A METHOD FOR THE CORRECT PROTECTION RESPONSE DURING POWER SYSTEM FAULTS SUBJECTED TO THE BAUCH S PARADOX PHENOMENON

Size: px
Start display at page:

Download "A METHOD FOR THE CORRECT PROTECTION RESPONSE DURING POWER SYSTEM FAULTS SUBJECTED TO THE BAUCH S PARADOX PHENOMENON"

Transcription

1 3 rd nternational Conference on Electricity Distribution Lyon, 5-8 June 5 Paper 448 A METHD FR THE CRRECT PRTECTN RESPNSE DRNG PWER SYSTEM FALTS SBJECTED T THE BACH S PARADX PHENMENN Cezary DZENS Matthias KERET Joerg BLMSCHEN SEMENS AG Germany SEMENS AG Germany SEMENS AG Germany cezary.dzienis@siemens.com matthias.kereit@siemens.com joerg.blumschein@siemens.com Michael CLAS SEMENS AG Germany michael.claus@siemens.com Gustav STEYNBERG SEMENS AG Germany gustav.steynberg@siemens.com ABSTRACT False tripping is frequently blamed on incorrect settings or poor system models. However in many cases, it may be attributed to not uncommon phenomena, such as the so called Bauch s paradox. n this paper the physical background of the Bauch s paradox phenomena will be explained. Based on this, a method for the correct response of distance protection under these extreme conditions is presented. Amongst others, this method consists of: the detection of the Bauch s paradox phenomena, optimised loop selection logic and a modified directional element. Chosen events recorded during distance protection test are used to illustrate the effectiveness of this method. NTRDCTN The classical power system fault on the transmission/ distribution line is characterised by typical behavior in currents and voltages. n most cases, the voltages drop and currents increase in faulty phases/loops as well as the phase shift between currents and voltages is close to the angle line impedance Z L. These rather trivial properties are used successfully by the numerous protection functions guarantying a selective and reliable protection operation. Nevertheless in some network configurations combined with common network operation states the voltages and currents are not significant enough to recognize the faulty phases or loops. As a result the reliable operation in the protection function is not guaranteed. The extension of protection functions is necessary to recognize such untypical behaviour. Bauch s paradox belongs to non classical fault transients. Therefore the recognition of the faulty loops/phases cannot be carried out using the traditional current/voltage pattern. n the case of Bauch s paradox, all currents are in the same electric phase and have the same magnitudes. Due to this fact, numerous protection algorithms cannot properly detect the faulty loop. n this paper, attention is paid to distance protection and its improvement in the case of Bauch s PHYSCAL BACKGRND F THE BACH S PARADX This phenomenon appears at a transmission or distribution line operating in a radial configuration. The strong, in-feed side does not need to be earthed. The second line side is solid earthed, has a weak in-feed and is connected with the other voltage level over a Star- Delta (Yd) grounding transformer. This configuration is very popular, especially if renewable dispersed energy sources are connected to the power system. The second condition for the phenomenon is the occurrence of the non-symmetrical fault with the earth connection. n figure, the condition for Bauch s paradox is illustrated. The current flow direction is marked using arrows. They also show relations between flowing currents. Figure : Equivalent circuit of the line under fault conditions (phase-to-earth fault during Bauch s paradox) The configuration of the transformer from figure allows for the propagation of the zero sequence component (represented as earth current), as presented in the equivalent circuit in the symmetrical component, based on figure. Since the very high magnetising, zero sequence impedance is connected to the leakage impedance of the secondary side the summarised impedance of the transformer (Yd) in zero sequence is relatively low. Therefore, due to unsymmetrical conditions the zero sequence current flows through transformer windings. Since the secondary windings are connected in Delta, the zero-sequence current cannot propagate outside of the transformer. This current circulates in secondary transformer windings, inducing currents on the primary side which are in phase and have the same magnitudes. CRED 5 /5

