IXIAN TM class V 1.5. EC Transmitter This is an evolving document. EC Transmitter IXIAN TM. Features
|
|
- Julia Foster
- 6 years ago
- Views:
Transcription
1 class V 1.5 EC Transmitter This is an evolving document check back for updates. Features 4 20mA output Reads conductivity from 0.07µs to 100,000µs Accuracy +/- 2% Calibrate remotely through a PLC or directly on the board On board conductivity display Din rail mount Self-test on startup Automatic fault detection Wide operating voltage (14 VDC to 36VDC) PT100 / PT1000 temperature probe compatible Fully electrically isolated for noise immunity EC Transmitter Works with 4 different probe types Probe type Range Range in TDS K 0.01 K 0.1 K 1.0 K µs to 2,000µs 1µs to 4,000µs 1µs to 25,000µs 1µs to 100,000µs 1 to 1,080 1 to 2,160 1 to 13,500 1 to 54,000 The IXIAN Class Conductivity Transmitter will work with any brand of 2 conductor conductivity probe so long as it is one of the four listed K types. TM Patent pending Description The IXIAN class Conductivity Transmitter is our premier technology designed exclusively for industrial processes. Operation, calibration and communication is both fast and easy. The IXIAN class Conductivity Transmitter is ready for 24 hour/365 day operation with no down time. From cash crop growing to chemical manufacturing, the IXIAN class Transmitter will ensure that your process yields profitable results. Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 1
2 Contents Hardware... How to read the 4 20 output with a multimeter... Mounting... Power connection... Conductivity and temperature probe connection... Resolution... Selecting a probe type... Calibration... Remotely calibrating through a PLC... Output connection mA calibration... Temperature compensation... Factory reset... How to smooth conductivity readings on the PLC side Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 2
3 Keyed power connector 14 36V EC Transmitter Power isolator Voltage attenuator 4-20 E.C. to PLC connection PLC calibration and fault detection node Data isolator Power on indicator (BLUE) 4-20 current loop generator Quick calibration buttons E.C. interpreter engine under EMI shield 7 segment E.C. display E.C. probe connecter PT100 / PT1000 temperature probe connecter with auto detect Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 3
4 35 mm DIN Rail mount DIN rail release notch Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 4
5 63.02mm (2.48 ) mm (4.27 ) 66.6mm (2.6 ) Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 5
6 Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 6
7 How to read the 4 20 output with a multimeter EC Transmitter 12.00mA ma Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 7
8 Mounting The IXIAN class Conductivity Transmitter is specifically designed to be mounted to 35mm Din rail. Power connection Any DC voltage from 14V to 36V can be used to power the IXIAN class Conductivity Transmitter. The power connector is keyed and different from all other connectors. This device must be connected to a power source that provides a smooth ripple free DC voltage. Any DC power supply designed for a PLC should be sufficient. Connecting this device to a cheap AC adapter also known as a wall wart may interfere with the devices ability to provide smooth readings that do not fluctuate. Power consumption table ma VDC Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 8
9 Conductivity and temperature probe connection Any brand of two wire conductivity probe can be used with the IXIAN class Conductivity Transmitter as long at the probe is one of 4 possible K values (also known as the probes cell constant). Any brand of PT100 or PT1000 temperature probe can be connected to the transmitter. EC Transmitter Either method of wiring will produce the same result. There is no polarity or Probe types that can be connected Probe type Range Range in TDS K 0.01 K 0.1 K 1 K µs 2,000µs 4mA = 0.07µs 20mA = 2,000µs 1µs 4,000µs 4mA = 1µs 20mA = 4,000µs 1µs 25,000µs 4mA = 1µs 20mA = 25,000µs 1µs 100,000µs 4mA = 1µs 20mA = 100,000µs 1 1, , , ,000 Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 9
10 Resolution The IXIAN class Conductivity Transmitters 4 20mA signal has 22 bits of resolution. However the ADC resolution of your PLC will limit the resolution of your conductivity readings. The IXIAN class Conductivity Transmitter has been built with this in mind. The set ranges for the different probe types are deigned to work well with a typical 12 bit PLC ADC. Using a higher bit ADC will enable your PLC to read the conductivity with a greater resolution. See the resolution chart to determine what resolution you can expect from your PLCs ADC. Resolution chart Where resolution refers to the smallest change in conductivity your PLC can detect. EC Transmitter K bit 0.48 µs 14 bit 0.12 µs 16 bit 0.03 µs K bit 0.97 µs 14 bit 0.24 µs 16 bit 0.06 µs K bit 6.10 µs 14 bit 1.52 µs 16 bit 0.38 µs K bit µs 14 bit 6.10 µs 16 bit 1.52 µs Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 10
11 Accuracy Once properly calibrated the IXIAN class Conductivity Transmitter has an Accuracy +/- 2%. Selecting a probe type The IXIAN class Conductivity Transmitter defaults to a K 1 conductivity probe. Probe types the can be used K 0.01 K 0.1 K 1 *default K 10 EC Transmitter To change the probe type Press and hold the DRY and HIGH buttons simultaneously for 1.5 seconds. This will open the setup menu. In the setup menu there are only 3 options. PrObE 4-20 H 4-20 L The first option is PrObE. Press the Low or high buttons to select you probe type. Press DRY when the correct probe type has been selected. Probe selection is now complete. Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 11
