Modbus Register Map: InfraStruXure Symmetra 3-Phase Absolute Starting Register Number, (Decimal)

Size: px
Start display at page:

Download "Modbus Register Map: InfraStruXure Symmetra 3-Phase Absolute Starting Register Number, (Decimal)"

Transcription

1 Modbus Map: InfraStruXure Symmetra 3-Phase // Status Word Reserved R = UPS ready to provide power to the load upon return of normal line voltage or upon user command = State == Enable Load Disconnect (Output is off - But not due to delayed wakeup command) 6 = UPS ready to provide power to the load upon user command = State == Load Disconnect (Output is off) (Number of modules!= 0) && (Bad Modules!= Installed Modules) = UPS in bypass mode as a result of manual bypass control = State == Manual Bypass (System bypass by front switch) 4 = UPS returning from bypass = State == Temporary Bypass (Bypass with intention of leaving bypass state) 3 = UPS in bypass due to command = State == Command Bypass (UPS Commanded into Bypass) 2 Reserved = UPS in bypass due to an internal fault (indicated through register or 40003) = State == Temporary Bypass (Bypass with no intention of leaving) 0 UPS turning on = State == Wakeup (Output turning on - Waiting for modules to start, processing system overrides) // Status Word Reserved R = UPS fault - internal temperature exceeded nominal limits Any battery is too hot (Cleared 2 minutes after battery cools off) 6 Reserved = Battery charger failure Any module has reported a charger fault (Cleared when no module has a charger failure) 4 = UPS in shutdown mode State == Enable Load Disconnect (Output is off - Waiting for power to return) 3 = UPS in sleep mode State == Enable Load Disconnect (Output is off - By sleep with delayed wakeup command) 2 Reserved = UPS unable to transfer to on-battery operation due to overload State == Load Disconnect (Output is off - No modules providing power to load, and bypass was not available) 0 = UPS output not receiving power due to low battery shutdown State == Enable Load Disconnect (Output is off - Due to low battery - Waiting for power to return) // Status Word Reserved R = UPS commanded out of bypass with no batteries connected UPS in bypass 0/200 UPS Fault - UPS commanded to leave bypass state but no batteries were connected InfraStruXure Symmetra 3-Phase Modbus Map

2 4 = UPS fault - UPS in bypass 3 = Output voltage selection failure UPS in bypass = UPS fault - output voltage select failure, UPS in bypass 2 Reserved Reserved 0 = Fan failure = UPS fault - UPS in bypass due to fan failure // Status Word Reserved R = Replace battery 6 = Low battery Low Battery Runtime <= Low Battery Setting ("j" <= "q") = Overload 4 = On battery = On battery - Any Module On Battery Battery Discharging Sim Power Failure UPS Doing Self Test Runtime Calibration 3 = Online 2 Reserved = Reboot/Sleep Mode Symmetra sets this bit when in Reboot or Sleep Mode 0 = Performing battery calibration discharge // Status Word Reserved R = Backfeed relay open (fault) 0 = Site wiring fault 9 = Fault found in register 40033, 40034, 4003, or Fault found in abnormal condition register (second abnormal condition register) 8 = Battery voltage high = No batteries 6 = System not synchronized = Output voltage out of range 4 = XR frame fault Extended Run (XR) frame fault 3 = Runtime below alarm threshold 2 = Load shutdown from bypass Input frequency or voltage outside limits = No good modules present 0 = Internal communication failure // Status Word 4000 = RIM is in control R 4 = System level fan failed 3 = Input CB tripped open = Input circuit breaker tripped open 2 = System is in maintenance bypass = UPS in bypass due to overload 0 = UPS in bypass due to internal fault 9 = Bypass contactor stuck in online position InfraStruXure Symmetra 3-Phase Modbus Map 2

