~ RG1 ~ RG2 ~ RG3 COORDINATION OF REGULATION SYSTEMS FOR GENERATORS AND TRANSFORMERS IN AN INDUSTRIAL COMBINED HEAT AND POWER PLANT 1.
|
|
- Tyler O’Neal’
- 5 years ago
- Views:
Transcription
1 49 COORDINATION OF REGULATION SYSTEMS FOR GENERATORS AND TRANSFORMERS IN AN INDUSTRIAL COMBINED HEAT AND POWER PLANT 1. INTRODUCTION All the national combined heat and power plants work with the national power system; usually they are connected to a 110 kv network. Generator transformer units in combined heat and power plants are connected to 110 kv busbars, because the power for their own needs is small compared with the power transferred to the system. Power received for technological purposes from industrial heat and power plants is comparable to the generated power. Generators (usually there are several of them) in industrial heat and power plants work in parallel, connected to 6 kv busbars. 6 kv busbars are connected to the 110 kv station with at least two (usually several) 110/6 kv transformers. Sometimes these are three-coil transformers aimed at reducing fault currents on the side of 6 kv. An example diagram of an industrial heat and power plant is shown in fig kv 6 kv RT1 RT2 RT3 ~ RG1 ~ RG2 ~ RG3 Fig. 1. Example diagram of industrial heat and power plant In accordance with the requirements of network operators, generators and transformers are equipped with control systems. The experience gained by the author in several industrial plants brings him to the conclusion that the generator control systems are often incorrectly adjusted, and the algorithms of transformer 110/6 kv controllers are wrong. The article presents a proposal for coordination of algorithms used in control systems. 2. GENERATOR CONTROL SYSTEMS Generally, all generators are equipped with systems for voltage regulation with current and power angle limiters. All control systems have a current compensation system, which is sometimes very simplified (depending on the controller supplier). Tab. 1 shows example data from the controllers in one of the industrial heat and power plants. Abstract Generators (usually there are several of them) in industrial heat and power plants work in parallel, connected to 6 kv busbars. 6 kv busbars are connected to the 110 kv station with at least two (usually several) 110/6 kv transformers. Generator control systems are often incorrectly adjusted, and the algorithms of 110/6 kv transformer controllers are wrong, making cooperation between the control systems in the plant impossible.the article presents a proposal for coordination of algorithms used in control systems.
2 50 Tab. 1. Generator control systems No. Symbol S n [MVA] P n [MW] Type LPS LPW LKM PSS Z k X k R k 1 TG Digital YES YES YES YES Rk+jXk YES YES 2 TG Digital NO YES YES NO YES NO 3 TG Digital NO YES YES NO YES NO S n, P n rated apparent and active power RN generator controller LPS, LPW, LKM limiter of stator and rotor current and power angle PSS system stabilizer Z k current compensation impedance Z k = R k + jx k A current compensation system makes the value of obtained voltage conditional on the load value (mainly reactive power) and allows a stable distribution of reactive power between cooperating generators, even in the case of cooperation of directly connected (without reactors) sections of busbars. As shown in tab. 1, TG1 has a full current compensation system, whereas TG2 and TG4 are only dependent on reactive power (part X k ). TG1 has all limiters. TG2 and TG4 have no stator current limiters. The present settings of power angle limiters (reactive power consumption): Q 0 of all generators are incorrect because they do not use the possibility of reactive power consumption by generators. Current compensation settings are mutually uncoordinated, which is caused by the fact that generators are started by various teams at several-year intervals. A similar condition was found in many industrial heat and power plants. Current use of control systems When adjusting the reference voltage of generators, the control room staff can control the proper distribution of reactive power, approximately proportional to the rated apparent power. With the adjusting cooperation of control room staff, the control systems are responsible for the following tasks: maintaining the traditionally set reference voltage on 6 kv busbars providing an approximate correct distribution of reactive power between cooperating generators. For the proper performance of the second task without constant intervention by the control room staff, it is necessary to set an equal in relative units current compensation of controllers in all generators. Correct properties Q-U of generator control systems, ensuring a proportionate or reference distribution of reactive power between generators In the task of controlling voltage, the modern generator controllers have the following properties U = f(q): Without current compensation with a very slight gradient resulting from finite value of amplification in the open loop of voltage control circuit. With current compensation introducing a virtual replacement impedance between 1 generator and controller. If generators do not run connected in parallel to the same busbar system, or their busbars are always separated by a reactor, they can operate with current compensation set to 0 (zero). If generators run connected in parallel to the same busbar system, or their busbars are not always separated by a reactor, two solutions may be used: 1. Assuming that the accuracy of digital controllers is very high and the aforementioned gradient without current compensation is sufficient, the current compensation should be set to 0 (zero). Also, the distribution of reactive power between generators without participation of control room staff should be observed. If the distribution of reactive power is approximately proportional to the apparent power 1 Some controller suppliers offer only simplified current compensation, which provides only virtual reactance.