12 Calibration The IXIAN class Conductivity Transmitter uses 3 point calibration: dry, low and high. The first calibration point is dry. The dry calibration only needs to be done when a new probe is connected for the first time to the transmitter. The other two calibration points have been preset to specific industry standard calibration values. The calibration values are dependent on what probe type the transmitter is connected to. EC Transmitter Probe type Low point calibration High point calibration K µs 1,413µs K µs 1,413µs K 1 1,413µs 12,880µs K 10 12,880µs 80,000µs Dry calibration This step is only done when a new probe is first connected to the device. Dry probe calibration is analogues to the tare function on a scale. After dry calibration the displayed conductivity should be 0. If the probe is not dry, dry it off. Press and hold the dry calibration button for 1.5 seconds. The screen will display dry then "done". Dry probe calibration has been completed. Low and high calibration The probe should be put in the correct low point calibration solution. Wait until the conductivity readings stabilize. Press and hold the low calibration button for 1.5 seconds. The screen will display Lo then "done". Low point calibration has been completed. Clean the probe and do the same procedure for high point calibration. The conductivity readings will not change after low point calibration. The conductivity readings will change only when both high and low point calibration has been completed. Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 12
13 Remotely calibrating through a PLC D, L, H Using the three input connections marked D, L, H it is possible to use a PLC to fully calibrate the IXIAN class Conductivity Transmitter. This is particularly beneficial when using a PLC touch screen. Setting a PLCs output to 200ms or more will trigger a calibration event. CAL 4 button press T1 CAL 4 Transmitter ( OUT ) Timer 1 200ms T1 System working Red Tower light ( OUT ) A calibration event will only trigger if the cosponsoring input pin has been held high for 200ms. Holding the line for more then 200ms will have no effect. Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 13
14 Output connection EC Transmitter Normal operation (24v typical) Fault 0 Volts F The connection marked F is the fault detect line. During normal operation the fault line will output a voltage equal to the voltage used to power the device. If the Conductivity Transmitter detects a problem the fault line will drop to 0 volts. Example The IXIAN Conductivity Transmitter is powered with 24V the F line will output 24V during normal operation. Events that will trigger the fault line to go to 0 volts disconnected temperature probe calibration in process loss of power Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 14
15 4 20mA calibration To ensure that the PLC is receiving the most accurate 4 20mA signal the current output from the IXIAN Conductivity Transmitter can be adjusted. The 4mA signal and the 20mA signal can both be adjusted independently. To enter 4 20 calibration mode press and hold the two Gray buttons ( DRY and HIGH ) simultaneously for 1.5 seconds. This will open the setup menu. In the setup menu there are only 3 options. PrObE 4-20 H 4-20 L The first option is PrObE. Press the DRY button to move to the second option 4-20 H 4 20mA H (H=High) The Conductivity Transmitter will now output exactly 20mA. Your PLC should show a current of 20mA Use the buttons to adjust the 20mA output so the current moves to 19.99mA, then move it back up, so it is just hits 20.00mA. To calibrate the 20mA signal When finished press the DRY button The 20 ma offset will be permanently stored in memory. Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 15
16 4 20mA L (L=Low) The Conductivity Transmitter will now output exactly 4mA. Your PLC should show a current of 4mA. Use the buttons to adjust the 4mA output so the current moves to 3.99mA, then move it back up, so it is just hits a current of 4.0 To calibrate the 20mA signal When finished press the Dry button When finished the 4 ma offset will be permanently stored in memory. Temperature compensation The IXIAN Conductivity Transmitter will automatically perform temperature compensation when a PT100, or PT1000 temperature probe is connected to the device. The Conductivity Transmitter will use 25 C as the default temperature if a temperature probe is not connected. The device will continue to operate normally however, the fault line will be low, indicating the system cannot perform temperature compensation. To view the temperature that the IXIAN Conductivity Transmitter is reading from the attached PT100, or PT1000 temperature probe, press the DRY and LOW buttons simultaneously. The display will now show the temperature. It will continue to display the temperature for 10 seconds. Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 16
17 Factory reset The IXIAN Conductivity Transmitter can be reset to its default settings. To issue a factory reset, press and hold the LOW and HIGH buttons for three seconds. The display will flash: reset Press and hold the LOW and HIGH Buttons again to confirm the factory reset. To cancel a factory reset, press the DRY button. Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 17
18 How to smooth conductivity readings on the PLC side Some PLCs will update its 4 20mA analog signal readings too quickly. This can give the appearance of a fluctuating conductivity reading. Although the fluctuations are small, it can make it difficult to determine what the conductivity actually is. One possible way stop this from happening is by making an IIR filter in software. EC Transmitter Where IXIAN_Conductivity = The input from the transmitter AFTER It has been converted into conductivity units *Yes, both sections are needed to make this work. How to derive TDS/PPM from conductivity Conductivity 0.54 = TDS Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 18
19 Atlas-Scientific.com Copyright Atlas Scientific LLC All Rights Reserved 19
Conductivity +/ 2% 1 or 2 point remotely through PLC or directly on board. Any two lead Conductivity probe (K 0.01, K 0.1, K 1.