3 // 8 = Bypass contactor stuck in bypass position = Bypass not in range (either frequency or voltage unacceptable) 6 = Redundancy below threshold = Loss of redundancy 4 = Load is above alarm threshold 3 = An installed battery has failed 2 = RIM is installed and failed = IM is installed and failed 0 An installed Power Module has failed Line Quality R WORD 00FF = Acceptable utility line quality 0000 = Unacceptable utility line quality 4000 % Battery Capacity R WORD % Runtime Remaining R WORD Min Battery Voltage R WORD V Present internal operating temperature (0-209 C) 00XX =Valid reading FFXX =Invalid reading 4000A 0 UPS Internal Temperature WORD (XX is sensor reading) 4000B Amps Drawn By Load R WORD A 4000C 2 Number of Battery Packs with Bad Batteries R WORD Variable ( 99) 4000D 3 Number of Battery Packs R WORD Variable ( 99) 4000E 4 % Power Drawn By Load R WORD % 4000F Maximum Input Voltage Since Last Reading R WORD V Minimum Input Voltage Since Last Reading R WORD V 400 Nominal Battery Voltage R WORD V Actual Battery Voltage R WORD V Utility Input Frequency R WORD Hz Utility Input Voltage Phase A R WORD V Utility Input Current Phase A R WORD A Bypass Input Voltage Phase A R WORD V Percent of Maximum Output VA s Phase n+0 R WORD % Percent of Maximum Output VA s Phase n+x R WORD % Output Phase A R WORD kva 400A 26 Output Voltage Phase A R WORD V 400B 2 Output Current Phase A R WORD A 400C 28 Peak Output Current Phase A R WORD A 400D 29 Utility Input Voltage Phase B R WORD V InfraStruXure Symmetra 3-Phase Modbus Map 3

4 400E 30 Utility Input Current Phase B R WORD A 400F 3 Bypass Input Voltage Phase B R WORD V Percent of Maximum Output VA s Phase n+0 R WORD % Percent of Maximum Output VA s Phase n+x R WORD % Output Phase B R WORD kva Output Voltage Phase B R WORD V Output Current Phase B R WORD A Peak Output Current Phase B R WORD A Utility Input Voltage Phase C R WORD V Utility Input Current Phase C R WORD A Bypass Input Voltage Phase C R WORD V Percent of Maximum Output VA s Phase n+0 R WORD % 4002A 42 Percent of Maximum Output VA s Phase n+x R WORD % 4002B 43 Output Phase C R WORD kva 4002C 44 Output Voltage Phase C R WORD V 4002D 4 Output Current Phase C R WORD A 4002E 46 Peak Output Current Phase C R WORD A 4002F 4 Measure-UPS Temperature Reading (sensor ) R WORD C Measure-UPS Humidity Reading (sensor ) R WORD % Measure-UPS Temperature Reading (sensor 2) R WORD C Measure-UPS Humidity Reading (sensor 2) R WORD % Reserved R WORD Reserved R WORD // Status Word Reserved R = Battery Charger Shut Down Externally 0 = System Startup Configuration Failed // Status Word = Static bypass switch module removed R 4 = UPS in forced bypass state 3 = System ID card failed 2 = System ID card removed = Static bypass switch module fault 0 = Internal DC disconnect switch tripped 9 = Switchgear communication card removed 8 = Switchgear communication card failure InfraStruXure Symmetra 3-Phase Modbus Map 4

5 // = XR communication card removed 6 = XR communication card failure = Battery monitor card removed 4 = Battery monitor card failure 3 = System power supply card failure 2 = External DC disconnect switch tripped = Isolation transformer over temperature 0 = Maintenance bypass failure 4003 Measure-UPS Contact Position R WORD Minimum Return Battery Capacity R WORD % Lower Transfer Point R WORD V 4003A 8 Upper Transfer Point R WORD V 4003B 9 Nominal Output Voltage R WORD V 4003C 60 Shutdown Delay R WORD Sec 4003D 6 Low Battery Duration R WORD Min 4003E 62 Turn On Delay R WORD Sec 4003F 63 Sensitivity R WORD Sensitivity UPS ID Character # R WORD UPS ID Character #2 R WORD UPS ID Character #3 R WORD UPS ID Character #4 R WORD UPS ID Character # R WORD UPS ID Character #6 R WORD UPS ID Character # R WORD 4004 UPS ID Character #8 R WORD Battery Current R WORD A F 3 9 Reserved R WORD 4000-FFFF INVALID ADDRESS InfraStruXure Symmetra 3-Phase Modbus Map

InfraStruXure Manager v4.x Addendum: Building Management System Integration

InfraStruXure Manager v4.x Addendum: Building Management System Integration InfraStruXure Manager v4.x Addendum: Building Management System Integration Introduction This addendum explains the integration of the APC InfraStruXure Manager Appliance with a Building Management System

More information

MODBUS Protocol for CS101 network card family

MODBUS Protocol for CS101 network card family MODBUS Protocol for CS1 network card family 1 MODBUS tables Please note that not all the data are available for all UPSs. The addresses are in PLC mode (base 1). Type: U means without arithmetic sign,

More information

Table 6.1 Fault Code List Code indication (Note 3)