2 3 rd nternational Conference on Electricity Distribution Lyon, 5-8 June 5 Paper 448 network impedances including the impedance of the earth path, fault location. THE BACH S PARADX N SYMMETRCAL CMPNENTS Figure : Star-Delta (Yd) grounding transformer 3-phase model. Since the single phase-to-earth or double phase-to-earth fault contributes to a strong un-symmetry in the network with a high zero sequence voltage component, the zero sequence current is flowing into the network. n figure 3 the electric circuit for the single phase-to-earth fault is presented. The strong, in-feed side of the network is not earthed. This assumption does not limit the consideration subjected to Bauch s paradox but simplifies the understanding of the phenomenon. Through analysing the voltages and currents and based on the equivalent circuits from figure 3 and 4, it can be concluded that phase quantities deliver distorted patterns according to the fault type. For better handling of this problem the symmetrical components should be involved in what is described in this section. Figure 3: Single phase-to-earth fault during Bauch s Figure 5: Current propagation in symmetrical components during single phase-to-earth fault (Bauch s paradox). Figure 4: Double phase-to-earth fault during Bauch s The single phase-to-earth fault causes the strong zero sequence voltage component. Since the strong, in-feed side is not grounded, the zero-sequence component can only propagate in transformer windings. Here it should be observed that zero sequence current can only be seen on side B of the network. Moreover the earth current is three times higher than the phase current. n figure 4, the circuit for the phase-to-phase with an earth fault is presented. Also, the strong distinct zero sequence current can be observed as well as similar effects, like the single phase-to-earth fault. The intensity of Bauch s paradox phenomenon depends on a number of network parameters: short circuit power of a strong, in-feed source, short circuit power of the transformer of the weak, in-feed side, Figure 6: Current propagation in symmetrical components during double phase-to-earth fault (Bauch s paradox). CRED 5 /5

3 3 rd nternational Conference on Electricity Distribution Lyon, 5-8 June 5 Paper 448 For both of these fault types, two different equivalent sequence circuits should be considered. n the case of single phase-to-earth faults, the sequence networks are connected to each other in series. t was assumed that the strong, in-feed side is not grounded. As a result, the zero sequence current of the strong, in-feed side A is not available. Due to the relatively low zero sequence impedance of the transformer, the fault current propagates through side B and can be measured there in zero sequence. The side A sees the fault current in negative and positive sequence. Because of that, only side B will recognize the phenomenon of Bauch s f the fault is located outside of the line, in the direction of the strong, in-feed side, both sides will experience Bauch s n the case of the external fault in the direction of the transformer, neither side experiences Bauch s Based on figure 5 and 6 it can be observed that side B does not measure negative or positive sequence. Due to this fact, only zero sequence can be used for the detection of the fault. X/hm Figure 7: mpedance trajectories during single phase-toearth fault with Bauch s MPACT N DSTANCE PRTECTN During Bauch s paradox the conventional distance protection algorithm can show some weaknesses, as mentioned here: n case of the single phase-to-earth fault computed impedance of non-faulty loop (apparent impedance) can lie in the so called operating polygon. t results from a significant earth current. n addition the conventional direction element can show the wrong direction result. t can contribute to an unselective or delayed trip. n the case of the phase-to-phase earth fault, the preferred double phase loop impedance cannot be computed, because the difference between phase currents is zero. For the fault handling, the single phase-to-earth loops and their impedances must be involved. This has negative consequences on determining the direction using directional elements. Namely one of the single phase loops determines the forward fault direction. The second single phase loop recognizes the reverse fault direction. t contributes to the unacceptable sequential or unselective trip. Moreover, due to low load flow, it can happen that the preferred double phase impedance are calculated, delivering a random result. Figure 8: Response of a classical distance protection during a reverse single phase-to-earth fault with Bauch s ne can observe that the distance protection determines a wrong loop and as a consequence, measures the wrong fault direction. Figure 9: mpedance trajectories during double phase-toearth fault with Bauch s CRED 5 3/5

