Technical Documentation Electronic Characterized Control Valves (CCV)

Size: px
Start display at page:

Download "Technical Documentation Electronic Characterized Control Valves (CCV)"

Transcription

1 Technical Documentation Electronic Characterized Control Valves (CCV) Effective March 005 Table of Contents Control Valve Product Range... Valve/ctuator Selection t Glance...4 Electronic Characterized Control Valves (CCV) Features/enefits...6 Sizing/Selection...0 rass Trim (/ -/4 ) Two-way/Three-way... Stainless Steel Trim (/ - ) Two-way/(/ - ) Three-way...4 Stainless Steel Trim (-/ - ) Two-way Flanged ccessories...4 Flow Pattern/Set-up...8 MFT Configuration Form... Specifications... Terms and Conditions...6 Quotation/Order Form...8 elimo Project: Mandalay uilding Las Vegas, Nevada Platinum Distributors...9

2 Control Valve Product Range Electronic Pressure Independent Characterized Control Valves U.S. Patent Electronic Characterized Control Valves U.S. Patent Electronic Zone Valves PICCV CCV PICCV Service: Flow Rate: Material: Control: Two-way / to Chilled/hot water, 60% glycol GPM rass ody rass/stainless trim Floating Multi-Function Technology Spring Return or Non-Spring Return Typical pplication ir Handling Units: Heating Coils Cooling Coils Unit Ventilators VV ox Re-heat Coils Series Series 6 Series Two-way Three-way Mixing/diverting Two-way Flanged / to Service: Chilled/hot water, 60% glycol C v Range: Material: Stainless trim or rass trim Control: On/Off, floating, -0 VDC Multi-Function Technology Spring Return or Non-Spring Return Typical pplication ir Handling Units: Heating Coils Cooling Coils Fan Coil Units: Heating Coils Cooling Coils Unit Ventilators VV ox Re-heat Coils ypass loops ZONE N Series Two-way NPT ZONE S Series Two-way Sweat ZONE N Series Three-way Diverting NPT ZONE S Series Three-way Diverting Sweat Service: Chilled/hot water, 50% glycol C v Range: Material: rass ody Control: On/Off Spring Return Typical pplication Fan Coil Units: / to aseboard Radiation Heating Coils Cooling Coils G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. For detailed information and submittal data, see Technical Documentation at or on CD-ROM.

3 Control Valve Product Range Electronic Globe Valves Electronic utterfly Valves Retrofit Solutions and Supplementary Valve Offering Call elimo for Details G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. G (S) Two-way Screwed Series ronze or Stainless Trim G6 C (S) Series Two-way Flanged G6 (S) Series ronze or Stainless Trim G6 (S)-50 Two-way Flanged Series NSI 50 ronze or Stainless Trim G (D) Three-way Screwed Series ronze Trim G7 (S) Three-way Flanged Series ronze or Stainless Trim G7 (S)-50 Three-way Flanged Series NSI 50 ronze or Stainless Trim Three-way Valves available in Mixing or Diverting Service: C v Range: Material: Control: / to 6 Chilled/hot water, 60% glycol, steam (Two-way).-40 (Three-way Mix.) (Three-way Div.) Stainless steel stem, ronze plug or Stainless plug On/Off, floating, -0 VDC Multi-Function Technology Spring Return or Non-Spring Return Typical pplication ir Handling Units: Heating Coils Cooling Coils Fan Coil Units: Heating Coils Cooling Coils Unit Ventilators VV ox Re-heat Coils ypass loops F6 Series (HS,HSU) F7 Series (HS,HSU) Two-way Three-way Mixing/diverting to 0 Service: Chilled/hot water, 50% glycol C v Range: 5-7,46 Material: Stainless shaft Stainless Disc Cast Iron, Full Lug ody EPDM r Control: On/Off, floating, -0 VDC On/Off, floating -0 VDC,-5 VDC, 4-0m (NEM 4 actuator) Multi-Function Technology Spring Return or Non-Spring Return Typical pplication Chiller and cooling tower isolation Change-over systems Large air handler coil control ypass control applications Retrofit Solutions Globe Valves: UNV Series Direct Coupled ctuator, Two-way Valves Three-way Valves UGLK Series Linkage Solution, Two-way Valves Three-way Valves utterfly Valve: UFLK Series Linkage Solution, Two-way Valves Three-way Valves Retrofit solutions for virtually any valve Manufacturers: Globe: Siemens, Johnson, Honeywell, Invensys, etc. utterfly: ray, Centerline, Keystone, Flowseal, etc. Control: On/Off, floating, -0 VDC Multi-Function Technology Spring or Non-Spring Return Supplementary Valve Offering Pressure Independent Valves: Up to 8 Non-Spring and Spring Return ctuation Industrial NEM 4 ctuation Standard all Valves: Stainless trim Non-Spring and Spring Return ctuation For Steam pplication utterfly Valves: Up to 0 NSI 50/00 Rated Stainless Trim Industrial Spring Return NEM 4 ctuation Pneumatic ctuation For detailed information and submittal data, see Technical Documentation at or on CD-ROM. Call Customer Service to discuss your application.

4 Valve/ctuator Selection t Glance ase product nomenclature 09 + LF4-MFT US VLVE CTUTOR 09 LF4 MFT US VLVE SIZES 4 VC/DC Power* For North/South merican Market Valve Designation Sizes CCV Valve = / TR LR TYPE OF VLVE CHRCTERIZED CONTROL VLVE (CCV) -way Stainless Steel all & Stem -way Chrome Plated rass all & rass Stem -way Stainless Steel all & Stem -way Chrome Plated rass all & rass Stem 6 -way Stainless Steel all & Stem, Flanged Non-Spring Return ctuator Spring Return ctuator NM M TF LF F Increasing Torque Increasing Torque Rotary Rotary DESIGNTOR MFT SR *0 volt available on some models DESCRIPTION Multi-Function Technology (MFT) 0 VDC Control or Selectable (See MFT chart opposite) -0 VDC Floating point None On/Off G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 4

5 Valve/ctuator Selection t Glance Specify upon ordering +NO/FO+P-000+HU- SET-UP MFT CONFIGURTION TGGING NO/FO P-000 HU- SET UP* Non-Spring Models NO = Normally Open NC = Normally Closed Spring Return Models NO/FO = Normally Open/Fail Open NO/FC = Normally Open/Fail Closed TGGING Valves may be tagged per customer specification Example: HU- FCU- NC/FO = Normally Closed/Fail Open NC/FC = Normally Closed/Fail Closed See default settings *Refers to valve ports to G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Multi-Function Technology See ppendix for Complete List of Configurations Code Control Input Running Time uilt-in Feedback List Price P VDC 50-0 VDC No Charge P VDC VDC No Charge P VDC VDC No Charge P VDC VDC No Charge P VDC VDC No Charge P sec. PWM 50-0 VDC No Charge P sec. PWM 50-0 VDC No Charge P-000 Floating Point 50-0 VDC No Charge Example: LF4-MFT US is the basic model. dd the P pre-set MFT configuration number and list price to the actuator when ordering, as needed. Note: Most popular configurations available at no additional cost. ll other configurations carry a $0.00 list price. ORDERING EXMPLE Choose the desired valve/actuator combination based on valve ratings and actuator control parameters from the following pages. 09+LF4-MFT US+ Specify Configuration (important) Multi-Function Technology: P-000 (0-0 VDC input / 0-0 feedback) Set-up: NO/FO (Normally Open / Fail Open) Tagging: HU- 09+LF4-MFT US+NO/FO+P-000+HU- Total 5

6 Characterized Control Valves (CCV) Equal percentage valve characteristic In order to ensure good stability of control, it is essential for a control valve to have an equal percentage characteristic. This type of characteristic produces a linear variation in thermal output according to the amount of opening of the valve (also known as the system characteristic). Under normal testing conditions a conventional ball valve exhibits an S-shaped characteristic. When it is installed in a real system, however, this characteristic is seriously deformed because, compared with its nominal size, a ball valve possesses an extremely high flow coefficient. Whether used with or without pipe reducers or a reduced bore, they do not normally allow stable regulation of the thermal capacity. elimo s unique Characterized Control Valve (CCV) is very different. special characterizing disc inside the valve gives it an equal percentage characteristic which is comparable with that of a globe valve of the same nominal size. The flow (the Cv value) is reduced to the required value by a combination of the hole in the ball and the shaped aperture in the disc. The increase in flow as the valve is opened is very slow and controlled. This produces better part-load behavior and improved stability of control while also optimizing energy consumption. enefit of the elimo Characterizing Disc Equal percentage flow characteristic. Patented Technology Excellent control stability assured with the characterizing disc. Cv values equal to C v values of globe valves the same size. The need for multiple pipe reduction is usually eliminated. etter control prevents hunting of the control loop, increasing life span of actuator and valve. Features Thermal isolating adapter between flange and actuator. Easy direct coupling of actuator with a single screw. Perpendicular mounting flange and square drive head eliminate lateral forces on the stem. low-out proof stem with thrustbearing double O-ring design for long service life.* Non-corroding chrome-plated brass or stainless ball. Vent holes reduce condensation build-up. Forged brass valve body no pinhole leaks. Characterizing disc made of Tefzel known for excellent strength and chemical resistance. Teflon seats with O-rings provide constant seating force against the ball and reduce torque requirement. ctuator can be mounted in four different positions. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. * Designed for service life of over 00,000 full cycles. Teflon and Tefzel are both registered trademarks of Dupont, Inc. 6

7 Characterized Control Valves (CCV) Coordinated motorized operation The optimum functionality of the elimo CCV is assured by properly coordinating its actuation with MFT. Specially developed rotary actuators provide the necessary precision for modulating, floating-point, and on/off methods of control. ll CCVs are supplied with the appropriate rotary actuator to provide the close-off and operation desired. Series Series 6 Series Two-way Three-way Mixing/diverting Two-way Flanged / to Optimized for control The elimo CCV marries known technology with an innovative development the unique characterizing disc. The marriage of CCV and MFT technologies has produced a range of valuable features which surpass the capabilities of globe valves at a very attractive price level: n equal-percentage valve characteristic Unlike a globe valve, no sudden change in inlet flow upon opening Excellent stability of control Cv values comparable with those of globe valves of the same size or larger Higher close-off ratings than standard globe valves 00% tight shut-off on two-way valves means NO leak-by unlike globe valves that have NSI IV shutoff (leakage rate of 0.0% of the Cv rating) Three-way valve can be piped in mixing or diverting application Service: Chilled/hot water, 60% glycol Cv Range: Material: Stainless trim or rass trim Control: On/Off, floating, -0 VDC Multi-Function Technology Spring Return or Non-Spring Return Flow Characteristics of Conventional all Valves versus elimo Characterized Control Valves G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Heat Emission Flow Heat Emission Flow 0% 00% 00% Resulting Heat Resulting Heat Output Reduced Port Valve Flow Characteristic Output Oversized Valve Flow Characteristic flow flow (Desired equal percentage Degree Opening Flow characteristic) characteristic) (Desired equal percentage 00% Stabile control is hard to achieve Desirable valve authority is not achieved Heat Emission Flow 0% 00% Typical coil characteristic elimo CCV Resulting heat output is linear. flow Degree Opening Flow characteristic = equal percentage 00% Desirable Equal Percent Flow and resulting heat output is achieved with linear results 0% Degree Opening Flow 00% 7

8 Characterized Control Valves (CCV) New TR rotary actuators New TF spring return actuator The small, exceptionally compact TR rotary actuator has been specially developed for the motorized operation of / to /4 Characterized Control Valves. On/Off, floating, or modulating control Easy-to-read position indicator shows flow pattern for twoand three-way valves Manual override Constant running time Compact dimensions.5 by.5 by.5 perfect for reheat applications and small spaces Protected terminal strip or cable options of -ft, 6-ft and 0-ft 4 mounting positions One central screw for easy mounting 4 VC power The compact TF spring return actuator has been designed for use with elimo / to /4 Characterized Control Valves and features a true mechanical fail/safe. On/Off, floating, or modulating control Mechanical spring fail safe rushless DC motor technology Reversible spring direction Compact size G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 8

9 Characterized Control Valves (CCV) Two-way with NSI 5 flanges, in sizes -/ - for use in large air handling applications Two-way NPT screwed body, sizes -/ - for use in large air handling applications New Expanded of CCV for LL of your control applications G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Two-way and Three-way / valves with low Cv values perfect for reheat applications Two-way - NPT screwed valves ideal for larger air handler applications Two-way -/ - flanged valves offer the combination of high close-off and large Cv values 9

10 Sizing/Selection Table : Valve Flow Rate for Water pplications (Gallons Per Minute, GPM) Cv Valve Two Three Pressure drop across the valve Maximum DN Way Way Rating Inches mm CCV CCV psi psi psi 4 psi 5 psi 6 psi 7 psi 8 psi 9 psi 0 psi 0. / / / / / / / / / 5 5* 5* / / / /4 0 0* 0* * 5* / /4 0* 0* / /4 * * / / / 40 40* 40* * 50* * / / / / / 65 65* * / / / / / * GPM = Cv x p * = Models with no characterizing disc. The influence of the pipe geometry due to reduced flow is negligible for all valves 57 C v and below with characterizing discs. bove information applies to chrome plated brass ball and stem versions also ( ). G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 0

11 Sizing/Selection Table : Piping Reduction Factor (Fp) - Correction Factor for Valves Valve size size Model # Inches DN mm / /4 -/4 -/ -/ / / / / / " " " " /" /" /" /" /" " " " G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 66 -/" /" /" /" /" " " "

12 / Series Characterized Control Valve, Non-Spring Return ctuator Two-way and Three-way Valves with Chrome Plated rass all and rass Stem, NPT female ends TR TR Two-way Characterized Control Valve, Chrome Plated rass all and rass Stem Valve Non-Spring Return ctuator Model Cv Valve On/Off, Floating Proportional # Rating Nominal Size Close- CCV DN Off Valve Inches mm psi TR4--T US TR4-SR-T US / 5 00 Pg 0 Pg / 5 00 Pg 0 Pg / 5 00 Pg 0 Pg 0. / 5 00 Pg 0 Pg.9 / 5 00 Pg 0 Pg.0 / 5 00 Pg 0 Pg 4.7 / 5 00 Pg 0 Pg / 5 00 Pg 0 Pg 5* 0 / 5 00 Pg 0 Pg / Pg 0 Pg / Pg 0 Pg 9 0 / Pg 0 Pg 0* 4 / Pg 0 Pg Electrical Covered Covered Connection Terminal Strip Terminal Strip * Models without characterizing discs. See pg for corrected C v s with piping reduction factor. Three-way Characterized Control Valve, Chrome Plated rass all and rass Stem Valve Non-Spring Return ctuator Model Cv Valve On/Off, Floating Proportional # Rating Nominal Size Close- CCV DN Off Valve Inches mm psi TR4--T US TR4-SR-T US / 5 00 Pg 4 Pg / 5 00 Pg 4 Pg / 5 00 Pg 4 Pg 6 0. / 5 00 Pg 4 Pg 6.9 / 5 00 Pg 4 Pg 6.0 / 5 00 Pg 4 Pg / 5 00 Pg 4 Pg 6 5* 0 / 5 00 Pg 4 Pg / Pg 4 Pg / Pg 4 Pg 6 0* 4 / Pg 4 Pg 6 Electrical Covered Covered Connection Terminal Strip Terminal Strip * Models without characterizing discs. See pg for MFT Configuration. TR4--T US TR4--T US TR4-SR-T US TR4-SR-T US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. TR4--T US Options (add to list price) TR4-SR-T US -foot cable TR4- US, TR4-SR US Pg 0//4/6 6-foot cable TR /00 US Pg 0//4/6 0-foot cable TR /00 US Pg 0//4/6

13 / Series Characterized Control Valve, Spring Return ctuator Two-way and Three-way Valves with Chrome Plated rass all and rass Stem, NPT female ends TF TF G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Two-way Characterized Control Valve, Chrome Plated rass all and rass Stem Valve Spring Return ctuator Model Cv Valve On/Off Floating Proportional # Rating Nominal Size Close- CCV DN Off Valve Inches mm psi TF4 US TF4- US TF4-SR US / 5 00 Pg 8 Pg 0 Pg / 5 00 Pg 8 Pg 0 Pg / 5 00 Pg 8 Pg 0 Pg 0. / 5 00 Pg 8 Pg 0 Pg.9 / 5 00 Pg 8 Pg 0 Pg.0 / 5 00 Pg 8 Pg 0 Pg 4.7 / 5 00 Pg 8 Pg 0 Pg / 5 00 Pg 8 Pg 0 Pg 5* 0 / 5 00 Pg 8 Pg 0 Pg / Pg 8 Pg 0 Pg / Pg 8 Pg 0 Pg 9 0 / Pg 8 Pg 0 Pg 0* 4 / Pg 8 Pg 0 Pg Electrical ft cable, ft cable, ft cable, Connection / conduit fitting / conduit fitting / conduit fitting * Models without characterizing discs. See pg for corrected C v s with piping reduction factor. Three-way Characterized Control Valve, Chrome Plated rass all and rass Stem TF4 US Valve Spring Return ctuator Model Cv Valve On/Off Floating Proportional # Rating Nominal Size Close- CCV DN Off Valve Inches mm psi TF4 US TF4- US TF4-SR US / 5 00 Pg 4 Pg 6 Pg / 5 00 Pg 4 Pg 6 Pg / 5 00 Pg 4 Pg 6 Pg 8 0. / 5 00 Pg 4 Pg 6 Pg 8.9 / 5 00 Pg 4 Pg 6 Pg 8.0 / 5 00 Pg 4 Pg 6 Pg / 5 00 Pg 4 Pg 6 Pg 8 5* 0 / 5 00 Pg 4 Pg 6 Pg / Pg 4 Pg 6 Pg / Pg 4 Pg 6 Pg 8 0* 4 / Pg 4 Pg 6 Pg 8 Electrical ft cable, ft cable, ft cable, Connection / conduit fitting / conduit fitting / conduit fitting * Models without characterizing discs. TF4 US, TF0 US available March 005. TF4-S US, TF0-S US, TF4- (-S) US, TF4-SR (-S) US available May 005. See pg for MFT Configuration. TF4 US TF4- US TF4- US TF4-SR US TF4-SR US Options (add to list price) TF4 US TF4- US TF4-SR US built-in aux. switch -S US Pg 8/4 Pg 0/6 Pg /8 0 VC power supply..0 Pg 8/4

14 Series Characterized Control Valve, Non-Spring Return ctuator Two-way Valve with Stainless Steel all and Stem, NPT female ends TR LR NM M Two-way Characterized Control Valve, Stainless Steel all and Stem Valve NM4 US Non-Spring Return ctuator On/Off, Floating On/Off, Floating Proportional Proportional Proportional / MFT Model Cv Valve Close- # Rating Nominal Size Off LR4- US LR4-SR US LR4-MFT US CCV DN psi TR4--T US NM4 US TR4-SR-T US NM4-SR US NM4-MFT US Valve Inches mm M4 US M4-MFT US / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg 48.9 / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg 48.0 / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg 48 5* 0 / 5 00 Pg 40 Pg 44 Pg 4 Pg 46 Pg / Pg 40 Pg 44 Pg 4 Pg 46 Pg / Pg 40 Pg 44 Pg 4 Pg 46 Pg / Pg 40 Pg 44 Pg 4 Pg 46 Pg 48 0* 4 / Pg 40 Pg 44 Pg 4 Pg 46 Pg Pg 44 Pg 46 Pg Pg 44 Pg 46 Pg Pg 44 Pg 46 Pg 48 5* Pg 44 Pg 46 Pg /4 00 Pg 44 Pg 46 Pg 48 0* 9 -/4 00 Pg 44 Pg 46 Pg /4 00 Pg 50 Pg 5 Pg 54 * 7 -/4 00 Pg 50 Pg 5 Pg / Pg 50 Pg 5 Pg / Pg 50 Pg 5 Pg 54 40* 7 -/ Pg 50 Pg 5 Pg Pg 50 Pg 5 Pg Pg 50 Pg 5 Pg 54 50* Pg 50 Pg 5 Pg Pg 56 Pg Pg 56 Pg Pg 56 Pg 58 54* Pg 56 Pg Pg 56 Pg Pg 56 Pg Pg 56 Pg Pg 56 Pg 58 65* Pg 56 Pg Pg 56 Pg Pg 56 Pg 58 80* Pg 56 Pg 58 Electrical Covered ft cable, Covered Terminal ft cable, ft cable, Connection Terminal Strip / conduit Strip / conduit / conduit fitting fitting fitting * Models without characterizing discs. See pg for corrected C v s with piping reduction factor. See pg for MFT Configuration. TR4--T US LR4- US M4 US TR4-SR-T US LR4-SR US NM4-SR US LR4-MFT US NM4-MFT US M4-MFT US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. TR4--T US Options (add to list price) TR4-SR-T US LR4- US built-in aux. switch LR -S US Pg 44 -foot cable TR4- US, TR4-SR US Pg 40/4 6-foot cable TR /00 US, LR /00 US Pg 40/4 Pg 44 0-foot cable TR /00 US, LR /00 US Pg 40/4 Pg 44 4

15 Series Characterized Control Valve, Non-Spring Return ctuator Three-way Valve with Stainless Steel all and Stem, NPT female ends TR LR NM G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Three-way Characterized Control Valve, Stainless Steel all and Stem Valve Non-Spring Return ctuator Model Cv Valve On/Off, Floating On/Off, Floating Proportional Proportional Proportional / MFT # Rating Nominal Size Close- CCV DN Off TR4--T US LR4- US TR4-SR-T US LR4-SR US LR4-MFT US Valve Inches mm psi NM4 US NM4-SR US NM4-MFT US / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg 68.9 / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg 68.0 / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg 68 5* 0 / 5 00 Pg 60 Pg 64 Pg 6 Pg 66 Pg / Pg 60 Pg 64 Pg 6 Pg 66 Pg / Pg 60 Pg 64 Pg 6 Pg 66 Pg 68 0* 4 / Pg 60 Pg 64 Pg 6 Pg 66 Pg Pg 64 Pg 66 Pg Pg 64 Pg 66 Pg 68 5* Pg 64 Pg 66 Pg /4 00 Pg 64 Pg 66 Pg 68 0* 9 -/4 00 Pg 64 Pg 66 Pg /4 00 Pg 70 Pg 7 Pg 74 * 7 -/4 00 Pg 70 Pg 7 Pg / Pg 70 Pg 7 Pg / Pg 70 Pg 7 Pg 74 40* 7 -/ Pg 70 Pg 7 Pg Pg 70 Pg 7 Pg Pg 70 Pg 7 Pg 74 50* Pg 70 Pg 7 Pg 74 Electrical Covered ft cable, Covered Terminal ft cable, ft cable, Connection Terminal Strip / conduit Strip / conduit / conduit fitting fitting fitting * Models without characterizing discs. See pg for MFT Configuration. TR4--T US LR4- US NM4 US TR4-SR-T US LR4-SR US NM4-SR US LR4-MFT US NM4-MFT US TR4--T US Options (add to list price) TR4-SR-T US LR4- US built-in aux. switch LR -S US Pg 64 -foot cable TR4- US, TR4-SR US Pg 60/6 6-foot cable TR /00 US, LR /00 US Pg 60/6 Pg 64 0-foot cable TR /00 US, LR /00 US Pg 60/6 Pg 64 5

16 Series Characterized Control Valve, Spring Return ctuator Two-way Valve with Stainless Steel all and Stem, NPT female ends TF LF F Two-way Characterized Control Valve, Stainless Steel all and Stem Valve Spring Return ctuator On/Off Floating Proportional Proportional / MFT Model Cv Valve # Rating Nominal Size Close- TF4US TF4- US TF4-SR US CCV DN Off LF4 US LF4- US LF4-SR US LF4-MFT US Valve Inches mm psi F4 US F4-SR US F4-MFT US / 5 00 Pg 76 Pg 78 Pg 80 Pg / 5 00 Pg 76 Pg 78 Pg 80 Pg / 5 00 Pg 76 Pg 78 Pg 80 Pg / 5 00 Pg 76 Pg 78 Pg 80 Pg 88.9 / 5 00 Pg 76 Pg 78 Pg 80 Pg 88 / 5 00 Pg 76 Pg 78 Pg 80 Pg / 5 00 Pg 76 Pg 78 Pg 80 Pg / 5 00 Pg 76 Pg 78 Pg 80 Pg 88 5* 0 / 5 00 Pg 76 Pg 78 Pg 80 Pg / Pg 76 Pg 78 Pg 80 Pg / Pg 76 Pg 78 Pg 80 Pg / Pg 76 Pg 78 Pg 80 Pg 88 0* 4 / Pg 76 Pg 78 Pg 80 Pg Pg 8 Pg 84 Pg 86 Pg Pg 8 Pg 84 Pg 86 Pg Pg 8 Pg 84 Pg 86 Pg 88 5* Pg 8 Pg 84 Pg 86 Pg /4 00 Pg 8 Pg 84 Pg 86 Pg 88 0* 9 -/4 00 Pg 8 Pg 84 Pg 86 Pg /4 00 Pg 90 Pg 9 Pg 94 * 7 -/4 00 Pg 90 Pg 9 Pg / Pg 90 Pg 9 Pg / Pg 90 Pg 9 Pg 94 40* 7 -/ Pg 90 Pg 9 Pg Pg 90 Pg 9 Pg Pg 90 Pg 9 Pg 94 50* Pg 90 Pg 9 Pg Pg 90 Pg Pg 90 Pg Pg 90 Pg 94 54* Pg 90 Pg / Pg 90 Pg / Pg 90 Pg / Pg 90 Pg / Pg 90 Pg 94 65* 0 -/ Pg 90 Pg Pg 90 Pg Pg 90 Pg 94 80* Pg 90 Pg 94 Electrical ft cable, ft cable, ft cable, ft cable, Connection / conduit fitting / conduit fitting / conduit fitting / conduit fitting * Models without characterizing discs. See pg for corrected C v s with piping reduction factor. See pg for MFT Configuration. TF4 US TF4- US TF4-SR US Options (add to list price) LF4 US LF4- US LF4-SR US LF4-MFT US F4 US F4-MFT US built-in aux. switch -S US Pg 76/8 Pg 78/84 Pg 80/86 Pg 88 Pg 90 Pg 94 0 VC power supply..0 Pg 76/8 Pg Ω control F4-MFT95 US Pg VDC control LF4-MFT-0 US Pg VDC with switch LF4-MFT-S-0 US Pg 88 dd to -MFT price Note: F not available on all valves. Please contact Customer Service. 6 TF4 US LF4 US F4 US LF4- US TF4- US TF4-SR US LF4-SR US F4-SR US F4-MFT US LF4-MFT US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc.

