Shunt Capacitance Influences on Single-Phase Transformer FRA Spectrum

Size: px
Start display at page:

Download "Shunt Capacitance Influences on Single-Phase Transformer FRA Spectrum"

Transcription

1 213 Electrical Insulation Conference, #25 Ottawa, Ontario, Canada, 2 to 5 June 213 Shunt Capacitance Influences on Single-Phase Transformer FRA Spectrum Mehdi Bagheri *, B.T. Phung *, Trevor Blackburn *,and Ali Naderian ** * University of New South Wales, Sydney, Australia ** Kinectrics, Transmission and Distribution Technologies, Toronto, ON, Canada Abstract Frequency response analysis (FRA) is considered as an accurate, fast, effective and sensitive method for detection of mechanical defects within power transformers, providing worthy information on active part structure. FRA measurement has been industrialized and employed since the last decade while FRA spectrum interpretation is still under development. The interaction of distributed resistances, series and shunt capacitances as well as self- and mutual-inductances in transformer winding leads to FRA spectrum oscillations. In fact, each and every parameter has its own impact on this spectrum. This study has concentrated on shunt capacitance influences on frequency response spectrum oscillations in Bode diagram. Shunt capacitance impacts on low-, mid- and highfrequency bands of FRA spectrum are discussed. A practical study on a single phase air-core glassy model transformer is carried out to explore the influence of shunt capacitances of HV and LV windings with respect to the transformer tank on FRA spectrum. In addition, a single phase 11/.25 kv, 25 kva core type distribution transformer is also tested to evaluate the shunt capacitance impacts on FRA fluctuations. Keywords- Frequency response analysis, Shunt capacitance, Transformer diagnosis, Transformer winding deformation. I. INTRODUCTION Power transformers are supposed to be and remain in service in various environmental circumstances under different electrical and mechanical stresses [1], [2]. Experience has shown that transformer failure especially in high voltage level like 23 kv or 4 kv can cause irrecoverable harms to pertaining power system. Based on historical data of failure in power transformers, one of the major problems in transformers is mechanical defect [3]. A number of monitoring and diagnostic methods have been introduced to recognize transformer active part displacement and winding deformation [4], [5]. Frequency Response Analysis (FRA) and Short Circuit Impedance (SCI) measurement have been employed as two common diagnosis methods in large power transformer winding deformation recognition [6]. Since SCI measurements are made only at the fundamental frequency, it is expected that they provide less detailed information on the state of the windings than the more comprehensive FRA measurements. Hence, FRA is supposed to be superior to SCI in the case of transformer mechanical defect recognition. Although FRA measurement has been utilized for some years now, FRA spectrum interpretation is still under development [7]. To reach to an acceptable level of FRA result interpretation, the influence of each distributed parameter should be investigated and discussed precisely. To date, a number of studies have been conducted and provided worthy information [8]- [14] on distributed parameters influences. Mathematical and practical studies reveal that more investigation is essential to reach appropriate level of FRA interpretation. Transformer winding resistance, self- and mutual-inductance as well as series and shunt capacitances have their own impacts on the spectrum response [15]- [16]. This study concentrates on shunt capacitance influences on frequency response spectrum oscillations in Bode diagram. Previous mathematical approach on the FRA case [5] is presented to explore shunt capacitance contribution in FRA spectrum. The contribution of this study is more focused on the transformer tank influence on frequency response fluctuations. For precise investigation, a single phase air-core glassy model transformer involving concentric HV and LV windings has been taken as the test object and practical study has been performed on it through different setup configurations. The results are then discussed from a physical perspective. Practical study is also continued through study on the shunt capacitance of a single phase 11/.25 kv, 25 kva core-type distribution transformer and the result is interpreted. II. MATHEMATICAL BACKGROUND Technical specifications and physical characteristics of the transformer under test are major factors in determining the limits of the low-, mid- and high-frequency bands of FRA spectrum. The most appropriate limits for each still not widely agreed. In [17], it has been stated that low-frequency band of FRA spectrum is influenced by the transformer core, mid-frequency band controlled by winding structure and high-frequency band dominated by connection leads. From a physical point of view, winding inductances as well as capacitances play a major role in formation of the frequency response trace. At low frequencies, transformer winding inductances are more dominant as inductive reactance of the transformer winding is considerably greater than capacitive reactance. Hence, frequency response magnitude reported in Bode diagram follows a falling trend as frequency increases. Indeed, self-inductance of transformer winding is greater than mutual inductances. Therefore, low frequency behavior is affected mainly by transformer winding self-inductance (L m ). The winding self-inductance is a function of transformer magnetic core reluctance as well as number of winding turns. Magnetic reluctance of the transformer could be changed due to the core deformation. Any changes in the magnetic reluctance or number of winding turns will lead to self-inductance is changed and followed it the inductive reactance is changed, accordingly. As frequency increases, inductive reactance will take values high enough to be neglected. Synchronously, capacitive reactance /13/$ IEEE 225

