not exceeding 50V a.c. or 120V d.c., whether between conductors or to earth. A switch (disconnector) (switch disconnector) in which a fuse link or a fuse carrier with fuse link forms the moving contact. In a general sense, the set of voltage levels in excess of low voltage (1,000V). In a restrictive sense, the set of upper voltage levels used in power systems for bulk transmission of electricity. Inverse Definite Minimum Time. A tripping characteristic that has a variable tripping time inversely related to the fault current with a definite minimum time lag. Components designed to support and insulate a conductive body. Lambar is a unique busbar trunking system; it can be used in various distribution systems such as horizontal power systems and rising mains. Light Emitting Diode A voltage below High voltage (1,000Va.c. between conductors or 600V to earth). A board having connection to the LV side of a distribution transformer. That which is connected to the LV side of distribution transformers (11 kv or 6.6 kv /400 V) and are located in substations. Moulded Case Circuit Breaker (MCCB) A circuit breaker having a supporting housing of moulded insulating material forming an integral part of the circuit breaker. OCR Over current Overload Over current relay A current exceeding the rated current. Operating conditions in an electrically undamaged circuit, which causes an over current. PILC PVC Screen Separation Short Circuit Current Paper Insulated Lead Covered, refers to a type of cable construction. Polyvinylchloride A device used for the protection of cables and circuits against interference of electrical fields on the pulse to be transmitted. Of conductors. An arrangement of conductors with solid insulation interposed in such a manner that disruptive discharges cannot occur between them. An over current resulting from a short circuit due to a fault or an incorrect connection in an electric circuit. Revision: 2 Feb 2012 Noel Corry Page 5 of 27

6 Switch Fuse A switch (disconnector) (switch disconnector) in which one or more poles has a fuse in series in a composite unit. Switchgear (Also see control gear) Switching Device A general term covering switching devices and their combination with associated control, measuring, protective and regulating equipment, also assemblies of such devices and equipment with associated interconnections, accessories, enclosures and supporting structures. A device designed to make or break the current in one or more electric circuits. For the purposes of this specification only, Switching Devices embraces, switches, disconnectors, switch disconnectors and fuse combination units as defined by BS EN XLPE Cross-linked polyethylene refers to a type of cable construction. 4. Construction 4.1 General The switchboard and components shall be designed, constructed, assembled and tested to comply with applicable parts of EN :2009. All live parts on the switchboard shall be fully shrouded to prevent accidental contact with live equipment when the doors are open or cabling is in progress. All doors shall be key lockable with Gull Wing type handles and all openings shall be properly gasketted and vermin proof. Key type shall be specified by the CCE responsible person. Main switchboards shall be suitable for front and rear access, with outgoing cables emanating from above or below. Easily accessible cable terminating and testing facilities shall be provided. Surge protection shall be installed in all low voltage switchboards. Construction shall comprise of multi-fold fully welded outer units manufactured from 2mm CR4 prime quality sheet steel, thus ensuring earth continuity and integrity. This would be inherent Form 4 design and when stacked in the outer units create a minimum steel thickness between incoming / outgoing compartments of 3mm / 4mm ensuring the maximum segregation. Doors shall be returned folded for increased rigidity and have all corners fully welded and ground smooth, and be manufactured fro a minimum 2mm CR4 sheet steel. Doors shall be manufactured to open to a minimum of 90 degrees to allow access for maintenance and adjustment. Gland plates shall be fixed by the use of clamping bolts or tapped bushes. Self tapping screws shall not be used. The paint finish shall be suitable for normal industrial duty with adequate priming/undercoat layers applied. The switchboard shall be painted to a BS or RAL colour as specified in the tender document, the total paint thickness shall not be less than 100 microns. The board shall be easily extendible in either direction. Revision: 2 Feb 2012 Noel Corry Page 6 of 27

7 4.2 Electricity Supply The equipment shall be designed for use in any European country with the nominal voltages of 230V, 1 Phase, 400V, 3 Phase, 50 Hz +/- 10% in accordance with harmonised standards and tolerant of legally permitted supply variations in terms of voltage, frequency and their combined effects at each extreme. Equipment shall be supplied for use with a neutral and earth TN-S system (with separate neutral and earthing conductors throughout). 4.3 Discrimination Discrimination of operation of protective devices shall be assured for all circuits and sub-circuits. MCCB discrimination by current is preferred. Discrimination by time shall only be permitted where discrimination by current is not possible. Where Discrimination by Time is required the agreement of CCE responsible person shall be obtained at the design stage. 4.4 Forms of Separation Unless otherwise stated in the contract, the internal separation of assemblies shall be Form 4b Type 2 (to EN :2009) namely, bus bars, functional units and terminals for external conductors separated from each other by rigid barriers or partitions 4.5 Ingress Protection The switchboard assembly shall be of metal construction dust and damp protected to EN :2007. The degree of protection for the switchboard shall be IP42 as a minimum (i.e. cubicle, multiple cubicle or multi-box assemblies). The internal degree of protection would be to IP2X (any live parts not isolated by the door interlocked isolation device. Additional protection shrouding can be offered id required. 4.6 Impact Protection Impact protection of enclosures shall be appropriate to the location and shall be stated by the supplier in accordance with the rating system (IK rating) defined in EN Pollution Degree Unless otherwise stated in the contract Pollution degree 3 (IEC :2007) shall apply. 4.8 Busbars All busbars and droppers shall be manufactured from Hard Drawn High Conductivity (HDHC) copper, run horizontally and vertically as required. Busbars shall be air insulated and shall be fault rated to carry the rated current of the switchboard. Access to busbar system and busbar connections shall only possible by the removal of covers by using a tool. All covers which, when removed, which give access to live parts will have warning labels firmly fixed, which also state the voltage which will be exposed. Busbars current rating shall be specified on all quotations. Busbar rating shall relate to boards in continuous operation. Busbar rating shall not be varied throughout the length of the switchboard. Busbar systems shall be ASTA certified. Revision: 2 Feb 2012 Noel Corry Page 7 of 27