V 2.0 Revised 1/16/17 Conductivity IXIAN Transmitter Reads Range Accuracy Calibration Supported probes Temp probe Conductivity 0.07µS 100,000µS +/ 2% 1 or 2 point remotely through PLC or directly on board
More informationIXIAN-ORP ORP. Reads mV mV. Range. +/ 1mV. Accuracy. Calibration. Single point remotely through PLC or directly on board
V 1.2 Revised 5/29/18 IXIN-ORP ORP Transmitter Reads Range ccuracy Calibration Supported probes ORP -1900.0mV 1900.0mV +/ 1mV Single point remotely through PLC or directly on board ny type & brand uto
More informationMFJ ENTERPRISES, INC.
TM Model MFJ-1924 INSTRUCTION MANUAL CAUTION: Read All Instructions Before Operating Equipment! MFJ ENTERPRISES, INC. 300 Industrial Park Road Starkville, MS 39759 USA Tel: 662-323-5869 Fax: 662-323-6551
More informationOVEN INDUSTRIES, INC. Model 5C7-362
OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-362 THERMOELECTRIC MODULE TEMPERATURE CONTROLLER TABLE OF CONTENTS Features... 1 Description... 2 Block Diagram... 3 RS232 Communications Connections...
More information8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE
8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE TRANSMILLE LTD. Version 1.1 : Apr 2015 TABLE OF CONTENTS PREPARING FOR CALIBRATION... 4 INTRODUCTION... 4 CALIBRATION INTERVAL SELECTION...
More informationFC Series Signal Conditioners
FC Series Signal Conditioners FC-33 DC Selectable Signal Conditioner with 3-way isolation Field configurable input and output ranges of 0-5V, 0-10 V, 0-20 ma and 4-20 ma with 1500 VDC isolation between
More informationTechnical data. General specifications. Measurement range min max. 360
Model Number Features Very small housing High climatic resistance 12 Bit singleturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling
More information1000TR. Instructions
1000TR ph Instructions CONTENTS 1. INTRODUCTION... 2 1.1 COMMON INTRODUCTION... 2 1.2 PARTS & ACCESSORIES... 2 2. INSTALLATION... 3 2.1 CASING... 3 2.2 MOUNTING... 3 2.3 ELECTRICAL INSTALLATION... 3 2.3.1
More informationUser manual V1.0 RTB231 RTB232. RTD transmitter
User manual 26.9.2007 V1.0 RTB231 RTB232 RTD transmitter 1 INTRODUCTION RTB231 and RTB232 are basic level DIN rail mounted transmitter for RTD sensors. The range and sensor type are programmable using
More informationModel 532 ma/v Loop Calibrator with Loop Diagnostic Operating Instructions
Practical Instrument Electronics Model 532 ma/v Loop Calibrator with Loop Diagnostic Operating Instructions A. Basic Keypad Operations j EZ-Check Switch/EZ-Step Pushbutton Slide the switch to select the
More informationWIRELESS MODBUS GATEWAY WGW410
WIRELESS MODBUS GATEWAY WGW410 The Tekon Wireless Modbus Gateway WGW410 is specifically designed to meet the most rigorous requirements of operation in the industrial process environments. Due to their
More informationCX105 Conductivity/Resistivity Transmitter
CX105 Conductivity/Resistivity Transmitter User Manual REV A.15 Sensorex Corporation, USA 11751 Markon Drive Garden Grove, CA. 92841 U.S.A. www.sensorex.com IMPORTANT SAFETY INFORMATION Please read and
More informationINSTRUCTION MANUAL Redox sensor M 1322 C
INSTRUCTION MANUAL Redox sensor M 1322 C From version 2.01 2013 Controlmatik ABW d.o.o. 2 1. General... 7 1.1 Assembly... 8 1.2 Storage of Redox probes... 9 1.3 Connection to the electrical power supply...
