Controllable Generation UCAP determination. Eligibility WG September 12, 2017

Size: px
Start display at page:

Download "Controllable Generation UCAP determination. Eligibility WG September 12, 2017"

Transcription

1 Controllable Generation UCAP determination Eligibility WG September 12, 2017

2 Purpose and objective The objectives of this presentation include: Recap the installed capacity (ICAP) and unforced capacity (UCAP) definitions Understand the data requirements for UCAP Compare GADs and AESO data Request feedback from workgroup 1

3 Recall from July 4 th meeting UCAP Calculation for a Thermal Resource Example: Gas Combined Cycle with a nameplate capacity of 500 MW Seasonal Net Dependable (ICAP) accounts for the impact of ambient weather conditions (Summer) on unit performance Unforced Capacity (UCAP) is the ICAP value of the unit reduced by its recent actual forced outage rate during system demand periods (EFORd) Generator will able to offer 396 UCAP MW into the capacity auction Nameplate capacity rating = 500 MW Nameplate capacity modified for seasonal ambient limitations (ICAP). Example: If ambient temprature reduction is 10 % of the nameplate capacity. Ex. ICAP = 500 MW * 90% = 450 MW UCAP= ICAP * (1-EFORd) Forced outage rate = 12% UCAP = ICAP * (1- forced outage rate) Ex. If UCAP = 450 MW * (1-0.12) = 396 MW Public 2

4 UCAP calculation and data requirements UCAP= ICAP x (1- EFORd) where Equivalent Demand Forced Outage Rate (EFORd) is a measure of probability that a generating unit will not be available due to forced outages or forced derates when there is a demand on the unit to generate* The EFORd calculation relies on reliability data that comes from the Generation Availability Data System (GADS). GADs data are collected by NERC and provide information about the performance and outages / derates of generating units** The UCAP calculation may have different data requirements for uncontrollable and controllable generation AESO does not have GADS data *PJM Capacity Market/ PJM Manual 18/PJM Capacity Market Operations ** 3

5 UCAP Calculation: ETS data deficiencies Information needed for calculating UCAP based on EFORd Duration of Forced outages, Planned Outages, Forced Derates and Planned Derates Service Hours (The period of time that the unit was generating electricity) Reserve Shutdown ( the period that the unit was available, but not dispatched) Number of Actual Starts and Attempted Unit Starts Do we have this information? NO Yes Yes NO Comments ETS gives the option to the participants to leave out the event type in their submissions within a 7 day period before the event. In the case that they do not submit this field, it would be automatically populated using a logic that does not allow participants to clearly distinguish between forced and planned events. Therefore the event field would not be useful in determining the type of the outages and derates. This could be extracted from the metered volumes. When the unit is available (AC 0) but generation is zero. The data are not available. Based on the data currently available, calculation of UCAP based on EFORd methodology will be time consuming and complex. This methodology needs information similar to what GADs provide. However, this method could be used in the future if the GADS data become available. 4

6 Conceptual differences between AC and UCAP Maximum Capability = 200 MW PJM Ambient temp and humidity adjustment Alberta Ambient temp and humidity adjustment Maximum Capability = 200 MW ICAP = 170 MW 30 MW Forced outages/derates 30 MW 30 MW Forced outages/derates 30 MW PJM based UCAP for thermal generator = 140 MW Planned Outages/derates Planned Outages/derates ACf: is 140MWs UCAP is ICAP adjusted for performance through GADS data In other jurisdictions This example is for illustrative purposes only 40 MW + Available 100 MW 40 MW Available Capacity (AC in ETS) 100 MW AC = 100 MW AESO AC data does not separate between ambient, forced or planned outages. AC accounts for all lost generation UCAP: ICAP after capacity reduction due to forced outages and derates AESO ACf: ICAP after capacity reduction due to implied forced outages and implied derates AESO AC: ICAP after capacity reduction due to forced outages and derates and planned outages 5