4 3 rd nternational Conference on Electricity Distribution Lyon, 5-8 June 5 Paper 448 il/ A -5 5 il/ A il3/ A -5 5 E*/ A - 5 ul/ V -5 5 ul/ V -5 ul3/ V - Trip L Trip L Trip L3 Pickp E Forward Reverse typical currents during Bauch s paradox Figure : Response of a classical distance protection during a forward double phase-to-earth fault with Bauch s ne can observe that distance protection detects the single-phase-to-earth fault and does not clear disturbance completely. The direction results are not plausible. PTMZATN N DSTANCE PRTECTN After considering the Bauch s paradox in symmetrical components, it can be concluded, that zero sequence quantity is a basis for detection of a faulty loop, as well as for determining a fault direction. Firstly, the Bauch s paradox effect must be detected. t is proposed that the zero sequence current is compared with the positive and negative sequence. f the zero sequence current is significantly higher than both other components, then the Bauch s paradox can be assumed. Mathematically it can be expressed in the following way: 3 () k 3, 3 k 3 where k>> is a comparison factor. This factor allows for detection of the Bauch s paradox even if a load flow at the considered line takes place. n order to confirm Bauch s paradox definitively, the zero sequence current is compared to the phase currents. The comparison takes place based on the magnitudes only. The requirement according to the equaled electric phases of the flowing currents during Bauch s paradox is covered during comparison with the symmetrical components. Following expressions describe the comparison process with a zero sequence: k k, k k A B C k k A B C,, () where ku and ko are the appropriate limits, which test if the currents are in the assumed range, signifying Bauch s After detection of the phenomenon the faulty loop must be determined. As a result the symmetrical components for voltage are involved. After considering the figure (double phase-to-earth fault), one can conclude that for this fault type, the negative and positive sequence voltages are equal. n order to determine the faulty loop, the phasor comparison between negative and positive sequences must be carried out. Since in conventional approach for symmetrical components one phase is considered as the reference phase, the difference between both phasor components can be, or 4. For a simplification in approach, the computed negative sequence voltage is rotated additionally by and 4 degrees. Thus, three differences are created and only one corresponds to the faulty loop: (3) j j4 e e where and are positive and negative sequence voltages respectively. The exponential complex component represents the phase shift. Since measurement errors are possible and load flow takes place on the line, the difference between positive and negative component can deviate from. Due to this fact it is recommended to calculate an adaptive difference limit in dependence from both considered components. To this end, we propose the following equation: m max(, ) M (4) where m and M are a percent factor and constant threshold respectively. f the criteria from formula 3 is not fulfilled the single phase-to-earth fault is detected in the loop, where the measured phase-to-earth voltage is lowest. As mentioned during the Bauch s paradox phenomenon, the directional element cannot operate loop-oriented. For a fault direction determination, the zero sequence current and voltage must be involved. This means that, independent from the faulty loop, only one directional element based on the zero sequence is applied. The characteristic for the fault direction is presented in figure. The idea of the zero sequence direction measurement consists in analysing the membership of the voltage and current phasors on the complex plane. For the forward fault, it is expected that both phasors are located in the first quadrant of the complex plane. f the reverse fault occurred, the phasors are placed in the third quadrant. A low deviation in phasor localisation according to quadrant membership is allowed. CRED 5 4/5

