Electricity Tariffs for Voltage-dependent Loads
|
|
- Rosemary Cobb
- 6 years ago
- Views:
Transcription
1 Electricity Tariffs for Voltage-dependent Loads Authors: Prof C. S. Indulkar and Dr K. Ramalingam Presenter : Dr K. Ramalingam
2 Abstract These days the regulators specify that the tariff report should include: The distribution and transmission tariffs charged by the supply companies; The tariff principles adopted in framing the structures and level of the tariffs; The basis on which the appropriate breakdown is determined between fixed and variable charges; The rationale for the introduction of new and the withdrawal of old tariffs; and The methodology adopted for allocating transmissionrelated costs to customers through its transmission tariffs.
3 Supply companies usually adopt the following \ tariff structures: General Purpose single rate tariff applicable for all times of the day with a fixed charge, for customers that consume small amounts of electricity, such as residential customers and farms; Time of Use two- rate tariff applicable to peak and offpeak periods with a standing charge,applicable to Residential and Small Business customers; Time of Use Demand two- rate tariff applicable to peak and off-peak periods, a demand charge (Rs/kW ) and a fixed charge.- for Large Business and Small Business customers
4 Factors influencing the energy structure are the time of the day, the power factor, and the fuel price.. In present times, because of all-pervading computerization in electricity billing, privatization, and availability of distribution companies consumer can choose the supply company Different tariffs are essential so that each consumer should pay a fair share of the costs. Different types of load should have different forms of tariff. The bulk tariff for supplies at 132, 220 or 400 kv comprises a fixed charge to cover peak and base load charges, and appropriate running charges for peak load and other periods.
5 There are still unsolved questions with regard to electricity billing at different voltage levels. There is a need to ascertain the relative benefits and economic gains from the utility company perspective as well as from the consumer s viewpoint in the billing charges considering a range of, say, + 10%. It is necessary to know the effects of constant power loads, constant current loads, constant impedance loads and mixed loads on the billing charges. The supply company may want to increase its profits by increasing the voltage level. on-line determination of load voltages would be possible along with on-line remote metering at load centres. Knowing that the frequency based tariff is already under implementation, the paper suggests, for the first time, a tariff based on the type of voltage dependent loads.
6 This paper shows a method of determining tariffs for voltage-dependent loads. Consumers gain if the supply company uses voltage-dependent tariffs for voltage dependent loads. For mixed type of loads, the supply Company gains, if it uses voltagedependent tariffs.
7 Voltage-dependent loads The following voltage-sensitive real power characteristics are considered: P=P 0 (Vr/V 0 ) m (1) where m = 0 for constant power load, = 1 for constant current load, = 2 for constant impedance load. A mixed load of the following combination of the above three types of load is also considered for framing the tariff. P = P 0 [ (Vr/V 0 ) +0.2(Vr/V 0 ) 2 ] (2)
8 A typical composition of a substation load is as follows: Induction motors, 50-70% Synchronous motors, 10 % Lighting and Heating, 20-25% Transmission loss, 10-12%. The lighting load consumes no reactive power. The power consumed by the lighting load does not vary as the (voltage) 2, but approximately as (voltage) 1.6. The heating load maintains constant resistance with voltage and hence the power varies with (voltage) 2.
9 Statistical Analysis of Voltage-dependent Loads on Monthly Billing A consumer with a constant current load of 10 kw when the supply voltage is 400V (L-L) is considered. The supply voltage and the hours of use are statistical quantities with normal distributions. Table 1 gives mean values and standard deviations of supply voltage and daily hours of use under peak loading conditions.
10 In table 1, the mean values of voltage and daily hours of use are set equal to their nominal values. The standard deviation, σ is σ= (α /100).µ/3 (3) where α = percent variation from the mean value µ = mean value. Formula (3) signifies that the per unit deviation of a statistical quantity from its mean value is equal to its 3σ value.
11 Table 2 gives the monthly charge for a constant current load of 10 kw at 400 V (L-L) nominal voltage and at 8 hours nominal use of electricity at a constant tariff of Rs 4.4 per kw-h. A random number generator generates thirty normally distributed values of Vr and h for thirty days in a month, using the mean and standard deviations given in Table 1. Table 2 gives the values of Pr for Pr= P 0 (Vr / V 0 ) 2, where P 0 = 10 kw at the nominal voltage, V 0 = 400 V. The daily charges are equal to kw-hrs multiplied by the tariff.