7 Questions for the workgroup discussion Which option should be used for the interim UCAP calculation? A NERC mandate for 20MW and greater generators: do Alberta generators follow this requirement and have GADS data? Is the quality robust enough for use for UCAP Calculation? Are categorization practices comparable for all generation owners? Approach for generators less than 20MWs? If In the event ETS data is used, should AESO prioritize classifying outages earlier for the purpose of calculating more accurate UCAP on time for delivery during the transition period? Should the AESO investigate GADS further? Use GADS, AC or ACf for UCAP calculations? What demand hours should be used? 6

8 Thank you

9 Appendix B AC and AC f Overview Option 1: Use Available Capability as UCAP For existing resources this option uses historically submitted AC Variable resource may use capacity factors New resources and technologies may use class averages either from historical available capabilities or from sources outside the AESO for units with no historical data Seasons and demand hours will need to be defined Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) For existing resources this option uses historical AC submissions AC f may be calculated using a derate factor that only takes into account hours with forced outages and derates Forced outages are any outages/derates submitted within 7 days. Any submissions before 7 days are assumed to be planned Variable resource may use capacity factors New resources and technologies may use class averages either from historical available capabilities or from sources outside the AESO for units with no historical data Seasons and demand hours will need to be defined 8

10 Appendix B AC and AC f Advantages Option 1: Use Available Capability as UCAP Simple to understand and implement Availability of historical data Provides a conservative estimate of a plant s true capability as it includes planned and forced outages. Historical performance can be measured Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) This approach is closer in nature to way UCAP is calculated in North American capacity markets using GADs data Transition to GADS may be smoother as the difference in UCAP and ACF volumes may be lower Rules and compliance procedures in place to evaluate quality of AC submissions 9

11 Appendix B AC and AC f Disadvantages Option 1: Use Available Capability as UCAP Determining true availability of a unit will require additional work as some units may show full AC but not be dispatchable i.e. Long lead time, Mothball, peaking units, etc. AC data and rules were designed to meet the needs of an energy-only market and were not intended to fulfill the requirements of the UCAP calculation Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) More complex to implement as it requires parsing the data into planned and forced outages, which requires assumptions AC F will still be based on AC submissions, which were designed to meet the needs of an energy-only market and were not intended to fulfill the requirements of the UCAP calculation Methodology requires defining an approach to account for the impact of ambient weather conditions Method is still under investigation. AESO needs to further examine AC submission data to assess feasibility 10

12 Appendix B AC and AC f Example This example is only for illustrative purpose It intends to show the expected differences in magnitude between AC and AC f It uses a dummy generator with a maximum capability equal to 452 MW The same data set was used to calculate the AC and AC f values For the purpose of this example, the summer season comprised months from May to October and the winter season covered the months from November to April The actual months and HEs to be used in the UCAP methodology are yet to be decided 11

13 Appendix B AC and AC f Terminology Forced Outage Hours - FOH Sum of all hours experienced during Forced Outages. Forced outages are any outages submitted within 7 days. Equivalent Forced Derated Hours EFDH Forced derates are any derates submitted within 7 days. Each individual Forced Derating is transformed into equivalent full outage hour(s). This is calculated by multiplying the actual duration of the derating (hours) by the size of the reduction (MW) and dividing by the Maximum Capacity (MC). These equivalent hour(s) are then summed. (Derating Hours x Size of Reduction*)/ MC NOTE: Includes Forced Deratings during Reserve Shutdowns (RS). Service Hours SH Sum of all Unit Service Hours Equivalent Forced Derated Hours During Reserve Shutdowns EFDHRS Each individual Forced Derating or the portion of any Forced derating which occurred during a Reserve Shutdown (RS) is transformed into equivalent full outage hour(s). This is calculated by multiplying the actual duration of the derating (hours) by the size of the reduction (MW) and dividing by the Maximum Capacity (MC). These equivalent hour(s) are then summed. (Derating Hours x Size of Reduction*)/ MC 12

14 Appendix B AC and AC f Example Option 1: Use Available Capability as UCAP Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) AB1 Avg AC Median AC Max AC Min AC Summer Winter AC f = MC (1 Derate Factor) Derate Factor = FOH + EFDH FOH + SH + EFDHRS 100% AB1 Derate Factor AC f Summer 2.67% 440 Winter 4.25%

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.