8 Busbars in switchboards fed from cast resin transformers capable of being up rated by forced cooling (See HV Standard section 6.3) shall be designed for this higher rating. Connections between busbars and outgoing circuits shall be manufactured from copper bars or suitably rated insulated cables for lower rated circuits. If cables are used a fault free concept with double insulation, shrouded terminals and no crossovers shall be applied. All busbars shall be totally enclosed and braced for the fault level nominated. Neutral busbars shall have an equal cross sectional area to the phase bus bars. Where cable connections are made to busbars, appropriate means (e.g. high temperature insulation) shall be taken to ensure the cable insulation integrity owing to any heat conduction from the busbars. 4.9 Outgoing Circuits Overload protection shall be provided on all three phases. Each outgoing circuit is to have an individual power meter measuring all three phases. Schneider Power Meter PM810 is the CCE preferred type Cable Chambers The cabling chambers shall be segregated to make it possible to cable any outgoing circuit in safety with the switchboard 'live'. Main board incoming sections shall be arranged to accept single core cables with top or bottom entry. If a cable gland plate is used it shall be non-ferrous to prevent eddy current circulation. Suitable cable lugs shall be provided to terminate the conductors. Alternatively the low voltage incoming section shall be arranged to accept busbar connections (Lambar or similar) for interconnection with the low voltage bus bars of the cast resin type transformers, which may form part of the suite Earthing On main switchboards a copper earth bar shall run the full length of the switchboard, be solidly fixed to the framework of each section and compartment and all non-current carrying metalwork shall be bonded to it. Dropper earth bars shall be available at each cable entry point for the connection of external earth conductors. The main earth bar size shall be 150 mm 2 minimum and shall be able to carry the maximum asymmetrical fault current of the board. Terminations shall be provided at both ends to facilitate connection to the earthing bar in the switch room. All gland plates, doors, component plates etc, shall be directly or indirectly earth bonded to the main earth bar. Each gland or gland plate shall be connected to the main earth bar. The neutral conductor shall be isolated from earth Low Smoke Zero Halogen All none metallic containment, equipment, associated items and cables installed in the switchboard shall be of low smoke halogen free materials (LS0H). Revision: 2 Feb 2012 Noel Corry Page 8 of 27

9 4.13 Installation of LV cables Suppliers shall only provide and install cables in compliance with current ISO Standards, national codes of practice, procedures and statutory instruments. All mechanical protection, i.e. cable tray and trunking, shall be both mechanically and electrically sound and complete, before wiring can commence. Suppliers shall provide documented evidence of cable sizing calculations. At all times the utmost care is to be exercised to avoid damaging the protective sheathing of the cable or of causing excessive bending or twisting which may result in bird caging of wire armour and/or damage to core insulation, sheaths etc. When routing cables, care must be taken not to obstruct access to and movement of plant. Cables shall be run in continuous unbroken lengths and joints will not be permitted unless authorised by the CCE Responsible Person. Where cables pass through floors, or rise through covered trenches, they shall be provided with adequate mechanical protection in the form of metallic sleeves or kick plates projecting not less than 75 mm above floor level. Kick plates shall be so positioned as not to constitute a trip hazard. Where vehicular access may be expected, exposed cables less than 4 m from floor level shall be adequately protected against damage. This protection must be sufficiently strong to withstand damage by trucks and shall also be applied to armoured cables where necessary. Steel pipe or suitable tubular guard may be used. Cables shall be handled and installed in accordance with the manufacturer's recommendations. Catenary support of cable will not be permitted unless all other methods of installation are impractical and then only with specific authorisation of CCE Responsible Person. Each cable shall be supported and secured in a manner that ensures that the cable will not sag. Storage and handling of cable before, during, and after installation is to be carried out with due regard to the manufacturers recommendations. Cables shall not be installed on exterior wall faces of buildings without the specific approval of the CCE Responsible Person Small Power Control and Wiring Cables shall be installed in such a way as to prevent entanglement with other cables in the conduit or trunking. All internal wiring shall be carried out using PVC insulated BS 6231 type BK cable neatly secure and loomed and run in PVC trunking where possible. Small wiring for protection and metering should be accessible whilst the board is still energised. All cables shall be fitted with crimped terminations and cable markers at each end, numbered to correspond with the appropriate wiring diagram and colour coded to BSPD 2379, IEC446. Where metering is required all protection shall be via HRC fuse cartridges Standard Wire Colours The following standard wire colours shall be utilised unless specific prior approval to use alternative colours is given in writing by the CCE Responsible Person. For mains voltage circuits of 400 V ac. or 230 V ac.: - Revision: 2 Feb 2012 Noel Corry Page 9 of 27

10 Phase 1 Phase 2 Phase 3 Neutral Earth Brown Black Grey Light Blue Green/Yellow For 230/110 V ac.: - Line Neutral Red Light Blue For 24 V supplies: - Positive Negative Dark Blue Dark Blue and White For PLC Connection (may be required for auto change over purposes): - PLC Input PLC Output Dark Blue Dark Blue All installations: - Interfacing Cabling Instrumentation Current Transformers Inter Tripping Orange White White White DC analogue signals (in shielded cable): - Positive Negative Brown White Power Cables Cable drums shall only be rotated in the direction indicated by drum markings and open cable ends are to be effectively sealed immediately after cutting to prevent the ingress of moisture. Cables shall be continuous and no joints are to be made along the length, reference shall be made to the CCE Responsible Person if this stipulation cannot be fulfilled. Only proprietary devices shall be used for clamping cables. Cable routes in production areas must be approved by the CCE Responsible Person before installation commences. Cables shall be neatly installed either separately or on banks arranged to form a maximum of two layers. The bunching of cables is unacceptable. Where cables require to be installed through or across the edges of tray or other metalwork the edges of the lips shall be made smoothed, painted and lined with protective sleeving to avoid cable damage. Revision: 2 Feb 2012 Noel Corry Page 10 of 27