12 In Table 2, the voltage and the daily usage hours vary every day in a statistical manner, and the tariff remains constant at Rs 4.4/kW-hr. Next, the tariff varys with the voltage. A tariff of Rs. T 0 /kw-hr at nominal voltage, V 0, varies with voltage Vr. If the voltage Vr exceeds the nominal voltage V 0, then the new tariff T 1 is: T 1 = T 0 (V 0 /Vr). (4) If Vr is less than V 0, then the new tariff T 2 is: T 2 = T 0 (Vr/V 0). (5)
13 Table 3 gives the results of the new study. The voltages Vr of Table 2 appear in a decreasing order of magnitude, along with the associated values of hours and Pr. The tariff at nominal voltage is Rs 4.4/kW-hr. At other voltages, the tariff suggested by formulae (4) and (5) is used. These formulae adjust the tariff by about 10 P for a 10V deviation from the nominal voltage of 400V.
14 The paper considers the constant power, constant impedance, and mixed loads. Table 4 gives the results for the different types of load indicating the monthly bills with fixed tariff and voltage dependent tariff. The study shows that the consumers gain if the supply companies use the voltagedependent tariffs for constant power, constant current, and constant impedance loads. The supply company gains for a mixed load if it uses the voltage dependent tariff.
15 Conclusions This paper suggests a voltage-dependent tariff for use by the supply companies. The tariff could be an additional principle adopted by the State Electricity Regulatory Commissions while framing the structures and level of the tariffs. Further work on electricity pricing may include voltage dependency of the reactive power in addition to the voltage dependency of the real power as presented in this paper. Future work can be on Changes in the hourly tariff dependent on the changes in the real and reactive powers, and the frequency, using appropriate weighting factors.
Benchmarking Distribution Power Quality at BGE
Benchmarking Distribution Power Quality at BGE Dewane Daley Engineer Baltimore Gas & Electric Company 410-291-3198 dewane.a.daley@bge.com Large Scale Benchmarking Projects at BGE Distribution System Power
More informationConnection Impact Assessment Application Form
Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information
More informationUNBALANCED CURRENT BASED TARRIF
UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage ¤t unbalance are serious power quality problems with
More informationConnection Impact Assessment Application
Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,
More informationPOWER QUALITY AND SAFETY
POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION
More informationHarmonic Planning Levels for Australian Distribution Systems
Abstract Harmonic Planning Levels for Australian Distribution Systems V.J. Gosbell 1, V.W. Smith 1, D. Robinson 1 and W. Miller 2 1 Integral Energy Power Quality Centre, University of Wollongong 2 Standards
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationAC Power Instructor Notes
Chapter 7: AC Power Instructor Notes Chapter 7 surveys important aspects of electric power. Coverage of Chapter 7 can take place immediately following Chapter 4, or as part of a later course on energy
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationStandard MOD Area Interchange Methodology
A. Introduction 1. Title: Area Interchange Methodology 2. Number: MOD-028-2 3. Purpose: To increase consistency and reliability in the development and documentation of Transfer Capability calculations
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationREMOTE ENERGY METER MONITORING WITH SMS
REMOTE ENERGY METER MONITORING WITH SMS Swathy Shankar, Muzna Nabhan Al Brashdi, Marwa Shirin, Aman Jawed Waljat College of Applied Sciences Tel: +968 92959028 Abstract. The project Remote Energy Meter
More information1C.4.1 Harmonic Distortion
2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well
More informationHarmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems
University of Wollongong Research Online University of Wollongong Thesis Collection 1954-2016 University of Wollongong Thesis Collections 2006 Harmonic impact of photovoltaic inverter systems on low and
More informationHarmonic Distortion Levels Measured at The Enmax Substations
Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned
More informationQUESTIONNAIRE for Wind Farm Power Stations only
TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationBUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP
The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series HARMONICS Presented by: Syed Khundmir T Department of Electrical Engineering University at Buffalo khundmir@buffalo.edu
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationChapter 6 Introduction to Statistical Quality Control, 6 th Edition by Douglas C. Montgomery. Copyright (c) 2009 John Wiley & Sons, Inc.
1 2 Learning Objectives Chapter 6 Introduction to Statistical Quality Control, 6 th Edition by Douglas C. Montgomery. 3 4 5 Subgroup Data with Unknown μ and σ Chapter 6 Introduction to Statistical Quality
More informationHarmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.