More information

Procedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process

Procedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process This procedure outlines the Electric Reliability Organization (ERO) process for supporting the Frequency Response Standard (FRS). A Procedure revision request may be submitted to the ERO for consideration.

More information

Geoff Brown & Associates Ltd

Geoff Brown & Associates Ltd Geoff Brown & Associates Ltd REVIEW OF WESTERN POWER S APPLICATION FOR A TECHNICAL RULES EXEMPTION FOR NEWMONT MINING SERVICES Prepared for ECONOMIC REGULATION AUTHORITY Final 20 August 2015 Report prepared

More information

Transmission Facilities Rating Methodology for Florida

Transmission Facilities Rating Methodology for Florida Document title Transmission Facilities Rating Methodology for Florida Document number EGR-TRMF-00001 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning Duke

More information

System Operating Limit Definition and Exceedance Clarification

System Operating Limit Definition and Exceedance Clarification System Operating Limit Definition and Exceedance Clarification The NERC-defined term System Operating Limit (SOL) is used extensively in the NERC Reliability Standards; however, there is much confusion

More information

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics: A. Introduction 1. Title: Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions 2. Number: MOD-027-1 3. Purpose: To verify that the turbine/governor

More information

FACILITY RATINGS METHOD TABLE OF CONTENTS

FACILITY RATINGS METHOD TABLE OF CONTENTS FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5

More information

Agricultural Data Verification Protocol for the Chesapeake Bay Program Partnership

Agricultural Data Verification Protocol for the Chesapeake Bay Program Partnership Agricultural Data Verification Protocol for the Chesapeake Bay Program Partnership December 3, 2012 Summary In response to an independent program evaluation by the National Academy of Sciences, and the

More information

Unit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition

Unit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition Unit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition NERC System Protection and Control Subcommittee March 2016 NERC Report Title Report Date I Table

More information

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities

More information

Transmission Facilities Rating Methodology

Transmission Facilities Rating Methodology Document title Transmission Facilities Rating Methodology Document number EGR-TRMC-00009 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning- Progress Energy

More information

Statistical Pulse Measurements using USB Power Sensors

Statistical Pulse Measurements using USB Power Sensors Statistical Pulse Measurements using USB Power Sensors Today s modern USB Power Sensors are capable of many advanced power measurements. These Power Sensors are capable of demodulating the signal and processing

More information

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation

More information

PJM Regulation Study Update

PJM Regulation Study Update PJM Regulation Study Update July 19, 2016 Eric J. Endress Engineer, Performance Compliance Acronym Definitions RegD = Regulation D, Dynamic Regulation RegA = Regulation A, Traditional Regulation ACE =

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Comfort and Load Control: It s Getting Hot in Here But is the Utility to Blame?

Comfort and Load Control: It s Getting Hot in Here But is the Utility to Blame? Comfort and Load Control: It s Getting Hot in Here But is the Utility to Blame? Frank Stern, Navigant, Boulder, CO, USA Nicholas DeDominicis, PECO, Philadelphia, PA, USA Greg Ekrem, Navigant, Boulder,

More information

POWER POTENTIAL: DISTRIBUTED ENERGY RESOURCES (DER) TECHNICAL SPECIFICATIONS GUIDANCE FOR PROVISION OF REACTIVE AND ACTIVE POWER SERVICES

POWER POTENTIAL: DISTRIBUTED ENERGY RESOURCES (DER) TECHNICAL SPECIFICATIONS GUIDANCE FOR PROVISION OF REACTIVE AND ACTIVE POWER SERVICES POWER POTENTIAL: DISTRIBUTED ENERGY RESOURCES (DER) TECHNICAL SPECIFICATIONS GUIDANCE FOR PROVISION OF REACTIVE AND ACTIVE POWER SERVICES For use with the Power Potential DER Technical Characteristics

More information

NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE)

NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE) COORDONNATEUR DE LA FIABILITÉ Direction Contrôle des mouvements d énergie Demande R-3944-2015 NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE) Original : 2016-10-14 HQCMÉ-10, Document 2 (En liasse) Standard

More information

Wireless Transmissions:

Wireless Transmissions: Wireless Transmissions: An Examination of OpenWay Smart Meter Transmissions in a 24-Hour Duty Cycle Jeff French Applications Engineer Mike Belanger Product Line Manager 2011, Itron Inc. All rights reserved.