11 Single Core Cables for 3 Phase Supplies When single core cables are used for three phase power distribution circuits (e.g. off main 400 V transformers), both ends shall be earthed and bonded together. Special attention shall be given to de-rating the cable to account for circulating currents owing to induced voltages in the armour. Under such circumstances: - a separate protective conductor shall be provided. insulated glands for cable terminations shall be fitted at one end. triangular formation shall be used for each three phase group of single core cables. contractors shall provide evidence of ability of cleats to withstand the axial forces. protection from contact with the cable armour shall be provided Labelling and Numbering Systems All elements of an installation, whether they are electric, or other means of control will be clearly identifiable with a reference mark and reproduced on plans and diagrams. Each component of an electrical installation shall be labelled according to the CCE E&A standard: each component, wire, terminal, cable, etc shall have a unique number. All numbers shall relate to the electrical drawings and shall be visible in the electrical drawings. Labels and signs shall comply with the relevant national and international standards. Labels shall be durable and remain clearly legible for minimum 10 years, appropriate for the physical environment. All labels shall be printer generated (handwritten labels or labels composed of pre-printed signs are not accepted). Label designations shall relate to those on drawings, which identify the items of equipment. Identification of all electrical equipment shall be unique, for a complete listing contact the CCE responsible person. Warning labels i.e. bus bar chambers shall be Yellow/Black/Yellow engraved laminate (Traffolyte). Enclosures labels shall be manufactured from Red/White/Red engraved laminate (Traffolyte). Labels shall be permanently fixed next to the equipment. The CCE numbering system is based on IEC The use of Group and Place structure for electrical drawings and numbering is mandatory. Explanation Group and Place: Group: Functional part of the machine. Indicated by symbol = Line number and machine number (= machine abbreviation) shall be included in the group number Machine abbreviation shall be taken from Industrial Network and Communication Standard. Place: Physical location of a component. Electrical cabinet or zone in the installation. Indicated by symbol +. Important notes: If a machine or installation is not subdivided in functional groups, the complete electrical drawing shall be in 1 group, the name of this group shall be the machine number. Example: =2FBC1 Line 2 Full Bottle Conveyors The indication of the physical location of each component by using the place indicator + is mandatory. The choice for a Group and Place project is a setting in Eplan, and is incorporated in the CCE Eplan P8 standard. Revision: 2 Feb 2012 Noel Corry Page 11 of 27

12 4.15 Enclosure Numbering and Labelling Each enclosure, electrical cabinet, panel, distribution board and junction box shall be uniquely numbered. The complete number of each cabinet shall be composed following the Group and Place syntax below: Syntax: =[LineNumber][MachineAbbreviation] + [CabinetNumber] Line Number: Number of the production line. Machine abbreviation: To be taken from Industrial Network and Communication Standard Cabinet number: Mandatory abbreviations for cabinets to be used see below: Main cabinet: +MP1, +MP2 Junction box: +JB1, +JB2 Control box: +CB1, +CB2 (cabinet containing operator control) Examples: =2FIL1 +MP1 =2FBC1 +MP1 =2FBC1+JB1 The supplier shall ascertain the required numbers from CCE for every contract. Electrical enclosure labels shall be manufactured from red/white/red engraved laminate (Traffolyte, Resopal) Main Panel Each enclosure will have unique number existing of number main panel plus index *.01,*.02, Example: =2FIL1 +MP1 =2FIL1 +MP2 Note: Main panels with more than 2 compartments shall be split up in different main panels to simplify finding components: +MP1, +MP2, etc. Nameplate of main panel shall indicate: Source of power supply (Supplied from) Description Panel No Location Rating Cable type Network Type Icc 3 value Definitions: Supplied from: Source of electrical supply to the equipment, including source panel number and source switch number. Description: Name of the equipment being supplied. Panel No.: Reference number of panel composed of machine number and location. Location: Area or place where panel being supplied is situated. Rating: Circuit breaker / Main disconnect maximum rating (maximum allowable current). Cable type: Description of what type of cable installed (No of cores x core size + cable type). Network Type: Type of distribution system (TNC/TNS). Icc 3 Short circuit rating Revision: 2 Feb 2012 Noel Corry Page 12 of 27

13 Supply Panel Label When the dimensions of the panel do not allow the application of a label with the dimensions prescribed above, a label with appropriate dimensions can be fixed. Edges to be chamfered to 45 0 Nameplate of the sub panel, powered must indicate: Description of the equipment. Cabinet number. Figure 1 Enclosure label main panel When the dimensions of the panel do not allow the fixture a label with the dimensions prescribed above, a label with appropriate dimensions can be fixed. Nameplate of sub enclosure, powered with power bus must indicate: Description of the equipment. Enclosure number. Each compartment or switchgear unit shall carry a label to identify circuit description together with plant reference number. On Main boards labels shall be fitted on the front and the rear of each compartment and on any moving carriages. All labels shall be fixed with non-ferrous rivets or screws. Covers to Busbar chambers shall have labels engraved with black text on a yellow background with 6 mm high letters DANGER LIVE BUSBARS. The switchgear shall have a main designation label to EN :2007, and include the following information: - Manufacturer's name or trademark. Type, designation and serial number. Rated voltage, frequency, and short circuit capability and certification authority. Rated current of each circuit. Revision: 2 Feb 2012 Noel Corry Page 13 of 27

14 Voltage warning labels shall also be fixed, at all appropriate positions on each enclosure Sub Panels in the Field Each sub panel shall have a unique number consisting of main cabinet number plus index 1, 2 Example: =2FIL1 +JB1 =2FIL1 +CB1 Nameplate of sub panel shall indicate: Source of power supply (Supplied from) Description Panel No composed of machine number and location. Location Rating Cable type Sub Panel Label Label - Sub Panel Revision: 2 Feb 2012 Noel Corry Page 14 of 27

15 Component Numbering and Labelling Component numbers have to identify each component with a unique number, indicating the group, the place, the page, symbol and the path where the component can be found in the electrical drawings and in the installation. Symbols used must be according to IEC Composition of component number: Syntax: =[Group]+[Place] [Page][Symbol][Consecutive Number] Example: =2FIL1.PS +MP1-8K3 Project subdivided in groups =2FBC1 +MP1-100U1 Total project is 1 group PLC cards shall be numbered to the page number of the page containing the PLC rack overview. Note: Sub division of the machine in functional groups is not mandatory. The complete machine can be in 1 general group Use of Group and Place syntax (IEC ) is mandatory Cabinet Internal Component Labelling Component labels in control panels and electrical cabinets shall be permanently fixed on the component and to the backplane next to the component. Wire channel covers (lids) shall be labelled with identification markings to aid replacement after removal. Numbering shall start upper left side and end lower right side. Syntax to be used: On each crossing of covers, a 2 digit number shall be put on both covers. Label inside the electrical cabinet shall be yellow background with black lettering Field Component Labelling Labels shall not be fixed directly on components but to a permanent support next to the component in such a manner as to avoid any device ambiguity. Component labels shall be manufactured from white/black/white engraved laminate (Traffolyte, Resopal). Component numbers in the field shall be permanently fixed next to the equipment. Each label shall be positioned so that it can be clearly read from a normal observation position, and will unambiguously relate to the item that it describes Wire Numbering Wire numbers shall uniquely identify each wire, indicating the group and the page where the wire can be found in the electrical drawings. Label colour shall be white background with black lettering. Composition of wire numbering shall be done according to syntax below: Syntax: =[Group] [Page]/[Consecutive Number] Group number: Example: =2FIL1.PS =2FBC1 Page number Consecutive number Number to be reset for each page Example: =2FIL1.PS-05/01 =2FBC1-25/01 Visibility in the electrical drawings: The wire numbers shall be visible in the electrical drawing. As a minimum, the wire numbers from the example above shall be minimum visible as follows: Wire number Wire number visible in the drawing =2FIL1.PS-05/01-05/01 Project subdivided in groups =2FBC1-25/01-25/01 Total project is 1 group Revision: 2 Feb 2012 Noel Corry Page 15 of 27