17 Series Characterized Control Valve, Spring Return ctuator Three-way Valve with Stainless Steel all and Stem, NPT female ends TF LF F Three-way Characterized Control Valve, Stainless Steel all and Stem Valve Spring Return ctuator Model Cv Valve On/Off Floating Proportional Proportional / MFT G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. # Rating Nominal Size Close- TF4 US TF4- US TF4-SR US CCV DN Off LF4 US LF4- US LF4-SR US LF4-MFT US Valve Inches mm psi F4 US F4-SR US F4-MFT US / 5 00 Pg 96 Pg 98 Pg 00 Pg / 5 00 Pg 96 Pg 98 Pg 00 Pg / 5 00 Pg 96 Pg 98 Pg 00 Pg / 5 00 Pg 96 Pg 98 Pg 00 Pg 08.9 / 5 00 Pg 96 Pg 98 Pg 00 Pg 08 / 5 00 Pg 96 Pg 98 Pg 00 Pg / 5 00 Pg 96 Pg 98 Pg 00 Pg 08 5* 0 / 5 00 Pg 96 Pg 98 Pg 00 Pg / Pg 96 Pg 98 Pg 00 Pg / Pg 96 Pg 98 Pg 00 Pg 08 0* 4 / Pg 96 Pg 98 Pg 00 Pg Pg 0 Pg 04 Pg 06 Pg Pg 0 Pg 04 Pg 06 Pg 08 5* Pg 0 Pg 04 Pg 06 Pg /4 00 Pg 0 Pg 04 Pg 06 Pg 08 0* 9 -/4 00 Pg 0 Pg 04 Pg 06 Pg /4 00 Pg 0 Pg Pg 4 * 7 -/4 00 Pg 0 Pg Pg / Pg 0 Pg Pg / Pg 0 Pg Pg 4 40* 7 -/ Pg 0 Pg Pg Pg 0 Pg Pg Pg 0 Pg Pg 4 50* Pg 0 Pg Pg 4 Electrical ft cable, ft cable, ft cable, ft cable, Connection / conduit fitting / conduit fitting / conduit fitting / conduit fitting * Models without characterizing discs. TF4 US, TF0 US available March 005. TF4-S US, TF0-S US, TF4- (-S) US, TF4-SR (-S) US available May 005. See pg for MFT Configuration. TF4 US F4 US LF4 US TF4- US LF4- US TF4-SR US F4-SR US LF4-SR US F4-MFT US LF4-MFT US TF4 US TF4- US TF4-SR US Options (add to list price) LF4 US LF4- US LF4-SR US LF4-MFT US F4 US F4-MFT US built-in aux. switch -S US Pg 96 Pg 98/04 Pg 00/06 Pg 08 Pg 96 Pg 4 0 VC power supply..0 Pg 0 0-5Ω control F4-MFT95 US Pg 4 Pg VDC control LF4-MFT-0 US Pg VDC with switch LF4-MFT-S-0 US Pg 08 dd to -MFT price Note: F not available on all valves. Please contact Customer Service. 7

18 6 Series Flanged CCV, Non-Spring Return ctuator Two-way Valve with Stainless Steel all and Stem, flanged ends M 6 Two-way Characterized Control Valve, Stainless Steel all and Stem Valve Non-Spring Return ctuator Model Cv Valve On/Off, Floating Proportional / MFT # Rating Nominal Size Close- CCV DN Off Valve Inches mm psi M4 US M4-MFT US Pg 6 Pg Pg 6 Pg Pg 6 Pg Pg 6 Pg 8 665* Pg 6 Pg Pg 6 Pg Pg 6 Pg 8 680* Pg 6 Pg 8 Electrical ft cable, ft cable, Connection / conduit fitting / conduit fitting * Models without characterizing discs. See pg for corrected C v s with piping reduction factor. Note: ll 6 valves assembled with CCV-EXT-KIT (See accessories page). See pg for MFT Configuration. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. M4 US M4-MFT US 8

19 6 Series Flanged CCV, Spring Return ctuator Two-way Valve with Stainless Steel all and Stem, flanged ends F 6 Two-way Characterized Control Valve, Stainless Steel all and Stem Valve Spring Return ctuator Model Cv Valve On/Off Proportional / MFT # Rating Nominal Size Close- CCV DN Off Valve Inches mm psi F4 US F4-MFT US Pg 0 Pg Pg 0 Pg Pg 0 Pg Pg 0 Pg 665* Pg 0 Pg Pg 0 Pg Pg 0 Pg 680* Pg 0 Pg Electrical ft cable, ft cable, Connection / conduit fitting / conduit fitting * Models without characterizing discs. See pg for corrected C v s with piping reduction factor. See pg for MFT Configuration. F4 US F4-MFT US Note: ll 6 valves assembled with CCV-EXT-KIT (See accessories page). G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Options (add to list price) F4 US F4-MFT US built-in aux. switch -S US Pg 0 Pg 0 VC power supply..0 Pg 0 0-5Ω control F4-MFT95 US Pg 9

20 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TR4--T US Control Input Impedance Nominal voltage Nominal voltage range Power Consumption Transformer Sizing Electrical Connection On-off/floating point.6 kω 4 VC 50/60 Hz VC W V (Class power source) Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into handle Manual override: Push down handle Running Time hz, hz Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level Max. 5 db () Quality Standard ISO 900 dditional Models TR4- US TR4--T US with ft plenum rated cable TR4-/00 US TR4--T US with 6 ft plenum rated cable TR4-/00 US TR4--T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 0 See Selection Chart Pg for Control Valve No., C v and Close-off

21 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuators, On-Off/Floating Point Dimensions.50 [6.5].8 [7.6].5 [8.6] D069 4 VC Transformer Common + W86 + Provide overload protection and disconnect as required. TR4--T US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] Flow Pattern Characterizing Disc (Where applicable) COM Controller Hot Two-way lk () Common Red () Wht () TR4--T US Provide overload protection and disconnect as required. The Common connection from the actuator must be connected to the Hot connection of the controller. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. Flow direction E L I M O W50 On/Off Control of TR4--T US. You may not use one wire control. 4 VC Transformer Provide overload protection and disconnect as required. Floating Control of TR4--T US Hot Controller COM Common + + TR4--T US lk () Common Red () Wht () Provide overload protection and disconnect as required. TR4--T US The actuator Hot must be connected to the control board Hot. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. W87 W5 Triac Sink Triac Source Note: TR4--T US cannot be wired in parallel with themselves or any other actuator.

22 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TR4-SR-T US Reversing switch under cover Control Proportional Input Impedance 00 kω Nominal voltage 4 VC 50/60 Hz, 4VDC Nominal voltage range VC, VDC Power Consumption 0.5 W Transformer Sizing V (Class power source) Electrical Connection Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into handle Manual override: Push down handle Running Time 90 seconds Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level max. 5 db () Quality Standard ISO 900 dditional Models TR4-SR US TR4-SR-T US with ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 6 ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. See Selection Chart Pg for Control Valve No., Cv and Close-off

23 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuators, Proportional Dimensions.50 [6.5].5 [8.6] D069 4 VC Transformer lk () Common Red () + Hot W90.8 [7.6] to 0 VDC ( ) Control Signal (+) Wht () Y to 0V Input TR4-SR-T US Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] Notes: Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. to 0 VDC Control of TR4-SR-T US Flow Pattern 4 VC Transformer W9 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 4 to 0 m ( ) Control Signal (+) Notes: Ω 500Ω lk () Common Red () + Hot Wht () Y to 0V Input TR4-SR-T US Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. 4 to 0 m Control of TR4-SR-T US Direct/Reverse acting switch is under wiring cover. R = CW with decrease in signal L = CCW with decrease in signal No feedback

24 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TR4--T US Control Input Impedance Nominal voltage Nominal voltage range Power Consumption Transformer Sizing Electrical Connection On-off/floating point.6 kω 4 VC 50/60 Hz VC W V (Class power source) Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into handle Manual override: Push down handle Running Time hz, hz Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level max. 5 db () Quality Standard ISO 900 dditional Models TR4- US TR4--T US with ft plenum rated cable TR4-/00 US TR4--T US with 6 ft plenum rated cable TR4-/00 US TR4--T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 4 See Selection Chart Pg for Control Valve No., C v and Close-off

25 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuators, On-Off/Floating Point Dimensions.50 [6.5].5 [8.6] D06 4 VC Transformer W86.8 [7.6] Common + + C Provide overload protection and disconnect as required. TR4--T US Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] On/Off Control of TR4--T US. You may not use one wire control. 4 VC Transformer Common + W87 Flow Pattern Three-way Mixing Three-way Diverting + G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) COM YPSS Controller Port Disc (ll -way models) Hot Characterizing Disc (where applicable) Port Disc (ll -way models) lk () Common Red () Wht () TR4--T US Provide overload protection and disconnect as required. The Common connection from the actuator must be connected to the Hot connection of the controller. W50 Provide overload protection and disconnect as required. Floating Control of TR4--T US Controller Hot COM TR4--T US lk () Common Red () Wht () Provide overload protection and disconnect as required. TR4--T US The actuator Hot must be connected to the control board Hot. W5 ctuators with plenum rated cable do not have numbers on wires; use color codes instead. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. Triac Sink Triac Source Note: TR4--T US cannot be wired in parallel with themselves or any other actuator. 5

26 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuator, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TR4-SR-T US Reversing switch under cover Control Proportional Input Impedance 00 kω Nominal voltage 4 VC 50/60 Hz, 4VDC Nominal voltage range VC, VDC Power Consumption 0.5 W Transformer Sizing V (Class power source) Electrical Connection Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into handle Manual override: Push down handle Running Time 90 seconds Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level max. 5 db () Quality Standard ISO 900 dditional Models TR4-SR US TR4-SR-T US with ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 6 ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 6 See Selection Chart Pg for Control Valve No., C v and Close-off

27 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TR ctuator, Proportional Dimensions.50 [6.5].5 [8.6] D07 4 VC Transformer W90.8 [7.6] to 0 VDC ( ) Control Signal (+) lk () Common Red () + Hot Wht () Y to 0V Input TR4-SR-T US C Notes: Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. to 0 VDC Control of TR4-SR-T US Flow Pattern 4 VC Transformer W9 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) 4 to 0 m ( ) Control Signal (+) Notes: Ω 500Ω lk () Common Red () + Hot Wht () Y to 0V Input TR4-SR-T US Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. 4 to 0 m Control of TR4-SR-T US Direct/Reverse acting switch is under wiring cover. R = CW with decrease in signal L = CCW with decrease in signal No feedback 7

28 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for on/off control using 4VC/DC or 00 to 40 VC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TF4 US TF4-S US TF0 US TF0-S US Control On-off Power supply TF4(-S) US: 4VC ± 0%, 50/60Hz 4VDC ± 0% Power supply TF0(-S) US: (nominal) 00 to 40 VC, 50/60 Hz (tolerance) 85 to 65 VC, 50/60 Hz Power consumption: running:.5 W holding:. W Transformer sizing: 5 V (class power source) Electrical connection: ft, 8 G appliance cable (-S models have cables) / conduit connector Overload protection: electronic throughout 0 to 95 rotation ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: reversible with cw/ccw mounting Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time: motor: < 75 sec (0 to 8 in-lb) spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Noise level: max: running < 50 db () spring return 6 d () Servicing: maintenance free Quality standard: ISO 900 Weight: TF4/0 US.4 lbs (0.6 kg) TF4/0(-S) US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 8 See Selection Chart Pg for Control Valve No., C v and Close-off

29 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, On-Off Dimensions.05" [76.].9" [74.5] 6.8" [59.55] D094.40" [6] 4 VC Transformer Common + Hot W7 TF4 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4VDC. Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] On-off wiring for TF4 US 00 to 40 VC N L H L Neutral Hot W7 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way TF0 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF0 US S S S NC NO TF -S US 0 to 95 W48 ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF -S US 9

30 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for floating point control using 4VC/DC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TF4- US TF4--S US Control Floating Power supply 4VC ± 0%, 50/60Hz Power consumption: running:.5 W holding:.0 W Transformer sizing 4 V (class power source) Electrical connection TF4- US ft, 8 G plenum rated cable TF4--S US ft, 8 G appl. cables () / conduit connector Overload protection electronic throughout 0 to 95 rotation Input impedance 000 Ω (0.6w) control inputs ngle of rotation max 95, adjust. with mechanical stop Torque min. 8 in-lb [ Nm] Direction of rotation spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity 5 to 95% RH non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing NEM type / IP4 Housing material UL94-5V gency listings culus listed acc. to UL Noise level max: running < 5 db () spring return 6 d () Servicing maintenance free Quality standard ISO 900 Weight TF4- US.4 lbs (0.6 kg) TF4--S US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 0 See Selection Chart Pg for Control Valve No., C v and Close-off

31 x x Two-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Floating Point Dimensions.05" [76.] 6.8" [59.55] D094 4 VC Transformer W4.9" [74.5].40" [6] Hot Com 7 lk () Common Red () ~ Hot Wht (W) ~ Or (W4) ~ TF4- (-S) US Controller The indication of direction is valid for switch position CW. Triac source Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] 4 VC Transformer Hot Com 7 lk () Common Red () ~ Hot Wht (W) ~ 4 Or (W4) ~ TF4- (-S) US W4 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Switch Positions a b () (4) CW stop Two-way 4 VC Transformer Installation Side CCW Direction of Rotation Switch CCW CW CCW stop stop stop Floating point control of TF4- (-S) US CW a b 7 lk () Common Red () ~ Wht (W) ~ Or (W4) ~ Flow direction E L I M O TF4- (-S) US The indication of direction is valid for switch position CW. W40 Triac sink Hot Controller Controller 4 VC Transformer Com Triac sink with separate transformers 4 VC Transformer uxiliary switch of TF4- (-S) US The indication of direction is valid for switch position CW. lk () Common Red () ~ Hot 4 Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. Notes: Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. The Common connection from the actuator must be connected to the Hot connection of the controller. 4 The actuator Hot must be connected to the control board Common. For end position indication, interlock control, fan startup, etc., TF4--S US 5 TF0-S US and TF0-S US incorporate one built-in auxiliary switch: x SPDT, VC, UL listed, adjustable 0 to Meets culus requirements without the need of an electrical ground connection. ctuators with plenum rated cable do not have numbers on wires; use color 7 coded instead. ctuators with appliance rated cable use numbers. S S S NC NO 7 TF4--S US 5 0 to 95 6 W44 W4

32 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox reheat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TF4-SR US TF4-SR-S US Control Proportional Power supply 4VC ± 0%, 50/60Hz 4VDC ± 0% Power consumption: running:.5 W holding:.0 W Transformer sizing: 4 V (class power source) Electrical connection: TF4-SR US ft. plenum rated cable TF4-SR-S US ft, 8 G appl. cables () / conduit connector Electrical protection: actuators are double insulated Overload protection: electronic throughout 0 to 95 rotation Operating range Y: to 0 VDC, 4 to 0 m Input impedance: 00 kω (0.m), 500Ω ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch: x SPDT 50 VC, UL listed adjustable 0 to 95 Running time: motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Quality standard: ISO 900 Noise level: max: running < 5 db () spring return 6 d () Servicing: maintenance free Weight:.4 lbs (0.6 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. See Selection Chart Pg for Control Valve No., C v and Close-off

33 Two-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Proportional Dimensions.05" [76.] 6.8" [59.55] D094 4 VC Transformer 4 W45.9" [74.5].40" [6] lk () Common Red () + Hot Control Signal ( ) to 0 VDC (+) Wht () Y Input, to 0V TF4-SR US Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. ctuators with plenum rated cable do not have numbers on wires; use color codes 4 instead. Flow Pattern to 0 VDC control of TF4-SR (-S) US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Two-way For end position indication, interlock control, fan startup, etc., TF4-SR-S US incorporates one built-in auxiliary switch: x SPDT, (0.5 VC, UL listed, adjustable 0 to 95. Meets culus requirements without the need of an electrical ground connection. uxiliary switch of TF4-SR-S US S S S NC NO TF4-SR-S US Flow direction E L I M O 0 to 95 W46 4 VC Transformer 4 to 0 m Control Signal ( ) (+) 5 Ω 500Ω Provide overload protection and disconnect as required. Up to 4 actuators may be connected in parallel. With 4 actuators wired to one 500Ω resistor, a +% shift of control signal may be required. Power consumption must be observed. ctuator may also be powered by 4 VDC Ω resistor converts the 4 0 m control signal to to 0 VDC. (ZG-R0) 5 Only connect common to neg. ( ) leg of control circuits. ctuators with plenum rated cable do not have numbers on wires; use color codes 6 instead. 4 to 0 m control of TF4-SR (-S) US 4 To other actuators 6 lk () Common Red () + Hot Wht () Y Input, to 0V TF4-SR US W47

34 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for on/off control using 4VC/DC or 00 to 40 VC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TF4 US TF4-S US TF0 US TF0-S US Control On-off Power supply TF4(-S) US: 4VC ± 0%, 50/60Hz 4VDC ± 0% Power supply TF0(-S) US: (nominal) 00 to 40 VC, 50/60 Hz (tolerance) 85 to 65 VC, 50/60 Hz Power consumption: running:.5 W holding:. W Transformer sizing: 5 V (class power source) Electrical connection: ft, 8 G appliance cable (-S models have cables) / conduit connector Overload protection: electronic throughout 0 to 95 rotation ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: reversible with cw/ccw mounting Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time: motor: < 75 sec (0 to 8 in-lb) spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Noise level: max: running < 50 db () spring return 6 d () Servicing: maintenance free Quality standard: ISO 900 Weight: TF4/0 US.4 lbs (0.6 kg) TF4/0(-S) US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 4 See Selection Chart Pg for Control Valve No., C v and Close-off

35 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, On-Off Dimensions.05" [76.].9" [74.5] 6.8" [59.55] D095.40" [6] 4 VC Transformer Common + Hot W7 TF4 US Provide overload protection and disconnect as required. C ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4VDC. Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] Flow Pattern On-off wiring for TF4 US 00 to 40 VC N L H L Neutral Hot W7 Three-way Mixing G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Characterizing Disc (where applicable) YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) TF0 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF0 US S S S NC NO TF -S US 0 to 95 W48 ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF -S US 5

36 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for floating point control using 4VC/DC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TF4- US TF4--S US Control Floating Power supply 4VC ± 0%, 50/60Hz Power consumption: running:.5 W holding:.0 W Transformer sizing 4 V (class power source) Electrical connection TF4- US ft, 8 G plenum rated cable TF4--S US ft, 8 G appl. cables () / conduit connector Overload protection electronic throughout 0 to 95 rotation Input impedance 000 Ω (0.6w) control inputs ngle of rotation max 95, adjust. with mechanical stop Torque min. 8 in-lb [ Nm] Direction of rotation spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity 5 to 95% RH non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing NEM type / IP4 Housing material UL94-5V gency listings culus listed acc. to UL Noise level max: running < 5 db () spring return 6 d () Servicing maintenance free Quality standard ISO 900 Weight TF4- US.4 lbs (0.6 kg) TF4--S US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 6 See Selection Chart Pg for Control Valve No., C v and Close-off

37 x x Three-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Floating Point Dimensions G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc..05" [76.] C.9" [74.5] Nominal 6.8" [59.55] Valve Valve Size Dimensions ody in [mm] C.40" [6] 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] Flow Pattern Characterizing Disc (where applicable) Three-way Mixing Switch Positions a b () (4) YPSS CW stop Port Disc (ll -way models) 4 VC Transformer Installation Side CCW CCW CW Direction of Rotation Switch CCW stop stop stop Characterizing Disc (where applicable) Floating point control of TF4- (-S) US CW a b Three-way Diverting 7 lk () Common Red () ~ Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. D095 Port Disc (ll -way models) W40 Triac source Triac sink 4 VC Transformer Hot Controller 4 VC Transformer Hot Controller Hot Controller 4 VC Transformer Com Com Com Triac sink with separate transformers 4 VC Transformer uxiliary switch of TF4- (-S) US lk () Common Red () ~ Hot Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. 7 7 lk () Common Red () ~ Hot Wht (W) ~ 4 Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. lk () Common Red () ~ Hot 4 Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. Notes: Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. The Common connection from the actuator must be connected to the Hot connection of the controller. 4 The actuator Hot must be connected to the control board Common. For end position indication, interlock control, fan startup, etc., TF4--S US 5 TF0-S US and TF0-S US incorporate one built-in auxiliary switch: x SPDT, VC, UL listed, adjustable 0 to Meets culus requirements without the need of an electrical ground connection. ctuators with plenum rated cable do not have numbers on wires; use color 7 coded instead. ctuators with appliance rated cable use numbers. S S S NC NO 7 TF4--S US 5 0 to 95 6 W4 W44 W4 W4 7

38 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox reheat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all chrome plated brass Stem brass Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TF4-SR US TF4-SR-S US Control Proportional Power supply 4VC ± 0%, 50/60Hz 4VDC ± 0% Power consumption: running:.5 W holding:.0 W Transformer sizing: 4 V (class power source) Electrical connection: TF4-SR US ft. plenum rated cable TF4-SR-S US ft, 8 G appl. cables () / conduit connector Electrical protection: actuators are double insulated Overload protection: electronic throughout 0 to 95 rotation Operating range Y: to 0 VDC, 4 to 0 m Input impedance: 00 kω (0.m), 500Ω ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch: x SPDT 50 VC, UL listed adjustable 0 to 95 Running time: motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Quality standard: ISO 900 Noise level: max: running < 5 db () spring return 6 d () Servicing: maintenance free Weight:.4 lbs (0.6 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 8 See Selection Chart Pg for Control Valve No., C v and Close-off

39 Three-way Characterized Control Valve, Chrome Plated rass all and Stem TF ctuators, Proportional Dimensions.05" [76.] 6.8" [59.55] D095 4 VC Transformer 4 W45.9" [74.5].40" [6] lk () Common Red () + Hot Control Signal ( ) to 0 VDC (+) Wht () Y Input, to 0V C TF4-SR US Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] Flow Pattern Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. ctuators with plenum rated cable do not have numbers on wires; use color codes 4 instead. to 0 VDC control of TF4-SR (-S) US Three-way Mixing Characterizing Disc (where applicable) YPSS Port Disc (ll -way models) 4 VC Transformer 6 W47 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Three-way Diverting For end position indication, interlock control, fan startup, etc., TF4-SR-S US incorporates one built-in auxiliary switch: x SPDT, (0.5 VC, UL listed, adjustable 0 to 95. Meets culus requirements without the need of an electrical ground connection. uxiliary switch of TF4-SR-S US Port Disc (ll -way models) S S S NC NO TF4-SR-S US 0 to 95 W46 4 to 0 m Control Signal ( ) (+) 5 Ω 500Ω Provide overload protection and disconnect as required. Up to 4 actuators may be connected in parallel. With 4 actuators wired to one 500Ω resistor, a +% shift of control signal may be required. Power consumption must be observed. ctuator may also be powered by 4 VDC Ω resistor converts the 4 0 m control signal to to 0 VDC. (ZG-R0) 5 Only connect common to neg. ( ) leg of control circuits. ctuators with plenum rated cable do not have numbers on wires; use color codes 6 instead. 4 to 0 m control of TF4-SR (-S) US 4 To other actuators lk () Common Red () + Hot Wht () Y Input, to 0V TF4-SR US 9

40 Two-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TR4--T US Control Input Impedance Nominal voltage Nominal voltage range Power Consumption Transformer Sizing Electrical Connection On-off/floating point.6 kω 4 VC 50/60 Hz VC W V (Class power source) Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into handle Manual override: Push down handle Running Time hz, hz Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level max. 5 db () Quality Standard ISO 900 dditional Models TR4- US TR4--T US with ft plenum rated cable TR4-/00 US TR4--T US with 6 ft plenum rated cable TR4-/00 US TR4--T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 40 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

41 Two-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, On-Off/Floating Point Dimensions.50 [6.5].8 [7.6].5 [8.6] D069 4 VC Transformer Common + W86 + Provide overload protection and disconnect as required. TR4--T US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] Flow Pattern Characterizing Disc (Where applicable) COM Controller Hot Two-way lk () Common Red () Wht () TR4--T US Provide overload protection and disconnect as required. The Common connection from the actuator must be connected to the Hot connection of the controller. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. Flow direction E L I M O W50 On/Off Control of TR4--T US. You may not use one wire control. 4 VC Transformer Provide overload protection and disconnect as required. Floating Control of TR4--T US Hot Controller COM Common + + TR4--T US lk () Common Red () Wht () Provide overload protection and disconnect as required. TR4--T US The actuator Hot must be connected to the control board Hot. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. W87 W5 Triac Sink Triac Source Note: TR4--T US cannot be wired in parallel with themselves or any other actuator. 4

42 Two-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TR4-SR-T US Reversing switch under cover Control Proportional Input Impedance 00 kω Nominal voltage 4 VC 50/60 Hz, 4VDC Nominal voltage range VC, VDC Power Consumption 0.5 W Transformer Sizing V (Class power source) Electrical Connection Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into handle Manual override: Push down handle Running Time 90 seconds Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level max. 5 db () Quality Standard ISO 900 dditional Models TR4-SR US TR4-SR-T US with ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 6 ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 4 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

43 Two-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, Proportional Dimensions.50 [6.5].8 [7.6].5 [8.6] D069 4 VC Transformer to 0 VDC ( ) Control Signal (+) lk () Common Red () + Hot Wht () Y to 0V Input W90 TR4-SR-T US Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] Notes: Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. to 0 VDC Control of TR4-SR-T US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way Notes: 4 VC Transformer 4 to 0 m ( ) Control Signal (+) Ω 500Ω lk () Common Red () + Hot Wht () Y to 0V Input TR4-SR-T US Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. 4 to 0 m Control of TR4-SR-T US W9 Direct/Reverse acting switch is under wiring cover. R = CW with decrease in signal L = CCW with decrease in signal No feedback 4