More information

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities at a level to prevent unnecessary tripping

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules. 45-day Formal Comment Period with Initial Ballot June July 2014

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules. 45-day Formal Comment Period with Initial Ballot June July 2014 Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed

More information

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0 ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2014-03-31 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding

More information

Voltage and Reactive Procedures CMP-VAR-01

Voltage and Reactive Procedures CMP-VAR-01 Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes

More information

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to

More information

Engineering Recommendation M30 Issue Standard Electricity Network Operator Electricity Smart Meter Configurations

Engineering Recommendation M30 Issue Standard Electricity Network Operator Electricity Smart Meter Configurations PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Engineering Recommendation M30 Standard Electricity Network Operator Electricity Smart Meter s www.energynetworks.org PUBLISHING AND

More information

Transmission Availability Data System Phase II Final Report

Transmission Availability Data System Phase II Final Report Transmission Availability Data System Phase II Final Report Prepared by the Transmission Availability Data System Task Force for the NERC Planning Committee Approved by the Planning Committee on: Table

More information

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed

More information

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed

More information

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents

More information

GridLiance Reliability Criteria

GridLiance Reliability Criteria GridLiance Reliability Criteria Planning Department March 1, 2018 FOREWORD The GridLiance system is planned, designed, constructed, and operated to assure continuity of service during system disturbances

More information

Unit Auxiliary Transformer (UAT) Relay Loadability Report

Unit Auxiliary Transformer (UAT) Relay Loadability Report Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC

More information

Bulk Electric System Definition Reference Document

Bulk Electric System Definition Reference Document Bulk Electric System Definition Reference Document Version 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying the definition.

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection: Utility Systems Technologies, Inc. Sag Fighter TM Deep Voltage Sag Protection: D e e p Vo l t a g e S a g P r o t e c t i o n For three phase application: Q u a l i t y P o w e r. B e t t e r B u s i n

More information

TRANSMISSION FACILITIES...7

TRANSMISSION FACILITIES...7 Table of Contents 1. INTRODUCTION...4 1.1. Objective... 4 1.2. NERC FAC-008 Compliance... 4 1.3. Seminole s Normal Rating... 5 1.4. Seminole s Four-Hour Rating... 5 1.5. Seminole s Emergency Rating...

More information

Planning Criteria. Revision 1.4 MAINTAINED BY: Transmission Working Group System Protection and Control Working Group Supply Adequacy Working Group

Planning Criteria. Revision 1.4 MAINTAINED BY: Transmission Working Group System Protection and Control Working Group Supply Adequacy Working Group Planning Criteria Revision 1.4 MAINTAINED BY: Transmission Working Group System Protection and Control Working Group Supply Adequacy Working Group PUBLISHED: 10/9/2017 LATEST REVISION: Effective 7/25/2017

More information

TTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line

TTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line TTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line Vince Leung March 27, 2017 Reviewed by Johnny Nguyen Table of Contents Background 2 Objective 3 Base Case Assumptions

More information

Capacity Market Prequalification

Capacity Market Prequalification Capacity Market Prequalification T-4 Auction December 2016 Early Auction January 2017 Transitional Arrangement Auction March 2017 Guidance document for Capacity Market participants Capacity Market Prequalification

More information

Final ballot January BOT adoption February 2015

Final ballot January BOT adoption February 2015 Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and

More information

MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above

MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above March 13, 2018 Issued by: Dehn Stevens, Director System Planning and Services 1.0 SCOPE This document defines the criteria

More information

Table 1 - Assignment of BA Obligations... 8

Table 1 - Assignment of BA Obligations... 8 Dynamic Transfer Reference Guidelines Version 2 June 2010 Table of Contents Table of Contents Chapter 1 Overview... 3 Purpose... 3 Terms... 3 Chapter 2 Dynamic Schedule Versus Pseudo-tie Fundamentals...

