USING OVER-DAMPING METHOD TO SUPPRESS THE FERRO-RESONANCE OF POTENTIAL TRANSFORMER

Size: px
Start display at page:

Download "USING OVER-DAMPING METHOD TO SUPPRESS THE FERRO-RESONANCE OF POTENTIAL TRANSFORMER"

Transcription

1 USING OVER-DAMPING METHOD TO SUPPRESS THE FERRO-RESONANCE OF POTENTIAL TRANSFORMER Lai Tianjiang, Lai Tianyu, Lai Qingbo Dalian Electric Power Company, China 1 Forward In power system, the phenomenon of Ferro-resonance caused by the non-linearity of electro-magnetic potential transformer (PT) may be classified into two categories according to the dissimilarity of physical model of the resonance network: One category is in neutral isolated kv distribution network, which is caused by a set of or several sets of PT together with the capacitance of network to ground, another category is on the HV idle bus bar of kV substations, i.e. the series resonance caused by a set of or several sets of equalizing capacitances of circuit breakers together with the bus bar PT (usually one set), the resonance weave is only restricted within the range of the bus bar in substation. This paper refers to the former as network resonance, and the latter as substation resonance. Essentially speaking, Ferro-resonance is caused by the non-linearity of PT, while the casualty is also of itself. If, however, explosion is resulted from damage of PT, then it is liable to endanger the safety of adjacent equipments, even induce more series aftereffect of system fault. Therefore, suppression of Ferro-resonance has become one of the tasks for global prevalent attention. There are manifold measures for suppressing Ferro-resonance, among which the damping method is the simplest one, traditional practice is to connect a resistance across two terminals of the secondary winding of every PT or across the open delta which is composed of the tertiary winding of 3 single-phase PTs. But practically, it is not allowed to do so due to restriction of thermal capacity of PT. N. Janssens etc [1] put forward an improved scheme, i.e. to connect a damping resistance (several kw) and a saturable reactor in series into the secondary side of PT to suppress the substation resonance; C. Stuckens etc also recommended to connect a resistance and a saturable reactor in series into the open delta of PT to suppress the network resonance. The damping performance of the resistance is thus improved after it is connected in series with a saturable reactor, under normal operation condition, non-saturated reactor has high-resistance characteristic, which may mitigate the influence of damping resistance against the accuracy of PT measurements. When resonance appears, the reactor reaches saturation prior to the PT so as to get the resonance suppressed. This kind of damping method with series reactor expands the applicable range of resistance damping method. But the practical effect of this improvement is still limited, unable to solve all problems, especially for the network of smaller critical damping resistance, it is still helpless. That is because the non-linearity of the reactor is impossible to reach idealization.(i.e. the reactance tends to infinite under normal operation, and zero when resonance appears). This paper introduces the strong damping method on the basis of power electronic technique. The basic practice is: to install a thyristor (SCR) of switching characteristic and a low resistance in series across the terminals of PT open delta. Normally, the SCR is in blocking state, isolates the damping circuit from PT to avoid any influence of low resistance to the accuracy of measurements. When resonance occurs, SCR is triggered to be conducting, and then the low resistance plays its strong damping role. This controllable strong damping method was put forward by one of the authors first in 1979 and successfully applied in the development of network resonance-suppression device (WX type) and DLP_TJLai_A1 Session 1 Paper No

2 substation resonance- suppression device (BX type, see Fig. 1) thereafter. Over the past two decades, the above devices are increasingly perfected through many times of improvements. The thought-way for every improvement is based on the information from on-site tests. We have carried out more than 80 times of tests in network and more than 30 tests in substations. At present there are several thousand of WX type and several hundred of BX devices under operation in power system. BX see Fig 2, Fig 3 respectively. We have accumulated many experiences from field test and operation, what caused us pleasantly surprised is that We accidentally found: when resonance appears on the idle bus bar of 110/220 kv Substation, the voltage of resonant phase is not an isolated one, it produces serious effect on the other phases through capacitance coupling between phases. If two phases or three phases appear resonance at the same time, then the mutual influence will be more intricate and complicate. Over many years, people always attribute the substation ferro-resonance to physical model of independent single-phase resonance, R. Gandre etc [1] and [3]. The new discovery of electric field coupling between phases challenges the traditional physical model of single-phase resonance. This paper shows in detail such influence by the oscillogram recorded on site and presents a new sort of single-phase resonance model, which takes the influence between phases into account. Fig.2 Block diagram of hardware circuit of WX type of resonance-suppression device Fig.3 Block diagram of hardware of BX type device 2.1 Connection-in of damping circuit Fig 1 BX type of s/s resonance suppressing device. 2 Design consideration of hardware circuit of the device For block diagram of hardware circuit of WX and Damping circuit of both devices is connected to the two terminals of open delta of PT. For BX type of device two additional auxiliary wires are needed, as shown in Fig.3 by dotted lines, so as to meet the requirement of split-phase damping. This connection method may obviously increase the damping effect as compared with the traditional one that is connected to the PT secondary side (three times increase). DLP_TJLai_A1 Session 1 Paper No