44 Two-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. ctuator Specifications Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to -/4 (0) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont LR4- US LR4--S US Running time: 95 seconds constant Direction of rotation: reversible w/switch CW/CCW Transformer sizing: V (Class power source) Input impedance: 900Ω (LR4- US with auxiliary switch) Switch 0-95 SPDT 6 resistive (.5 4 VC ll LR On-Off/Floating Point Control On-off/floating point Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption W Transformer sizing V (Class power source) Electrical connection ft, 8 G, UL CLP plenum cable / conduit fitting Overload protection Electronic throughout 0 to 95 rotation Torque min 5 in-lb [4 Nm] Position indication Indicator/handle Manual override external push button Humidity 5 to 95% RH, non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing type NEM type Housing material rating UL94-5V (flammability rating) Noise level less than 5 d () Servicing maintenance free gency listings UL87 listed, CS C. No. 4 certified, CE Quality standard ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL 44 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

45 Two-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, On-Off/Floating Point Dimensions.7" [69].9" [8] 0.75" [9] 5.75" [46].44" [6] D070 4 VC Transformer a open a closed a lk () Common Red () + Wht () + W9 The indication of direction is valid for switch position R. CCW CW LR4- US On-Off control Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] Provide overload protection and disconnect as required. ctuators are provided with color coded wires. Wire numbers are provided for reference. May also be powered by 4 VDC. F098/ /0-0M-IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Size Dimensions in inches [mm] in mm /4 0.6 [66.8].75 [44.5] 5.50 [88.9].8 [46.0] -/4 4.0 [0].87 [48] Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 4 VC Transformer The indication of direction is valid for switch position CW. Floating Point control ux. switch lk () Common Red () + Wht () + CCW CW LR4- US S S S NC NO 0 to 95 LR4--S US W W69 45

46 Two-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to -/4 (0) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont LISTED 94D5 TEMP. IND & REG. EQUIP. UL ctuator Specifications LR4-SR US Running time: 95 seconds constant Transformer sizing 4 V (Class power source) Control signal Y: 0 to 0 VDC, 0 to 0 m Input impedance: 00 kω (0. m), 500Ω Operating range: to 0 VDC, 4 to 0 m Feedback output U: to 0 VDC, max. 0.7 m Direction of rotation: reversible with switch CW/CCW, CW = CW with voltage CCW = CCW with voltage ll LR Proportional Control Proportional Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption W Electrical connection ft, 8 G, UL CLP plenum cable / conduit fitting (not on - models) Overload protection Electronic throughout 0 to 95 rotation Torque min 5 in-lb [4 Nm] Position indication Indicator/handle Manual override external push button Humidity 5 to 95% RH, non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing type NEM type Housing material rating UL94-5V (flammability rating) Noise level less than 5 d () Servicing maintenance free gency listings UL87 listed, CS C. No. 4 certified, CE Quality standard ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 46 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

47 Two-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, Proportional Dimensions.7" [69].9" [8] 0.75" [9] 5.75" [46].44" [6] D070 4 VC Transformer to 0 VDC Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) lk () Common Red () + Hot Wht () Y to 0V Input Grn (5) U to 0V Output CCW CW LR4-SR US W98 to 0 VDC control 4 VC Transformer W5 Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] Nominal Valve Size Dimensions in inches [mm] in mm /4 0.6 [66.8].75 [44.5] 5.50 [88.9].8 [46.0] -/4 4.0 [0].87 [48] 4 to 0 m Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) 4 to 0 m control Ω lk () Common Red () + Hot Wht () Y to 0V Input Grn (5) U to 0V Output CCW CW LR4-SR US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 47

48 Two-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to -/4 (0) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications LR4-MFT US Control MFT Control signal Y: 0 to 0 VDC, 0 to 0 m Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption W Transformer sizing: 4 V (Class power source) Electrical connection ft, 8 G, UL CLP plenum cable / conduit fitting Overload protection Electronic throughout 0 to 95 rotation Operating range: to 0 VDC, 4 to 0 m Input impedance: 00 kω (0. m), 500Ω Input impedance: 00kΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m, 750Ω for PWM 500Ω for on/off and floating point Feedback output U: to 0 VDC, max. 0.5 m Torque min 5 in-lb [4 Nm] Direction of rotation: reversible with switch CW/CCW, CW = CW with voltage CCW = CCW with voltage Position indication: Indicator/handle Manual override: external push button Humidity: 5 to 95% RH, non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing type: NEM type Housing material rating: UL94-5V (flammability rating) Noise level: less than 5 d () Servicing: maintenance free gency listings: UL87 listed, CS C. No. 4 certified, CE Quality standard: ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT 48 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

49 Two-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, MFT Dimensions.7" [69] 5.75" [46] D070 4 VC/DC Transformer W04.9" [8] 0.75" [9].44" [6] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US On-Off control Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] Nominal Valve Size Dimensions in inches [mm] in mm /4 0.6 [66.8].75 [44.5] 5.50 [88.9].8 [46.0] -/4 4.0 [0].87 [48] 4 VC Transformer (C only) Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Controller COM Position Feedback lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US Diode may be placed at the control panel. Reduces field wiring W0 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Two-way 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Flow direction E L I M O lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 49

50 Two-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes -/4 () to (50) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications NM4 US Control Power consumption: Transformer sizing: Electrical connection: Overload protection: On-off/floating point.0 W.5 V class power source ft, 8 G plenum rated cable, / conduit fitting electronic throughout rotation ngle of rotation: 95 Direction or rotation: L/R external switch Position indication: Indicator/handle Manual override: push button Running time: 75 to 50 sec. mbient temperature: -4 F to F [-0 C to 50 C] Housing: NEM / IP54 Housing material: UL 94-5V (flammability rating) gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: less than 5 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 50 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

51 Two-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, On-Off/Floating Point Dimensions.5" [79.7].9" [86] 0.7" [8] 7.0" [78] Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads..8" [58] D07 4 VC Transformer a open a closed The indication of direction is valid for switch position R. On-Off control 4 VC Transformer a lk () Common Red () + Wht () + L R NM4 US lk () Common Red () + Wht () + W0 W50 Flow Pattern The indication of direction is valid for switch position R. L R NM4 US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Flow direction E L I M O Two-way Floating Point control Notes: Provide overload protection and disconnect as required. ctuators are provided with color coded wires. Wire numbers are provided for reference. May also be powered by 4 VDC. 5

52 Two-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes -/4 () to (50) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications NM4-SR US Control Control signal: Power consumption: Transformer sizing: Electrical connection: Overload protection: Input impedance: Feedback output: Proportional to 0 VDC (4 to 0 m with 500Ω resistor). W.5 V class power source ft, 8 G plenum rated cable, / conduit fitting electronic throughout rotation 00kΩ (500Ω) to 0 VDC ngle of rotation: 95 Direction or rotation: L/R external switch Position indication: Indicator/handle Manual override: push button Running time: 50 sec. independent of load mbient temperature: -4 F to F [-0 C to 50 C] Housing: NEM / IP54 Housing material: UL 94-5V (flammability rating) gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: less than 5 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 5 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

53 Two-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, Proportional Dimensions.5" [79.7] 7.0" [78] D07 4 VC Transformer 4 W094.9" [86] 0.7" [8].8" [58] to 0 VDC ( ) Control Signal (+) lk () Common Red () + Hot Wht () Y to 0V Input Grn (4) U to 0V Output L R NM4-SR US to 0 VDC control G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 4 VC Transformer 4 to 0 m Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) 4 to 0 m control Notes: Ω 500Ω 5 4 lk () Common Red () + Hot Wht () Y to 0V Input Grn (4) U to 0V Output L R NM4-SR US Provide overload protection and disconnect as required. ctuators are provided with color coded wires. Wire numbers are provided for reference. Connect actuator common (Wire ) to Negative ( ) leg of control circuits only. 4 May also be powered by 4 VDC. 5 The 500Ω resistor converts the 4 to 0m control signal to to 0 VDC. W095 5

54 Two-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes -/4 () to (50) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications NM4-MFT US Control Control signal: Power consumption: Transformer sizing: Electrical connection: Overload protection: Input impedance: Feedback output: MFT to 0 VDC. W.5 V class power source ft, 8 G plenum rated cable, / conduit fitting electronic throughout rotation 00kΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m 750Ω for PWM 500Ω for on/off and floating point to 0 VDC, 0.5 m max ngle of rotation: 95 Direction or rotation: L/R external switch Position indication: Indicator/handle Manual override: push button Running time: 50 sec. independent of load (proportional) mbient temperature: -4 F to F [-0 C to 50 C] Housing: NEM / IP54 Housing material: UL 94-5V (flammability rating) gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: less than 5 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 54 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

55 Two-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, MFT Dimensions.5" [79.7].9" [86] 0.7" [8] 7.0" [78].8" [58] D07 Position 4 VC/DC Transformer ( ) a lk () Common Red () Hot Wht () Y Input W04 Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US On-Off control Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. Flow Pattern 4 VC Transformer (C only) Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Controller COM Position Feedback lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US Diode may be placed at the control panel. Reduces field wiring W0 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 55

56 Two-way Characterized Control Valve, Stainless Steel all and Stem M ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications: Service Chilled or Hot Water, 60% glycol Flow Characteristic port equal percentage Sizes to Type of end fitting female, npt Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications M4 US Control On-off/floating point Power Supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption:.5w Transformer sizing: 4.5 V (Class power source) Electrical connection: ft., 8 G, appliance cable, / conduit connector Overload protection: electronic throughout 0 to 95 rotation ngle of rotation: 0-95 adjustable stops Torque: min 60 in-lb [8 Nm] Direction or rotation: reversible with switch CCW-CW Position indication: indicator/handle Running time: 00 to50 sec. for 0 to 60 in-lb Manual override: external push button Humidity: 5 to 95% RH, non-condensing mbient temperature: - F to F [-0 C to +50 C] Storage temperature: -40 F to 76 F [-40 C to +80 C] Housing type: NEM (IP54 with cable entry down) Housing material: UL94-5V (flammability rating) Noise level: less than 45 d () Servicing: maintenance free gency listings: UL 87 listed, CS C. No. 4 certified, CE Quality standard: ISO 900 LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 56 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

57 Two-way Characterized Control Valve, Stainless Steel all and Stem M ctuators, On-Off/Floating Point Dimensions.6" [9] 4.09" [04].05" [06].99" [76] D076 4 VC Transformer 4 lk () Common Wht () + W074." [79] a open a closed a Wht () + The indication of direction is valid for switch position CW. CCW CW M4 (-S) US On-off control Nominal Valve Size Dimensions in inches [mm] in mm [4].78 [69.45 ] [8 ].78 [69.45 ] [45 ].78 [69.45 ] 4 VC Transformer 4 lk () Common Wht () + W075 Wht () + The indication of direction is valid for switch position CW. CCW CW M4 (-S) US Floating point or on-off control G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way S S S S4 S5 S6 NC NO NC NO 0 to to 95 M4 (-S) US uxiliary switch wiring for M4-S US Notes Provide overload protection and disconnect as required. ctuators may also be powered by 4 VDC. W076 4 For end position indication, interlock control, fan startup, etc., M4-S US incorporates two built-in auxiliary switches: x SPDT, VC, UL listed, adjustable between 0 and 95. Meets UL and CS requirements without the need of an electrical ground connection. 57

58 Two-way Characterized Control Valve, Stainless Steel all and Stem M ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input. Valve Specifications: Service Chilled or Hot Water, 60% glycol Flow Characteristic port equal percentage Sizes to Type of end fitting female, npt Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT ctuator Specifications M4-MFT US Control MFT Power Supply 4 VC, ± 0%, 50/60 Hz 4 VDC ± 0% Power consumption:.5 W running,. W holding Transformer sizing: 5 V (Class power source) Electrical connection: ft., 8 G, appliance cable, / conduit connector Overload protection: electronic throughout 0 to 95 rotation Control signal Y*: to 0 VDC Operating range*: to 0 VDC, 4 to 0 m (w/500ω, /4W resistor) ZG-R0 Input impedance: 00kΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m, 750Ω for PWM 500Ω for on/off and floating point Feedback output U*: to 0 VDC, 0.5 m max Torque: min 60 in-lb [8 Nm] Direction or rotation*: control direction selected by switch CW=CW with decrease in signal CCW=CCW with a decrease in signal ngle of rotation: 0-95 adjustable mechanical stops Running time: 50 seconds constant ngle of rotation adaptation: Off (default) Override control*: Min. (min position) = 0% ZS (mid position) = 50% Max. (max position) = 00% Manual override: manual push button Position indication: clip on indicator handle Humidity: 5 to 95% RH, non-condensing Operating temperature: - F to F [-0 C to +50 C] Storage temperature: -40 F to 76 F [-40 C to +80 C] Housing type: NEM IP54 (with cable entry down) Housing material: UL 94-5V (flammability rating) Noise level: less than 45 d () gency listings: UL 87 listed, CS C. No. 4 certified Quality standard: ISO 900 Servicing: maintenance free *variable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 58 See Selection Chart Pg 4 for Control Valve No., C v and Close-off

59 Two-way Characterized Control Valve, Stainless Steel all and Stem M ctuators, MFT Valve ssembly Dimensions.6" [9].05" [06] D076 4 VC/DC Transformer W " [04]." [79].99" [76] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US On-Off control Nominal Valve Size Dimensions in inches [mm] in mm [4].78 [69.45] [8].78 [69.45] [45].78 [69.45] 4 VC Transformer (C only) Hot COM Diode may be placed at the control panel. Reduces field wiring lk () Common W0 Flow Pattern MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US Controller Position Feedback G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 59

60 Three-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TR4--T US Control Input Impedance Nominal voltage Nominal voltage range Power Consumption Transformer Sizing Electrical Connection On-off/floating point.6 kω 4 VC 50/60 Hz VC W V (Class power source) Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into Handle Manual override: Push down handle Running Time hz, hz Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level max. 5 db () Quality Standard ISO 900 dditional Models TR4- US TR4--T US with ft plenum rated cable TR4-/00 US TR4--T US with 6 ft plenum rated cable TR4-/00 US TR4--T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 60 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

61 Three-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, On-Off/Floating Point Dimensions.50 [6.5].8 [7.6].5 [8.6] D07 4 VC Transformer Common + + W86 Provide overload protection and disconnect as required. TR4--T US C Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] On/Off Control of TR4--T US. You may not use one wire control. 4 VC Transformer Common + W87 Flow Pattern Three-way Mixing Three-way Diverting + G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) COM YPSS Controller Port Disc (ll -way models) Hot Characterizing Disc (where applicable) Port Disc (ll -way models) lk () Common Red () Wht () TR4--T US Provide overload protection and disconnect as required. The Common connection from the actuator must be connected to the Hot connection of the controller. W50 Provide overload protection and disconnect as required. Floating Control of TR4--T US Controller Hot COM TR4--T US lk () Common Red () Wht () Provide overload protection and disconnect as required. TR4--T US The actuator Hot must be connected to the control board Hot. W5 ctuators with plenum rated cable do not have numbers on wires; use color codes instead. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. Triac Sink Triac Source Note: TR4--T US cannot be wired in parallel with themselves or any other actuator. 6

62 Three-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes /, /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TR4-SR-T US Reversing switch under cover Control Proportional Input Impedance 00 kω Nominal voltage 4 VC 50/60 Hz, 4VDC Nominal voltage range VC, VDC Power Consumption 0.5 W Transformer Sizing V (Class power source) Electrical Connection Screw Terminals accessible after removal of small cover ( ft, 6 ft, 0 ft cables optional) ngle of Rotation 90 Torque 8 in-lbs (Nm) Position Indication Integrated into Handle Manual override: Push down handle Running Time 90 seconds Humidity 5 to 95% non-condensing mbient Temperature 9 F to F (-7 C to +50 C) Storage Temperature -40 F to 76 F (-40 C to +80 C) Housing NEM Housing Rating UL94-5V() gency Listing CE, UL EMC CE according to 89/6/EEC Mode of Operation Type to UL Noise Level max. 5 db () Quality Standard ISO 900 dditional Models TR4-SR US TR4-SR-T US with ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 6 ft plenum rated cable TR4-SR/00 US TR4-SR-T US with 0 ft plenum rated cable G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 6 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

63 Three-way Characterized Control Valve, Stainless Steel all and Stem TR ctuators, Proportional Dimensions.50 [6.5].5 [8.6] D07 4 VC Transformer lk () Common Red () + Hot W90.8 [7.6] to 0 VDC ( ) Control Signal (+) Wht () Y to 0V Input TR4-SR-T US Notes: C Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. to 0 VDC Control of TR4-SR-T US Flow Pattern 4 VC Transformer W9 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. 4 to 0 m ( ) Control Signal (+) Notes: Ω 500Ω lk () Common Red () + Hot Wht () Y to 0V Input TR4-SR-T US Provide overload protection and disconnect as required. ctuators with color coded wires are optional. Wire numbers are provided for reference. May also be powered by 4 VDC. 4 to 0 m Control of TR4-SR-T US Direct/Reverse acting switch is under wiring cover. R = CW with decrease in signal L = CCW with decrease in signal No feedback 6

64 Three-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, On-Off/Floating pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. ctuator Specifications Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont LR4- US LR4--S US Running time: 95 seconds constant Direction of rotation: reversible w/switch CW/CCW Transformer sizing: V (Class power source) Input impedance: 900Ω (LR4- US with auxiliary switch) Switch 0-95 SPDT 6 resistive (.5 4 VC ll LR On-Off/Floating Point Control On-off/floating point Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption W Transformer sizing V (Class power source) Electrical connection ft, 8 G, UL CLP plenum cable / conduit fitting Overload protection Electronic throughout 0 to 95 rotation Torque min 5 in-lb [4 Nm] Position indication Indicator/handle Manual override external push button Humidity 5 to 95% RH, non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing type NEM type Housing material rating UL94-5V (flammability rating) Noise level less than 5 d () Servicing maintenance free gency listings UL87 listed, CS C. No. 4 certified, CE Quality standard ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL 64 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

65 Three-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, On-Off/Floating Dimensions.7" [69] 5.75" [46] D0 4 VC Transformer W9.9" [8] 0.75" [9].44" [6] a open a closed a lk () Common Red () + Wht () + The indication of direction is valid for switch position R. CCW CW LR4- US C On-Off control Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] Provide overload protection and disconnect as required. ctuators are provided with color coded wires. Wire numbers are provided for reference. May also be powered by 4 VDC. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Size Dimensions in inches [mm] in mm C /4 0.6 [66.8].75 [44.5].8 [5.] 5.50 [88.9].8 [46.0].6 [4.4] -/4 4.0 [0].87 [48]. [56.5] Flow Pattern Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. 4 VC Transformer The indication of direction is valid for switch position CW. Floating Point control ux. switch lk () Common Red () + Wht () + CCW CW LR4- US S S S NC NO 0 to 95 LR4--S US W W69 65

66 Three-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications LR4-SR US Running time: 95 seconds constant Transformer sizing 4 V (Class power source) Control signal Y: 0 to 0 VDC, 0 to 0 m Input impedance: 00 kω (0. m), 500Ω Operating range: to 0 VDC, 4 to 0 m Feedback output U: to 0 VDC, max. 0.7 m Direction of rotation: reversible with switch CW/CCW, CW = CW with voltage CCW = CCW with voltage ll LR Proportional Control Proportional Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption W Electrical connection ft, 8 G, UL CLP plenum cable / conduit fitting (not on - models) Overload protection Electronic throughout 0 to 95 rotation Torque min 5 in-lb [4 Nm] Position indication Indicator/handle Manual override external push button Humidity 5 to 95% RH, non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing type NEM type Housing material rating UL94-5V (flammability rating) Noise level less than 5 d () Servicing maintenance free gency listings UL87 listed, CS C. No. 4 certified, CE Quality standard ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL 66 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

67 Three-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, Proportional Dimensions.7" [69].9" [8] 0.75" [9] 5.75" [46].44" [6] D0 4 VC Transformer to 0 VDC Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) lk () Common Red () + Hot Wht () Y to 0V Input Grn (5) U to 0V Output CCW CW LR4-SR US W98 C to 0 VDC control Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] Nominal Valve Size Dimensions in inches [mm] in mm C /4 0.6 [66.8].75 [44.5].8 [5.] 5.50 [88.9].8 [46.0].6 [4.4] -/4 4.0 [0].87 [48]. [56.5] 4 VC Transformer 4 to 0 m Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) 4 to 0 m control Ω lk () Common Red () + Hot Wht () Y to 0V Input Grn (5) U to 0V Output CCW CW LR4-SR US W5 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. 67

68 Three-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed with MFT functionality which facilitates the use of various control input. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications LR4-MFT US Control MFT Control signal Y: 0 to 0 VDC, 0 to 0 m Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption W Transformer sizing: 4 V (Class power source) Electrical connection ft, 8 G, UL CLP plenum cable / conduit fitting Overload protection Electronic throughout 0 to 95 rotation Operating range: to 0 VDC, 4 to 0 m Input impedance: 00 kω (0. m), 500Ω Input impedance: 00kΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m, 750Ω for PWM 500Ω for on/off and floating point Feedback output U: to 0 VDC, max. 0.5 m Torque min 5 in-lb [4 Nm] Direction of rotation: reversible with switch CW/CCW, CW = CW with voltage CCW = CCW with voltage Position indication: Indicator/handle Manual override: external push button Humidity: 5 to 95% RH, non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing type: NEM type Housing material rating: UL94-5V (flammability rating) Noise level: less than 5 d () Servicing: maintenance free gency listings: UL87 listed, CS C. No. 4 certified, CE Quality standard: ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT 68 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

69 Three-way Characterized Control Valve, Stainless Steel all and Stem LR ctuators, MFT Dimensions.7" [69] 5.75" [46] D0 4 VC/DC Transformer W04.9" [8] 0.75" [9].44" [6] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US C On-Off control 4 VC Transformer (C only) W0 Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] Nominal Valve Size Dimensions in inches [mm] in mm C /4 0.6 [66.8].75 [44.5].8 [5.] 5.50 [88.9].8 [46.0].6 [4.4] -/4 4.0 [0].87 [48]. [56.5] Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Controller COM Position Feedback lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US Diode may be placed at the control panel. Reduces field wiring G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (where applicable) Three-way Mixing YPSS Port Disc (ll -way models) Characterizing Disc (where applicable) Port must be piped to the by-pass leg. 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Three-way Diverting Port Disc (ll -way models) lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 69

70 Three-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation -/4 () to (50) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications NM4 US Control Power consumption: Transformer sizing: Electrical connection: Overload protection: On-off/floating point.0 W.5 V class power source ft, 8 G plenum rated cable, / conduit fitting electronic throughout rotation ngle of rotation: 95 Direction or rotation: L/R external switch Position indication: Indicator/handle Manual override: push button Running time: 75 to 50 sec. mbient temperature: -4 F to F [-0 C to 50 C] Housing: NEM / IP54 Housing material: UL 94-5V (flammability rating) gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: less than 5 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 70 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

71 Three-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, On-Off/Floating Point Dimensions.5" [79.7] C Nominal Valve Size.9" [86] 0.7" [8] 7.0" [78] Dimensions in inches [mm] in mm C *-/ [].87 [48]. [56.5] -/ [09.5].88 [47.8].00 [50.8].8" [58] [06.4].44 [6.0].9 [55.6] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. D04 4 VC Transformer a open a closed The indication of direction is valid for switch position R. On-Off control 4 VC Transformer a lk () Common Red () + Wht () + L R NM4 US lk () Common Red () + Wht () + W0 W50 Flow Pattern The indication of direction is valid for switch position R. L R NM4 US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. Floating Point control Notes: Provide overload protection and disconnect as required. ctuators are provided with color coded wires. Wire numbers are provided for reference. May also be powered by 4 VDC. 7

72 Three-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for modulating control using...0vdc or 4...0m. (for 4...0m control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 4 VC/VDC. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation -/4 () to (50) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications NM4-SR US Control Control signal: Power consumption: Transformer sizing: Electrical connection: Overload protection: Input impedance: Feedback output: Proportional to 0 VDC (4 to 0 m with 500Ω resistor). W.5 V class power source ft, 8 G plenum rated cable, / conduit fitting electronic throughout rotation 00kΩ (500Ω) to 0 VDC ngle of rotation: 95 Direction or rotation: L/R external switch Position indication: Indicator/handle Manual override: push button Running time: 50 sec. independent of load mbient temperature: -4 F to F [-0 C to 50 C] Housing: NEM / IP54 Housing material: UL 94-5V (flammability rating) gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: less than 5 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 7 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

73 Three-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, Proportional Dimensions.5" [79.7] 7.0" [78] D04 4 VC Transformer 4 W094.9" [86] 0.7" [8].8" [58] to 0 VDC ( ) Control Signal (+) lk () Red () Wht () Grn (4) Common + Hot Y to 0V Input U to 0V Output L R NM4-SR US C to 0 VDC control Nominal Valve Size Dimensions in inches [mm] in mm C *-/ [].87 [48]. [56.5] -/ [09.5].88 [47.8].00 [50.8] [06.4].44 [6.0].9 [55.6] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. 4 VC Transformer 4 to 0 m Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) Ω 500Ω 5 4 lk () Common Red () + Hot Wht () Y to 0V Input Grn (4) U to 0V Output L R NM4-SR US W095 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. 4 to 0 m control Notes: Provide overload protection and disconnect as required. ctuators are provided with color coded wires. Wire numbers are provided for reference. Connect actuator common (Wire ) to Negative ( ) leg of control circuits only. 4 May also be powered by 4 VDC. 5 The 500Ω resistor converts the 4 to 0m control signal to to 0 VDC. 7

74 Three-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed with MFT functionality which facilitates the use of various control input. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation -/4 () to (50) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications NM4-MFT US Control Control signal: Power consumption: Transformer sizing: Electrical connection: Overload protection: Input impedance: Feedback output: MFT to 0 VDC. W.5 V class power source ft, 8 G plenum rated cable, / conduit fitting electronic throughout rotation 00kΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m 750Ω for PWM 500Ω for on/off and floating point to 0 VDC,0.5 m max ngle of rotation: 95 Direction or rotation: L/R external switch Position indication: Indicator/handle Manual override: push button Running time: 75 to 50 sec. (NM4 US) 50 sec. independent of load (proportional) mbient temperature: -4 F to F [-0 C to 50 C] Housing: NEM / IP54 Housing material: UL 94-5V (flammability rating) gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: less than 5 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 74 See Selection Chart Pg 5 for Control Valve No., C v and Close-off

75 Three-way Characterized Control Valve, Stainless Steel all and Stem NM ctuators, MFT Dimensions.5" [79.7] 7.0" [78] D04 4 VC/DC Transformer W04.9" [86] 0.7" [8].8" [58] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US C On-Off control Nominal Valve Size Dimensions in inches [mm] in mm C *-/ [].87 [48]. [56.5] -/ [09.5].88 [47.8].00 [50.8] [06.4].44 [6.0].9 [55.6] 4 VC Transformer (C only) Hot COM Diode may be placed at the control panel. Reduces field wiring lk () Common W0 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. Flow Pattern Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Port must be piped to the by-pass leg. lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Controller Position Feedback Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 75