More information

Module 7-4 N-Area Reliability Program (NARP)

Module 7-4 N-Area Reliability Program (NARP) Module 7-4 N-Area Reliability Program (NARP) Chanan Singh Associated Power Analysts College Station, Texas N-Area Reliability Program A Monte Carlo Simulation Program, originally developed for studying

More information

Load-Frequency Control Service in a Deregulated Environment

Load-Frequency Control Service in a Deregulated Environment Load-Frequency Control Service in a Deregulated Environment A. P. Sakis Meliopoulos Fellow School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, GA 30332-0250 George J.

More information

Transmission Availability Data System 2008 Automatic Outage Metrics and Data Report Region: RFC

Transmission Availability Data System 2008 Automatic Outage Metrics and Data Report Region: RFC Transmission Availability Data System 2008 Automatic Outage Metrics and Data Report Region: RFC Table of Contents 1 Introduction...1 1.1 Contributors and Acknowledgements... 1 1.2 TADS History... 1 1.3

More information

Evaluation of Algorithm Performance /06 Gas Year Scaling Factor and Weather Correction Factor

Evaluation of Algorithm Performance /06 Gas Year Scaling Factor and Weather Correction Factor Evaluation of Algorithm Performance - 2005/06 Gas Year Scaling Factor and Weather Correction Factor The annual gas year algorithm performance evaluation normally considers three sources of information

More information

Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards

Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards Applicability: Balancing Authorities (BAs) Introduction and Purpose: It is in the public interest for NERC to develop

More information

VI.D AIR DISCONNECT SWITCHES

VI.D AIR DISCONNECT SWITCHES VI.D AIR DISCONNECT SWITCHES DMS #84474 Page 1 of 20 Revised: AIR DISCONNECT SWITCH RATINGS PENNSYLVANIA - NEW JERSEY - MARYLAND INTERCONNECTION PLANNING AND ENGINEERING COMMITTEE TRANSMISSION AND SUBSTATION

More information

System Ratings, Limits and Real-Time Monitoring. Presented to: Operating Committee April 21, 2016

System Ratings, Limits and Real-Time Monitoring. Presented to: Operating Committee April 21, 2016 System Ratings, Limits and Real-Time Monitoring Presented to: Operating Committee April 21, 2016 Thermal Facility Ratings In New England Summer ratings (April 1 to October 31) Winter ratings (November

More information

Standard MOD Area Interchange Methodology

Standard MOD Area Interchange Methodology A. Introduction 1. Title: Area Interchange Methodology 2. Number: MOD-028-2 3. Purpose: To increase consistency and reliability in the development and documentation of Transfer Capability calculations

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

Air Monitoring Directive Chapter 9: Reporting

Air Monitoring Directive Chapter 9: Reporting Air Monitoring Directive Chapter 9: Reporting Version Dec 16, 2016 Amends the original Air Monitoring Directive published June, 1989 Title: Air Monitoring Directive Chapter 9: Reporting Number: Program

More information

General Specifications

General Specifications General Specifications GS 77J0A070E Model VJA7 Distributor (Multifunction) (Isolated Singleoutput and Isolated Dualoutput Types) Overview This plugin type distributor is used in combination with wire type

More information

Recently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.