More informationContinental Hydraulics Installation Manual CEM-RA-A
CEM-RA-A Description: This ramp amplifier drives either single or dual solenoid proportional valve coils up to 2.6A. It is suitable to control current to either proportional directional, flow, or pressure
More informationJUMO dtrans T04 Four-wire Transmitter, settable via DIP switch/pc setup program
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More informationPM8005/6 PM8005/6. Panel Meter Panel Meter. AC and DC supply options. 5 digit LED display. Direct access menu
PM8005/6 AC and DC supply options 5 digit LED display Direct access menu Functions for calibration, alarm setting and more Wide range of optional functions Description The PM8000 Series digital panel meters
More informationLYRA 501 USER S MANUAL
LYRA 501 USER S MANUAL D O R A D O e n e r g y Belgrade, February 2005 1 GENERAL DESCRIPTION 1.1. IMPORTANT NOTICE 2 TECHNICAL SPECIFICATIONS CONTENTS 2.1. INPUT (MAINS) 2.2. OUTPUT 2.3. ENVIROMENTAL CONDITIONS
More informationConductivity Transmitter N-LF V AC
OPERATING INSTRUCTIONS Conductivity Transmitter N-LF2000 230V AC These operating instructions apply to the following device: Article Measuring range Order number N-LF2000, Conductivity measuring device
More informationAssembly Instructions
Assembly Instructions optocontrol 2520 Functions Edge measurement with the shadow principle (Edge low-high; edge high-low) Measurement of diameter-, width-, gap incl. center axis Counting of edges or segments,
More informationQAM Snare Isolator User Manual
QAM Snare Isolator User Manual QS-ISO-1.6 9/1/15 This document details the functions and operation of the QAM Snare Isolator leakage detector Table of Contents Overview... 3 Screen Navigation... 4 Settings...
More informationF4-04DA-1 4-Channel Analog Current Output
F4-4DA- 4-Channel Analog Current 32 Analog Current Module Specifications The Analog Current Module provides several features and benefits. ANALOG PUT 4-Ch. Analog It is a direct replacement for the popular
More informationData Acquisition Modules/ Distributed IO Modules
User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332
More informationProcess Calibrator. TechChek 820
Process Calibrator TechChek 80 CONTENTS GENERAL... TURN ON... CONNECTIONS... TILT STAND...4 CHANGING BATTERIES...4 RESTORING DEFAULT SETTINGS... CONFIGURING TEMPERATURE SCALES... ENABLING AUTO-OFF... SELECTING
More informationFC-33, DC SELECTABLE SIGNAL CONDITIONER
FC-33, DC SELECTABLE SIGNAL CONDITIONER Description. The FC-33 is a DIN rail or side mount, selectable input/output signal conditioner with 1500VDC isolation between input and output, and 1500VDC isolation
More informationJUMO ecotrans Lf 03 Microprocessor Transmitter / Switching Device for conductivity or resistivity and temperature
Data Sheet 20272 Page /7 JUMO ecotrans Lf 0 Microprocessor Transmitter / Switching Device for conductivity or resistivity and temperature Type 20272 Housing for DIN rail mounting (5 x 7.5 mm to DIN EN
More informationCZ-K Series. RGB Digital Fiberoptic Sensors. Description MAIN MENU PRODUCTS APPLICATIONS INDEX SELECTION GUIDE
RGB Digital Fiberoptic Sensors CZ-K Series Features RGB three-light source Wide detection range of 70 ±20 mm 2.75" ±0.78" High-speed response of 300 µs Water-resistant sensor head IP-67 rated Detecting
More informationMetaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1
ULC Version 7.X August 2015 USER MANUAL pg. 1 Overview Universal LED Controller () provides independent true constant-current or voltage control of two LED loads from 0.02 to 4 Amps continuous (DC) with
More informationMFJ ENTERPRISES, INC.