2 becomes gradually a major player in the formation of frequency response trace. On the other hand, mutual inductances are considerable in mid frequencies as their inductive reactance becomes significant. Hence, the first anti-resonance (minima) in FRA trace is given as (1) [12], f r( low frequency ) 1 (1) 2 LC m where f r(low-frequency) is the resonance frequency of low-frequency band of FRA spectrum, L m is the winding self-inductance and C denotes total series and shunt capacitances (equivalent capacitance). Series capacitances consist of turn-to-turn and discto-disc capacitances whereas shunt capacitance is the capacitance of winding with respect to the core and to the electrostatic screens/tank. Mid frequency fluctuations of the frequency response are controlled by winding structure including series and shunt capacitances as well as inductances. The resonance frequencies of mid-frequency band within FRA spectrum is given as (2) [5], f k 1 2 ( c k ( ) c ) l r( mid frequency ) g s where f r(mid-frequency) is the resonance frequency of mid-frequency band of FRA spectrum, c g represents shunt capacitance per unit conductor length, c s is series capacitance per unit conductor length, l denotes inductance per unit conductor length, λ is the winding length and k is variable coefficient (k=1, 2, 3 ). According to (2), significant value for c g will increase resonance frequencies, while considerable amount of c s will lead to fewer resonance frequencies within the mid-frequency band of FRA trace [5], [12], [18], [19]. (2) #25 Figure 1. Glassy model transformer For the first experiment, the frequency response trace of the test object has been recorded for HV winding when the terminals of LV winding were left open circuit (end to end measurement). A frequency response analyzer with 2 V pp swept sinusoidal signals as the voltage source was used for entire measurements. Input and output impedances of the measurement cables were 5 ohm. Input signal was injected at the line terminal of the HV winding and the response was recorded at the neutral end. For this measurement, the test object did not have the aluminum wrapping (without tank). Similar measurement was carried out for LV side when the HV winding was left open circuit. Afterwards, the aluminum foil was wrapped over the glass casing to serve as a metal tank. The tank was isolated from the ground and the frequency response traces for HV and LV windings were then recorded. Frequency response traces under such circumstances are shown in Fig. 2 and Fig. 3. A. Case Study 1 III. PRACTICAL STUDY In order to study the impacts of shunt capacitance on FRA trace, a model transformer with air-core concentric continuous disc type HV and LV windings is used as the test object. The HV winding consists of 8 discs including 7 conductor turns per disc. The LV winding has 1 discs with 6 conductor turns per disc. The tank was manufactured by plexiglass. Line and neutral leads of the windings were brought out from the tank through appropriate HV and LV bushings. An aluminum foil has been wrapped over the glass casing to simulate the metal transformer tank. The test object is shown in Fig.1. Four different experiments have been performed on HV and LV windings of the test object. Significant value of the air-core magnetic reluctance of the test object results in small self-inductances for the windings. Hence, inductive reactance due to the self-inductance experiences low value and the resonance frequencies in FRA traces for HV and LV windings would be considerably shifted to higher frequencies. Therefore, the upper band limits for FRA measurements were extended from 2 MHz to 2 MHz to observe entire oscillations. -7 HV-Without Tank HV-With Tank 1.58 MHz, db Figure 2. FRA traces of HV winding in the presence and absence of aluminum tank LV-Without Tank LV-With Tank MHz, db 1.63 MHz, db 1.74 MHz, 1.93 MHz, db Figure 3. FRA traces of LV winding in the presence and absence of aluminum tank 226