5 3 rd nternational Conference on Electricity Distribution Lyon, 5-8 June 5 Paper 448 / V 5-5 Reverse Fault LE / V / V / A / A Figure : The directional characteristic with zerosequence component. RESLTS AND SMMARY The experimental tests of the proposed algorithm were performed on a digital relay. The typical high-voltage radial feeder with both strong and weak in-feed side (connected to Yd transformer) was modelled. The different faults were simulated in order to prove the behaviour of the device. The responses of the device on typical faults were as expected. Also in the case of the fault during Bauch s paradox, device behaviour was satisfying. n this paper we presented three fault cases with the responses of the digital relays. 3/ A Trip L Trip L Trip L3 Pickp L Pickp L Pickp L3 Pickpp E Forward Reverse Figure 3: Single phase-to-earth fault in reverse direction with Bauch s ptimized distance protection algorithm indicates correct loop and does not trip. Figure 4: Double phase-to-earth fault in forward direction. ptimized distance protection algorithm indicates correct loop and trip. REFERENCES Figure : Single phase-to-earth fault in forward direction with Bauch s ptimized distance protection algorithm indicates correct loop and trip. [] C. Dzienis, M. Kereit, G. Steynberg and M. Claus, 4, "Behandlung von Netzfehlern mit Bauch schem Paradoxon", STE ETG Konferenz [] G. Ziegler, 8, Distanzschutz, Grundlagen und Anwendungen, Siemens AG, Berlin, Germany. [3] A. Hochrainer, 957, Symmetrische Komponenten in Drehstromsystemen, Springer, Berlin, Germany. [4] R. Roeper, 985, Short Circuit Currents in Threephase Systems, John Wiley and Sons, Berlin, Germany. CRED 5 5/5

NEW DESIGN OF GROUND FAULT PROTECTION

NEW DESIGN OF GROUND FAULT PROTECTION NEW DESIGN OF GROUND FAULT PROTECTION J. Blumschein*, Y. Yelgin* *SIEMENS AG, Germany, email: joerg.blumschein@siemens.com Keywords: Ground fault protection, directional element, faulted phase selection

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Differential Protection Optimal differential protection for phase shifter transformers and special transformers Differential Protection Optimal differential protection for phase shifter transformers and special transformers Due to the energy transition, a demand for renewable energy sources integration into power

More information

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer

More information

DIRECTIONAL PROTECTION

DIRECTIONAL PROTECTION UNIVERSITY OF LJUBLJANA FACULTY OF ELECTRICAL ENGINEERING DIRECTIONAL PROTECTION Seminar work in the course Distribution and industrial networks Mentor: Prof. Grega Bizjak Author: Amar Zejnilović Ljubljana,

More information

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS

A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS Georg Achleitner, Clemens Obkircher, Lothar Fickert, Manfred Sakulin Graz University of Technology Inffeldgasse

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS DFFERENTAL PROTECTON METHODOLOGY FOR ARBTRARY THREE-PHASE POWER TRANSFORMERS Z. Gaji ABB AB-SA Products, Sweden; zoran.gajic@se.abb.com Keywords: power transformer, phase shifting transformer, converter

More information

Power Quality and Digital Protection Relays

Power Quality and Digital Protection Relays Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

Harmonic Distortion Levels Measured at The Enmax Substations

Harmonic Distortion Levels Measured at The Enmax Substations Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B2-1030 AORC Technical meeting 2014 Implementation Approaches on Fault Information Analyzing System In Thailand s Power System N.AKEKURANANT S.CHAMNANVANICHKUL Electricity Generating

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION 23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB

More information

NEW DIGITAL METHOD FOR THE DIRECTIONAL DETECTION OF TRANSIENT GROUND FAULTS

NEW DIGITAL METHOD FOR THE DIRECTIONAL DETECTION OF TRANSIENT GROUND FAULTS NEW DIGITAL METHOD FOR THE DIRECTIONAL DETECTION OF TRANSIENT GROUND FAULTS Stefan WERBEN Ignaz HÜBL Klaus BÖHME Siemens AG Germany KNG-Kärnten Netz GmbH Austria Siemens AG Germany Stefan.werben@siemens.com

More information

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

Protective Relaying of Power Systems Using Mathematical Morphology

Protective Relaying of Power Systems Using Mathematical Morphology Q.H. Wu Z. Lu T.Y. Ji Protective Relaying of Power Systems Using Mathematical Morphology Springer List of Figures List of Tables xiii xxi 1 Introduction 1 1.1 Introduction and Definitions 1 1.2 Historical