Table 6.1 Fault Code List Code indication (Note 3) 62 Table 6.1 Fault List UA801 UA802 UA803 UA804 UA805 UA806 UA807 UA808 UA810 UA812 UA813 UA814 UA815 UA817 UA821 AC VOLTAGE OUT OF RANGE AC FREQUENCY OUT OF RANGE AC PHASE ROTATION ERROR OPE. OVER OVER

More information

Gutor PxW AC UPS Designed for North American Market

Gutor PxW AC UPS Designed for North American Market Gutor PxW AC UPS Designed for North American Market PEW 5 200 kva single phase PDW 10 220 kva three phase Higher ratings upon request schneider-electric.com 2 schneider-electric.com schneider-electric.com

More information

MODULAR DC POWER SUPPLIES & SYSTEMS. DC Power Systems DC/AC Inverters Static Switches DC/DC Converters. GAMATRONIC, A SolarEdge Division

MODULAR DC POWER SUPPLIES & SYSTEMS. DC Power Systems DC/AC Inverters Static Switches DC/DC Converters. GAMATRONIC, A SolarEdge Division MODULAR DC POWER SUPPLIES & SYSTEMS DC Power Systems DC/AC Inverters Static Switches DC/DC Converters GAMATRONIC, A SolarEdge Division 17 Hartom Street, Jerusalem 9777517, Israel 1-800-20-70-90 Tel: +972-2-5888277

More information

W o r l d C l a s s P o w e r S o l u t i o n s Internal power supply UPS mains operation UPS battery operation Bypass operation Parallel operation Manual bypass Overload Inverter failure Mains failure

More information

Solectria Renewables Modbus Level 6 For models SGI 500XT

Solectria Renewables Modbus Level 6 For models SGI 500XT Solectria Renewables Modbus Level 6 For models SGI 500XT Revision B 2014, Solectria Renewables, LLC DOCR 070382 B Table of Contents 1 Solectria Renewables Modbus Level 6... 3 1.1 Determine Modbus Level...

More information

SPECIFICATION. Online UPS 3000VA

SPECIFICATION. Online UPS 3000VA Page 1 / 7 DESCRIPTION Pure sine-wave output UPS on-line double conversion type. INPUT AC Mains voltage 230V ac 1 phase Mains voltage range 184...264V ac Mains frequency range 47...63Hz Power factor at

More information

Solectria Renewables Modbus Level 5 For models PVI KW

Solectria Renewables Modbus Level 5 For models PVI KW Solectria Renewables Modbus Level 5 For models PVI 50 100KW Revision B 2014, Solectria Renewables, LLC DOCR 070381 B Table of Contents 1 Solectria Renewables Modbus Level 5... 3 1.1 Determine Modbus Level...

More information

Single Phase Soft Starters

Single Phase Soft Starters Submittal Data English Language/IP Units 04/14 Contact Information: Hyper Engineering, Pty. Ltd. 4 / 14 Ralph Black Dr Wollongong Nth, NSW 2500 AUSTRALIA www.hypereng.com sales@hypereng.com (877) 304-0724

More information

BMS BMU Vehicle Communications Protocol

BMS BMU Vehicle Communications Protocol BMS Communications Protocol 2013 Tritium Pty Ltd Brisbane, Australia http://www.tritium.com.au 1 of 11 TABLE OF CONTENTS 1 Introduction...3 2 Overview...3 3 allocations...4 4 Data Format...4 5 CAN packet

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SG Series 80 100 120 kva 400 Vac CE Series 0 Date of issue: 01.11.2007 SGSE_080_UPS_GE_01a SGSE_100-120_UPS_GE_01a

More information

SHI Series Pure Sine Wave Inverter (SHI2000 AND SHI3000) User s Manual

SHI Series Pure Sine Wave Inverter (SHI2000 AND SHI3000) User s Manual SHI Series Pure Sine Wave Inverter (SHI2000 AND SHI3000) User s Manual The information presented in this document does not form part of any quotation or contract, is believed to be accurate and reliable

More information

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors.