3 According to Fig. 2, moving from left hand side to right hand side on the FRA traces, frequency response trace for HV winding with metal tank has shifted to higher frequency at compared to HV without tank. Moving to higher frequencies, oscillation trends in both graphs remain essentially the same. Similar pattern occurred for LV side as seen in Fig.3. The first anti-resonance (minima) and resonance (maxima) have shifted to higher frequencies. Since self-inductance and series capacitance of the HV and LV winding have not changed, the deviations of FRA traces in Fig.2 and Fig.3 come through shunt capacitance changes of the HV and LV winding with respect to the tank. Deviated frequencies are provided in Table I and Table II for HV and LV windings respectively, and shunt capacitance variations are calculated by considering (1). C 1 and C 2 denote the shunt capacitances for f 2 and f 1 respectively. In the case of frequency response trace of HV winding, shunt capacitance variation was estimated 52%, while LV winding reports 59 % approximately. TABLE I. CAPACITANCE RATIO AND ANTI-RESONANCE FREQUENCIES FOR THE SPECTRA OF FIG.2. Minima MHz 1.58 MHz TABLE II. CAPACITANCE RATIO, ANTI-RESONANCE AND RESONANCE FREQUENCIES FOR THE SPECTRA OF FIG.3. Minima 1.74 MHz MHz 1.59 Maxima 1.93 MHz 1.63 MHz For the second measurement, the aluminum tank of the test object was grounded through laboratory earth and FRA trace for HV winding was measured when LV terminals were left open circuit. Similar trace was measured for LV side. HV and LV FRA traces for isolated and grounded tank are shown in Fig.4 and Fig. 5 respectively. According to Fig.4 and Fig.5, numbers of resonance frequencies for grounded tank have been increased as compared to the un-grounded case, in particular the mid-frequency band. It can be interpreted through shunt capacitance increment as it was stated earlier for mid-frequency band. In addition, the magnitude of the first anti-resonance in HV trace and second one in LV trace have changed considerably due to the changes of conductance between HV and LV windings with respect to the tank. This can be interpreted by winding loss factor (conductivity). In fact, any changes in winding loss factors can result in FRA magnitude of resonance/anti-resonance points are changed accordingly. For the third measurement, the aluminum tank has been deformed deliberately as shown in Fig.6. FRA trace for HV winding was recorded when LV winding was left open circuit. Similar measurement was performed for the LV side. HV and LV FRA traces for grounded normal and deformed tanks are illustrated in Fig.7 and Fig. 8. According to Fig.7 and Fig.8, moving from low frequencies towards mid frequencies the first anti-resonances of HV and LV windings have slightly moved to lower frequencies. The same has happened for the first resonance point in LV winding. Based on (1), shifting from higher to lower frequency may be due to the shunt capacitance increment. # HV-Grounded Tank HV-Isolated Tank MHz, db Figure 4. FRA traces of HV winding for isolated and grounded tank. LV-Grounded Tank LV-Isolated Tank 1.74 MHz, MHz, dB MHz, 79 db MHz, db Figure 5. FRA traces of LV winding for isolated and grounded tank. Figure 6. Schematic of the deformed aluminum tank of the test object (top view) HV-Normal Grounded Tank HV-Deformed Grounded Tank MHz, db MHz, db Figure 7. FRA traces of HV winding for normal and deformed tank. 227

4 # MHz, db MHz, db MHz, db MHz, db MHz,.79 db 4.59 MHz, db -45 LV-Normal Grounded Tank MHz, MHz, LV-Deformed Grounded Tank db db Figure 8. FRA traces of LV winding for grounded normal and deformed tank. TABLE III. CAPACITANCE RATIO AND ANTI-RESONANCE FREQUENCIES FOR THE SPECTRA OF FIG.7. Minima MHz MHz 1.21 TABLE IV. CAPACITANCE RATIO, ANTI-RESONANCE AND RESONANCE FREQUENCIES FOR THE SPECTRA OF FIG.8 Minima MHz MHz Maxima MHz MHz Measured frequencies for the first HV and LV anti-resonances are provided in Table III and Table IV. Table IV also shows the frequency of the first resonance point of LV trace. Based on the calculated capacitance ratio in Table III and Table IV, shunt capacitance deviation for HV was 2.1%, while the values for LV side were estimated at 16.8%. As the last study on glassy test object, the deformed aluminum tank was isolated from the ground and HV FRA trace was measured when LV was left open circuit. Similar measurement was performed for LV winding. HV and LV FRA traces for isolated normal and deformed tank are shown and compared in Fig.9 and Fig. 1. Table V and Table VI provide frequency variations as well as capacitance ratio for the FRA traces of HV and LV windings. According to Fig.9 and Fig.1, the first anti-resonances of the HV and LV windings have slightly shifted to lower frequencies in low-frequency band, while mid-frequency oscillations have perfectly remained the same. Capacitance ratios in Table V and Table VI show around 14% changes for anti-resonances and 11.6% for the first resonance point in LV winding. It may be concluded that the shunt capacitance for HV and LV windings with respect to tank have increased 14% approximately. LV-Normal Isolated Tank LV-Deformed Isolated Tank MHz,.69 db 1.74 MHz, Figure 1. FRA traces of LV winding for isolated normal and deformed tank. TABLE V. CAPACITANCE RATIO AND ANTI-RESONANCE FREQUENCIES FOR THE SPECTRA OF FIG.9. Minima MHz MHz TABLE VI. CAPACITANCE RATIO, ANTI-RESONANCE AND RESONANCE FREQUENCIES FOR THE SPECTRA OF FIG.1 Minima 1.74 MHz MHz Maxima MHz MHz B. Case Study 2 In order to study shunt capacitance impact of HV winding respect to the LV winding, a single phase 11/.25 kv, 25 kva core-type transformer was taken as another test object and FRA traces for its HV winding were recorded for different configurations. At first, FRA trace was recorded for HV side when the line and neutral terminals of LV winding were shortcircuited and isolated from the ground. Afterwards, the LV winding was grounded and the FRA trace for HV side was remeasured. Test setups were configured as shown in Fig. 11(a) and 11(b). In fact, the configurations in Fig. 11 can identify turn-toturn or disc-to-disc short circuits which are isolated or directly connected to transformer tank or core. (a) (b) Fig. 11. FRA test setup (a) LV is short-circuited (b) LV is short-circuited and grounded khz, db HV-Normal Isolated Tank HV-Deformed Isolated Tank MHz, Figure 9. FRA traces of HV winding for isolated normal and deformed tank. -7 HV-LV is shortened HV-LV is shortened and grounded 9.3 khz, db Fig. 12. FRA of HV winding for different configurations of LV. 228