76 Two-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for on/off control using 4VC/DC or 00 to 40 VC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TF4 US TF4-S US TF0 US TF0-S US Control On-off Power supply TF4(-S) US: 4VC ± 0%, 50/60Hz 4VDC ± 0% Power supply TF0(-S) US: (nominal) 00 to 40 VC, 50/60 Hz (tolerance) 85 to 65 VC, 50/60 Hz Power consumption: running:.5 W holding:. W Transformer sizing: 5 V (class power source) Electrical connection: ft, 8 G appliance cable (-S models have cables) / conduit connector Overload protection: electronic throughout 0 to 95 rotation ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: reversible with cw/ccw mounting Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time: motor: < 75 sec (0 to 8 in-lb) spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Noise level: max: running < 50 db () spring return 6 d () Servicing: maintenance free Quality standard: ISO 900 Weight: TF4/0 US.4 lbs (0.6 kg) TF4/0(-S) US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 76 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

77 Two-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, On-Off Dimensions.05" [76.].9" [74.5] 6.8" [59.55] D094.40" [6] 4 VC Transformer Common + Hot W7 TF4 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4VDC. Nominal On-off wiring for TF4 US Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] 00 to 40 VC N L H L Neutral Hot W7 Flow Pattern G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Flow direction E L I M O Two-way TF0 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF0 US S S S NC NO TF -S US 0 to 95 W48 ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF -S US 77

78 Two-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for floating point control using 4VC/DC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TF4- US TF4--S US Control Floating Power supply 4VC ± 0%, 50/60Hz Power consumption: running:.5 W holding:.0 W Transformer sizing 4 V (class power source) Electrical connection TF4- US ft, 8 G plenum rated cable TF4--S US ft, 8 G appl. cables () / conduit connector Overload protection electronic throughout 0 to 95 rotation Input impedance 000 Ω (0.6w) control inputs ngle of rotation max 95, adjust. with mechanical stop Torque min. 8 in-lb [ Nm] Direction of rotation spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity 5 to 95% RH non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing NEM type / IP4 Housing material UL94-5V gency listings culus listed acc. to UL Noise level max: running < 5 db () spring return 6 d () Servicing maintenance free Quality standard ISO 900 Weight TF4- US.4 lbs (0.6 kg) TF4--S US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 78 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

79 x x Two-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Floating Point Dimensions G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc..05" [76.].9" [74.5] Nominal 6.8" [59.55] Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] Flow Pattern Characterizing Disc (Where applicable) Switch Positions a b () (4) CW stop Two-way 4 VC Transformer Installation Side CCW CCW CW Direction of Rotation Switch CCW stop stop stop Floating point control of TF4- (-S) US CW a b 7 lk () Common Red () ~ Wht (W) ~ Or (W4) ~ Flow direction E L I M O TF4- (-S) US The indication of direction is valid for switch position CW. D094.40" [6] W40 Triac source Triac sink 4 VC Transformer Hot Controller 4 VC Transformer Hot Controller Hot Controller 4 VC Transformer Com Com Com Triac sink with separate transformers 4 VC Transformer uxiliary switch of TF4- (-S) US lk () Common Red () ~ Hot Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. 7 7 lk () Common Red () ~ Hot Wht (W) ~ 4 Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. lk () Common Red () ~ Hot 4 Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. Notes: Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. The Common connection from the actuator must be connected to the Hot connection of the controller. 4 The actuator Hot must be connected to the control board Common. For end position indication, interlock control, fan startup, etc., TF4--S US 5 TF0-S US and TF0-S US incorporate one built-in auxiliary switch: x SPDT, VC, UL listed, adjustable 0 to Meets culus requirements without the need of an electrical ground connection. ctuators with plenum rated cable do not have numbers on wires; use color 7 coded instead. ctuators with appliance rated cable use numbers. S S S NC NO 7 TF4--S US 5 0 to 95 6 W4 W44 W4 W4 79

80 Two-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox reheat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications TF4-SR US TF4-SR-S US Control Proportional Power supply 4VC ± 0%, 50/60Hz 4VDC ± 0% Power consumption: running:.5 W holding:.0 W Transformer sizing: 4 V (class power source) Electrical connection: TF4-SR US ft. plenum rated cable TF4-SR-S US ft, 8 G appl. cables () / conduit connector Electrical protection: actuators are double insulated Overload protection: electronic throughout 0 to 95 rotation Operating range Y: to 0 VDC, 4 to 0 m Input impedance: 00 kω (0.m), 500Ω ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch: x SPDT 50 VC, UL listed adjustable 0 to 95 Running time: motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Quality standard: ISO 900 Noise level: max: running < 5 db () spring return 6 d () Servicing: maintenance free Weight:.4 lbs (0.6 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 80 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

81 Two-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Proportional Dimensions.05" [76.] 6.8" [59.55] D094 4 VC Transformer 4 W45.9" [74.5].40" [6] lk () Common Red () + Hot Control Signal ( ) to 0 VDC (+) Wht () Y Input, to 0V TF4-SR US Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 7-0 /4 0.6 [66.8].75 [44.5] Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. ctuators with plenum rated cable do not have numbers on wires; use color codes 4 instead. Flow Pattern to 0 VDC control of TF4-SR (-S) US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Two-way For end position indication, interlock control, fan startup, etc., TF4-SR-S US incorporates one built-in auxiliary switch: x SPDT, (0.5 VC, UL listed, adjustable 0 to 95. Meets culus requirements without the need of an electrical ground connection. uxiliary switch of TF4-SR-S US S S S NC NO TF4-SR-S US Flow direction E L I M O 0 to 95 W46 4 VC Transformer 4 to 0 m Control Signal ( ) (+) 5 Ω 500Ω Provide overload protection and disconnect as required. Up to 4 actuators may be connected in parallel. With 4 actuators wired to one 500Ω resistor, a +% shift of control signal may be required. Power consumption must be observed. ctuator may also be powered by 4 VDC Ω resistor converts the 4 0 m control signal to to 0 VDC. (ZG-R0) 5 Only connect common to neg. ( ) leg of control circuits. ctuators with plenum rated cable do not have numbers on wires; use color codes 6 instead. 4 to 0 m control of TF4-SR (-S) US 4 To other actuators 6 lk () Common Red () + Hot Wht () Y Input, to 0V TF4-SR US W47 8

82 Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for on/off control using 4VC/DC where fail safe is required. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications LF4 US LF4-S US LF0 US LF0-S US Control Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: (LF4 US with built-in aux. switch) (LF0 US with built-in aux. switch) On-off/floating.5 to 5.5 W running, to.5 W holding (models vary) 7 V (LF4 US), 7.5 V (LF0 US), 7 V (LF4-S US), 7.5 V (LF0-S US), class power ft, 8 G appl. cable, / conduit fitting 0V actuators/aux. switches double insulated electronic throughout rotation ngle of rotation: 95 Spring return direction: CW/CCW mounting Position indication: visual indicator uxiliary switch: x SPDT. 5 to 85 (-S) Running time: <40 to 75 sec. (on-off) spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] mbient temperature: - F to F [-0 C to 50 C] Housing: NEM gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: max. 6 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 8 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

83 Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, On-Off Dimensions.65" [9] 7.64" [94] D07 4 VC Transformer W047.7" [94].8" [58] Common + Hot LF4 US Provide overload protection and disconnect as required. Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. On-off wiring for LF4 US Nominal Valve Size Dimensions in inches [mm] in mm /4 0.6 [66.8].75 [44.5] 5.50 [88.9].8 [46.0] -/4 4.0 [0].87 [48] 4 VC Transformer Common + Hot W048 Flow Pattern G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 4 5 LF4-S US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. For end position indication, interlock control, fan startup, etc., LF4-S US incorporates a built-in auxiliary switch: x SPDT, 6 VC, UL listed, adjustable 0 to 95. S S S NC NO 4 0 to 95 5 Meets UL and CS requirements without the need of an electrical ground connection. On-off wiring for LF4-S US 8

84 Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for floating point control using 4VC/DC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to -/4 (0) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) mbient temp. range - F to F (-0 C to 50 C) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications LF4- US LF4- (-S) US Power supply Power consumption: Transformer sizing: Electrical connection: Overload protection: Input Impedance: ngle of rotation: Torque: Direction of rotation: Position indication: uxiliary switch: (-S US) Running time: (LF4- US with built-in aux. switch) 4 VC ± 0% 50/60 Hz 4 VDC ± 0% running:.5 W; holding: W 5 V (class power source) LF4- US, ft. plenum rated cable LF4--S US, ft, 8 G appliance cables () / conduit connector electronic throughout 0 to 95 rotation 000Ω (0.6w) control inputs max. 95, adjust with mechanical stop 5 in-lb [Nm] spring: reversible with cw/ccw mounting motor: reversible with built-in switch visual indicator 0 to 90 (0 is spring return position) x SPDT. 6 VC,UL adjustable 0 to 95 (double insulated) motor:50 sec. constant independent of load spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to F [-0 C to 50 C] Storage temperature: -40 F to 76 F [-40 C to 80 C] Housing: NEM type /IP54 Housing material: zinc coated metal gency listings: UL 87 listed, CS C. No. 4 certified, CE Noise level: max: running < 0 db() spring return 6 d() Servicing: maintenance free Quality standard: ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL 84 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

85 x x Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, Floating Point Dimensions.65" [9] 7.64" [94] D07 4 VC Transformer 8 lk () Common Red () + W05.7" [94].8" [58] a open a closed The indication of direction is valid for switch position CW. a Wht () + Grn (4) + CW CCW LF4- (-S) US On-Off control of LF4- (-S) US 4 VC Transformer 8 lk () Common Red () + W05 Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] Switch Positions a b () (4) CW stop Installation Side CCW Direction of Rotation Switch CCW CW CW CCW stop stop stop a b Wht () + Grn (4) + CW CCW LF4- (-S) US The indication of direction is valid for switch position CW. Nominal Valve Size Dimensions in inches [mm] in mm /4 0.6 [66.8].75 [44.5] 5.50 [88.9].8 [46.0] -/4 4.0 [0].87 [48] Floating point control of LF4- (-S) US 4 VC Transformer 8 W054 Hot Com lk () Common Flow Pattern Flow direction Red () + Hot Wht () + Grn (4) + CW CCW LF4- (-S) US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (Where applicable) uxiliary switch of LF4- (-S) US Two-way S NC S S NO E L I M O LF4--S US 6 0 to 95 Notes: Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. May also be powered by 4 VDC. The Common connection from the actuator must be connected to the Hot connection of the controller. 4 5 The actuator Hot must be connected to the control board Common. For end position indication, interlock control, fan startup, etc., LF4--S US 6 LF0-S US and LF0-S US incorporate one built-in auxiliary switch: x SPDT, 6 VC, UL listed, adjustable 0 to Meets UL and CS requirements without the need of an electrical ground connection. ctuators with plenum rated cable do not have numbers on wires; use color 8 coded instead. ctuators with appliance rated cable use numbers. 7 W05 Triac source Triac sink Controller 4 VC Transformer Hot Controller 4 VC Transformer Hot Controller Com Com Triac sink with separate transformers The indication of direction is valid for switch position CW. lk () Common 4 Red () + Hot 5 Wht () + Grn (4) + CW 4 VC Transformer CCW LF4- (-S) US The indication of direction is valid for switch position CW. 8 lk () Common Red () + Hot 5 Wht () + Grn (4) + CW CCW LF4- (-S) US The indication of direction is valid for switch position CW. 8 W056 W055 85

86 Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to -/4 (0) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications LF4-SR US LF4-SR-S US (LF4-SR US with built-in aux. switch) Control Proportional Control signal: to 0 VDC 4 to 0 m (with 500Ω resistor) Power consumption:.5 W running, W holding Transformer sizing: 5 V, class power Electrical connection: ft, 8 G appl. cable, / conduit fitting Electrical protection: 0V actuators/aux. switches double insulated Overload protection: electronic throughout rotation Input impedance: 00 kω Feedback output: to 0 VDC ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator uxiliary switch: x SPDT. 5 to 85 (-S) Running time: <40 to 75 sec. (on-off) 50 sec. independent of load (proportional) spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] mbient temperature: - F to F [-0 C to 50 C] Housing: NEM gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: max. 6 d() G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL 86 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

87 Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, Proportional Dimensions.65" [9] 7.64" [94] D07 4 VC Transformer 4 W057.7" [94].8" [58] lk () Common Red () + Hot Control Signal ( ) to 0 VDC (+) 5 Wht () Y Input, to 0V Grn (5) U Output, to 0V CW CCW LF4-SR US Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] Nominal Valve Size Dimensions in inches [mm] in mm /4 0.6 [66.8].75 [44.5] 5.50 [88.9].8 [46.0] -/4 4.0 [0].87 [48] 4 5 Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. The LF4-SR-S US wire 5 is white. to 0 VDC control of LF4-SR (-S) US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Two-way S S S Flow direction LF4-SR-S US E L I M O For end position indication, interlock control, fan startup, etc., LF4-SR-S US incorporates one built-in auxiliary switch: x SPDT, 6 (.5 VC, UL listed, adjustable 0 to 95. Meets UL & CS requirements without the need of an electrical ground connection. NC NO 0 to 95 W058 4 VC Transformer 4 to 0 m Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) 5 Ω 500Ω 4 To other actuators Provide overload protection and disconnect as required. Up to 4 actuators may be connected in parallel. With 4 actuators wired to one 500Ω resistor, a +% shift of control signal may be required. Power consumption must be observed. ctuator may also be powered by 4 VDC Ω resistor converts the 4 0 m control signal to to 0 VDC. (ZG-R0) 5 Only connect common to neg. ( ) leg of control circuits. ctuators with plenum rated cable do not have numbers on wires; use color codes 6 instead. 6 lk () Common Red () + Hot Wht () Y Input, to 0V Grn (5) U Output, to 0V CW CCW LF4-SR US W059 uxiliary switch of LF4-SR-S US 4 to 0 m control of LF4-SR (-S) US with to 0 VDC feedback output 87

88 Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input. This valve is designed for use where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage ction Max 95 rotation Sizes / to -/4 (0) Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications LF4-MFT US LF4-MFT-S US Control Control signal: Power consumption: Transformer sizing: Electrical connection: Overload protection: Input impedance: Feedback: MFT to 0 VDC.5 W running, W holding 5 V, class power ft, 8 G appl. cable, / conduit fitting electronic throughout rotation 00 kω for to 0 VDC (0. m) 500 Ω for 4 to 0m 750 Ω for PWM 500 Ω for on/off and floating point to 0 VDC, 0.5 m max ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator uxiliary switch: x SPDT. 5 to 85 (-S) Running time: <40 to 75 sec. (on-off) 50 sec. independent of load (proportional) spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] mbient temperature: - F to F [-0 C to 50 C] Housing: NEM gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: max. 6 d() G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT 88 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

89 Two-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, MFT Dimensions.65" [9].7" [94] 7.64" [94].8" [58] D07 Position 4 VC/DC Transformer ( ) a lk () Common Red () Hot Wht () Y Input W04 Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US On-Off control Nominal Valve Valve Size Dimensions ody in [mm] 07- / 5.06 [5.].9 [5.] -5 / 5.8 [60.5].6 [4.4] 4 VC Transformer (C only) Hot COM Diode may be placed at the control panel. Reduces field wiring lk () Common W0 Nominal Valve Size Dimensions in inches [mm] in mm /4 0.6 [66.8].75 [44.5] 5.50 [88.9].8 [46.0] -/4 4.0 [0].87 [48] MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Controller Position Feedback Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Two-way 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Flow direction E L I M O lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 89

90 Two-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for on/off control is required using 4VC/DC where fail safe is required. Valve Specifications: Service Chilled or hot water, 60% glycol Flow Characteristic port equal percentage Sizes to Type of end fitting female, npt Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications F4 US F4-S US F0 US F0-S US Control Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: (F4 US with built-in aux. switches) (F0 US with built-in aux. switches) On-off 5 to 6.5 W running,.5 to. W holding (models vary) 0 V, class power ft, 8 G appl. cable, / conduit fit. 0 V actuators/ux. switches double insulated electronic throughout rotation ngle of rotation: 95 Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank uxiliary switches: x SPDT. 5 fixed/5 to 85 (-S) Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 90 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

91 Two-way Characterized Control Valve, Steel all and Stem F ctuators, On-Off Dimensions.86" [98] 0.47" [66] D077 4 VC Transformer W94.66" [9].4" [57] Common + Hot F4 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0 ] ** [4].78 [69.45 ] [8 ].78 [69.45 ] [45 ].78 [69.45 ] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. pplies to ** pplies to 5-54 Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way On-off wiring for F4 US VC Transformer 5 Common + Hot S S S S4 S5 S6 NC NO NC NO F4-S US to 85 Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. For end position indication, interlock control, fan startup, etc., F4-S US incorporates two built-in auxiliary switches: x SPDT, 7 VC, UL listed, one switch is fixed at +5, one is adjustable 5 to 85. Meets UL and CS requirements without the need of an electrical ground connection. W95 On-off wiring for F4-S US 9

92 Two-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications: Service Chilled or hot water, 60% glycol Flow Characteristic port equal percentage Sizes to Type of end fitting female, npt Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications F4-SR US Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Feedback output: Control Power consumption: Transformer sizing: Electrical connection: Overload protection: to 0 VDC, 0.5 m max Proportional 6 W running, W holding 0 V, class power ft, 8 G appl. cable, / conduit fit. electronic throughout rotation ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 9 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

93 Two-way Characterized Control Valve, Steel all and Stem F ctuators, Proportional Dimensions.86" [98].66" [9] 0.47" [66].4" [57] D077 4 VC Transformer Control Signal ( ) to 0 VDC (+) Common + Hot Y Input, 0 to 0V 5 U Output to 0V W96 F4-SR US 4 VC Transformer G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0 ] ** [4].78 [69.45 ] [8 ].78 [69.45 ] [45 ].78 [69.45 ] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. pplies to ** pplies to 5-54 Flow Pattern Characterizing Disc (Where applicable) Flow direction E L I M O Two-way 4 to 0 m ( ) Control Signal (+) to 0 VDC ( ) Feedback Signal (+) 5 Ω 500Ω 4 Common + Hot Y Input, 0 to 0V 5 U Output to 0V F4-SR US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. 4 The ZG-R0 500Ω resistor converts the 4 to 0 m control signal to to 0 VDC. 5 Only connect common to neg. ( ) leg of control circuits Proportional to 0 VDC or 4 to 0 m control signal 9

94 Two-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input. This valve is designed for use where fail safe is required. Valve Specifications: Service Chilled or hot water, 60% glycol Flow Characteristic port equal percentage Sizes to Type of end fitting female, npt Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications F4-MFT US F4-MFT-S US Control Control signal: Power supply Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: Input impedance: Feedback output: (F4-MFT US with built-in aux. switches) MFT to 0 VDC, (4 to 0 m with 500Ω resistor) 4 VC ± 0% 50/60 Hz 4 VDC ± 0% 6 W running,.5 W holding 0 V, class power ft, 8 G appl. cable, / conduit fit. ux. switches double insulated electronic throughout rotation 00 KΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m 750Ω for PWM 500Ω for on/off and floating point to 0 VDC, 0.5 m max ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank uxiliary switches: x SPDT. 5 fixed/5 to 85 (-S) Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT 94 See Selection Chart Pg 6 for Control Valve No., C v and Close-off

95 Two-way Characterized Control Valve, Steel all and Stem F ctuators, MFT Dimensions.86" [98] 0.47" [66] D077 4 VC/DC Transformer W04.66" [9].4" [57] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US On-Off control Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0 ] ** [4].78 [69.45 ] [8 ].78 [69.45 ] [45 ].78 [69.45 ] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. pplies to ** pplies to VC Transformer (C only) Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Controller COM Position Feedback lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US Diode may be placed at the control panel. Reduces field wiring W0 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Two-way 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Flow direction E L I M O lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 95

96 Three-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for on/off control using 4VC/DC or 00 to 40 VC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TF4 US TF4-S US TF0 US TF0-S US Control On-off Power supply TF4(-S) US: 4VC ± 0%, 50/60Hz 4VDC ± 0% Power supply TF0(-S) US: (nominal) 00 to 40 VC, 50/60 Hz (tolerance) 85 to 65 VC, 50/60 Hz Power consumption: running:.5 W holding:. W Transformer sizing: 5 V (class power source) Electrical connection: ft, 8 G appliance cable (-S models have cables) / conduit connector Overload protection: electronic throughout 0 to 95 rotation ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: reversible with cw/ccw mounting Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time: motor: < 75 sec (0 to 8 in-lb) spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Noise level: max: running < 50 db () spring return 6 d () Servicing: maintenance free Quality standard: ISO 900 Weight: TF4/0 US.4 lbs (0.6 kg) TF4/0(-S) US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 96 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

97 Three-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, On-Off Dimensions.05" [76.].9" [74.5] 6.8" [59.55] D095.40" [6] 4 VC Transformer Common + Hot TF4 US W7 Provide overload protection and disconnect as required. C ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4VDC. Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] On-off wiring for TF4 US 00 to 40 VC N L H L Neutral Hot W7 Flow Pattern G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Three-way Mixing YPSS Characterizing Disc (where applicable) Port Disc (ll -way models) ( Characterizing Disc (where applicable) Three-way Diverting Port Disc (ll -way models) Port must be piped to the by-pass leg. TF0 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF0 US S S S NC NO TF -S US 0 to 95 W48 ctuators may be connected in parallel. Power consumption must be observed. Meets culus requirements without the need of an electrical ground connection. On-off wiring for TF -S US 97

98 Three-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox re-heat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for floating point control using 4VC/DC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TF4- US TF4--S US Control Floating Power supply 4VC ± 0%, 50/60Hz Power consumption: running:.5 W holding:.0 W Transformer sizing 4 V (class power source) Electrical connection TF4- US ft, 8 G plenum rated cable TF4--S US ft, 8 G appl. cables () / conduit connector Overload protection electronic throughout 0 to 95 rotation Input impedance 000 Ω (0.6w) control inputs ngle of rotation max 95, adjust. with mechanical stop Torque min. 8 in-lb [ Nm] Direction of rotation spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication visual indicator, 0 to 95 (0 spring return position) uxiliary switch x SPDT 50 VC, (-S models) UL listed adjustable 0 to 95 Running time motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity 5 to 95% RH non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing NEM type / IP4 Housing material UL94-5V gency listings culus listed acc. to UL Noise level max: running < 5 db () spring return 6 d () Servicing maintenance free Quality standard ISO 900 Weight TF4- US.4 lbs (0.6 kg) TF4--S US.5 lbs (0.7 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 98 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

99 x x Three-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Floating Point Dimensions G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc..05" [76.] C.9" [74.5] Nominal 6.8" [59.55] Valve Valve Size Dimensions ody in [mm] C.40" [6] 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] Flow Pattern Characterizing Disc (where applicable) Three-way Mixing YPSS Port Disc (ll -way models) Characterizing Disc (where applicable) Port must be piped to the by-pass leg. Switch Positions a b () (4) CW stop 4 VC Transformer Installation Side CCW CCW CW Direction of Rotation Switch CCW stop stop stop Floating point control of TF4- (-S) US CW a b Three-way Diverting 7 lk () Common Red () ~ Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. D095 Port Disc (ll -way models) W40 Triac source Triac sink 4 VC Transformer Hot Controller 4 VC Transformer Hot Controller Hot Controller 4 VC Transformer Com Com Com Triac sink with separate transformers 4 VC Transformer uxiliary switch of TF4- (-S) US lk () Common Red () ~ Hot Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. 7 7 lk () Common Red () ~ Hot Wht (W) ~ 4 Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. lk () Common Red () ~ Hot 4 Wht (W) ~ Or (W4) ~ TF4- (-S) US The indication of direction is valid for switch position CW. Notes: Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. The Common connection from the actuator must be connected to the Hot connection of the controller. 4 The actuator Hot must be connected to the control board Common. For end position indication, interlock control, fan startup, etc., TF4--S US 5 TF0-S US and TF0-S US incorporate one built-in auxiliary switch: x SPDT, VC, UL listed, adjustable 0 to Meets culus requirements without the need of an electrical ground connection. ctuators with plenum rated cable do not have numbers on wires; use color 7 coded instead. ctuators with appliance rated cable use numbers. S S S NC NO 7 TF4--S US 5 0 to 95 6 W4 W44 W4 W4 99

100 Three-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators and VV ox reheat coils. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes / to /4 Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) mbient temp. range - F to F [-0 C to 50 C] Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications TF4-SR US TF4-SR-S US Control Proportional Power supply 4VC ± 0%, 50/60Hz 4VDC ± 0% Power consumption: running:.5 W holding:.0 W Transformer sizing: 4 V (class power source) Electrical connection: TF4-SR US ft. plenum rated cable TF4-SR-S US ft, 8 G appl. cables () / conduit connector Electrical protection: actuators are double insulated Overload protection: electronic throughout 0 to 95 rotation Operating range Y: to 0 VDC, 4 to 0 m Input impedance: 00 kω (0.m), 500Ω ngle of rotation: max 95, adjust. with mechanical stop Torque: min. 8 in-lb [ Nm] Direction of rotation: spring: reversible with cw/ccw mounting motor: reversible with built-in switch Position indication: visual indicator, 0 to 95 (0 spring return position) uxiliary switch: x SPDT 50 VC, UL listed adjustable 0 to 95 Running time: motor: 95 sec constant independent of load spring:< 5 F to + F [-0 C to +50 C] < 60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to + F [-0 C to +50 C] Storage temperature: -40 F to +76 F [-40 C to +80 C] Housing: NEM type / IP4 Housing material: UL94-5V gency listings: culus listed acc. to UL Quality standard: ISO 900 Noise level: max: running < 5 db () spring return 6 d () Servicing: maintenance free Weight:.4 lbs (0.6 kg) G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 00 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