3 51 in generators during changes in load, the first solution should be used. Otherwise the second solution solution should be selected. 2. Current compensation should be set to e.g. X k = 0.02 (2%), then the distribution of reactive power between generators without participation of control room staff should be observed. If the distribution of reactive power is approximately proportional to the apparent power in generators during changes in load, the above solution should be used. Despite the high accuracy of digital controllers, the unsystematic deviations in voltage transformers may require the use of the above solution. Due to the lack of or inaccurate information on the value of real strengthening in the open loop of a control system, an experimental procedure according to point 1 or 2 is necessary. In the unlikely event that at the value of X k = 0.02 pu the distribution of reactive power is not approximately proportional to the apparent power in generators, the value X k should be increased to X k = 0.03 pu. The method for setting generator controllers described above should ensure that the voltage in busbars is maintained with high accuracy and without interference of transformer operators and controllers. 3. TRANSFORMER CONTROL SYSTEMS Current state Usually, all transformers are equipped with voltage controllers that operate tap switches. The used controllers come from different manufacturers, but in principle, according to the documentation of one of the producers, they are designed to automatically control the voltage of lower side or the number of transformer (transmission) tap. Such controllers are designed to be used in 110/15 kv transformers located in stations supplying the 15 kv distribution network, the so-called switching stations. Controllers have no components that ensure mutual coordination during parallel operation of transformers. Algorithms for operation of such controllers prevent cooperation with the generator control systems on the side of 6 kv. In industrial heat and power plants such transformer controllers are always off. The off state is correct because probably because of poor project documentation transformer voltage controllers with incorrect operation algorithms have been used. The algorithms used in controllers are for voltage regulation appropriate for e.g. 110/15 kv transformers powering medium-voltage distribution networks. The designer probably designed a transformer with controller without considering the specificity of three transformers connecting the 6 kv network in heat and power plant with the 110 kv network. Presently the tap switches of transformers in industrial heat and power plants are controlled manually by control room staff, which controls the appropriate exchange of reactive power with the 110 kv network and proper distribution of reactive power between cooperating transformers. Correct properties Q-U of 110/6 kv transformer control systems, ensuring a proportionate or reference distribution of reactive power between transformers and proper cooperation with generator control systems Assumptions Transformer regulators should control the tap switches in all 110/6 kv transformers without constant interference by the control room staff. The operation algorithm should ensure: Proper cooperation between transformers and reactive power distribution in approximation proportional to the rated power in particular transformer coils Maintaining the exchange of reactive power with the 110 kv network of an average value minimizing the tariff charges for readings of kvarh meters That the acceptable tap switching frequency is not exceeded. Under normal conditions, the task of maintaining the set voltage on 6 kv busbars is performed by generators control systems.