5 #25 In Fig. 12, frequency response traces of HV winding for grounded and isolated internal short circuit are illustrated and compared to explore why FRA trace has deviated. According to Fig. 12, frequency response trace for grounded internal short circuit is not deviated from isolated one in very low frequencies. In fact, self-inductance of the HV winding does not change for grounded and isolated internal short circuit. Also, moving from very low frequencies to low frequencies shows that minimal peak has slightly moved to right. In addition, in mid and high frequencies grounded internal short circuit trace displays greater absolute magnitude compared to isolated one, while oscillation trends in both graphs remain approximately the same. Since HV winding structure has not changed and short circuit has apparently happened in LV winding, series capacitance of HV winding has not varied, accordingly. Based on this fact, minimal peak movement in Fig. 12 can be interpreted due to the winding shunt capacitance variations. Indeed, resonance point movement in the grounded internal short circuit trace to higher frequency indicates a slight reduction in shunt capacitance of the winding. On the other hand, capacitive reactance increases when capacitance of the winding decreases. This in turn results in greater absolute frequency response magnitude in mid and high frequencies. Therefore, self-inductance does not change during isolated and grounded internal short circuit while total capacitance has been decreased. IV. CONCLUSION Mechanical defects and transformer frequency response measurement were discussed. It was elaborated that transformer winding inductance, series and shunt capacitances have their own influence on FRA trace. Practical study indicated that the winding shunt capacitance can specifically influence low- and mid- and high-frequency bands of FRA spectrum. The shunt capacitance of HV and LV windings with respect to the tank had more impact on the first anti-resonance in FRA trace and generally impacted on low-frequency band. The shunt capacitance of the HV winding with respect to the LV winding influenced more the mid- and high frequency band. Grounding of the test object tank led to total capacitance variation and also increasing numbers of resonance frequencies within the mid-frequency band. In addition, it caused considerable damping of the resonant peaks of mid-frequency band of FRA spectrum. It could be interpreted through conductivity variation of the HV winding respect to the tank. Since this study concentrated on single-phase transformers, further investigations will be conducted on three-phase transformers. REFERENCES [1] M. Bagheri, Mohammad S. Naderi, T. Blackburn, B.T. Phung, Dean-Stark vs FDS and KFT methods in moisture content recognition of transformers, IEEE Int I Conf. Power Energy (PECON 12), Kota Kinabalu, Malaysia, 212, pp [2] M. Bagheri, Mohammad S. Naderi, T. Blackburn, B.T. Phung, Transformer efficiency and de-rating evaluation with non-sinusoidal loads, IEEE Int l. Conf. Power Sys. Tech. (POWERCON 12), Auckland, New Zealand, 212, pp [3] M. Bagheri, Mohammad S. Naderi, T. Blackburn, B.T.Phung, Bushing characteristic impacts on on-line frequency response analysis of transformer winding, IEEE Int I Conf. Power Energy (PECON 12), Kota Kinabalu, Malaysia, 