3 2.2 Selection of damping resistor The connecting cable between tertiary winding of PT and this device acts concurrently as a damping resistor, therefore no more dedicated damping resistor will be installed in the device. Under certain special occasion, if the resistance of the above connecting cable still cannot meet the requirement of the resistance of network or bus bar whereabouts, then resistance-reduction measure should be taken to the cable. artificial single-phase ground fault. Altogether 23 times of excitation operations were conducted, among which 16 operations excited stable 1/2 sub-harmonic resonance. The probability of occurrence of resonance is 70%. Whenever resonance occurs, the device always can operate to eliminate them. Fig. 4 reflexes the different results under different value of damping resistances. 3 Test of WX type of device in network In 1981, more than 50 times of resonance-suppression tests were carried out in 10kV networks of Tieling old city, Liaoyang Lighthouse etc. Considering that the higher is the network voltage level, stricter is the requirement of damping resistance value; therefore, in order to strictly check the function of the device, in 1982, the 66kV Tieling network was once more selected for performing another 20 resonance-suppression tests. The purpose of these tests is: understanding the probability of resonance generated by excitation. Checking the validity of WX type device for resonance suppression. Seeking for the critical resistance of network. (b) (a) The neutral point of network is originally grounded through arc-suppression coil, in order to carry out Ferro- resonance test, all arc-suppression coils were taken out of service temporally. The tested networks have the following main parameters: capacitive current to ground 28A altogether 6 sets of PTs Ratio of capacitance to ground to reactance of PT X CO /X L =0.023 In order to facilitate estimation of critical resistance of network, only one set of PT open delta was installed with WX device, other 5 sets of PTs were without any damping means. The mode of resonance excitation: using pre-determined circuit breaker to switch off the (c) Fig 4 Different effects result in suppressing 1/2 sub- harmonic resonance with different damping resistance (a) R Z =0.197Ω, resonance cleared by damping 0.1s after connection of R Z (b) Rz=0.247Ω, resonance cleared by damping 0.26s after connection of Rz (c) Rz=0.377Ω,damping invalid Where, Ua, Ub, Uc are secondary phase voltage of PT; U is open delta voltage, I is the current when SCR is conducting. From Fig.4 it can also estimate the critical resistance DLP_TJLai_A1 Session 1 Paper No