101 Three-way Characterized Control Valve, Stainless Steel all and Stem TF ctuators, Proportional Dimensions.05" [76.] 6.8" [59.55] D095 4 VC Transformer 4 W45.9" [74.5].40" [6] lk () Common Red () + Hot Control Signal ( ) to 0 VDC (+) Wht () Y Input, to 0V C TF4-SR US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] 7-0 /4 0.6 [66.8].75 [44.5].8 [5.] Flow Pattern Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing For end position indication, interlock control, fan startup, etc., TF4-SR-S US incorporates one built-in auxiliary switch: x SPDT, (0.5 VC, UL listed, adjustable 0 to 95. Meets culus requirements without the need of an electrical ground connection. uxiliary switch of TF4-SR-S US YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) S S S Port must be piped to the by-pass leg. NC NO TF4-SR-S US 0 to 95 W46 Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. ctuators with plenum rated cable do not have numbers on wires; use color codes 4 instead. to 0 VDC control of TF4-SR (-S) US 4 VC Transformer 4 to 0 m Control Signal ( ) (+) 5 Ω 500Ω Provide overload protection and disconnect as required. Up to 4 actuators may be connected in parallel. With 4 actuators wired to one 500Ω resistor, a +% shift of control signal may be required. Power consumption must be observed. ctuator may also be powered by 4 VDC Ω resistor converts the 4 0 m control signal to to 0 VDC. (ZG-R0) 5 Only connect common to neg. ( ) leg of control circuits. ctuators with plenum rated cable do not have numbers on wires; use color codes 6 instead. 4 to 0 m control of TF4-SR (-S) US 4 To other actuators 6 lk () Common Red () + Hot Wht () Y Input, to 0V TF4-SR US W47 0

102 Three-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for on/off control using 4VC/DC where fail safe is required. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications LF4 US LF4-S US LF0 US LF0-S US Control Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: (LF4 US with built-in aux. switch) (LF0 US with built-in aux. switch) On-off/floating.5 to 5.5 W running, to.5 W holding (models vary) 7 V (LF4 US), 7.5 V (LF0 US), 7 V (LF4-S US), 7.5 V (LF0-S US), class power ft, 8 G appl. cable, / conduit fitting 0V actuators/aux. switches double insulated electronic throughout rotation ngle of rotation: 95 Spring return direction: CW/CCW mounting Position indication: visual indicator uxiliary switch: x SPDT. 5 to 85 (-S) Running time: <40 to 75 sec. (on-off) spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] mbient temperature: - F to F [-0 C to 50 C] Housing: NEM gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: max. 6 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 0 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

103 Three-way Characterized Control Valve, Steel all and Stem LF ctuators, On-Off Dimensions.65" [9] 7.64" [94] D06 4 VC Transformer W047.7" [94].8" [58] Common + Hot LF4 US C Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. On-off wiring for LF4 US Nominal Valve Size Dimensions in inches [mm] in mm C /4 0.6 [66.8].75 [44.5].8 [5.] 5.50 [88.9].8 [46.0].6 [4.4] -/4 4.0 [0].87 [48]. [56.5] 4 VC Transformer Common + Hot W048 Flow Pattern G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. 4 5 LF4-S US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. For end position indication, interlock control, fan startup, etc., LF4-S US incorporates a built-in auxiliary switch: x SPDT, 6 VC, UL listed, adjustable 0 to 95. S S S NC NO 4 0 to 95 5 Meets UL and CS requirements without the need of an electrical ground connection. On-off wiring for LF4-S US 0

104 Three-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for floating point control using 4VC/DC where fail safe is required. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications LF4- US LF4--S US Power supply Power consumption: Transformer sizing: Electrical connection: Overload protection: Input Impedance: ngle of rotation: Torque: Direction of rotation: Position indication: uxiliary switch: (-S US) Running time: (LF4- US with built-in aux. switch) 4 VC ± 0% 50/60 Hz 4 VDC ± 0% running:.5 W; holding: W 5 V (class power source) LF4- US, ft. plenum rated cable LF4--S US, ft, 8 G appliance cables () / conduit connector electronic throughout 0 to 95 rotation 000Ω (0.6w) control inputs max. 95, adjust with mechanical stop 5 in-lb [Nm] spring: reversible with cw/ccw mounting motor: reversible with built-in switch visual indicator 0 to 90 (0 is spring return position) x SPDT. 6 VC,UL adjustable 0 to 95 (double insulated) motor:50 sec. constant independent of load spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] Humidity: 5 to 95% RH non-condensing mbient temperature: - F to F [-0 C to 50 C] Storage temperature: -40 F to 76 F [-40 C to 80 C] Housing: NEM type /IP54 Housing material: zinc coated metal gency listings: UL 87 listed, CS C. No. 4 certified, CE Noise level: max: running < 0 db() spring return 6 d() Servicing: maintenance free Quality standard: ISO 900 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL 04 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

105 x x Three-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, Floating Point Dimensions.65" [9].7" [94] 7.64" [94].8" [58] 4 VC Transformer a open a closed The indication of direction is valid for switch position CW. a 8 lk () Common Red () + Wht () + Grn (4) + CW CCW LF4- (-S) US W05 On-Off control of LF4- (-S) US C 4 VC Transformer 8 lk () Common Red () + W05 Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] Switch Positions a b () (4) CW stop Installation Side CCW Direction of Rotation Switch CCW CW CW CCW stop stop stop a b Wht () + Grn (4) + CW CCW LF4- (-S) US The indication of direction is valid for switch position CW. Nominal Valve Size Dimensions in inches [mm] in mm C /4 0.6 [66.8].75 [44.5].8 [5.] 5.50 [88.9].8 [46.0].6 [4.4] -/4 4.0 [0].87 [48]. [56.5] Floating point control of LF4- (-S) US 4 VC Transformer 8 W054 Flow Pattern Hot Com lk () Common Red () + Hot Three-way Mixing Three-way Diverting Wht () + Grn (4) + CW CCW LF4- (-S) US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) YPSS Port Disc (ll -way models) uxiliary switch of LF4- (-S) US Characterizing Disc (where applicable) Port must be piped to the by-pass leg. S NC S S NO LF4--S US Port Disc (ll -way models) 6 0 to 95 Notes: Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. May also be powered by 4 VDC. The Common connection from the actuator must be connected to the Hot connection of the controller. 4 5 The actuator Hot must be connected to the control board Common. For end position indication, interlock control, fan startup, etc., LF4--S US 6 LF0-S US and LF0-S US incorporate one built-in auxiliary switch: x SPDT, 6 VC, UL listed, adjustable 0 to Meets UL and CS requirements without the need of an electrical ground connection. ctuators with plenum rated cable do not have numbers on wires; use color 8 coded instead. ctuators with appliance rated cable use numbers. 7 W05 Triac source Triac sink Controller 4 VC Transformer Hot Controller 4 VC Transformer Hot Controller Com Com Triac sink with separate transformers The indication of direction is valid for switch position CW. lk () Common 4 Red () + Hot 5 Wht () + Grn (4) + CW 4 VC Transformer CCW LF4- (-S) US The indication of direction is valid for switch position CW. 8 lk () Common Red () + Hot 5 Wht () + Grn (4) + CW CCW LF4- (-S) US The indication of direction is valid for switch position CW. 8 W055 W056 05

106 Three-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications LF4-SR US LF4-SR-S US (LF4-SR US with built-in aux. switch) Control Proportional Control signal: to 0 VDC 4 to 0 m (with 500Ω resistor) Power consumption:.5 W running, W holding Transformer sizing: 5 V, class power Electrical connection: ft, 8 G appl. cable, / conduit fitting Electrical protection: 0V actuators/aux. switches double insulated Overload protection: electronic throughout rotation Input impedance: 00 kω Feedback output: to 0 VDC ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator uxiliary switch: x SPDT. 5 to 85 (-S) Running time: <40 to 75 sec. (on-off) 50 sec. independent of load (proportional) spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] mbient temperature: - F to F [-0 C to 50 C] Housing: NEM gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: max. 6 d() G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL 06 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

107 Three-way Characterized Control Valve, Steel all and Stem LF ctuators, Proportional Dimensions.65" [9] 7.64" [94] D06 4 VC Transformer 4 W057.7" [94].8" [58] lk () Common Red () + Hot C Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] Nominal Valve Size Dimensions in inches [mm] in mm C /4 0.6 [66.8].75 [44.5].8 [5.] 5.50 [88.9].8 [46.0].6 [4.4] -/4 4.0 [0].87 [48]. [56.5] 4 5 Control Signal ( ) to 0 VDC (+) Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. ctuators with plenum rated cable do not have numbers on wires; use color codes instead. The LF4-SR-S US wire 5 is white. to 0 VDC control of LF4-SR (-S) US 5 Wht () Y Input, to 0V Grn (5) U Output, to 0V CW CCW LF4-SR US Flow Pattern G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing For end position indication, interlock control, fan startup, etc., LF4-SR-S US incorporates one built-in auxiliary switch: x SPDT, 6 (.5 VC, UL listed, adjustable 0 to 95. Meets UL & CS requirements without the need of an electrical ground connection. uxiliary switch of LF4-SR-S US YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) S S S Port must be piped to the by-pass leg. NC NO LF4-SR-S US 0 to 95 W058 4 VC Transformer 4 to 0 m Control Signal ( ) (+) to 0 VDC ( ) Feedback Signal (+) 5 Ω 500Ω 4 To other actuators Provide overload protection and disconnect as required. Up to 4 actuators may be connected in parallel. With 4 actuators wired to one 500Ω resistor, a +% shift of control signal may be required. Power consumption must be observed. ctuator may also be powered by 4 VDC Ω resistor converts the 4 0 m control signal to to 0 VDC. (ZG-R0) 5 Only connect common to neg. ( ) leg of control circuits. ctuators with plenum rated cable do not have numbers on wires; use color codes 6 instead. 4 to 0 m control of LF4-SR (-S) US with to 0 VDC feedback output 6 lk () Common Red () + Hot Wht () Y Input, to 0V Grn (5) U Output, to 0V CW CCW LF4-SR US W059 07

108 Three-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed with MFT functionality which facilitates the use of various control input. This valve is designed for use where fail safe is required. Valve Specifications Service Flow characteristic ction Sizes Type of end fitting Materials: ody all Stem Seats chilled or hot water, 60% glycol port equal percentage port modified linear for constant flow Max 95 rotation / to -/4 (0) female, NPT forged brass, nickel plated fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 600 psi (/ to -/4 ) Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications LF4-MFT US LF4-MFT-S US Control Control signal: Power consumption: Transformer sizing: Electrical connection: Overload protection: Input impedance: Feedback: MFT to 0 VDC.5 W running, W holding 5 V, class power ft, 8 G appl. cable, / conduit fitting electronic throughout rotation 00 kω for to 0 VDC (0. m) 500 kω for 4 to 0m 750 Ω for PWM 500 Ω for on/off and floating point to 0 VDC, 0.5 m max ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator uxiliary switch: x SPDT. 5 to 85 (-S) Running time: <40 to 75 sec. (on-off) 50 sec. independent of load (proportional) spring: <5 F to + F [-0 C to +50 C] <60 F [-0 C] mbient temperature: - F to F [-0 C to 50 C] Housing: NEM gency listings: UL 87, CS C. No. 4 certified, CE Quality standard: ISO 900 Noise level: max. 6 d() G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT 08 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

109 Three-way Characterized Control Valve, Stainless Steel all and Stem LF ctuators, MFT Dimensions.65" [9] 7.64" [94] D06 4 VC/DC Transformer W04.7" [94].8" [58] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US C On-Off control Nominal Valve Valve Size Dimensions ody in [mm] C 07- / 5.06 [5.].9 [5.].07 [7.] -5 / 5.8 [60.5].6 [4.4]. [.] Nominal Valve Size Dimensions in inches [mm] in mm C /4 0.6 [66.8].75 [44.5].8 [5.] 5.50 [88.9].8 [46.0].6 [4.4] -/4 4.0 [0].87 [48]. [56.5] 4 VC Transformer (C only) Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. Controller COM Position Feedback lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US Diode may be placed at the control panel. Reduces field wiring W0 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Three-way Mixing YPSS Characterizing Disc (where applicable) Port Disc (ll -way models) ( Characterizing Disc (where applicable) Port must be piped to the by-pass leg. 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Three-way Diverting Port Disc (ll -way models) lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 09

110 Three-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, On-Off pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for on/off control is required using 4VC/DC where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications F4 US F4-S US F0 US F0-S US Control Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: (F4 US with built-in aux. switches) (F0 US with built-in aux. switches) On-off 5 to 6.5 W running,.5 to. W holding (models vary) 0 V, class power ft, 8 G appl. cable, / conduit fit. 0 V actuators/ux. switches double insulated electronic throughout rotation ngle of rotation: 95 Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank uxiliary switches: x SPDT. 5 fixed/5 to 85 (-S) Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 0 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

111 Three-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, On-Off Dimensions.86" [98] 0.47" [66] D07 4 VC Transformer Common + Hot W94.66" [9].4" [57] F4 US Provide overload protection and disconnect as required. C ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0 ] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. On-off wiring for F4 US 4 VC Transformer Common + Hot W95 5 S G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. 4 5 S S S4 S5 S6 NC NO NC NO F4-S US to 85 Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. For end position indication, interlock control, fan startup, etc., F4-S US incorporates two built-in auxiliary switches: x SPDT, 7 VC, UL listed, one switch is fixed at +5, one is adjustable 5 to 85. Meets UL and CS requirements without the need of an electrical ground connection. On-off wiring for F4-S US

112 Three-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, Proportional pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for modulating control using...0vdc or 4...0m and fail safe is required. (for 4...0m control input a 500 ohm resistor is required). Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications F4-SR US Power supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Feedback output: Control Power consumption: Transformer sizing: Electrical connection: Overload protection: to 0 VDC, 0.5 m max Proportional 6 W running, W holding 0 V, class power ft, 8 G appl. cable, / conduit fit. electronic throughout rotation ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. See Selection Chart Pg 7 for Control Valve No., C v and Close-off

113 Three-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, Proportional Dimensions.86" [98] 0.47" [66] D07 4 VC Transformer Common + Hot W96.66" [9].4" [57] Control Signal ( ) to 0 VDC (+) Y Input, 0 to 0V 5 U Output to 0V C Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0 ] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. 4 VC Transformer 4 to 0 m ( ) Control Signal (+) to 0 VDC ( ) Feedback Signal (+) 5 Ω 500Ω 4 F4-SR US Common + Hot Y Input, 0 to 0V 5 U Output to 0V F4-SR US G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (where applicable) Characterizing Disc (where applicable) Three-way Mixing YPSS Three-way Diverting Port Disc (ll -way models) Port Disc (ll -way models) Port must be piped to the by-pass leg. Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. 4 The ZG-R0 500Ω resistor converts the 4 to 0 m control signal to to 0 VDC. 5 Only connect common to neg. ( ) leg of control circuits Proportional to 0 VDC or 4 to 0 m control signal

114 Three-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed with MFT functionality which facilitates the use of various control input. This valve is designed for use where fail safe is required. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic port equal percentage port modified linear for constant flow ction Max 95 rotation Sizes Type of end fitting female, NPT Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing EPDM O-rings, lubricated Pressure rating 400 psi Media temp. range 0 F to F [-8 C to 00 C] Close off pressure 00 psi Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage port: 0% port: 0.5% - % of full rated CV port: 0% Cv rating port: see product chart for values port: 70% of port flow Tefzel is a registered trademark of DuPont ctuator Specifications F4-MFT US F4-MFT-S US Control Control signal: Power supply Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: Input impedance: Feedback output: (F4-MFT US with built-in aux. switches) MFT to 0 VDC, (4 to 0 m with 500Ω resistor) 4 VC ± 0% 50/60 Hz 4 VDC ± 0% 6 W running,.5 W holding 0 V, class power ft, 8 G appl. cable, / conduit fit. ux. switches double insulated electronic throughout rotation 00 KΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m 750Ω for PWM 500Ω for on/off and floating point to 0 VDC, 0.5 m max ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank uxiliary switches: x SPDT. 5 fixed/5 to 85 (-S) Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT 4 See Selection Chart Pg 7 for Control Valve No., C v and Close-off

115 Three-way Characterized Control Valve, Stainless Steel all and Stem F ctuators, MFT Dimensions.86" [98] 0.47" [66] D07 4 VC/DC Transformer W04.66" [9].4" [57] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US C On-Off control Nominal Valve Size Dimensions in inches [mm] in mm *-/ [].87 [48] -/ [09.5].88 [47.8] [06.4].44 [6.0 ] * On model numbers and, the -/4 valve has the same dimensions as a -/ valve. These are -/ valve bodies with -/4 NPT Threads. 4 VC Transformer (C only) Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. COM Diode may be placed at the control panel. Reduces field wiring lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US W0 Controller Position Feedback Flow Pattern G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Characterizing Disc (where applicable) Three-way Mixing YPSS Port Disc (ll -way models) Characterizing Disc (where applicable) Three-way Diverting Port must be piped to the by-pass leg. 4 VC Transformer (C only) Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Port Disc (ll -way models) lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. MFT US W04 IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. Floating Point control 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. MFT US W0 PWM, triac source and sink Proportional to 0 VDC or 4 to 0 m control signal 5

116 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem M ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications: Service chilled or hot water, 60% glycol Flow Characteristic port equal percentage Sizes.5 to Type of end fitting pattern to mate with NSI 5 flange Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Flanges carbon steel/zinc plated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications M4 US Control On-off/floating point Power Supply 4 VC ± 0% 50/60 Hz 4 VDC ± 0% Power consumption:.5w Transformer sizing: 4.5 V (Class power source) Electrical connection: ft., 8 G, appliance cable, / conduit connector Overload protection: electronic throughout 0 to 95 rotation ngle of rotation: 0-95 adjustable stops Torque: min 60 in-lb [8 Nm] Direction or rotation: reversible with switch CCW-CW Position indication: indicator/handle Running time: 00 to50 sec. for 0 to 60 in-lb Manual override: external push button Humidity: 5 to 95% RH, non-condensing mbient temperature: - F to F [-0 C to +50 C] Storage temperature: -40 F to 76 F [-40 C to +80 C] Housing type: NEM (IP54 with cable entry down) Housing material: UL94-5V (flammability rating) Noise level: less than 45 d () Servicing: maintenance free gency listings: UL 87 listed, CS C. No. 4 certified, CE Quality standard: ISO 900 LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 6 See Selection Chart Pg 8 for Control Valve No., C v and Close-off

117 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem M ctuators, On-Off/Floating Point Dimensions.6" [9] 4.09" [04]." [79].05" [06].99" [76] D099 4 VC Transformer a open a closed a 4 lk () Common Wht () + Wht () + W074 The indication of direction is valid for switch position CW. CCW CW M4 (-S) US On-off control Nominal Valve Size Dimensions in inches [mm] in mm [90].50 [89] 4 VC Transformer 4 lk () Common Wht () + W [09.5].75 [95.5] Wht () + The indication of direction is valid for switch position CW. CCW CW M4 (-S) US Floating point or on-off control G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Two-way Flange Detail for merican Standard 5 lb. Notes 4 uxiliary switch wiring for M4-S US S S S S4 S5 S6 NC NO NC NO 0 to to 95 M4 (-S) US Provide overload protection and disconnect as required. ctuators may also be powered by 4 VDC. For end position indication, interlock control, fan startup, etc., M4-S US incorporates two built-in auxiliary switches: x SPDT, VC, UL listed, adjustable between 0 and 95. Meets UL and CS requirements without the need of an electrical ground connection. Flanges Drilling olting E W076 C D Length of Nominal Flange Flange Diameter of Diameter of Number Diameter Machine Pipe Size Diameter Thickness olt Circle olt Holes of olts of olts olts -/ 7 /6 5-/ 7-/ /4 6 /4 4 5/8 -/ 7

118 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem M ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input. Valve Specifications: Service chilled or hot water, 60% glycol Flow Characteristic port equal percentage Sizes.5 to Type of end fitting pattern to mate with NSI 5 flange Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Flanges carbon steel/zinc plated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont LISTED 94D5 TEMP. IND & REG. EQUIP. UL ctuator Specifications M4-MFT US Control MFT Power Supply 4 VC, ± 0%, 50/60 Hz 4 VDC ± 0% Power consumption:.5 W running,. W holding Transformer sizing: 5 V (Class power source) Electrical connection: ft., 8 G, appliance cable, / conduit connector Overload protection: electronic throughout 0 to 95 rotation Control signal Y*: to 0 VDC Operating range*: to 0 VDC, 4 to 0 m (w/500ω, /4W resistor) ZG-R0 Input impedance: 00kΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m, 750Ω for PWM 500Ω for on/off and floating point Feedback output U *: to 0 VDC, 0.5 m max Torque: min 60 in-lb [8 Nm] Direction or rotation*: control direction selected by switch CW=CW with decrease in signal CCW=CCW with a decrease in signal ngle of rotation: 0-95 adjustable mechanical stops Running time: 50 seconds constant ngle of rotation adaptation: Off (default) Override control*: Min. (min position) = 0% ZS (mid position) = 50% Max. (max position) = 00% Manual override: manual push button Position indication: clip on indicator Humidity: 5 to 95% RH, non-condensing Operating temperature: - F to F [-0 C to +50 C] Storage temperature: -40 F to 76 F [-40 C to +80 C] Housing type: NEM IP54 (with cable entry down) Housing material: UL 94-5V (flammability rating) Noise level: less than 45 d () gency listings: UL 87 listed, CS C. No. 4 certified Quality standard: ISO 900 Servicing: maintenance free G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 8 See Selection Chart Pg 8 for Control Valve No., C v and Close-off

119 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem M ctuators, MFT Dimensions.6" [9] 4.09" [04]." [79].05" [06].99" [76] D099 Position 4 VC/DC Transformer ( ) a lk () Common Red () Hot Wht () Y Input W04 Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US On-Off control Nominal Valve Size Dimensions in inches [mm] in mm [90].50 [89] [09.5].75 [95.5] Flow Pattern 4 VC Transformer (C only) Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. COM Diode may be placed at the control panel. Reduces field wiring lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US W0 Controller Position Feedback Characterizing Disc (Where applicable) Two-way IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. 4 VC Transformer (C only) W04 Floating Point control G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. PWM, triac source and sink Flange Detail for merican Standard 5 lb. MFT US 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW MFT US Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. W0 Proportional to 0 VDC or 4 to 0 m control signal Flanges Drilling olting E C D Length of Nominal Flange Flange Diameter of Diameter of Number Diameter Machine Pipe Size Diameter Thickness olt Circle olt Holes of olts of olts olts -/ 7 /6 5-/ 7-/ /4 6 /4 4 5/8 -/ 9

120 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem F ctuators, On-Off/Floating Point pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off or floating point control is required using 4VC. Valve Specifications: Service chilled or hot water, 60% glycol Flow Characteristic port equal percentage Sizes.5 to Type of end fitting pattern to mate with NSI 5 flange Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Flanges carbon steel/zinc plated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications F4 US F4-S US F0 US F0-S US Control Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: (F4 US with built-in aux. switches) (F0 US with built-in aux. switches) On-off 5 to 6.5 W running,.5 to. W holding (models vary) 0 V, class power ft, 8 G appl. cable, / conduit fit. 0 V actuators/ux. switches double insulated electronic throughout rotation ngle of rotation: 95 Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank uxiliary switches: x SPDT. 5 fixed/5 to 85 (-S) Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() LISTED 94D5 TEMP. IND & REG. EQUIP. UL G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 0 See Selection Chart Pg 9 for Control Valve No., C v and Close-off

121 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem F ctuators, On-Off Dimensions.86" [98] 0.47" [66] D00 4 VC Transformer W94.66" [9].4" [57] Common + Hot F4 US Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. On-off wiring for F4 US Nominal Valve Size Dimensions in inches [mm] in mm [90].50 [89] [09.5].75 [95.5] 4 VC Transformer Common + Hot W95 5 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Flow Pattern Characterizing Disc (Where applicable) Two-way Flange Detail for merican Standard 5 lb. Flanges Drilling olting E C D Length of Nominal Flange Flange Diameter of Diameter of Number Diameter Machine Pipe Size Diameter Thickness olt Circle olt Holes of olts of olts olts 4 5 Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption must be observed. ctuator may also be powered by 4 VDC. For end position indication, interlock control, fan startup, etc., F4-S US incorporates two built-in auxiliary switches: x SPDT, 7 VC, UL listed, one switch is fixed at +5, one is adjustable 5 to 85. Meets UL and CS requirements without the need of an electrical ground connection. On-off wiring for F4-S US S S S S4 S5 S6 NC NO NC NO F4-S US to 85 -/ 7 /6 5-/ 7-/ /4 6 /4 4 5/8 -/

122 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem F ctuators, MFT pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV ox re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionality which facilitates the use of various control input. This valve is designed for use where fail safe is required. Valve Specifications: Service chilled or hot water, 60% glycol Flow Characteristic port equal percentage Sizes.5 to Type of end fitting pattern to mate with NSI 5 flange Materials: ody forged brass, nickel plated all Stem Seats fiberglass reinforced teflon PTFE Characterizing Disc TEFZEL Packing EPDM O-rings, lubricated Flanges carbon steel/zinc plated Pressure rating 400 PSI Media Temp Range 0 F to F Close-off pressure 00 PSI Maximum differential: For Characterized -port pressure ( P) 0 psi for typical applications 0 psi max for quiet service For full flow versions only (no -disc) On/Off control 50 psi Leakage 0% Cv rating port: see product chart for values Tefzel is a registered trademark of DuPont ctuator Specifications F4-MFT US F4-MFT-S US Control Control signal: Power supply Power consumption: Transformer sizing: Electrical connection: Electrical protection: Overload protection: Input impedance: Feedback output: (F4-MFT US with built-in aux. switches) MFT to 0 VDC, (4 to 0 m with 500Ω resistor) 4 VC ± 0% 50/60 Hz 4 VDC ± 0% 6 W running,.5 W holding 0 V, class power ft, 8 G appl. cable, / conduit fit. ux. switches double insulated electronic throughout rotation 00 KΩ for to 0 VDC (0. m) 500Ω for 4 to 0 m 750Ω for PWM 500Ω for on/off and floating point to 0 VDC, 0.5 m max ngle of rotation: 95 Direction of rotation: selected by switch: CW=CW with decrease signal CCW=CCW with decrease signal Spring return direction: CW/CCW mounting Position indication: visual indicator Manual override: hex crank uxiliary switches: x SPDT. 5 fixed/5 to 85 (-S) Running time: 50 sec. independent of load (control) < 0 sec. (spring) mbient temperature: - F to F [-0 C to 50 C] Housing: NEM / IP54 gency listings: UL 87, CS C. No. 4 certified, CE Noise level: max. 45 d() G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. LISTED 94D5 TEMP. IND & REG. EQUIP. UL MFT See Selection Chart Pg 9 for Control Valve No., C v and Close-off