More information

INSTRUCTIONS FOR THE COMMISSIONING AND MAINTENANCE OF DIGITAL GENERATOR PROTECTION 3 I - PRINCIPLES AND APPLICATIONS 4 on 5 6 7 Figure 5 - Inverse time curve (N1) 8 9 1 0 1 1 1 2 1 3 All relays are delivered

More information

PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK

PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK J.L. Fraisse, F. Boulanger, Ph. Juston, P. Lemerle, O. Jeannin EDF-DEGS; EDF-R&D, France Since early in 1990

More information

New design of distance protection for smart grid applications

New design of distance protection for smart grid applications New design of distance protection for smart grid applications Blumschein Jörg, Dzienis Cezary, Yelgin Yilmaz Siemens AG, Energy Management Division, Berlín, Alemania RESUMEN Este artículo presenta un nuevo

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

APPARENT POWER DEPENDENT VOLTAGE CONTROL IN THE LV GRIDS WITH DISTRIBUTED GENERATION USING ON-LOAD TAP CHANGING TRANSFORMER

APPARENT POWER DEPENDENT VOLTAGE CONTROL IN THE LV GRIDS WITH DISTRIBUTED GENERATION USING ON-LOAD TAP CHANGING TRANSFORMER 3 rd nternational Conference on Electricity Distribution Lyon, 5-8 June 05 APPARENT POWER DEPENDENT VOLTAGE CONTROL N THE LV GRDS WTH DSTRBUTED GENERATON USNG ON-LOAD TAP CHANGNG TRANSFORMER Haijun Feng

More information

The Effect of Transformer s Vector Group on Retained Voltage Magnitude and Sag Frequency at Industrial Sites Due to Faults

The Effect of Transformer s Vector Group on Retained Voltage Magnitude and Sag Frequency at Industrial Sites Due to Faults The Effect of Transformer s Vector Group on Retained Voltage Magnitude and Sag Frequency at Industrial Sites Due to Faults M. N. Moschakis, V. V. Dafopoulos, I. G. Andritsos, E. S. Karapidakis, and J.

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

MODELLING AND ANALYSIS OF THE ENHANCED TAPP SCHEME FOR DISTRIBUTION NETWORKS

MODELLING AND ANALYSIS OF THE ENHANCED TAPP SCHEME FOR DISTRIBUTION NETWORKS MODELLIN AND ANALYSIS OF THE ENHANCED TAPP SCHEME FOR DISTRIBUTION NETWORKS Maciej Fila Brunel University/EDF Energy, UK maciej.fila@brunel.ac.uk areth A. Taylor Brunel Institute of Power Systems Brunel

More information

FAULT CLASSIFICATION FOR DISTANCE PROTECTION

FAULT CLASSIFICATION FOR DISTANCE PROTECTION FAULT CLASSIFICATION FOR DISTANCE PROTECTION Magnus Akke, Member IEEE ABB Automation Technology Products AB SE-7 59 Västerås, Sweden E-mail: magnus.akke@se.abb.com Abstract: This paper presents an overview

More information

GMD Impacts on Generators

GMD Impacts on Generators Walling Energy Systems Consulting, LLC GMD Impacts on Generators Reigh Walling 1 CME interacts with earth magnetic field Large solar flare - Coronal Mass Ejection (CME) Protons and electrons in solar wind

More information

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real

More information

Sample Question Paper

Sample Question Paper Scheme G Sample Question Paper Course Name : Electrical Engineering Group Course Code : EE/EP Semester : Third Subject Title : Electrical Circuit and Network 17323 Marks : 100 Time: 3 hrs Instructions:

More information

Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits

Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient eents occur during short-circuits Short-circuit formation: fault connection between phases

More information

DISTRIBUTION PROTECTION RELAY SOFTWARE MODELS IN INTERACTION WITH POWER SYSTEM SIMULATORS

DISTRIBUTION PROTECTION RELAY SOFTWARE MODELS IN INTERACTION WITH POWER SYSTEM SIMULATORS 23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 149 DISTRIBUTION PROTECTION RELAY SOFTWARE MODELS IN INTERACTION WITH POWER SYSTEM SIMULATORS Ivan Goran KULIŠ Končar