4 52 Characteristics of transformer controllers 110/6 kv transformer controllers should have characteristics that ensure: Maintaining the reference value of reactive power in range Q trn,q trm if the voltage on the 6 kv side is within U trn,u trm Taking over the task of maintaining voltage on the 6 kv side after exhausting the generator capability The assumed distribution of reactive power, proportional to rated power of respective transformer windings. Controllers offered by the better suppliers have components ensuring such cooperation. The characteristics proposed for transformer controllers are shown in fig. 2. Dead bands and time delays Dead bands, independent of variables U and Q, should ensure stable operation of the control system at the borders of the O area in fig.2. Time delays For variable Q, they should ensure that the allowed frequency of tap switching is not not exceeded For variable U, they should ensure that tap switches are controlled as quickly as possible. The need for action in order to maintain a safe voltage for the plant is rare and fast switching will not cause a significant increase in the number of switches. The priority ensuring a proper quality of electricity that determines the continuity of plant operation is obvious. U tr - - U trzm U trzm Q mtr Q Mtr Q tr Fig. 2. Characteristics of transformer with controller Q tr transformer reactive power received from the 110 kv network U tr transformer voltage Ut rzm, Ut rzm lower and upper reference value of transformer voltage Q Mtr reduction of reactive power consumption from the network Q mtr reduction of reactive power supply to the network the area where transformer controllers are not running increasing voltage on the 6 kv side reducing voltage on the 6 kv side absence of transmission switching. 4. GUIDELINES FOR CHANGES IN SETTINGS AND IN ALGORITHMS FOR GENERATOR CONTROL SYSTEMS IN HEAT AND POWER PLANTS AND 110/6 KV TRANSFORMERS Assumptions Synchronous generator and 110/6 kv transformer control systems in heat and power plants should cooperate and ensure: Maintaining voltages that guarantee the proper operation of all receivers connected with the technological process in the plant
5 53 Reducing consumption of reactive power from the 110 kv network for the purpose of minimizing the costs of purchasing electricity from the 110 kv network The possibility of using the entire area of acceptable generator states, taking into account all limitations (stator current, rotor current, power angle, temperature of extreme stator packages) Proper (approximately proportional) distribution of reactive power between cooperating generators Proper (approximately proportional) distribution of reactive power between cooperating transformers That the acceptable transformer switching frequency is not exceeded. Characteristics of generators The following are important elements in modern generator controllers: Z k = R k + jx k I g = I P + ji Q z0 Fig. 3. Equivalent diagram of generator with controller with Zk Current compensation system providing equivalent diagram in the area of steady states is shown in fig.3. z0 reference voltage in generator at idle run generator voltage Z k = R k + jx k current compensation impedance. Current compensation impedance Z k = R k + jx, with adjusted value in four quadrants of complex plane allows the introduction of virtual voltage measurement and almost any shape of equivalent circuit (steady state) in the controller in the diagram of a power subsystem of heat and power plant. Stator current limiter ensuring that the acceptable value of stator current is not exceeded Rotor current limiter ensuring that the acceptable value of rotor current is not exceeded Power angle (reactive power consumption) limiter that ensures stable cooperation with the system and, sometimes, prevents the extreme parts of stator core from heating. z0 Q g Fig. 4. Characteristics of generator with controller Q g generator reactive power generator voltage z0 reference voltage in generator at idle run stator or rotator current limitation power angle limitation Generator characteristics on the plane Q, U with control system containing the aforementioned elements show the relation U = f(q) with limitations controlled by limiters, fig. 4.
6 54 Combination of generator and transformer characteristics Combination of the characteristics of generator and transformer control systems, which implement the algorithms described above, gives the resultant characteristics, shown in fig. 5 z0 U trzm U trzm 0 Q g, Q tr, Q Σ Range Q g Fig. 5. Combined characteristics of generators and transformers Q g, Q tr,, Q Σ total reactive power of generators and transformers voltage in 6 kv busbars z0 reference voltage at idle run stator or rotator current limitation power angle limitation U trzm reference value of the highest voltage in transformers on the 6 kv side U trzm reference value of the lowest voltage in transformers on the 6 kv side resultant characteristics of generators and transformers fuzzy part of the resultant characteristics the area where transformer controllers are not running 5. DESCRIPTION OF COOPERATION BETWEEN CONTROL SYSTEMS OF GENERATORS AND TRANSFORMERS Normal state In normal states, the generator and transformer controllers run autonomously. Generator regulators with the reference voltage occasionally adjusted by the control room staff ensure the correct distribution of reactive power between cooperating generators. Generator controllers maintain the reference voltage in 6 kv busbars (fig. 4 and 5) in the full range of reactive power generation or consumption from limitation of power angles to current reduction (within the acceptable states). Transformers controllers maintain reactive power consumption (fig. 2 and 5) within the limits ensuring avoidance of charges for readings of kvarh meters (the so-called reactive power). Abnormal state After reaching the boundaries of acceptable states, the generator controllers are not able to maintain the reference voltage on 6 kv busbars (fig. 3 and 5) as a result of working power angle limiters or current limiters. After exhausting the ability to maintain reference voltage by generators, the task of maintaining reference voltage is assumed by transformer controllers (fig. 2 and 5). Emergency During emergencies such as short circuits in 110 kv and 6 kv networks, short-term voltage dips, etc., the transformer control systems should not be running. Generator control systems must react quickly, according to the current characteristics, in order to maintain the stability of cooperation between the heat and power plant and the power system, as well as to ensure proper operation of power protection systems.