4 of that network is about 0.247, if the device is installed indoor, then the connecting cable between the device and PT open delta may be too long, then it is very difficult to meet the requirement of resistance value. If,however, the damping means are adopted at 3 sets or 6 sets of PTs in the same time, then the critical damping resistance sensed by each set of PT can increase to 0.741Ω or 1.48Ω. 4 Test of BX device in substation Tests of resonance-suppression were carried out in three 220kV substations of Diaobingshan, Liaoyang and Ganxi, and four 110kV substations of Ganxi, Fuding, Lufeng, Tangshan one after another. The main purpose of test in early stage was to check whether the device could reliably suppress the resonance of a specified substation. I.e. to check the pertinence and validity of the device; the purpose of the test in recent years since 1993 is to lay particular attention to check whether the device, after many years improvement, has the function of suppressing resonance of all substations. I.e. to check its universal validity. There are many unexpected problems happened in field tests, which forced us to modify the technical scheme for resonance-suppression, and the hardware circuit and software are correspondingly modified along with. The tested circuit breakers, whether they are of 110kV or 220 kv, are all with double breaks; unit capacitance of the equipotential capacitor is about 1800 PF. Except in Liaoyang substation the bus bar is connected to power source through two sets of circuit breakers, the other are all through one set of circuit breaker. Resonance excitation mode: to switch off the last circuit breaker, which is connected with the idle bus bar. 4.1 Test of 220kV substation Liaoyang substation: On Nov. 15, 1993, 10 times of opening operation were conducted, among which 6 times of operations initiated stable resonance. Mainly basic frequency resonance, 1/3 sub-harmonic resonance second. And these two resonance weaves often present interactively. Fig 5 is the oscillogram recorded during opening of the circuit breaker. It shows: After opening, Both phase A and B present 1/3 sub-harmonic resonance at the same time, about 2 cycles later, transit to basic frequency resonance simultaneously. Under strong damping of the device, resonance weaves of phase B is quickly eliminated, that of phase A is eliminated gradually after a longer time too. Fig 5 Two-phase basic frequency resonance, Liaoyang 500kV substation Mengda power plant substation: On April 18, 2002, altogether 2 times of opening operation were conducted, stable basic frequency resonance was initiated on phase A and B one after another during second time of opening, and vanished successively under strong damping of the device. (See fig 6) Fig. 6 Suppressing phase A and B basic frequency resonance, Mengda power plant substation 4.2 Typical oscillogram of 110kV substation test Fig 7 Successively suppressing phase A and C basic frequency resonance, Ganxi Shangzhuang substation, June 1,2000 Fig. 8 The course of excitation of 3-phase basic DLP_TJLai_A1 Session 1 Paper No

5 frequency resonance, Ganxi Shangzhuang substation, Dec. 3, 2001 Fig.9 Fig. 9 The course of 3-phase basic frequency resonance Being damped, Lufeng Nantang substation, Jan. 6, 2002/12/29 Fig 10 the course of excitation and damping of 3-phase 1/3 sub-harmonic resonance, and variation of each harmonic content during the course. Tangshan power plant central substation. Nov. 28, Fig Discussion In the resonance test of substation, some problems were found worth discussing: Fig. 7 Fig. 8 1) Viewing the physical model of single-phase resonance from the influence between phases. It can be seen from Fig.7, after 0s opening 0f circuit breaker, basic frequency resonance presented on phases A, C successively. At the time of 0.27s, the device started up to implement damping over phase A. Along with attenuation of resonance voltage on phase A, the peak value of resonance voltage on phase C dropped from 100V to 68.9V, voltage weave of phase B changed along with. The phase voltage, after reduction of amplitude, conversely influences phase A, the resonance of which had just been damped, and the adjacent phase B. At the time of 0.5s, phase B was damped, the above influence became unstable and variable along with, up to 0.93s the resonance was eliminated. It can be seen from this course, the two resonant phases A, C generated strong mutual influence through coupling of spatial capacitance, and they also influenced the non-resonant phase B at the same time. So that we have reason to doubt the preciseness of the physical model for traditional substation single-phase resonance (Fig.11). We consider that the single-resonance model should be as shown in Fig.12 after considering the influence between phases. DLP_TJLai_A1 Session 1 Paper No

6 power system caused by PT. 2) Due to that the device makes use of the external connecting cable as damping element concurrently, the damping strength is enhanced to the greatest limit. In practical application, it fully uses this characteristic: Fig.11 Traditional physical model of single-phase resonance For the 10kV network with higher critical damping resistance, generally it only needs to install WX device on one or two PTs, to save the expenses. C A For 35kV network, generally one piece of WX device may be installed on every 2 or 3 sets of PTs. C A C B Fig. 12 Physical model of Single-phase resonance after considering influence between phases 2) Under general condition, the amplitude of resonance has something to do with the basic frequency, the higher the frequency, the higher the amplitude and vice versa, For example, the amplitude of basic frequency resonance weave is obviously higher than that of power supply voltage, the amplitude of 1/3 harmonic resonance weave is obviously lower than that of power supply voltage, This basic rule has been proved by many tests. But there is exception anyhow, such as shown in Fig.7, the amplitude of phase C is less than 0.8 P U during the interval from 0.27s to 0.5s, obviously lower than system phase voltage, for this further research is needed. 5 Conclusion 1) The strong damping method on the base of power-electronic technique has the unique effect of suppressing ferro-resonance. In principle, it can suppress all of the ferro-resonance phenomenon in On 220kV idle bus bar, if there are multi-sets of circuit breakers equipped with equalizing capacitance connected to the bus bar, then the critical damping resistance may be about 1 Ω. This moment, if the resistance value of the external connecting cable is too high, it will be likely to influence the damping effect. Substation resonance presents as a phenomenon of single-phase resonance. Therefore, the traditional physical model of single-phase resonance is the core. But only when the mutual influence between phases is taken into consideration, will the model further accord with the practical condition. That is to say, the electric field should be introduced into the model on the basis of electric circuit. References: 1 N.Janssens, V. Vanderstockt, H. Denoel, P.A.Monfils, 1990, Elimination of temporary over voltage due to ferroresonance of voltage transformers: design and testing of a damping system, CIGRE 1990 Paper C. Stuckens, P.A. Monfils, N.Janssens, TH. Van Craenenbroeck, D. Van Dommelen, 1997, Risk of ferroresonance in isolated neutral networks and remedies, CIRED 1997, Paper DLP_TJLai_A1 Session 1 Paper No