Recently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team. December 7 th, 2010 NPCC Full Member Committee; Please find attached a draft revised NPCC Regional Reliability Directory #12 Underfrequency Load Shedding Program Requirements and a draft revised NPCC UFLS

More information

Cymbaluk Noise Complaints

Cymbaluk Noise Complaints Decision 20259-D01-2015 Cymbaluk Noise Complaints December 22, 2015 Alberta Utilities Commission Decision 20259-D01-2015 Cymbaluk Noise Complaints Proceeding 20259 Application 20259-A001 December 22, 2015

More information

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.: WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO-00111 Job No.: 16-7003 To Respondent of Record: ADDENDUM 2 July 5, 2017 This addendum, applicable to work referenced

More information

AHRI Standard Standard for Performance Rating of Modulating Positive Displacement Refrigerant Compressors

AHRI Standard Standard for Performance Rating of Modulating Positive Displacement Refrigerant Compressors AHRI Standard 545 2017 Standard for Performance Rating of Modulating Positive Displacement Refrigerant Compressors IMPORTANT SAFETY RECOMMENDATIONS AHRI does not set safety standards and does not certify

More information

60V, 50mA, Ultra-Low Quiescent Current, Linear Regulator

60V, 50mA, Ultra-Low Quiescent Current, Linear Regulator General Description The MAX17651 ultra-low quiescent current, high-voltage linear regulator is ideal for use in industrial and batteryoperated systems. The device operates from a 4V to 60V input voltage,

More information

Calculating and Using Reporting ACE in a Tie Line Bias Control Program

Calculating and Using Reporting ACE in a Tie Line Bias Control Program Calculating and Using Reporting ACE in a Tie Line Bias Control Program Introduction: Tie Line Bias 1 (TLB) control has been used as the preferred control method in North America for 75 years. In the early

More information

ROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT

ROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT ROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT Page 1 of 8 The document describes the current methodology used for developing facility ratings

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements NPCC Regional Reliability Reference Directory # 12 Under frequency Load Shedding Program Requirements Task Force on System Studies Revision Review Record: June 26 th, 2009 March 3 rd, 2010 Adopted by the

More information

Alberta Reliability Standard Frequency Response and Frequency Bias Setting BAL-003-AB-1.1

Alberta Reliability Standard Frequency Response and Frequency Bias Setting BAL-003-AB-1.1 1. Purpose The purpose of this reliability standard is to: (a) require sufficient frequency response from the ISO to maintain Interconnection frequency within predefined bounds by arresting frequency deviations

More information

Bulk Electric System Definition Reference Document

Bulk Electric System Definition Reference Document Bulk Electric System Definition Reference Document JanuaryVersion 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying

More information

OPTIONS [MATH FUNCTION] [TOTALIZER] [FLOW CORRECTION]

OPTIONS [MATH FUNCTION] [TOTALIZER] [FLOW CORRECTION] INST. INE-288C OPTIONS [MATH FUNCTION] [TOTALIZER] [FLOW CORRECTION] FOR AL/AH3000 SERIES HYBRID RECORDER Retain this manual apart from the instrument and in an easily accessible. Please make sure that

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

COURSE NOTES Testing Compliance to Energy Efficiency Standards

COURSE NOTES Testing Compliance to Energy Efficiency Standards COURSE NOTES Testing Compliance to Energy Efficiency Standards Introduction These course notes are to be read in association with the PI University video course, Testing Compliance to Energy Efficiency

More information

Frequency Response Characteristic Survey Training Document

Frequency Response Characteristic Survey Training Document Frequency Response Characteristic Survey Training Document Training Document Subsections Frequency Response Characteristic Response to Internal and External Generation/Load Imbalances Frequency Bias versus

More information

Lab/Project Error Control Coding using LDPC Codes and HARQ

Lab/Project Error Control Coding using LDPC Codes and HARQ Linköping University Campus Norrköping Department of Science and Technology Erik Bergfeldt TNE066 Telecommunications Lab/Project Error Control Coding using LDPC Codes and HARQ Error control coding is an

More information

Line Impedance Estimation Using SCADA Data

Line Impedance Estimation Using SCADA Data Line Impedance Estimation Using SCADA Data Presenter: Ramiro Da Corte - Power System Engineer Prepared by: James Shen - Principal Engineer, AESO Nov. 5, 214 Background AESO is responsible for grid reliability

More information

Available Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University

Available Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University Available Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University i Available Transfer Capability (ATC) ATC measures the residual transfer capability in the