123 6 Two-way Flanged Characterized Control Valve, Stainless Steel all and Stem F ctuators, MFT Dimensions.86" [98] 0.47" [66] D00 4 VC/DC Transformer W04.66" [9].4" [57] Position ( ) a lk () Common Red () Hot Wht () Y Input Feedback VDC (+) Wht (5) U Output (Grn) CCW CW MFT US On-Off control Nominal Valve Size Dimensions in inches [mm] in mm [90].50 [89] [09.5].75 [95.5] Flow Pattern 4 VC Transformer (C only) Hot MFT actuators are compatible with contact closure, triac source and triac sync type controllers. COM Diode may be placed at the control panel. Reduces field wiring lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW MFT US W0 Controller Position Feedback Characterizing Disc (Where applicable) Two-way IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055) Triac and can also be contact closures. Why is a diode required? The actuator is designed to recognize the rectified voltage as an opposite control signal request. 4 VC Transformer (C only) W04 Floating Point control G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Position Feedback VDC ( ) (+) Control signal may be pulsed from either the Hot (Source) or Common (Sink) 4 VC line Flange Detail for merican Standard 5 lb. lk () Common Red () + Hot Wht () Y Input Wht (5) U Output (Grn) CCW CW Position feedback cannot be used with a Triac sink controller. The actuators internal common reference is not compatible. PWM, triac source and sink MFT US 4 VC/DC Transformer Control Signal to 0 VDC ( ) (+) Ω to 0 VDC Position Feedback Signal With a 4-0 m Input, up to 4 actuators may be wired in parallel. % shift in the signal is seen when using a 500Ω resistor. Power consumption must be observed Ω /4 watt 4 lk () Common Red () + Hot Wht () Y Input to 0V Grn (5) U Output to 0V CCW CW MFT US Provide overload protection and disconnect as required. ctuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. ctuator may also be powered by 4 VDC. For 4 to 0 m a 500Ω resistor is required. ZG-R0 may be used. W0 Proportional to 0 VDC or 4 to 0 m control signal Flanges Drilling olting E C D Length of Nominal Flange Flange Diameter of Diameter of Number Diameter Machine Pipe Size Diameter Thickness olt Circle olt Holes of olts of olts olts -/ 7 /6 5-/ 7-/ /4 6 /4 4 5/8 -/

124 uxiliary Switches S US, S US For the direct coupled actuator M... Operation The S US and S US auxiliary switches are used to indicate when a desired position of a damper is reached or to interface additional controls for a specific control sequence. They are modular units that mount directly onto the M type actuators and held in place with a prefitted screw. driver disk is attached to the actuator clamp and offers direct transmission of the actuator position to the microswitch operating cams. The switching points can be set over the full scale of 0 to simply by adjusting the slotted discs. Diagrams Technical Data S US S US No. of switches xspdt xspdt Switching capacity 6 (.5) 50 VC Switching point adjustable over full actuator rotation 0 to. Pre-setting with scale possible. Electrical connection ft, 8 G appliance cable / conduit connector Humidity 5 to 95% RH non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing type NEM type Housing material rating UL 94-5V (flammability rating) gency listings UL 87 listed, CS 48 0 certified, CE Weight 8 oz [5 g] 9. oz [65 g] S NC N.C. S S NO N.O. S US S S S S4 S5 S6 N.C. N.O. N.C. N.O. S US Voltage Resistive Inductive G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 4

125 SNMV/SNMV uxiliary Switch Kit For NM ctuator SNMV/SNMV uxiliary Switch Kit For NM ctuator Operation The SNMV and SNMV auxiliary switches are used to indicate when a desired position is reached or to interface additional controls for a specific control sequence. They are modular units that mount directly onto the NM type actuators and are held in place with a prefitted screw. The switching points can be set over the full scale of 0 to 0 simply by adjusting the slotted discs. Technical Data SNMV SNMV No. of switches xspdt xspdt Switching capacity 6 (.5) 50 VC Switching point adjustable over full actuator rotation 0 to 0. Pre-setting with scale possible. Electrical connection ft. 8 G cable [ m long 0.75mm ] Humidity 5 to 95% RH non-condensing mbient temperature - F to + F [-0 C to +50 C] Storage temperature -40 F to +76 F [-40 C to +80 C] Housing type NEM type Housing material rating UL 94-V0 (flammability rating) Weight 4 oz [5 g] 5.6 oz [75 g] Diagrams S NC N.C. S S NO N.O. SNMV S S S S4 S5 S6 N.C. N.O. N.C. N.O. SNMV Voltage Resistive Inductive G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 5

126 CCV-EXT-KIT CCV Valve Neck Extension Kit pplication The CCV-EXT-KIT can be used with most CCV s* in order to achieve a large clearance over the pipe. The Extension Kit will provide an additional " of space between the top of the valve and the base of the actuator. The bracket is made from aluminum and is not intended as a thermal block. Extension kit will be automatically assembled with any Flanged CCV assembly. " *vailable for previous NF assemblies..65".65" Technical Data: Extension Height " Total Weight 0.7 lb Material: Extension Housing Shaft Threaded Hardware earing Retaining Clip Extension racket CCV-EXT-KIT luminum - nodized Stainless Steel Stainless Steel Oil Light earing Stainless Steel LR NM M LF NF* F G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. *CCV-EXT-KIT cannot be used with any valve smaller than the () and (). 6

127 ZS-CCV New Characterized Control Valve Weather Shield Installation Instructions PPLICTION The ZS-CCV weather shield provides moderate protection for valves which are mounted outdoors. This product is designed as a water tight enclosure. The housing allows easy mounting over the Characterized Control Valve actuator, while allowing easy viewing of the actuator in operation. Weather shield for CCV to provide protection for actuators in outdoor applications. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Specifications Cover Plate Perimeter Gasket Rubber Gasket Spring Clips Temperature limitations: Part Number ZS - CCV - 50 ZS - CCV - 60 ZS - CCV - 70 ZS - CCV - 80 ZS - CCV - 90 PRTS LIST PETG with UV resistant smoke tint Galvaneal w/black powder coat Silicon Rubber Silicon Rubber Stainless Steel - F to F (-0 C to 50 C) For ctuator LR LF NM M NF/F Cover including Rubber Perimeter Gasket, Rubber Gasket ack Plate nti-rotation Post with screw and lock washer Valve Gasket ssorted Caplugs for unused holes Part Number L W H ZS - CCV - 50 ZS - CCV [54] 7.75 [97] 4 [00] ZS - CCV - 70 ZS - CCV - 80 ZS - CCV [4] 8.75 [] 4.5 [4] Screws: NM/LF/LR - screws provided M - screw provided NF/F - bolts with nylon insert locking nuts NM - Large washer 7

128 .8 6 Characterized Control Valves (CCV) Flow Pattern Two-way Characterized Control Valves Characterizing Disc (Where applicable) Two-way (elimo Series) (elimo 6 Series) *Two-way valves should be installed with the disc upstream. Flow direction E L I M O Three-way Characterized Control Valves (elimo Series) Three-way Mixing *The port must be piped to the coil to maintain proper control. Three-way Diverting Characterizing Disc (where applicable) YPSS Port Disc (ll -way models) Characterizing Disc (where applicable) Port Disc (ll -way models) Port must be piped to the by-pass line. Mounting: The valves can be mounted in any position, except stem below horizontal Multi-Function Technology See ppendix for Complete List of Configurations Code Control Input Running Time uilt-in Feedback List Price P VDC 50-0 VDC No Charge P VDC VDC No Charge P VDC VDC No Charge P VDC VDC No Charge P VDC VDC No Charge P sec. PWM 50-0 VDC No Charge P sec. PWM 50-0 VDC No Charge P-000 Floating Point 50-0 VDC No Charge Example: LF4-MFT US is the basic model. dd the P pre-set MFT configuration number and list price to the actuator when ordering, as needed. Note: Most popular configurations available at no additional cost. ll other configurations carry a $0.00 list price. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 8

129 Electronic Characterized Control Valves / Series Characterized Control Valves Default Set-Up: Two-way valve Two-way valve Three-way valve Three-way valve (Default) (specify upon ordering) (Default) (specify upon ordering) Non-Spring Return - Stays in last position TR4--T US Power to pin will Power to pin will drive valve CCW drive valve CCW Power to pin will Power to pin will drive valve CW drive valve CW TR4-SR-T US NC: Closed to, will NO: Open to, will close NC: Closed to, will NO: Open to, will close open as voltage increases as voltage increases. open as voltage increases as voltage increases. (Can be chosen with (Can be chosen with switch inside terminal switch inside terminal block of actuator). block of actuator). LR4(-) US, NC: Closed to, will NO: Open to, will close NC: Closed to, will NO: Open to, will close LR4-SR, -MFT US open as voltage increases as voltage increases or power open as voltage increases as voltage increases or power NM4 US, NM4-SR,-MFT US or power applied applied. (Can be chosen or power applied applied. (Can be chosen M4 US, M4-MFT US with CW/CCW switch ). with CW/CCW switch ). TF4 US NO/FO Valve: Open to NC/FC Valve: Closed to NO/FO Valve: Open to NC/FC Valve: Closed to LF4 US will drive closed. will drive open. will drive closed. will drive open. F4 US Spring ction: Will spring Spring ction: Will spring Spring ction: Will spring Spring ction: Will spring open to closed to open to closed to upon power loss. upon power loss. upon power loss. upon power loss. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Spring Return - Note Fail Position LF,TF, F (-), -MFT, -SR NC/FO Valve: Closed to NC/FC or NO/FC NC/FO Valve: Closed to NC/FC or NO/FC Floating or proportional will drive open. Valve: Closed to or will drive open Valve: Closed to type actuators Spring ction: Will spring Open to Spring ction: Will spring or Open to open to (Can be chosen with open to (Can be chosen with upon power loss. CW/CCW switch). upon power loss. CW/CCW switch). Spring ction: Will spring Spring ction: Will spring closed to closed to upon power loss. upon power loss. General Instructions WRNING The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit. lways read the controller manufacturer's installation literature carefully before making any connections. Follow all instructions in this literature. If you have any questions, contact the controller manufacturer and/or elimo. Transformer(s) elimo actuators require a 4 VC class transformer and draws a maximum of 0 V per actuator. The actuator NO/FO Valve: Open to Spring ction: Will spring open to upon power loss. (NO action can be chosen with CW/CCW switch). NO/FO Valve: Open to Spring ction: Will spring open to upon power loss. (NO action can be chosen with CW/CCW switch). enclosure cannot be opened in the field, there are no parts or components to be replaced or repaired. EMC directive: 89/6/EEC Software class : Mode of operation type Low voltage directive: 7//EEC CUTION: It is good practice to power electronic or digital controllers from a separate power transformer than that used for actuators or other end devices. The power supply design in our actuators and other end devices use half wave rectification. Some controllers use full wave rectification. When these two different types of power supplies are connected to the same power transformer and the DC commons are connected together, a short circuit is created across one of the diodes in the full wave power supply, damaging the controller. Only use a single power transformer to power the controller and actuator if you know the controller power supply uses half wave rectification. 9

130 Electronic Characterized Control Valves / Series Characterized Control Valves Operation/Installation Correct Piping: -way valves should be installed with the disc upstream. If installed with disc downstream, flow curve will be deeper. If installed backwards it is NOT necessary to remove and change. No damage or control problems will occur. Two-Way Valve Piping Diagram ( Input, Output) Three-Way Mixing Valve Piping Diagram ( Inputs, Output) Three-Way Diverting Valve Piping Diagram ( Input, Outputs) Return Return Return Coil Supply Coil Supply Coil Supply -way valves must be piped correctly. They can be mixing or diverting. Mixing is the preferred piping arrangement. The ELIMO Characterized Control Valve is a CONTROL valve, not a manual valve adapted for actuation. The control port is the port. It is similar to the globe valve in that the middle port is the or bypass port. The common port is on the main opposite the port. These diagrams are for typical applications only. Consult engineering specification and drawings for particular circumstances. The port must be piped to the coil to maintain proper control. The port restricts flow by 0% of port value. Incorrect Piping: Three-Way Mixing Valve Piping Diagram ( Inputs, Output) Three-Way Diverting Valve Piping Diagram ( Input, Outputs) Coil Return Supply Coil Return Supply WRNING! Do Not Pipe in this manner! Note Valve Porting! The port must be piped to the coil! Not the port! Flow is not possible from to. If port is not piped as the common port, the valve must be re-piped. It is good practice to install a balancing valve in the bypass line. These valves are intended for closed loop systems. Do not install in an open loop system or in an application that is open to atmospheric pressure. ssembly: 4 5 One screw attaches actuator to valve Four actuator mounting positions -way flow pattern -way flow pattern (mixing shown) Top of valve stem indicates direction of flow (Flow to shown) Note: For diverting flow, flow enters in and diverts to and ports. 0 CCW CCW 4 x 90 G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 0 - = 00% - =00% - =0% 5 4

131 Notes/Work Pad G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc.

132 Custom MFT Configuration Order Form FX: US Toll Free # Select an ctuator (use one sheet for each unique actuator/configuration) F4-MFT US F4-MFT95 US NF4-MFT US LF4-MFT US LF4-MFT-0 US GM4-MFT US M4-MFT US NM4-MFT US LM4-MFT US LR4-MFT US Control Types ➁ Feedback signals U 5 ➂ Diagnostic Feedback Maintenance and fault signals U 5 ➃ Running time ➄ Quantity ngle of rotation setting ➀ Please call elimo if you wish to make use of the maintenance and fault signals. F4-MFT-S US NF4-MFT-S US LF4-MFT-S US LF4-MFT-S-0 US NV4-MFT US NVF4-MFT US NVF4-MFT-E US NVFD4-MFT US NVFD4-MFT-E US (-S=uxiliary Switch) # Create a Custom Configuration Quantity Deactivated (default) ctivated VDC PWM Floating On/Off 0 0. to 5.0 sec to 5.5 sec. Variable 0.59 to.9 sec. Start. Variable Stop. Start. Position Feedback U Position Feedback U Position Feedback U OFF Manual triggering by pressing the pushbutton twice utomatic triggering each time the unit is powered up or by pressing the pushbutton twice. (default) Position and Diagnostic feedback Maintenance signal Fault signal 50 s (default) Running time Name Company ddress City State Zip Stop. DC...0 V (Default) DC V Select all maintenance and fault signals required ctuator hunting, Stop-Go ratio Start DC. V (0...8 V) Finish DC. V (...0 V) Mechanical overload, actuator stopped Mechanical load limit reached Mechanical travel changed 0% ➁➅ The following settings - refer to the full angle of rotation of 95º. The following settings ➁➅ - are automatically adapted to the effective mechanical angle of rotation. s ( s) (in 5 sec. increments) Note: The sound power level [d()] increases when the running time is below 50 s. The finish must be at least V above the start! For these functions! with a mechanicallylimited angle of rotation (<95º) the angle of rotation setting ➀ must be activated! Phone Fax Field Labeling: LL-MFT ($8.00 List) Custom configuration labels required -/8 X -/4 orange labels preprinted to your specifications label sets per sheet. Includes configuration code and wiring labels. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Override control and electronic angle of rotation limiting ➅ Torque ➆ Non-Spring Return Only! Min. (min. position) = % (0...00%) (beginning of working range) default 0 ZS (intermediate position) = % (0...00%) (0% = Min.; 00% = Max.) default 50 Max.(max. position) = % (0...00%) (end of working range) default 00 normal (default 00%) 75% 50% 5%

133 ctuator/valve Specification To download specifications, see G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. I. GENERL. Warranty all actuators for a period of two or five years from the production date as stated in the Terms and Conditions of Sale and Warranty.. Electronic valve and damper actuators shall be as manufactured, brand labeled, or distributed by elimo. C. Electronic control valves, as specified, shall be elimo or other brands manufactured, brand labeled or distributed by elimo. D. Other manufacturers must be approved, in writing, 0 days prior to the bid date. II. PRODUCTS. Electronic Damper ctuators. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO 900 quality certification and be UL listed under standard 87, CS C. No. 4 and have CE certification.. Electronic actuators used on dampers shall be designed to directly couple and mount to a stem, shaft or ISO style-mounting pad. ctuator mounting clamps shall be a V-bolt with a toothed V-clamp creating a cold weld, positive grip effect. Single point, bolt, or single screw actuator type fastening techniques or direct-coupled actuators requiring field assembly of the universal clamp is not acceptable.. ctuators shall be fully modulating/proportional, pulse width, floating/tri-state, or two position as required and be factory or field selectable. ctuators shall have visual position indicators and shall operate in sequence with other devices if required. 4. Optional auxiliary switches shall be available. 5. ctuators shall have an operating range of to F. 6. Proportional actuators shall accept a 0-0 VDC or 0-0 m input signal and provide a -0 VDC or 4-0 m (with a 500 W load resistor) operating range. 7. ctuators shall be capable of operating on 4, 0 or 0VC, or 4VDC and Class wiring as dictated by the application. Power consumption shall not exceed 0 V for C, including 0VC actuators, and 8 watts per actuator for DC applications. 8. NEM rated actuators shall be provided with a three foot (minimum), pre-wired, electrical cable. ctuators requiring removal of the actuator cover for access to wiring terminals, exposing electronic, printed circuit boards to damage, are unacceptable. 9. ctuators shall have electronic overload protection or digital rotation sensing circuitry to prevent actuator damage throughout the entire rotation. End switches to deactivate the actuator at the end of rotation or magnetic clutches are not acceptable. 0. For power-failure/safety applications, an internal mechanical spring return mechanism shall be built into the actuator housing. Spring return actuators shall be capable of CW or CCW mounting orientation. Spring return models > 60 in-lbs. will be capable of mounting on shafts up to.05" in diameter. Spring return actuators with more than 60 in-lb. of torque shall have a metal, manual override crank.. ctuators using "on-board" chemical storage systems, capacitors, or other "on-board" non-mechanical forms of fail-safe operation are unacceptable.. Upon loss of control signal, a proportional actuator shall fail open or closed based on the minimum control signal. Upon loss of power, a non-spring return actuator shall maintain the last position.. ctuators shall be capable of being mechanically and electrically paralleled to increase torque if required. Valves and dampers requiring greater torque or higher close off may be assembled with multiple low torque actuators. 4. Dual mounted actuators using additional anti-rotation strap mechanical linkages, or special factory wiring to function are not acceptable. ctuators in a tandem pair must be "off the shelf," standard actuators ready for field wiring. 5. Damper and valve actuators will not produce more than 6 d () when furnished with a mechanical fail-safe spring. Non-spring return actuators shall conform to a maximum noise rating of 45 d() with power on or in the running or driving mode. 6. Proportional actuators shall be fully programmable. Control input, position feedback and running time shall be factory or field programmable. Diagnostic feedback shall provide indications of hunting or oscillation, mechanical overload, mechanical travel and mechanical load limit. The actuators shall also provide actuator service data, at minimum, number of hours powered and number of hours in motion. 7. Proportional actuators shall be capable of digital communication, as built.. Smoke and Combination Fire and Smoke ctuators In Section 580 or equivalent. ll smoke and combination fire and smoke dampers shall be provided with elimo ircontrols FSLF (0 in-#), FSNF (70 in-#), or FSF ( in-#) actuators.. Equals shall be approved 0 days prior to submission of bid.. ctuator shall carry a manufacturer s 5-year warranty and be manufactured under ISO 900 quality control. 4. ctuator shall have microprocessor or electronic based motor controller providing: a. Electronic cut off at full open so that no noise can be generated while holding open. Holding noise level shall be inaudible. b. Protection so that actuator shall be incapable of burning out if stalled before full rotation is reached. 5. Housing shall be steel and gears shall be permanently lubricated. 6. The actuators shall be direct coupled and employ a steel toothed cold-weld clamp for connecting to damper or jack shafts. luminum clamps or set-screw attachment are not acceptable. 7. ctuator shall have UL555S Listing by the damper manufacturer for 50 F. 8. FSLF shall be applied on dampers up to 6 sq. ft. Current draw shall be no more than.5 at 0V running, or.06 holding at 0V (5 V and.5 V respectively for 4V power).fsnf shall be applied on dampers up to 6 sq.ft. Current draw shall be no more than. at 0V running, or. holding at 0V (7 V and 0 V respectively for 4V power). 9. FSF shall be applied on dampers up to 4 sq.ft. Current draw shall be no more than. at 0V running, or.05 holding at 0V (0 V and V respectively for 4V power). 0. Dampers shall be installed straight and true, level in all planes, and square in all dimensions. Dampers shall move freely without undue stress due to twisting, racking, bowing, or other installation error.. Do not install in area where moisture can penetrate damper or actuator nor where actuator temperature exceeds 0 F. Note: FSLF and FSNF are 50 F actuators, 5 seconds open and close. UC and UL555S FSF is a 50F actuator, 75 seconds open, 0 seconds close. UL555S. C. Electronic Valve ctuators. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO 900 quality certification and be cul or UL listed under standard 87, CS C. No. 4 and have CE certification.. Electronic actuators used on valves shall be designed to directly couple and mount to a stem, shaft or ISO style-mounting pad.. ctuators shall be fully modulating/proportional, floating/tri-state, or two position as required and be factory or field selectable. 4. Optional auxiliary switches shall be available. 5. ctuators shall have an operating range of to F. 6. Proportional actuators shall accept a 0-0 VDC or 0-0 m input signal and provide a -0 VDC or 4-0 m (with a load resistor) operating range. 7. ctuators shall be capable of operating on 4VC, 0VC or 0VC, or 4VDC and Class wiring as dictated by the application. Power consumption shall not exceed 0 V for C, including 0VC actuators, and 8 watts per actuator for DC applications.

134 ctuator/valve Specification 8. NEM rated actuators shall be provided with either a covered terminal strip, or a three, six, or ten foot pre-wired, electrical cable. 9. For power-failure/safety applications, an internal mechanical spring return mechanism shall be built into the actuator housing. Spring return actuators shall be capable of CW or CCW mounting orientation. Spring return actuators with more than 60 in-lb. of torque shall have a metal, manual override crank. 0. ctuators using "on-board" chemical storage systems, capacitors, or other "on-board" non-mechanical forms of fail-safe operation are unacceptable.. Upon loss of control signal, a proportional actuator shall fail open or closed based on the minimum control signal. Upon loss of power, a non-spring return actuator shall maintain the last position.. ctuators utilizing brushless DC technology shall be capable of being mechanically and electrically paralleled to increase torque if required. Valves requiring greater torque or higher close off may be assembled with two low torque actuators.. Dual mounted actuators using additional anti-rotation strap mechanical linkages, or special factory wiring to function are not acceptable. ctuators in a tandem pair must be "off the shelf," standard actuators ready for field wiring. 4. Valve actuators will not produce more than 6 d () when furnished with a mechanical fail-safe spring. Non-spring return actuators shall conform to a maximum noise rating of 45 d() with power on or in the running or driving mode. 5. Proportional actuators shall be fully programmable. Control input, position feedback and running time shall be factory or field programmable. Diagnostic feedback shall provide indications of hunting or oscillation, mechanical overload, mechanical travel and mechanical load limit. The actuators shall also provide actuator service data, at minimum, number of hours powered and number of hours in motion. 6. Proportional actuators shall be capable of digital communication, as built. D. Industrial ctuators. elimo SY Series Industrial Electric ctuators a. The valve actuator shall consist of a thermally protected capacitor-type reversible electric motor, a patented planetary worm combination drive, heater, limit switches and wiring termination blocks, all contained in a die cast aluminum enclosure. The drive system will provide continuous, smooth torque transmission throughout a 90 degree travel. djustable stops provide mechanical adjustment of end-of-travel. The transmission shall allow continuous duty operation of a manual override handwheel without the need to remove power, or de-clutch the manual system. b. Enclosure shall be designed to meet NEM 4, 4X (weatherproof) requirements, or CS approved for non-hazardous locations. c. The actuator shall employ ISO5 mounting standards to provide for a wide range of international applications. d. The enclosure will have an industrial quality coating. e. ctuator shall have a motor rated for a minimum of 5% duty cycle in modulating applications. f. ctuator shall be suitable for operation in ambient temperature ranging from -4 F to +50 F [-0 C to +65 C]. g. The motor shall be fractional horsepower; permanent split capacitor type designed to operate on 4 VC, 0 VC or 0 VC, ph, 50/60 Hz supply. self resetting thermal switch shall be imbedded in the motor for overload protection. h. Internal terminal blocks shall be clearly marked for field wiring. wiring diagram shall be permanently attached to the OUTSIDE of the actuator housing. i. ctuator will have a suitable sized NPT entry for external connections. j. Gears shall be hardened alloy steel, permanently lubricated. The worm drive system negates the need for a brake. k. Two adjustable cam actuated end travel limit switches shall be provided to control electrical movement of the actuator. l. SPDT auxiliary switches, rated 0 at 50 VC shall be included. The switches are factory pre-set at degrees and 87 degrees rotation, and may be field adjusted. m. ctuator shall be equipped with a hand wheel or shaft for manual override to permit operation of the actuator in the event of electrical power failure or system malfunction. Hand wheel, where applicable, must be permanently attached to the actuator. (SY and larger) n. The handwheel override shall be continuously operational regardless of the powered state of the actuator, without the need to remove electrical power if present during the override phase. (SY and larger) o. The hand wheel will not rotate while the actuator is electrically driven. p. The actuator shall provide a visual indicator beacon on the top of the housing for position status of the actuator and attached devices. q. ctuator shall have an internal heater and thermostat to minimize the build-up of moisture inside the sealed enclosure. r. Modulating units shall operate under -0 VDC, 4-0m, and - 5 VDC control modes. The default shall be -0 VDC control. E. Electronic Control Valves. General a. The manufacturer shall be capable of providing individual valve identification tagging on each printed valve label. Valve tag identification shall be documented on the approved, submitted valve schedule. b. Valves shall be designed and provided with the proper actuators to provide the rated valve close-off.. Pressure Independent Characterized Control Valves a. Control valves shall be pressure independent. alancing valves and associated balancing shall not be required on devices where pressure independent control valves are installed. alancing valves and balancing are required if self-contained pressure independent control valves are not installed. b. The absolute flow accuracy through the valve shall be +/- 5 % due to system pressure fluctuations across the valve in the selected operating range, and +/- 5% variation due to manufacturing tolerances. c. The control valves shall be available with floating or proportional actuators. The actuator shall be directly coupled to the valve at the factory. Proportional actuators shall be Multi Function Technology as manufactured by elimo. Multi-turn actuators are not acceptable. d. The valve shall have an equal percentage characteristic and shall accurately control the flow from 0 to 00% full rated flow. e. minimum of 5 PSI shall be required to operate the valve pressure independently. f. Valves shall require no maintenance and shall not include replaceable cartridges. g. Exact flow setting shall be achieved by a mechanical device inserted between the valve and actuator. h. Valves shall be available with optional pressure/temperature ports to allow flow verification. j. Control valves shall be by elimo. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 4