212, pp [4] M. Florkowski, J. Furgal,P. Pajak, Analysis of fast transient voltage distributions in transformer windings under different insulation conditions, IEEE Trans. Dielectr. Electr. Insul., vol. 19, 212, pp [5] M. Bagheri, Mohammad S. Naderi, T. Blackburn, D. Zhang, Transformer frequency response analysis: A mathematical approach to interpret midfrequency oscillations, IEEE Int I Conf. Power Energy (PECON 12), Kota Kinabalu, Malaysia, 212, pp [6] M. Bagheri, Mohammad S. Naderi, T. Blackburn, B.T. Phung, Frequency response analysis and short circuit impedance measurement measurement in detection of winding deformation within power transformers, IEEE Electr. Insul. Mag.,vol. 29, issue 3, 213, pp. 33. [7] M. Bagheri, Mohammad S. Naderi, T. Blackburn, B.T. Phung, Z.Liu Frequency response analysis to recognize inductance variation in transformer due to internal short circuit, IEEE Int l Power Energy Conf. (IPEC 12), Ho Chi Minh City, Vietnam, 212, pp [8] M. Bagheri, Mohammad S. Naderi, T. Blackburn, Advanced transformer winding deformation diagnosis: moving from off-line to on-line, IEEE Trans. Dielectr. Electr. Insul., 212, pp [9] E. P. Dick and C. C. Erven, Transformer diagnostic testing by frequency response analysis, IEEE Trans. Power App. Syst., vol. PAS-97, no. 6, 1978, pp [1] M. Bagheri, Mohammad S. Naderi, T. Blackburn, T. Phung, FRA vs. short circuit impedance measurement in detection of mechanical defects within large power transformer, IEEE Int l. Sympos. Electr. Insul. (ISEI 12), Puerto Rico, USA, 212, pp [11] K. G. N. B. Abeywickrama, Y. V. Serdyuk, S. M. Gubanski, Exploring possibilities for characterization of power transformer insulation by frequency response analysis (FRA), IEEE Trans. Power Del., vol. 21, 26, pp [12] Z. Wang, J. Li, D.M. Sofian, Interpretation of Transformer FRA responses Part I: Influence of Winding Structure, IEEE Trans. Power Del., vol 24, issue 2, pp.73-71, 29. [13] M. Bagheri, Mohammad S. Naderi, T. Blackburn, B.T. Phung, Frequency Response Analysis vs. Flux Division Measurement in detection of transformer winding internal short circuit, IEEE Int l. Conf. Power Sys. Tech. (POWERCON 12), Auckland, New Zealand, 212, pp [14] M. Bagheri, Mohammad S. Naderi, T.R. Blackburn and B.T. Phung, Practical challenges in online transformer winding deformation diagnostics, Int l. Conf. Electric Power and Energy Conversion Syst. (EPECS 11), Sharjah, UAE, 211, pp [15] M. Bagheri, Mohammad S. Naderi, T. Blackburn, T. Phung and H. Haeri, On-line transformer winding deformation diagnosis: A profound insight to methods, 26 th Int l Power Sys. Conf. (PSC 11), Tehran, Iran, 211, pp [16] M. Bagheri, Mohammad S. Naderi, T. Blackburn, T. Phung, Case study on FRA capability in detection of mechanical defects within a 4MVA transformer, CIGRE, Paris, France, 212, pp [17] IEC Standard ; Measurement of frequency response, Edition 1., [18] M. Bagheri, A. Hekmati, R. Heidarzadeh, Mohammad S. Naderi, Impulse voltage distribution in intershield disk winding vs interleaved and continuous disk winding in power transformer, IEEE Power and Energy Conf. (PECON 8), pp [19] M. Bagheri, M.Vakilian, A.Hekmati, R.Heidarzadeh, Influence of electrostatic shielding of disc winding on increasing the series capacitance in transformer, IEEE PowerTech 7, Lausanne, Switzerland, 27, pp