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors. Three-phase Industrial Inverter OND4 SERIES The new OND4 SERIES inverter provides safe, pure sine wave, single-phase or three-phase reliable power to critical control equipment. These inverters are of

More information

JBUS/MODBUS communication card

JBUS/MODBUS communication card JBUS/MODBUS communication card JBUS/MODBUS Installation and user manual 66061 51029066EN/BF - Page 1 Page 2-51029066EN/BF Introduction Thank you for selecting an APC by Schneider Electric product to protect

More information

UPS Communication Protocol

UPS Communication Protocol PAGE 1/21 UPS Communication Protocol 1 INQUIRY COMMAND... 3 1.1 QPI: PROTOCOL ID INQUIRY... 3 1.2 QMD: MODEL INQUIRY... 3 1.3 QGS: THE GENERAL STATUS PARAMETERS INQUIRY... 4 1.4 QFS: FAULT

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

StatiVolt. Inverter UPS Systems. Features. Contents

StatiVolt. Inverter UPS Systems. Features. Contents Redundant, clean, sine-wave AC power ensures a high availability of mission-critical safety devices, instrumentation, alarms, controls and computers. Robust, StatiVolt UPS Systems are designed and built

More information

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS Copyright Mitsubishi Electric Power Products TABLE OF CONTENTS 1. SCOPE... 1 1.1 The System... 1 2. SYSTEM DESCRIPTION... 1 2.1 Components... 1 2.2 Modes

More information

R&D TECHNICAL SPECIFI

R&D TECHNICAL SPECIFI INTRODUCTION Present document defines technical specs of a three phase UPS covering the power range from 20 to 30 kva ON-LINE DOUBLE CONVERSION Uninterruptible Power Supply Systems with forced ventilation

More information

GESS Industrial UPS System. Overview

GESS Industrial UPS System. Overview GESS Industrial UPS System Overview Industrial UPS System Rectifier with Isolation Transformer Inverter with Isolation Transformer By-pass line Voltage Stabilizer with Isolation Transformer > Individual

More information

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS TABLE OF CONTENTS Section 1.0 General... 3 1.1 Work Included... 3 1.2 Related Work... 3 1.3 System Description... 3 1.4 System Operation... 4 1.5

More information

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners IEEE Canada Webinar Presentation May 21, 2008 Bob Hanna, FIEEE, P.Eng. RPM Engineering Ltd. www.rpm-eng.com David

More information

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL 1.1 SUMMARY Liebert NX UPS GUIDE SPECIFICATIONS 40-80kVA, 80-120kVA and 160-200kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL This specification defines the electrical and mechanical

More information

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION GUIDE SPECIFICATIONS 256920-UGS-A-0506 Simplicity Intelli-Comfort Optional Control in 3-25 Ton Packaged Units GENERAL DESCRIPTION CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP Equipment with Simplicity

More information

JBus/Modbus Communication Card

JBus/Modbus Communication Card JBus/Modbus Communication Card Installation and Operation 05/2018 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors. Industrial Inverter The Gentec inverter systems, OND2 SERIES, provide safe, pure sine wave, reliable power to critical control equipment. These inverters are online type, usually the load is fed by the

More information

NLG513 SOFTWARE. Translation of the original German operating instructions

NLG513 SOFTWARE.   Translation of the original German operating instructions SOFTWARE NLG513 Translation of the original German operating instructions www.brusa.biz BRUSA Elektronik AG Neudorf 14 CH-9466 Sennwald +41 81 758 19 00 info@brusa.biz LEGAL NOTICE Publisher BRUSA Elektronik

More information

Dale Power Solutions Ltd

Dale Power Solutions Ltd DC SWITCH TRIPPER CHARGER DATASHEET Features Erskine STU 110W Range 24V, 30V, or 48VDC nominal Constant voltage current limited charger output Standard alarms LCD voltmeter LED indica ons Equipped with

More information

USER S MANUAL. 3KSS6050/ nd Edition

USER S MANUAL. 3KSS6050/ nd Edition USER S MANUAL 3KSS6050/5060 2 nd Edition Frequency Converter Visicomm Industries LLC 4525 Sheridan Rd. Racine WI 53403 1. INTRODUCTION The conversion of electrical power is an essential requirement for

More information

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V Technical Data Sheet Uninterruptible Power Supply On-line VH Series UPS 2000-3000 UL / 208V GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850

More information

Always On UPS Systems NX Series Online UPS

Always On UPS Systems NX Series Online UPS UPS SYSTEMS TVSS POWE CONDITIONING Always On UPS Systems NX Series Online UPS Extended S-232 Communication Protocol M0701_NX_Series_S-232_Protocol_Manual V1.0 2012-06-12.doc UPS SYSTEMS TVSS POWE CONDITIONING

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

MGETM EPSTM /625/750/800 kva. Three phase UPS

MGETM EPSTM /625/750/800 kva. Three phase UPS MGETM EPSTM 8000 Three phase UPS 555/625/750/800 kva > Performance 3 phase Power Protection with high active power density and adaptability to meet the unique requirements of very large datacenters, buildings

More information

Operation Manual. Congratulations on purchasing your high quality AIMS Power pure sine inverter!