16 : Low Voltage Switchboards d Printed wire number visible in the cabinet: Wire number shall be the same on both sides of the wire The part of the actual wire number to be printed depends if the project consists of 1 general group or if the project is divided into functional groups Minimum the syntax below shall be printed on the wire number: Wire number Printed wire number visible in the cabinet =2FIL1.PS-05/01 PS-05/01 Project subdivided in groups =2FBC1-25/01-25/01 Total project is 1 group Cores of a cable shall have a unique wire number. Core numbers printed on the cable cores shall be visible in the electrical drawing. Wire numbering shall be sequential. Numbering shall re-start for each page. Material wire numbers: Phoenix PATG. For wires connected to PLC-cards, shall be used Terminal the supplier shall assure that the doors of the PLC cards can be closed. When necessary, extended covers Wiring Each terminal row shall be labelled with a unique number, to be put at the left side of the terminal block. Each physically separated block of terminals is consideredd as a terminal row. A terminal row should not consist of more than 30 terminals. Symbols to be used: Power terminals: XP Control voltage terminals: XC Each terminal must be labelled with a unique number within the terminal block Cable Numbering Cable numbers shall uniquely identify each cable, indicating source and destinationn of the cable. Label colour shall be yellow background with black lettering. Cable numbers shall be placed inside the cabinet (between floor plate and terminal row) for floor mounted cabinets. Cable numbers shall be placed outside the cabinet for wall mounted (sub)-cabinets with sufficient freee space below. Network cables shall be numbered on entering the electrical cabinet and where connected to the network component. The division between source and destination in the cable number will be made by a slash sign ( / ). The cable number has to be engraved on 2 lines to improve legibility of the number. First line shall contain source of the cable followed by the slash sign. Second line shall contain the destination of the cable. Syntax: Source/ =[Group]+[Place] [Component Number]/ Destination =[Group]+[Place] [Component Number] Example =2FBC1+F3-300M1/ =2FBC1+F3-301M1 Laser engraved cable markers shall be used. Labels must be legible for a minimumm period of 10 years. Following label brands are approved by CCE: Murr Plastic, Elmaro. All other material must be approved by the CCE responsible person before use. Example Cable Number Material / Syntax For floor standing cabinets, the cable markers shall be fixed inside the cabinet. SC Procedure Revision: 2 Feb 2012 Author: Noel Corry Low Voltage Switchboard Standard Page 16 of 27

17 Power supply Cable Source: Destination: Cabinet number (=2LVB+MP1) and component number of the circuit breaker with number of the page in the electrical drawing (101) that shows the circuit breaker. =Group (including machine number)+place Component Number of the Main Disconnect Note: Example: =2LVB1+MP1-101F5 / =2FBC1+MP1-100Q1 (2LVB1 = First low voltage board of line 1) When supplying new machines from existing low voltage boards, the origin of the power cable shall not always be in =Group+Place-Component format. Existing cabinet number and component number of the circuit breaker shall be taken as source of the cable Cables Between Cabinets (between 2 machines OR between Main Cabinet and Sub Cabinet to Terminals) Source: =Group+Place Terminal row / Destination: =Group+Place Terminal row Example: =2FIL1.PS+MP1-XP101 / =2FIL1.PS+JB2-XP101 Project subdivided in groups =2FBC1+MP1-XC20 / =2FBC1+JB2-XC40 Total project is 1 group Actuator/ Sensor Cables Source: Destination: =Group+Place Terminal row or Component Number/ =Group+Place Sensor or Actuator Number Example: =2FIL1.PLC+MP1-XC50 / =2FIL1.PLC+JB2-2B1 Project subdivided in groups =2FBC1+MP1-XC20 / =2FBC1+F2-150B1 Total project is 1 group If the destination is a sensor or actuator, the page number in the electrical drawings is indicated by the component number, which includes the page number. In the first example above the reference 2B1, 2 is the page number, B is the symbol, and 1 is the consecutive number, to be restarted for each page Cable between Components in different cabinets (e.g. Network Cabling) Source: Destination: =Group+Place Component Number/ =Group+Place Component Number Note: Component number contains page number of the electrical drawing. Example: From PLC Filler to PLC Bottle Conveyors: =2FIL1.PLC+MP1-3A2 / =2FBC1+MP1-50U1 Where several connections are required from one unit to another i.e. Power, Control & Network the numbering of the cable should reflect this by adding an identifier to define the connection point. Example: From drive motor 300M1 to drive motor 301M1 =2FBC1+F3-300M1.2 / =2FBC1+F3-301M1.2 Revision: 2 Feb 2012 Noel Corry Page 17 of 27

18 Example Numbering =2LVB1+MP1 Low Voltage Board Line 2 Cable Number: =2FBC1+MP1-10XP1 / =2FBC1+JB2-10Q1 Cable Number: =2LVB1+MP1-101F5 / =2FBC1+MP1-100Q1 =2FBC1+MP1 Conveyors Main Panel 1 Cable Number: =2FIL1.PLC+MP1-3U2 / =2FBC1+MP1-50U1 =2FIL1+MP1 =2FBC1+MP2 Cable Number: =2FBC1+MP2-10XP1 / =2FBC1+F3-300M1 =2FBC1+JB2 Sub-enclosure in the field Cable Number: =2FBC1+F3-300M1 / =2FBC1+F3 =2FBC1+F3-301M1-300M1 =2FBC1+F3-301M1 Motor 300M1 Motor 301M1 Example of Numbering 4.16 Electromagnetic Compatibility (EMC) The manufacturer shall confirm compliance with the EMC statutory legislation Electrolytic Action Every precaution shall be taken to prevent chemical or electrolytic action where dissimilar metals are used in close proximity. This is particularly important where aluminium or aluminium alloys are used. Revision: 2 Feb 2012 Noel Corry Page 18 of 27