7 3 R.G.Andrei, P.E.B.R.Halley, P.E.: Voltage transformer ferroresonance from an energy transfer standpoint, IEEE 89WM PWRD 4 CIGRE 1990, Paper The origin, effect and estimation of transient overvoltage. 5 Gao Qiang, Lai Tianyu, Lai Qingbo, 1997, Study on features of ferromagnetic resonance of 110kV substation and its eliminating method, CIRED 1997, Paper DLP_TJLai_A1 Session 1 Paper No

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Grounding System Theory and Practice

Grounding System Theory and Practice Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems

More information

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS Seminar / Workshop on Controlled Switching Possible Benefits for Transformers Applications PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS Esteban Portales Yvon Filion André Mercier

More information

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions PQ20 June 16-18, 2010 Kuressaare Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions A. Shirkovets, A. Vasilyeva, A. Telegin LLC BOLID, Novosibirsk, Russia

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

Parameter Study of Ferro-Resonance with Harmonic Balance Method

Parameter Study of Ferro-Resonance with Harmonic Balance Method Parameter Study of Ferro-Resonance with Harmonic Balance Method ALI ERBAY Degree project in Electric Power Systems Second Level, Stockholm, Sweden 2012 XR-EE-ES 2012:010 PARAMETER STUDY OF FERRO RESONANCE

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

Ironing out resonance

Ironing out resonance Ironing out resonance Ferroresonance prevention in MV voltage transformers Wojciech Piasecki, Marek Florkowski, Marek Fulczyk, Pentti Mahonen, Mariusz Luto, Wieslaw Nowak, Otto Preiss Every engineer knows

More information

The Advantages and Application of Three Winding Transformers

The Advantages and Application of Three Winding Transformers The Advantages and Application of Three Winding Transformers MSc, CEng, FIEE, FIMechE, FIPENZ Principal, Sinclair Knight Merz Abstract Although seldom used in Australia and New Zealand, three winding transformers

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor Module 2 : Current and Voltage Transformers Lecture 8 : Introduction to VT Objectives In this lecture we will learn the following: Derive the equivalent circuit of a CCVT. Application of CCVT in power

More information

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid 5th International Conference on Computer Sciences and Automation Engineering (ICCSAE 2015) Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault

More information

Simulation and Analysis of Ferroresonance in Power System

Simulation and Analysis of Ferroresonance in Power System Simulation and Analysis of Ferroresonance in Power System Mitra Patel 1, Manish N Sinha 2 P.G. Student, Department of Electrical Engineering, BVM Engineering College, V.V.Nagar, Gujarat, India 1 Assistant

More information

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir

More information

Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers

Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers I Gusti Ngurah Satriyadi Hernanda, I Made Yulistya Negara, Adi Soeprijanto, Dimas Anton Asfani, Mochammad

More information

Power Transmission of AC-DC Supply in a Single Composite Conductor

Power Transmission of AC-DC Supply in a Single Composite Conductor IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 03 August 2015 ISSN (online): 2349-6010 Power Transmission of AC-DC Supply in a Single Composite Conductor P.