Screwdriver Antenna Controller Model MFJ-1926 INSTRUCTION MANUAL CAUTION: Read All Instructions Before Operating Equipment! MFJ ENTERPRISES, INC. 300 Industrial Park Road Starkville, MS 39759 USA Tel:
More informationModbus communication module for TCX2: AEX-MOD
Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation
More informationTechnical Data Sensor Input Input voltage measuring range (FSO) V 0 ±10 Max. input voltage V <±15 Resolution mv 5 with oversampling 14 Bit mv
Electronics SUNSTAR & 传感与控制 Software http://www.sensor-ic.com/ TEL:0755-83376549 E-MAIL: Remote Control Monitor Type 5825A1 Portable Display Unit for Controlling Transmitters Charge Amplifier The remote
More informationIsolators & converters
Isolators & converters The 3100 series A d d i n g v A l u e t o f A c t o r y A n d p r o c e s s A u t o m A t i o n isolation display i.s. interface temperature universal THE SLIM SErIES for a wide
More informationContinental Hydraulics Installation Manual CEM-PA-A
CEMPAA Description: This closed loop PID amplifier drives a single solenoid proportional pressure or flow control valve coil up to 2.6A. It is suitable to provide precise closed loop control in pressure,
More informationThe I-2532 CAN to Fiber Converter
The I-2532 CAN to Fiber Converter User s Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the
More informationMetaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 6.2 June 12, 2013 USER MANUAL. metaphase-tech.com. pg. 1
ULC Version 6.2 June 12, 2013 USER MANUAL pg. 1 Overview Universal LED Controller () provides independent true constant-current or voltage control of two LED loads from 0.02 to 4 Amps continuous (DC) with
More informationPACSystems* RX3i and Series 90-30
May 2012 PACSystems* RX3i and Series 90-30 Series 90*-30 Analog Output Module, Current/Voltage, 8 Channel, IC693ALG392 RX3i Analog Output Module, Current/Voltage, 8 Channel, IC694ALG392 The PACSystems
More informationINPUT RESISTANCE OR CLAMP VOLTAGE. 2 Years 23 C ±5 Voltage mv 3 10 nv > 10 G
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 www.keithley.com Model 2010 Low-Noise Multimeter Specifications DC CHARACTERISTICS CONDITIONS: MED (1 PLC) 1 or SLOW (5 PLC)
More information1.0 Introduction. Related Products and Documentation
Quick Start t Guide ER450 Data Radio 1.0 Introduction Welcome to the Quick Start Guide for the ER450 Data Radio. This guide provides step-by-step instructions, with simple explanations to get you up-and-running.
More informationCharacteristics and functioning
Characteristics and functioning /25 ENOD4 PRODUCT RANGE:... 4. General presentation:... 4.2 enodview software tool... 4.3 Versions and options:... 4.3. Versions:...4.3.2 Options :...4.4 Dimensions:...
More informationGuidelines to Using a Three Phase Voltage Monitor
September 2000 Guidelines to Using a Three Phase Voltage Monitor Introduction A phase monitor can be used with any three phase motor. A monitor such as the Copeland 085-0160-00 is recommended for monitoring
More informationHC-220 PID Controller
HC-220 PID Controller Operation and Maintenance Manual The information contained in this manual was current at the time of printing. The most current versions of all Hydro Instruments manuals can be found
More informationSCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD
Modular Wireless I/O System User Manual Version V. for BENTEK SYSTEMS LTD #, 0 Ave S.E. Calgary, AB, Canada TB 0L Ph:(0) Fax:(0) email: sales@scadalink.com web: The is a Modular Wireless I/O System that
More informationHow to make a list sweep measurement
How to make a list sweep measurement This material shows how to perform a list sweep measurement through an example of the Photovoltaic Cell IV measurement. Figure 1 illustrates the connection and condition
More informationsw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS
INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS
More informationF2-04AD-1, F2-04AD-1L 4-Channel Analog Current Input
F2-4AD-1, F2-4AD-1L 4-Channel Analog Current 2 InThisChapter... Module Specifications Setting the Module Jumpers Connecting the Field Wiring Module Operation Writing the Control Program 2-2 Module Specifications
More informationSMART TWEEZERS Model ST-1 User s Manual Version 1.0
SMART TWEEZERS Model ST-1 User s Manual Version 1.0 Patent Pending TABLE OF CONTENTS Notice The contents of this document is believed to be accurate, but is not guaranteed by Excelta Corporation. The information
More informationINSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12
INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.
More informationF2-04AD-2, F2-04AD-2L 4-Channel Analog Voltage Input
F2-04AD-2, F2-04AD-2L 4-Channel Analog Voltage 2 F2-04AD-2, F2-04AD-2L 4-Channel Analog Voltage Module Specifications The F2-04AD-2 (24 VDC input power model) and F2-04AD-2L (12 VDC input power model)
More informationMTC-2 highlight features: ACU highlight features: Contents. MTC-2 and ACU User Manual V5.1
MTC-2 can work alone as a twin motor ECS (electronic speed controller) for RC tanks. When the ACU (auxiliary control unit) is connected, it can also control turret rotation, gun elevation, gun firing,
More informationAV3672 Series Vector Network Analyzer
AV3672 Series Vector Network Analyzer AV3672A/B/C/D/E (10MHz 13.5 GHz/26.5 GHz/43.5 GHz/50 GHz/67 GHz) Product Overview: AV3672 series vector network analyzer include AV3672A (10MHz 13.5GHz), AV3672B (10MHz
More informationUSER MANUAL. EPP Intelligent Positioner Control Unit 1/22.