7 55 6. PROPOSED CONCEPT OF PRIMARY SYSTEM COORDINATING THE COOPERATION OF ALL GENERATOR CONTROLLERS IN HEAT AND POWER PLANTS AND 110/6 KV TRANSFORMERS Local demand for reactive power is met from the following sources: Generators of heat and power plants The 110 kv network (by 110/15 kv transformers) Capacitor banks in the 6 kv network. The selection of characteristics and settings in control systems of generators and 110/6 kv transformers described above provides the correct voltage on 6 kv busbars and correct value of reactive power received from the 110 kv network. Capacitor banks are controlled manually from the control room. It is possible to develop a control algorithm for the primary system which includes all the mentioned sources; however, this algorithm should be based on technical and economic analysis: Optimal voltage on 6 kv busbars, taking into account the voltage drops 6 kv busbars receivers relation Optimal use of capacitor banks Optimal use of exchange of reactive power with the 110 kv network, not only for the purpose of avoiding charges A proper selection of settings in 6/0.4 kv transmissions in transformers. The algorithm mentioned above can be included in the manual for the control room (to be implemented by the staff on duty), or implanted in the primary control circuit. Such systems are used in the country in production nodes, the so-called GCPN (Group Control of Production Node). Domestic suppliers offer such systems, which can execute algorithms required by the ordering parties. 7. SUMMARY AND CONCLUSIONS Generator controllers In general, the present generator controllers described above do not require replacement. Using appropriate settings, these controllers can implement the algorithms described above and properly cooperate with new transformer regulators. Transformer controllers The currently used controllers are designed to automatically control the voltage of lower side or the number of transformer tap. Typical controllers have no components that ensure mutual coordination during parallel operation of transformers. Algorithms for operation of these controllers prevent cooperation with the generator control systems. These controllers should be replaced with the controllers executing the algorithm described in the article. Transformer controllers are currently offered on the domestic market, and are used only for the purpose of voltage regulation. No controller executes the proposed algorithm. Domestic suppliers should offer controllers that execute the proposed algorithm for control of reactive power in the specified range of 6 kv voltage value and control of voltage at the borders of this range. Primary control system The decision to use a primary GCPN (Group Control of Production Node) system in a particular heat and power plant should be made after the preparation of technical and economic analysis that takes into account the benefits of optimizing the voltage levels and reactive power management in the entire facility, including the plant. Domestic suppliers offer such systems, which can execute algorithms required by the ordering parties. BIBLIOGRAPHY 1. Work of the Department of Electrical Power Engineering at Gdańsk University of Technology carried out within the research project Power System Security, Hellmann W., Szczerba Z., Regulacja Częstotliwości i Napięcia w Systemie Elektroenergetycznym, WNT Machowski J. et al., Power System Dynamics Stability and Control. J. Wiley, Szczerba Z. et al., Poradnik Inżyniera Elektryka, rozdział 7, Systemy Elektroenergetyczne, WNT 2005.
Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationEE 742 Chapter 9: Frequency Stability and Control. Fall 2011
EE 742 Chapter 9: Frequency Stability and Control Fall 2011 Meeting demand with generation Large and slow changes (24 hr) in power demand are met by unit commitment Medium and relatively fast changes (30
More informationIncreasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)
Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) K. Manoz Kumar Reddy (Associate professor, Electrical and Electronics Department, Sriaditya Engineering College, India)
More informationEnhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices
Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices Aarti Rai Electrical & Electronics Engineering, Chhattisgarh Swami Vivekananda Technical University,
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationImproving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)
International Journal of Scientific and Research Publications, Volume 2, Issue 5, May 2012 1 Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) K. Manoz
More informationCHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES
22 CHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES 2.1 INTRODUCTION For the accurate analysis of synchronous machines using the two axis frame models, the d-axis and q-axis magnetic characteristics
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationA Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System
7 International Journal of Smart Electrical Engineering, Vol.3, No.2, Spring 24 ISSN: 225-9246 pp.7:2 A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System Mehrnaz Fardamiri,
More informationModelling to stability analysis of brushless excitation systems on synchronous generator
1 Modelling to stability analysis of brushless excitation systems on synchronous generator Joel Gonçalves, Instituto Superior Técnico, Universidade Técnica de Lisboa Abstract The synchronous generators
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationVar Control. Adding a transformer and transformer voltage regulation. engineers loadflow program. The control system engineers loadflow.