19 5. Components 5.1 Air Circuit Breakers (ACB) General The circuit breakers shall comply with EN , and shall be certified by an approved testing station for the rated short circuit capacity. The operating handle shall be lockable in the OFF position. The circuit breaker ON - OFF state shall be indicated by a flag or other means of positive indication. Air Circuit Breakers shall be of the Withdrawable type / design of metal clad construction. The protection relay shall be of the self diagnostic type incorporating a watchdog circuit for internal checking; indication of this shall be displayed via an alarm CPU LED. Volt free contacts and LED s shall be provided for overload and short circuit fault functions. An in built OCR check with trip / non trip feature shall be provided to allow calibration settings to be checked on site. Fault and thermal ratings of circuit breaker shall be related to the specific enclosure in which they are installed. Free Air ratings are not acceptable Main Boards Incoming circuits and bus sections shall be 4 pole air circuit breakers (ACB's). Manual closing and tripping shall be independent of operator effort. The circuit breaker closing operation shall be at least independent manual closing as defined in EN :2006. ACB tripping circuits other than integral protection circuits shall be designed for shunt operation from an independent power supply. ACB's designed for shunt tripping operations shall not be closed unless the shunt tripping supply and system mains is available. Such ACB's shall remain closed unless opened by integral protection and/or shunt trip operation. System mains supply failure shall not cause such circuit breakers to open. Facilities shall be provided for testing the circuit breaker closing and tripping mechanisms when the circuit breakers are in the isolated position. It shall not be possible to withdraw or insert a circuit breaker unless it is in the OFF position. The busbar and circuit shutters shall be provided with suitable padlocking facilities Inter-Tripping Inter-tripping circuits shall be designed for shunt trip operation from an independent power supply. Either: - Main board incoming circuit breakers shall be equipped with inter-tripping from HV circuit breaker with cross interlock facilities provided. Revision: 2 Feb 2012 Noel Corry Page 19 of 27

20 Or: - On switchboards with bus couplers, a fault trip on an incoming circuit breaker shall also trip the closed bus coupler. The particular design of the installation shall dictate the interlocking requirements. It is the responsibility of the supplier to obtain approval from the CCE Ltd Site Electrical Representative for each installation. The supplier shall co-operate with the CCE Ltd Site Electrical Representative in developing suitable written procedures for operation of the system. Power supply equipment for shunt tripping circuits shall be rated at 30 V d.c. with a short term capacity rating of XX 1 ampere hours available with or without the system mains supply available, where 1 is the required battery capacity Protection for Main Low Voltage Switch Boards Main Incomer Overload protection shall be provided on all three phases. The LV main switchboard manufacturer shall arrange a facility to trip the main incoming circuit breaker from an over temperature trip signal. Transformer over temperature alarm and trip volt free contacts shall be provided by the transformer manufacturer. Restricted earth fault protection shall be provided with arrangements to trip low voltage incoming and high voltage circuit breakers. In order to ensure compatibility, the LV main switchboard manufacturer shall include for providing a suitable current transformer as a free issue to the power transformer manufacturer for installation on the neutral busbar of the transformer 5.2 Moulded Case Circuit Breakers (MCCB) Withdrawable or Plug in 4-Pole Moulded Case Circuit Breakers up to and including 630A shall comply with the construction and operating requirements as stipulated by EN :2006. Cascade rating and operation between circuit breakers is not acceptable and absolute selectivity is required. MCCB s shall be rated at 500 volts minimum and will be ASTA certified. MCCB s shall incorporate circuit protective features. MCCB's shall be capable of withstanding prevailing fault levels or shall be protected by appropriately rated back-up fuses. MCCB's shall be pad lockable door interlocked handle and be lockable in the OFF position. Each MCCB shall be mounted within individual compartments and be of plug in pattern up to 630 A current rating, above this rating MCCB s shall be of the fixed pattern. The live side of the MCCB shall be fully shrouded and phase colours for connections shall be clearly identified. All relevant circuit breaker manufacturers' tabulated test data shall be provided. 5.3 Switching Devices All switching devicess shall comply with EN Utilisation categories for switching and disconnecting devices shall be AC23B (infrequent operation of motor or other highly inductive loads) as a minimum. Revision: 2 Feb 2012 Noel Corry Page 20 of 27

21 Switching devices shall not be used as the normal means of motor starting and stopping (i.e. contactors shall be the normal means of motor starting and stopping). The ON or OFF state of the switching device shall be indicated by a flag or other means of positive indication. The mechanism shall be interlocked with the door so that the latter can only be opened when the switching device is in the OFF position. The switching device must be capable of being padlocked in the OFF position. All live parts are to be shrouded (IP20) when the door is open. 5.4 Fuses and Fuse Equipment Fuse and fuse equipment shall comply with the relevant parts of EN :2007 All fuses shall be of the HRC type of class gg utilisation category and comply with EN IEC :2007, for protection against overload and short circuit currents. Class gm fuses for motor protection shall not be used for distribution purposes. All fuse links shall be provided by the switchgear manufacturer. A full set of spare fuse links shall be supplied. 5.5 Metering Energy Meters Where metering is required all protection shall be via HRC fuse cartridges. Instrumentation shall be of the flush pattern type and shall be included on all outgoing circuits, and shall be provided with: Current Display per phase Voltage display per phase / phase and phase / neutral. Power Factor Correction Incomers A kwh meter for 3 phase 4 wire unbalanced loads shall be provided on each main board incoming circuit, complete with facilities to transmit by Ethernet and Pulse Type energy usage signals, at 1 pulse equal to 1Kw to a remotely mounted supervisory computer system. All main incomers shall be provided with a multi function auto meter with a digital display unless otherwise stated. Maximum demand shall be indicated on each incoming circuit Outgoing Circuits Each outgoing circuit is to have an individual 3 phase 4 wire power meter, complete with facilities to transmit by Ethernet and Pulse Type energy usage signals at 1 pulse equal to 1Kw to a remotely mounted supervisory computer system. 5.6 Cables & Wiring Types All wiring shall be carried out in one or more of the following types of cable or as otherwise agreed with the CCE Responsible Person. Wires: Single core stranded copper PVC insulated wires in conduit and trunking to IEC Revision: 2 Feb 2012 Noel Corry Page 21 of 27