135 ctuator/valve Specification G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc.. Characterized Control Valves a. Control valves shall be of the Characterized Control Valve type provided by elimo. b. Characterized Control Valves shall be used for all water applications requiring equal percentage characteristics. c. TEFZEL flow-characterizing disc shall be installed in the inlet of Two-way characterized control valves and in the control port of Three-way valves. The valve trim shall utilize a ball and stem for all water or glycol solutions up to 60%. For water applications, an optional chrome plated brass ball and brass stem may be used for sizes /4 and smaller. d. Valve bodies shall be nickel-plated, forged brass with female NPT threads. odies to -/4" shall be rated at 600 psi and sizes -/" to " at 400 psi. e. Characterized Control Valves shall have a self-aligning, blowout proof, brass stem with a dual EPDM O-ring packing design. Fiberglass reinforced Teflon seats shall be used. f. The valves shall have a four bolt mounting flange to provide a 4 position, field changeable, electronic actuator mounting arrangement. g. non-metallic coupling, constructed of high temperature, continual use material shall provide a direct, mechanical connection between the valve body and actuator. The coupling shall be designed to provide thermal isolation and eliminate lateral and rotational stem forces. Vent hole shall be provided to reduce condensation build-up. 4. Globe Valves a. Globe valves, as specified, shall be by elimo. b. Two-way and Three-way globe valves may be used only if characterized control valves do not fit the sizing criteria or application. c. Globe valves may be used for chilled or hot water, steam, or glycol solutions to 60%. Screwed and flanged water valves shall have equal percentage or linear flow characteristics for Two-way or Three-way valves, respectively. ll stems shall be. d. Screwed globe valves /" through " shall have bronze bodies rated at NSI Class 50. For water up to 5 psi or steam up to 5 psi, trim shall include a brass plug, a spring-loaded TFE packing, and a bronze seat. The maximum differential shall be 5 psi for water and 5 psi for steam. e. Two-way and Three-way flanged globe valves -/" to 6" shall have cast iron bodies rated for NSI Class 5 or NSI 50. The maximum differential shall be 5 psi for water and 0 psi for steam. Trim shall include stems, bronze plugs, bronze seats, and a TFE V-ring packing. f. For steam inlet pressures higher than those stated above, furnish globe valves with trim specifically rated for the application. 5. Direct Coupled Globe Valve ctuator and daptor racket a. ctuator shall be designed with an integrated adaptor bracket that will direct mount to the valve. b. ctuator shall provide a linear force capable of fulfilling the required close-off of the valve. c. ctuator shall include an automatic valve coupling device that shall lock securely to the valve stem. d. Proportional and spring return actuators shall adapt upon powering the actuator. This adaptation will determine stroke length and enable the actuator to set the minimum and maximum limits of the supplied control signal, thereby utilizing the entire control signal range. Feedback, running time and other parameters are automatically adjusted to the effective stroke. e. ctuator shall have a manual override equipped with an interlocking device to protect the actuator from over-torque of the manual override. 6. utterfly Valves a. utterfly valves, as specified, shall be by elimo. b. utterfly valves " to " shall have a fully lugged, drilled and tapped, cast iron body, rated to 00 psi body pressure, with 4" and larger valves having a body pressure rating of 50 psi. Flanges shall meet NSI 5/50 standards. The one-piece body shall feature an extended neck allowing sufficient clearance for flanges and " of piping insulation. The disc shall be 04 and provide bi-directional bubble-tight close off in either direction for chilled or hot water or 50% glycol applications. The disc shall be polished and contoured to minimize torque and wear. Shaft shall be mechanically retained in valve body using split-thrust washer and internal retaining-ring design for ease of service. The valve body shall employ ISO5 actuator mounting and shaft connection standards. c. The disc shall have full 60-degree concentric seating. Valves up through " shall utilize an internal spline for the disc-to-stem connection. External mechanical methods to achieve this mechanical connection, such as pins or screws, shall not be employed. Valves 4" and larger will utilize a dual-pin method to prevent the heavy disc from settling onto the liner, causing distortion. phenolic backed, non-collapsing, EPDM seat shall be field replaceable and shall create a positive seal between flange face and valve body. No gaskets shall be required between the valve and flange faces. The shaft shall be supported at four locations by RPTFE bushings. d. The flow characteristic shall be modified equal percentage for Two-way valves and linear for Three-way valves. Valves " through " shall be rated for standard HVC service of up to 50 psi close-off, or for heavy commercial service of up to 00 psi close-off. Valves 4" and larger shall be rated for up to 50 psi close-off. e. permanent metal tag shall designate manufacturer, series number and materials of construction. f. utterfly valves may be used in all two-position applications and modulating applications larger than ", or where the close off rating of other valve styles does not meet the design requirements. g. utterfly valves shall be sized primarily by using velocity calculations to prevent fluid velocities from exceeding feet per second. For modulating applications, CV factors at sixty (60) degrees shall be used for determining delta P once size has been determined by the velocity calculations. h. High torque industrial valve actuators, >00 in-lb. of rated torque, may be used where low torque actuators are not suitable. High torque actuators shall be as manufactured or provided by elimo. 7. Zone Valves a. Zone valves, as specified, shall be by elimo. b. Zone valves shall be used in terminal unit water applications requiring a Two-way or Three-way diverting valve in sizes and smaller. c. Zone valves shall have brass bodies with female NPT or sweat ends and a stem. d. Zone valve actuators shall be on/off and shall be available in 4VC or 0VC. e. Zone valve actuators shall have a minimum of 0 psi close-off rating. f. Zone valves shall have push button for quick removal of actuator. g. Zone valves shall have a leakage rate of 0.% or lower. 5

136 Terms and Conditions of Sale and Warranty I. General Until otherwise arranged, in writing, the following conditions are valid. The Seller as referred to in the terms of sale is elimo ircontrols (US) Inc. or elimo ircontrols (CN) Inc. II. III. IV. Price. Our prices are net, FO Point of Origin in US currency for sales made by elimo ircontrols (US), Inc. and CN currency for sales made by elimo ircontrols (CN) Inc.. Freight and packaging (wooden crates, pallets etc) will be charged at cost for each shipment.. Orders with a net value of less than US$00 (CN$450) will be subject to a US$0 (CN$5) handling fee. 4. No handling fee will be applied to orders placed through the elimo Internet ordering system ( 5. We reserve the right to make partial deliveries, which can be invoiced separately. 6. diagrams, installation, and commissioning are not included in our prices. Payment. Invoices are payable in US currency for sales made by elimo ircontrols (US), Inc. and in CN currency for sales made by elimo ircontrols (CN) Inc. within 0 days from the date of invoice without any deductions.. ccounts with balances exceeding 60 days will be subject to an interest charge of % per month.. ccounts with balances exceeding 45 days will be subject to restricted shipments or COD status. Title and Risk Title in and property to the goods shall not pass to the uyer until the Seller has received payment in full. V. Damage or loss in Transit Seller assumes no liability for damage or loss of shipment. ll shipments should be unpacked and examined immediately upon receipt. ny external evidence or loss or damage must be noted on the freight bill or carrier s receipt and signed by the carrier s agent at the time of delivery. Failure to do so will result in the carrier s refusal to honor the claim. uyer then should notify Seller with copy of freight bill or damage report so that Seller then can file claim for loss or damage in transit with the carrier. If damage does not become apparent until shipment is unpacked, customer must make a request for inspection by the carrier s agent and file with the carrier within 5 days after receipt of product and notify Seller. Seller is not liable for consequential damages resulting from the installation of damaged product. VI. VII. Delivery elimo undertakes to make every attempt to adhere to its delivery promise(s), but does not accept cancellation of contract or liability for any direct or indirect losses which may arise, for any reason whatsoever, due to our failure to adhere to such promise(s). Return of Goods. Goods received by the uyer cannot be returned unless previously agreed upon with Seller. uyer must acquire Return Material uthorization (RM) number from elimo prior to return of the goods. t this time uyer will also receive instructions where product is to be returned to. Only products returned to proper location with RM number will be considered for credit.. Only goods in original packaging can be accepted. Goods returned must be in condition for resale as new equipment to qualify for credit. minimum restocking charge of 0% for actuators and 5% for valve products and valve assemblies of the invoice value will be applied. Return material must be shipped prepaid.. Returns resulting from errors by the Seller will not be subject to restocking charges. VIII. Warranty VIII. 5-year warranty. The 5-year warranty applies to products listed in our literature as having a five-year warranty if shipped after May, 000 and if the product was shipped to locations within the US and Canada.. The warranty is unconditional for the first two years from the date of production. For the following three years, a conditional warranty applies. Under this conditional warranty, the consequences of ordinary wear and tear, damage due to negligence or improper use, or other causes beyond our control are excluded from warranty coverage. Product specific terms of warranty with regard to warranty period or conditions of warranty may apply to certain specified products as stated in the documentation for those products. VIII. -year conditional warranty. Warranty for products listed in our literature as a -year warranty and shipped after March, 005 for products shipped to locations within the US and Canada.. The warranty is conditional for two years from the date of production.. Under this conditional warranty, the consequences of ordinary wear and tear, damage due to negligence or improper use, or other causes beyond our control are excluded from warranty coverage. Product specific terms of warranty with regard to warranty period or conditions of warranty may apply to certain specified products as stated in the documentation for those products. VIII.C General Warranty Terms. The warranty shall be null and void should the uyer or any other persons modify or repair any part of our equipment. uyer must acquire a Return Material uthorization (RM) number from Seller required in all cases to complete the warranty process. sk our Customer Service department for detailed information.. Repaired, replaced or exchanged product will be warranted for the repair warranty period (6 months) in effect as of the date the repaired, exchanged or replaced product is shipped by elimo, or the remainder of the original warranty, whichever is longer. 4. Products found to be defective for which warranty is applicable will be replaced or repaired at Seller s discretion. Seller is not responsible for charges resulting from the removal and/or replacement of product. 5. efore removing a product from the installation we suggest to contact an UTHORIZED elimo technical support technician by calling elimo customer service at the locations listed on the back page of the Product Guide and Price List. G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. 6

137 Terms and Conditions of Sale and Warranty G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. IX. 6. The elimo specialist will work with the field technician to troubleshoot the problem. (Many problems are site-related and can be solved over the phone.) 7. If deemed necessary, an RM# will be issued for return of the product by the support technician. 8. Carefully package the product for shipping, and clearly mark the RM# on the outside of the package.without the RM# clearly marked, the package may be refused at the receiving point. 9. Product returned without proper RM# documentation will void the warranty process. 0. Ship the product to the designated service facility as directed by the elimo Customer Service.. dvanced warranty products can be obtained from the elimo technical staff after the troubleshooting process has been completed. In order to obtain advanced warranty product, you will be required to issue a purchase order for the replacement product, which will be credited upon the receipt and verification of the defective product under the RM number. dditional charges may apply if the nature of the problem has been misrepresented.. Warranty products are shipped from elimo service centers via GROUND shipment. Other shipping methods are available at the expense of the recipient.. The conditional and unconditional warranty covers the product only, and does NOT cover labor associated with troubleshooting, removal or replacement of such product, unless, after troubleshooting the product it is deemed to be a factory defect. In these cases, labor costs associated with the process can be negotiated EFORE the work is done. This is a process that consists of the elimo Quality Control Manager, the Product Manager, and the elimo Service Technician, who review the data associated with the incident before negotiating with the contractor of record. 4. NEW products ordered in an attempt to circumvent the warranty process may NOT be reimbursed if, upon receipt of a returned product, it is determined that the product defect is actually field related, or product has been returned for cosmetic reasons only. 5. dvanced Warranty for utterfly Valves products may or may not be "new", but have been thoroughly checked by the factory for electrical and mechanical operation, and carry the full warranty through to the end of the original product warranty period. No warranty for non-hvc application The Seller does not grant any warranty for the use of ELIMO products in fields which are not standard HVC applications; in particular, ELIMO does not grant any warranty for the use of ELIMO products in aircraft, industrial processes, etc. uyers will be fully responsible for any resulting damage in this case. X. Liability disclaimer The liability of the Seller is defined conclusively in section 0. ny other buyer claims towards the Seller, irrespective upon which legal basis these are made, especially those concerning price reduction or cancellation, are excluded and expressly dismissed. XI. XII. uyers do not have any rights to claim for damage, which does not occur on ELIMO products. In particular, the Seller does not accept any liability for costs incurred for determination of the causes of damage, for expert opinions or indirect or resulting damage (including damage resulting from faults) of any kind, such as loss of use, downtimes, loss of profit or returns etc. The Seller does not accept any liability for damage resulting from or contributed by the buyer or third parties acting within the scope of responsibility of the buyer when. ELIMO products are used for non HVC applications, especially in aircrafts, industrial processes, etc.;. ELIMO products are used without compliance with applicable legal or institutional regulations or the ELIMO data and installation sheets;. ELIMO products are used by personnel who have not received suitable instruction; 4. ELIMO products are modified or repaired without the written approval of ELIMO. When requested to do so, the buyer shall immediately release ELIMO in full from any possible third party claims resulting in connection with the circumstances listed above. This also applies to claims in connection with product liability. Force majeure Neither the Seller nor the buyer accept liability for damage of any kind if obstacles occur which they are unable to prevent in spite of all due care, irrespective of whether these occur at the site of the Seller, the buyer or a third party. Such obstacles are, for example, epidemics, mobilization, war, uprisings, serious operational problems, accidents, labor disputes, delayed or faulty delivery of the required raw materials, semi-finished or finished goods, off-spec rejection of important work pieces, institutional measures or injunctions, natural hazards or any other circumstances which are, to a large extent, not within the scope of control of the Seller or the buyer. However, payment may not be retained or delayed for product(s) delivered to uyer with reference to such circumstances. In such cases, both parties shall undertake all effective measures, which can be expected of them to prevent damage, or if damage occurs, to minimize the scope of this damage as far as possible. Non-Stock and Non-Catalog Items Products not listed in the current price list or catalogs are considered to be special order items and subject to minimum order quantities, special handling charges, and/or other conditions stipulated to us by suppliers. Such items normally are subject to longer delivery times. Special order items may carry cancellation charges once an order is placed and may also be subject to a restricted return policy. XIII. Proper Law and Jurisdiction For sales made by elimo ircontrols (US) Inc., this contract is and shall be deemed to have been made in the United States, and shall in all respects, be governed by U.S. laws or the laws of the State of manufacture. For sales made by elimo ircontrols (CN) Inc., this contract is and shall be deemed to have been made in Canada, and shall in all respects, be governed by Canadian laws or the laws of the Province from which they were sold. 7

138 Valve Quotation Form Contact Name: Company: ddress: Phone: Fax: elimo ircontrols (US), Inc. 4 Old Ridgebury Rd. 675 East Prater Way 5 E. Thomas Street 65 South Roselle Rd Danbury, CT 0680 Suite 0 Inverness, FL 445 Schaumburg, IL 609 (0) Sparks, NV 8944 (5) (847) Fax: (0) (775) Fax: (5) Fax: (847) 5-44 Toll Free: Fax: (775) Toll Free: Toll Free: Phone: (800) Toll Free: Phone: (888) Phone: (877) Fax: (800) 8-88 Phone: (800) Fax: (888) 89-4 Fax: (877) 8-66 (800) CTUTE Fax: (800) Project Name: From Project Specifications Valve Type and ctuator Specifications System Flow (GPM) Desired Pressure Drop (PSI) Desired C v Pipe Size (in.) System Close-Off Pressure (PSI) Notes 0 VC Modulating Spring Return Switches G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. Quantity PICCV CCV Globe utterfly Zone Two-way Three-way 4 VC On-Off -Point Floating 8

139 elimo Platinum Distributors G049-0/05 - IG-Subject to change. elimo ircontrols (US), Inc. US ireco Supply 90 Washington lvd. Savage, MD Phone: With branch in MD, V mcon Controls, Inc. 906 Warfield San ntonio,tx 786 Phone: pplied utomation 86 South Washington Street, #0 Salt Lake City, UT 845 Phone: oston ircontrols, Inc. 8 lanchard Road urlington, M 080 Phone: Charles D. Jones Co. 445 ryant Street, Unit # Denver, CO Phone: With branches in CO, MO Climatic Control Co., Inc. 506 W. State Street Milwaukee, WI 508 Phone: With branches in WI Cochrane Supply and Engineering, Inc. 00 Stephenson Highway Madison Heights, MI Phone: With branches in MI Columbus Temperature Control 05 E. 5th ve. Columbus, OH 40 Phone: Control Consultants & Supply Co. 0 Hampton venue St. Louis, MO Phone: With branch in TN Controlco 5600 Imhoff Drive, Ste. G Concord, C 9450 Phone: With branches in C Edward C. Smyers & Co. Fort Pitt lvd. Pittsburgh, P Phone: G & O Thermal Supply 545 N. Northwest Highway Chicago, IL 6060 Phone: With branches in IL, WI Hoffman Hoffman, Inc. 86 Patterson Street Greensboro, NC 7407 Phone: Industrial Controls Distributors LLC 776 loomsbury venue Wanamassa, NJ 077 Phone: With branches in NY, P Interstate Electric Equipment 0 Vineland St. righton, M 05 Phone: Jackson Controls 708 E. 0th Street Indianapolis, IN 460 Phone: M & M Controls 9E West ylesbury Road Timonium, MD 09 Phone: MICONTROLS, Inc th Place South Seattle, W 984 Phone: With branches in W, OR Minvalco, Inc. 40 Gorham venue Minneapolis, MN Phone: RSD/Total Control 60 tlantic Ocean Dr. Lake Forest, C 960 Phone: With branches in C, NV, OR, K, Z, ID, UT, W South Side Control Supply, Co. 488 N. Milwaukee venue Chicago, IL Phone: With branches in IL, IN Stromquist and Company 460 tlanta Rd. Smyrna, G 0080 Phone: With branch in FL Temperature Control Systems 05 rockwood Road Dallas, TX 758 Phone: With branches in TX - Temperature Controls-Dallas, Climate Control Systems, ustin Controls and OK - Tulsa Controls Tower Equipment Co., Inc. 0 West road Street Stratford, CT 0665 Phone: Twinco Supply Corporation 55 Craven Street Huntington Station, NY Phone: With branches in NY CND irex C - 5 Sandhill Crt. rampton, ON, L6T 5J5 Phone: aymar Supply Co. 00 Jefferson lvd. Windsor, ON N8T W8 Phone: Controls Depot #05 50 Thurston Drive Ottawa, ON KG 5T9 Phone: With branches in Scarborough, ON Cypress Sales 65 Wentz ve. Saskatoon, SK, S7K 5J Phone: With branches in Regina O Dell ssociates Inc. # - 08 Cooke lvd. urlington, ON L7T 48 Phone: Prokontrol 989 Michelin Laval, QC, H7L 57 Phone: With branches in Ville Vanier and Ontario Refrigerative Supply 958 Myrtle Street, urnaby, C, V5C 4G Phone: With branches in ritish Columbia, lberta, Saskatchewan,Manitoba Regal Controls 56 Kingsway Vancouver, C, V5V C8 Phone: With branch in Langley Regulvar Laval 985 oul Industriel Laval Q.C H7S-P6 Phone: With branches in Hull, Sherbrooke, St. Hubert, Lachine, Quebec City Regulvar Ottawa Inc. 70 Laurier x West Suite 74 Ottawa, Ontario, KP-5V6 Phone: Sinclair Supply Street Edmonton,, T5H P7 Phone: With branches in ritish Columbia, lberta, Saskatchewan Southern Supplies loor St. W Oshawa, ON, LJ 6X4 Phone: With branch in elleville SCI oul Industriel Laval, QC, H7L 4S Phone: Wiles & Legault #5-505 Industriel venue Ottawa, ON, KG 0Z Phone: Yorkland Controls 689 Steeles venue, W. Downsview, ON, MJ Z8 Phone: With branch in Mississauga For Latin merican distributors please call

140 Together to the Top elimo ircontrols (US), Inc. / Old Ridgebury Road 675 East Prater Way Danbury, CT 0680 Suite 0 Toll Free: (800) Sparks, NV 8944 (0) Toll Free: (800) Fax: (800) 8-88 (775) (800-CTUTE) Fax: (775) (0) (800) E. Thomas Street Inverness, FL 445 Toll Free: (888) (5) Fax: (5) (888) South Roselle Road Schaumburg, IL 609 Toll Free: (877) (847) Fax: (847) 5-44 (877) 8-66 elimo Worldwide elimo ircontrols serves customers throughout the United States, Canada, and Latin merica. It is part of elimo Holding, a publicly held company in Switzerland with business units in the mericas, Europe, and sia Pacific. elimo ircontrols (CN), Inc. 4/6 576 Coopers ve. Mississauga, Ontario L4Z E8 Toll Free: (866) (905) 7-8 Fax: (905) 7-4 elimo in Latin merica 50 E. Hallandale each lvd. Suite 80 Hallandale each, FL 009 (954) Fax: (954) elimo Servomoteur, Inc. 790 Chemin du Lac Longueuil, Québec J4N 8 Toll Free: (866) (450) Fax: (450) G049 0/05-0M-IG-Subject to change. elimo ircontrols (US), Inc.

B2 Series Characterized Control Valve, Spring Return Actuator

B2 Series Characterized Control Valve, Spring Return Actuator Series Characterized Control Valve, Spring ctuator Two-way Valve with Stainless Steel all and Stem, NPT Female Ends Service: Flow Characteristic: Media Temp Range: Maximum Differential: Pressure ( P) mbient

More information

P2050B050, 1/2, Pressure Independent Valve Chrome Plated Brass Ball and Brass Stem, NPT Female Ends

P2050B050, 1/2, Pressure Independent Valve Chrome Plated Brass Ball and Brass Stem, NPT Female Ends pplication The Pressure Independent haracterized ontrol Valve is typically used in air handling units on heating and cooling coils, and fan coil unit heating or cooling coils. Some other common applications

More information

B350L, 3-Way, Diverting Ball Valve Chrome Plated Brass Ball and Nickel Plated Brass Stem

B350L, 3-Way, Diverting Ball Valve Chrome Plated Brass Ball and Nickel Plated Brass Stem B350L, 3-Way, Diverting Ball Valve hrome Plated Brass Ball and Nickel Plated Brass Stem pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating

More information

B212, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem

B212, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem , -Way, haracterized ontrol Valve Stainless Steel all and Stem pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some

More information

GM24-MFT US. Proportional damper actuator, non-spring return, Multi-Function Technology

GM24-MFT US. Proportional damper actuator, non-spring return, Multi-Function Technology GM-MFT US Proportional damper actuator, non-spring return, Multi-Function Technology GM-MFT US Torque min. 0 in-lb Control to 0 VDC (DEFULT) Feedback to 0 VDC (DEFULT) pplication For proportional modulation

More information

P2050B005, 1/2, Pressure Independent Valve Chrome Plated Brass Ball and Brass Stem, NPT Female Ends

P2050B005, 1/2, Pressure Independent Valve Chrome Plated Brass Ball and Brass Stem, NPT Female Ends P2050005, 1/2, Pressure Independent Valve hrome Plated rass all and rass Stem, NPT emale nds pplication The Pressure Independent haracterized ontrol Valve is typically used in air handling units on heating

More information

B2150VB-055, 1-1/2, V Ball Control Valve Hardened Chrome Plated Carbon Steel Body, Stainless Steel Ball and Stem

B2150VB-055, 1-1/2, V Ball Control Valve Hardened Chrome Plated Carbon Steel Body, Stainless Steel Ball and Stem 50V-055, -/, V all ontrol Valve Hardened hrome Plated arbon Steel ody, Stainless Steel all and Stem Product eatures ast quarter turn open or closed operation, Stainless steel ball and stem, Positive shut-off,

More information

P2075B100-P, 3/4, Pressure Independent Valve Chrome Plated Brass Ball and Brass Stem, NPT Female Ends

P2075B100-P, 3/4, Pressure Independent Valve Chrome Plated Brass Ball and Brass Stem, NPT Female Ends P2075100-P, 3/4, Pressure Independent Valve hrome Plated rass all and rass Stem, NPT emale nds pplication The Pressure Independent haracterized ontrol Valve is typically used in air handling units on heating

More information

F780HD, 3, 3-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F780HD, 3, 3-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc F80HD, 3, 3-Way utterfly Valve Resilient Seat, 304 Stainless Steel Disc pplication Valve is designed for use in NSI flanged piping systems to meet the needs of bi-directional high flow HV hydronic applications

More information

2007 Technical Documentation Pressure Independent Characterized Control Valves (PICCV) Patented

2007 Technical Documentation Pressure Independent Characterized Control Valves (PICCV) Patented 2007 Technical Documentation Pressure Independent Characterized Control Valves (PICCV) Patented Effective December 2007 Table of Contents Control Valve Product Range...2 Valve /Actuator Selection At A

More information

B6400VB-350, 4, V Ball Control Valve Carbon Steel Body, Hardened Chrome Plated, Stainless Steel Ball and Stem

B6400VB-350, 4, V Ball Control Valve Carbon Steel Body, Hardened Chrome Plated, Stainless Steel Ball and Stem 6400V-350, 4, V all ontrol Valve arbon Steel ody, Hardened hrome Plated, Stainless Steel all and Stem Product eatures ast quarter turn open or closed operation, Stainless steel ball and stem, Positive

More information

F650HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F650HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc 650H, -Way utterfly Valve Resilient Seat, 304 Stainless Steel isc Product eatures 00 psi ( to ) and 50 psi (4 to 4 ) 0% leakage, Long stem design allows for insulation, Valve face-to-face dimensions comply

More information

B6400S-186, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem

B6400S-186, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem 6400S-86, 2-Way, haracterized ontrol Valve Stainless Steel all and Stem pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils.

More information

B250, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem

B250, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem 250, 2-ay, haracterized ontrol Valve Stainless Steel all and Stem pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils.