A Literature Survey on Frequency Response Analysis for Detection of Transformer Winding Fault

A Literature Survey on Frequency Response Analysis for Detection of Transformer Winding Fault IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 07, 2015 ISSN (online): 2321-0613 A Literature Survey on Frequency Response Analysis for Detection of Transformer Winding

More information

INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER

INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER Volume: 03 Issue: 07 July16 www.irjet.net p-issn: 2395-0072 INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER Sameer S. Patel 1, 1 Student, Electrical Dept, Rajasthan Institute

More information

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis Ambuj Kumar, Sunil Kumar Singh, Shrikant Singh Abstract Sweep frequency response analysis has been turning out a

More information

Performing reliable and reproducible frequency response measurements on power transformers

Performing reliable and reproducible frequency response measurements on power transformers Topic Performing reliable and reproducible frequency response measurements on power transformers Prof. Dr. Stephanie Uhrig, Munich University of Applied Sciences Michael Rädler, OMICRON electronics GmbH

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage Grupesh Tapiawala Raychem Innovation Centre Raychem RPG (P) Ltd Halol, India

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA) Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA) Priti G 1*, Sindekar AS 2 P.G. Scholar, Department of Electrical Engineering, Government College of

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 2321-0613 Conditioning Monitoring of Transformer Using Sweep Frequency Response for Winding Deformation

More information

متلب سایت MatlabSite.com

متلب سایت MatlabSite.com 11-E-TRN-1315 Determining Intensity of Radial Deformation and Axial Displacement of Transformer Winding Using Angular Proximity Index K.Pourhossein Tabriz Branch, Islamic Azad University, Tabriz, Iran

More information

Vallabh Vidyanagar, Anand, INDIA

Vallabh Vidyanagar, Anand, INDIA IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 1 Ver. V (Feb. 2014), PP 01-06 Interpretation of Sweep Frequency Response Analysis

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Matz Ohlen Director Transformer Test Systems. Megger Sweden Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Research Article Transformer Winding Deformation Profile using Modified Electrical Equivalent Circuit

Research Article Transformer Winding Deformation Profile using Modified Electrical Equivalent Circuit Research Journal of Applied Sciences, Engineering and Technology 9(4): 288-295, 215 DOI:1.1926/rjaset.9.147 ISSN: 24-7459; e-issn: 24-7467 215 Maxwell Scientific Publication Corp. Submitted: August 13,

More information

Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method

Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method C. Homagk 1*, T. Leibfried 1, K. Mössner 1 and R. Fischer 1 Institute of Electric

More information

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Miss. Kajal R. Pachbhai PG Student at Ballarpur Institute of Technology, Ballarpur-442701 India kajalpachbhai86@gmail.com Mr. Sagar

More information

Improved Method for Winding Deformation Detection Sensitivity in Transformer

Improved Method for Winding Deformation Detection Sensitivity in Transformer International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 10ǁ October 2013 ǁ PP.48-55 Improved Method for Winding Deformation Detection Sensitivity

More information

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks Mohammad Tavakoli Bina, G.N.Alexandrov and Mohammad Golkhah Abstract A new shunt reactive power compensator,

More information

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 38 CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 3.1 INTRODUCTION Addition of more generating capacity and interconnections to meet the ever increasing power demand are resulted in

More information

Be on guard for effective testing: Introduction

Be on guard for effective testing: Introduction Be on guard for effective testing: Introduction The development of the insulation tester by Evershed and Vignoles is part of our electrical history, with insulation testers produced by Megger Instruments

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

FRAX Series Sweep Frequency Response Analyzers

FRAX Series Sweep Frequency Response Analyzers FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software. FRAX 150 with built

More information

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding Research Journal of Applied Sciences, Engineering and Technology 10(10): 1102-1107, 2015 DOI: 10.19026/rjaset.10.1879 ISSN: 2040-7459; e-issn: 2040-7467 2015 Maxwell Scientific Publication Corp. Submitted:

More information

EFFECT OF RADIAL AND AXIAL MOVEMENT OF WINDING ON COHERENCE FUNCTION IN A 220/132 KV, 100 MVA, AUTO TRANSFORMER

EFFECT OF RADIAL AND AXIAL MOVEMENT OF WINDING ON COHERENCE FUNCTION IN A 220/132 KV, 100 MVA, AUTO TRANSFORMER EFFECT OF RADIAL AND AXIAL MOVEMENT OF WINDING ON COHERENCE FUNCTION IN A 220/132 KV, 100 MVA, AUTO TRANSFORMER K.Shashidhar Reddy 1 Vishal Kulkarni 2, St.Martin s Engineering College, Dhulapally, Secunderabad,

More information

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)

More information

A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2

A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2 A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding Mohammed Abd Ali Aziz 1, Zulkurnain Abdul-Malek 2 1 Ministry of Electricity, Republic of Iraq 2 Institute of

More information

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Abstract: A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Vijay Bendre, Prof. Pat Bodger, Dr. Alan Wood. Department of Electrical and Computer Engineering, The University of

More information

Core Technology Group Application Note 1 AN-1

Core Technology Group Application Note 1 AN-1 Measuring the Impedance of Inductors and Transformers. John F. Iannuzzi Introduction In many cases it is necessary to characterize the impedance of inductors and transformers. For instance, power supply