22 Cables: PVC insulated PVC sheathed copper conductor multi core cable to IEC This is to be used in general control circuit applications. All power cables must be shielded cables, excluding cables from low tension distribution board to machine. Every shielded cable shall be connected to an earth bar at the entrance of the cabinet. Care shall be taken that the shielding is resistant to the chemicals used in the area. All feed cables must consist of 4 cores (3 phases and earth conductor). For cable types see section 13.1 if these cables are not suitable for the area / installation / equipment then a different Lapp Group cable shall be used, this shall be agreed with the CCE responsible person. 5.7 Tools Any special tools, equipment or test leads required for testing and maintenance shall be provided by the manufacturer. 6. Interlocking Interlocks should be mechanical in nature and shall be preventative rather than corrective in operation. For with more than one source of supply the following will apply. 6.1 Non Paralleled Supplies Standard Castell interlocking facilities shall be incorporated between each incomer and the relevant bus section to prevent parallel supplies, which could prevent a source of energy to an isolated transformer. The engraving of the locks shall be as specified by the CCE Inc. Responsible Person. 6.2 Paralleled Supplies Operation and interlocking shall give due consideration to:- Isolation of transformer for maintenance Isolation of Low Voltage Switchboard sections for maintenance Fault level of paralleled supplies Standard Castell type interlocking facilities shall be incorporated between incomers and bus section circuit breakers to prevent supplies being paralleled. The engraving of the locks shall be specified by the CCE Inc. Responsible Person. Circuit breaker interlocks shall be provided to prevent: - the circuit breaker being inserted into its housing unless it is in the isolated position. the circuit breaker being closed unless it is in its service or isolated position. the circuit breaker being inserted or withdrawn unless it is open. the circuit breaker cannot be inserted into any position other than that that has been selected on the selector mechanism. Revision: 2 Feb 2012 Noel Corry Page 22 of 27

23 7. Fault Rating LV switchboard bus bars shall be ASTA Certified as follows: Board Rating Short Circuit Rating 800 A 26 ka for 1 second > 2,000 A 50 ka for 1 second 2,000 A > 80 ka for 1 second Certificates for the tested assemblies shall be provided prior to installation. The fault rating, making and breaking capacity of distribution boards and control gear shall be appropriate to the system fault level at the point of installation. It is the contractor's responsibility to ascertain relevant parameters. Fault and thermal ratings shall be related to the specific enclosure in which the circuit breaker is installed. Free Air ratings are not acceptable. 8. Diversity Where not otherwise specified in the contract or obvious from known loading conditions Diversity factors applied to switchboards shall be as recommended in EN : Spare Capacity A minimum of 20% additional equipped spare capacity shall be provided. The configuration of the spare capacity shall be agreed with the CCE responsible person at the design stage. 10. Power Factor Correction 10.1 Power Factor Correction Design of power factor correction equipment shall take into account present and likely harmonic content. Power factor equipment shall form an integral part of the LV main switchboard. Power factor correction cubicles shall be equipped with incoming fuse switches interlocked with the cubicle door. 300 kvar (maximum) capacitor banks shall be divided into six groups of 50 kvar each. De Tuning capacitor banks shall be considered. Each group shall be provided with a set of suitable fuses and a contactor. Indication for each group shall be viewable at the PFC controller / meter. Power factor correction equipment shall be fully automatic and controlled from six stage automatic power factor correction relays. Revision: 2 Feb 2012 Noel Corry Page 23 of 27

24 A loss of supply volts facility shall be incorporated, so that if the supply is lost for any reason, the capacitors will be automatically de-energised, and when the supply is restored, they will be re-energised in sequence with suitable time delay between stages. A suitable current transformer shall be included in the Phase 1 supply of the incoming main switchboard bus bars for PFC control reference. 11. Inspection & Testing 11.1 Manufactures Type Tests Switchgear suites shall be completely assembled, wired and tested at the manufacturer's premises. The following type tests shall be undertaken and recorded: - Verification of temperature rise limits. Verification of dielectric properties. Verification of short-circuit capacity. Verification of continuity of protective circuits. Verification of creep distances. Verification of mechanical operations. Verification of degree of protection Particular Board Test The following routine tests shall be conducted. In all cases, test results shall be furnished on completion. Inspection of the switchboard including all wiring and interlocks. Electrical operational tests. Dielectric tests. Checking of all metering, protective devices and continuity of circuits. Routine inspection and tests shall be repeated before commissioning on site Energisation Prior to Energisation of the switchboard on site, it shall be demonstrated that it is safe to be put into service. This shall include, but not be limited to, proving that all protection relay, safety and control devices have been correctly set and that the installation complies with this specification and any other relevant requirements. Test certificates shall be provided and accepted before energisation. Revision: 2 Feb 2012 Noel Corry Page 24 of 27

25 12. Documentation 12.1 Electrical Drawings Electrical engineering drawings shall be made in the latest version of Eplan, following the guidelines described in the CCE Eplan P8 standard (CCE_Eplan_P8_Standard_Issue_2011.doc). Structure of electrical drawing shall be according to IEC61346 (group and Place). Symbols shall be according to IEC Electrical drawings shall contain only components present in the cabinet and shall be drawn in landscape. Electrical drawings shall be delivered as-built: they shall be a perfect reproduction of the installation. On all electrical drawings, each symbol (sensor-actuator-device- ) must have a comment at the bottom of the page which explains functionality. This comment must be identical to the comment in PLC-program. For modifications to an existing project, the latest version of electrical drawings and PLC-program shall be requested from the CCE responsible person. Each electrical component shall be linked with manufacturer details, visible in properties of the component. All components shall be listed in a table comprising of: component number, location in electrical drawing, supplier, manufacturer and manufacturer reference number. Electrical drawings shall contain an overview of the physical location of the electrical cabinets used in the electrical drawing (indicated by + ). All + codes shall be indicated on a layout of the machine. Electrical drawings shall contain an overview of all networks (ASI Profibus Ethernet), including the cabinet number in which the network component is built-in / including the electrical component number of all network components / including a cross reference between overview drawing and electrical drawing. Supplier shall provide a preliminary version of the electrical drawings before starting the construction of the panels. CCE responsible person will advise/comment, but the responsibility remains with the supplier. The electrical drawing shall be fully documented in English and the language specified by the table below. France Belgium Gent/Antwerp Belgium Chaudfontaine The Netherlands Great-Britain Norway Sweden French OR English Dutch OR English French OR English Dutch OR English English Norwegian OR English Swedish OR English It is the Supplier s responsibility to ensure that an up to date set of drawings are left on site whilst the as built drawings are finalised. As Built electrical drawings shall be delivered in electronic format and on paper, no later than 2 months after commissioning. The verification procedure done by the drawing software shall result in a set of error free drawings (empty error list). The supplier shall deliver 1 x Electronic copy & 1 x Hard copy (paper). Interfacing between machines: The terminal block and terminal numbers and I/O addresses of destination cabinet have to be drawn in the electrical drawing of the originating cabinet. Machine interface signals have to be exchanged before installation on-site. Revision: 2 Feb 2012 Noel Corry Page 25 of 27