Power Quality Standards in India Power Quality is a measure of an ideal power supply system. It can be defined as any power problem manifested in voltage, current and frequency deviations that result in
More informationKnowledge of load characteristics in distribution feeders is critical to operating distribution networks. Do the loads include electric heating, air
Knowledge of load characteristics in distribution feeders is critical to operating distribution networks. Do the loads include electric heating, air conditioning, or induction motors? This presentation
More informationChapter 7. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Chapter 7 Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Learning Objectives 1. Understand the meaning of instantaneous and average power, master AC power notation,
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More informationUnit Auxiliary Transformer (UAT) Relay Loadability Report
Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationOne-Sample Z: C1, C2, C3, C4, C5, C6, C7, C8,... The assumed standard deviation = 110
SMAM 314 Computer Assignment 3 1.Suppose n = 100 lightbulbs are selected at random from a large population.. Assume that the light bulbs put on test until they fail. Assume that for the population of light
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationINCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS
INCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS Carter-Brown Clinton Eskom Distribution - South Africa cartercg@eskom.co.za Gaunt CT University of Cape Town
More informationElectricity Ten Year Statement November Electricity Ten Year Statement November Appendix D
Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault
More informationUse only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at
Reviewed: Sergey Kryuchkov Distribution Engineering Scott Merriman Distribution Standards Valentina Dabic Distribution Planning Warren Quan Distribution Operations, FVO Raj Solanki Distribution Engineering
More informationDocument C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting
Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.
More informationSOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson
SOURCES OF ERROR IN UNBALANCE MEASUREMENTS V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson Integral Energy Power Quality Centre School of Electrical, Computer and Telecommunications Engineering
More informationHigh Voltage DC Transmission 2
High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion
More informationAppendix D Fault Levels
Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses
More informationIMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES
IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES (Summary) N S Markushevich and A P Berman, C J Jensen, J C Clemmer Utility Consulting International, JEA, OG&E Electric Services,
More informationThyristorised Automatic Power Factor
Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor
More informationCHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE
98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems
More informationCHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS
40 CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 3.1 INTRODUCTION The low power factor effects on transmission line, switchgear, transformers etc. It is observed that if the power
More informationENGINEERING DATA SUBMITTAL For the Interconnection of Generation System
WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric
More informationAPPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION
APPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION This application should be completed and returned to in order to begin processing the request for interconnecting as required by
More informationPerformance of high voltage transducers for measurement of power quality disturbances modeling and simulation
Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation HÉDIO TATIZAWA 1, ERASMO SILVEIRA NETO 2, GERALDO F. BURANI 1, ANTÔNIO A. C. ARRUDA 1, KLEIBER
More informationPREMIER INSTALLATION AND OPERATING INSTRUCTIONS
PREMIER INSTALLATION AND OPERATING INSTRUCTIONS Copyright 2002-2006, PRI Ltd. 9600-3003-2 Issue C Information contained within this document is subject to change without notice and does not represent a
More informationState of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company
Engineering data submittal Page 1 WHO SHOULD FILE THIS SUBMITTAL : Anyone in the final stages of in terconnecting a Generation System with Otter Tail Power. This submittal shall be completed and provided
More informationPower factor correction and harmonic filtering. Automatic power factor regulators R.1
Power factor correction and harmonic filtering Automatic power factor regulators R.1 R.1 Automatic power factor regulators R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent
More informationAPPENDIX B: Generation Interconnection Application Form
2 APPENDIX B: Generation Interconnection Application Form WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect with Xcel Energy (Local electric utility)
More informationELG2336 Introduction to Electric Machines
ELG2336 Introduction to Electric Machines Magnetic Circuits DC Machine Shunt: Speed control Series: High torque Permanent magnet: Efficient AC Machine Synchronous: Constant speed Induction machine: Cheap
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationANALYSIS OF VOLTAGE UNBALANCE REGULATION. Edwin B. Cano, PEE IIEE Life Member
ANALYSIS OF OLTAGE UNBALANCE REGULATION Edwin B. Cano, PEE IIEE Life Member ABSTRACT This paper presents an analysis of the present voltage unbalance regulation in the deregulated power industry in the
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationFault Induced Delayed Voltage Recovery (FIDVR) Advisory
Fault Induced Delayed Voltage Recovery (FIDVR) Advisory NERC Synchronized Measurement Subcommittee (SMS) NASPI Engineering Analysis Task Team (EATT) July 2015 Why the Advisory? The goal of this advisory
More informationProcedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process
This procedure outlines the Electric Reliability Organization (ERO) process for supporting the Frequency Response Standard (FRS). A Procedure revision request may be submitted to the ERO for consideration.
More informationParallel tap-changer controllers under varying load conditions (Part 1)
Parallel tap-changer controllers under varying load conditions (Part 1) by Prof. B S Rigby, T Modisane, University of KwaZulu-Natal This paper investigates the performance of voltage regulating relays
More informationVar Control. Adding a transformer and transformer voltage regulation. engineers loadflow program. The control system engineers loadflow.