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

High Voltage DC Transmission 2

High Voltage DC Transmission 2 High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

SRI VIDYA COLLEGE OF ENGG AND TECH

SRI VIDYA COLLEGE OF ENGG AND TECH EEE6603 PSOC Page 1 UNIT-III REACTIVE POWER VOLTAGE CONTROL 1. List the various components of AVR loop? The components of automatic voltage regulator loop are exciter, comparator, amplifier, rectifier

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

Current limiting characteristic of saturated iron core SFCLs

Current limiting characteristic of saturated iron core SFCLs Journal of Physics: Conference Series Current limiting characteristic of saturated iron core SFCLs To cite this article: W Z Gong et al 2010 J. Phys.: Conf. Ser. 234 032016 Related content - Development

More information

DC current interruption tests with HV mechanical DC circuit breaker

DC current interruption tests with HV mechanical DC circuit breaker http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit

More information

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

DEPARTMENT OF EEE QUESTION BANK

DEPARTMENT OF EEE QUESTION BANK DEPARTMENT OF EEE QUESTION BANK (As Per AUT 2008 REGULATION) SUB CODE: EE1004 SUB NAME: POWER SYSTEM TRANSIENTS YEAR : IV SEM : VIII PREPARED BY J.S. MEGAVATHI AP/EEE UNIT-I SWITCHING TRANSIENTS 1.What

More information

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks by Alex Baitch FIEAust, CPEng Manager Network Capability, Integral Energy This paper was presented to the Annual Conference

More information

Insulation Level and Test Technology of. 1000kV Power Transformer

Insulation Level and Test Technology of. 1000kV Power Transformer Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC

More information

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:

More information

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation

More information

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)

More information

Do Capacitor Switching Transients Still Cause Problems?

Do Capacitor Switching Transients Still Cause Problems? Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution

More information

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453 www.ijecs.in International Journal Of Engineering And Computer Science ISSN:2319-7242 Volume 3 Issue 6 June, 2014 Page No. 6453-6457 Role of Fault Current Limiter in Power System Network Poornima G P.1,

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, Volume 8, Issue 6 (September 2013), PP.35-39 A Reduction of harmonics at the Interface of Distribution

More information

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS A. Nikander*, P. Järventausta* *Tampere University of Technology, Finland, ari.nikander@tut.fi,

More information

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 97 RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS Pengfei WEI Yonghai XU Yapen WU Chenyi

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

System grounding of wind farm medium voltage cable grids

System grounding of wind farm medium voltage cable grids Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007

More information

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems WHITE PAPER Medium Voltage On-Site Generation Overview BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems INTRODUCTION It seems that just about everyone is looking for more power. As our

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

RESONANT TRANSFORMER

RESONANT TRANSFORMER RESONANT TRANSFORMER Whenever the requirement of the test voltage is too much high, a single unit transformer can not produce such high voltage very economically, because for high voltage measurement,

More information

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH Michael Freiburg Erik Sperling Michael Krueger OMICRON Austria

More information

How adjustable speed drives affect power distribution

How adjustable speed drives affect power distribution How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually

More information

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900 Coil Products Coil Products Customer partnership around the globe More than 250,000 coil products delivered to more than 170 countries. More than 60 years of operational experience. 35,000 in Europe 13,000

More information

Abstract- At the time of transformer energization, a high current will be drawn by the transformer. The mentioned current

Abstract- At the time of transformer energization, a high current will be drawn by the transformer. The mentioned current A Case Study of Reduction of Single-Phase Transformer Magnetizing Inrush Current Kunal Wakode 1,Shaikh Sabir 2, Nishant Adhau 3, Abuzar Khan 4, Prof. P. B. Shelke 5 Department of Electrical Engineering

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

AGN 124 AVR Power Supplies

AGN 124 AVR Power Supplies Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 124 AVR Power Supplies DESCRIPTION The simplest way to provide a power supply for an AVR is to take power directly

More information

Great Northern Transmission Line: Behind the (Electrical) Design

Great Northern Transmission Line: Behind the (Electrical) Design Great Northern Transmission Line: Behind the (Electrical) Design November 8, 2017 Christian Winter, P.E. Minnesota Power Sivasis Panigrahi, P.E. POWER Engineers, Inc. What is the Great Northern Transmission