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,

More information

AN IMPROVED MODEL FOR ESTIMATING RADIATED EMISSIONS FROM A PCB WITH ATTACHED CABLE

AN IMPROVED MODEL FOR ESTIMATING RADIATED EMISSIONS FROM A PCB WITH ATTACHED CABLE Progress In Electromagnetics Research M, Vol. 33, 17 29, 2013 AN IMPROVED MODEL FOR ESTIMATING RADIATED EMISSIONS FROM A PCB WITH ATTACHED CABLE Jia-Haw Goh, Boon-Kuan Chung *, Eng-Hock Lim, and Sheng-Chyan

More information

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS PERODCA POLYTECHNCA SER. EL. ENG. VOL. 41, NO. 1, PP. 27-40 (1997) OVERVOLTAGE PROTECTON OF POLE MOUNTED DSTRBUTON TRANSFORMERS Attila SOMOGY and Lasz16 VZ Department of Electric Power Systems Technical

More information

TRANSFORMER TECHNOLOGY GPT

TRANSFORMER TECHNOLOGY GPT Core-Form TRANSFORMER TECHNOLOGY GlobalPT Corporation performs research and engineering developments and co-ordination of works of technical partners in the field of technological progress and commercial

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Analysis of Frequency Response measurement results with end-to-end/interwinding test setup correlation

Analysis of Frequency Response measurement results with end-to-end/interwinding test setup correlation ARCHIVES OF ELECTRICAL ENGINEERING VOL. 67(1), pp. 51 64 (2018) DOI 10.24425/118991 Analysis of Frequency Response measurement results with end-to-end/interwinding test setup correlation SZYMON BANASZAK,

More information

AN ANN BASED FAULT DETECTION ON ALTERNATOR

AN ANN BASED FAULT DETECTION ON ALTERNATOR AN ANN BASED FAULT DETECTION ON ALTERNATOR Suraj J. Dhon 1, Sarang V. Bhonde 2 1 (Electrical engineering, Amravati University, India) 2 (Electrical engineering, Amravati University, India) ABSTRACT: Synchronous

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

Design and Analysis of Resonant Harmonic Filter

Design and Analysis of Resonant Harmonic Filter Design and Analysis of Resonant Harmonic Filter M.Raja Vidya Bharathi, AP/EEE T.Arputhamary, AP/EEE J.Divineshia Sharon, AP/EEE K.B.P. Mahavishnu, AP/EEE DMI College of Engineering,Chennai-6000123 Abstract

More information

Transient Recovery Voltage at Transformer Limited Fault Clearing

Transient Recovery Voltage at Transformer Limited Fault Clearing Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H.

More information

Power Transformer Condition Assessment Based on Standard Diagnosis

Power Transformer Condition Assessment Based on Standard Diagnosis Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of

More information

Impact of Power Transformer Insulating Mineral Oil Degradation on FRA Polar Plot

Impact of Power Transformer Insulating Mineral Oil Degradation on FRA Polar Plot Copyright 2015 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material

More information

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik,

More information

Transformer Winding Deformation Analysis using SFRA Technique

Transformer Winding Deformation Analysis using SFRA Technique Journal for Research Volume 01 Issue 11 January 2016 ISSN: 2395-7549 Transformer Winding Deformation Analysis using SFRA Technique Mr. Patil Ritesh Anil PG Student Prof. G.K.Mahajan Associate Professor

More information

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,

More information

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is

More information

Transformers handling and transport

Transformers handling and transport Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Effects of GIC on Power Transformers and Power Systems

Effects of GIC on Power Transformers and Power Systems Effects of GIC on Power Transformers and Power Systems Prepared by Dr. Ramsis Girgis and Kiran Vedante (USA) in the name of CIGRE SC A2 Background There has been some misconception in the electric power

More information

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation P.S.Diwakar High voltage Engineering National Engineering College Kovilpatti, Tamilnadu, India S.Sankarakumar Department

More information

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan

More information

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments

More information

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James School of Electrical Engineering and Telecommunications University of New South Wales, Australia

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks

Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks Diptargha Chakravorty Indian Institute of Technology Delhi (CES) New Delhi, India diptarghachakravorty@gmail.com Jan

More information

Common myths, fallacies and misconceptions in Electromagnetic Compatibility and their correction.

Common myths, fallacies and misconceptions in Electromagnetic Compatibility and their correction. Common myths, fallacies and misconceptions in Electromagnetic Compatibility and their correction. D. A. Weston EMC Consulting Inc 22-3-2010 These are some of the commonly held beliefs about EMC which are

More information

The design of Ruthroff broadband voltage transformers M. Ehrenfried G8JNJ

The design of Ruthroff broadband voltage transformers M. Ehrenfried G8JNJ The design of Ruthroff broadband voltage transformers M. Ehrenfried G8JNJ Introduction I started investigating balun construction as a result of various observations I made whilst building HF antennas.