USER MANUAL - Intelligent Positioner Control Unit 1/22 Table of contents: 1 General... 3 1.1 Safety instructions... 3 2 Application... 4 3 Electrical specifications and terminals... 5 3.1 Control loop...
More informationBU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS
INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported
More information5000 series Signal Isolation
5000 series Signal Isolation PERFORMANCE MADE SMARTER COMMUNICATION FOUNDATION TEMPERATURE I.S. INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY 33 3 33 33 3 3 33 3 33 2 The Process
More informationGFL-1000 User Manual Ground Fault Locator
GFL-Series User Manual V1.1 GFL-1000 User Manual Ground Fault Locator Contents Contents... 1 1 Declaration of Conformity... 3 2 Introduction... 3 3 Equipment Information... 3 3.1 Safety Precautions...
More informationThermo Electric Cooling Temperature Controller TEC Controller / Peltier Driver ±16 A / ±22 V or 31 V
Thermo Electric Cooling Temperature Controller TEC Controller / Peltier Driver ±16 A / ±22 V or 31 V OEM TEC Controller Features The is a specialized TEC controller / power supply able to precision-drive
More informationTemperature Transmitters - Head Mounted
XTH Features - Non-programmable Models Sensor Types: Models for thermocouple Types J, K, or T Models for RTD Type Pt100 3-wire Select from a variety of pre-configured measuring ranges Internal cold junction
More informationAbout the DSR Dropout, Surge, Ripple Simulator and AC/DC Voltage Source
About the DSR 100-15 Dropout, Surge, Ripple Simulator and AC/DC Voltage Source Congratulations on your purchase of a DSR 100-15 AE Techron dropout, surge, ripple simulator and AC/DC voltage source. The
More informationContents. Software Requirements
CALIBRATION PROCEDURE NI PXIe-4154 This document contains information for calibrating the NI PXIe-4154 Battery Simulator. For more information about calibration, visit ni.com/calibration. Contents Software
More informationOperator Manual 1.4 FRACSIM MINI
FracSim Meters FracSim Meters was founded with the intention of providing specifically designed tools for the well service industry. Our goal is to provide quality tools with a robust design to meet the
More informationICS REPEATER CONTROLLERS
ICS REPEATER CONTROLLERS BASIC CONTROLLER USER MANUAL INTEGRATED CONTROL SYSTEMS 1076 North Juniper St. Coquille, OR 97423 Email support@ics-ctrl.com Website www.ics-ctrl.com Last updated 5/07/15 Basic
More informationThermo Electric Cooling Temperature Controller TEC Controller / Peltier Driver ±16 A / ±19 V
Thermo Electric Cooling Temperature Controller TEC Controller / Peltier Driver ±16 A / ±19 V TEC-1090 OEM Precision TEC Controller DC Input Voltage: TEC Controller / Driver: Output Current: Output Voltage:
More informationDigital amplifier for proportional valves PEM XD
Digital amplifier for proportional valves PEM XD FEATURES - Amplifier for cap rail mounting according to DIN EN 50022 - Control of 2 coils in open loop, or 2 proportional valves with 1 coil in open loop
More informationExercise 2: Temperature Measurement
Exercise 2: Temperature Measurement EXERCISE OBJECTIVE When you have completed this exercise, you will be able to explain the use of a thermocouple in temperature measurement applications. DISCUSSION the
More informationStrain Gauge Measuring Amplifier BA 662
Strain Gauge Measuring Amplifier BA 662 Original of the Manual Table of Contents 1. Safety precautions... 2 1.1. Field of application... 2 1.2. Installation... 2 1.3. Maintenance... 2 2. Function... 2
More informationINTAC Microprocessor Humidifier Controller
PURE Humidifier Company Read and Save These Instructions INTAC Microprocessor Humidifier Controller Installation Instructions Operation and Maintenance Manual 002 % Power 68% Heaters 1 2 3 4 INTAC Humidifier
More informationIncreasing security. Saving space. Gaining flexibility. Signal Conditioners for Industrial Automation
Increasing security. Saving space. Gaining flexibility. Signal Conditioners for Industrial Automation The SC-System: Interference-Free Signals, Maximum Performance The SC-System from Pepperl+Fuchs offers
More informationLoop calibration and maintenance