More information

Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms

Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms WWWJOURNALOFCOMPUTINGORG 21 Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms Bruno Osorno Abstract This paper analyses and explains from the systems point of

More information

Relay-assisted commissioning

Relay-assisted commissioning Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital

More information

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Ehsan Behrouzian 1, Massimo Bongiorno 1, Hector Zelaya De La Parra 1,2 1 CHALMERS UNIVERSITY OF TECHNOLOGY SE-412

More information

Single Phase to Ground Fault Detection and Location in Compensated Network

Single Phase to Ground Fault Detection and Location in Compensated Network Single Phase to Ground Fault Detection and Location in Compensated Network Matthieu Loos A thesis submitted for the degree of PhD in Engineering Sciences Academic year 2013-2014 Thesis director: Professor

More information

Parallel tap-changer controllers under varying load conditions (Part 1)

Parallel tap-changer controllers under varying load conditions (Part 1) Parallel tap-changer controllers under varying load conditions (Part 1) by Prof. B S Rigby, T Modisane, University of KwaZulu-Natal This paper investigates the performance of voltage regulating relays

More information

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay Anurag Choudhary Department of Electrical and Electronics Engineering College of Engineering Roorkee, Roorkee

More information

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT * Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Module 1. Introduction. Version 2 EE IIT, Kharagpur Module 1 Introduction Lesson 1 Introducing the Course on Basic Electrical Contents 1 Introducing the course (Lesson-1) 4 Introduction... 4 Module-1 Introduction... 4 Module-2 D.C. circuits.. 4 Module-3

More information

VARIATION OF LOW VOLTAGE POWER CABLES ELECTRICAL PARAMETERS DUE TO CURRENT FREQUENCY AND EARTH PRESENCE

VARIATION OF LOW VOLTAGE POWER CABLES ELECTRICAL PARAMETERS DUE TO CURRENT FREQUENCY AND EARTH PRESENCE VARATON OF LOW VOLTAGE POWER CABLES ELECTRCAL PARAMETERS DUE TO CURRENT FREQUENCY AND EARTH PRESENCE G.T. Andreou, D.P. Labridis, F.A. Apostolou, G.A. Karamanou, M.P. Lachana Aristotle University of Thessaloniki

More information

Impulse noise features for automatic selection of noise cleaning filter

Impulse noise features for automatic selection of noise cleaning filter Impulse noise features for automatic selection of noise cleaning filter Odej Kao Department of Computer Science Technical University of Clausthal Julius-Albert-Strasse 37 Clausthal-Zellerfeld, Germany

More information

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits QUESTION BANK ETE (17331) CM/IF Chapter1: DC Circuits Q1. State & explain Ohms law. Also explain concept of series & parallel circuit with the help of diagram. 3M Q2. Find the value of resistor in fig.

More information

Beyond the Knee Point: A Practical Guide to CT Saturation

Beyond the Knee Point: A Practical Guide to CT Saturation Beyond the Knee Point: A Practical Guide to CT Saturation Ariana Hargrave, Michael J. Thompson, and Brad Heilman, Schweitzer Engineering Laboratories, Inc. Abstract Current transformer (CT) saturation,

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY LIST OF TOPICS 1 Electric Circuit Principles 2 Electronic Circuit Principles 3 Generation 4 Distribution 5 Utilisation The expected learning outcome is

More information

Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components

Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components American Journal of Electrical and Electronic Engineering, 207, Vol. 5, No. 4, 44-5 Available online at http://pubs.sciepub.com/ajeee/5/4/4 Science and Education Publishing DOI:0.269/ajeee-5-4-4 Double

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Abstract: A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Vijay Bendre, Prof. Pat Bodger, Dr. Alan Wood. Department of Electrical and Computer Engineering, The University of

More information

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK Eduardo MARTÍNEZ eduardo_martinez@fcirce.es Samuel BORROY sborroy@fcirce.es Laura