November 2012 Adding a transformer and transformer voltage regulation to the control system engineers loadflow program The control system engineers loadflow program The loadflow program used by this website
More informationPOWER FACTOR CORRECTION AND ITS PITFALLS
Technical Note No. May 1999 POWER FACTOR CORRECTION AND ITS PITFALLS This Technical Note considers power factor correction as applied by large customers and the possible consequences when power factor
More informationFault Ride Through Technical Assessment Report Template
Fault Ride Through Technical Assessment Report Template Notes: 1. This template is intended to provide guidelines into the minimum content and scope of the technical studies required to demonstrate compliance
More informationImpact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods
Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing
More informationCork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)
Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationLARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS
LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS Giuseppe Di Marzio NTNU giuseppe.di.marzio@elkraft.ntnu.no Olav B. Fosso NTNU olav.fosso@elkraft.ntnu.no Kjetil Uhlen SINTEF
More informationIOCL Electrical Engineering Technical Paper
IOCL Electrical Engineering Technical Paper 1. Which one of the following statements is NOT TRUE for a continuous time causal and stable LTI system? (A) All the poles of the system must lie on the left
More informationStatic Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1
Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of
More informationThe Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller
The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS
ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS R. A. Walling, K. Clark, N. W. Miller, J. J. Sanchez-Gasca GE Energy USA reigh.walling@ge.com ABSTRACT
More informationSAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)
SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SLIDE In this video, we will cover a sample exam problem for the Power PE Exam. This exam problem falls under the topic of Protection, which accounts for
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationThe power transformer
ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationSafety through proper system Grounding and Ground Fault Protection
Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationSystem Requirements for Wind Farms and Distributed Generation. Giuseppe Di Marzio
ystem Requirements for Wind Farms and Distributed Generation Giuseppe Di Marzio giuseppe.di.marzio@elraft.ntnu.no 1 Contents Grid interconnection schemes Power quality requirements Fault Level considerations
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationWILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS
CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION Qing-Chang Zhong The University of Sheffield, UK Tomas Hornik Turbo Power Systems Ltd., UK WILEY A John Wiley & Sons, Ltd., Publication
More information, ,54 A
AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate
More informationDiscussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation
Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation TSAI-HSIANG CHEN a NIEN-CHE YANG b Department of Electrical Engineering National Taiwan University
More informationConstant Terminal Voltage. Working Group Meeting 4 19 th September 2014
Constant Terminal Voltage Working Group Meeting 4 19 th September 014 Overview Options summary System under investigation Options analysis Discussion Options Option 1 Constant Terminal Voltage controlled
More informationEXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS
Oil Shale, 2007, Vol. 24, No. 2 Special ISSN 0208-189X pp. 285 295 2007 Estonian Academy Publishers EXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS R. ATTIKAS *, H.TAMMOJA Department
More informationExcitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation
Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability
More informationPower System Stability. Course Notes PART-1
PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed
More informationINVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER
INVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER Abstract S Perera, V J Gosbell, D Mannix, Integral Energy Power Quality Centre School of Electrical, Computer
More informationVOLTAGE STABILITY OF THE NORDIC TEST SYSTEM
1 VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM Thierry Van Cutsem Department of Electrical and Computer Engineering University of Liège, Belgium Modified version of a presentation at the IEEE PES General
More informationZambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years
21, rue d Artois, F-758 PARIS B4-18 CIGRE 216 http : //www.cigre.org Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years T G MAGG, Power System
More informationIJSER. Fig-1: Interconnection diagram in the vicinity of the RajWest power plant