Loop calibration and maintenance pplication Note Introduction Process instrumentation requires periodic calibration and maintenance to ensure that it is operating correctly. This application note contains
More informationA Guide to Calibration on the BioFlo 120 and BioFlo 320: Dissolved Oxygen Sensors
SHORT PROTOCOL No. 40 I May 2017 A Guide to Calibration on the BioFlo 120 and BioFlo 320: Dissolved Oxygen Sensors Stacey Willard Eppendorf Inc., USA Abstract Dissolved oxygen (DO) is a critical process
More informationDigital Fiber-Optic Switches
CP-PC-2259E Digital Fiber-Optic Switches Model HPX-EG0 0/01 : Standard Model HPX-EG/ 51 : Long-dis tance Sensing Satisfaction Freedom from Frequent Adjustments Please read Terms and Conditions from the
More informationM1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL
M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity
More informationFluke 192/196/199. MS 190 and MA 190. Users Manual Supplement
Fluke 192/196/199 MS 190 and MA 190 Users Manual Supplement 4822 872 00979 April 2000, Rev.2, 9/00 2000 Fluke Corporation. All rights reserved. Printed in the Netherlands. All product names are trademarks
More informationW100/W600/W900 Controller ph Electrode Troubleshooting Guide
W100/W600/W900 Controller ph Electrode Troubleshooting Guide Table of Contents Section 1 Section 2 Section 3 Section 4 Section 5 Electrode Reading Responds Slowly Electrode Reading is Stuck on one Value
More informationSF Series. 900 MHz Wireless Switch Follower/Remote Control Receiver (with On-Board 10-Amp Relays) Typical Applications
Long Range Wireless Applications 900 MHz Wireless Switch Follower/Remote Control Receiver (with On-Board 10-Amp Relays) The switch followers are a two way system designed to provide a quick and cost effective
More informationKICHFS1002 ONE TOUCH ENGINE START KIT WITH RFID. Parts Included: 1 ECO 1 HF500 1 KICSWBM22**
KICHFS1002 Parts Included: 1 ECO 1 HF500 1 KICSWBM22** Mount in Dry Location Install Fuses Good Ground Required Use High Amp Relay Remote Transmitter Turn power on. For a successful communication between
More informationRoline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL
Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the
More informationBlockMon Block Monitor LongMon Long Monitor
BlockMon Block Monitor LongMon Long Monitor Bypass range 2.2V to 5.0V. Bypass current 0A to 2A (typically 1A). Over-voltage protection up to ±20V. Noise immune opto-isolated. Cell temperature and bypass
More informationF4 08DA 2 8-Channel Analog Voltage Output
8-Channel Analog Voltage In This Chapter.... Module Specifications Setting the Module Jumper Connecting the Field Wiring Module Operation Writing the Control Program 92 8-Ch. Analog Voltage Module Specifications
More informationYGE ProgCard II - Programming Card
YGE ProgCard II - Programming Card With the programming card, we offer an easy to use programming unit, with which all our ProgCard II capable speed controllers can have their individual functions changed.
More informationJUMO Wtrans Receiver Universal Receiver for JUMO Wireless Measuring Probes
Data sheet 902931 Page 1/10 JUMO Wtrans Receiver Universal Receiver for JUMO Wireless Measuring Probes For processing physical measurands of the JUMO Wtrans series RS485 interface with Modbus protocol
More informationecotrans Lf 01/02 Transmitter / Switching Device for Conductivity Type B Operating Instructions 02.07/
ecotrans Lf 01/02 Transmitter / Switching Device for Conductivity Type 202731 B 20.2731.0 Operating Instructions 02.07/00435548 1 Notes 4 2 Identifying the device version 5 2.1 Type designation 5 3 Mounting
More informationTechnical Information itemp TMT180
TI00088R/09/EN/14.16 71315611 Technical Information itemp TMT180 Temperature head transmitter for resistance thermometers Pt100 Configurable using a PC, for installation in a terminal head, form B Application
More informationSERIES 70. R SERVO PRO Version 3.0 OPERATION AND MAINTENANCE MANUAL. The High Performance Company
SERIES 70 R SERVO PRO Version 3.0 OPERATION AND MAINTENANCE MANUAL The High Performance Company Contents 1.0 Safety Instructions - Definition of Terms 2 1.1 Hazard-free Use 2 1.2 Qualified Personnel 2
More informationma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals.