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

DIGITAL THERMOMETER VIEW RECORDERS Digital Thermometer FEATURES

DIGITAL THERMOMETER VIEW RECORDERS Digital Thermometer FEATURES Digital Thermometer High-Accuracy Reference Junction Compensation: Compensation accuracy (±0.2 C) Input terminals are provided on both front and rear panels, and an input site is switch selectable. The

More information

Category: ELECTRICITY Requirement: EL-ENG Page: 1 of 13. Document(s): S-E-01, S-E-04 Issue Date: Effective Date:

Category: ELECTRICITY Requirement: EL-ENG Page: 1 of 13. Document(s): S-E-01, S-E-04 Issue Date: Effective Date: Requirements for Certification Category: ELECTRICITY Requirement: EL-ENG-11-02 Page: 1 of 13 Requirements for Certification and Use of Portable Measuring Apparatus for Reverification and Dispute Meter

More information

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

ST662AB ST662AC. DC-DC converter from 5 V to 12 V, 0.03 A for Flash memory programming supply. Features. Description

ST662AB ST662AC. DC-DC converter from 5 V to 12 V, 0.03 A for Flash memory programming supply. Features. Description ST662AB ST662AC DC-DC converter from 5 V to 12 V, 0.03 A for Flash memory programming supply Features Output voltage: 12 V ± 5 % Supply voltage range: 4.5 V to 5.5 V Guaranteed output current up to 30

More information

Appendix D Fault Levels

Appendix D Fault Levels Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses

More information

General report format, ref. Article 12 of the Birds Directive, for the report

General report format, ref. Article 12 of the Birds Directive, for the report Annex 1: General report format, ref. Article 12 of the Birds Directive, for the 2008-2012 report 0. Member State Select the 2 digit code for your country, according to list to be found in the reference

More information

Proposed Language in BAL-003-1/Comments New Standard or Other Action R1. Each Balancing Authority shall This. Attachment A.

Proposed Language in BAL-003-1/Comments New Standard or Other Action R1. Each Balancing Authority shall This. Attachment A. in Approved Standard Translation to R1. Each Balancing Authority shall review its Frequency Bias Each Balancing Authority shall report its previous year s Settings by January 1 of each Frequency Response

More information

The LIPAedge program has established the following rules for its operation:

The LIPAedge program has established the following rules for its operation: LIPAedge Impact Methodology The LIPAedge program is a residential and small commercial direct load control program. The program has the following components: 1. Customer receives a programmable thermostat

More information

Tampa Electric Company Facility Rating Methodology Approved 11/20/2018

Tampa Electric Company Facility Rating Methodology Approved 11/20/2018 Tampa Electric Company Facility Rating Methodology Approved 11/20/2018 Effective Date: 12/01/2018 Responsible Department: System Planning Review Cycle: 3 Years Last Date Reviewed: 11/16/2018 Next Planned

More information

15.2 Rate Schedule 2 - Payments for Supplying Voltage Support Service

15.2 Rate Schedule 2 - Payments for Supplying Voltage Support Service 15.2 Rate pport Service This Rate Schedule applies to payments to Suppliers who provide Voltage Support Service to the ISO. Transmission Customers and Customers will purchase Voltage Support Service from

More information

Area Control Error (ACE) Equation Special Cases

Area Control Error (ACE) Equation Special Cases Area Control Error (ACE) Equation Special Cases Purpose: It is the obligation of each Balancing Authority to manage its Area Control Error in accordance with NERC reliability standards. This Standard provides

More information

ATTACHMENT Y STUDY REPORT

ATTACHMENT Y STUDY REPORT Dynegy Marketing and Trade, LLC Wood River Units 4 & 5: 473 MW Retirement: June 1, 2016 ATTACHMENT Y STUDY REPORT March 23, 2016 PUBLIC / REDACTED PUBLIC VERSION EXECUTIVE SUMMARY An Attachment Y notification

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the Board of Trustees. Description