More information

IOCL Electrical Engineering Technical Paper

IOCL Electrical Engineering Technical Paper IOCL Electrical Engineering Technical Paper 1. Which one of the following statements is NOT TRUE for a continuous time causal and stable LTI system? (A) All the poles of the system must lie on the left

More information

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T. Aalborg Universitet Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T. Published in: Proceedings of the Danish PhD Seminar on Detailed

More information

AGN 124 AVR Power Supplies

AGN 124 AVR Power Supplies Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 124 AVR Power Supplies DESCRIPTION The simplest way to provide a power supply for an AVR is to take power directly

More information

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter 1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

Overvoltage and undervoltage. Dr Audih 1

Overvoltage and undervoltage. Dr Audih 1 Overvoltage and undervoltage Dr Audih 1 A Overvoltage is defined as an increase in the r.m.s. value of the voltage up to a level between 1.1 pu to 1.8 pu at power frequency for periods ranging from a half

More information

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur Module No. # 01 Lecture No. # 02 Comparison of HVAC and HVDC Systems Welcome

More information

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks Mohammad Tavakoli Bina, G.N.Alexandrov and Mohammad Golkhah Abstract A new shunt reactive power compensator,

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

FORM 2 THE PATENTS ACT, (39 of 1970) & The Patent Rules, 2003 COMPLETE SPECIFICATION

FORM 2 THE PATENTS ACT, (39 of 1970) & The Patent Rules, 2003 COMPLETE SPECIFICATION FORM 2 THE PATENTS ACT, 1970 (39 of 1970) & The Patent Rules, 2003 COMPLETE SPECIFICATION 1. TITLE OF THE INVENTION: CURRENT TRANSFORMER 2. APPLICANTS: Name: SEARI ELECTRIC TECHNOLOGY CO., LTD. Nationality:

More information

The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10 kv Power Grid

The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10 kv Power Grid Energy and Power Engineering, 2013, 5, 897-901 doi:10.4236/epe.2013.54b172 Published Online July 2013 (http://www.scirp.org/journal/epe) The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10

More information

Fault Current Limiter Selection Considerations for Utility Engineers

Fault Current Limiter Selection Considerations for Utility Engineers 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http: //www.cigre.org 2014 Grid of the Future Symposium Fault Current Limiter Selection Considerations for Utility Engineers K. TEKLETSADIK,

More information

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Application of SVCs to Satisfy Reactive Power Needs of Power Systems 1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

Chapter 16: Mutual Inductance

Chapter 16: Mutual Inductance Chapter 16: Mutual Inductance Instructor: Jean-François MILLITHALER http://faculty.uml.edu/jeanfrancois_millithaler/funelec/spring2017 Slide 1 Mutual Inductance When two coils are placed close to each

More information

Transient Recovery Voltage at Transformer Limited Fault Clearing

Transient Recovery Voltage at Transformer Limited Fault Clearing Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H.

More information

Short-Circuit Apparent Power of System Survey Comments

Short-Circuit Apparent Power of System Survey Comments WG Item 87 Short-Circuit Apparent Power of System Survey Comments Again, the values given in Table 18 are totally unrealistic of system conditions. I do not know any systems for which the short-circuit

More information

IMPORTANCE OF VSC IN HVDC

IMPORTANCE OF VSC IN HVDC IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM Dolly Chouhan 1, Kasongo Hyacinthe Kapumpa 2, Ajay Chouhan 3 1 M. Tech. Scholar, 2

More information

Analysis of a 405 km transmission line with series compensation

Analysis of a 405 km transmission line with series compensation Analysis of a 405 km transmission line with series compensation by Dr. Rupert Gouws, North-West University This paper presents an investigative case study and energy efficiency analysis of the 405 km,

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Power Systems Modelling and Fault Analysis

Power Systems Modelling and Fault Analysis Power Systems Modelling and Fault Analysis Theory and Practice Nasser D. Tleis BSc, MSc, PhD, CEng, FIEE AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD PARIS SAN DIEGO SAN FRANCISCO SINGAPORE SYDNEY

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

HVDC High Voltage Direct Current

HVDC High Voltage Direct Current HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the

More information

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Demagnetization of Power Transformers Following a DC Resistance Testing

Demagnetization of Power Transformers Following a DC Resistance Testing Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.

More information