Operation Manual. Congratulations on purchasing your high quality AIMS Power pure sine inverter! Operation Manual Congratulations on purchasing your high quality AIMS Power pure sine inverter! It is very important that you read and understand this instruction manual completely prior to use. Contained

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

1KVA-2KVA-3KVA 6KVA-10KVA. NUPS22 Series

1KVA-2KVA-3KVA 6KVA-10KVA. NUPS22 Series 1KVA-2KVA-3KVA 6KVA-10KVA NUPS22 Series Niveo Professional True Sine Wave Double-Conversion Online Rack/Tower UPS NUPS22-1000U- 1.0KVA/900W NUPS22-2000U-2.0KVA/1800W NUPS22-3000U- 1.0KVA/2700W NUPS22-6000U

More information

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX SSE-N NEGATIVE FIELD FORCING SHUNT STATIC EXCITER/REGULATOR SYSTEM Control Chassis 6 SCR Power Chassis APPLICATION The SSE-N Negative Field Forcing Exciter/Regulator is used for both new and old installations

More information

TECHNICAL DATA SHEET B9600FXS kva

TECHNICAL DATA SHEET B9600FXS kva GENERAL INFORMATION TECHNICAL DATA SHEET B9600FXS 400-500-600-800 kva UPS Type ON LINE - Double Conversion Nominal output power (Cos 0.9) kva 400 500 600 800 Nominal output power (Cos 1.0) kw 360 450 540

More information

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN UNINTERRUPTIBLE POWER SYSTEMS PF >0.98 G8000MM Series 100 to 750 KVA UPS IGBT DESIGN 94% Efficiency Main Features State-of-the-Art Modular Design Provides Maximum Flexibility The Toshiba G8000MM Uninterruptible

More information

The world is changing but our power is constant...

The world is changing but our power is constant... The world is changing but our power is constant...... Su-Kam Online UPS Su-Kam Power Systems Ltd. Corporate Office: Plot No. 54, Udyog Vihar Phase VI, Sector-37, Gurgaon-122001, Haryana, India. Tel.:+91-124-4030700,4170500,Fax:+91-124-4038700/1/2.

More information

BlockMon Block Monitor LongMon Long Monitor

BlockMon Block Monitor LongMon Long Monitor BlockMon Block Monitor LongMon Long Monitor Bypass range 2.2V to 5.0V. Bypass current 0A to 2A (typically 1A). Over-voltage protection up to ±20V. Noise immune opto-isolated. Cell temperature and bypass

More information

SECTION [ ] [16611] SOLID STATE UNINTERRUPTIBLE POWER SUPPLY

SECTION [ ] [16611] SOLID STATE UNINTERRUPTIBLE POWER SUPPLY APC by Schneider Electric MGE GALAXY PW Data Center Grade Three Phase Uninterruptible Power Supply Parallel Module - Guide Specifications 150-225 kva UPS THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM SECTION 263353 - THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM PART 1 GENERAL 1.1 SUMMARY A. This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty three-phase,

More information

INSTRUCTIONS FOR THE COMMISSIONING AND MAINTENANCE OF DIGITAL GENERATOR PROTECTION 3 I - PRINCIPLES AND APPLICATIONS 4 on 5 6 7 Figure 5 - Inverse time curve (N1) 8 9 1 0 1 1 1 2 1 3 All relays are delivered

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual PREFACE VACON 3 PREFACE Document ID: DPD01083D Date: 15.10.2014 Software version: FW0159V010 ABOUT THIS MANUAL This manual is copyright of Vacon Plc. All Rights

More information

BACnet- MS/TP COMMUNICATION V

BACnet- MS/TP COMMUNICATION V - MS/TP COMMUNICATION V1.00.08.17 11.1 Introduction The VFD can be controlled and monitored through the BACnet MS/TP protocol over an RS-485 connection. The VFD operates as an MS/TP master device, which

More information

SENTINEL XR PLUS 5-10kVA

SENTINEL XR PLUS 5-10kVA SENTINEL R PLUS 5-10kVA Uninterruptible Power Supply Absolute protection Sentinel R Plus is the ideal solution for powering vital mission critical, sensitive loads such as electro-medical security applications

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

Three phase sine wave inverter - 3KVA to 30KVA

Three phase sine wave inverter - 3KVA to 30KVA Three phase sine wave inverter - 3KVA to 30KVA MEDI has designed and developed DSP based three phase / single phase sine wave inverter. This inverter can be used for the following applications 1. Offline

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12 INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.