More information

Office for Nuclear Regulation

Office for Nuclear Regulation Office for Nuclear Regulation ASSESSMENT REPORT Civil Nuclear Reactors Programme NNB Genco: Hinkley Point C Pre-Construction Safety Report 2012 Assessment Report for Work Stream B14, Radiation Protection

More information

NARUC. Summer Committee Meetings. Staff Subcommittees on Electricity & Electric Reliability

NARUC. Summer Committee Meetings. Staff Subcommittees on Electricity & Electric Reliability NARUC Summer Committee Meetings Staff Subcommittees on Electricity & Electric Reliability NARUC Summer Committee Meetings Agenda 10:00-11:00 am Tour of the Newtown Creek Biodigester Plant 1:00 2:00 pm

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

8th Floor, 125 London Wall, London EC2Y 5AS Tel: +44 (0) Fax: +44 (0)

8th Floor, 125 London Wall, London EC2Y 5AS Tel: +44 (0) Fax: +44 (0) Ms Kristy Robinson Technical Principal IFRS Foundation 30 Cannon Street London EC4M 6XH 27 January 2016 Dear Kristy This letter sets out the comments of the UK Financial Reporting Council (FRC) on the

More information

Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II

Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II Informational Webinar on Level 2 NERC Alert Ryan Quint, Senior Manager, Advanced Analytics and Modeling Rich Bauer,

More information

MSI Design Examples. Designing a circuit that adds three 4-bit numbers

MSI Design Examples. Designing a circuit that adds three 4-bit numbers MSI Design Examples In this lesson, you will see some design examples using MSI devices. These examples are: Designing a circuit that adds three 4-bit numbers. Design of a 4-to-16 Decoder using five 2-to-4

More information

Transmission Availability Data System Automatic Outage Metrics and Data. Region: RFC 2009 Report

Transmission Availability Data System Automatic Outage Metrics and Data. Region: RFC 2009 Report Transmission Availability Data System Automatic Outage Metrics and Data Region: RFC 2009 Report Table of Contents 1 Introduction... 1 1.1 Contributors and Acknowledgements...1 1.2 TADS History...1 1.3

More information

Parasitically Powered Digital Input

Parasitically Powered Digital Input EVALUATION KIT AVAILABLE Click here for production status of specific part numbers. General Description The is an IEC 61131-2 compliant, industrial digital input (DI) device that translates a 24V digital

More information

Bulk Electric System Definition Reference Document

Bulk Electric System Definition Reference Document Bulk Electric System Definition Reference Document January, 2014 This draft reference document is posted for stakeholder comments prior to being finalized to support implementation of the Phase 2 Bulk

More information

The Engineering Problem. Calculating GIC Flow through the EHV System

The Engineering Problem. Calculating GIC Flow through the EHV System The Engineering Problem Calculating GIC Flow through the EHV System 1 Creating the GIC System Model Since the EHV system is a three-phase balanced network, it is only necessary to model a single-phase

More information

Consultation on Proposed National Rollout of Electricity and Gas Smart Metering

Consultation on Proposed National Rollout of Electricity and Gas Smart Metering Consultation on Proposed National Rollout of Electricity and Gas Smart Metering RESPONSE FROM: Elster Metering Ltd RESPONSE SUBMISSION DATE: 12 th December 2011 DOCUMENT TYPE: Consultation Paper REFERENCE:

More information

Distributed generation on 11kV voltage constrained feeders

Distributed generation on 11kV voltage constrained feeders Distributed generation on 11kV voltage constrained feeders Report produced by University of Strathclyde for the Accelerating Renewables Connection Project Authors: Simon Gill: simon.gill@strath.ac.uk Milana

More information

G1 Capacity Market Metering

G1 Capacity Market Metering G1 Capacity Market Metering EMRS Guidance Public Version: 3.0 Date: 20 April 2018 Table of Contents Change Amendment Record 3 1. Introduction 4 2. Purpose 4 3. What are the allowed types of metering configuration?

More information

PRC Disturbance Monitoring and Reporting Requirements

PRC Disturbance Monitoring and Reporting Requirements Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed

More information