More information

Analysis of Modern Digital Differential Protection for Power Transformer

Analysis of Modern Digital Differential Protection for Power Transformer Analysis of Modern Digital Differential Protection for Power Transformer Nikhil Paliwal (P.G. Scholar), Department of Electrical Engineering Jabalpur Engineering College, Jabalpur, India Dr. A. Trivedi

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Substation Testing and Commissioning: Power Transformer Through Fault Test

Substation Testing and Commissioning: Power Transformer Through Fault Test 1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations

Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations Gheorghe Ioan Nicolaescu, Horia Andrei, Stefan Radulescu Electrical

More information

Phase Rolling and the Impacts on Protection

Phase Rolling and the Impacts on Protection Phase Rolling and the Impacts on Protection Denglin (Dennis) Tang Burns & McDonnell 1700 West Loop South, Houston, TX 77027 Office: (713) 622-0227 Fax: (713) 622-0224 dtang@burnsmcd.com Abstract: During

More information

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Tripping of circuit breakers in PV installations due to zero sequence field impedance Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be

More information

POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM

POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM 1 VIJAY KUMAR SAHU, 2 ANIL P. VAIDYA 1,2 Pg Student, Professor E-mail: 1 vijay25051991@gmail.com, 2 anil.vaidya@walchandsangli.ac.in

More information

New solution for feeder earth-fault protection

New solution for feeder earth-fault protection Application Note New solution to feeder earth-fault protection 1 (8) APPLICATION NOTE New solution for feeder earth-fault protection AQ-200 IED series Application Note New solution to feeder earth-fault

More information

Contents. Core information about Unit

Contents. Core information about Unit 1 Contents Core information about Unit UEENEEH114A - Troubleshoot resonance circuits......3 UEENEEG102A Solve problems in low voltage AC circuits...5 TextBook...7 Topics and material Week 1...9 2 Core

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Analysis of metallic ropes magnetisation during magneto-inductive testing

Analysis of metallic ropes magnetisation during magneto-inductive testing 11th European Conference on Non-Destructive Testing (ECNDT 2014), October 6-10, 2014, Prague, Czech Republic Analysis of metallic ropes magnetisation during magneto-inductive testing More Info at Open

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Visualization and Animation of Protective Relay Operation

Visualization and Animation of Protective Relay Operation Visualization and Animation of Protective Relay Operation A. P. Sakis Meliopoulos School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, Georgia 30332 George J. Cokkinides

More information

VOLTAGE DIPS are generally considered a power-quality

VOLTAGE DIPS are generally considered a power-quality IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 19, NO. 2, APRIL 2004 783 Assessment of Voltage Dips in HV-Networks: Deduction of Complex Voltages From the Measured RMS Voltages Math H. J. Bollen, Senior Member,

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

NEW METHOD FOR HIGH-IMPEDANCE FAULT DETECTION

NEW METHOD FOR HIGH-IMPEDANCE FAULT DETECTION NEW METHOD FOR HIGH-IMPEDANCE FAULT DETECTION ABSTRACT Hannu LAAKSONEN ABB Oy Finland hannu.laaksonen@fi.abb.com Correct detection of high-impedance faults (HIFs) is crucial because they produce a serious

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

Distance Element Performance Under Conditions of CT Saturation

Distance Element Performance Under Conditions of CT Saturation Distance Element Performance Under Conditions of CT Saturation Joe Mooney Schweitzer Engineering Laboratories, Inc. Published in the proceedings of the th Annual Georgia Tech Fault and Disturbance Analysis

More information

WHY DOES THE EARTH FAULT DETECTION METHOD BASED ON 3RD HARMONIC WORK IN LARGE MESHED 110-KV-NETWORKS

WHY DOES THE EARTH FAULT DETECTION METHOD BASED ON 3RD HARMONIC WORK IN LARGE MESHED 110-KV-NETWORKS WHY DOES THE ERTH FULT DETETION METHOD SED ON 3RD HRMONI WORK IN LRGE MESHED 0-KV-NETWORKS Gernot DRUML Oliver SKRINJEK Uwe SHMIDT Peter SHEGNER Lothar FIKERT Sprecher utomation - Energie Steiermark -