More information

DIGITAL SWITCH MODE POWER SUPPLIES MAIN APPLICATIONS GENERAL INTRODUCTION TO QP23 SERIES

DIGITAL SWITCH MODE POWER SUPPLIES MAIN APPLICATIONS GENERAL INTRODUCTION TO QP23 SERIES MAIN APPLICATIONS DIGITAL SWITCH MODE POWER SUPPLIES GENERAL INTRODUCTION TO QP SERIES The new generation of Digital Switch Mode Power Supplies F series QP, has been designed and is manufactured by SALICRU

More information

What is VC-VH? Old capacitor voltage terminology. Terminals on capacitor

What is VC-VH? Old capacitor voltage terminology. Terminals on capacitor What is VC-VH? Old capacitor voltage terminology Terminals on capacitor VC=Voltage common; VH= voltage hermetic 2-Stage Board Voltage constantly monitored at compressor run capacitor. Looks for voltage

More information

Chloride 80-NET Secure Power For Mission Critical Applications 60kVA to 120kVA. AC Power For Business-Critical Continuity

Chloride 80-NET Secure Power For Mission Critical Applications 60kVA to 120kVA. AC Power For Business-Critical Continuity Chloride 80-NET Secure Power For Mission Critical Applications 60kVA to 120kVA AC Power For Business-Critical Continuity A Commitment to Best-in-Class Technologies When it comes to protecting critical

More information

Protection and safety SQZ3 phase and sequence relay

Protection and safety SQZ3 phase and sequence relay SQZ3 phase and sequence relay Supply voltage [Vn] 400 V a.c. Frequency [Hz] 0/60 SQZ3 2CSC4001F0201 Contact type [A] 1 CO, 20 V, 10 A (cos =1) safety switching Minimum voltage adjustment trimmer [%] 100

More information

Connection of Embedded Generating Plant up to 5MW

Connection of Embedded Generating Plant up to 5MW Engineering Recommendation No.3 of the Electricity Distribution Code Connection of Embedded Generating Plant up to 5MW Version 1.0 30th November 2005 Prepared by: Al Ain Distribution Company, Abu Dhabi

More information

3400 Series. Three Phase UPS Specification. 80/100/125kVA

3400 Series. Three Phase UPS Specification. 80/100/125kVA 3400 Series Three Phase UPS Specification 80/100/125kVA TABLE OF CONTENTS 1. SCOPE... 3 2. SYSTEM DESCRIPTION...3 2.1 Components...3 2.2 Modes of Operation...4 2.3 Application Standards...5 3. PERFORMANCE

More information

Relay Driver Overview and Applications

Relay Driver Overview and Applications Relay Driver Overview and Applications Describes Basic and Advanced Settings for common and alternative/novel uses for the Relay driver (RD-1). Morningstar s Relay Driver (RD-1) is a fully programmable

More information

ES-777-MV-P2_A1 03/01/10

ES-777-MV-P2_A1 03/01/10 ENGINEERING SPECIFICATION SYMCOM MODEL 777-MV-P2 Electronic Overload Relay PART 1 GENERAL 1.1 REFERENCES A. UL 508 Industrial Control Equipment Underwriters Laboratories B. IEC 60947 Low Voltage Switchgear

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. SHI 400 / SHI 600 / SHI 1000 Pure Sine Wave Inverter The information presented in this document does not form

More information

TRIOL KN24+ VOLTAGE COMPENSATORS

TRIOL KN24+ VOLTAGE COMPENSATORS TRIOL KN24+ VOLTAGE COMPENSATORS Dear Customers! KN24+ voltage compensators will help you cut financial and process losses due to unreliable power supply of your enterprises. Triol Corporation has offices

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

TRC ELECTRONICS, INC

TRC ELECTRONICS, INC Bauart gepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 2000000000 SPECIFICATION MODEL DRC-100A DRC-100B OUTPUT NUMBER DC VOLTAGE CH1 13.8V CH2 13.8V CH1 27.6V CH2 27.6V RATED CURRENT CURRENT

More information

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.