PROJECT: SUPPLY & INSTALL ELECTRICAL SWITCHBOARD AT SENGKURONG EXCHANGE PHASE 1, JLN TUTONG, BSB. SCOPE OF WORK The scope of work under Electrical Services shall include but not limited to the supply,

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) GENERAL MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) SUBMITTED BY SASHIKUMAR G BHARAT HEAVY ELECTRICALS LIMITED INDUSTRIAL SYSTEMS GROUP Prof. C. N. R. Rao Circle I. I. Sc. POST Malleswaram Bangalore

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION-16075 ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Electrical identification to identify all electrical items for easy operation and maintenance including, but not limited

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

General Requirements. Technical Specification LVAC Systems

General Requirements. Technical Specification LVAC Systems Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks LVAC Systems NO: 423-1

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC System units The two units of the are used as below: Approvals 1. with

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and Guidance NSI 26 RAILWAY CONNECTION CIRCUITS Copyright National Grid plc 2016, all rights reserved. No part of this publication

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

SUBJECT HEADING: Switching Programmes ISSUE: 18

SUBJECT HEADING: Switching Programmes ISSUE: 18 SUBJECT: Switchgear/Switching PROCEDURE: S04 SUBJECT HEADING: Switching Programmes ISSUE: 18 DATE: Apr 2017 1. INTRODUCTION 1.1 A written programme of switching operations shall be prepared. This programme

More information

MISTRAL SYSTEM IMPACT 2

MISTRAL SYSTEM IMPACT 2 MISTRAL 25-40A SYSTEM 100-400A IMPACT 2 400-6300A Megabarre Group represents the perfect fusion of a global offer, a highly-qualified service and a great working efficiency. The certificated quality of

More information

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS ENGINEERING DESIGN STANDARD EDS 08-2109 LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS Network(s): Summary: EPN, LPN, SPN This standard provides guidance on the installation of

More information

Busbar and Modular Wiring Systems

Busbar and Modular Wiring Systems Chapter 11 Busbar and Modular Wiring Systems 11.1 BUSBAR SYSTEM The wide range of busbar system is available and can be used for single or three-phase distribution to many types of applications ranging

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 13 DISTRIBUTION SWITCHBOARDS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Power Quality. Case Study. Conrad Bottu Laborelec January 2008 Case Study Electromagnetic compatibility (EMC) study Breakdown of low voltage electronic equipment in a 25 kv substation Conrad Bottu Laborelec January 2008 Power Quality Power Quality 1 Introduction Description

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

SYNCHRONISING AND VOLTAGE SELECTION

SYNCHRONISING AND VOLTAGE SELECTION SYNCHRONISING AND VOLTAGE SELECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

Signal converter for electromagnetic flowmeters

Signal converter for electromagnetic flowmeters Quick Start Signal converter for electromagnetic flowmeters Electronic revision: ER 3.0.xx The documentation is only complete when used in combination with the relevant documentation for the flow sensor.

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

INTERPLANT STANDARD - STEEL INDUSTRY

INTERPLANT STANDARD - STEEL INDUSTRY INTERPLANT STANDARD - STEEL INDUSTRY SPECIFICATION FOR MOULDED - CASE CIRCUIT-BREAKER FOR VOLTAGES NOT EXCEEDING 1000 V ac OR 1500 V dc (FIRST REVISION) IPSS:1-04-004-11 IPSS BASED ON IS/IEC 60947(Part

More information

ELECTRICAL INSTALLATIONS REGULATIONS FOR

ELECTRICAL INSTALLATIONS REGULATIONS FOR KINGDOM OF BAHRAIN ELECTRICITY AND WATER AUTHORITY REGULATIONS FOR ELECTRICAL INSTALLATIONS PREFACE This revised and enlarged edition of the wiring regulation replaces the 1985 edition of the Regulations

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013

ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013 ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

ACCESS TO HIGH VOLTAGE APPARATUS

ACCESS TO HIGH VOLTAGE APPARATUS CORPORATE PROCEDURE ACCESS TO HIGH VOLTAGE APPARATUS Approved By: Prepared By: Issue Date: 17/6/2011 Andrew Macrides Access to Apparatus Rules File No: Managing Director Committee QDOC2011/63 Status: Approved

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Section five. Connection systems. Isobar 4 Evo MCB pan assemblies Mulitclip busbar and Polybloc 126. Comb busbars 127

Section five. Connection systems. Isobar 4 Evo MCB pan assemblies Mulitclip busbar and Polybloc 126. Comb busbars 127 Connection systems Section five Isobar 4 Evo MCB pan assemblies 122 1 Mulitclip busbar and Polybloc 126 Comb busbars 127 Terminals and installation accessories 128 129 121 Isobar 4 Evo MCB pan assemblies

More information

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17

More information

ZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR

ZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR ZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR The flexibility of the Zucchini MS range during planning and installation makes it ideal for frequently changing requirements in small to medium sized commercial

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

BGE STRATEGIC CUSTOMER ENGINEERING

BGE STRATEGIC CUSTOMER ENGINEERING TABLE OF CONTENTS 1. GENERAL. 2 2. BGE SUPPLY FEEDER. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY. 5 4. CIRCUIT BREAKER. 9 5. SWITCHGEAR EQUIPMENT... 10 6. MAIN AND GROUND BUS.... 15 7. GROUND AND TEST DEVICE.