More information

A Novel Fuzzy Neural Network Based Distance Relaying Scheme

A Novel Fuzzy Neural Network Based Distance Relaying Scheme 902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 A Novel Fuzzy Neural Network Based Distance Relaying Scheme P. K. Dash, A. K. Pradhan, and G. Panda Abstract This paper presents a new

More information

Power System Stability. Course Notes PART-1

Power System Stability. Course Notes PART-1 PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed

More information

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS) KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK YEAR / SEM : I / II SUBJECT CODE & NAME : EE 1151 CIRCUIT THEORY UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

More information

Tutorial on Symmetrical Components

Tutorial on Symmetrical Components Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental

More information

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method W H I T E PA P E R Preventing transformer saturation in static transfer switches A Real Time Flux Control Method TM 2 SUPERSWITCH 4 WITH REAL TIME FLUX CONTROL TM Preventing transformer saturation in static

More information

POWER SYSTEM II LAB MANUAL

POWER SYSTEM II LAB MANUAL POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2

More information

Techniques for Generating Sudoku Instances

Techniques for Generating Sudoku Instances Chapter Techniques for Generating Sudoku Instances Overview Sudoku puzzles become worldwide popular among many players in different intellectual levels. In this chapter, we are going to discuss different

More information

Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1

Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1 Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1 Xichen Jiang (in collaboration with J. Zhang, B. J. Harding, J. J. Makela, and A. D. Domínguez-García) Department of Electrical and Computer

More information

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Transformer & Induction M/C

Transformer & Induction M/C UNIT- 2 SINGLE-PHASE TRANSFORMERS 1. Draw equivalent circuit of a single phase transformer referring the primary side quantities to secondary and explain? (July/Aug - 2012) (Dec 2012) (June/July 2014)

More information

Estimation of DC Time Constants in Fault Currents and Their Relation to Thévenin s Impedance

Estimation of DC Time Constants in Fault Currents and Their Relation to Thévenin s Impedance Estimation of DC Time Constants in Fault Currents and Their Relation to Thévenin s Impedance Philipp Stachel and Peter Schegner Institute of Electrical Power Systems and High Voltage Engineering TU Dresden,

More information

Transformer Inrush and Voltage Sag P28 Studies. August 2017

Transformer Inrush and Voltage Sag P28 Studies. August 2017 Transformer Inrush and Voltage Sag P28 Studies August 2017 Introduction This presentation is intended to give a simple overview of transformer inrush and energisation and why it is important to network

More information

~ RG1 ~ RG2 ~ RG3 COORDINATION OF REGULATION SYSTEMS FOR GENERATORS AND TRANSFORMERS IN AN INDUSTRIAL COMBINED HEAT AND POWER PLANT 1.

~ RG1 ~ RG2 ~ RG3 COORDINATION OF REGULATION SYSTEMS FOR GENERATORS AND TRANSFORMERS IN AN INDUSTRIAL COMBINED HEAT AND POWER PLANT 1. 49 COORDINATION OF REGULATION SYSTEMS FOR GENERATORS AND TRANSFORMERS IN AN INDUSTRIAL COMBINED HEAT AND POWER PLANT 1. INTRODUCTION All the national combined heat and power plants work with the national

More information

COAXIAL / CIRCULAR HORN ANTENNA FOR A STANDARD

COAXIAL / CIRCULAR HORN ANTENNA FOR A STANDARD COAXIAL / CIRCULAR HORN ANTENNA FOR 802.11A STANDARD Petr Všetula Doctoral Degree Programme (1), FEEC BUT E-mail: xvsetu00@stud.feec.vutbr.cz Supervised by: Zbyněk Raida E-mail: raida@feec.vutbr.cz Abstract:

More information