More information

Liebert Hipulse-U. Fully Digital Dual DSP Controlled Transformer Based UPS

Liebert Hipulse-U. Fully Digital Dual DSP Controlled Transformer Based UPS Liebert Hipulse-U Fully Digital Dual DSP Controlled Transformer Based UPS Addressing a Variety of Needs The Liebert Hipulse-U offers a reliable, scalable and user-friendly solution to ensure availability

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) SL AND B SERIES PRODUCT OVERVIEW Elgar SL and B Series power sources are wide range, solid-state linear amplifiers that

More information

Pure Sine Wave Inverter

Pure Sine Wave Inverter 1 Inverter Pure sine wave inverter is one of the most advanced DC to AC conversion products in the world, it has the main advantages of high quality sine wave AC output, microcomputer control, humanness

More information

DRC-100 series. 100W Single Output with Battery Charger (UPS Function) File Name:DRC-100-SPEC Sicherheit ID

DRC-100 series. 100W Single Output with Battery Charger (UPS Function) File Name:DRC-100-SPEC Sicherheit ID Bauartgepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 2000000000 SPECIFICATION MODEL OUTPUT INPUT PROTECTION OUTPUT NUMBER DC VOLTAGE LINE REGULATION LOAD REGULATION SETUP, RISE TIME Note.4

More information

SOUTHERN AVIONICS COMPANY. SE125 Transmitter. SE125 Transmitter 1-1

SOUTHERN AVIONICS COMPANY. SE125 Transmitter. SE125 Transmitter 1-1 1-1 1 Introduction The SE Series transmitters are computer controlled systems designed around an embedded microprocessor. These systems are capable of remote monitoring and maintenance via Ethernet (optional).

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

Series PCI + PIT PIT5738 U IN PIT5748 U IN PCI5748 PCI5738. Series PIT 19 - Cabinet G10

Series PCI + PIT PIT5738 U IN PIT5748 U IN PCI5748 PCI5738. Series PIT 19 - Cabinet G10 PCI + PIT PCI5728 U IN 20 32 PIT5738 U IN 40 64 PIT5748 U IN 50 80 PIT5658 U IN 80 160 PIT5678 3000VA 3000VA 3000VA 3000VA 3000VA Serie PCI5728 U IN 20 32 PCI5738 U IN 40 64 PCI5748 U IN 50 80 PCI5758

More information

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks 2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution

More information

NBU-1012 Square pulse flashlamp driver User Manual

NBU-1012 Square pulse flashlamp driver User Manual rev 1.07/ 2009 02 03 NBU-1012 Square pulse flashlamp driver User Manual Overview / Applications Cooling NBU-1012 Square Pulse Flashlamp Driver is designed for simplification of solid-state laser systems

More information

Table of Contents. Proximity Sensors. IEC Limit Switches. Encoders. Current Sensors. Section 17

Table of Contents. Proximity Sensors. IEC Limit Switches. Encoders. Current Sensors. Section 17 Proximity Section 17 Table of Contents............ 21 2 Application Guide........................ 21 3 ACT Series Transducers......... 21 4 ACTR Series Transducers........ 21 6 ACS150 Series Switches..................

More information

USER S MANUAL. 1KSS60400/ ST Edition

USER S MANUAL. 1KSS60400/ ST Edition USER S MANUAL 1KSS60400/50400 1 ST Edition Frequency Converter Visicomm Industries LLC 911A Milwaukee Ave. Burlington, WI 53105 1. INTRODUCTION The conversion of electrical power is an essential requirement

More information

NIPSCO Energy Symposium

NIPSCO Energy Symposium Backup Power Automatic Transfer NIPSCO Energy Symposium symposium Backup Power Applications/Considerations Backup Power Types Automatic Transfer Switch Basics Presenters McGill Power - Jeremy Irmeger Eaton

More information

New Eagle J1772 Vehicle Power Interface Module (VPIM)

New Eagle J1772 Vehicle Power Interface Module (VPIM) New Eagle P.O. Box #272 Ann Arbor, MI 48105-2603 Phone 734.395.2112 Fax 928.395.2114 New Eagle J1772 Vehicle Power Interface Module (VPIM) Revision 0.8 VPIM-024-1301 8/5/2013 New Eagle 3588 Plymouth Road,

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd Safety Terms and Symbols This manual may contain the terms: Warning! Indicate the conditions

More information

LPS TRC ELECTRONICS, INC

LPS TRC ELECTRONICS, INC LPS Bauart gepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 2000000000 SPECIFICATION MODEL DRC-60A DRC-60B OUTPUT NUMBER DC VOLTAGE CH1 13.8V CH2 13.8V CH1 27.6V CH2 27.6V RATED CURRENT CURRENT