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters Section [26 35 26][16280] Active Harmonic Filters (Low Voltage) Part 1 General 1.1 Summary A. Scope: Provide design and engineering, labor,

More information

5/2 Introduction. Unequipped Distribution Boards 5/4 Modular distribution boards 5/5 Add-on parts

5/2 Introduction. Unequipped Distribution Boards 5/4 Modular distribution boards 5/5 Add-on parts ALPHA AS Modular Distribution Boards /2 Introduction Unequipped Distribution Boards /4 Modular distribution boards / Add-on parts Assembly Kits for Unequipped Distribution Boards /6 8GK4 assembly kits

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2 FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

page 2 of 86 Report reference No:

page 2 of 86 Report reference No: articulars: test item vs. test requirements 3. Classification 3.1. Utilization category: (A or B)... : A 3.2. Interruption medium: (air, vacuum, gas Break)... : Air 3.3. Design: (open construction, moulded

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

2014 NEC Changes Part 1

2014 NEC Changes Part 1 www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL

INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL IPSS: 1-10-035-06 IPSS Corresponding IS does not exist 0. FOREWORD 0.1 This

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation 2394 EXAM PAPER 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation 2. There are various documents that are relevant to the Inspection and

More information

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General Section 16621A - AUTOMATIC TRANSFER SWITCH Part 1 General 1.01 One 600 Amp, 3 Phase, 480 Volt Automatic Transfer Switch (ATS) shall be provided with gasketed enclosure. The ATS shall consist of an inherently

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

Cast resin transformers HARMONY TM

Cast resin transformers HARMONY TM Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing

More information

Testing Manual for Electrical Equipment

Testing Manual for Electrical Equipment EPPM, Singapore, 20-21 Sep 2011 Abstract Testing Manual for Electrical Equipment Nahed Al-Hajeri 1 and Anantha Madhavan 2 Quality Assurance (QA) refers to a program for the systematic monitoring and evaluation

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

KENYA ELECTRICITY GENERATING COMPANY LTD

KENYA ELECTRICITY GENERATING COMPANY LTD KENYA ELECTRICITY GENERATING COMPANY LTD TENDER No. KGN-HYD-014-2016 TENDER FOR REHABILITATION OF PROTECTION EQUIPMENT FOR MASINGA HYDRO POWER STATION 20/06/2016 ADDENDUM NO. 1 In accordance with the tender

More information

Absolute Block. Uncontrolled When Printed Document to be part superseded by GKRT0055 Iss 1 and GKRT0077 Iss 1 (published on 07/09/2013)

Absolute Block. Uncontrolled When Printed Document to be part superseded by GKRT0055 Iss 1 and GKRT0077 Iss 1 (published on 07/09/2013) Signatures removed from electronic version Submitted by... Richard Genner Nominated Responsible Manager Approved by... Philip Wiltshire Chairman, Train Control & Communications Subject Committee Approved

More information

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201 Low Voltage Products Enclosed Third Harmonic Filter and star Enclosed units Brochure S1GB 3_4 1SCC333C21 The Third Harmonic - a Growing Problem Today's electrical networks and plants are under much more

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions conduit? 9/8/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Can branch circuits of different services be installed in the same Yes, see 300.3(C)(1) for conductors of different systems

More information

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011 NATIONAL RULES FOR ELECTRICAL INSTALLATIONS Fourth Edition ET 101:2008 Extracts from Amendment No.1:2011 22 June 2011 Page vi: Insert after 1 st Paragraph: Section 710: Medical Locations was prepared by

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT NAME DESIGNATION SIGNATURE DATE Compiled by Ephantus Nyagah Ag. Senior Engineer Checked by Eng. Thagichu Kiiru Deputy

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 00 00.00 20 (July 2006) ------------------------------- Preparing Activity: NAVFAC Superseding UFGS-26 00 00.00 20 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Operating instructions Fail-safe delay timer AZS About this document. Content

Operating instructions Fail-safe delay timer AZS About this document. Content 8 Appendix 8.1 Wiring example...4 8.2 Integral System Diagnostics (ISD)....5 9 EU Declaration of conformity Operating instructions.............pages 1 to 6 Original x.000 / 11.2017 / v.a. - 101126753-

More information

Hamdy Faramawy Senior Application Specialist ABB Sweden

Hamdy Faramawy Senior Application Specialist ABB Sweden Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy

More information

EMC filters. Mounting instructions. Date: January 2006

EMC filters. Mounting instructions. Date: January 2006 Date: January 2006 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS prior express consent is prohibited. EMC cannot be assured

More information

VARIABLE FREQUENCY DRIVE SPECIFICATION

VARIABLE FREQUENCY DRIVE SPECIFICATION VARIABLE FREQUENCY DRIVE SPECIFICATION 1.0. SUMMARY The use of variable frequency drives (VFDs) in conjunction with wastewater lift stations has been identified as a means improve efficiency and to moderate

More information

HAWK5000 Operators Manual

HAWK5000 Operators Manual HAWK5000 Operators Manual Keison Products P.O. Box 2124, Chelmsford CM1 3UP, England Tel: +44 (0) 1245 600560 Fax: +44 (0) 1245 600030 Email: sales@keison.co.uk www.keison.co.uk KANE INTERNATIONAL LIMITED

More information

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations Version: 3.1 Date of Issue: September 2016 Page: 1 of 21 NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations 1. Purpose The purpose of this document is to detail the technical requirements

More information

11/0 IZM circuit-breakers, IN switch-disconnectors

11/0 IZM circuit-breakers, IN switch-disconnectors 11/0 IZM circuit-breakers, IN switch-disconnectors Contents IZM circuit-breakers, IN switch-disconnectors 11/1 from 630 A 6300 A Page Description 11/2 Technical overview 11/4 Overview of functions for

More information

Earthing, HV Switching and Associated Operational Equipment. Approval: Chief Operating Officer

Earthing, HV Switching and Associated Operational Equipment. Approval: Chief Operating Officer ACCESS PRACTICE AP 24 Earthing, HV Switching and Associated Operational Equipment Process Authority: Manager Operations Improvement Approval: Chief Operating Officer Version Date: 27/08/2013 Revision:

More information