International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 696 AN INVESTIGATION ON USE OF POWER SYSTEM STABILIZER ON DYNAMIC STABILITY OF POWER SYSTEM Mr. Bhuwan Pratap Singh
More informationFOUR TOTAL TRANSFER CAPABILITY. 4.1 Total transfer capability CHAPTER
CHAPTER FOUR TOTAL TRANSFER CAPABILITY R structuring of power system aims at involving the private power producers in the system to supply power. The restructured electric power industry is characterized
More informationTransmission Line Models Part 1
Transmission Line Models Part 1 Unlike the electric machines studied so far, transmission lines are characterized by their distributed parameters: distributed resistance, inductance, and capacitance. The
More informationSynchronous Generator Load Angle Estimation
Synchronous Generator Load Angle Estimation Hrvoje Čuček 1, Damir Sumina, Nikola Švigir 3 Faculty of electrical engineering and computing, University of Zagreb Unska 3, Zagreb, Croatia 1 hrvoje.cucek@fer.hr
More informationApplication of a thyristor-controlled series reactor to reduce arc furnace flicker
ELEKTROTEHNIŠKI VESTNIK 78(3): 112-117, 2011 ENGLISH EDITION Application of a thyristor-controlled series reactor to reduce arc furnace flicker Ljubiša Spasojević, Boštjan Blažič, Igor Papič University
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationUNBALANCED CURRENT BASED TARRIF
UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage ¤t unbalance are serious power quality problems with
More informationPHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE*
Vol. 1(36), No. 1, 2016 POWER ELECTRONICS AND DRIVES DOI: 10.5277/PED160112 PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE* ADAM GOZDOWIAK,
More information1. Introduction 1.1 Motivation and Objectives
1. Introduction 1.1 Motivation and Objectives Today, the analysis and design of complex power electronic systems such as motor drives is usually done using a modern simulation software which can provide
More informationBECAUSE OF their low cost and high reliability, many
824 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 45, NO. 5, OCTOBER 1998 Sensorless Field Orientation Control of Induction Machines Based on a Mutual MRAS Scheme Li Zhen, Member, IEEE, and Longya
More informationVoltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)
Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti
More informationTABLE OF CONTENT
Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES
More informationAnalysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.
Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of
More informationFacilitating Bulk Wind Power Integration Using LCC HVDC
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 213 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC A. HERNANDEZ * R.MAJUMDER W. GALLI
More informationAnalysis of Single Phase Self-Excited Induction Generator with One Winding for obtaining Constant Output Voltage
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 2 (2011), pp.173-181 International Research Publication House http://www.irphouse.com Analysis of Single Phase Self-Excited
More informationPower Factor. Power Factor Correction.
Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationPower System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)
Vol. 3, Issue. 4, Jul - Aug. 2013 pp-2530-2536 ISSN: 2249-6645 Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC) B. M. Naveen Kumar Reddy 1, Mr. G. V. Rajashekar 2,
More informationInfluence of Wind Generators in Voltage Dips
Influence of Wind Generators in Voltage Dips E. Belenguer, N. Aparicio, J.L. Gandía, S. Añó 2 Department of Industrial Engineering and Design Universitat Jaume I Campus de Riu Sec, E-27 Castelló (Spain)
More informationA new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage
21, rue d Artois, F-758 PARIS B4_16_212 CIGRE 212 http : //www.cigre.org A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant
More informationeach time the Frequency is above 51Hz. Continuous operation is required
GC0101 EXTRACT OF EUROPEAN CONNECTION CONDITIONS LEGAL TEXT DATED 08/01/2018. ECC.6 ECC.6.1 ECC.6.1.1 ECC.6.1.2 ECC.6.1.2.1 ECC.6.1.2.1.1 ECC.6.1.2.1.2 ECC.6.1.2.1.3 TECHNICAL, DESIGN AND OPERATIONAL CRITERIA
More informationConnection Impact Assessment Application
Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,
More informationConnection Impact Assessment Application Form
Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information
More informationSizing Generators for Leading Power Factor
Sizing Generators for Leading Power Factor Allen Windhorn Kato Engineering 24 February, 2014 Generator Operation with a Leading Power Factor Generators operating with a leading power factor may experience
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationReliability Considerations for PPMV. Ryan Quint, NERC Dmitry Kosterev, BPA NASPI-NERC PPMV Tools Workshop October 2016
Reliability Considerations for PPMV Ryan Quint, NERC Dmitry Kosterev, BPA NASPI-NERC PPMV Tools Workshop October 2016 MOD Standards Framework NERC MOD Standards Modeling, Data, and Analysis MOD-032 Data