November 2012 Adding a transformer and transformer voltage regulation to the control system engineers loadflow program The control system engineers loadflow program The loadflow program used by this website
More informationCHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses
CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses 8.1 Introduction The present level of Transmission and Distribution (T & D) losses in Indian power system is estimated
More informationPower factor correction and harmonic filtering. Automatic power factor regulators
Power factor correction and harmonic filtering Automatic power factor regulators Automatic power factor reguladors R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent
More informationMath 2311 Bekki George Office Hours: MW 11am to 12:45pm in 639 PGH Online Thursdays 4-5:30pm And by appointment
Math 2311 Bekki George bekki@math.uh.edu Office Hours: MW 11am to 12:45pm in 639 PGH Online Thursdays 4-5:30pm And by appointment Class webpage: http://www.math.uh.edu/~bekki/math2311.html Math 2311 Class
More informationPOWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER
POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationResistor Glossary. Token Electronics Industry Co., Ltd. Version: January 12, Web:
Version: January 12, 2017 Resistor Glossary Web: www.token.com.tw Email: rfq@token.com.tw Token Electronics Industry Co., Ltd. Taiwan: No.137, Sec. 1, Zhongxing Rd., Wugu District, New Taipei City, Taiwan,
More informationLab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009
Lab 1 Objectives In this lab, our objective is to simulate a simple single machine infinite bus configuration using the PowerWorld Simulator software. We design a local generator system (a synchronous
More informationElectrical Protection System Design and Operation
ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection
More informationElectrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018
Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine
More informationNetwork Monitoring and Visibility Summary
Network Monitoring and Visibility Summary This article reviews the shortfalls in legacy monitoring and what will be needed to manage the changing nature of the distribution network. This includes a particular
More informationVOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION SYSTEMS
66 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006 VOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION
More informationDownloaded from / 1
PURWANCHAL UNIVERSITY II SEMESTER FINAL EXAMINATION-2008 LEVEL : B. E. (Computer/Electronics & Comm.) SUBJECT: BEG123EL, Electrical Engineering-I Full Marks: 80 TIME: 03:00 hrs Pass marks: 32 Candidates
More informationOwner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:
Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document January, 2014 This draft reference document is posted for stakeholder comments prior to being finalized to support implementation of the Phase 2 Bulk
More informationThe Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller
The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric
More informationFIBER OPTICS. Prof. R.K. Shevgaonkar. Department of Electrical Engineering. Indian Institute of Technology, Bombay. Lecture: 20
FIBER OPTICS Prof. R.K. Shevgaonkar Department of Electrical Engineering Indian Institute of Technology, Bombay Lecture: 20 Photo-Detectors and Detector Noise Fiber Optics, Prof. R.K. Shevgaonkar, Dept.
More informationChapter 2: Transformers
Chapter 2: Transformers 2-1. The secondary winding of a transformer has a terminal voltage of v s (t) = 282.8 sin 377t V. The turns ratio of the transformer is 100:200 (a = 0.50). If the secondary current
More informationOklahoma Gas and Electric Co. Facility Connection Requirements MAINTAINED BY. Transmission Planning Engineering Department
Oklahoma Gas and Electric Co. Facility Connection Requirements MAINTAINED BY Transmission Planning Engineering Department Table of Contents Transmission and Generation Facility Interconnections... 3 Attachment
More informationENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS
ENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS Copyright 2002-2006 PRI Ltd. 9600-3004-2 Issue C Information contained within this document is subject to change without notice and does not represent
More informationQuestion Paper Profile
I Scheme Question Paper Profile Program Name : Electrical Engineering Program Group Program Code : EE/EP/EU Semester : Third Course Title : Electrical Circuits Max. Marks : 70 Time: 3 Hrs. Instructions:
More information, ,54 A
AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate
More informationOPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS
OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED
More informationCOSEM. Identification System EXCERPT FROM. Companion Specification for Energy Metering. DLMS User Association
EXCERPT FROM Companion Specification for Energy Metering COSEM Identification System DLMS User Association device language message specification Reference number: EXCERPT FROM DLMS UA -:999, First Edition
More informationStudy of Power Factor Correction in Single Phase AC-DC Converter
Avneet Kaur, Prof. S.K Tripathi, Prof. P. Tiwari 89 Study of Power Factor Correction in Single Phase AC-DC Converter Avneet Kaur, Prof. S.K Tripathi, Prof. P. Tiwari Abstract: This paper is regarding power
More informationPower Factor & Harmonics
Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics
More informationA compact, integrated solution for medium voltage connection, transformer and low voltage distribution
Low to medium voltage distribution M2L integrated power distribution system A compact, integrated solution for medium voltage connection, transformer and low voltage distribution Turnkey solution medium
More informationCHAPTER ELECTRIC AND MAGNETIC FIELDS
CHAPTER 62-814 ELECTRIC AND MAGNETIC FIELDS 62-814.100 Intent, Findings, Basis of Standards, and Research Needs 62-814.200 Electric and Magnetic Fields; Definitions 62-814.300 General Technical Requirements
More informationSouthern Company Power Quality Policy
Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...
More informationADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS
ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS R. A. Walling, K. Clark, N. W. Miller, J. J. Sanchez-Gasca GE Energy USA reigh.walling@ge.com ABSTRACT
More informationElectricity Meters Grid metering. Electricity Meter. Landis+Gyr E850 ZMQ200. Increased revenue through high accuracy and tailored grid functions
Electricity Meters Grid metering Electricity Meter Landis+Gyr E850 ZMQ200 Increased revenue through high accuracy and tailored grid functions Landis+Gyr E850 (ZMQ200) is our latest high precision meter
More informationIE 361 Module 4. Metrology Applications of Some Intermediate Statistical Methods for Separating Components of Variation
IE 361 Module 4 Metrology Applications of Some Intermediate Statistical Methods for Separating Components of Variation Reading: Section 2.2 Statistical Quality Assurance for Engineers (Section 2.3 of Revised
More informationModule 1. Introduction. Version 2 EE IIT, Kharagpur
Module 1 Introduction Lesson 1 Introducing the Course on Basic Electrical Contents 1 Introducing the course (Lesson-1) 4 Introduction... 4 Module-1 Introduction... 4 Module-2 D.C. circuits.. 4 Module-3
More informationRENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana
RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana JANUARY 2015 i Table of Content PART A: 1 1 Introduction 1 1.1 Scope 1 1.2 Status 1 1.3 Terms
More informationCork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)
Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:
More informationNZECP 36:1993 ISSN COVER PAGE
NZECP 36:1993 ISSN 0114-0663 COVER PAGE NZECP 36:1993 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for HARMONIC LEVELS Issued by the Office of The Chief Electrical Inspector, Energy and Resources Division,
More informationDetermining Dimensional Capabilities From Short-Run Sample Casting Inspection
Determining Dimensional Capabilities From Short-Run Sample Casting Inspection A.A. Karve M.J. Chandra R.C. Voigt Pennsylvania State University University Park, Pennsylvania ABSTRACT A method for determining
More informationOPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS
OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS CONNECTED TO THE DISTRIBUTION SYSTEM ORANGE AND ROCKLAND
More informationSTATE OF THE ART TIME OF USE METERING ISSUES
STATE OF THE ART TIME OF USE ING ISSUES 15 Author & Presenter Dr R Billiet BSc (Elec Eng), Hons B Comm, DBA General Manager Sales and Marketing Strike Technologies (Pty) Ltd 1 Introduction This paper will
More informationPhase and Waveform Comparative Analysis for Electric Heater, Induction Motor and Static Capacitor
International Journal of Innovative Research in Education, Technology & Social Strategies IJIRETSS ISSN Print: 2465-7298 ISSN Online: 2467-8163 Volume 5, Number 1, March 218 Phase and Waveform Comparative
More informationdomovea energy tebis
domovea energy tebis TABLE OF CONTENTS TABLE OF CONTENTS Page 1. INTRODUCTION... 2 1.1 PURPOSE OF THE DOCUMENT... 2 2. THE ARCHITECTURE OF ELECTRICITY MEASUREMENT... 3 2.1 OBJECTS USED FOR MEASUREMENT...
More informationPMU-based Voltage Instability Detection through Linear Regression
PMU-based Voltage Instability Detection through Linear Regression Rujiroj Leelaruji and Prof. Luigi Vanfretti Smart Transmission Systems Lab. Electric Power Systems Department KTH Royal Institute of Technology,
More informationDEP 2008 ELECTRIC AND MAGNETIC FIELDS CHAPTER ELECTRIC AND MAGNETIC FIELDS
CHAPTER 62-814 ELECTRIC AND MAGNETIC FIELDS TABLE OF CONTENTS PAGE 62-814.100 Intent, Findings, Basis of Standards, and Research Needs. 2 62-814.200 Electric and Magnetic Fields; Definitions. 3 62-814.300
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More information