More information

Phoenix DX Clean Power (18 Pulse) AC Drive

Phoenix DX Clean Power (18 Pulse) AC Drive PHOENIX DX Phoenix DX Clean Power (18 Pulse) AC Drive Poor power quality can be costly. Nonlinear loads, including AC Drives, introduce undesirable harmonic currents into the power system that can damage

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

FEATURES OPTIONAL FEATURES

FEATURES OPTIONAL FEATURES -00--0 B Series The Assured Automation B Series electric valve actuators offer a rugged design for quarter turn industrial applications. Designed for use on quarter turn (0 ) ball valves, butterfly valves,

More information

PACSystems* RX3i IC695MDL765

PACSystems* RX3i IC695MDL765 March 2011 PACSystems* RX3i IC695MDL765 Digital Output Module with Diagnostics 16-Channel The 24/125 volt DC 2A Smart Digital Output module, IC695MDL765, provides 16 discrete outputs in two isolated groups

More information

RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES. Power Management Instruments ELECTRONIC STABILIZER FROM PMI & OES GROUP COMPANIES SUD

RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES. Power Management Instruments ELECTRONIC STABILIZER FROM PMI & OES GROUP COMPANIES SUD RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES Power Management Instruments FROM PMI & OES GROUP COMPANIES SUD Today, as technology evolves, Electrical, Electronic and Electromechanical devices are

More information

LPS. DRC-60 SERIES 60 Watt Battery Charger Power Supply Measures: 3.94 x 3.54 x 1.57 (866) MEAN WELL

LPS. DRC-60 SERIES 60 Watt Battery Charger Power Supply Measures: 3.94 x 3.54 x 1.57 (866) MEAN WELL Bauar t gepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 2000000000 MEAN WELL LPS File Name:DRC-60-SPEC 2014-1122 /mean-well-drc-60-power-supply.html SPECIFICATION MODEL DRC-60A DRC-60B MEAN

More information

Overcurrent and Overload Protection of AC Machines and Power Transformers

Overcurrent and Overload Protection of AC Machines and Power Transformers Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Instruction Sheet UPS SERIES. Serial Control Protocol. I Rev E

Instruction Sheet UPS SERIES. Serial Control Protocol. I Rev E Instruction Sheet UPS SERIES Serial Control Protocol I-00341 Rev E (THIS PAGE INTENTIONALLY LEFT BLANK) Page 1 TABLE OF CONTENTS 1 Protocol Overview...3 1.1 Signal characteristics...3 1.2 Primary DB9 Pin

More information

Brushless DC Motor Controller Specification Assemblies 025F0248

Brushless DC Motor Controller Specification Assemblies 025F0248 Brushless DC Motor Controller Specification Assemblies 025F0248 600A1099 Rev. B April 4 th, 2014 Revision History EC Date Description Rev EC54318 09/03/13 Initial Release A EC58093 04/04/14 Added cap discharge

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS

UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS TABLE OF CONTENTS PART 1 GENERAL... 2 1.1 SUMMARY... 2 1.2 STANDARD... 2 1.3 SYSTEM DESCRIPTION... 2 1.3.1 Components... 2 1.3.2 Mode of Operation...

More information

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems SECTION 26 33 53 - STATIC UNINTERRUPTIBLE POWER SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty three-phase,

More information

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE)

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE) USER MANUAL ATS-I Tel.+39.0522.832004 P1/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.1/17 Index General description...3 Electrical specifics...3 Device operative logic...4 Manual mode...4

More information

Product Catalog PRODUCT CATALOG. Power supply system & test equipment

Product Catalog PRODUCT CATALOG. Power supply system & test equipment Product Catalog PRODUCT CATALOG 2018 2018 Power supply system & test equipment. 138/79, Moo 2 Tambon Ban Klang, Amphoe Mueang Pathumthani, Pathumthani Province 12000, Thailand. Tel: +66 21475048-9 Fax:

More information

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD) Drives 101 Lesson 3 Parts of a Variable Frequency Drive (VFD) This lesson covers the parts that make up the Variable Frequency Drive (VFD) and describes the basic operation of each part. Here is the basics

More information

G Series. Advanced Test Equipment Rentals ATEC (2832) AC Power Systems. 6 to 90 kva 45 to 5,000 Hz

G Series. Advanced Test Equipment Rentals ATEC (2832) AC Power Systems. 6 to 90 kva 45 to 5,000 Hz Es ablished 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) G Series t AC Power Systems 6 to 90 kva 45 to 5,000 Hz Solid State AC Power Conversion Programmable AC test power, 45

More information