More informationIncrease Productivity and Absorption of Reactive Power for Power Station with Using Static Reactive Power Compensator
Increase Productivity and Absorption of Reactive Power for Power Station with Using Static Reactive Power Compensator Abstract: SinaGhasempour 1 and MostafaMalekan² 1 Department of Electrical and Electronic,
More informationTransient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM
Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM P.P. Panchbhai 1, P.S.Vaidya 2 1Pratiksha P Panchbhai, Dept. of Electrical Engineering, G H Raisoni College of Engineering
More informationHISTORY: How we got to where we are. March 2015 Roy Boyer 1
HISTORY: How we got to where we are March 2015 Roy Boyer 1 Traditional Stability Analysis: 1. Maintain synchronism of synchronous machines 2. Simplifying assumptions: 1. Balanced positive sequence system
More informationSRI VIDYA COLLEGE OF ENGG AND TECH
EEE6603 PSOC Page 1 UNIT-III REACTIVE POWER VOLTAGE CONTROL 1. List the various components of AVR loop? The components of automatic voltage regulator loop are exciter, comparator, amplifier, rectifier
More informationDeleted: 9 4 anuary ... [1] Deleted: much more. Formatted ... [2] Formatted Table. Formatted: Indent: Left: 0.06 cm
(Comparison based on GB Grid Code Issue 4 Revision 13 only and ENSTO - E RFG Internal Version dated 6 June 01) (Note Does not include other Industry Codes) Table compares the GB Grid Code with the ENTSO-E
More informationR10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours
Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationOn Using Fuzzy Logic Based Automatic Voltage Relay In Distribution Network
On Using Fuzzy Logic Based Automatic Voltage Relay In Distribution Network 1 Uchegbu C.E 2, Ekulibe James 2. Ilo F.U 1 Department of Electrical and Electronic Engineering Enugu state University of science
More informationTarget Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management
GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Target Mchunu and Themba Khoza Eskom Transmission
More informationSensitivity Analysis for 14 Bus Systems in a Distribution Network With Distributed Generators
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 3 Ver. I (May Jun. 2015), PP 21-27 www.iosrjournals.org Sensitivity Analysis for
More informationDigital Simulation of Thyristor Controlled Interphase Power Control Technology (TC- IPC) to limit the fault currents
Digital Simulation of Thyristor Controlled Interphase Power Control Technology (TC- IPC) to limit the fault currents V.V.Satyanarayana Rao.R #1, S.Rama Reddy *2 # EEE Department,SCSVMV University Kanchipuram,India
More informationINTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY
INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY Internal Use Only Date Received Time Received Received By: 1. The undersigned Interconnection Customer submits this request to interconnect its Large
More informationPROTECTION APPLICATION HANDBOOK
BOOK No 6 Revision 0 Global Organization Innovative Solutions Product & Substation System Business Business PROTECTION APPLICATION HANDBOOK BA THS / BU Transmission Systems and Substations LEC Support
More informationImprovement of Power system transient stability using static synchronous series compensator
Improvement of Power system transient stability using static synchronous series compensator 1 Dharmendrasinh Chauhan, 2 Mr.Ankit Gajjar 1 ME Student, 2 Assistant Professor Electrical Engineering Department,
More informationUnit Auxiliary Transformer (UAT) Relay Loadability Report
Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC
More informationGENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW
GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationDesign a Power System Simulator Model and Implement the Generator and Motor Controlling
Design a Power System Simulator Model and Implement the Generator and Motor Controlling G.U De Silva, G.B Alahendra, A.C.P Aluthgama, P.G.L Arachchi Supervised by: Prof. J Rohan Lucas, Eng. J. Karunanayake
More informationDocument C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting
Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.
More informationUNDERSTANDING SUB-HARMONICS
UNDERSTANDING SUB-HARMONICS Joe Perez, P.E., SynchroGrid, College Station, TX 77845, jperez@synchrogrid.com Introduction: Over the years, engineers have employed fundamental principles of electrical engineering
More informationOptimal Reactive Power Dispatch Considering Power Loss of Transformer
Optimal Reactive Power Dispatch Considering Power Loss of Transformer AN Guo Jun1, a, MAO Le Er2, b, YAO Qiang1, c, SHI Chang Min1, d, and WU Lan Xu3, e* 1 East Inner Mongolia EPRI, Zhaowuda Road, Jinqiao
More informationChapter L Power factor correction and harmonic filtering
Chapter L Power factor correction and 1 2 3 4 5 6 7 8 9 10 Contents Reactive energy and power factor 1.1 The nature of reactive energy L2 1.2 Equipment and appliances requiring reactive energy L2 1.3 The
More information