More information

Methods of secondary short circuit current control in single phase transformers

Methods of secondary short circuit current control in single phase transformers 2015; 1(8): 412-417 ISSN Print: 2394-7500 ISSN Online: 2394-5869 Impact Factor: 5.2 IJAR 2015; 1(8): 412-417 www.allresearchjournal.com Received: 17-05-2015 Accepted: 20-06-2015 Parantap Nandi A/2, Building

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS Qin Jiang School of Communications & Informatics Victoria University P.O. Box 14428, Melbourne City MC 8001 Australia Email: jq@sci.vu.edu.au

More information

Benefits of SFRA - Case Studies

Benefits of SFRA - Case Studies 6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

Transformer Technology Seminar Winding Selection

Transformer Technology Seminar Winding Selection Pomona, CA May 24 25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Windings: Page 2 Example GSU 274/464MVA H0 H1 H2 H3 U U I I H L H L N = N N = N L H H L HV: 405kV ±8x1.25%

More information

Mitigating Murphy s Law While Test. Frédéric Dollinger

Mitigating Murphy s Law While Test. Frédéric Dollinger Mitigating Murphy s Law While Test Frédéric Dollinger Curriculum Vitae Frédéric Dollinger HAEFELY HIPOTRONICS factory Basel Switzerland Area Sales & Marketing Manager Dipl. Ing. / M.Sc. Mechatronic Language:

More information

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment Australasian Universities Power Engineering Conference (AUPEC 24) 26-29 September 24, Brisbane, Australia Correlation between time and frequency domain polarisation measurements for transformer moisture

More information

RESONANT TRANSFORMER

RESONANT TRANSFORMER RESONANT TRANSFORMER Whenever the requirement of the test voltage is too much high, a single unit transformer can not produce such high voltage very economically, because for high voltage measurement,

More information

Variation in SFRA plot due to design and external parameter

Variation in SFRA plot due to design and external parameter Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements

More information

FRAX Series Sweep Frequency Response Analyzers

FRAX Series Sweep Frequency Response Analyzers FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software Imports data from other

More information

A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE

A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE Mojtaba Rostaghi-Chalaki, A Shayegani-Akmal, H Mohseni To cite this version: Mojtaba Rostaghi-Chalaki, A Shayegani-Akmal,

More information

University of Pennsylvania Department of Electrical and Systems Engineering ESE319

University of Pennsylvania Department of Electrical and Systems Engineering ESE319 University of Pennsylvania Department of Electrical and Systems Engineering ESE39 Laboratory Experiment Parasitic Capacitance and Oscilloscope Loading This lab is designed to familiarize you with some

More information

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements EMEL ONAL Electrical Engineering Department Istanbul Technical University 34469 Maslak-Istanbul TURKEY onal@elk.itu.edu.tr http://www.elk.itu.edu.tr/~onal

More information

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM G.SUNDAR, S.RAMAREDDY Research Scholar, Bharath University Chenna Professor Jerusalam College of Engg. Chennai ABSTRACT This paper deals with simulation

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer. 208 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 A Sequential Phase Energization Method for Transformer Inrush Current Reduction Transient Performance and Practical Considerations

More information

Experiment 4: Grounding and Shielding

Experiment 4: Grounding and Shielding 4-1 Experiment 4: Grounding and Shielding Power System Hot (ed) Neutral (White) Hot (Black) 115V 115V 230V Ground (Green) Service Entrance Load Enclosure Figure 1 Typical residential or commercial AC power

More information

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion

More information

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.

More information

Importance of Transformer Demagnetization

Importance of Transformer Demagnetization Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance

More information

ISSN: [IDSTM-18] Impact Factor: 5.164

ISSN: [IDSTM-18] Impact Factor: 5.164 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant

More information

A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection.

A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection. International Conference on Power Systems Transients IPST 3 in New Orleans, USA A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection. M A Redfern, S C Terry,

More information

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH Michael Freiburg Erik Sperling Michael Krueger OMICRON Austria

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Experiment 5: Grounding and Shielding

Experiment 5: Grounding and Shielding Experiment 5: Grounding and Shielding Power System Hot (Red) Neutral (White) Hot (Black) 115V 115V 230V Ground (Green) Service Entrance Load Enclosure Figure 1 Typical residential or commercial AC power

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans. Electronic Measurements & Instrumentation

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans.   Electronic Measurements & Instrumentation UNIT 2 Q.1) Describe the functioning of standard signal generator Ans. STANDARD SIGNAL GENERATOR A standard signal generator produces known and controllable voltages. It is used as power source for the

More information