1 Definition ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals. 2 Operating Principle An electronic circuit
More informationUser manual Firmware V1.0-V1.2 HTB230. In-head transmitter
User manual 18.2.2013 Firmware V1.0-V1.2 HTB230 In-head transmitter 1 INTRODUCTION Nokeval HTB230 is a basic level in-head transmitter for RTD sensors. The range and sensor type are programmable using
More informationTOP SERVO SIGNAL 5 SERVO SIGNAL 3 SERVO SIGNAL 4 SERVO SIGNAL 6 T B T B T B T B T B SERVO TRIGGER 1 BOTTOM
Micro Miniatures Servo Controller Channel Location of connections and switches TOP SERVO SIGNAL SERVO SIGNAL 7 SERVO SIGNAL 6 SERVO SIGNAL 5 SERVO SIGNAL SERVO SIGNAL SERVO SIGNAL SERVO SIGNAL SIGNAL COMMON
More informationEnglish. Money Counter. Coin and banknote counter. DEUTsCH. Manual
ITALIANO ESPAÑOL FRANçAIS NEDERLANDS English Money Counter DEUTsCH Coin and banknote counter Manual Money Counter for Coins and Banknotes Introduction Thank you for choosing the Money Counter series. The
More informationTroubleshooting Guide for Aquatrac Smart AS and Flex
Troubleshooting Guide for Aquatrac Smart AS and Flex Part 1 Sensors and Analog Signals Alpha Release July 28 th, 2000 Alpha Release Page 1 of 21 Preface Welcome to the Aquatrac troubleshooting guide. This
More informationIRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL
IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL Confirm contents of package: 1 sensor, 1 cable, 1 wide lens (default), 1 narrow lens, mounting template, User s Guide. Install the sensor at the desired
More informationF4 16DA 2 16-Channel Analog Voltage Output
F46DA2 6-Channel Analog Voltage In This Chapter.... Module Specifications Setting Module Jumpers Connecting the Field Wiring Module Operation Writing the Control Program 22 F46DA2 6-Ch. Analog Voltage
More informationECE 480: SENIOR DESIGN LABORATORY
ECE 480: SENIOR DESIGN LABORATORY DEPARTMENT OF ELECTRICAL AND COMPUTER ENGINEERING MICHIGAN STATE UNIVERSITY I. TITLE: Lab I - Introduction to the Oscilloscope, Function Generator, Digital Multimeter
More informationPROCESS & TEMPERATURE CONTROLLERS
PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs
More informationOP5340-1/OP USER GUIDE
OP5340-1/OP5340-2 USER GUIDE Analog to Digital Converter Module www.opal-rt.com Published by OPAL-RT Technologies, Inc. 1751 Richardson, suite 2525 Montréal (Québec) Canada H3K 1G6 www.opal-rt.com 2014
More informationAMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH
AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH INSTRUCTION MANUAL PLEASE READ THIS MANUAL BEFORE OPERATING THIS EQUIPMENT! 116 Willow Road Starkville, MS 39759 USA 662-323-8211 Version 3B Printed in U.S.A.
More informationThe Smartest RGB Sensor in the Industry
NEW RGB Digital Fiberoptic Sensors CZ-V20 Series More stability & reliability in every detection The Smartest RGB Sensor in the Industry Introducing the CZ-V20 Series SUPER HIGH POWER RGB sensor Industry's
More informationTemperature head transmitter itemp PCP TMT 181
Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage
More informationContents CALIBRATION PROCEDURE NI PXI-5422
CALIBRATION PROCEDURE NI PXI-5422 This document contains instructions for calibrating the NI PXI-5422 arbitrary waveform generator. This calibration procedure is intended for metrology labs. It describes
More informationAMERITRON SDC-102 Screwdriver Antenna Controller
AMERITRON SDC-102 Screwdriver Antenna Controller INSTRUCTION MANUAL PLEA S E REA D T H IS M A NU A L BEFORE OP ERA T I N G T H IS EQU IP M EN T! 116 Willow Road Starkville, MS 39759 USA 662-323-8211 Version
More informationGE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor
clear mode enter clear mode enter GE Sensing Introduction The GE Telaire Vaporstat 900 sensor measures in applications in the range of 0 to 0 F dew point. The sensor package is designed for wall mounting.
More informationModel OI-6940 Notis Quad 4-Gas Sensor Assembly
Model OI-6940 Notis Quad 4-Gas Sensor Assembly Operation Manual Revision 2.3w Product Overview The Otis Instruments, Inc. Gen II WireFree OI-6940 Notis Quad is a battery-powered explosion-proof 4-gas sensor
More informationELECTRONIC THERMOSTAT: T920
μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with
More informationF4 04DAS 1 4-Channel Isolated 4 20mA Output
F44DAS 4-Channel Isolated 4mA F44DAS 4-Channel Isolated 4mA Module Specifications The F44DAS 4-channel Isolated Analog module provides several features and benefits. ANALOG 4 CHANNELS PUT F44DAS 4-Ch.
More information