More information

Ball Valve Features and Benefi ts B2...VS / VSS and B3...L

Ball Valve Features and Benefi ts B2...VS / VSS and B3...L all Valve Features and enefi ts 2...VS / VSS and 3...L Tech.Doc - 07/17 - Subject to change. elimo ircontrols (US), Inc. 2-way and 3-way confi guration ronze with stainless steel trim (2-way) Nickel plated

More information

B240, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem

B240, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem 0, 2-ay, haracterized ontrol Valve Stainless Steel all and Stem pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some

More information

F6125HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F6125HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc 6125H, 2-Way utterfly Valve Resilient Seat, 304 Stainless Steel isc Product eatures 200 psi (2 to 12 ) and 150 psi (14 to 24 ) 0% leakage, Long stem design allows for 2 insulation, Valve face-to-face dimensions

More information

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc 6100H, 4, 2-Way utterfly Valve Resilient Seat, 304 Stainless Steel isc pplication Valve is designed for use in NSI flanged piping systems to meet the needs of bi-directional high flow HV hydronic applications

More information

F680HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F680HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc 680H, 2-Way utterfly Valve Resilient Seat, 304 Stainless Steel isc Product eatures 200 psi (2 to 12 ) and 150 psi (14 to 24 ) 0% leakage, Long stem design allows for 2 insulation, Valve face-to-face dimensions

More information

B2...VS Series, 2-way, Ball Valve Bronze Body, Stainless Steel Ball and Stem

B2...VS Series, 2-way, Ball Valve Bronze Body, Stainless Steel Ball and Stem 2...VS Series, 2-way, all Valve ronze ody, Stainless Steel all and Stem Live-load packing set Stainless steel ball & stem low-out proof stem design Technical Data Media chilled or hot water, glycol, #

More information

F6100HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F6100HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc 6100H, 2-Way utterfly Valve Resilient Seat, 304 Stainless Steel isc Product eatures 200 psi (2 to 12 ) and 150 psi (14 to 24 ) 0% leakage, Long stem design allows for 2 insulation, Valve face-to-face dimensions

More information

B6300VB-207, 3, V Ball Control Valve Carbon Steel Body, Hardened Chrome Plated, Stainless Steel Ball and Stem

B6300VB-207, 3, V Ball Control Valve Carbon Steel Body, Hardened Chrome Plated, Stainless Steel Ball and Stem 6300V-207, 3, V all ontrol Valve arbon Steel ody, Hardened hrome Plated, Stainless Steel all and Stem Product eatures ast quarter turn open or closed operation, Stainless steel ball and stem, Positive

More information

V Ball Control Valve Product Range

V Ball Control Valve Product Range V all ontrol Valve Product ange VSI all Valve Product ange...v, 6...V Type Suitable ctuators v Inches DN [mm] -way NPT Flange Spring eturn Electronic Fail-Safe Non-Spring eturn 4 1 5 00V-04 55 1½ 40 50V-055

More information

7000 Series Bronze Globe Valves Two-Way Normally Open

7000 Series Bronze Globe Valves Two-Way Normally Open 7000 Series Bronze Globe Valves Two-Way Normally Open / to in. Screwed NPT Two-Way Normally Open Spring Return Stem Up Open Globe Valves Two-Way Normally Open Assemblies Size in. / /4 Cv (K vs ) 0.4 (0.4).

More information

F6 Series 2-Way, Victaulic Butterfly Valve

F6 Series 2-Way, Victaulic Butterfly Valve F6 Series 2-Way, Victaulic Butterfly Valve 200 psi (2 to 12 ) bubble tight shut-off Long stem design allows for 2 insulation Completely assembled and tested, ready for installation Application These valves

More information

Spring Return DuraDrive Proportional Actuator

Spring Return DuraDrive Proportional Actuator MS40-7043, MS4-7073, MS4-753 Spring Return DuraDrive Proportional Actuator For spring return applications that require proportional modulation control of dampers and valves in HVAC systems. Features: Proportional

More information

Non-Spring Return EconoDrive Proportional Actuator

Non-Spring Return EconoDrive Proportional Actuator MSD-0x3 Series Non-Spring Return EconoDrive Actuator EconoDrive overshaft actuators are designed to provide an economical and reliable solution for many overshaft damper and ball valve requirements. All

More information

Wiring for Damper Actuators and Control Valves July 2011

Wiring for Damper Actuators and Control Valves July 2011 Wiring for Damper ctuators and Control Valves July 011 Wiring for Damper ctuators and Control Valves eneral Wiring Instructions WRNIN: The wiring technician must be trained and experienced with electronic

More information

3-Way Ball Valves. Overview. Applications. Features & Benefits. Datasheet

3-Way Ball Valves. Overview. Applications. Features & Benefits. Datasheet 3-Way Ball s Datasheet Overview 3-way Ball s are coupled with DA-Series Actuators to provide three-way mixing or diverting flow control. The ball valves are 1/4-turn rotary control valves and are available

More information

Non-Spring Return DuraDrive Modulating Actuator

Non-Spring Return DuraDrive Modulating Actuator MS41-60xx Series n-spring Return DuraDrive Modulating Actuator The DuraDrive direct coupled 24 Vac non-spring return rotary electric actuators are designed for modulating control of dampers. S41-60xx ries

More information

F6 VIC Butterfly Valves Way Ductile Iron Grooved End Body

F6 VIC Butterfly Valves Way Ductile Iron Grooved End Body 6 VI utterfly Valves 2 12 2-Way uctile Iron rooved nd ody psi (2 to 12 ) bubble tight shut-off Long stem design allows for 2 insulation ompletely assembled and tested, ready for installation pplication

More information

F6/F7...HD/HDU Series Butterfl y Valves

F6/F7...HD/HDU Series Butterfl y Valves 71150-00001. INSTLLTION N MINTENNE INSTRUTIONS F6/F7...H/HU Series utterfl y Valves F6 HU utterfly Valves 2 12 uctile Iron Lug ody Resilient Seat, 304 Stainless isc 50 psi bubble tight shut-off Long stem

More information

DCS-62 Series Spring Return Electronic Actuator Product Bulletin

DCS-62 Series Spring Return Electronic Actuator Product Bulletin Delta Control Products, Inc. 0 West Rose Garden Lane Phoenix, Z 807 6-780-08 DCS-6 Series Spring Return Electronic ctuator Product ulletin Description The Delta DCS-6 direct-coupled spring return electronic

More information

LM Series Direct Coupled Actuator

LM Series Direct Coupled Actuator LM Series Direct Coupled Actuator Small Yet Powerful Minimum in-lb torque in a compact package. For damper areas up to 8 sq-ft*. Quiet Plus VAV terminal unit by Warren Technology Areas of Application VAV

More information

4CONTROL VALVES CONTROL VALVES ULTRAFLO BUTTERFLY VALVES 522 SERIES NEW! H2X E2X KMSC-0 SPECIFICATIONS

4CONTROL VALVES CONTROL VALVES ULTRAFLO BUTTERFLY VALVES 522 SERIES NEW! H2X E2X KMSC-0 SPECIFICATIONS SERIES DESRIPTION The Series resilient seated butterfly valves are available in "-0" sizes. Economical and designed to meet todayʼs HV and industrial process requirements, they come standard with full

More information

ph or ORP Transmitter

ph or ORP Transmitter ph or ORP Transmitter Programmable outputs: two transistor and single or dual analog 4-20 ma (Process + Temp) Removable backlighted display Universal process connection Compatible with 120 mm ph/ ORP probes

More information

optional View the installation video for FGVL on Belimo's YouTube channel: 1https://youtu.be/fqs8XfRPyQw 32 mm 19 mm 20 Nm

optional View the installation video for FGVL on Belimo's YouTube channel: 1https://youtu.be/fqs8XfRPyQw 32 mm 19 mm 20 Nm 4-0000.B QUICK MOUNT VISUL INSTRUCTION MNUL FGVL Linkage with EV Series ctuators b STYLE mm optional /4 - UNF /4-3 UNEF 3 3/ - 4 UNF 05/6 - Subject to change. Belimo ircontrols (US), Inc. Optional /6-0

More information

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

Technical data. Safety notes.  T3-LR24A-SR en v Subject to changes 1 / 2 echnical data sheet LR4A-SR Modulating rotary actuator for and -way control ball valves orque Nm Nominal voltage AC/DC 4 V Control: Modulating DC... V Position feedback: DC... V echnical data Safety notes

More information

Functional data Factory settings Variable Settings

Functional data Factory settings Variable Settings echnical data sheet Rotary actuator RF-MF(-O) Multifunctional rotary actuator with emergency control for and 3 way control ball valve orque Nm Nominal voltage AC/DC V Control: Modulating DC... V or variable

More information

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing echnical data sheet Rotary actuator LR4A Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage AC/DC 4 V Control: Open/close or -point echnical data Electrical data Nominal voltage

More information

Value Valves USA. Electric Actuator DOUBLE ACTING SPRING RETURN.

Value Valves USA. Electric Actuator DOUBLE ACTING SPRING RETURN. Value Valves US Electric ctuator DOUBLE CTING SPRING RETURN www.bvcusa.com 01~02 VLUE VLVE U.S.. ELECTRIC CTUTORS QURTER-TURN ELECTRIC CTUTOR FETURES FETURES Enclosure: IP 67 (Nema 4, Nema 4X) waterproof

More information

Rotary gear motor series AG8...

Rotary gear motor series AG8... Rotary gear motor series AG8... The electric actuator belonging to AG8 series is designed to operate gas valves and air dampers in ventilation and air conditioning systems. The compact design and universal

More information

Technical Instructions Document No EA GQD June 23, OpenAir

Technical Instructions Document No EA GQD June 23, OpenAir OpenAir Spring Return, 20 lb-in (2 Nm), Rotary GQD Series, Electronic Damper Actuators Technical Instructions Document No. 155-760 EA GQD Description Features Application The OpenAir GQD Series direct-coupled

More information

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable echnical data sheet S--MF- Multifunctional rotary actuator for butterfly valves orque 00 Nm Nominal volta e V Control: ontrol configurable confi urable Position feedback: configurable Auxiliary u iliary

More information

FA-3300 Heavy Duty Electric Actuator. Features and Benefits. FA-3300 Actuator with VG8000 valve. Constant running time. Fixed close-off force.

FA-3300 Heavy Duty Electric Actuator. Features and Benefits. FA-3300 Actuator with VG8000 valve. Constant running time. Fixed close-off force. European Electronic Controls Catalogue Section E Product Bulletin FA-3300 Issue Date 0998 FA-3300 Heavy Duty Electric Actuator I ntroduction The FA-3300 series synchronous motor-driven, reversible, heavy

More information

2/2 way Proportional Valve (motordriven)

2/2 way Proportional Valve (motordriven) 2/2 way Proportional (motordriven) Actuator isolated from fl ow path Excellent range and fast response times Low power consumption Orifi ce sizes 8 to 25 mm Versions: Standard, positioner, process controller

More information

Provides line voltage capable single Pole Double-Throw (SPDT) switch and 140Ω, 1KΩ, 2KΩ or 10KΩ feedback potentiometric.

Provides line voltage capable single Pole Double-Throw (SPDT) switch and 140Ω, 1KΩ, 2KΩ or 10KΩ feedback potentiometric. VA9310 Non Spring Return Actuators Product Bulletin The VA9310 Series Electric Non Spring Return Actuators are used to provide accurate positioning on Johnson Controls VG1000 Series DN15 up to DN50 ball

More information

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator ANSI version Application Control valves designed for mechanical and plant engineering. Suitable for liquids, gases and steam

More information

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2 echnical data sheet Rotary actuator LRA Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage AC... 4 V Control: Open/close or -point echnical data Electrical data Nominal voltage

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement Digital flow ELEMENT transmitter for continuous flow measurement Type 8036 can be combined with... DN06 to DN65 fluidic process connection Programmable outputs : one or two transistor output(s) and single

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement ELEMENT Transmitter Digital flow ELEMENT transmitter for continuous flow measurement Type can be combined with... PN10, DN15 to DN400 fluidic process connection Programmable outputs : one or two transistor

More information

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series OpenAir GQD Series Spring Return, 20 lb-in (2 Nm), Rotary Electronic Damper Actuators Technical Instructions Document No. 155-760 EA GQD Description Features Application The OpenAir GQD Series direct-coupled

More information

Explosion proof rotary actuator - On/Off or programmable regulating actuator

Explosion proof rotary actuator - On/Off or programmable regulating actuator Explosion proof rotary actuator - On/Off or programmable regulating actuator Direct mounting for quarter-turn valves Manual override standard Corrosion resistant Adjustable limit switches Type 3004 can

More information

658 Current to Position Converters

658 Current to Position Converters 658 Current to Position Converters Current to Position Converters for Solid State Switching Output Adjustable Zero, Span and Deadband Two Wire Input from Controller Operates with 90 to 1000 Ω Feedback

More information

2/2-Way Solenoid Control Valve

2/2-Way Solenoid Control Valve 2/2-Way Solenoid Control Valve Excellent range (1:200) Very good response Compact valve design Orifice sizes 0.8... 4 mm Port connection 1/8, 1/4 or sub-base Type 2873 can be combined with Type 8605 Digital

More information

The transducer component converts the measured signal and displays the actual value.

The transducer component converts the measured signal and displays the actual value. Digital inductive conductivity transmitter System Integration Provides low Total Cost of Ownership PEEK/PPA version for CIP applications TEACH IN and SIMULATION Function Approval PVDF Version PEEK Version

More information

Digital flow transmitter for continuous flow measurement

Digital flow transmitter for continuous flow measurement Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:

More information

Overview of types. Technical data. T5-NRDVX24-SR-T-.. en v Subject to changes 1 / 3

Overview of types. Technical data.   T5-NRDVX24-SR-T-.. en v Subject to changes 1 / 3 echnical data sheet NRDVX4-SR--.. Modulating short stroke actuator for the motorisation of Cazzaniga and Siemens short stroke valves in HVAC systems Nominal stroke max. 5.5 mm Actuation force 500 Nm Nominal

More information

Power consumption In operation At rest For wire sizing. 150 s / C Sound power level Motor. Emergency setting function 61 db (A)

Power consumption In operation At rest For wire sizing. 150 s / C Sound power level Motor. Emergency setting function 61 db (A) echnical Data sheets GRK4A-SR-5 Modulating SuperCap rotary actuator with emergency setting function and extended functionalities for butterfly valves and ball valves with mounting flange ISO 511-F05 orque

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet LMA-MF-P Multifunctional damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx.

More information

Power consumption In operation At rest For wire sizing. Auxiliary switch NRF24A-SR-S2 NRF24A-SR-S2-O

Power consumption In operation At rest For wire sizing. Auxiliary switch NRF24A-SR-S2 NRF24A-SR-S2-O echnical data sheet NRF24A-SR-S2(-O) Modulating rotary actuator with emergency function for 2- and 3-way ball valves orque or ue 10 Nm Nominal voltage AC/DC 24 V Control: modulating DC 0... 10 V Position

More information

FEATURES OPTIONAL FEATURES

FEATURES OPTIONAL FEATURES -00--0 B Series The Assured Automation B Series electric valve actuators offer a rugged design for quarter turn industrial applications. Designed for use on quarter turn (0 ) ball valves, butterfly valves,

More information

VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service

VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service Product Bulletin Code No. LIT-977319 Issued September 26, 2014 The VA-9070 Series Electric Rotary Actuators for Two-Position

More information

Electric actuator for quarter-turn valves. For output torques to 17,700 lb. in.

Electric actuator for quarter-turn valves. For output torques to 17,700 lb. in. Electric actuator for quarter-turn valves. For output torques to 17,700 lb. in. Features Standard Standard actuator accepts 24 to 240 Volt DC or C single phase input, 50 and 60 Hz. Three phase is optional.

More information

FAS 10 mm PICOSOL Direct acting solenoid valve

FAS 10 mm PICOSOL Direct acting solenoid valve FS 0 mm PICOSOL > > /, /; Manifold mounting > > Long life 00 million cycles > > Compact Design > > Low power consumption Technical features Medium: ir, oxygen, neutral gases (0 %... 9 % humidity, non condensing),

More information

Electromagnetic Flow Transmitter

Electromagnetic Flow Transmitter Electromagnetic Flow Transmitter Sensor in solid state technology Working as a transmitter and/or as an On/Off controller Automatic-calibration of full scale: Teach-In Clean in place (CIP) Type can be

More information

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC echnical data sheet SMA-PC Parameterisable damper actuator for adjusting air dampers in ventilation and air-conditioning systems in buildings Air damper size up to approx. m orque 0 Nm Nominal voltage

More information

Posiflow Proportional Solenoid Valves % ^ ) 2/2. Brass or Stainless Steel Bodies 1/8" to 1/2" NPT. Proportional Valves. Features.

Posiflow Proportional Solenoid Valves % ^ ) 2/2. Brass or Stainless Steel Bodies 1/8 to 1/2 NPT. Proportional Valves. Features. 4 Posiflow Solenoid Brass or Stainless Steel Bodies 1/8" to 1/2" NPT 2/2 Features Flow rates adjustable between 0% and 100% of rating Control achieved by applying straight voltage between 0 and 24 VDC

More information

MODEL: MRP5. Final Control Elements. [2] TERMINAL BOX T: With

MODEL: MRP5. Final Control Elements. [2] TERMINAL BOX T: With Final Control Elements MINI-TOP ELECTRONIC ACTUATOR (rotary type) Functions & Features Small-size control valve actuator 1/1 high resolution Easy adjustment: electronic limiter at the valve open & closed

More information

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation Vmax low-n: Vmax for low-noise operation

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation Vmax low-n: Vmax for low-noise operation echnical data sheet EP..R-R6+BAC Characterised control valve with sensor-operated flow control, 6-way, Internal thread, PN 16 (EPIV) Nominal voltage AC/DC 24 V Control modulating, communicative wo sequences

More information

Conductivity Transmitter

Conductivity Transmitter Conductivity Transmitter Programmable outputs: two transistor and single or dual analog 4-20 ma Removable backlighted display Universal process connection Type can be combined with... Three cell constants

More information

Posiflow Proportional Solenoid Valves % ^ ) 2/2. Brass or Stainless Steel Bodies 1/4" to 1/2" NPT. Proportional Valves. Features.

Posiflow Proportional Solenoid Valves % ^ ) 2/2. Brass or Stainless Steel Bodies 1/4 to 1/2 NPT. Proportional Valves. Features. 4 Posiflow Solenoid Brass or Stainless Steel Bodies 1/4" to 1/2" NPT 2/2 Features Flow rates adjustable between 0% and 100% of rating Flow rate can also be regulated by a range of electrical inputs (sensors,

More information

MODEL: MRP6. Final Control Elements

MODEL: MRP6. Final Control Elements Final Control Elements MINI-TOP ELECTRONIC ACTUATOR (rotary type) Functions & Features Small-size control valve actuator Electrical positioner incorporated 1/1000 high resolution Easy adjustment: electronic

More information

SAT.. Electromotoric actuators for valves ACVATIX. with a 5.5 mm stroke and 300 N positioning force

SAT.. Electromotoric actuators for valves ACVATIX. with a 5.5 mm stroke and 300 N positioning force 4 584 ACVATIX Electromotoric actuators for valves SAT.. with a 5.5 mm stroke and 300 N positioning force SAT31.. Operating voltage AC 230 V, 3-position control signal SAT61.. Operating voltage AC/DC 24

More information

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke s 4 501 ACVATIX Electromotoric actuators for valves SAX.. with a 20 mm stroke SAX31.. Operating voltage AC 230 V, 3-position control signal Operating voltage AC/DC 24 V, control signal DC 0 10 V, 4 20

More information

LA-5000 SERIES LINEAR VALVE ACTUATORS

LA-5000 SERIES LINEAR VALVE ACTUATORS LA-5000 SERIES LINEAR VALVE ACTUATORS GENERAL DESCRIPTION The LA-5000 Series are bi-directional, linear actuators internally geared to produce up to 6,500 lbs. (28,913 N) of thrust, and offer continuous

More information

Technical data. T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC

Technical data.  T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC echnical data sheet SMASR Modulating damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. 4 m orque Nm

More information

MODEL: VOS-ER. [4] LEVER POSITION 1: Upper side 2: Lower side. Position Sensors

MODEL: VOS-ER. [4] LEVER POSITION 1: Upper side 2: Lower side. Position Sensors Position Sensors 2-WIRE POSITION TRANSMITTER (flameproof, rotary motion type) Functions & Features Differential transformer incorporated Light weight and compact design High resolution Zero & Span adjustable

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet GM4A-SR-P Modulating damper actuator for operating air control dampers in ventilation and airconditioning systems for building services installations For air dampers up to approx. 8

More information

SAX.. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

SAX.. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke s 4 501 ACVATIX Electromotoric actuators for valves SAX.. with a 20 mm stroke SAX31.. Operating voltage AC 230 V, 3-position control signal SAX61.. Operating voltage AC/DC 24 V, control signal DC 0 10

More information

Technical data. Parameterisable damper actuator in the

Technical data. Parameterisable damper actuator in the echnical data sheet Parameterisable damper actuator in the IP66 protective housing for or adjusting ad usting air dampers in industrial plants and in technical building installations For air dampers up

More information

Electric actuator for quarter-turn valves. For output torques to 17,700 lb. in.

Electric actuator for quarter-turn valves. For output torques to 17,700 lb. in. Electric actuator for quarter-turn valves. For output torques to 17,700 lb. in. Features Standard Standard actuator accepts 24 to 240 Volt DC or C single phase input, 50 and 60 Hz. Three phase is optional.

More information

2-way motor valve. Power consumption. Type 8746 MFC/MFM. Technical data Materials Body Housing Seals 1) Pressure Range 2) < 1 % FS Sensitivity Span

2-way motor valve. Power consumption. Type 8746 MFC/MFM. Technical data Materials Body Housing Seals 1) Pressure Range 2) < 1 % FS Sensitivity Span 2-way motor valve Actuator isolated from flow path Excellent range and fast response times Low power consumption Orifice sizes 1 to 10 mm Versions: Standard, positioner, process controller and high pressure

More information

.1 Materials and installation for steel piping, valves and fittings for hydronic systems in building services piping..2 Related Sections.

.1 Materials and installation for steel piping, valves and fittings for hydronic systems in building services piping..2 Related Sections. Issued 2006/08/01 Section 15183 Hydronic Systems: Steel Page 1 of 6 PART 1 GENERAL 1.1 SUMMARY.1 Section Includes..1 Materials and installation for steel piping, valves and fittings for hydronic systems

More information

Technical data. Safety notes. Power consumption In operation At rest For wire sizing

Technical data. Safety notes. Power consumption In operation At rest For wire sizing echnical data sheet Damper actuator NM4A-SR-P Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations For air control dampers up

More information

Type 3374 Electric Actuator

Type 3374 Electric Actuator Type 3374 Electric Actuator Application Electric actuator for plant engineering and HVAC The actuator is a linear actuator with or without fail-safe action available either in a version with a three-step

More information

Type overview. Technical data

Type overview. Technical data echnical data sheet P..W..EV-BAC Characterised control valve (CCV) with adjustable flow rate and sensor-operated flow control, as well as power and energy-monitoring function, 2-way, with flange PN For

More information

Electro-Magnetic Flowmeters COPA-XE

Electro-Magnetic Flowmeters COPA-XE Data Sheet Electro-Magnetic Flowmeters COPA-XE 10DX4311 Flowmeter system utilizes a smart microprocessor converter System accuracy of ± 0.5% of rate Field configurable via integral pushbuttons, eliminates

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke s 4 501 ACVATIX Electromotoric actuators for valves SAX.. with a 20 mm stroke SAX31.. Operating voltage AC 230 V, 3-position control signal SAX61.. Operating voltage AC/DC 24 V, control signal DC 0 10

More information

IP26 Series Current to Pneumatic Converter

IP26 Series Current to Pneumatic Converter Product Specifications 06.2016 PSS EVE0403 A-(en) IP26 Series Current to Pneumatic Converter The IP26 (current to pressure) transducer converts a 4 20mA electrical current signal to a proportional linear

More information

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return echnical data sheet SF24A- Communicative spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx.

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 048 RCU15 Room Temperature Controllers for heating and cooling systems RCU15 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Control depending on room-

More information

AE SERIES ACTUATORS. Electric Actuators. Standard Voltages 110/240/380/480V 24VAC/24VDC. Modulating Capable. 100% Duty Cycle Models Fast Acting Models

AE SERIES ACTUATORS. Electric Actuators. Standard Voltages 110/240/380/480V 24VAC/24VDC. Modulating Capable. 100% Duty Cycle Models Fast Acting Models AE SERIES ACTUATORS Electric Actuators Standard Voltages 110/240/380/480V 24/24VDC Modulating Capable 100% Duty Cycle Models Fast Acting Models Max-Air Technology, Inc. 751 Hoff Rd O Fallon, Missouri 63366

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GR24A--R Communicative Retrofit rotary actuator for rotary valves and butterfly valves Nominal torque 40 Nm Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Position

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet SMA--P Multifunctional damper actuator for adjusting air dampers in ventilation and air-conditioning systems for building services installations For air dampers up to approx. m orque

More information

Grundfos Direct Sensor

Grundfos Direct Sensor GRUNDFOS DT OOKLET Grundfos Direct Sensor sensors Grundfos Direct Sensor Table of contents 1. Product introduction 3 Type key 4 2. Relative- sensor, Industry (RPI) 5 RPI / RPI +T general data 5 RPI, 0-0.6

More information

Contents. ensure product integrity and each product manufactured undergoes rigorous testing to guarantee its performance and dependability.

Contents. ensure product integrity and each product manufactured undergoes rigorous testing to guarantee its performance and dependability. Contents More than a quarter of a century s manufacturing experience has gone into every product that carries the Neptronic name. From inspiration to realization, innovation has been the standard in design.

More information

CHINA ZHEJIANG ZHONGGONG VALVE GROUP CO,.LTD FORMEN VALVE

CHINA ZHEJIANG ZHONGGONG VALVE GROUP CO,.LTD FORMEN VALVE INTERNATIONAL SALES: FORMEN VALVE ADD: OUBEI TOWN, YONGJIA COUNTY, WENZHOU, ZHEJIANG, CHINA HEADQUARTER: ZHEJIANG ZHONGGONG VALVE GROUP ADD: WUXING INDUSTRY ZONE, OUBEI TOWN, WENZHOU, CHINA ABOUT US Formen

More information

SENSORS. Seamlessly Integrated SENSORS

SENSORS. Seamlessly Integrated SENSORS 20 Seamlessly Integrated Innovative technology to work seamlessly with all leading control companies ensuring performance. Reliable and accurate readings providing energy and cost-effi cient control backed

More information